DET Series EARTH GROUND ELECTRODE TESTERS

Size: px
Start display at page:

Download "DET Series EARTH GROUND ELECTRODE TESTERS"

Transcription

1 M DET Series EARTH GROUND ELECTRODE TESTERS USER GUIDE

2 CONTENTS CONTENTS 2 INTRODUCTION 3 G SAFETY WARNINGS 4 G LIVE EARTH SAFETY PRECAUTIONS 5 G BATTERY INSTALLATION 5 G BATTERY CHARGING (DET4TCR ONLY) 5 GENERAL DESCRIPTION 6 PREPARATIONS FOR USE 9 GENERAL OPERATING INSTRUCTIONS 10 INSTRUMENT ILLUSTRATIONS 12 BATTERY 18 DESCRIPTION OF TESTS 23 PREVENTIVE INSTRUMENT MAINTENANCE 60 TECHNICAL SPECIFICATION 61 REPAIR AND WARRANTY 64 Symbols used on the instrument are: G Caution: refer to accompanying notes t c Equipment protected throughout by Double Insulation (Class II) Equipment complies with current EU directives Equipment complies with C tick requirements Do not dispose of in normal waste stream Note: The safety warnings provided in this document are indicative of safe practice and shall not be considered exhaustive. Additionally, they are not intended to replace local safety procedures where the instrument is being used. Note: This user guide uses the terms earth and ground interchangeably. 2

3 INTRODUCTION Thank you for purchasing the Megger Earth Ground Tester. For your own safety and to get the maximum benefit from your instrument, please ensure that you read and understand the following safety warnings and instructions before attempting to use the instruments. This user manual describes the operation and functions of the DET series of Earth Ground Testers: DET3TA DET3TC DET3TD DET4TD DET4TC DET4TCR ICLAMP VCLAMP CALIBRATION ADAPTOR TWO-CLAMP CALIBRATION ADAPTOR These instruments are designed and manufactured by: Megger Limited Archcliffe Road Dover Kent CT17 9EN England Megger Limited reserves the right to change the specification of these instruments at any time without prior notice. 3

4 G SAFETY WARNINGS Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed during use. Do not leave the instrument connected to the system under test when not in use. Do not touch circuit connections and exposed metalwork of an installation or equipment under test. Do not touch the earth stakes, test leads and their terminations (including connections to the earthing system under test) if an installation earth fault can arise unless adequate precautions are taken. Do not touch the earth stakes, test leads and their terminations (including connections to the earthing system under test) while the instrument is switched on. Do not operate the instrument or connect it to any external system if it shows any visible signs of damage or if it has been stored for prolonged periods in unfavourable conditions. Do not operate the instrument or connect it to any external system if the battery compartment or casing is open or any parts of the case (including keypad, selector switch, display window, etc.) are missing. Special precautions are necessary when operating in situations where "live" earths may be encountered: isolation switches and fuses (not supplied with this instrument) must be used. Special precautions are necessary when working near high tension systems (MV and HV): rubber gloves and shoes (not supplied with this instrument) should be worn. Special precautions are necessary when working in wet conditions or in agricultural areas: observe the local safety standards and take all necessary special precautions applicable to the particular location and do not touch the test leads with bare hands. Always disconnect the instrument from the earthing system under test while batteries are being changed or the fuse replaced. Always replace batteries and fuses with parts of the correct type and rating. Do not replace the rechargeable cells in the DET4TCR with non-rechargeable dry cells. Do not use any other charging equipment other than that supplied by Megger for use with the DET4TCR. Do not operate the charging equipment supplied with the DET4TCR in damp or wet environments or outside. NOTE: THE INSTRUMENT MUST ONLY BE USED BY SUITABLY TRAINED AND COMPETENT PERSONS. Users of this equipment and/or their employers are reminded that National Health and Safety Legislation requires them to carry out valid risk assessments of all electrical work so as to identify potential sources of electrical danger and risk of electrical injury such as inadvertent short circuits. Where the assessments show that the risk is significant then the use of fused test leads may be appropriate. 4

5 G LIVE EARTH SAFETY PRECAUTIONS A 'Live' earth is one that carries current from the mains supply, or could do so under fault conditions. The following warnings apply in addition to those listed previously. All persons involved must be trained and competent in isolation and safety procedures for the system to be worked on. They must be clearly instructed not to touch the earth electrode, test stakes, test leads, or their terminations if any 'Live' earths may be encountered. It is recommended that they wear appropriate rubber gloves, rubber soled shoes, and stand on a rubber mat. The earth electrode under test should be isolated from the circuit it is protecting before testing commences. If this is not possible, ART may be used to measure electrode resistance. The instrument terminals should be connected to the system under test through isolation switches that are rated to handle the likely maximum fault voltages and currents that could be encountered at the installation. The isolation switch must be open whilst any personal contact is made with the remote test stakes, or the connecting leads, e.g. when changing their position. The instrument terminals should be connected to the system under test through fuses that are rated to handle the likely maximum fault voltages and currents that could be encountered at the installation. G BATTERY INSTALLATION Warning: Whenever battery cells are being fitted or replaced, there should be no connections to the instrument terminals and the instrument should be switched off. Warning: To avoid damage by leaking electrolyte or deep discharge, do not leave cells fitted in an instrument which will remain unused for extended periods of time. Warning: Incorrect battery cell polarity can cause electrolyte leakage, resulting in damage to the instrument. If the battery condition indicator does not show a full charge when battery cells are new, a cell may be reversed. DET4TCR ONLY Warning: Only use the cells recommended by Megger, part number G BATTERY CHARGING (DET4TCR ONLY) Warning: Whenever battery cells are being recharged, there should be no connections to the instrument terminals and the instrument should be switched off. Warning: Do not attempt to recharge non-rechargeable (dry) cells in the DET4TCR. Doing so will result in instrument damage and may cause personal injury. Warning: Only use the charging equipment provided by Megger for use with this instrument. 5

6 GENERAL DESCRIPTION The Megger DET family of test instruments offers a unique solution to the measurement of earth or ground electrode (rod) resistance and soil resistivity. The family has six variants supporting 2, 3 and 4-wire measurements: The DET3TA provides 2 and 3-wire measurements and offers an analogue display. The DET3TC and DET3TD provide 2 and 3-wire measurements and offer a digital display. The DET4TD, DET4TC and DET4TCR provide 2, 3 and 4-wire measurement and offer a digital display. The DET3TC, DET4TC and DET4TCR can use an optional current clamp (ICLAMP) to measure conductor current and electrode (rod) resistance without disconnection, leaving the installation earthing system intact (Attached Rod Technique, ART). Additionally, the DET4TC and DET4TCR can drive an optional voltage-inducing clamp (VCLAMP) which, in conjunction with the ICLAMP, can be used to make stakeless measurements of the earthing system. An explanation of the part numbering system is shown in Figure 1. Figure 1: part numbering system 6

7 The DET family have the following features: Feature DET3TA DET3TD DET3TC DET4TD DET4TC DET4TCR Automatic C stake check Automatic P stake check Manual P stake check Automatic noise check Manual noise check Noise rejection (40 V pk-pk) 2-wire test 3-wire test 4-wire test (2 k) 4-wire test (20 k) No disconnect testing (ART) Stakeless measurement Voltmeter (ground noise voltage measurement) Current meter LCD display Backlit display Moving coil meter IP54 rated EN V CAT IV Built-in battery charger 7

8 Each instrument kit comprises the following: DET instrument Test leads (for 3-wire instruments, lead lengths are: 3m, 10m and 15m; for 4-wire instruments: 3m, 10m, 10m and 15m) Test stakes (for 3-wire instruments: 2 stakes are supplied; for 4-wire instruments, 4 stakes are supplied) Batteries 8x AA (LR6) alkaline (except DET4TCR) Batteries 8x AA (LR6) 1800mAhr NiMH (DET4TCR only) Warranty card Calibration certificate (not DET3TA) Owners CD-ROM manual Tough polypropylene carrying-case External AC/DC adaptor (DET4TCR only) 8

9 PREPARATIONS FOR USE Batteries The Megger DET series instruments are supplied with batteries fitted. When batteries become exhausted, refer to the section on battery replacement or recharging. Warning: Do not switch the instrument on with the battery cover removed. Inspection Before each use of the instrument, visually inspect the instrument case, test leads, stakes and connectors to confirm that their condition is good, with no damaged or broken insulation. 9

10 GENERAL OPERATING INSTRUCTIONS Instrument output voltage selection The maximum output voltage of the instrument is 50 V. It is possible to reduce this to 25 V for operation in situations which require it. The most appropriate output voltage should be selected by the operator based on local safety procedures. The procedure for changing the output voltage is as follows: DET3TA: 1. Press and hold the TEST button and switch instrument ON to the V setting using the selector switch. 2. The needle will sweep across the scaleplate and return to the rest position. [On older DET3TC and DET3TD instruments, the firmware version will be displayed followed by tst ]. 3. Release TEST button. The maximum output test voltage will be displayed, either 50 V or 25 V. 4. To toggle between the maximum output test voltages, press the TEST button. 5. Switch off instrument when the desired maximum test voltage is displayed. DET3TC, DET3TD, DET4TD, DET4TC and DET4TCR: 1. Press the 25V/50V button after selecting the measurement mode; the display will indicate the selected output voltage. Note: For ART mode, the output voltage is automatically set to 25 V and cannot be changed. Note: Some older versions of the DET3TC and DET3TD do not have the the 25V/50V button. The procedure for changing the output voltage is as per the DET3TA. Auto power down To extend battery life, the instrument will automatically switch off six minutes after the last operation. The instrument can be switched back on by turning the selector switch to the OFF position and then selecting the desired mode of operation. Display symbols (DET3TC, DET3TD, DET4TD, DET4TC and DET4TCR) Symbol Meaning Warning triangle. (Refer to user guide) Fuse blown. Battery indicator. ART Situation is suitable for making ART measurements [DET3TC, DET4TC and DET4TCR only]. 10

11 ART >100V Rp Rp Rc Rc I V V Situation is not suitable for making ART measurements [DET3TC, DET4TC and DET4TCR only]. Indicates that the ground noise voltage exceeds the instrument measurement capability (test is inhibited). Potential stake (P stake) is within range for accurate measurement. Potential stake (P stake) resistance exceeds range for accurate measurement. Current stake (C stake) is within range for accurate Measurement. Current stake (C Stake) resistance exceeds range for accurate measurement. Ground noise voltage is within range for accurate measurement of resistance. Ground noise voltage exceeds range for accurate measurement of resistance. ICLAMP is connected; VCLAMP is connected [DET3TC, DET4TC and DET4TCR only]. ICLAMP is not connected; VCLAMP is not connected [DET3TC, DET4TC and DET4TCR only]. I Sufficient ICLAMP current [DET3TC, DET4TC and DET4TCR only]. I Insufficient ICLAMP current [DET3TC, DET4TC and DET4TCR only]. Display symbols (DET3TA) Symbol Meaning Current stake (C Stake) resistance exceeds range for accurate measurement. Rc OR Fuse blown. Current stake (C stake) is within range for accurate measurement. Rc Instrument is performing pre-measurement checks. Rc 11

12 INSTRUMENT ILLUSTRATIONS DET3TA Multi-function analogue display Test lead connections (at rear) Rc OK Resistance measurement settings (2P and 3P) Spike button Selector switch Battery check setting voltage setting Test button Resistance scale Voltage scale Potential test spike resistance indicator Battery charge indicator Test lead connections (at rear of instrument) 12

13 DET3TC LCD display Test lead connections (at rear) Resistance measurement settings (2P and 3P and clamp) Selector switch Test button Voltage and current measurement settings Over/under range indicator Ruptured fuse indicator Warning refer to user manual Battery charge indicator Measuring range Clamp current indicator (OK or low) Potential probe resistance indicator (OK or high) Current probe resistance (OK or high) Ground noise voltage indicator (OK high) Test lead connections (at rear of instrument) 13

14 DET3TD LCD display Test lead connections (at rear) Resistance measurement settings (2P and 3P) Selector switch Test button Voltage measurement settings Over/under range indicator Ruptured fuse indicator Warning refer to user manual Battery charge indicator Measuring range Potential probe resistance indicator (OK or high) Current probe resistance (OK or high) Ground noise voltage indicator (OK high) Test lead connections (at rear of instrument) 14

15 DET4TD LCD display Test lead connections (at rear) Resistance measurement settings (2P, 3P and 4P) Selector switch Test button Voltage measurement settings Over/under range indicator Ruptured fuse indicator Warning refer to user manual Battery charge indicator Measuring range Potential probe resistance indicator (OK or high) Current probe resistance (OK or high) Ground noise voltage indicator (OK high) Test lead connections (at rear of instrument) 15

16 DET4TC LCD display Test lead connections (at rear) Resistance measurement settings Selector switch Test button Voltage and current measurement settings 25 V/ 50 V output voltage select button Backlight control button Output voltage indicator Ruptured fuse indicator Warning refer to user manual Battery charge indicator Over/under range indicator ART measurement indicator (Possible/Not possible Measuring range Potential probe resistance indicator (OK/Not OK) Current probe resistance (OK/Not OK) Ground noise voltage indicator (OK/Not OK) Clamp current/presence indicator (OK/Not OK) Test lead connections (at rear of instrument) 16

17 DET4TCR LCD display Test lead connections (at rear) Resistance measurement settings Selector switch Voltage and current measurement settings 25 V/ 50 V output voltage select button Output voltage indicator Over/under range indicator Test button Ruptured fuse indicator Backlight control button Warning refer to user manual Battery charge indicator ART measurement indicator (Possible/Not possible Measuring range Potential probe resistance indicator (OK/Not OK) Current probe resistance (OK/Not OK) Ground noise voltage indicator (OK/Not OK) Clamp current/presence indicator (OK/Not OK) Test lead connections (at rear of instrument) 17

18 BATTERY Battery status indication (DET3TC, DET3TD, DET4TD and DET4TC) The battery condition indicator is displayed whilst the instrument is switched on as shown: 100% battery charge remaining. 75% battery charge remaining. 50% battery charge remaining. 25% battery charge remaining. Some charge remaining, but instrument may auto power down at any time. 0% battery charge remaining instrument will auto power down. Battery status indication (DET4TCR) The battery condition indicator is displayed whilst the instrument is switched on as shown: Battery charge remaining. Partially charged batteries. Some change remaining, but instrument may auto power down at any time. 18

19 0% battery charge remaining instrument will auto power down. Note: If the DET4TCR s rechargeable batteries are replaced with alkaline batteries the instrument may automatically disable its charging circuit to prevent inadvertent charging of non-rechargeable cells. Follow the instructions Re-enabling the DET4TCR charger circuit to switch the charger back on when the NiMH cells are re-inserted. Battery status indication (DET3TA) 1. Set the rotary selector switch to the position. 2. Press and hold the TEST button. 3. The battery charge level will be indicated on the scaleplate as shown in Figure 2. Figure 2: battery charge level indicator 4. Release the TEST button. Battery charging (DET4TCR) When the battery status indicator shows a nearly empty or exhausted battery, the instrument may be recharged using the following procedure. Warning: Do not attempt to operate the instrument whilst the external AC/DC adaptor is connected. Warning: Do not attempt to recharge non-rechargeable (dry) cells in the DET4TCR. Doing so will result in instrument damage and may cause personal injury. Only use the cells recommended by Megger. Warning: Only use the external charging equipment provided by Megger. 1. To avoid the possibility of electric shock, switch instrument OFF and disconnect the instrument from any electrical circuits. 2. Move the slide on the terminal panel until the external AC/DC adaptor socket is exposed. 19

20 3. Remove the bung from the AC/DC adaptor socket. 4. Connect the AC/DC adaptor and switch on. 5. The charging cycle will commence and last approximately 15.5 hours. Follow the progress using the charge status LED as shown in Figure 3. NOTE: The instrument ambient temperature should be between +10ºC (50ºF) and +40ºC (105ºF) during the charging cycle. Figure 3: charge status LED progression Battery charging complete. Battery charging in progress. Defective/non-rechargeable cells detected or no batteries present. Defective/non-rechargeable cells detected or no batteries present. Charging terminated. Battery type DET3TA, DET3TC, DET3TD, DET4TD, DET4TC: DET4TCR: 8 x AA (LR6) 1.5V Alkaline. Megger part number: x AA (LR6) 1.2V NiMH 1800mAhr. Megger part number: Battery replacement Battery replacement Warning: Do not operate instrument with the battery cover removed. Warning: Incorrect battery cell polarity can cause electrolyte leakage, resulting in damage to the instrument. If the battery condition indicator does not show a full charge when battery cells are new, a cell may be reversed. Warning: To avoid damage by leaking electrolyte or deep discharge, do not leave cells fitted in an instrument, which will remain unused for extended periods of time. 1. To avoid the possibility of electric shock, switch instrument OFF and disconnect the instrument from any electrical circuits. 2. The rear cover must not be opened if the test leads are connected. 20

21 3. To avoid the possibility of electric shock, do not press the TEST button or touch the fuse when changing batteries. 4. To remove the rear cover, release the screw at the bottom of the cover and lift the cover upwards. 5. Remove the exhausted cells and dispose of in an appropriate manner. 6. Refit new batteries of the correct type observing the correct polarity as marked on the battery compartment. 7. Replace the instrument back cover and secure by tightening the retaining screw. Re-enabling the battery charging circuit on the DET4TCR If the DET4TCR s rechargeable batteries are replaced with alkaline batteries the instrument may automatically disable its charging circuit to prevent inadvertent charging of non-rechargeable cells. Follow the instructions below to switch the charger back on when the NiMH cells are re-inserted. 1. Switch the instrument on in to the 4P position while holding down the TEST button. The display will carry out a self test then briefly display the software version number. 2. The screen will show the letters tst release the TEST button. 3. The Charger Enable Screen will be shown (see below) 4. The state of the charger circuit is shown by either a cross or a tick being shown below the letters CHg. A cross indicates that the charger circuit is disabled. 5. If the cross is shown, re-enable the charger by pressing the TEST button once (the cross should change to a tick). 6. Switch the instrument OFF to save the new setting. 21

22 FUSE Fuse status indication (DET3TC, DET3TD, DET4TD, DET4TC and DET4TCR) The fuse blown status indicator is displayed whilst the instrument is switched on and performing a test as shown: Fuse blown. Fuse status indication (DET3TA) The fuse blown indication is given by the Rc LED when performing a test as shown: Rc Fuse blown. Fuse type All instruments: 500 ma (F), HBC (50 ka, 600 V), 32mm x 6mm. Fuse replacement Megger part number: Warning: Do not operate instrument with the battery cover removed. Warning: Fitting an incorrect fuse type will reduce operator safety. 1. To avoid the possibility of electric shock, switch instrument OFF and disconnect the instrument from any electrical circuits. 2. The rear cover must not be opened if the test leads are connected. 3. To remove the rear cover, release the screw at the bottom of the cover and lift the cover upwards. 4. To avoid the possibility of electric shock, do not press the TEST button when changing the fuse. 5. Remove the ruptured fuse. 6. Refit new fuse of the correct type. 7. Replace the instrument back cover and secure by tightening the retaining screw. 22

23 DESCRIPTION OF TESTS The description of tests contained within this user guide are instructions for the use of the DET family of instruments by competent persons. Suitable applications Where there is doubt about a particular application, reference should be made to the advice and guidance contained in the publication, Getting Down to Earth which is available from Megger, part number The DET range of instruments can be used in agricultural locations (as per IEC ). In these circumstances, the output voltage should be switched to 25 V in order to comply with the standard. Principle of operation (two-terminal resistance measurement) This technique is used to measure the resistance between two earth points, e.g. between an earth electrode of unknown resistance and a known good ground connection such as metallic underground pipework or building steelwork. The DET injects an a.c. current of known magnitude into the system under test and measures the voltage developed across it as shown in Figure 4. The system resistance is a simple ratio as per Ohm s Law, i.e. R=V/I. Figure 4: schematic for two-terminal resistance measurement C1 (E/X) P2 (P/S) C2 (C/H) The DET instruments automatically link the C1-P1 and C2-P2 terminals when a two-terminal test is selected. 23

24 Principle of operation (three-terminal resistance measurement) The classic fall of potential test is used to accurately measure the resistance of an earth electrode using auxiliary stakes driven into the soil, which form a circuit for the test current injection and voltage measurement as used for the two-terminal method. The DET injects an a.c. current of known magnitude into the system under test and measures the voltage developed across it as shown in Figure 5. The system resistance is a simple ratio as per Ohm s Law. In this case, the potential stake is moved by fixed increments in a straight line between the electrode under test and the current stake. At each location, the resistance is calculated as R=V/I. A graph of resistance versus potential stake position is plotted and the resistance of the electrode under test is taken to be the point at which the curve is flattest. Empirical testing has shown that with suitably positioned stakes, this method can be shortened by placing the potential stake at a distance of approximately 62% between the electrode under test and the current stake, i.e. at A = 0.62 x B. Figure 5: schematic for three-terminal resistance measurement with lead null C1 (E/X) P2 (P/S) C2 (C/H) In this diagram, the C1and P1 terminals are connected together at the electrode under test. This is the three-terminal with lead null configuration which is only applicable in four-terminal testers. This configuration allows the resistance of the P1 lead to the electrode under test to be nulled out. For three-terminal testers or when lead null is not required, only the P1 terminal (or X terminal on a three-terminal instrument) connects to the electrode under test. This is shown in Figure 6. 24

25 Figure 6: schematic for three-terminal resistance measurement without lead null Principle of operation (three-terminal resistance measurement using ART) The classic three-terminal test method has a disadvantage, namely that the electrode under test must be disconnected from the system it is supposed to protect in the event of a power system fault. The reason for this is that the injected test current will take all possible routes to ground and not all of it will necessarily flow through the electrode under test. In this case, the instrument will make a reading of the entire earthing network, not just the individual electrode. By using a current transducer (the Megger ICLAMP) to measure the current flowing through the electrode under test as a fraction of the total test current injected, the instrument can determine the individual resistance. This arrangement is shown in Figure 7. Figure 7: schematic for three-terminal resistance measurement using ART without lead null In this configuration, the injected test current I splits along two paths into I1 (flowing into the connected earthing system) and I2 (flowing into the electrode under test, i.e. I=I1+I2. The resistance 25

26 of the electrode under test is calculated as R=V/I2 or R=V/(I-I1). The current transducer (ICLAMP) measures I2 and feeds this value back to the instrument. Principle of operation (two-clamp stakeless resistance measurement) In this example, the electrode under test is connected to a network of other electrodes. It is either impractical or unsafe to disconnect an individual electrode for testing. Also, there might be insufficient space to perform a classic three-terminal resistance measurement. The stakeless test method using both VCLAMP and ICLAMP can be used to obtain a measurement for the electrode under test. A defined test voltage is injected into the system using the VCLAMP, inducing a current, I, to flow and be measured by the ICLAMP. The model shown in Figure 8 can be simplified to the resistance of the electrode under test, Rx and the resistance of the other electrodes in parallel, i.e. R1 R2 Rn. Therefore, the current induced by the test voltage is I=V/[R x +(R 1 R 2 R n )]. It follows that as the resistance of the other electrodes in parallel approaches zero, then the resistance measured, approaches the value of the electrode under test. Figure 8: schematic for two-clamp stakeless resistance measurement 26

27 Principle of operation (four-terminal resistivity measurement) The soil resitivity measurement works on a similar principle to the other measurements which use stakes: a current is injected around an outer loop and a voltage measured, shown in Figure 9. In this case, however, the measurement made by the instrument requires further conversion using a formula to derive the volumetric soil resistivity from the resistance value display. Figure 9: schematic for 4-terminal resistivity measurement For this test, the relative spacing and depth of the stakes is important. When configured as shown in Figure 9, the soil resistivity can be calculated from the resistance value, R, displayed on the instrument as = 2 A R. 27

28 Measurement of ground noise voltage (DET3TC, DET3TD, DET4TD, DET4TC and DET4TCR) 1. Ensure the rotary selector switch is in the OFF position. 2. Connect the instrument as shown in Figure 10. Figure 10: instrument connection for measuring ground noise voltage Potential stake Electrode under test DET3TD Potential stake Electrode under test DET4TD 28

29 Potential stake Electrode under test DET3TC Potential stake Electrode under test DET4TC DET4TCR 3. Set the rotary selector switch to the V position. 4. The ground noise voltage reading will be displayed as shown in Figure 11. Figure 11: example ground noise voltage reading (DET4TC / DET4TCR display shown) 29

30 Note: The instrument will display the warning triangle and an excessive noise voltage indicator above 40 V pk-pk (14 Vrms). The instrument will display the warning triangle and an over-range condition above 100 V. Measurement of ground noise voltage (DET3TA) 1. Ensure the rotary selector switch is in the OFF position. 2. Connect the instrument as shown in Figure 12. Figure 12: instrument connection for measuring ground noise voltage Potential stake Electrode under test 3. Set the rotary selector switch to the V position. 4. The ground noise voltage reading will be indicated on the scaleplate as shown in Figure 13. Figure 13: example ground noise voltage reading 30

31 Two-terminal resistance measurement (DET3TC, DET3TD, DET4TD, DET4TC and DET4TCR) 1. Ensure the rotary selector switch is in the OFF position. 2. Connect the instrument as shown in Figure 14. Figure 14: instrument connection for measuring two-terminal resistance Metallic interconect Electrode under test DET3TD Metallic interconnect Electrode under test DET4TD 31

32 Metallic interconnect Electrode under test DET3TC Metallic interconnect Electrode under test DET4TC DET4TCR 3. Set the rotary selector switch to the 2P position. 4. Select the desired test voltage using the 25V/50V button. 5. Press and release the TEST button [by holding the TEST button, the resistance measurement will be continually updated]. 6. The instrument will perform pre-measurement check, the status of which will be indicated on the display. 7. The two-terminal resistance reading will be displayed as shown in Figure

33 Figure 15: example two-terminal resistance reading (DET4TC / DET4TCR display shown) Note: The test voltage used to make the two-terminal resistance reading is a.c. and may not be suitable for continuity testing according to some local regulations. The instrument will display the warning triangle and an excessive noise voltage indicator if the ground noise voltage is above 40 V pk-pk (14 Vrms). The instrument will display the warning triangle and a voltage over-range condition if the ground noise voltage is above 100 V no resistance reading is possible under these conditions. 33

34 Two-terminal resistance measurement (DET3TA) 1. Ensure the rotary selector switch is in the OFF position. 2. Select the desired test voltage using the procedure in the section on General Operating Instructions. 3. Connect the instrument as shown in Figure 16. Figure 16: instrument connection for measuring two-terminal resistance Metallic interconnect Electrode under test 4. Set the rotary selector switch to the 2P position. 5. The ground noise voltage will be indicated on the scale plate as shown in Figure 17. Figure 17: ground noise voltage indication 6. If the ground noise voltage is less than 40 V pk-pk (14 V rms), press and hold the TEST button. [Testing will be inhibited if the ground noise voltage exceeds 40 V pk-pk.] 7. The Rc LED will flash to indicate that the instrument is carrying out pre-measurement checks. 34

35 8. If the Rc LED does not illuminate following the pre-measurement checks, this indicates that the instrument fuse has ruptured. 9. If the Rc LED illuminates solidly following the pre-measurement checks, this indicates that a two-terminal measurement can be made. 10. The two-terminal resistance reading will be indicated on the scaleplate as shown in Figure 18. Figure 18: example two-terminal resistance reading Note: The test voltage used to make the two-terminal resistance reading is a.c. and may not be suitable for continuity testing according to some local regulations. No resistance reading is possible if the ground noise voltage exceeds 100 V. 35

36 Three-terminal resistance measurement (DET3TC, DET3TD, DET4TD, DET4TC and DET4TCR) 1. Ensure the rotary selector switch is in the OFF position. 2. Connect the instrument as shown in Figure 19. Figure 19: instrument connection for measuring three-terminal resistance Electrode under test Current stake Potential stake DET3TD Electrode under test Current stake Potential stake DET4TD 36

37 Electrode under test Current stake Potential stake DET3TC Electrode under test Current stake Potential stake DET4TC DET4TCR 3. Set the rotary selector switch to the 3P position. 4. Select the desired test voltage using the 25V/50V button. 5. Press and release the TEST button [by holding the TEST button, the resistance measurement will be continually updated]. 6. The instrument will perform pre-measurement check, the status of which will be indicated on the display. 7. The three-terminal resistance reading will be displayed as shown in Figure

38 Figure 20: example three-terminal resistance reading (DET4TC / DET4TCR display shown) Note: The instrument will display the warning triangle and an excessive noise voltage indicator if the ground noise voltage is above 40 V pk-pk (14 Vrms). The instrument will display the warning triangle and a voltage over-range condition if the ground noise voltage is above 100 V no resistance reading is possible under this condition. 38

39 Three-terminal resistance measurement (DET3TA) 1. Ensure the rotary selector switch is in the OFF position. 2. Select the desired test voltage using the procedure in the section on General Operating Instructions. 3. Connect the instrument as shown in Figure 21. Figure 21: instrument connection for measuring three-terminal resistance Electrode under test Current stake Potential stake 4. Set the rotary selector switch to the 3P position. 5. The ground noise voltage will be indicated on the scaleplate as shown in Figure 22. Figure 22: ground noise voltage indication 6. If the ground noise voltage is less than 40Vpk-pk (14Vrms), press and hold the Rp button. [Testing will be inhibited if the ground noise voltage exceeds 40Vpk-pk.] 7. The P stake resistance will be indicated on the scaleplate: the needle will move into the green region (Figure 23) if the P stake resistance is within limits for an accurate measurement and into the red region (Figure 24) if the P stake resistance exceeds the limits for an accurate measurement. 39

40 Figure 23: P stake resistance OK (green region) Figure 24: P stake resistance not OK (red region) 8. If the P stake resistance is acceptable (needle in the green region of the scaleplate), release the Rp button. 9. Press and hold the TEST button. 10. The Rc LED will flash to indicate that the instrument is carrying out pre-measurement checks. 11. If the Rc LED does not illuminate following the pre-measurement checks, this indicates that the C stake resistance exceeds the limits for an accurate measurement or that the instrument fuse has ruptured. 12. If the Rc LED illuminates solidly following the pre-measurement checks, this indicates that a three-terminal measurement can be made. 13. The three-terminal resistance reading will be indicated on the scaleplate as shown in Figure

41 Figure 25: example three-terminal resistance reading Note: No resistance reading is possible if the ground noise voltage exceeds 100 V. 41

42 Three-terminal resistance measurement with lead null (DET4TD, DET4TC and DET4TCR) In certain circumstances, the resistance of the test lead connecting to the electrode under test may itself form a significant part of the measurement electrode resistance. This effect can be eliminated using the lead-null technique described in this section. 1. Ensure the rotary selector switch is in the OFF position. 2. Connect the instrument as shown in Figure 26. Figure 26: instrument connection for measuring three-terminal resistance with lead-null Electrode under test Current stake Potential stake DET4TD Electrode under test Current stake Potential stake DET4TC DET4TCR 3. Set the rotary selector switch to the 4P position. 4. Select the desired test voltage using the 25 V/50 V button. 5. Press and release the TEST button [by holding the TEST button, the resistance measurement will be continually updated]. 42

43 6. The instrument will perform pre-measurement check, the status of which will be indicated on the display. 7. The three-terminal resistance with lead-null reading will be displayed as shown in Figure 27. Figure 27: example three-terminal resistance with lead-null reading (DET4TC / DET4TCR display shown) Note: The instrument will display the warning triangle and an excessive noise voltage indicator if the ground noise voltage is above 40 V pk-pk (14 Vrms). The instrument will display the warning triangle and a voltage over-range condition if the ground noise voltage is above 100 V no resistance reading is possible under this condition. 43

44 Four-terminal resistivity measurement (DET4TD, DET4TC and DET4TCR) The DET4TD, DET4TC and DET4TCR can be used to make soil resistivity measurements. The resistivity value can be derived from the four-terminal resistance reading made by the instrument and the particular separation and depth of the stakes. 1. Ensure the rotary selector switch is in the OFF position. 2. Connect the instrument as shown in Figure 28. Figure 28: instrument connection for measuring four-terminal resistance DET4TD 3. Set the rotary selector switch to the 4P position. 4. Select the desired test voltage using the 25 V/50 V button. DET4TC DET4TCR 5. Press and release the TEST button [by holding the TEST button, the resistance measurement will be continually updated]. 44

45 6. The instrument will perform pre-measurement check, the status of which will be indicated on the display. 7. The four-terminal resistance reading will be displayed as shown in Figure 29. Figure 29: example four-terminal resistance reading (DET4TC / DET4TCR display shown) 8. A soil resistivity value can be derived from the resistance reading and the stake geometry. Note: The instrument will display the warning triangle and an excessive noise voltage indicator if the ground noise voltage is above 40 V pk-pk (14 Vrms). The instrument will display the warning triangle and a voltage over-range condition if the ground noise voltage is above 100 V no resistance reading is possible under this condition. 45

46 Measurement of ground current (DET3TC, DET4TC and DET4TCR) Before measuring ground current, please follow the procedure contained in the section on ICLAMP calibration. 1. Ensure the rotary selector switch is in the OFF position. 2. Connect the instrument as shown in Figure 30. Figure 30: instrument connection for measuring ground current Installation earthing conductor ICLAMP Electrode under test DET3TC Installation earthing conductor ICLAMP Electrode under test DET4TCR DET4TC 3. Close the ICLAMP around the conductor under test. 4. Set the rotary selector switch to the A position. 5. The ground current flowing in the conductor will be displayed as shown in Figure

47 Figure 31: example ground current reading (DET4TC / DET4TCR display shown) Note: The instrument will display the warning triangle above 2 A no ART testing is possible under this condition. The instrument will display the warning triangle and an over-range condition above 20 A no ART testing is possible under this condition. 47

48 Three-terminal resistance measurement using ART (DET3TC, DET4TC and DET4TCR) Before making a measurement using ART, please follow the procedure contained in the section on ICLAMP calibration. 1. Ensure the rotary selector switch is in the OFF position. 2. Connect the instrument as shown in Figure 32. Figure 32: instrument connection for measuring three-terminal resistance using ART Electrode under test Current stake Potential stake DET3TC Electrode under test Current stake Potential stake DET4TC DET4TCR 3. Close the ICLAMP around the conductor under test. 4. Set the rotary selector switch to the 3P position. 5. Press and release the TEST button [by holding the TEST button, the resistance measurement will be continually updated]. 48

49 6. The instrument will perform pre-measurement checks, the status of which will be indicated on the display. 7. The three-terminal resistance reading using ART will be displayed as shown in Figure 33. Figure 33: example three-terminal resistance reading using ART (DET4TC / DET4TCR display shown) 8. Under certain circumstances, the instrument may display a noise warning as shown: This means that interference has been detected which may impair the accuracy of the measurement. In particular, the reading could be lower than the actual resistance. The resistance of the electrode or system must be verified by an alternative method. Note: The instrument will display the warning triangle and an excessive noise voltage indicator if the ground noise voltage is above 40 V pk-pk (14 Vrms). The instrument will display the warning triangle and a voltage over-range condition if the ground noise voltage is above 100 V no resistance reading is possible under this condition. The instrument will display the warning triangle above 2 A no ART testing is possible under this condition. 49

50 The instrument will display the warning triangle and an over-range condition above 20 A no ART testing is possible under this condition. Ensure that the ICLAMP jaw mating surfaces are free of dust and contamination and that they contact completely when the ICLAMP is closed. Currents carried by conductors in close proximity to the ICLAMP may affect calibration and reduce the accuracy of measurements made. 50

51 Three-terminal resistance measurement with lead-null using ART (DET4TC and DET4TCR) In certain circumstances, the resistance of the test leads connecting to the electrode under test may itself form a significant part of the measurement electrode resistance. This effect can be eliminated using the lead-null technique described in this section. Before making a measurement using ART, please follow the procedure contained in the section on ICLAMP calibration. 1. Ensure the rotary selector switch is in the OFF position. 2. Connect the instrument as shown in Figure 34. Figure 34: instrument connection for measuring three-terminal resistance with lead-null using ART Electrode under test Current stake Potential stake DET4TC DET4TCR 3. Close the ICLAMP around the conductor under test. 4. Set the rotary selector switch to the 4P position. 5. Press and release the TEST button [by holding the TEST button, the resistance measurement will be continually updated]. 6. The instrument will perform pre-measurement checks, the status of which will be indicated on the display. 7. The three-terminal resistance reading with lead-null using ART will be displayed as shown in Figure

52 Figure 35: example three-terminal resistance reading with lead-null using ART (DET4TC / DET4TCR display shown) 8. Under certain circumstances, the instrument may display a noise warning as shown: This means that interference has been detected which may impair the accuracy of the measurement. In particular, the reading could be lower than the actual resistance. The resistance of the electrode or system must be verified by an alternative method. Note: The instrument will display the warning triangle and an excessive noise voltage indicator if the ground noise voltage is above 40 V pk-pk (14 Vrms). The instrument will display the warning triangle and a voltage over-range condition if the ground noise voltage is above 100 V no resistance reading is possible under this condition. The instrument will display the warning triangle above 2 A no ART testing is possible under this condition. The instrument will display the warning triangle and an over-range condition above 20 A no ART testing is possible under this condition. Ensure that the ICLAMP jaw mating surfaces are free of dust and contamination and that they contact completely when the ICLAMP is closed. Currents carried by conductors in close proximity to the ICLAMP may affect calibration and reduce the accuracy of measurements made. 52

53 Two-clamp stakeless measurement (DET4TC and DET4TCR) Before making a stakeless measurement, please follow the procedures contained in the sections on ICLAMP calibration. 1. Ensure the rotary selector switch is in the OFF position. 2. Connect the instrument as shown in Figure 36. Figure 36: instrument connection for two-clamp stakeless measurement >100mm VCLAMP Electrode under test ICLAMP DET4TC DET4TCR 3. Close the ICLAMP around the conductor under test. Ensure the arrow on the side of the jaw is pointing in the same direction as the arrow on the VCLAMP. 4. Close the VCLAMP around the conductor under test. Ensure the arrow on the side of the jaw is pointing in the same direction as the arrow on the ICLAMP. 5. Ensure a minimum separation of 100mm between the ICLAMP and VCLAMP. 6. Set the rotary selector switch to the position. 7. Press and release the TEST button [by holding the TEST button, the resistance measurement will be continually updated]. 8. The instrument will perform pre-measurement checks, the status of which will be indicated on the display. 9. The stakeless resistance reading will be displayed as shown in Figure

54 Figure 37: example resistance reading using two-clamp stakeless method 10. Under certain circumstances, the instrument may display a noise warning as shown: This means that interference has been detected which may impair the accuracy of the measurement. In particular, the reading could be lower than the actual resistance. The resistance of the electrode or system must be verified by an alternative method. Note: The instrument will display the warning triangle above 2 A no Stakeless testing is possible under this condition. The instrument will display the warning triangle and an over-range condition above 20 A no Stakeless testing is possible under this condition. Ensure that the VCLAMP and ICLAMP jaw mating surfaces are free of dust and contamination and that they contact completely when the VCLAMP and ICLAMP are closed. Currents carried by conductors in close proximity to the VCLAMP and ICLAMP may affect calibration and reduce the accuracy of measurements made. If the VCLAMP opens at any time after the TEST button is pressed, the test will be aborted. 54

55 ICLAMP calibration (DET3TC, DET4TC and DET4TCR) The ICLAMP should be calibrated once at each test site to take into account the effects of transportation, temperature and humidity on the ICLAMP. 1. Ensure the rotary selector switch is in the OFF position. 2. Connect the instrument as shown in Figure Ensure that the ICLAMP is not clamped around a conductor. 4. Press and hold the TEST button and switch instrument ON to the A setting using the selector switch. 5. Release the TEST button. Figure 38: ICLAMP zero calibration ICLAMP DET4TC DET4TCR ICLAMP DET3TC 6. Press and hold the TEST button until a 0 reading is obtained on the display. 7. Connect the C1 and C2 terminals together using the calibration lead supplied with the ICLAMP. [X and C terminals for DET3TC] 8. Close the ICLAMP around the calibration lead, which connects the C1 and C2 terminals as shown in Figure 39. [X and C terminals for DET3TC] 55

56 Figure 39: ICLAMP 100% calibration ICLAMP DET4TC DET4TCR ICLAMP DET3TC 9. Press and hold the TEST button until a 100 reading is obtained on the display. 10. Switch the instrument OFF using the selector switch. 11. The instrument is now calibrated to the ICLAMP and the calibration stored in non-volatile memory. 56

57 OPERATION OF THE TWO-CLAMP CALIBRATION ADAPTOR 1. Ensure the rotary selector switch is in the OFF position. 2. Connect the instrument as shown. 3. Close the ICLAMP around one loop of the two-clamp calibration adaptor. 4. Close the VCLAMP around the other loop of the two-clamp calibration adaptor. 5. Ensure a minimum separation of 100mm between the ICLAMP and VCLAMP. 6. Set the rotary selector switch to the position. 7. Press and release the TEST button [by holding the TEST button, the resistance measurement will be continually updated]. 8. The instrument will perform pre-measurement checks, the status of which will be indicated on the display. 9. The two-clamp resistance reading will be displayed and should match the value written on the two-clamp calibration adaptor. Note: 1. Ensure that the ICLAMP and VCLAMP jaw mating surfaces are free of dust and contamination and that they contact completely when the units are closed. 57

58 2. Currents carried by conductors in close proximity to the ICLAMP may affect calibration and reduce the accuracy of measurements made. 58

59 OPERATION OF THE CALIBRATION ADAPTOR 1. Ensure the rotary selector switch is in the OFF position. 2. Connect the instrument as shown. CALIBRATION ADAPTOR 3. Set the rotary selector switch to the 2P, 3P or 4P position. 4. Press and release the TEST button [by holding the TEST button, the resistance measurement will be continually updated]. 5. The instrument will perform pre-measurement checks, the status of which will be indicated on the display. 6. The resistance reading will be displayed and should match the value written on the calibration adaptor. 59

60 PREVENTIVE INSTRUMENT MAINTENANCE 1. The DET series instruments require very little maintenance. 2. Test leads should be checked before use to ensure there is no damage. 3. Ensure batteries are removed if left unused for extended periods. 4. When necessary, the instrument can be cleaned with a damp cloth. 5. Do not use alcohol-based cleaners, as these may leave a residue. 60

61 TECHNICAL SPECIFICATION DET3Tx & DET4Tx General Specification Only values with tolerance or limits are guaranteed data. Parameters without tolerances are for information only. Ingress protection: IP54 C stake, P stake and Noise check: Automatic Noise rejection: 40 V pk to pk (14 V rms) 2-wire, 3-wire, 4-wire test: Yes, no shorting links required No disconnect testing (ART): Yes, with ICLAMP Stakeless measurement: Yes, with ICLAMP and VCLAMP Instrument output: Voltage: ±25 V or ±50 V at 128Hz Current: 4.5 ma or 0.4 5mA Ground current range with clamp: 0.5 ma to 19.9 A Ground current accuracy: 5% ±3 digits Ground voltage range: 0 to 100 Vac Ground voltage accuracy: 2% ±2 V Resistance range: 0.01 to 20 k (DET4TC and DET4TCR) 0.01 to 2 k (all other DET s) Resistance accuracy: 2P measurements: 2% ±3 digits 3P measurements: 2% ±3 digits 4P measurements: 2% ±3 digits ART measurements: 5% ±3 digits Stakeless measurements: 7% ±3 digits Maximum probe resistance: Rp limit: 100 k (5 0 V output voltage) Rc limit: 100 k (50 V output voltage) Limits reduced to 50 k for 25 V output voltage Limits reduced to 5 k for 0.01 resolution Display: 3½ digit high contrast liquid crystal, backlit Battery type: DET4TC - 8 off AA (LR6) dry cells DET4TCR 8 off AA (LR6) NiMH rechargeable cells Operating temperature range: -15 C to +55 C / 5 F to 131 F Storage temperature range: -40 C to +70 C / -40 F to 158 F Safety Complies with the requirements of EN V CAT IV between terminal pairs. EMC In accordance with IEC61326 including amendment No.1 Standards compliance Complies with the requirements of KEMA K85B Complies with the following parts of EN61557 Part 1 General requirements Part 5 Resistance to earth Dimensions: 203mm x 148mm x 78mm / 8in x 5.8in x 3in Weight: 1 kg / 2.2 lb 61

DET3TA, DET3TC, DET3TD and DET4TD Earth Ground Electrode Testers USER MANUAL

DET3TA, DET3TC, DET3TD and DET4TD Earth Ground Electrode Testers USER MANUAL M DET3TA, DET3TC, DET3TD and DET4TD Earth Ground Electrode Testers USER MANUAL GSAFETY WARNINGS Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed

More information

MIT300 Series Insulation and Continuity Testers

MIT300 Series Insulation and Continuity Testers MIT300_UG_en_V11.qxp 14/1/09 3:03 pm Page 1 M MIT300 Series Insulation and Continuity Testers Megger MIT300-EN MIT 300 EN Insulation Resistance Continuity Tester Megger MIT310A-EN MIT 310A EN Insulation

More information

This instrument is manufactured in the United Kingdom. The company reserves the right to change the specification or design without prior notice.

This instrument is manufactured in the United Kingdom. The company reserves the right to change the specification or design without prior notice. M Megger Limited Archcliffe Road, Dover Kent CT17 9EN England T +44 (0)1 304 502101 F +44 (0)1 304 207342 E uksales@megger.com Megger Z.A. Du Buisson de la Couldre 23 rue Eugène Henaff 78190 TRAPPES France

More information

BM kv Digital Insulation Tester USER MANUAL

BM kv Digital Insulation Tester USER MANUAL M BM5200 5 kv Digital Insulation Tester USER MANUAL CONTENTS Safety warnings...3 Symbols used on instrument...4 Cleaning...4 General description...5 Insulation resistance test modes...5 Automatic discharge...5

More information

MIT300 Series Insulation and Continuity testers USER MANUAL

MIT300 Series Insulation and Continuity testers USER MANUAL M MIT300 Series Insulation and Continuity testers USER MANUAL GSAFETY WARNINGS Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed during use.

More information

MIT300 Series Insulation and Continuity testers USER MANUAL

MIT300 Series Insulation and Continuity testers USER MANUAL M MIT300 Series Insulation and Continuity testers USER MANUAL GSAFETY WARNINGS Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed during use.

More information

BATTERY OPERATED DIGITAL MILLI-OHMMETER

BATTERY OPERATED DIGITAL MILLI-OHMMETER BATTERY OPERATED DIGITAL MILLI-OHMMETER C 1 P 1 P 2 C 2 MAX. DC20V MICROPROCESSOR CONTROLLED AC DC HOLD M A X M I N AUTO-HOLD Hz mv km ka ms DIGITAL MILLIOHM METER 2000 200.0 20.00 2000m Test Current Range

More information

1.Safe testing IMPORTANT:

1.Safe testing IMPORTANT: Electricity is dangerous and can cause injury and death. Always treat it with the greatest of respect and care. If you are not quite sure how to proceed, then stop, take advice from a qualified person.

More information

MIT300 Series Insulation and Continuity Testers USER MANUAL

MIT300 Series Insulation and Continuity Testers USER MANUAL M MIT300 Series Insulation and Continuity Testers USER MANUAL GSAFETY WARNINGS Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed during use.

More information

MAX. AC 600V HOLD V M H.V. LIVE CIRCUIT DIGITAL INSULATION TESTER DO NOT OPERATE IF LIT POWER DATA HOLD TEST ON / OFF 250V 500V 1000V OFF CAT.

MAX. AC 600V HOLD V M H.V. LIVE CIRCUIT DIGITAL INSULATION TESTER DO NOT OPERATE IF LIT POWER DATA HOLD TEST ON / OFF 250V 500V 1000V OFF CAT. INSULATION TESTER EARTH MAX. AC 600V LINE AC -+ HOLD V k M LIVE CIRCUIT DIGITAL INSULATION TESTER DO NOT OPERATE IF LIT M H.V. POWER DATA HOLD TEST ON / OFF 250V 500V 1000V ACV OFF 0 CAT.III 600V INSTRUCTION

More information

RCDT300 Series Residual Current Device testers USER MANUAL

RCDT300 Series Residual Current Device testers USER MANUAL M RCDT300 Series Residual Current Device testers USER MANUAL G SAFETY WARNINGS Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed during use.

More information

LRCD200 Series Combined Loop and RCD Tester USER MANUAL

LRCD200 Series Combined Loop and RCD Tester USER MANUAL M LRCD200 Series Combined Loop and RCD Tester USER MANUAL G SAFETY WARNINGS Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed during use.

More information

RISH Insu 10 Analog-Digital Insulation Tester

RISH Insu 10 Analog-Digital Insulation Tester User Manual RISH Insu 10 Analog-Digital Insulation Tester RISHABH INSTRUMENTS PT. LTD. F-31, M.I.D.C., Satpur, Nashik 422 007, India. Tel.: +91 253 2202196, 2202192, Fax :+ 91 253 2351064,2202302, Email

More information

KEWTECH. KT56 digital multi function tester. Instruction manual

KEWTECH. KT56 digital multi function tester. Instruction manual KEWTECH KT56 digital multi function tester Instruction manual Contents 1 Safety Notice 1 2 Features and Principles of Measurement 3 3 Introduction 6 4 Specifications 7 5 Instrument layout 9 6 Operating

More information

DLRO10HDX 10 Amp Digital Low Resistance

DLRO10HDX 10 Amp Digital Low Resistance 10 Amp Digital Low Resistance NEW Onboard memory storage for test results up to 200 records (HDX only) Download to PowerDB NEW interchangeable test lead terminations High or low output power selection

More information

MEGGER BM15/MJ15 MEGGER. Insulation Testers. User Guide. MeterCenter (800)

MEGGER BM15/MJ15 MEGGER. Insulation Testers. User Guide. MeterCenter (800) MEGGER BM15/MJ15 Insulation Testers User Guide MEGGER MeterCenter (800) 230-6008 Contents Guide de l utilisateur - p.14 Gebrauchsanleitung - s.26 Guía del usuario - p.38 Safety Warnings 3 General Description

More information

PAT120, PAT150 and PAT150R

PAT120, PAT150 and PAT150R PAT120, PAT150 and PAT150R Simple tick or cross, pass or fail indication plus measurement Battery powered with rechargeable options Safe 250 V insulation and leakage test for surge-protected and IT equipment

More information

SafetyPAT Plus A B P/N:

SafetyPAT Plus A B P/N: SafetyPAT Plus A B C P/N:110401103864 Test Instrument Solutions SafetyPat Plus Instructions A.Features SafetyPat Plus The SafetyPat Plus is a handheld battery powered unit suitable for carrying out electrical

More information

KD1E Range Potential Indicators

KD1E Range Potential Indicators KD1E Range Potential Indicators Operating Instructions 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Limited Warranty & Limitation

More information

5 kv and 10 kv Insulation Resistance

5 kv and 10 kv Insulation Resistance S1-552/2 and S1-1052/2 5 kv and 10 kv Insulation Resistance Testers n CAT IV 600 V n Mains or battery powered n Digital/analogue backlit display n Variable test voltage from 50 to 5000 or 10,000 V n Automatic

More information

DLRO 10 and DLRO 10X. Digital Microhmmeter. DLRO 10 and DLRO 10X Digital Microhmmeter. NEW interchangeable test lead terminations

DLRO 10 and DLRO 10X. Digital Microhmmeter. DLRO 10 and DLRO 10X Digital Microhmmeter. NEW interchangeable test lead terminations DLRO 10 and DLRO 10X DESCRIPTION NEW interchangeable test lead terminations Auto current reversal cancels standing emfs Protected to 600 V Automatically detects continuity in potential and current connections

More information

S1-568, S1-1068, S1-1568

S1-568, S1-1068, S1-1568 S1-568, S1-1068, S1-1568 Resistance range up to 35 TΩ 8 ma noise rejection plus 4 filters Safety up to CATIV 1000V to 4000 m Rapid charge Li-ion battery meets IEC62133 Operate with flat battery from an

More information

Rental Industry Safety Tester Safe Check 5s

Rental Industry Safety Tester Safe Check 5s Rental Industry Safety Tester Safe Check 5s Feb 2006 2006 Clare Instruments Inc. Issue 2.0 Firmware Version : 1.2a Limited Warranty & Limitation of Liability Clare Instruments Inc, guarantees this product

More information

INSTRUCTION MANUAL MARTINDALE CM52 CLAMP METER. ELECTRIC Trusted by professionals. Other products from Martindale:

INSTRUCTION MANUAL MARTINDALE CM52 CLAMP METER. ELECTRIC Trusted by professionals. Other products from Martindale: Other products from Martindale: 18th Edition Testers All-in-one s Calibration Equipment Continuity Testers Electrician s Kits Full Calibration & Repair Service Fuse Finders Digital Clamp Meters Digital

More information

RS-3 PRO RS-1007 PRO. CAT IV Analog Clamp meter Series. Users Manual. For detailed specifications and ordering info go to

RS-3 PRO RS-1007 PRO. CAT IV Analog Clamp meter Series. Users Manual. For detailed specifications and ordering info go to RS-3 PRO RS-1007 PRO CAT IV Analog Clamp meter Series Users Manual For detailed specifications and ordering info go to www.testequipmentdepot.com RS-3 PRO RS-1007 PRO CAT IV Analog Clampmeter Series English

More information

Users Manual. Accessories Motor and Phase Rotation Indicator ships with the following items: 3 test leads 3 test probes 3 alligator clips 9 V battery

Users Manual. Accessories Motor and Phase Rotation Indicator ships with the following items: 3 test leads 3 test probes 3 alligator clips 9 V battery MS5900 Users Manual Table of Contents Introduction Motor and Phase Rotation Indicator is a handheld, battery-operated instrument designed to detect the rotary field of three-phase systems and determine

More information

OPERATING INSTRUCTION

OPERATING INSTRUCTION 11/05 Form #273 OPERATING INSTRUCTION MODEL 4105 Disital Earth Resistance Tester 2150 joshua's Path, Suite 302, Hauppauge, NY 11788 Phone : 1-800-645-5398 or 1-639-231-7050 Fax : 1-639-434-3128 E-mail

More information

EZYPAT / EZYPAT+ / SMARTPAT PORTABLE APPLIANCE TESTER INSTRUCTION MANUAL

EZYPAT / EZYPAT+ / SMARTPAT PORTABLE APPLIANCE TESTER INSTRUCTION MANUAL EZYPAT / EZYPAT+ / SMARTPAT PORTABLE APPLIANCE TESTER INSTRUCTION MANUAL CONTENTS 1. Safe testing... 2 2. Product summary and explanation... 5 2.1 Product summary... 5 2.2 Test Function... 5 2.3 Features...

More information

MIT515, MIT525, MIT1025, MIT1525

MIT515, MIT525, MIT1025, MIT1525 MIT515, MIT525, MIT1025, MIT1525 Measures up to 30 TΩ Safety rated up to CAT IV 1000 V to 3000 m Unique dual-case design - additional user protection Operates from battery or a.c. mains supply Rapid charge

More information

R&S RT-ZC02 R&S RT-ZC03 AC/DC Current Probe User Manual

R&S RT-ZC02 R&S RT-ZC03 AC/DC Current Probe User Manual R&S RT-ZC02 R&S RT-ZC03 AC/DC Current Probe User Manual / User Manual Content 1 Introduction 3 2 Safety 3 3 Specifications RT-ZC03 6 Specifications RT-ZC02 7 4 Operating Instructions RT-ZC03 8 Operating

More information

DLRO10HD 10 A Digital Low Resistance Ohmmeter USER GUIDE

DLRO10HD 10 A Digital Low Resistance Ohmmeter USER GUIDE mm DLRO10HD 10 A Digital Low Resistance Ohmmeter USER GUIDE 1 G SAFETY WARNINGS These safety warnings must be read and understood before the instrument is used. Whenever possible, circuits should be de-energised

More information

USER MANUAL. 200A AC Mini Clamp Meter. Model MA130. Please visit for user manual translations

USER MANUAL. 200A AC Mini Clamp Meter. Model MA130. Please visit   for user manual translations USER MANUAL 200A AC Mini Clamp Meter Model MA130 Please visit www.extech.com for user manual translations Introduction Thank you for selecting the Extech Instruments 200A AC Mini Clamp Meter. The MA130

More information

Instruction Manual. Model 310 Digital Milli-Ohm Meter

Instruction Manual. Model 310 Digital Milli-Ohm Meter Instruction Manual Model 310 Digital Milli-Ohm Meter DESCRIPTION PAGE SAFETY RULES... 01 GENERAL DESCRIPTION... 02-03 FRONT PANEL LAYOUT... 04 PREPARATION FOR USE... 05 PRELIMINARY CHECKS... 05 PRECAUTIONS...

More information

Mini Multimeter with Non-Contact Voltage Detector (NCV)

Mini Multimeter with Non-Contact Voltage Detector (NCV) Owner s Manual Mini Multimeter with Non-Contact Voltage Detector (NCV) Model No. 82314 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product.

More information

I I e k ill L ill. INDUSTRIAL DIGITAL EARTH LEAKAGE CIRCUIT BREAKER and 3 PHASE ROTATION TESTER BESANTEK BST-ELC01 INSTRUCTION MANUAL

I I e k ill L ill. INDUSTRIAL DIGITAL EARTH LEAKAGE CIRCUIT BREAKER and 3 PHASE ROTATION TESTER BESANTEK BST-ELC01 INSTRUCTION MANUAL = = = = - - - BESANTEK - - BST-ELC1 INDUSTRIAL DIGITAL EARTH LEAKAGE CIRCUIT BREAKER and 3 PHASE ROTATION TESTER EARTH DIGITAL INDUST RIAL ELCB HAS OT ATl ONTE O C, 1:. : ==== === ;... P E R STE R ==!

More information

DIGITAL RCD(ELCB) TESTER

DIGITAL RCD(ELCB) TESTER INSTRUCTION MANUAL DIGITAL RCD(ELCB) TESTER KEW 5410 R KYORITSU ELECTRICAL INSTRUMENTS WORKS, LTD. Contents 1. Safety Warnings.... 1 2. Procedure of removing Cover. 3 2-1 Method of removing the Cover.

More information

ANALOGUE INSULATION-CONTINUITY and VOLTAGE METER

ANALOGUE INSULATION-CONTINUITY and VOLTAGE METER 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com BST-IT26 ANALOGUE INSULATION-CONTINUITY and VOLTAGE METER INSTRUCTION MANUAL Index

More information

Non-Contact Phase Rotation Tester

Non-Contact Phase Rotation Tester USER GUIDE Non-Contact Phase Rotation Tester Model PRT00 Model PRT00-M Introduction Congratulations on your purchase of this Extech Meter. The PRT00 is used to quickly and accurately determine three phase

More information

Model Insulation Tester / Megohmmeter. User Manual

Model Insulation Tester / Megohmmeter. User Manual Model 380363 Insulation Tester / Megohmmeter User Manual Introduction Congratulations on your purchase of Extech s Insulation Tester/Megohmmeter. The Model 380363 provides three test ranges plus continuity

More information

l The Battery Tester is designed for measuring the l AC four-terminal method to measure the internal

l The Battery Tester is designed for measuring the l AC four-terminal method to measure the internal Certificate of Calibration We hereby certify that this product has been calibrated and found to be in accordance with the applicable SPECIFICATIONS and STANDARDS. Accuracies of the standard equipment used

More information

51 & 52 Series II. Users Manual. Thermometer. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

51 & 52 Series II. Users Manual. Thermometer. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot. 51 & 52 Series II Thermometer Test Equipment Depot - 800.517.8431-99 Washington Street Melrose, MA 02176 - TestEquipmentDepot.com Users Manual English September 1999 Rev.2, 11/10 1999-2010 Fluke Corporation,

More information

Clamp Earth Tester MET-2. Instruction Manual

Clamp Earth Tester MET-2. Instruction Manual Clamp Earth Tester MET-2 Instruction Manual Thank you very much for selecting our clamp earth tester. This model is complex instrument and employs a very reliable mechanical/electronic design. Before you

More information

LH41A. User Manual. Clamp On Ammeter. For detailed specifications and ordering info go to

LH41A. User Manual. Clamp On Ammeter. For detailed specifications and ordering info go to LH41A Clamp On Ammeter User Manual For detailed specifications and ordering info go to www.testequipmentdepot.com LH41A Clamp On Ammeter Users Manual English April 2007, Rev.2 2007 Amprobe Test Tools.

More information

INSTRUCTION MANUAL CM69 TRMS AC EARTH LEAKAGE CLAMP METER. 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT

INSTRUCTION MANUAL CM69 TRMS AC EARTH LEAKAGE CLAMP METER. 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT CM69 TRMS AC EARTH LEAKAGE CLAMP METER INSTRUCTION MANUAL 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT These instructions contain both information and warnings

More information

Instruction Manual. 99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Model 308A Digital Insulation & Continuity Meter

Instruction Manual. 99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Model 308A Digital Insulation & Continuity Meter Instruction Manual 99 Washington Street Melrose, MA 02176 Fax 781-665-0780 TestEquipmentDepot.com Model 308A Digital Insulation & Continuity Meter INDEX PAGE INSTRUMENT LAYOUT... 1 INTRODUCTION... 2 SAFETY

More information

INSTRUCTION MANUAL CM95/ CM100 TRUE RMS FLEXIBLE CLAMP METER. 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT

INSTRUCTION MANUAL CM95/ CM100 TRUE RMS FLEXIBLE CLAMP METER. 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT CM95/ CM100 TRUE RMS FLEXIBLE CLAMP METER INSTRUCTION MANUAL 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT These instructions contain both information and warnings

More information

MARTINDALE INSTRUCTIONS ELITE FUSE FINDER KIT ELECTRIC. Trusted by professionals. 4.4 Storage Conditions

MARTINDALE INSTRUCTIONS ELITE FUSE FINDER KIT ELECTRIC. Trusted by professionals. 4.4 Storage Conditions 4.4 Storage Conditions The FD650/R and FD500/T or FD600/T should be kept in warm dry conditions away from direct sources of heat or sunlight, with the battery removed and in such a manner as to preserve

More information

True RMS Autoranging Multimeter

True RMS Autoranging Multimeter Owner's Manual True RMS Autoranging Multimeter Model No. 73754 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation Maintenance

More information

Table of Contents Title Page No.

Table of Contents Title Page No. Table of Contents Title Page No. INTRODUCTION 1 SAFETY PRECAUTIONS / WARNINGS 2 CONTROLS AND INDICATORS 4 PREPARATION AND CAUTION BEFORE USE 5 TESTING PROCEDURES 6 A. AC/DC VOLTAGE MEASUREMENT 6 B. RESISTANCE

More information

USER MANUAL. 10KV Digital High Voltage Insulation Tester. Model MG500. Additional User Manual Translations available at

USER MANUAL. 10KV Digital High Voltage Insulation Tester. Model MG500. Additional User Manual Translations available at USER MANUAL 10KV Digital High Voltage Insulation Tester Model MG500 Additional User Manual Translations available at www.extech.com Introduction Thank you for selecting the Extech Instruments Model MG500.

More information

MARTINDALE MARTINDALE IN2001/IN2003 INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL IN2001/IN2003 INSULATION & CONTINUITY TESTERS

MARTINDALE MARTINDALE IN2001/IN2003 INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL IN2001/IN2003 INSULATION & CONTINUITY TESTERS MARTINDALE ELECTRIC Martindale Electric Company LTD Metrohm House Penfold Trading Estate Imperial Way Watford Herts WD24 4YY T: 01923 441717 F: 01923 446900 Email: sales@martindale-electric.co.uk web:

More information

INSTRUCTION MANUAL IDM93N DIGITAL MULTIMETER EN FR IT DE

INSTRUCTION MANUAL IDM93N DIGITAL MULTIMETER EN FR IT DE INSTRUCTION MANUAL IDM93N DIGITAL MULTIMETER EN FR IT DE ISO-TECH IDM93N DIGITAL MULTIMETER INSTRUCTION MANUAL 1 2 WARNING THE SERVICING INSTRUCTIONS DESCRIBED WITHIN THIS MANUAL ARE FOR USE BY QUALIFIED

More information

POWERED BY KT71 / Portable Appliance Tester. Instruction Manual

POWERED BY KT71 / Portable Appliance Tester. Instruction Manual KT71 / Portable Appliance Tester POWERED BY Instruction Manual CONTENTS 1. Safe testing 1 2. Procedure of removing cover.. 3 2.1 Method of removing the cover... 3 2.2 Method of storing the cover... 3 3.

More information

Table of Contents. Title Page UT501/UT502 OPERATING MANUAL. Introduction. Unpacking the Meter. Safety Information. International Electrical Symbols

Table of Contents. Title Page UT501/UT502 OPERATING MANUAL. Introduction. Unpacking the Meter. Safety Information. International Electrical Symbols Table of Contents Title Page Introduction Unpacking the Meter Safety Information International Electrical Symbols The Meter Structure Key Functions Rotary Switch Measurement Operation A. Measuring Voltages

More information

MOdel No: MM19.V3 WARNING CAUTION 1. SAFETY INSTRUCTIONS

MOdel No: MM19.V3 WARNING CAUTION 1. SAFETY INSTRUCTIONS Instructions for: Digital Multimeter - 6 Function MOdel No: MM19.V3 Thank you for purchasing a Sealey product. Manufactured to a high standard this product will, if used according to these instructions

More information

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2 1 27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2 STX2401-C STX2401-T FEATURES 0843-CPR-0213 14 Elmdene International Ltd Tel: +44(0)23 9269 6638 3 Keel Close, Interchange Park, Fax:

More information

User Guide. Model Insulation Tester / Megohmmeter. Introduction

User Guide. Model Insulation Tester / Megohmmeter. Introduction User Guide Model 380363 Insulation Tester / Megohmmeter Introduction Congratulations on your purchase of Extech s Insulation Tester/Megohmmeter. The Model 380363 provides three test ranges plus continuity

More information

OPERATING INSTRUCTION

OPERATING INSTRUCTION 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com 8/05 Form #270 OPERATING INSTRUCTION MODEL 3005 DIGITAL INSULATION-CONTINUITY TESTER

More information

OPERATING MANUAL EARTH RESISTANCE METER MRU-20

OPERATING MANUAL EARTH RESISTANCE METER MRU-20 OPERATING MANUAL EARTH RESISTANCE METER MRU-20 SONEL SA ul. Wokulskiego 11 58-100 Świdnica Version 3.0 18/06/2014 The MRU-20 meter is a modern, easy and safe measuring device. Please acquaint yourself

More information

Major MEGGER Insulation Testers MJ159, MJ160, MJ359, MJ459, MJ559. User Guide MEGGER

Major MEGGER Insulation Testers MJ159, MJ160, MJ359, MJ459, MJ559. User Guide MEGGER Major MEGGER Insulation Testers MJ159, MJ160, MJ359, MJ459, MJ559 User Guide MEGGER Contents Safety Warnings 3 General Description 4 Operation Testing precautions 5 Preliminary checks 5 Battery condition

More information

OPERATING INSTRUCTION

OPERATING INSTRUCTION 11/05 Form #271 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 OPERATING INSTRUCTION Visit us at www.testequipmentdepot.com MODEL 3132 ANALOG INSULATION-CONTINUITY TESTER

More information

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions.

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. 1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. KYORITSU will not accept liability for any damage or injury caused by misuse

More information

MIT510/2 5kV Digital Insulation Tester USER MANUAL

MIT510/2 5kV Digital Insulation Tester USER MANUAL M MIT510/2 5kV Digital Insulation Tester USER MANUAL GSAFETY WARNINGS Safety Warning must be observed during use. The circuit under test must be switched off, de-energised, isolated and checked to be safe

More information

Multi-Function Ground Resistance Tester Model 6472

Multi-Function Ground Resistance Tester Model 6472 Multi-Function Ground Resistance Tester Model 6472 NEW! The Model 6472 measures from 0.01 to 99.99kΩ and is auto-ranging, automatically seeking out the optimum measurement range, test frequency and test

More information

1662/1663/1664 FC. Electrical Installation Tester. Safety Information. Warnings

1662/1663/1664 FC. Electrical Installation Tester. Safety Information. Warnings 1662/1663/1664 FC Electrical Installation Tester Safety Information Go to www.fluke.com to register your Product and find more information. A Warning identifies conditions and procedures that are dangerous

More information

Model 8 Mk7 AVOMETER USER GUIDE GUIDE DE L UTILISATEUR BEDIENUNGSANLEITUNG GUÍA DEL USUARIO

Model 8 Mk7 AVOMETER USER GUIDE GUIDE DE L UTILISATEUR BEDIENUNGSANLEITUNG GUÍA DEL USUARIO M Model 8 Mk7 AVOMETER USER GUIDE GUIDE DE L UTILISATEUR BEDIENUNGSANLEITUNG GUÍA DEL USUARIO GSAFETY WARNINGS The circuit under test must be switched off and de-energised before test connections are made

More information

USER MANUAL. Insulation Tester + DMM. Model MG320

USER MANUAL. Insulation Tester + DMM. Model MG320 USER MANUAL Insulation Tester + DMM Model MG320 Table of Contents 1. INTRODUCTION 3 2. SAFETY 3 3. METER DESCRIPTION 5 4. CONTROL BUTTONS 6 5. SYMBOLS AND ANNUNCIATORS 6 6. OPERATING INSTRUCTIONS 7 6.1

More information

NEW 15KV HIGH VOLTAGE INSULATION RESISTANCE TESTER MODEL KM 7015 IN FEATURES : CAT IV 600V. Short Circuit Current 5mA.

NEW 15KV HIGH VOLTAGE INSULATION RESISTANCE TESTER MODEL KM 7015 IN FEATURES : CAT IV 600V. Short Circuit Current 5mA. An ISO 9001:2008 Company 15KV HIGH VOLTAGE INSULATION RESISTANCE TESTER FEATURES : MODEL KM 7015 IN Microprocessor controlled Menu driven. Variable High Voltage : 500 V ~ 15 kv DC. Measuring 30 Insulation

More information

INSP-3 Wiring Inspection Tester

INSP-3 Wiring Inspection Tester INSP-3 Wiring Inspection Tester Users Manual For detailed specifications and ordering info go to www.testequipmentdepot.com INSP-3 Wiring Inspection Tester Users Manual English December 2009, Rev.1 2009

More information

Flex current clamps A 1179 A 1257 A 1395 User Manual Version 1.6; Code No

Flex current clamps A 1179 A 1257 A 1395 User Manual Version 1.6; Code No Flex current clamps A 1179 A 1257 A 1395 User Manual Version 1.6; Code No. 20 751 167 Distributor: Producer: METREL d.d. Ljubljanska 77 SI-1354 Horjul Tel.: +386 1 75 58 200 Fax: +386 1 75 49 226 E-mail:

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Digital Ground Resistance Tester Model 4610 & 4610 Kits 99 Washington Street Melrose, MA 02176 Fax 781-665-0780 TestEquipmentDepot.com

More information

Autoranging Multimeter

Autoranging Multimeter Owner's Manual Autoranging Multimeter Model No. 82334 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation Maintenance

More information

OPERATING MANUAL CMP-200

OPERATING MANUAL CMP-200 OPERATING MANUAL MINI AC LEAKAGE CURRENT METER CMP-200 Version 1.7 The CMP-200 digital clamp meter has been designed for the purpose of clamp measurements of alternative leakage current. Main features

More information

3 PHASE TESTER & MOTOR ROTATION TESTER

3 PHASE TESTER & MOTOR ROTATION TESTER 3 PHASE TESTER & MOTOR ROTATION TESTER R S T TEST CAT. III 500V 3 PHASE TESTER & MOTOR ROTATION TESTER CCW CW BAT. L2 L1 L3 L1 L2 L3 MOTOR ROTATION INSTRUCTION MANUAL INDEX Page 1. INTRODUCTION... 1 2.

More information

Non-Contact Phase Rotation Tester

Non-Contact Phase Rotation Tester User's Guide 99 Washington Street Melrose, MA 076 Phone 78-665-400 Toll Free -800-57-84 Visit us at www.testequipmentdepot.com Non-Contact Phase Rotation Tester Model PRT00 Introduction Congratulations

More information

Distributor. Kewtech Corporation Limited 76 St. Catherine s Grove Lincoln LN5 8NA KEWTECH

Distributor. Kewtech Corporation Limited 76 St. Catherine s Grove Lincoln LN5 8NA  KEWTECH Distributor Kewtech Corporation Limited 76 St. Catherine s Grove Lincoln LN5 8NA www.kewtechcorp.com KEWTECH 92-1618 04-03 KEWTECH KT61 digital multi function tester Instruction manual Contents 1 Safe

More information

Digital/Analog Megohmmeter Model 1026

Digital/Analog Megohmmeter Model 1026 Digital/Analog Megohmmeter Model 1026 USER MANUAL 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Table of Contents Warning...3

More information

INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN

INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN Contents 1. Safety Precautions... 1 2. Features... 3 3. Specifications... 4 4. Instrument

More information

KMP Insulation-Continuity Tester. Users Manual

KMP Insulation-Continuity Tester. Users Manual KMP 7036 Insulation-Continuity Tester Users Manual KMP7036 Insulation-Continuity Tester Users Manual English September 2011, Rev.1 2011 Amprobe Test Tools. All rights reserved. Printed in China Limited

More information

Calibrator Capabilities Function Range Resolution Measure V dc 28 V 1 mv Measure ma dc Source ma dc

Calibrator Capabilities Function Range Resolution Measure V dc 28 V 1 mv Measure ma dc Source ma dc 707 Loop Calibrator Instruction Sheet Introduction The Fluke 707 Loop Calibrator (hereafter, the Calibrator) is a compact sourcing and measuring tool. The Calibrator tests current loops of 0-20 ma or 4-20

More information

323/324/325 Clamp Meter

323/324/325 Clamp Meter 323/324/325 Clamp Meter Users Manual PN 4045153 May 2012 2012 Fluke Corporation. All rights reserved. Printed in China. Specifications are subject to change without notice. All product names are trademarks

More information

PSU1 Power Supply Unit

PSU1 Power Supply Unit OM2443 PSU1 Power Supply Unit Distributed By: GMW Associates 955 Industrial Road, San Carlos, CA, 94070 USA PHONE: +1 650-802-8292 FAX: +1 650-802-8298 EMAIL: sales@gmw.com WEB: www.gmw.com Table of Contents

More information

INSTRUCTION MANUAL IDM67 DIGITAL MULTIMETER

INSTRUCTION MANUAL IDM67 DIGITAL MULTIMETER INSTRUCTION MANUAL IDM67 DIGITAL MULTIMETER EN FR IT DE JP IDM67 DIGITAL MULTIMETER INSTRUCTION MANUAL 1 2 INTRODUCTION 1-1 Unpacking and Inspection Upon removing your new Digital Multimeter from its packing,

More information

FALL-OF-POTENTIAL GROUND RESISTANCE TESTER

FALL-OF-POTENTIAL GROUND RESISTANCE TESTER FALL-OF-POTENTIAL GROUND RESISTANCE TESTER Models 3620, 3640 & 4610 Call toll free (800) 537-0351 or visit www.allspec.com Measures soil resistivity (4-Point) (Model 4610) Measures ground resistance (2-

More information

i3000s/i2000 Flex AC Current Probe

i3000s/i2000 Flex AC Current Probe i3000s/ AC Current Probe Instruction Sheet Introduction The i3000s 24 Flex, i3000s 36 Flex, and AC Current Probes (the Probe) are used with oscilloscopes, digital multimeters, recorders or data loggers.

More information

Autoranging Industrial Multimeter

Autoranging Industrial Multimeter Owner's Manual Autoranging Industrial Multimeter Model No. 82005 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation

More information

Instruction Manual VT25 / VT28 VOLTAGE TESTER ALWAYS READ THESE INSTRUCTIONS BEFORE PROCEEDING

Instruction Manual VT25 / VT28 VOLTAGE TESTER ALWAYS READ THESE INSTRUCTIONS BEFORE PROCEEDING VT25 / VT28 VOLTAGE TESTER Instruction Manual ALWAYS READ THESE INSTRUCTIONS BEFORE PROCEEDING Thank you for buying one of our products. For safety and full understanding of its benefi ts please read this

More information

User's Manual. High Voltage Megohmmeter. Analog Insulation Tester plus AC Voltage and Continuity Tests. Model

User's Manual. High Voltage Megohmmeter. Analog Insulation Tester plus AC Voltage and Continuity Tests. Model User's Manual High Voltage Megohmmeter Analog Insulation Tester plus AC Voltage and Continuity Tests Model 380353 Warranty EXTECH INSTRUMENTS CORPORATION warrants this instrument to be free of defects

More information

BT508/BT510/BT520/BT521 Battery Analyzer Safety Sheet

BT508/BT510/BT520/BT521 Battery Analyzer Safety Sheet BT508/BT510/BT520/BT521 Battery Analyzer Safety Sheet Go to www.fluke.com to register your product, download manuals, and find more information. A Warning identifies conditions and procedures that are

More information

MIT515, MIT525, MIT1025, MIT kv, 10 kv, 15 kv DC Insulation resistance testers

MIT515, MIT525, MIT1025, MIT kv, 10 kv, 15 kv DC Insulation resistance testers MIT515, MIT525, MIT1025, MIT1525 5 kv, 10 kv, 15 kv DC Insulation Resistance Testers MIT515, MIT525, MIT1025, MIT1525 5 kv, 10 kv, 15 kv DC Insulation resistance testers Measures up to 30 TΩ Safety rated

More information

MM300. INSTRUCTION MANUAL Manual-Ranging Digital Multimeter

MM300. INSTRUCTION MANUAL Manual-Ranging Digital Multimeter INSTRUCTION MANUAL Manual-Ranging Digital Multimeter MM300 DATA HOLD AUDIBLE CONTINUITY BATTERY TEST DIODE TEST 10A 2MΩ ESPAÑOL pg. 13 FRANÇAIS pg. 25 MM300-1390109ART.indd 1 9/21/2015 2:48:00 PM GENERAL

More information

190M. Medical ScopeMeter. Safety Information

190M. Medical ScopeMeter. Safety Information 190M Medical ScopeMeter PN 4202934 June 2012, Rev. 1 2012 Fluke Corporation. All rights reserved. Printed in Romania. All product names are trademarks of their respective companies. WX Warning To prevent

More information

Atlas ESR and ESR + Equivalent Series Resistance and Capacitance Meter. Model ESR60/ESR70. Designed and manufactured with pride in the UK.

Atlas ESR and ESR + Equivalent Series Resistance and Capacitance Meter. Model ESR60/ESR70. Designed and manufactured with pride in the UK. GB60/70-9 Atlas ESR and ESR + Equivalent Series Resistance and Capacitance Meter Model ESR60/ESR70 Designed and manufactured with pride in the UK User Guide Peak Electronic Design Limited 2004/2016 In

More information

DC POWER SUPPLY ALIMENTATION C.C.

DC POWER SUPPLY ALIMENTATION C.C. DC POWER SUPPLY ALIMENTATION C.C. ISO-TECH IPS 303A 201-3424 ISO-TECH IPS 601A 201-3446 SAFETY TERMS AND SYMBOLS These terms may appear in this manual or on the product: WARNING. Warning statements identify

More information

DT33B/C/D OPERATOR S MANUAL LIMITED WARRANTY AND LIMITATION OF LIABILITY

DT33B/C/D OPERATOR S MANUAL LIMITED WARRANTY AND LIMITATION OF LIABILITY BACK LIGHT D I G I TA L M U LT I M E T E R DT33B OPERATOR LIMITED WARRANTY AND LIMITATION OF LIABILITY This product will be free from defects in material and workmanship for one year from the date of purchase.

More information

Digital/Analog Megohmmeter Model 1026 USER MANUAL

Digital/Analog Megohmmeter Model 1026 USER MANUAL Digital/Analog Megohmmeter Model 1026 USER MANUAL Limited Warranty The Megohmmeter Model 1026, is warranted to the owner for a period of 2 years from the date of original purchase against defects in manufacture.

More information

The following table shows the symbols used on the product and/or in this manual. Hazardous Voltage. Risk of electric shock.

The following table shows the symbols used on the product and/or in this manual. Hazardous Voltage. Risk of electric shock. i6000s Flex AC Current Probe Instruction Sheet Introduction The i6000s 24 Flex and i6000s 36 Flex AC Current Probes (hereafter referred to as the Probes ) are used with oscilloscopes, digital multimeters,

More information

Users Manual. MegOhmMeter

Users Manual. MegOhmMeter 1520 MegOhmMeter Users Manual September 2000 Rev.2, 2/03 2000-2003 Fluke Corporation. All rights reserved. Printed in USA All product names are trademarks of their respective companies. Table of Contents

More information

7/05 FORM#347 OPERATING INSTRUCTIONS MULTI FUNCTION TESTER MODEL 6030

7/05 FORM#347 OPERATING INSTRUCTIONS MULTI FUNCTION TESTER MODEL 6030 7/05 FORM#347 OPERATING INSTRUCTIONS MULTI FUNCTION TESTER MODEL 6030 Contents 1. Safety Precautions 1 2. Features 3 3. Specifications 4 4. Layout Diagram 7 5. Preparation for Measurement 9 6. Operation

More information

Atlas ESR. User Guide. Capacitance and Equivalent Series Resistance Meter. Model ESR60 (Enhanced)

Atlas ESR. User Guide. Capacitance and Equivalent Series Resistance Meter. Model ESR60 (Enhanced) Atlas ESR Capacitance and Equivalent Series Resistance Meter Model ESR60 (Enhanced) User Guide Peak Electronic Design Limited 2004/2008 In the interests of development, information in this guide is subject

More information