SECTION ISOLATOR SERIES LABORATORY FUME HOODS

Size: px
Start display at page:

Download "SECTION ISOLATOR SERIES LABORATORY FUME HOODS"

Transcription

1 SECTION ISOLATOR SERIES LABORATORY FUME HOODS ISOLATOR SERIES LABORATORY FUME HOODS PART 1 GENERAL 1.00 SUMMARY A. Section Includes: 1. Laboratory Fume Hoods B. Related Sections: 1. Section Steel Laboratory Casework: Base units and work surfaces for fume hood/base unit assembly. 2. Section Flex Laboratory Furniture System. 3. Section Smart Sash 3. Division 15: Furnishing and installation of plumbing utilities and final connections to fume hoods. 4. Division 15: Furnishing and installation of exhaust duct work and equipment, and final connection of fume hoods. 5. Division 16: Furnishing and installation of electrical utilities and final connections to fume hoods. C. Reference Standards: 1. UL 1805 Standard for Laboratory Fume Hoods and Cabinets 2. ANSI/ASHRAE Method of testing Performance of Laboratory Fume Hoods 3. CSA Z Fume Hoods and Associated Exhaust Systems 1.01 FUME HOOD GENERAL DESIGN REQUIREMENTS A. All fume hoods covered in this section are Isolator Series with a top and bottom airfoil and aerodynamically shaped fascia posts to minimize turbulence. 1. CAV (Constant Air Volume) type: Design incorporates an automatic air bypass system so that the exhaust air volume is constant. Bypass is recessed behind plane of the sash and affords velocity tempering performance with face velocities not in excess of 3.8 times full-open face velocity. 2. VAV (Variable Air Volume) type: Design uses a restricted by-pass design. Maximum air is exhausted when the sash is open, minimum air is exhausted when the sash is closed. A minimum flow of 25 CFM/sq ft of surface area, as stated by NFPA 45, should be maintained to achieve optimum containment and satisfactory dilution when the sash is closed

2 B. Fume hoods shall be designed for consistent and safe air flow through the hood face. Negative variations of face velocity shall not exceed 20% of the average face velocity at any designated measuring point as defined in this section. C. Average illumination of work area: minimum 80 foot-candles. Work area shall be defined as the area inside the superstructure from side to side and from face of baffle to the inside face of the sash, and from the working surface to a height of 48 inches. D. Fume hood shall be designed to minimize static pressure loss with stainless steel round duct collar configuration. Maximum average static pressure loss readings taken three diameters above the hood outlet from four points, 90 degrees apart, shall not exceed the following maximums: Face Velocity at sash full open- CAV design - measured S.P.L. (W.G.) 75 F.P.M..30 inches 100 F.P.M..50 inches 125 F.P.M..80 inches 150 F.P.M inches E. Fume hood shall maintain essentially constant exhaust volume at any baffle position for safety. Maximum variation in exhaust CFM, static pressure and average face velocity as a result of baffle adjustment shall not exceed 5% for any baffle position at the specified face velocity SUBMITTALS A. Submit manufacturer's test data and installation instructions for each type of fume hood. Provide data indicating compliance with ANSI/ASHRAE Standard B. Provide samples of the following: 1. 6" x 6" section of the interior fume hood liner material " x 12" section of countertops with dish formation. 3. Color samples of manufacturer's finish. 4. Hardware and accessories including sample sash handle and/or pulls, chains, axles, and sprockets. NOTE: Samples of the approved manufacturer will be kept at the job site or the office of the architect until completion of the project

3 C. Provide submittal drawings for fume hoods showing plans, elevations, sections and service run spaces. Details shall include notation of all specified items. 1. Provide location and type of service fittings as related to the fume hood when required. 2. Provide roughing-in drawings for mechanical and electrical services as related to the fume hood when required. 3. Provide face opening, air volume and static pressure drop data FUME HOOD PERFORMANCE REQUIREMENTS See APPENDIX A PART 2 PRODUCTS 2.00 MANUFACTURER A. Laboratory Fume Hoods and related equipment designed and manufactured by: Jamestown Metal Products LLC, 178 Blackstone Avenue, Jamestown, New York, MATERIALS A. Typical sheet steel used in the construction of fume hoods: 1. Mild carbon, cold rolled and leveled unfinished steel 2. Type 304 or 316 stainless steel, #4 finish one side 3. Mild carbon, cold rolled and hot dipped galvanized steel B. Typical gauges: 1. Stainless steel: 12, 14, 16, 18 and 20 GA 2. Mild Steel: 18 GA 3. Galvanized steel: 18 GA C. Sash glass: 1. ¼ clear tempered glass (standard) 2. ¼ clear laminated glass (optional) D. Sash tracks: Corrosion-resistant polyvinyl chloride (PVC). E. Fastening devices: 1. Interior surfaces: Nylon bolts, PVC fasteners, PVC-capped 410 stainless screws 2. Exterior structural members: 410 stainless steel screws 3. Exterior panel members: #8-32 zinc plated screws

4 F. Interior liners: The liner consists of all interior surfaces, including sides, top, back and baffles. See APPENDIX B for liner performance requirements. 1. Standard: Fiberglass reinforced polyester material (polyglass), ¼ nom. thickness, white 2. Optional liner materials: a. Type 304 stainless steel, 16 GA, #4 finish b. Type 316 stainless steel, 16 GA, #4 finish c. PVC plastic sheet, ¼ nom. thickness, white d. Polypropylene plastic sheet, ¼ nom. thickness, white e. Composition stone, ¼ nom. thickness, light grey 2.02 FUME HOOD CONSTRUCTION BENCH HOODS A. Superstructure: Shall consist of 18 gauge galvanized steel side pans, maximum 4-3/4" thick, holding side and rear liner panels, and fastened together with pinions and screws so that the entire structure is secure and rigid. Any framing system not providing structural support is unacceptable. Front and both sides of the superstructure are aligned and precision fit, eliminating the need for exterior gaskets. B. Airfoils: 1. Lower airfoil: Shall be constructed of 14 gauge 304 #4 finish stainless steel and be equipped with power cord/tube pass-throughs 3" square near each side post. These pass-throughs shall allow sash handle to seal against airfoil without running cords and tubes under the airfoil, but by simply resting cords and tubes into the pass-through cavity. 2. Upper airfoil (Specifier s Option choose one): a. 18 GA mild steel and painted (standard) b. Type 304 stainless steel, #4 finish (optional) C. Sash (Specifier s Option choose one): 1. Provide a frameless vertical sash containing a 1/4" (6 mm) tempered glass panel and a full width anodized aluminum aerodynamic wedgeshaped sash handle connected to a steel rear-hung counterweight system insuring non-tilting, non-binding, and non-creeping sash performance. Rear-mounted counterweight shall be connected to a #35 case-hardened steel chain engaging a twin sprocket axle system with positive master link connection points both front and rear. Sash systems utilizing cables and pulleys are not acceptable. Painted steel parts in the sash are not acceptable. Note: Sash interlock system utilized on double sided pass-through hoods

5 1. Provide a combination sash with horizontal sliding panels no wider than 18". Standard sash elements are tempered glass panels set into an aluminum track housed within the stainless steel sash frame giving either horizontal or vertical movement options to the end user. A steel rear-hung, counterweight system is used to insure non-tilting, nonbinding, and non-creeping sash performance. Rear-mounted counterweight shall be connected to a #35 case-hardened steel chain engaging a twin sprocket axle system with positive master link connection points both front and rear. Sash systems utilizing cables and pulleys are not acceptable. Painted steel parts in the sash are not acceptable. Note: Not available on double sided pass-through hoods. 2. Provide a horizontal sliding sash consisting of a stainless steel top rail holding stainless steel framed glass panels and an aluminum bottom track. Standard sash elements are tempered glass panels set into an aluminum track housed within the stainless steel rail. Painted steel parts in the sash are not acceptable. Note: Not available on double sided pass-through hoods. 3. Provide a framed vertical sash containing a standard tempered glass panel set into a stainless steel frame connected to a steel rear-hung counterweight system insuring non-tilting, non-binding, and noncreeping sash performance. Rear-mounted counterweight shall be connected to a #35 case-hardened steel chain engaging a twin sprocket axle system with positive master link connection points both front and rear. Sash systems utilizing cables and pulleys are not acceptable. Painted steel parts in the sash are not acceptable. Note: Sash interlock system utilized on double sided pass-through hoods. D. Baffles: Control air vectors into and through the fume hood, and shall be fabricated of the same material as the liner. Provide three fixed baffles and one adjustable baffle at bottom. E. Bypass: Isolator Viewpass system consisting of a ¼ thick clear laminated glass panel allowing complete visual display of fume hood interior. F. Duct collars: Standard 10" or 12" round exhaust outlet collar(s), fabricated of 20 gauge Type 304 stainless steel. Coated steel collars are not acceptable. G. Fascia posts (Specifier s Option choose one): GA mild steel and painted (standard) 2. Type 304 #4 finish stainless steel (optional)

6 H. Exterior end panels (Specifier s Option choose one): GA mild steel and painted (standard) 2. Type 304 #4 finish stainless steel (optional) 3. No end panels (optional) I. Interior clearance: All bench type fume hoods are designed to have an interior vertical clearance of not less than 47" in the front twelve inches of the hood depth. Internal dimensions may be affected by accessories or options. J. Interior lighting: Standard configurations for fluorescent light fixtures are: 36" hood (1-24" fixture); 48" hood (1-36" fixture); 60" hood (1-48" fixture); 72" hood (1-48" fixture); 96" hood (2-36" fixtures). (Specifier s Option choose one): 1. Standard hinged fluorescent light fixture configured for T-8 lamp tubes shall be provided and installed on the exterior of the fume hood roof. A tempered glass panel is provided and has a vapor-tight seal to isolate the fluorescent fixture from the hood interior. The largest possible double tube UL approved fixture is provided for each hood. 2. Incandescent, explosion-proof 150 watt light. K. Fluorescent Tubes or Incandescent Bulbs (Specifier s Option choose one): 1. Provided by others (standard) 2. Included with fixture (optional) L. Service Fittings and Fixtures: 1. All laboratory service fittings and fixtures shall be as manufactured by the Water Saver Fixture Company or an approved equal. Fixtures, including handles, shall be color coded to indicate the proper service. Color code requirements for indexing service fixtures shall be as follows: Service Index Color Gas Blue Air Orange Vacuum Yellow Steam Black Cold Water Green Hot Water Red Deionized Water White Other Services On Application

7 2. Finish of Service Fixtures: a. Laboratory service fixtures (except fittings inside the fume hood) shall have (Specifier s Option choose one): 1. A polished chrome finish with clear epoxy coating (standard) 2. A satin chrome finish with clear epoxy coating (optional) b. Fittings inside the fume hood shall have an epoxy finish colorcoded to match the fixture service index color. M. Electrical services (Specifier s Option choose one): 1. Specified electrical outlets and switches are shipped loose for field installation by the electrical contractor. All electrical receptacles are 3- wire, 20 amp duplex, 120/277VAC or as specified. Light switch shall be 3-wire polarized grounded, 15 amp, 125VAC or as specified. Face plates are stainless steel. 2. Wiring harnesses shall be furnished for each specified fascia post mounted electrical device and field-installed. 3. Specified electrical services are prewired to a junction box located on the roof of the fume hood for field connection by the electrical contractor. All electrical receptacles are 3-wire, 20-amp duplex, 120/277VAC or as specified. Light switch shall be 3-wire polarized grounded, 15 amp, 125VAC or as specified. Face plates are stainless steel. N. Work surfaces (Specifier s Option choose one): 1. Epoxy resin, 1-1/4" thick, molded top made in the form of a watertight pan, not less than 1/4" deep to contain spillage. Work surfaces are non-glaring finish and black, grey or white in color. 2. Type 304 stainless steel, 16 gauge, formed down, making a 1-1/4" high face, and dished to form a watertight containment not less than 1/4" deep to contain any spills within the fume hood. NOTE: See APPENDIX C for work surface performance requirements. O. Instruction Plate: Corrosion resistant or plastic plate attached to the fume hood exterior with condensed information covering recommended locations for apparatus and accessories, use of sash and recommended safe operating procedures FUME HOOD CONSTRUCTION WALK-IN HOODS Walk-in hoods shall employ the same materials and construction methods as standard bench hoods with the following exceptions:

8 ISOLATOR SERIES LABORATORY FUME HOODS A. Hood roof: Shall be fabricated from the same liner material as the rest of the containment cavity as standard. If additional containment for accidental fire is desired, an optional 18 GA galvanized steel roof with liner material identical to that used in the rest of the containment cavity mounted to the interior is available. B. Sash (Specifier s Option choose one): 1. Provide two frameless vertical sashes, each containing a standard ¼ tempered glass panel and a full width anodized aluminum aerodynamic wedge-shaped sash handle connected to a steel rearhung counterweight system insuring non-tilting, non-binding, and noncreeping sash performance. Rear-mounted counterweight shall be connected to a #35 case- hardened steel chain engaging a twin sprocket axle system with positive master link connection points both front and rear. Sash systems utilizing cables and pulleys are not acceptable. Painted steel parts in the sash are not acceptable. 2. Provide two sashes; the upper being a combination sash with horizontal sliding panels no wider than 18" and the lower being a framed vertical sash. Sash elements in the combination sash are tempered glass panels set into an aluminum track housed within the stainless steel sash frame giving either horizontal or vertical movement options to the end user. Sash elements in the framed vertical sash are a standard ¼ tempered glass panel set into a stainless steel frame connected to a steel rear-hung counterweight system insuring non-tilting, non-binding, and non-creeping sash performance. Rear-mounted counterweight shall be connected to a #35 case-hardened steel chain engaging a twin sprocket axle system with positive master link connection points both front and rear. Sash systems utilizing cables and pulleys are not acceptable. Painted steel parts in the sash are not acceptable. 3. Provide a horizontal sliding sash consisting of a stainless steel top rail holding stainless steel framed glass panels and a stainless steel bottom track. Sash elements are standard tempered glass panels set into an aluminum track housed within the stainless steel rail. Painted steel parts in the sash are not acceptable. 4. Provide two framed vertical sashes, each containing a standard ¼ tempered glass panel set into a stainless steel frame connected to a steel rear-hung counterweight system insuring non-tilting, non-binding, and non-creeping sash performance. Rear-mounted counterweight shall be connected to a #35 case-hardened steel chain engaging a twin sprocket axle system with positive master link connection points both front and rear. Sash systems utilizing cables and pulleys are not acceptable. Painted steel parts in the sash are not acceptable

9 C. Baffles: Control air vectors into and through the fume hood, and shall be fabricated of the same material as the liner. Provide four fixed baffles and two adjustable baffles at bottom. D. Interior clearance: All walk-in type fume hoods are designed to have an interior vertical clearance of not less than 83" in the front twelve inches of the hood depth. Accessories or options may affect internal dimensions OPTIONAL FEATURES A. Velocity alarm: Fume hoods shall be equipped with Jamestown-Tel fume hood velocity alarm to detect low hood face velocities. The units are surfacemounted on the hood's fascia panel. No control module, when mounted, shall be thicker than 1-1/2". The UL approved velocity alarm signals an unsafe operating condition when the fume hood face velocity falls below a preset amount. The alarm set-point calibration is performed by the user/owner once a proper face velocity has been set and measured. The alarm system consists of the following: 1. LCD digital display that registers face velocities between 0 and 1000 FPM plus a safety reference display that actuates in low velocity conditions. 2. Programmable alarm set point. 3. Audible alarm of at least 80 db. 4. Flashing red warning light in synchronization with the audible alarm. 5. Silencer button for the audible alarm; flashing red light will continue to flash. 6. Optional 0-10VDC available to signal BAC. 7. Alarm system is furnished with velocity detector, 110V/12VDC power supply, and detector mounting hardware. The system operation at 110V, 60 Hz power. B. Smart sash: See Section for details

10 2.05 PERCHLORIC ACID FUME HOODS ISOLATOR SERIES LABORATORY FUME HOODS Perchloric Acid bench hoods shall employ the same materials and construction methods as standard bench hoods with the following exceptions: A. Standard type GA stainless steel liner and baffles with coving on all containment chamber corners for easy cleaning. B. Integral type GA stainless steel work surface with sloped trench and single drain. C. Wash down system including perforated PVC wash down bar, water valve, and remote knob. D. Incandescent, vapor proof, fume resistant and UL listed light fixture, installed in roof of hood; bulb replacement from interior RADIOISOTOPE FUME HOODS Radioisotope bench hoods shall employ the same materials and construction methods as standard bench hoods with the following exceptions: A. Standard type GA stainless steel liner and baffles with coving on all containment chamber corners for easy cleaning. B. Integral type GA stainless steel work surface and cupsink, reinforced to carry up to 200 lb/sq.ft.; type GA stainless steel with square corners optional

11 2.07 METAL FINISH (Painted Components) ISOLATOR SERIES LABORATORY FUME HOODS A. Preparation: Metal shall be treated with a heated alkaline based acid solution, rinsed with water, and a coat of epoxy-link applied; immediately dried in heated ovens, then gradually cool prior to application of finish. B. Application: Electrostatically apply a hybrid epoxy powder coat of selected color and bake in controlled high temperature oven to assure a smooth, hard satin finish. Surfaces shall have a chemical resistant, high grade laboratory furniture quality finish of the following thicknesses: 1. Exterior and interior surfaces exposed to view: 1.5 mil average and 1.3 mil minimum. 2. Backs of cabinets and other surfaces not exposed to view: 1.0 mil average. C. Chemical Resistance : 1. Test procedure: Place test panel on a flat surface, clean with soap and water and blot dry. Condition the test panel for 48 hours at 73 F ± 3 F and 50% ± 5% relative humidity. Panel will be subjected to chemical reagents according to SEPA 8/1999 Recommended Practice using one of the following two test methods: a. Method A Test volatile chemicals by placing a cotton ball saturated with reagent in the mouth of a 1-oz. bottle and inverting the bottle on the surface of the panel. b. Method B Test non-volatile chemicals by placing five drops of the reagent on the surface of the panel and covering with a 24 mm watch glass, convex side down. c. For both test methods, leave the reagents on the panel for a period of one hour. Wash off the panel with water, clean with detergent and naptha, and rinse with deionized water. Dry with a towel and evaluate after 24 hours at 73 F ± 3 F and 50% ± 5% relative humidity using the following rating system. 2. Evaluation ratings: Change in surface finish and function shall be described by the following ratings: a. Level 0 No detectable change. b. Level 1 Slight change in color or gloss. c. Level 2 Slight surface etching or severe staining. d. Level 3 Pitting, cratering, swelling, or erosion of coating. Obvious and significant deterioration.

12 Test Results: REAGENT METHOD RATING Acetate, Amyl A 0 Acetate, Ethyl A 1 Acetic Acid, 98% B 1 Acetone A 1 Acid Dichromate, 5% B 0 Alcohol, Butyl A 0 Alcohol, Ethyl A 1 Alcohol, Methyl A 1 Ammonium Hydroxide, 28% B 0 Benzene A 1 Carbon Tetrachloride A 1 Chloroform A 1 Chromic Acid, 60% B 2 Cresol A 1 Dichlor Acetic Acid A 2 Dimethylformanide A 1 Dioxane A 1 Ethyl Ether A 0 Formaldehyde, 37% A 0 Formic Acid, 90% B 3 Furfural A 2 Gasoline A 0 Hydrochloric Acid, 37% B 1 Hydrofluoric Acid, 48% B 1 Hydrogen Peroxide, 28% B 0 Iodine, Tincture of B 0 Methyl Ethyl Ketone A 1 Methylene Chloride A 1 Mono Chlorobenzene A 0 Naphthalene A 0 Nitric Acid, 20% B 1 Nitric Acid, 30% B 1 Nitric Acid, 70% B 3 Phenol, 90% A 1 Phosphoric Acid, 85% B 0 Silver Nitrate, Saturated B 1 Sodium Hydroxide, 10% B 0 Sodium Hydroxide, 20% B 0 Sodium Hydroxide, 40% B 0 Sodium Hydroxide, Flake B 0

13 Sodium Sulfide, Saturated B 0 Sulfuric Acid, 33% B 0 Sulfuric Acid, 77% B 1 Sulfuric Acid, 96% B 3 Sulfuric Acid (77%) B 3 & Nitric Acid (70%), (equal parts) Toluene A 0 Trichloroethylene A 0 Xylene A 0 Zinc Chloride, Saturated B 0 Note: Manufacturer shall provide independent certified test report on chemical resistance of finish if requested QUALITY ASSURANCE A. All laboratory fume hoods specified herein will be the product of one manufacturer and will be based on the specifications of the product line described in Part 2. All manufacturers other than those of the specified products will provide evidence of expertise in the manufacture of fume hoods and be willing to have their manufacturing facility scrutinized by the customer. B. All manufacturers desiring approval for this project must maintain a fume hood test facility at their factory location. This facility must provide for variable exhaust and make-up air control. In addition, any facility that provides for fume hood make-up air by using floor-to-ceiling wall diffusers is unacceptable. All qualified test facilities must contain, as part of their permanent equipment, ANSI/ASHRAE testing hardware as specified in that standard. In addition, all data readings shall be computerrecorded and the raw data submitted in disc format. C. The manufacturer shall provide certification that fume hoods shall meet the performance requirements described under Appendix A "Fume Hood Performance Testing Requirements. D. The manufacturer shall warrant the sash counterweight system, excluding glass, against defects in materials and workmanship for the life of the fume hood. Any material or manufacturing defect in these components will be repaired without charge by the manufacturer.

14 ISOLATOR SERIES LABORATORY FUME HOODS E. The manufacturer shall, for a period of one (1) year from date of shipment, warrant that furnished products shall be free from defects in material and workmanship. The manufacturer shall also warrant the products to be as represented and will repair or replace any part, under normal use, if examination discloses it to have been defective within the warranty period. F. UL 1805 Specification: Fume hoods must be UL 1805 approved. This standard covers electrical and mechanical hazards, investigates the flammability of materials and measures the effectiveness of airflow characteristics. Proper labeling must be affixed to the face of each fume hood indicating classification to UL UL listings covering electrical components only or other listings that do not encompass all elements of UL 1805 are insufficient. APPENDIX A FUME HOOD PERFORMANCE TESTING REQUIREMENTS A. General: 1. One (1) hood of the same design as specified herein will be successfully tested as detailed below. Production of the hoods specified herein will not commence until the "Performance Test" has been successfully performed by the manufacturer. In general, the below detailed "Performance Test" will consist of the ANSI/ASHRAE test procedure using a five-minute tracer gas challenge at a rate of four (4) liters per minute. The PPM concentration outside the hood of a tracer gas released inside the hood will be measured utilizing a MIRAN 203 Gas Analyzer, or equivalent. B. Test Procedure: 1. Tracer gas orifice and ejector as specified in ANSI/ASHRAE Tracer gas is sulfur hexafluoride supplied from a cylinder capable of maintaining 30 PSI pressure at the test flow rate for at least five minutes. The test flow rate is four (4) liters per minute. 3. Detector is a MIRAN 203 Infrared Spectrophotometer capable of indicating or recording concentrations of tracer gas in the range of PPM, with an accuracy of + 10% and a response time not to exceed ten (10) seconds to 90% indication of actual concentration. 4. "Dummy" will be a manikin such as used in clothing display. The height of the manikin will be 67 inches with a shoulder height of 55" to 57", and otherwise represent normal proportions of the human body. Hairless dummies or torsos are unacceptable. 5. The detector is calibrated with a known concentration of tracer gas within 24 hours preceding a test, using the methods furnished or specified by the detector manufacturer.

15 ISOLATOR SERIES LABORATORY FUME HOODS C. Test conditions: 1. Hood is tested with ceiling-supplied make-up air in a test area where face velocity, temperature, and room air flow can be monitored and documented. D. Hood Condition: 1. The sash or sashes shall be located in the design position or positions. 2. If the hood has an auxiliary air supply, the supply shall be in operation. E. Quantitative Test Procedure: 1. Turn on detector, allow time to reach equilibrium. 2. Insert orifice in test diffuser to give (4) liter per minute release rate. 3. Install diffuser to a central test position. This position is equidistant from the inside side walls, six inches behind the sash plane. 4. Install manikin standing 3" from the plane of the sash. 5. Turn on tracer gas block valve. Position the detector probe between the nose and lip of the manikin. 6. Observe and record the detector readings automatically. Background readings are to be taken before each test and subtracted from the actual test readings. The tests are run for five (5) minutes. An average reading above 0.07 PPM constitutes unsatisfactory performance under the conditions that exist for that test. 7. During the sixth and seventh minute of testing, the sash is closed completely. Then, at 420 seconds elapsed time, the sash is reopened. 8. Between 450 and 510 seconds elapsed time, the hood perimeter is tested at a distance of 1" outside the plane of the sash. 9. During all these procedures, breathing zone gas concentration shall not exceed 0.05 PPM. F. Qualitative Test Procedure: 1. Excerpt from SEFA (formerly SAMA Standard LF ) It is recommended that the user make provisions to have the following tests performed on all laboratory fume hoods. These tests should be performed by qualified personnel to verify proper operation of the fume hoods before they are put to use. The tests of the fume hoods should be performed after the installation is complete, the building ventilation system has been balanced and all connections made. Any unsafe conditions disclosed by these tests should be corrected before using the hood.

16 Test Conditions Verify that building make-up air system is in operation, the doors and windows are in normal operating position, and that all other hoods and exhaust devices are operating at design conditions. 7.2 Test Procedure Equipment List a. A properly calibrated hot-wire thermal anemometer. b. A supply of 2 -minute smoke candles. c. A bottle of titanium tetrachloride and supply of cotton swabs or other recognized device for producing smoke Room Conditions Check room conditions in front of the fume hood using a thermal anemometer and a smoke source to verify that the velocity of cross drafts does not exceed 20 percent of the specified average fume hood face velocity. Any cross drafts that exceed these values shall be eliminated before proceeding with fume hood test. Caution: Titanium Tetrachloride fumes are toxic and corrosive. Use sparingly; avoid inhalation and exposure to body, clothing and equipment that might be affected by corrosive fumes. Note: It must be recognized that no fume hood can operate properly if excessive cross drafts are present Face Velocity Determine specified average face velocity for fume hood being tested. Perform the following test to determine if fume hood velocities conform to specifications or to the designated fume hood class. With the sash(es) positioned, turn on the exhaust blower. The face velocity shall be determined by averaging the velocity readings taken at the open fume hood face. Note: If not in accordance with specified face velocity, refer to Appendix A (Troubleshooting Guide) of the complete SEFA document for aid in determining the cause of variation in air flow. If face velocity cannot be corrected to that specified, reclassify fume hood to conform to actual face velocity.

17 7.2.4 Sash Operation ISOLATOR SERIES LABORATORY FUME HOODS Check operation by moving sash(es) through its (their) full travel. Sash operation shall be smooth and easy. Vertical rising sashes shall hold at any height without creeping up or down, unless designed otherwise Verification of Proper Air Flow and Patterns Fume Hoods without Auxiliary Air a. Turn fume hood exhaust blower on. b. With sash(es) in full open position, check air flow into the fume hood using a cotton swab dipped in titanium tetrachloride or other smoke source. Note: On fume hoods with horizontal sliding sash(es), check air flow with sash(es) at various full open positions. A complete traverse of the fume hood face should verify that air flow is into the fume hood over the entire face area. A reverse flow of smoke indicates unsafe fume hood operation. c. Move a lighted smoke candle throughout the fume hood work area, directing smoke across the work surface and against the side walls and baffle. Smoke should be contained within the fume hood and be rapidly exhausted. (Fume hoods with horizontal sliding sash(es) will show reverse flow and turbulence behind sash panel, but no outflow of smoke shall be evident.) Fume Hoods with Auxiliary Air a. Turn exhaust blower on and determine face velocity in accordance with Note: Face velocity and exhaust volumes shall be determined with the auxiliary air blower off. b. Calculate exhaust volume from face velocity data. c. Turn on auxiliary air, verify that auxiliary air volume is as specified. Locate a straight section of the supply air duct and drill two holes of a size appropriate for the pitot tubes to be used, 90 degrees apart, on a plane through the duct,

18 at the downstream end of the straight section. Measure the air velocity and calculate the air volume. Compare volumes determined with the specified volume of auxiliary air and with exhaust volume, to determine if proper ratio exists. Deviations of plus or minus five percent are acceptable. If deviations of more than five percent are noted, corrective measures should be taken. Seal holes in duct with duct tape or suitable sealant. d. With sash(es) in the open position, check air flow into the fume hood using a cotton swab dipped in titanium tetrachloride or other smoke source. A complete traverse of the fume hood face should verify that air flow is into the fume hood over the entire face area. A reverse flow of air indicates unsafe fume hood operation. e. Move a lighted smoke candle throughout the fume hood work area, directing smoke across the work surface and against the side walls and baffle. Smoke should be contained within the fume hood and be rapidly exhausted. Fume hoods with horizontal sliding sash(es) will show reverse flow and turbulence behind sash panel, but no outflow of smoke shall be evident Evaluation of Low Air Flow Monitor On fume hoods with low flow warning devices, verify that monitor functions properly and indicates unsafe conditions.

19 APPENDIX B LINER PERFORMANCE REQUIREMENTS ISOLATOR SERIES LABORATORY FUME HOODS POLYGLASS PVC POLYPROPYLENE EPOXY RESIN 304 SS 316 SS HYDROCHLORIC ACID 35% HYDROFLUORIC ACID PHOSPHORIC ACID 80% NITRIC ACID 35% SULFURIC 70% ACETIC ACID SODIUM HYDROXIDE 20% ACETONE ETHANOL METHANOL MEK GASOLINE CARBON TETRACHLORIDE FORMALIN 35% XYLENE = NO EFFECT 1= EXCELLENT 2=GOOD 3=FAIR 4= FAILURE No effect: Excellent: Good: Fair: Failure: No detectable change in working surface material. Slight detectable change in color or gloss, but no change to the function or life of the working surface material. A clearly discernable change in color or gloss, but no significant impairment of working surface function or life. Objectionable change in appearance due to surface discoloration or etch, possibly resulting in deterioration of function over a period of time. Pitting, cratering or erosion of working surface material. Obvious and significant deterioration.

20 APPENDIX C WORK SURFACE PERFORMANCE REQUIREMENTS A. TEST RESULTS OF CHEMICAL RESISTANCE OF EPOXY RESIN WORKTOP (BLACK): Reagent Acetate, Ethyl Acetic Acid, 5% Acetic Acid, Glacial Acetone Alcohol, Ethyl, 95% Alcohol, Methyl Ammonium Hydroxide, 10% Aniline Benzene Carbon Tetrachloride Chromic Acid, 40% Citric Acid, 1% Diethyl Ether Dimethylformanide Ethylene Dichloride Heptane Hydrochloric Acid, 10% Hydrochloric Acid, 37% Isooctane Kerosene Mineral Oil Nitric Acid, 40% Nitric Acid, 70% Oleic Acid Olive Oil Phenol Solution, 5% Soap Solution, 1% Sodium Carbonate Solution, 20% Sodium Hydroxide Solution, 60% Sodium Hypochlorite Solution, 4% Sulfuric Acid, 60% Sulfuric Acid, 96% Toluene Transformer Oil Turpentine Results Excellent Excellent Excellent Good Excellent Excellent Excellent Excellent Failure

21 Test results duplicated above were conducted on black material. Other colors of epoxy resin may have slightly different results. PART 3 EXECUTION 3.00 INSTALLATION - REFER TO INSTRUCTION AND INSTALLATION MANUAL A. Install fume hoods and equipment in accordance with manufacturer's instructions. B. Install equipment plumb, square, and straight with no distortion and securely anchored as required. C. Secure work surfaces to casework and equipment components with material and procedures recommended by the manufacturer. D. Accessory installation: Install accessories and fittings in accordance with manufacturer's recommendations OPTIONAL FIELD QUALITY CONTROL TESTING OF FUME HOODS A. Have [all] [a representative number of one of each width of the] fume hoods static tested for three (3) minutes using ANSI/ASHRAE All hoods shall pass with an average rating of AI 0.05 or less. B. Have [all] [a representative number of one of each width of the] fume hoods tested using SEFA All units tested shall pass using the specified criteria ADJUSTING A. Repair (or remove and replace) defective work, as directed by Owner's Representative upon completion of installation. B. Adjust sash and other moving or operating parts to ensure smooth, nearsilent and accurate sash operation with one hand and with uniform contact of rubber bumpers. Ensure counterweights operate without interference. C. Adjust fixtures and accessories to function smoothly CLEANING A. Clean equipment, touch up as required.

22 PROTECTION OF FINISHED WORK A. Provide all reasonable protective measures to prevent exposure of equipment from exposure to other construction activity. B. Advise contractor of procedures and precautions for protection of material and installed fume hoods from damage by work of other trades. END OF SECTION

23

SECTION LABORATORY FUME HOODS

SECTION LABORATORY FUME HOODS LABORATORY FUME HOODS GEN5 SERIES - ISOLATOR³ RELEASED APRIL, 2012 SECTION 11610.4 LABORATORY FUME HOODS GEN5 SERIES - ISOLATOR³ (HIGH PERFORMANCE/LOW FLOW) PART 1 GENERAL 1.00 SUMMARY A. Section Includes:

More information

Section Fume Hoods Specifications 6/1/14 LABORATORY FUME HOODS

Section Fume Hoods Specifications 6/1/14 LABORATORY FUME HOODS 1.01 SUMMARY A. Section Includes: Fume hoods LABORATORY FUME HOODS B. Related Sections 1. Division 12 Section - 12345 - Steel Laboratory Casework 2. Division 12 Section - 12346 - Agility Adaptable Furniture

More information

SECTION LABORATORY FUME HOODS

SECTION LABORATORY FUME HOODS SECTION 115313 LABORATORY FUME HOODS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes Laboratory Fume Hoods: B. Related Sections include the following: 1. [Division 12 Section Painted Steel Laboratory

More information

SECTION LABORATORY FUME HOODS UNIFLOW LE SERIES

SECTION LABORATORY FUME HOODS UNIFLOW LE SERIES SECTION 11610.1 LABORATORY LE FUME HOODS UNIFLOW LE SERIES REVISED AUGUST 2, 2013 LABORATORY FUME HOODS UNIFLOW LE SERIES PART 1 GENERAL 1.00 SUMMARY A. Section Includes: 1. Laboratory Fume Hoods B. Related

More information

F. VAV hoods shall have a restricted bypass plate.

F. VAV hoods shall have a restricted bypass plate. 1.01 SUMMARY A. Section Includes: 1. Laboratory fume hoods. B. Related Sections: 1. Section 6500 Laboratory casework 2. Section 15 Mechanical: Furnishing and installation of plumbing utilities and final

More information

LABORATORY FUME HOODS OF 5

LABORATORY FUME HOODS OF 5 SECTION 11 5313 - LABORATORY FUME HOODS AND RELATED PRODUCTS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Bench-top laboratory fume hoods. 2. Service fittings and electrical service fitting inside

More information

DESIGN STANDARDS WASHINGTON UNIVERSITY SCHOOL OF MEDICINE

DESIGN STANDARDS WASHINGTON UNIVERSITY SCHOOL OF MEDICINE SECTION 11 53 00 (11610) - LABORATORY FUME HOODS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

Supreme AirLV- FUME HOODS. KEWAUNEE encouraging new discovery LOW CONSTANT VOLUME

Supreme AirLV- FUME HOODS. KEWAUNEE encouraging new discovery LOW CONSTANT VOLUME Supreme AirLV- LOW CONSTANT VOLUME FUME HOODS KEWAUNEE encouraging new discovery Supreme Air LV Fume Hood Low Velocity Low Volume Full Access Hold-Open Catch for set-up sash position Flush Mounted Convergent

More information

.1 Special Building Areas 8. Laboratories..3 Laboratory Casework (section ).4 Chemical storage cabinets (section )

.1 Special Building Areas 8. Laboratories..3 Laboratory Casework (section ).4 Chemical storage cabinets (section ) Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying Laboratory Fume Hoods. These standards are not intended to restrict or replace professional judgment..2

More information

General Purpose Walk-In Fume Hood

General Purpose Walk-In Fume Hood General Purpose Walk-In Fume Hood with Vertical Rising Sash Available Models: Open By-Pass Restricted By-Pass Auxiliary Air Available Option: Adjustable Baffles Air Flow and Static Pressure Alarms Service

More information

General Purpose Walk-In Fume Hood

General Purpose Walk-In Fume Hood General Purpose Walk-In Fume Hood with Vertical Rising Sash Available Models: Open By-Pass Restricted By-Pass Auxiliary Air Available Option: Adjustable Baffles Air Flow and Static Pressure Alarms Service

More information

Selection of DODGE E-Z KLEEN Polymer and Stainless Steel Housed Ball Bearings. P = (X x F R ) + (Y x F A ) F A C o

Selection of DODGE E-Z KLEEN Polymer and Stainless Steel Housed Ball Bearings. P = (X x F R ) + (Y x F A ) F A C o Selection of DODGE and Stainless Steel Housed Ball Bearings DODGE ball bearings are primarily designed for radial loading. However, they have the capacity to carry thrust loads and combined radial/thrust

More information

Bedcolab Vanguard Laboratory Fume Hoods

Bedcolab Vanguard Laboratory Fume Hoods Bedcolab Vanguard Laboratory Fume Hoods 1. General 2. Conditions 3. Scope of work A. This section includes all material, equipment, tools and workmanship related to the supply and installation of fume

More information

TEST REPORT: CHM12-01-LSM

TEST REPORT: CHM12-01-LSM Date: Tel: +65 68851335 Fax: +65 67784301 Client s Ref: QM-0112-056 Email: Sihai.LI@tuv-sud-psb.sg Note: This report is issued subject to the Testing and Certification Regulations of the TÜV SÜD Group

More information

Design Requirements The system shall be designed, manufactured, tested and installed in compliance with the current versions or issuance of:

Design Requirements The system shall be designed, manufactured, tested and installed in compliance with the current versions or issuance of: SECTION 15877 FUME HOODS 1. General 1.1. Summary These specifications provide a performance specification for a chemical laboratory Fume Hood (herein referred to as FH). The intent of the specification

More information

Protector XStream Laboratory Hoods

Protector XStream Laboratory Hoods High Performance Hood offers enhanced containment combined with energy savings. With its unsurpassed containment and substantial energy savings potential, the patented* Protector XStream Fume Hood delivers

More information

Requires Ductwork and Blower

Requires Ductwork and Blower 6' Protector XStream Laboratory Hood 9840600 is shown with SpillStopper Work Surface 9849800, Protector Acid Storage Cabinet 9901100 and Protector Standard Storage Cabinet 9900100. Requires Ductwork and

More information

FUME HOOD SELECTION GUIDE

FUME HOOD SELECTION GUIDE FUME HOOD SELECTION GUIDE FUME HOOD SELECTION GUIDE Laboratory fume hoods are one of the most vital pieces of safety equipment in a working laboratory. Fume hoods are designed to safely exhaust dangerous

More information

Thermo Scientific Hamilton Horizon Fume Hoods. Operation, Maintenance and Installation Instructions

Thermo Scientific Hamilton Horizon Fume Hoods. Operation, Maintenance and Installation Instructions Thermo Scientific Hamilton Horizon Fume Hoods Operation, Maintenance and Installation Instructions Thermo Scientific Horizon Fume Hood Table of Contents Introduction.............................................................

More information

Protector XStream Laboratory Hood is shown with SpillStopper Work Surface , Protector Acid Storage Cabinet and Protector

Protector XStream Laboratory Hood is shown with SpillStopper Work Surface , Protector Acid Storage Cabinet and Protector Protector XStream Laboratory Hood 9840600 is shown with SpillStopper Work Surface 9849800, Protector Acid Storage Cabinet 9901100 and Protector Standard Storage Cabinet 9900100. Protector XStream Laboratory

More information

Fume Hoods Overview OVERVIEW

Fume Hoods Overview OVERVIEW OVERVIEW What Is A Fume Hood - A laboratory chemical fume hood is first and foremost a safety device. Users need to be able to rely on their fume hood as a primary containment device to protect them from

More information

Accessories Standard Service Fixture Kits

Accessories Standard Service Fixture Kits Standard Service Fixture Kits For mounting on the left or right side of any Protector Premier, XStream, XL, XLE or PVC Hood. Each kit includes one remotely-controlled service fixture with valve and 0.25"

More information

Fume hood construction details. VANGUARD FUME HOODS Listed by Intertek to UL 1805 standard page 1. Features

Fume hood construction details. VANGUARD FUME HOODS Listed by Intertek to UL 1805 standard page 1. Features Fume hood construction details 1 9 2 10 3 11 13 4 14 5 15 6 16 17 7 12 18 8 Features 1 Fluescent light fixture with interi sealed glass offering a safe and bright wking area (100 foot candles) 2 SEFA-8

More information

BMC. Laboratory Fume Hoods SEFA SCIENTIFIC EQUIPMENT & FURNITURE ASSOCIATION M E M B E R

BMC. Laboratory Fume Hoods SEFA SCIENTIFIC EQUIPMENT & FURNITURE ASSOCIATION M E M B E R BMC Laboratory Fume Hoods M E M B E R SEFA SCIENTIFIC EQUIPMENT & FURNITURE ASSOCIATION Table of Contents Airfoil ADA Fume Hoods...12 ADA Fume Hood Assemblies...13 Add Air Fume Hoods...10 Add Air Fume

More information

Fume hood construction details VANGUARD FUME HOODS. Listed by Intertek to UL 1805 standard. page 1. Features

Fume hood construction details VANGUARD FUME HOODS. Listed by Intertek to UL 1805 standard. page 1. Features Fume hood construction details 1 2 3 4 5 6 7 9 10 11 13 14 15 16 17 12 18 8 Features 1 Fluescent light fixture with interi sealed glass offering a safe and bright wking area (100 foot candles) 2 SEFA-8

More information

RDM. Laboratory Fume Hoods SEFA SCIENTIFIC EQUIPMENT & FURNITURE ASSOCIATION

RDM. Laboratory Fume Hoods SEFA SCIENTIFIC EQUIPMENT & FURNITURE ASSOCIATION RDM Laboratory Fume Hoods SEFA SCIENTIFIC EQUIPMENT & FURNITURE ASSOCIATION Table of Contents Airfoil ADA Fume Hoods...12 Demonstration Fume Hood...22 ADA Fume Hood Assemblies...13 Drains... 30 SB-MAX-A

More information

Protector Special Application Hoods Laboratory Hoods for Radioisotope, Perchloric Acid and Acid Digestion Use Fiberglass 28, Demonstration and Canopy

Protector Special Application Hoods Laboratory Hoods for Radioisotope, Perchloric Acid and Acid Digestion Use Fiberglass 28, Demonstration and Canopy Protector Special Application Hoods Laboratory Hoods for Radioisotope, Perchloric Acid and Acid Digestion Use Fiberglass 28, Demonstration and Canopy Hoods A Applications involving perchloric acid, acid

More information

Labconco 48, 60, and 72 Hoods

Labconco 48, 60, and 72 Hoods Labconco 48, 60, and 72 Hoods PROTECTOR LABORATORY HOODS INSTRUCTION MANUAL Model Nos. Remote Blower Integral Blower Style Style 48705 60705 72705 48713 60713 72713 48707 60707 72707 48714 60714 72714

More information

High Performance Fume Hood Laminar Topography and Perfect Protection Perimeter

High Performance Fume Hood Laminar Topography and Perfect Protection Perimeter High Performance Fume Hood Laminar Topography and Perfect Protection Perimeter Frontier Acela TM High Performance Fume Hood, (vertical sash shown), Model EFA-4UDRVW-8. (Shown with EBA-4UDG-0) Frontier

More information

LABORATORY FUME HOODS

LABORATORY FUME HOODS Fume Hoods Fume Hood Applications Laboratory professionals and students across the country, and all over the world, depend on the safety of our hoods. Your protection is our first concern and the fume

More information

January, 2014 Page 1 of 6

January, 2014 Page 1 of 6 Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying chemical fume hood modifications or installations. These standards are not intended to restrict or replace

More information

CORPORATION DURALAB CORPORA

CORPORATION DURALAB CORPORA DURALAB CORPORATION The Tradition Continues the most complete, versatile and colorful line of LABORATORY FUME HOODS and accessories DURALAB CORPORATION 3145 Bordentown Avenue Parlin, NJ 08859 Ph: 888-805-1740

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Copyright 2008 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA SECTION 11 53 00 - LABORATORY EQUIPMENT PART

More information

Ducting & Ventilation Components

Ducting & Ventilation Components Ducting & Ventilation Components 111 Powell Road Independence, MO 64056 visit www.hemcocorp.com Phone: 816-796-2900 Fax : 816-796-3333 E-Mail : info@hemcocorp.com Exhaust Blowers are constructed of chemical

More information

Protector Demonstration Hoods

Protector Demonstration Hoods Protector Demonstration Hoods Protector Demonstration Hoods are low profile, light-duty fume hoods designed to provide close observation of procedures during educational demonstrations. ll models feature:

More information

V05 General Purpose Bench Fume Hood

V05 General Purpose Bench Fume Hood V05 General Purpose Bench Fume Hood with Vertical Rising ash Accessories Included: 4 120 VAC 20 amp GFCI protected duplex receptacles 1 LED light fixture with illumination and color controller 1 Electronic

More information

Laboratory Demonstration Space Located at Price Research Center North Winnipeg. Fume Hoods. ehpricesales.com

Laboratory Demonstration Space Located at Price Research Center North Winnipeg. Fume Hoods. ehpricesales.com Laboratory Demonstration Space Located at Price Research Center North Winnipeg Fume Hoods ehpricesales.com 2 www.ehpricesales.com FUME HOODS Contents Dynamic Bench Fume Hood Features High Performance Fume

More information

Supreme Air. Fume Hoods KEWAUNEE LABORATORY. encouraging new discovery

Supreme Air. Fume Hoods KEWAUNEE LABORATORY. encouraging new discovery Supreme Air LABORATORY Fume Hoods KEWAUNEE encouraging new discovery Stainless Steel H05 Fume Hood with Vertical Rising Sash LV05 Low Constant Volume Fume Hood Supreme Air Fume Hoods Kewaunee s Fume Hood

More information

Annexure-1. Annexure- 1 TECHNICAL SPECIFICATIONS FOR THE MODULAR LABORATORY FURNITURE (CNSNT/RL-4)

Annexure-1. Annexure- 1 TECHNICAL SPECIFICATIONS FOR THE MODULAR LABORATORY FURNITURE (CNSNT/RL-4) Annexure- 1 TECHNICAL SPECIFICATIONS FOR THE MODULAR LABORATORY FURNITURE (CNSNT/RL-4) Item Number-1 ----------------------------------------------------------------------------------------------------------

More information

P17 Tempra Pro plugs, mobile sockets, fixed sockets, surface mounting sockets and appliance inlets - IP 66/67-63 A A

P17 Tempra Pro plugs, mobile sockets, fixed sockets, surface mounting sockets and appliance inlets - IP 66/67-63 A A CONTENTS Page 5 555 09 5 555 29 5 555 59 5 555 9 1. General characteristics...1 2. Use...1 3. Range/Equivalence table...2 4. Dimensions..............................3 5. Technical characteristics...5 6.

More information

Protector XL Floor-Mounted Laboratory Hoods Features & Benefits

Protector XL Floor-Mounted Laboratory Hoods Features & Benefits Protector XL FLOOR-MOUNTED LAORATORY HOODS Protector XL Floor-Mounted Laboratory Hoods Features & enefits Protector XL Floor-Mounted Laboratory Hoods accommodate laboratory procedures that require over-sized

More information

Fume Hood Operation & Maintenance Manual

Fume Hood Operation & Maintenance Manual Fume Hood Operation & Maintenance Manual Fume Hood Operation & Maintenance Manual TABLE OF CONTENTS Fume Hood Applications 2 Safety 3 Aerodynamic Principles & Safety 4 Fume Hood Cleaning 7 Basic Maintenance

More information

LABORATORY CABINETRY AND SPECIALTIES: FUME HOODS

LABORATORY CABINETRY AND SPECIALTIES: FUME HOODS Laboratory Cabinetry and Specialties: Fume Hoods LABORATORY CABINETRY AND SPECIALTIES: FUME HOODS 217.540.3100 www.stevensind.com Laboratory Cabinetry and Specialties Fume Hoods.2 Laboratory Cabinetry

More information

Supreme Air Fume Hood Option Availability

Supreme Air Fume Hood Option Availability Supreme Air Fume Hood Option Availability Options V05 V06 V07 V15 V16 V25 V26 Kemglass Liner ( 1 /4") G KMER Liner ( 1 /4") K Type 316L Stainless Steel Liner (16 ga) L Type 304L Stainless Steel Liner (16

More information

LABORATORY FUME HOODS

LABORATORY FUME HOODS Fume Hoods Fume Hood Applications Laboratory professionals and students across the country, and all over the world, depend on the safety of our hoods. Your protection is our first concern and the fume

More information

Model ND-2 Specification

Model ND-2 Specification Model ND-2 Specification The model ND-2 is an exhaust only canopy hood rated for all types of cooking equipment. The hood shall have the size, shape and performance specified on drawings. Construction

More information

new fume hoods providing performance and protection

new fume hoods providing performance and protection new fume hoods providing performance and protection five questions to get us started 1. Will the use of your hood require a special application hood? 2. How high of a priority is energy conservation? 3.

More information

A. Each cabinet must be constructed and installed in accordance with EN12469:2000.

A. Each cabinet must be constructed and installed in accordance with EN12469:2000. BIOLOGICAL SAFETY CABINETS Class II, Biological Safety Cabinet PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this section to the extent referenced. The publications are referred

More information

Frontier. Laboratory Fume Hood. Perfectly tailored solutions for your fume containment needs

Frontier. Laboratory Fume Hood. Perfectly tailored solutions for your fume containment needs Frontier Laboratory Perfectly tailored solutions for your fume containment needs 2 About Esco...02 Esco Frontier s are Tested and Certified for Safety.03 Esco Global Network and Product Overview...04 General

More information

Lab Safety & Energy Optimization. Introduction & Agenda

Lab Safety & Energy Optimization. Introduction & Agenda Lab Safety & Energy Optimization Determining Appropriate Airflow Specifications for VAV Fume Hoods Thomas C. Smith tcsmith@labhoodpro.com Introduction & Agenda Thomas C. Smith President, BSME (NCSU), MSEE

More information

Strength, resilience, rigidity - these are all attributes needed to combat arduous and aggressive conditions. Tufflite has them all.

Strength, resilience, rigidity - these are all attributes needed to combat arduous and aggressive conditions. Tufflite has them all. Strength, resilience, rigidity - these are all attributes needed to combat arduous and aggressive conditions. Tufflite has them all. From commercial applications requiring a simple sealed luminaire, right

More information

User s Manual. LabShield. Laboratory Fume Hoods. Air Foil By-Pass Models: 6714, 6716, ADA Models: 8796, 8798, Demonstration Hood 6725G

User s Manual. LabShield. Laboratory Fume Hoods. Air Foil By-Pass Models: 6714, 6716, ADA Models: 8796, 8798, Demonstration Hood 6725G User s Manual LabShield By CampbellRhea Laboratory Fume Hoods Air Foil By-Pass Models: 6714, 6716, 6718 ADA Models: 8796, 8798, 8800 Demonstration Hood 6725G CampbellRhea 1865 North Market Street Paris

More information

Physical properties of PET resins. 1. Intrinsic Viscosity (IV)

Physical properties of PET resins. 1. Intrinsic Viscosity (IV) Physical properties of PET resins 1. Intrinsic Viscosity (IV) Intrinsic viscosity (IV) is a measure of polymer molecular weight, which in turn is a measure of the mechanical strength capability of the

More information

Issue 4 (Record Only) Job #: Innovent Submittal Date: October 30, 2012 Project: Location: Columbus, OH Innovent Job #: Submittal Issue: 4 (Record Only) Engineer: Contractor: Tag Innovent Model # AHU-BG-01

More information

How to Use the Chemical Compatibility Chart. Vials and Closures >> Chemical Compatibility Chart

How to Use the Chemical Compatibility Chart. Vials and Closures >> Chemical Compatibility Chart How to Use the Chemical Compatibility Chart The following chart contains information regarding the expected effects of 7 day direct solvent exposure on materials used for production of vials, caps and

More information

3.5 Exposure Control Measures

3.5 Exposure Control Measures 3.5 Exposure Control Measures 3.5.1 Chemical Fume Hoods Chemical fume hoods are the most reliable and primary engineering control used in the laboratory to protect against the inhalation of hazardous vapors

More information

Metallic Systems TYPE SPTC

Metallic Systems TYPE SPTC CONDUIT 27/01/2009 Technical Data Sheet Page No. 1 Applications Hospitals External Safety Critical Area Fittings IP54 SPB Fittings type A & B Characteristics Very High UV Resistance High Flexibility Medium

More information

AUDIO-VISUAL EQUIPMENT

AUDIO-VISUAL EQUIPMENT 11 52 00 AUDIO-VISUAL EQUIPMENT 1. GENERAL A. Related sections: i. 00 00 13 Designing Learning Environments ii. 11 52 13 Projection Screens iii. 12 56 52 Audio-Visual Equipment iv. 72 41 00 General Audio-Visual

More information

ROLLER SHADE SPECIFICATIONS

ROLLER SHADE SPECIFICATIONS Part 1 General 1.1 Scope A. Furnish and install roller shades provided by Fabtex Inc., (800) 778-2791 B. Substitutions: Not Permitted C. Related work specified elsewhere 1.2 Quality Assurance A. Installer

More information

Square Inline Fans with Multi-Directional Discharge

Square Inline Fans with Multi-Directional Discharge SQN Square Inline Fans with Multi-Directional Discharge Page Introduction............................................2 Standard Construction Features............................ 3 Specifications and Dimension

More information

Ventilated Balance Enclosures

Ventilated Balance Enclosures Ventilated Balance Enclosures by PLAS n LABS Meets and exceeds ANSI/ASHRAE 110:2016 standard for containment & performance PLAS n LABS, INC. www.plas-labs.com PLI@PLAS-LABS.com 517-372-7177 Ventilated

More information

HEMCO. Laboratory Fume HoodsR

HEMCO. Laboratory Fume HoodsR Laboratory Fume HoodsR UniFlow SE Hoods UniFlow LE Hoods 2018 Made in USA 9001: 2008 Certified 60th Year UniFlow AireStream Laboratory Fume Hoods Fume Hood Service Components Special Purpose Hoods Laboratory

More information

FR PVC COATED RAINWEAR

FR PVC COATED RAINWEAR FR COATED RAINWEAR INDUSTRY/FORESTRY/RAINWEAR All fabrics are tested and certified in accordance with en 343; the european standard for waterproof clothing. Extreme weather protection - EN 343 Protection

More information

Laboratory Fume Hoods & Enclosures

Laboratory Fume Hoods & Enclosures Laboratory Fume Hoods & Enclosures Protector ClassMate Laboratory Hoods Fiberglass 30 Laboratory Hoods Protector Demonstration Hoods Basic Laboratory Hoods Protector XVS Ventilation Stations Canopy Hoods

More information

SECTION WELDING FUME EXHAUST SYSTEM

SECTION WELDING FUME EXHAUST SYSTEM SECTION 233500 WELDING FUME EXHAUST SYSTEM PART 1 - GENERAL 1.1 WORK INCLUDES Welding fume exhaust system and controls Accessories Additional System Equipment Engineering Support Commissioning 1.2 RELATED

More information

2520- EC Motor Speed Controller

2520- EC Motor Speed Controller 2520- EC Motor Speed Controller T1 AC Line Voltage From Contactor T2 or Neutral 760-ECM ECM Motor BLACK ORANGE BLACK RED (+) Signal 24VAC (-) GND Features Motor Types: ECM (dc brushless) Motors Motor Speed:

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,

More information

Direct Gas-Fired Heating

Direct Gas-Fired Heating Direct Gas-Fired Heating Model DG 800 to 15,000 cfm Up to 1,600,000 BTU/hr Optional Evaporative Cooling January 2005 PRODUCT FEATURES Model DG Direct Gas-Fired Make-Up Air Unit The Greenheck model DG is

More information

HYPRA Prisinter 16/32/63 A

HYPRA Prisinter 16/32/63 A 8704 LIMOGES Cedex Telephone: + 33 0 06 87 87 - Fax: + 33 0 06 88 88 HYPR Prisinter 16/32/63 Page 1. General characteristics........1 2. Range......................1 3. Dimensions............... 2-3 4.

More information

Laboratory Design Standards

Laboratory Design Standards Laboratory Design Standards This design guide shall apply to all laboratories where hazardous chemicals, biological agents, and radioactive materials are stored, handled, used, or produced. All such laboratories

More information

Catalog June Mounted Bearings

Catalog June Mounted Bearings Catalog June 2014 Mounted Bearings Contents. Ultra Kleen Features/Benefits.... 1-3 How to order/nomenclature............................................. 1-6 Easy Selection.... 1-7..................................................

More information

High Performance Fume Hood Laminar Topography and Perfect Protection Perimeter

High Performance Fume Hood Laminar Topography and Perfect Protection Perimeter Frontier Acela High Performance Fume Hood, (vertical sash shown), Model EFA-4UDRVW-8. (Shown with EBA-4UDG-0) High Performance Fume Hood Laminar Topography and Perfect Protection Perimeter TABLE OF CONTENTS

More information

STATE OF NORTH CAROLINA D DEPARTMENT OF ADMINISTRATION MARCH 20, 1995 PURCHASE AND CONTRACT DIVISION 7125-LM-2C November 9, 1989

STATE OF NORTH CAROLINA D DEPARTMENT OF ADMINISTRATION MARCH 20, 1995 PURCHASE AND CONTRACT DIVISION 7125-LM-2C November 9, 1989 STATE OF NORTH CAROLINA 7125-2D DEPARTMENT OF ADMINISTRATION MARCH 20, 1995 PURCHASE AND CONTRACT DIVISION Superseding 7125-LM-2C November 9, 1989 SPECIFICATION FOR LOCKERS, METAL (This specification is

More information

Completing Your Fume Removal System

Completing Your Fume Removal System Once a laboratory hood has been selected, the next step is to select the proper blower and ductwork. It is important that these be sized correctly depending on hood size, application, CFM, and distance

More information

The Industrial Choice. Model TFBD. Model FBD FIBERGLASS AXIAL FLOW FANS. Model FDP / FRV / FBD / TFBD / VTFBD

The Industrial Choice. Model TFBD. Model FBD FIBERGLASS AXIAL FLOW FANS. Model FDP / FRV / FBD / TFBD / VTFBD The Industrial Choice. Model TFBD Model FBD FIBERGLASS AXIAL FLOW S Model FDP / FRV / FBD / TFBD / VTFBD CATALOG 85 October 207 Fiberglass Axial Flow Fans Models FDP FRV FBD TFBD VTFBD Medium Pressure

More information

A. This Section includes the following types of sectional overhead doors:

A. This Section includes the following types of sectional overhead doors: SECTION 08361 - SECTIONAL OVERHEAD DOORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

th Avenue Spring Lake, MI Ph:

th Avenue Spring Lake, MI Ph: LABORATORY FUME HOOD CATALOG CA Style fume hoods FUME HOODS SPECIAL HOODS CANOPY HOODS FUME REMOVAL STANDS ACCESSORIES 18784 174 th Avenue Spring Lake, MI 49456 Ph: 616-846-6990 www.keurindustries.com

More information

SECTION METAL LOCKERS. A. ADAAG - Americans with Disabilities Act, Accessibility Guidelines.

SECTION METAL LOCKERS. A. ADAAG - Americans with Disabilities Act, Accessibility Guidelines. Section 10_51_13_MetalLockerPenco-ProTough_8-19-09 PART 1 GENERAL SECTION 10 51 13 METAL LOCKERS 1.01 SECTION INCLUDES A. Heavy Duty Welded Tubular Frame Lockers. B. Locker benches. 1.02 REFERENCES A.

More information

Fume Hood Standard. The appropriate maintenance/engineering division on each campus or other business unit operating on UofT property shall:

Fume Hood Standard. The appropriate maintenance/engineering division on each campus or other business unit operating on UofT property shall: Fume Hood Standard A fume hood is an enclosed working chamber fitted with an exhaust ventilation system. It is one component of an exposure control system which is designed to contain, dilute and disperse

More information

PERCHLORIC ACID FUME HOOD H25. Fume Hoods. 48"- 60"- 72"- 96" long

PERCHLORIC ACID FUME HOOD H25. Fume Hoods. 48- 60- 72- 96 long Supreme Air PERCHLORIC ACID FUME HOOD with Vertical Rising Sash H25 S T Y L E Fume Hoods 48"- 60"- 72"- 96" long Publication No. IIH25-SA 11/05 Part Number: IMAN-H25 Supreme Air Bench Hood Perchloric Acid

More information

MM PISTON PUMP

MM PISTON PUMP MM-76500-50 PUMP NATIONAL INSTRUMENT COMPANY Part No. 8649, FSV-60-1 with O-Ring Piston Note: To be used only on the MM-76400-20 and MM-76400-25 Fillers For filling semi viscous** to heavy viscosity***

More information

SafeAire Fume Hoods. Operation, Maintenance and Installation Instructions

SafeAire Fume Hoods. Operation, Maintenance and Installation Instructions SafeAire Fume Hoods Operation, Maintenance and Installation Instructions GENERAL INFORMATION Fisher Hamilton is pleased to have had the privilege of furnishing your laboratory equipment. This is a major

More information

SECTION HVAC AIR CLEANING DEVICES

SECTION HVAC AIR CLEANING DEVICES SECTION 23 40 00 HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes activated carbon filters, automatic renewable media filters, disposable, extended area panel filters, disposable

More information

Series 301. Horizontal Laminar Flow Clean Bench. C l e a n B e n c h e s. s o l u t i o n s. Series 301 Horizontal Laminar Flow Clean Bench

Series 301. Horizontal Laminar Flow Clean Bench. C l e a n B e n c h e s. s o l u t i o n s. Series 301 Horizontal Laminar Flow Clean Bench Series 301 Horizontal Laminar Flow Clean Bench s o l u t i o n s The Series 301 is a general-purpose, horizontal flow clean bench ideally suited to many types of mechanical or processing work. It is designed

More information

DetectAir KEWAUNEE FILTERED FUME HOODS. encouraging new discovery

DetectAir KEWAUNEE FILTERED FUME HOODS. encouraging new discovery DetectAir FILTERED FUME HOODS KEWAUNEE encouraging new discovery KEWAUNEE DetectAir Filtered Fume Hoods powered by 2 Kewaunee encouraging new discovery DetectAir Filtered Fume Hoods powered by AirClean

More information

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section SECTION 15910 DUCT ACCESSORIES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division-1 Specification Sections,

More information

KVR Capture Jet. KVR- Capture Jet Round Island Hood with Perimeter Jets. Round Island Hood with Perimeter Jets

KVR Capture Jet. KVR- Capture Jet Round Island Hood with Perimeter Jets. Round Island Hood with Perimeter Jets KVR Capture Jet Round Island Hood with Perimeter Jets The KVR Round Island Capture Jet hood with perimeter jets is a highly efficient kitchen ventilation hood that removes contaminated air and excess heat

More information

LABGARD FEATURES

LABGARD FEATURES LABGARD 425 - FEATURES Front Filter Removal and Maintenence Minihelic Guage Sliding Tempered Glass Window Closes Completely Duplex Outlet 10 Access Opening Ergonomic PVC Armrest Optional Base Stand Clean

More information

SECTION RAPIDVIEW MODEL 999. Copyright ARCAT, Inc. All rights reserved

SECTION RAPIDVIEW MODEL 999. Copyright ARCAT, Inc. All rights reserved SECTION 08 33 23.13 HIGH PERFORMANCE OVERHEAD HIGH SPEED DOORS RAPIDVIEW MODEL 999 Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2016 2018 ARCAT, Inc. All rights reserved **

More information

SECTION METAL ATHLETIC SPORT LOCKERS

SECTION METAL ATHLETIC SPORT LOCKERS SECTION 10 50 13 - METAL ATHLETIC SPORT LOCKERS PART 1 GENERAL 1.1 SECTION INCLUDES A. DESCRIPTION: Furnish and install factory-assembled Heavy-Duty MIG-Welded Metal Lockers, complete, as shown and specified

More information

Design Standard - Fume Hoods & Fume Hood Exhausts

Design Standard - Fume Hoods & Fume Hood Exhausts Design Standard - Fume Hoods & Fume Hood Exhausts 1.0 Introduction The fume hood is the primary control device in most laboratories for protecting employees and students from exposure to hazardous chemicals.

More information

AUDIO-VISUAL EQUIPMENT

AUDIO-VISUAL EQUIPMENT 11 52 00 AUDIO-VISUAL EQUIPMENT 1. GENERAL A. Related sections: i. 00 00 13 Designing Learning Environments ii. 11 52 13 Projection Screens iii. 12 56 52 Audio-Visual Equipment iv. 72 41 00 General Audio-Visual

More information

SECTION [ ] HIGH PERFORMANCE OVERHEAD HIGH SPEED DOORS. Display hidden notes to specifier. (Don't know how?

SECTION [ ] HIGH PERFORMANCE OVERHEAD HIGH SPEED DOORS. Display hidden notes to specifier. (Don't know how? SECTION 08337 [08 33 23.13] HIGH PERFORMANCE OVERHEAD HIGH SPEED DOORS Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2016 ARCAT, Inc. - All rights reserved PART 1 GENERAL 1.1

More information

P17 plugs, mobile sockets and surface-mounting sockets «New range 16 and 32 A»

P17 plugs, mobile sockets and surface-mounting sockets «New range 16 and 32 A» 87045 LIMOGES Cedex Telephone : + 33 0 5 55 06 87 87 - Fax : + 33 0 5 55 06 88 88 P7 plugs, mobile and surface- Cat. Nos. : 555 53/57/58/73/77/78-5 53/57/58/73/77/78 CONTENTS Page 575 4. Definition....

More information

How to Use a Chemical Fume Hood Safely

How to Use a Chemical Fume Hood Safely Published on UC Davis Safety Services (https://safetyservices.ucdavis.edu) How to Use a Chemical Fume Hood Safely SafetyNet #: 35 A chemical fume hood is designed to protect the worker from volatile and

More information

Laboratory Fume Hoods & Enclosures

Laboratory Fume Hoods & Enclosures Laboratory Fume Hoods & Enclosures Protector ClassMate Laboratory Hoods Fiberglass 30 Laboratory Hoods Protector Demonstration Hoods Basic Laboratory Hoods Protector XVS Ventilation Stations Canopy Hoods

More information

MM PISTON PUMP

MM PISTON PUMP MM-76500-30 PISTON PUMP NATIONAL INSTRUMENT COMPANY Part No. 8655, FKS-60-75 Pump with O-Ring Piston For filling free flowing* to semi viscous** liquids INSTRUCTIONS U.S. AND FOREIGN PATENTS ISSUED AND

More information

Laboratory Fume Hood. Operation & Maintenance Manual APR 2005

Laboratory Fume Hood. Operation & Maintenance Manual APR 2005 Laboratory Fume Hood Operation & Maintenance Manual APR 2005 TABLE OF CONTENTS I. Introduction p. 3 II. Fume Hood Services p. 4 III. Operation Recommendations p. 4 IV. General Fume Hood Maintenance p.

More information

SECTION DUCTWORK ACCESSORIES

SECTION DUCTWORK ACCESSORIES SECTION 15910 DUCTWORK ACCESSORIES PART 1- GENERAL SCOPE This sections includes accessories used in the installation of duct systems. Included are the following topics: PART 1- GENERAL Related Work Reference

More information

SECTION METAL LOCKERS. A. ADAAG Americans with Disabilities Act, Accessibility Guidelines.

SECTION METAL LOCKERS. A. ADAAG Americans with Disabilities Act, Accessibility Guidelines. SECTION 10 51 13 METAL LOCKERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Heavy Duty Welded Gear Lockers. B. Locker benches. 1.02 REFERENCES A. ADAAG Americans with Disabilities Act, Accessibility Guidelines.

More information