LIQUI-MOVER PUMP HANDBOOK
|
|
- Roy Shepherd
- 6 years ago
- Views:
Transcription
1 LIQUI-MOVER PUMP HANDBOOK Kadant Johnson Inc., 805 Wood Street, Three Rivers, MI USA fax: LMP Handbook-4002
2 What is a Liqui-Mover Pump? A Liqui-Mover pump is a positive displacement pressure powered pump with a minimum of moving parts. The pumping action is accomplished using a positive pressure to push the liquid from the pump tank into the return line. The Liqui-Mover pump can handle high temperature and high pressure condensate without difficulty. Liqui-Mover pumps are available in nine sizes. They are available in many configurations, from individual components that are field assembled to complete packaged systems ready for connection to field piping. A basic Liqui-Mover pump consists of a receiver/reservoir, pump tank, 3-way motive valve, inlet and outlet check valves, level control, and various other fittings. How a Liqui-Mover Pump Works In describing How a Liqui-Mover Pump Works, it is advantageous to look at the overall operation, and then break it down into smaller operations for a better understanding. Condensate from the equipment being drained enters the receiver/reservoir tank and flows down the fill line into the pump tank. When the predetermined high level is reached in the pump tank, the level control system sends out a signal, which causes the 3-way motive valve to cycle. When the 3-way valve cycles, the equalizing line between the receiver/reservoir and the pump tank is closed off and a regulated motive pressure is admitted into the pump tank. This motive pressure is confined above the condensate in the pump tank and its effect is to move the condensate out of the pump tank and into the return line. When the condensate reaches a predetermined low level, the level control sends another signal, causing the 3-way valve to revert to its original position. The residual motive pressure remaining in the pump tank will flow through the equalizing line, into the receiver/reservoir, enabling the pressures in the two tanks to equalize with each other. When this is complete, the flow of condensate from the receiver/reservoir to the pump tank will start again. The cycle will now repeat. See below for more details of each stage of the cycle: STAGE ONE: During the fill cycle, fluid flows from the receiving chamber (A) through the inlet check valve (B) into the pumping chamber (C). The 3-way valve (D) is open between the pumping chamber and the receiving chamber, equalizing the pressure between them through the equalizing line (E). STAGE TWO: When the level control (F) senses that the pumping chamber is full, the 3-way valve energizes to admit the motive pressure into the pumping chamber (C). The inlet check valve (B) prevents backflow into the fill line. The discharge cycle begins when pressure inside the pumping chamber is greater than in the discharge line. The discharge check valve (G) opens and fluid flows into the discharge line. During this cycle, incoming condensate is stored in the receiver. STAGE THREE: Once the level control (F) senses the pumping chamber has emptied, the 3- way valve (D) de-energizes, shutting off the motive pressure, and opening the vent port in the valve. This equalization cycle allows the pumping chamber (C) and the receiving chamber (A) to equalize in pressure, and the fill cycle begins again.
3 Installation Preparation For ease of future maintenance, the Liqui-Mover pump should be installed with the check valve side of the pump tank most accessible. Normally the motive inlet and the condensate discharge connections are on the left when facing the check valves. If a Johnson receiver is supplied, the replaceable sacrificial anode is also installed and removed from this end. On ERC and FAC (pneumatic operated 3-way valve) units, the control air is located on the right when facing the check valves. Refer to the enclosed assembly drawing for additional information. Setting the Unit On LOOO models, the pump tank has (4) holes for mounting to the floor. On LROO models, you will also need to install a Johnson supplied receiver. The receiver is held in saddles with U bolts supported by (4) pipes on floor flanges. The floor flanges have mounting holes for attachment to the floor. On LRFP models, the entire base of the frame should be supported. Mounting holes can be drilled through the frame base for attachment to the floor. All tanks should be installed level. Piping On LROO and LRFP models, the Johnson supplied receiver will normally have (3) top connections for: condensate inlet, atmospheric vent, and pressure gauge. For closed systems (no atmospheric vent), an air eliminator and safety relief valve will need to be installed. On LOOO models, the condensate is piped directly to the inlet check valve from an existing receiver or pipe accumulator. The motive pressure (normally steam or compressed air) is piped to the 3-way valve through a strainer and a pressure reducing valve. The strainer is supplied on LRFP models. Compressed air of at least 55 psig should be piped to the pilot valve through a filter/regulator/lubricator on ERC and FAC models. The pilot valve and the filter/regulator/lubricator are supplied with the unit. For LROO and LOOO models, friction loss through the piping should be kept to a minimum. Therefore, pipe reducers should not be used and pipe runs kept to a minimum. All hand valves should be full port if at all possible. Electrical Connect the electrical service to the on/off switch located on the door of the electrical enclosure per the instruction label located near the switch. The electrical voltage must be the same as the rating of the level control relay and the valve, unless a step-down transformer has been supplied. NOTE: An on/off switch is not standard on NEMA 7 units.
4 Pressure Reducing Valve Installation A pressure reducing valve (PRV) should be installed in the motive pressure line to regulate how fast the Liqui-Mover pump discharges the condensate out of the pump tank. When properly adjusted, the discharge time should not be less than 20 seconds. A longer discharge time is acceptable, so long as the Liqui-Mover pump can keep up with the incoming condensate load. Normally the motive pressure setting will be approximately 20 psig higher than the back pressure to achieve a 20 second discharge time. Here are some guidelines to be followed when installing a PRV in conjunction with a Liqui-Mover pump: 1. Never install a PRV immediately adjacent to the 3-way motive valve. The shock caused by the sudden opening and closing of the motive 3-way valve will ultimately damage the PRV. We recommend a distance of feet between the PRV and the 3-way valve, where the pipe size is the same as the 3-way valve connection. A larger diameter pipe of a shorter length that has an equivalent volume is also acceptable. The PRV should be sized by a pressure reducing valve manufacturer or representative. 2. A safety relief valve should be installed downstream of the PRV to prevent over-pressurization at the 3-way valve. The safety relief valve should be sized by a safety relief valve manufacturer or representative. 3. When steam is the motive pressure, a drip trap, dirt leg, and strainer should be installed ahead of the PRV. The drip trap should not be piped to the Liqui-Mover pump, unless the receiver is vented. When compressed air is the motive pressure, a liquid drainer, dirt leg, and strainer should be installed ahead of the PRV. The liquid drainer should not be piped to the Liqui-Mover pump. 4. The piping from the PRV outlet to the 3-way valve inlet should be sized to minimize the pressure drop under flow conditions. 5. A throttling valve should be installed immediately ahead of the 3-way motive valve so it can be used in conjunction with the PRV to adjust the Liqui-Mover pump discharge time. Typically the throttling valve is a globe valve. Motive Supply Header - Steam or Compressed Air Y Strainer Safety Relief Valve (Piped to safe location) Equalization Line To Receiver / Condensate Header 3-Way Valve Dirt Leg PRV Throttle Valve (Globe) To Liqui-Mover Pump Drip Trap(Steam) or Liquid Drainer(Air Motive) The above sketch is for reference only. Always consult with the PRV and safety relief valve manufacturer or representative for proper sizing and application of their products.
5 Printed on 12/15/2008 at 11:41:12 AM Property of Kadant Johnson - Confidential
6 Installation Diagram for Liqui-Mover Pump with Compressed Motive Motive - Compressed Air Supply Filter w/ Auto Drain Safety Relief Valve (When Needed) To Motive Inlet of Liqui-Mover Pump Regulator w/ Gage Throttle Valve (Globe) To 1/4" NPT Air Inlet Connection of Liqui-Mover Pump This Connection Required For Liqui-Mover Pumps Having a Pneumatic Operated 3-Way Valve (ERC and FAC units) Liqui-Mover Pump 1. This is the recommended piping for a Liqui-Mover pump with compressed motive. 2. The air should be clean, dry and regulated so that the Liqui-Mover pump discharges in the recommended time. 3. The above parts furnished by customer.
7 Start-Up Instructions 1. On Liqui-Mover pumps that are not pre-piped, inspect the inlet and outlet check valves for proper flow direction. Refer to the Liqui-Mover pump assembly drawing and parts list. 2. If the receiver and/or pump tank contains sub-cooled condensate, this needs to be drained prior to start-up. 3. On ERC and FAC units, open the compressed air line to the filter/regulator/lubricator and set the air pressure to 55 psig, minimum. 4. On ERC and ERS units, turn on the electrical power. 5. Open the motive steam or compressed air supply to the PRV and set the pressure to approximately 20 psig higher than the back pressure. The throttling (globe) valve should be closed. 6. Open all remaining isolation (hand) valves, except the isolation valve ahead of the inlet check valve (fill line). 7. Once condensate in seen in the receiver, slowly open the isolation valve in the fill line and watch for condensate to fill the pump tank. 8. When the 3-way motive valve energizes, slowly open the throttling (globe) valve ahead of the 3-way motive valve. This will allow the pump tank to discharge. 9. After a few discharge cycles, you will be able to fully open the throttling valve and set the motive pressure to achieve a second discharge time using the PRV. 10. The unit is now in service. Incoming Condensate Vent Line Motive Supply Equalize Line Check Valve Globe Valve PRV Strainer Control Panel Receiver May Be JoCo ASME Labeled Receiver, Existing Receiver, Oversized Pipe Header, or Etc. 3-Way Motive Valve Pumping Tank Drip Trap - Steam Liquid Drainer - Air TYPICAL INSTALLATION SKETCH Discharged Condensate Outlet Check Valve Inlet Check Valve NOTE: 1. The above sketch is for reference only. 2. Additional isolation hand valves may be added as required for maintenance purposes. 3. Globe valves should be used where flow restriction is required. 4. Gate valves should be used where minimal flow restriction is required. 5. For proper PRV installation, see manufacturers installation instructions.
8 CV3S-1000 Series with 4-Way Pilot Valve Pilot De-Energized Pilot Energized Solenoid Pilot Valve 4-Way Filter/Regulator/Lubricator Solenoid Pilot Valve 4-Way B Filter/Regulator/Lubricator B B EX B EX A IN A IN A A Port 1 (Common) Port 1 (Common) Port 3 (Motive In) Port 2 (Equalize) Port 3 (Motive In) Port 2 (Equalize) CV3S-100 Series with 3-Way Pilot Valve Pilot De-Energized Pilot Energized Solenoid Pilot Valve 3-Way Filter/Regulator/Lubricator Solenoid Pilot Valve 3-Way Filter/Regulator/Lubricator Equalize Equalize Common Common Motive In Motive In
9 Johnson Solenoid Coil and Fuse Specification Sheet Coil Voltage Freq. Coil No. Approx. Current Fuse Service JOCO Fuse No. Size (Amps) (Amps) Inrush Sealed B Cont. CSE B Cont. CSE B Cont. CSE C Cont. CSE C Cont. CSE C Cont. CSE D Cont. CSE D Cont. CSE D Cont. CSE D Cont. CSE D Cont. CSE D Cont. CSE D Int. * CSE D Int. * CSE D Int. * CSE Int. * : Intermittent service - solenoid energized not over 45% of the time and not longer than 1/2 hour at one time Fuses manufactured by: Gould Shawmut TR XX R Bussman FRN-R-XX (Replace X's with Fuse Amps) Reference Johnson Drawing A37786
10 Troubleshooting Contents General Troubleshooting General ERC and ERS Troubleshooting ERC Troubleshooting ERS Troubleshooting FAC Troubleshooting Preventative Maintenance Check List Preventative Maintenance Check List Additional For FAC Ceramic Electrode Plugs Electrode Lengths 8300 Series Relay Installation and Maintenance Intrinsically Safe Relay Installation and Maintenance
11 Page 1 - General Troubleshooting LMTSO GENERAL TROUBLESHOOTING OF LIQUI-MOVER PUMPS OBSERVATION PROBABLE CAUSE REMEDY 1. Liqui-Mover pump fails to fill. 1. Increase in liquid level in receiver, possible flood in receiver. Obstruction in fill line, valve closed, inlet check valve backwards. Inspect fill line for closed valve, inlet check valve in reverse, or obstruction in fill line. Refer to Assembly & Parts List Drawing. 2. Increase in liquid level in receiver, possible flood in receiver, increase in receiver pressure. 3. Receiver empty. Liqui-Mover pump level fluctuating Way Motive Valve will not deenergize. 3-Way Valve Assembly out of adjustment. Receiver pressure greater than pressure in discharge line. See observation under specific ERS or ERC Troubleshooting Section. Inspect 3-Way Valve Assembly. Refer to Valve Section. If unit has been in operation for a period of time without problems, check for traps blowing through. If new installation receiver pressure may be greater than anticipated. Back pressure may be less than anticipated. A 2-Way Controlled Valve may be required in discharge line. See specific remedy. 2. Liqui-Mover pump fills too slow. 1. No liquid level in receiver. Load to unit not as great as anticipated. No action required. 2. Receiver flooding. Obstruction or restriction in fill line. Inspect fill line for partially closed valve or defective check valve. Inspect fill line for proper size fittings and pipe. Refer to Assembly and Parts List Drawing for specific unit.
12 Page 2 - General Troubleshooting LMTSO OBSERVATION PROBABLE CAUSE REMEDY 3. Receiver flooding. Restriction in vent line, 3-Way Valve assembly out of adjustment. Inspect vent line for partially closed valve, proper size fittings and pipe. Refer to Assembly and Parts List Drawing. Inspect 3-Way Valve Assembly. Refer to Valve Section. 3. Liqui-Mover pump fills very rapidly. 1. Unit cycling almost normally, receiver flooding. Defective check valve in discharge line and/or fill line. Possible back flow to Liqui-Mover pump. Inspect discharge line check valve and fill line check valve. Refer to Assembly and Parts List Drawing. 4. Noise in or at fill line check valve. 1. Vibration and water hammer at fill line check valve. Cold condensate. Inspect for cold condensate. Throttle flow control valve, ahead of 3-Way Motive Valve Assembly. Refer to Assembly and Parts List Drawing, and start-up procedure. 5. Liqui-Mover pump discharges very rapidly. 1. Water hammer in discharge line. Motive pressure too high. Throttle flow control valve or install pressure reducing valve. See start-up procedure. 2. Receiver flooding, rise in receiver pressure during discharge. Defective check valve in fill line, discharging condensate back into receiver. Inspect fill line check valve. Refer to Assembly and Parts List Drawing. 6. Liqui-Mover pump discharge cycle too long. 1. Possible receiver flooding, discharge time greater than 30 seconds. Flow control valve throttled too much. No action required, if receiver not flooding. If receiver flooding, adjust flow control valve for discharge of seconds (approx.).
13 Page 3 - General Troubleshooting LMTSO OBSERVATION PROBABLE CAUSE REMEDY 2. Receiver flooding. Discharge time greater than 30 seconds. 3. No motive pressure flow. Receiver flooding. Restriction or increase of back pressure in discharge line. Motive supply failure, obstruction in motive supply line. Inspect discharge line for partially closed valve(s), obstructions or change in pressure. A pressure increase may require adjustment of flow control valve to reduce discharge time. Inspect discharge check valve. Inspect for motive supply pressure, closed valve, or obstruction in motive supply line. Inspect strainer Way Motive Valve noisy. Condensate in motive supply line. Inspect motive supply line for condensate. Check drip trap. Refer to Assembly and Parts List Drawing. 5. Receiver pressure increase during discharge Way Motive Valve will not deenergize. 3-Way Valve out of adjustment, leakage into receiver. See observation under specific Relay Section. Refer to Valve Section. See specific remedy.
14 Page 4 - ERC or ERS Troubleshooting GENERAL ERC & ERS TROUBLESHOOTING LMTSO OBSERVATION PROBABLE CAUSE REMEDY 1. 3-Way Valve erratic. Operates from one level only. 1. Condensate level in Liqui-Mover pump at one level. Electrode wires reversed. Poor ground connection. Refer to Relay Troubleshooting Section Way Valve erratic. Operates from low level only. 1. Condensate level in Liqui- Mover pump at low level. Electrode plugs shorted. Electrode plug grounded. Holding contact bad. Refer to Relay Troubleshooting Section Way Valve erratic. 1. Condensate level can be high or low. Moisture in electrode holder. Dirty electrodes. Cracked or broken electrode plug. Refer to Relay Troubleshooting Section.
15 Page 5 - ERC Troubleshooting TROUBLESHOOTING ERC UNITS (w/electrodes-relay-cylinder Operated Valves) LMTSO OBSERVATION PROBABLE CAUSE REMEDY 1. 3-Way Cylinder Operated Valve will not cycle on (closed motive side open vent side). 1. Relay pulls in. Air pilot shifts. Packing nut too tight. Back-off packing nut. Refer to Valve Section. 2. Relay pulls in. Air pilot shifts. Obstruction in air line to cylinder. Check air lines for obstructions or breaks. 3. Relay pulls in. Air pilot not shifting. Air pilot valve. Check wiring, check for voltage to pilot coil. Check air pressure (55 psig minimum). 4. Relay will not pull in. Power failure. Refer to Relay Troubleshooting Section. 5. Relay will not pull in. Electrode circuit or relay malfunction. Refer to Relay Troubleshooting Section Way Cylinder Operated Valve will not cycle off (open motive side closed vent side). 1. Relay drops out. Air pilot shifts. Packing nut too tight. Back-off packing nut. Refer to Valve Section. 2. Relay drops out. Air pilot not shifting. Air supply or air pilot valve. Check for proper air pressure. Inspect relay contacts for being welded together. If okay, repair or replace pilot valve. 3. Relay drops out. Air pilot shifts. Receiver flooding. 3-Way Cylinder Valve Assembly jammed. Inspect 3-Way Cylinder Valve Assembly for obstruction, dirt or foreign debris. Refer to Valve Section. 4. Relay will not drop out. Receiver flooding. Electrode holder wet or dirty, probe or wire grounded. Refer to Relay Troubleshooting Section Way Cylinder Operated Valve cycles On Off erratically. 1. Relay does not follow erratic valve operation. Air supply fluctuating. Inspect air supply for fluctuations. Air pilot requires 55 psig minimum.
16 Page 6 - ERS Troubleshooting TROUBLESHOOTING ERS UNITS (w/electrodes-relay-solenoid Steam Valve) LMTSO OBSERVATION PROBABLE CAUSE REMEDY 1. 3-Way Valve will not energize (closed motive side open vent side). 1. Relay pulls in. Liqui-Mover pump flooded. Overload tripped or fuse bad. Replace fuse. Refer to Valve Section. 2. Relay pulls in. Solenoid valve noisy. Packing nut too tight. Dirty armature. Back-off packing nut. Refer to Valve Section. Check valve adjustment. 3. Relay pulls in. Fuse not blown. Solenoid valve coil open. Inspect Solenoid Valve for burnt or broken lead wires or bad coil. Inspect Solenoid Valve for mechanical jam. Refer to Valve Section. 4. Relay will not pull in. Power failure. Inspect for supply voltage. Refer to Relay Troubleshooting Section. 5. Relay will not pull in. Electrode circuit or relay malfunction. Refer to Relay Troubleshooting Section Way Valve will not deenergize (open motive side close vent side). 1. Relay drops out. Receiver flooding. Packing nut too tight. Back off packing nut. Refer to Valve Section. 2. Relay will not drop out. Receiver flooding. Electrode holder wet or dirty, probe or wire grounded. Refer to Relay Troubleshooting Section. 3. Relay will not drop out. Receiver flooding. Electrodes shorted. Inspect Liqui-Mover pump chamber for debris. Refer to Relay Troubleshooting Section 4. Relay drops out. Receiver flooding. 3-Way Steam Valve Assembly jammed. Inspect 3-Way Solenoid Valve Assembly for obstruction, dirt, or foreign debris. Refer to Valve Section.
17 Page 7 - FAC Troubleshooting TROUBLESHOOTING FAC UNITS (Refer to General Troubleshooting Section, Pages 1 through 3, then the following.) LMTSO OBSERVATION PROBABLE CAUSE REMEDY 1. 3-Way Cylinder Operated Valve will not cycle on (closed motive side open vent side). 1. Air pilot shifts. Air pressure too low. Raise air pressure. 2. Air pilot shifts. Packing nut too tight. Back-off packing nut. Refer to Valve Section. 3. Air pilot shifts. Obstruction in air line to cylinder. Check air lines for obstructions or breaks. 4. Air pilot not shifting. Wisker valve not operating or bad. Break air line between pilot valve and wisker valve. 1. If pilot valve still does not shift, break air line between air filter and choke. Clean.010 hole in choke or replace choke. Reassemble and retest. If pilot valve still does not shift, replace pilot valve. 2. If pilot valve shifts, shut off all steam, condensate, and motive lines to and from the unit. Reconnect the air line between the pilot valve and the wisker valve. Remove the cover (LMH or 6) and manually raise the float tube.
18 Page 8 - FAC Troubleshooting LMTSO OBSERVATION PROBABLE CAUSE REMEDY a. If the pilot valve shifts, disassemble flanges that mount the control head and remove, inspect, and repair float assembly as required. Refer to Dwg. A , Pg. 5. b. If the pilot valve does not shift, remove the air switch and inspect for missing or broken spring pins, magnet, or snap rings. Note: The magnet must be able to rotate freely only 30 degrees. If all appears proper, replace the wisker valve, Refer to Dwg. A , Pg Way Cylinder Operated Valve will not cycle off (open motive side closed vent side). 1. Air pilot shifts. Low air pressure. Raise air pressure. 2. Air pilot shifts. Packing nut too tight. Back-off packing nut. Refer to Valve Section. 3. Air pilot shifts. Obstruction in air line to cylinder. Check air lines for obstructions or breaks. 4. Air pilot not shifting. Wisker valve not operating or bad. Break the air line between the pilot valve and the wisker valve. Block off air flow from the fitting on top of the pilot valve.
19 Page 9 - FAC Troubleshooting LMTSO OBSERVATION PROBABLE CAUSE REMEDY 1. If pilot valve does not shift, replace the pilot valve. 2. If the pilot valve shifts, shut off all steam, condensate, and motive lines to and from the unit. Reconnect the air line between the pilot valve and the wisker valve. Remove the cover (LMH or 6) and manually lower the float tube. a. If the pilot valve shifts, disassemble flanges that mount the control head and remove, inspect, and repair float assembly as required. Refer to Dwg. A , Pg. 5. b. If the pilot valve does not shift, remove the air switch and inspect for missing or broken spring pins, magnet, or snap rings. Note: The magnet must be able to rotate freely only 30 degrees. If all appears proper, replace the wisker valve. Refer to Dwg. A , Pg. 3.
20 LIQUI-MOVER PUMP PREVENTATIVE MAINTENANCE CHECK LIST HOW OFTEN CHECK REFERENCE 6 Months 1. Check electrodes for build up of foreign matter. With build up, poor conductivity may occur creating erratic pumping behavior. 2. Check 3-Way valve adjustment and make necessary adjustments. Also check valve packing and replace if required. Remove cap on electrode holder. Remove electrode plugs, this will also remove electrodes. Clean electrodes with steel wool or emery cloth. Replace. Refer to specific valve repair and maintenance guide. 1 Year 1. Check electrical wiring. Inspect wires at electrode plugs and valve for a deterioration of insulation and frayed wires. 2. Check anode in receiver tank. Drain tank remove anode by unscrewing anode plug on the receiver tank end. If over 60% eaten away, replace. 3. Clean gauge glasses when required. Disassemble and pull clean cloth through glass with cleaning wire. 4. Drain tanks to remove residue. Remove drain plugs in bottom of both tanks. Replace. 5. Check relay contacts (points). If dirty, clean. if burnt, replace, (ERS units only). 6. Check Solenoid Valve current. With Solenoid Valve energized, measure current. Too high a current could indicate a dirty armature or worn armature clean or replace as necessary. Refer to A in Valve Section. CAUTION: Before performing any of the above maintenance checks, shut off electrical power, steam, and condensate ahead of the unit.
21 Page 2 Preventative Maintenance FAC LIQUI-MOVER PUMP PREVENTATIVE MAINTENANCE CHECK LIST HOW OFTEN CHECK REFERENCE 1 Month 1. Oiler Level. Should deliver (1) drop per week. Adjustment screw. 2. Air Filter Main. Blow down or clean as required. 3. Air Filter Secondary. (Located on Control Head) Blow down or clean as required. 6 Months 1. Flush External Float Housing. Remove 1-1/2 drain plug and flush. CAUTION: These items in addition to standard Liqui-Mover pump maintenance check items. Before performing any of the above maintenance checks, shut off all steam, condensate and air lines.
22 8300 Series Relay Installation and Maintenance Black A.C. Line White BLACK A.C. Line WHITE 1 LCR 3 to SHORT ELECT. 4 to LONG ELECT. 5 GND. & ELECT. 2 LCR 1 LCR 3 to SHORT ELECT. 4 to LONG ELECT. 5 GND. & ELECT. 2 LCR LCR 9 10 OPT. COUNTER SOV1 OPT. CYCLE COUNTER LCR APR FU 9 APR 10 AUX PWR RELAY SOV1 OPT. COUNTER OPT. CYCLE COUNTER ERC ERS CAUTION: Since Line Voltage is often present during electrical tests, only qualified electricians should perform electrical tests. A. OPERATION This description applies to a pump down or direct type of level control. The sequence is as follows: 1. The relay is deenergized as shown in the diagram and the valve is deenergized and closed while the liquid in the tank is rising. 2. When the liquid reaches the high level electrode, it completes the circuit from terminal 5 to 3, energizing the relay. This can be heard as a click as the load contact is reversed. 3. The load contact closes and the valve opens admitting pressurized steam or air into the tank which causes the liquid level to lower. 4. When the relay energized, an internal holding circuit closed from terminal 4 to 3. When the liquid leaves the high level electrode this holding circuit through the ground, the liquid, and the low level electrode keeps the relay energized. 5. When the liquid drops below the low level electrode this holding circuit is broken and the relay is deenergized, opening the load contact. 6. The valve closes, shutting off the pressurized gas line and allowing the liquid to rise again. B. RELAY DOES NOT PULL IN 1. POWER FAILURE Check for voltage at the two (2) terminals located on the lower left hand corner of the level control relay. This voltage should be either 120 or 240 volts A.C. as determined by the voltage of the relay(s) and solenoid operated valve(s). 2. DEFECTIVE LEVEL CONTROL Disconnect the electrodes and jumper the terminal marked C to the terminal marked H. The 3-way steam valve should turn on when the jumper is connected and shut off when the jumper is removed. To check the holding circuit proceed as above but do not remove the jumper wire; instead add another jumper wire from the terminal marked C to the terminal marked L. Remove the first jumper wire connected to H and the relay should remain energized. If the relay does not remain energized, it is bad and will have to be replaced.
23 3. POOR GROUND CONNECTION The control will not function unless a good dependable ground connection is made to the terminal marked C. When installed in non-conductive tanks a third electrode (the longest) is required for a ground connection. 4. BROKEN WIRES Check for broken wires by grounding the spark plug holding the short electrode. If the relay fails to energize, one or both of the electrode leads are open, or there is a bad ground connection. Run temporary wires from the control panel to the electrode holder and retest. 5. BUZZ OR CHATTER If the resistance or conductivity of the liquid is too low, the relay may buzz, chatter, or fail to operate at all. Consult area representative for selecting a relay with proper sensitivity. 6. FOULED ELECTRODES Accumulated dirt, oil, and other deposits may insulate the electrodes and prevent operation. Electrodes should be inspected and cleaned at regular intervals. C. VALVE DOES NOT ENERGIZE WHEN THE RELAY DOES 1. FUSE ERS ERS units are equipped with a fuse for solenoid valve coil protection. Check the fuse for continuity and replace if bad. One spare is included with each Liqui-Mover pump. Refer to Drawing A-27541, Symbol No. A for solenoid coil protection. 2. SOLENOID COIL Remove the wires going to the solenoid coil from the terminal strip and check for continuity. If an open circuit is found, there is a broken wire, a bad connection, or the coil itself is bad. Repair or replace as necessary. 3. AUXILIARY RELAY ERS ERS units are equipped with an auxiliary relay because the level control relay contacts are not heavy enough to handle the inrush current of a direct operated solenoid valve. Inspect this relay for burnt contacts. Clean or replace contacts/relay as required. D. VALVE ENERGIZED WHEN RELAY IS NOT ENERGIZED 1. RELAY CONTACTS The relay contacts may have failed to open. On ERS units inspect the auxiliary relay visually for stuck contacts. On ERC and ERS units check the contacts on the level control relay with a V.O.M. E. RELAY WILL NOT DEENERGIZE 1. GROUND WIRE A wire from the relay to an electrode may be grounded to the conduit or enclosure. 2. WET PLUG Dirt or moisture on an electrode plug can ground the electrode to the holder. Cleaning the electrode plugs periodically and using a proper holder will help keep the plugs clean. 3. CRACKED PLUG The electrode plug may be cracked, allowing moisture to ground the electrode to the enclosure. F. RELAY FLUCTUATES AT HIGH LEVEL 1. ELECTRODE WIRING Wire to low level electrode may be broken. 2. ELECTRODE Low level electrode may have broken off or become insulated due to grease or dirt.
24 3. RELAY HOLDING CIRCUIT If the internal holding circuit of the relay fails to close, the relay would fluctuate at the high level. To test relay see Section B-2. G. RELAY FLUCTUATES AT LOW LEVEL 1. WIRES REVERSED Wires to electrodes may be reversed. 2. RELAY HOLDING CIRCUIT If the internal holding circuit of the relay is shorted, it would cause the relay to fluctuate at the low level. To test the relay see Section B-2. H. RELAY CHATTERS AFTER DISCHARGING 1. WET PLUG The underside of the electrode plug may be coated with dirt or moisture causing continuity across the insulator. If steam is used as the motive substance to lower the liquid level, when the tank is vented at the start of the fill period the steam expands. This may leave a film of moisture on the underside of the plug which can cause relay fluctuation a few times before the moisture evaporates and lets the relay drop out. This can be avoided by using a relay with lower sensitivity if the liquid is sufficiently conductive, or by insulating the electrodes, leaving 1/4 bare at the lower end.
25 INTRINSICALLY SAFE RELAY FOR LEVEL CONTROL 120 V AC V AC Sol. Valve 3 7 Sol. Valve Fuse B Fuse B Electrode Holder High Level Electrode Low Level Electrode A * Note: For ERC type units no overload is used. The air pilot valve is connected to relay terminals 11 and 7 or as shown on wiring assembly. B Older models use a thermal element in place of the fuse shown. INSTALLATION The electrode circuit of this relay is intrinsically safe and can be located in a hazardous area with an electrode holder and tank which are not explosion-proof. However, the rest of the circuits must be protected by explosion-proof enclosures and rigid conduit with conduit seals. OPERATION This description applies to a pump down type of level control and the sequence is as follows: 1. The relay is deenergized as shown in the diagram and the valve is deenergized and closed while the liquid in the tank is rising. 2. When the liquid reaches the high level electrode, it completes the circuit from terminal 14 to 15, energizing the relay. This can be heard as a click and all the load contacts are reversed. 3. Load contact 10 7 closes and the valve opens admitting pressurized steam or air which causes the liquid level to lower. 4. When the relay was energized, an internal holding circuit closed from terminal 16 to 15. Hence when the liquid leaves the high level electrode this holding circuit through the ground, the liquid, and the low level electrode keeps the relay energized. 5. When the liquid drops below the low level electrode this holding circuit is broken and the relay is deenergized, opening the internal holding connection from 14 to 16 and opening load contact The valve closes, shutting the pressurized gas line and allowing the liquid to rise again. When the liquid reaches the low level electrode the relay remains deenergized since the internal connection from 16 to 15 is now open, so the cycle will be repeated.
26 SERVICE INSTRUCTIONS For 120V Control. (For 240V see diagram) A. RELAY DOES NOT PULL IN 1. POWER FAILURE Check for voltage at terminals 11 and 12. Should be within 10% of rated value. 2. RELAY FAILURE Remove leads from terminals 14, 15, and 16. With power on, touch a jumper from 14 to 15 and you should hear the relay click on. If not, the relay should be replaced. To test see Section POOR GROUND CONNECTION There must be a low resistance ground connection from terminal 14 to the liquid either through the tank or through a ground electrode which contacts the liquid. 4. BROKEN WIRES An open connection in the line from 15 to the short electrode will prevent the relay from energizing. To check, run a temporary wire from terminal 15 to the short electrode. 5. FOULED ELECTRODES Deposits of dirt or grease on the upper electrode can insulate it and prevent relay from pulling in. If this occurs, electrodes should be cleaned regularly as required. If large quantities of oil, grease, or sludge are encountered, the electrodes can be mounted inside a pipe with the bottom below the lowest water level and a vent hole above high water level. A small flow of water into the top of the pipe will keep the electrodes operating in clean water. 6. ELECTRODES TOO SHORT If the liquid can not reach the high level electrode, the relay will not pull in. 7. LOW CONDUCTIVITY If the conductivity of the liquid is below 17 micromhos it may not allow conduction of enough current to operate the relay. Specify conductivity data to the factory and a more sensitive relay can be supplied. B. VALVE DOES NOT ENERGIZE WHEN RELAY DOES 1. OVERLOAD TRIPPED If the overload has tripped, reset it. If it continues to trip, see Drawing A RELAY CONTACT With relay energized (water at high level or a jumper on terminals 14-15) check for voltage on terminals If not voltage, and connection from is okay, relay contact 10-7 may be defective. Transfer its connections to spare contact SOLENOID COIL OR AIR PILOT VALVE COIL Check wires to coil. If coil is mechanically free, apply voltage to coil. If coil does not pull and wiring is proper, replace coil. C. VALVE ENERGIZED WHEN RELAY IS NOT 1. RELAY CONTACT Relay contact 10-7 may fail to open. Transfer its connections to spare contact 6-3. D. RELAY FLUCTUATES AT HIGH LEVEL 1. ELECTRODE WIRING Wire from 16 to low level electrode may be broken. 2. ELECTRODE Low level electrode may have broken off or become insulated due to grease or dirt. 3. RELAY HOLDING CIRCUIT If the internal holding circuit of the relay fails to close, the relay would fluctuate at the high level. To test relay see Section 1.
27 E. RELAY FLUCTUATES AT LOW LEVEL AFTER ONE CYCLE 1. ELECTRODE GROUND Turbulance may cause long electrode to contact stilling well or tank. 2. WET PLUG The underside of the electrode plug may be coated with dirt or moisture causing a short across the insulator. If steam is used as the motive substance to lower the liquid level, when the tank is vented at the start of the fill period the steam expands. This may leave a film of moisture on the underside of the plug which can cause relay fluctuation a few times before it evaporates and lets the relay drop out. This can be avoided by using a relay with lower sensitivity if the liquid is sufficiently conductive, or by insulating the electrodes, leaving 1/4 bare at the lower end. F. RELAY FLUCTUATES AT LOW LEVEL 1. WIRES REVERSED Wires to electrodes may be reversed. Terminal 15 should connect to high level (short) electrode and terminal 16 to low level (long) electrode. 2. RELAY HOLDING CIRCUIT If the internal holding circuit of the relay is shorted, it would cause the relay to fluctuate at the low level. To test the relay see Section 1. G. RELAY CONTINUOUSLY ENERGIZED AFTER ONE CYCLE 1. GROUNDED WIRE Wire from terminal 16 to the low level electrode may be shorted to the conduit or enclosure. 2. CRACKED PLUG The insulating plug on the low level (long) electrode may be cracked, allowing moisture to short the electrode to the enclosure. 3. SHORTED ELECTRODE The low level (long) electrode may be touching the stilling well or tank. H. RELAY CONTINUOUSLY ENERGIZED 1. GROUNDED WIRE Wire from terminal 15 to the high level (short) electrode may be shorted to the conduit or enclosure. 2. WET PLUG Dirt or moisture on the electrode plug for the high level electrode can short the electrode to the holder. Cleaning periodically or using a stilling well may help keep the plugs clean. If the problem persists it may be solved by using a relay with lower sensitivity if the liquid is sufficiently conductive, or by insulating the electrodes, leaving 1/4 bare at the lower end. 3. CRACKED PLUG The insulating plug on the high level relay may be cracked, allowing moisture to short the electrode to the enclosure. I. RELAY TEST To test the relay, disconnect leads from terminals 14, 15, 16, 7 and the solenoid wire to terminal 11. Connect a 120V lamp to 11 and 7. Connect one end of a 47,000 ohm resistor to 14. With 120V supplied to 11 and 12, placing jumpers as shown should give the indicated response: Jumper Resistor to 16 Leave Resistor to 16, Add Leave Resistor to 16, Remove Remove Resistor to 16 Response Lamp Off Lamp On Lamp On Lamp Off
28 THE JOHNSON LIQUI-MOVER PUMP CERAMIC ELECTRODE PLUGS PREVENTIVE MAINTENANCE TO: SUBJECT: All Sales Personnel ELECTRODE PLUGS The Ceramic Electrode Plugs supplied with Johnson Liqui-Mover pumps, are by the nature of their material, fragile. While it is true that they can operate at high temperatures and pressures with no adverse affect, any rough handling will be a source of future problems. To avoid operating difficulties always follow these tips to prevent damage to the Electrode Plugs. 1. Do not tap Upper Ceramic Insulator with any tool. 2. Do not use excessive force when tightening The Knurled Nut at the top of the Electrode Plug. 3. When tightening the Probe Rod to the Electrode Plug, do not apply torque to the Middle Collar on the plug, instead hold by coupling on bottom of Electrode Plug. 4. Do not bend Probe Rod after it is installed in Electrode Plug.
29 Assembly Instructions for Valve Packing Instructions Packing Gland Bull Ring Packing Stagger Ends Bull Ring Bushing 1. Remove worn packing. 2. Disconnect stem. Check surface for scratches and wear. 3. Install one bull ring, two piece packing (stagger ends), then one bull ring. 4. Reinstall packing gland. Tighten snug only. Do not overtighten. 5. Readjust valve seat with stem coupling. See instructions sent with valve. Stem Note: During operation of valve, packing will require adjustment periodically. Tighten only enough to prevent leakage in 1/8 turn increments. Packing Computer Bull Ring Packing Assembly No. No. Two Required Two Required V S10000 CSS TE CSS TK V S10025 CSS TE CSS TK V S10050 CSS TE CSS TK * V S10075 CSS TE CSS TK MATERIAL: Packing Crane Style K17-60 Teflon Filled Kevlar with Break-in Lube TEMPERATURE: -100 F to 600 F Bull Ring 1/16 Thick Virgin Teflon * For all 600 Series Solenoid Valves which use bracket SV-603-1, new packing nut SV ( ) must be furnished with new packing.
30 NOTES: FAC ELECTRODE LENGTHS ERC-ERS NEW STYLE LMH GAUGE GLASS LEVELS ELECTRODES GAUGE GLASS LEVELS SIZE TOP BOTTOM SHORT LONG TOP BOTTOM 5 N/A N/A N/A All levels shown are nominal dimensions. 2. All high level alarm electrodes 1 shorter than short electrode. 3. All low level alarm electrodes 1 longer than long electrode. 4. Holder meets NEMA 1 and NEMA 4 requirements for NEMA 7 applications An intrinsically safe relay must be used with this holder. 5. All ground electrodes are 2 longer than long electrode.
MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P
MANUAL NUMBER P-EFS-1 MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P TRAC Regulator Company Inc. 160 South Terrace Avenue Mount Vernon, New York USA 10550-2408 Phone: (914)
More informationTYPE E Main Valve Sizes 3 /8 through 12
Technical Data SD 3001E PRINTED IN U.S.A. SD 3001E/9709 SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 A B TYPE E MAIN VALVE FACE TO FACE DIMENSIONS C D E DIMENSIONS (inches)
More informationAdvantage-D. Operating Instructions and Maintenance Manual. Central Vacuum Systems (Expandable/Modular Models) (Ver.
Advantage-D Series 3 Central Vacuum Systems (Expandable/Modular Models) (Ver. 8/05) Operating Instructions and Maintenance Manual DESCRIPTION The Becker Advantage-D and Advantage-L central vacuum systems
More informationCIRCLE SEAL CONTROLS
CIRCLE SEAL CONTROLS ATKOMATIC SOLENOID VALVES INSTALLATION, MAINTENANCE, AND OPERATION INSTRUCTIONS 3000 SERIES Bronze, Normally Closed, Direct Lift Installation Instructions WARNING: These instructions
More informationArmstrong Double Duty 6 Steam Trap/Pump Combination Installation and Maintenance
Armstrong Double Duty 6 Steam Trap/Pump Combination Installation and Maintenance 119 Overview Warning: This bulletin should be used by experienced personnel as a guide to the installation and maintenance
More informationCrispin Valves Operating Guide. Crispin
Crispin Valves Operating Guide Crispin Since 1905 Crispin Multiplex Manufacturing Co. 600 Fowler Avenue Berwick, PA 18603 1-800-AIR-VALV T: (570) 752-4524 F: (570) 752-4962 www.crispinvalve.com sales@crispinvalve.com
More informationFarval. Dualine Installation System Start-Up. Bulletin DL300 BIJUR DELIMON INTERNATIONAL
Farval Dualine Installation System Start-Up Bulletin DL300 BIJUR DELIMON INTERNATIONAL 2685 Airport Road Kinston, NC 28504 Tel. 800-227-1063 Fax: 252-527-9232 website: www.bijurdelimon.com DC1-1 SECTION
More information4 - Way Control 4 - Way Control 4 - Way Control with lock
INSTALLATION / OPERATION / MAINTENANCE 1. DESCRIPTION MODEL 0-02 (Full Internal Port) Powertrol Valve This manual contains information for installation, operation and maintenance of the Cla-Val Co. 0-02
More informationSeries 20 Installation Instructions
Series 20 Installation Instructions Installation Instructions and field service checklist Read these instructions carefully. Failure to follow them could result in a fire or explosion causing property
More informationCIRCLE SEAL CONTROLS
CIRCLE SEAL CONTROLS ATKOMATIC SOLENOID VALVES INSTALLATION, MAINTENANCE, AND OPERATION INSTRUCTIONS 13000 SERIES Stainless, Normally Closed, Direct Lift, 3-Way Valve Installation Instructions WARNING:
More informationPT-516 Pumping Trap Installation and Maintenance
PT-516 Pumping Trap Installation and Maintenance IB-104-B This bulletin should be used by experienced personnel as a guide to the installation and maintenance of the PT-516 Pumping Trap or Pumping Trap
More informationCla-Val. Service Training Manual. Simple solutions plus learning with a purpose
Cla-Val Service Training Manual Simple solutions plus learning with a purpose 5 Application Series Section General Identify What Valve You Have 5-1 Rate of Flow 40 Series 5-2 Pressure Relief 50 Series
More informationBMF TROUBLESHOOTING GUIDE
BMF TROUBLESHOOTING GUIDE This document contains troubleshooting guidelines for PEP's standard BMF filters with pumps. REFERENCE DOCUMENTS: W-X-0039 BMF Electrical Wiring Drawing WP0011 BMF Control Panel
More informationMODEL NUMBER: MEDIUM DUTY ONBOARD AIR SYSTEM
MODEL NUMBER: 10003 MEDIUM DUTY ONBOARD AIR SYSTEM IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using
More informationIdeal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators
I & M Mark (/ ) 0 Wasson Road Cincinnati, OH 0 USA Phone --00 Fax -8-00 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark Pressure Regulators Warning: Jordan Valve
More informationTechnical Data P3 PISTON POWER PUMP NON-ELECTRIC CONDENSATE PUMP SD 9952B
Technical Data SD 9952B SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NEW YORK, 12586-2035 P3 PISTON POWER PUMP NON-ELECTRIC CONDENSATE PUMP Pressures To 250 PSIG (20.7 barg) Temperatures
More informationPAGE 1. TES Operation & Testing Guidelines: Tes Trouble shooting
PAGE 1 This document outlines questions to ask and components to check during TES troubleshooting. More detailed troubleshooting procedures are available in the TES Troubleshooting Guide. 1. Flow Light
More informationINSTRUCTIONS FOR INSTALLATION, START-UP, AND OPERATION
30/8.5.1 INSTRUCTIONS FOR INSTALLATION, START-UP, AND OPERATION VKP PILOT OPERATED PRESSURE REDUCING VALVE 12501 Telecom Drive, Tampa, Florida 33637 1. Introduction The Class VKP pilot-controlled steam
More informationDIFFERENTIAL PRESSURE RELIEF REGULATOR TYPE A4AL Port Size 3/4"- 4" (20-100mm) For Ammonia, R-22, R134a, R404a, R507 and other common refrigerants.
DIFFERENTIAL PRESSURE RELIEF REGULATOR TYPE A4AL Port Size 3/4"- 4" (20-100mm) For Ammonia, R-22, R134a, R404a, R507 and other common refrigerants. FEATURES Pilot operated characterized Modulating Plug
More informationPurging Air From Divider Block Lubrication Systems
FROST ENGINEERING SERVICE Purging Air From Lubrication Systems A D I V I S I O N O F G E C S E Y S A L E S & S E R V I C E DESCRIPTION Divider block lubrication systems operate correctly only when all
More informationPrincipals of Operation... 1 Rotary Vane Priming Pump VPE and VPES... 2 Rotary Vane Priming Pump VPO and VPOS Priming Valve...
Priming Systems Installation Priming Systems Operation & Maintenance Form No. F 1031 Section 2312 Issue Date 10/07/94 Rev. Date 02/27/06 Table of Contents Illustrations Principals of Operation...........................
More informationINSTALLATION & MAINTENANCE MODEL mm
MODEL 65-25mm INSTALLATION INSTRUCTIONS CAUTION: Installation of Backflow Preventers must be performed by qualified, licensed personnel. The installer should be sure the proper device has been selected
More informationInstructions for Installing and Operating Clark Reliance EA100 Series Levalarm
Section: R500.532F Bulletin: 532F Date: 7/1/2015 Supersedes: 532E Instructions for Installing and Operating Clark Reliance EA100 Series Levalarm This manual covers the following model numbers: EA100D,
More information4" PPF-P Pilot-Operated Pressure Powered Pump
INSTALLATION AND MAINTENANCE INSTRUCTIONS IMI 5.220 January 1996 4" PPF-P Pilot-Operated Pressure Powered Pump Operating Pressure Range 25 to 150 psi (1.7 to 10.3 bar) The 4" PPF-P incorporates a spring-loaded,
More informationMODEL 106/206-PG POWER OPERATED GLOBE VALVE Sizes 1/2" to 8" (106-PG) 3" to 10" (206-PG) Installation, Operating and Maintenance Instructions
MODEL 106/206-PG POWER OPERATED GLOBE VALVE Sizes 1/2" to 8" (106-PG) 3" to 10" (206-PG) Installation, Operating and Maintenance Instructions DESCRIPTION: This valve is the basic component used for most
More informationDELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : VALVE OPERATION TRIM DESCRIPTION DESCRIPTION PRESSURE THREADED OPENING
DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : NOMINAL SIZE MATERIAL MAXIMUM SERVICE PRESSURE 200, 150, 100, 80 & 50NB Cast Iron 12 Bar (175 PSI) THREADED OPENING MOUNTING FACTORY HYDROSTATIC TEST PRESSURE
More informationAir Trap TATSU2. Copyright 2013 by TLV CO., LTD. All rights reserved ISO 9001/ ISO M-02 (TATSU2) 7 August 2013.
172-65177M-02 (TATSU2) 7 August 2013 ISO 9001/ ISO 14001 Manufacturer Kakogawa, Japan is approved by LRQA LTD. to ISO 9001/14001 Air Trap TATSU2 Copyright 2013 by TLV CO., LTD. All rights reserved 1 Contents
More informationVal-Matic Air / Oil Hydraulic Panel Pump Control System. Operation, Maintenance and Installation Manual
Manual No. 5AOP-OM1-2 Val-Matic Air / Oil Hydraulic Panel Pump Control System Operation, Maintenance and Installation Manual INTRODUCTION... 1 RECEIVING AND STORAGE... 1 DESCRIPTION OF OPERATION... 1 INSTALLATION...
More informationINSTALLATION AND OPERATING MANUAL
Publication T3-76, Rev. 1 Dated: May 9, 21 INSTALLATION AND OPERATING MANUAL MODEL: T3-I TURBOTWIN Engine Air Starter AN96-419 From Tech Development Inc 68 Poe Ave. Dayton OH 45414 Tel: (937) 898-96 Fax:
More informationINSTALLATION AND OPERATING MANUAL
Dated: May 10, 2001 INSTALLATION AND OPERATING MANUAL MODEL: T30-Y TURBOTWIN Engine Air Starter From Tech Development Inc AN96-425 6800 Poe Ave. Dayton OH 45414 Tel: (937) 898-9600 Fax: (937) 898-8431
More informationDWS 41. Installation Data 44 Performance Specs DWS & DW-PRV Series
IRRIGATION Title Description Details Page Intro 3 2000 Series 4 Model 2000 Solenoid 1 3 12 Model 2000 Solenoid 4 8 15 Model 2030 Low Power Solenoid 1 3 17 Model 2030 Low Power Solenoid 4 8 19 Model 2160
More informationFLOOD PROTECTION SHUT DOWN VALVE (3 and smaller)
FLOOD PROTECTION SHUT DOWN VALVE ( and smaller) 01/10 2 6 To Floor Drain L X JB11 4 FS99 5 Installed upstream of Reduced Zone Backflow Preventer. Normally Open Valve - Closes when discharge from RPZ Relief
More informationEasytork Solenoid Valve IOM
Easytork Solenoid Valve IOM General This installation document is to be read in conjunction with the Easytork Vane Actuator IOM. Description The Easytork Solenoid Valve ( ESV ) series is intended for the
More informationWALKIE HIGH LIFT HYDRAULIC SYSTEM
WALKIE HIGH LIFT HYDRAULIC SYSTEM W30-40ZA [B453]; W20-30ZR [B455]; W25-30-40ZC [B454] PART NO. 1524251 2000 SRM 1025 SAFETY PRECAUTIONS MAINTENANCE AND REPAIR When lifting parts or assemblies, make sure
More informationInstallation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps
Installation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps EI-700-008 Rev -- Table of Contents Safety Guidelines 3 Caution 4 Wiring 4 Maintenance 4 Nameplate format 4 Prior to Operation
More informationRELEASING PRESSURE IN THE HYDRAULIC SYSTEM,
Testing And Adjusting Introduction NOTE: For Specifications with illustrations, make reference to SPECIFICATIONS for 225 EXCAVATOR HYDRAULIC SYSTEM, Form No. SENR7734. If the Specifications are not the
More informationSECTION H3 TRAYMASTER SERIES DEAERATORS
SECTION H3 TRAYMASTER SERIES DEAERATORS SAMPLE SPECIFICATIONS PART 1 GENERAL... H3-12 1.1 Packaged Deaerator Specification... H3-12 PART 2 PRODUCTS... H3-12 2.1 Deaerator... H3-12 2.2 Deaerator Vessel...
More informationAPT10-2 Automatic Pump Trap
6120050/3 IM-P612-18 ST Issue 3 APT10-2 Automatic Pump Trap Installation and Maintenance Instructions 1. General safety information 2. Product information 3. Installation Closed loop steam systems only
More informationWEBER CARBURETOR TROUBLESHOOTING GUIDE
This guide is to help pinpoint problems by diagnosing engine symptoms associated with specific vehicle operating conditions. The chart will guide you step by step to help correct these problems. For successful
More informationPRESSURE RELIEF VALVE
PRESSURE RELIEF VALVE INSTRUCTIONS Installation - Operation - Inspection - Maintenance 4" - 36" MODEL 50RWR Pressure Relief Valve Globe Flat Seat Style ROSS VALVE Mfg. Co., Inc. PO BOX 595, TROY, NY 12181
More informationTroubleshooting the Transmission Hydraulic System
Testing and Adjusting IT28F INTEGRATED TOOLCARRIER POWER TRAIN Testing And Adjusting Introduction Reference: For Specifications with illustrations, refer to SENR5974, IT28F Integrated Toolcarrier Power
More informationSingle Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-40 RX-63 RX-100
V acuum Pumps Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-40 RX-63 RX-100 www.republicsales.com Revised 02.15 2015 Republic Sales & Manufacturing Single Stage Rotary Vane
More informationLevalarm Gold. Installation, Operation, & Maintenance Instructions R500.E253A 03/16/2016
Installation, Operation, & Maintenance Instructions R500.E253A 03/16/2016 Levalarm Gold STORAGE AND HANDLING The Reliance Levalarm Gold meets or exceeds all applicable specifications when shipped from
More informationINSTALLATION AND OPERATING
Publication T5-704, Rev. 4 Dated: November 1, 2006 INSTALLATION AND OPERATING MANUAL T50-P TURBOTWIN Engine Air Starter AN 99-448 TABLE OF CONTENTS Section Subject Page 1.0 General Information. 1 2.0 Orientation
More informationCOOKSON OWNER'S MANUAL
COOKSON OWNER'S MANUAL FDO-A10 INDUSTRIAL DUTY FIRE DOOR OPERATOR R L I S T E D 3040233 US CONTROL PANEL SERIAL# OPERATOR SERIAL# 9001.DWG ECN 0959 REV 4 SPECIFICATIONS MOTOR TYPE:...INTERMITTENT HORSEPOWER:...1/8
More informationSingle Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-10 RX-21 RX-25
V acuum Pumps Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-10 RX-21 RX-25 www.republicsales.com Revised 10.14 2014 Republic Sales & Manufacturing Single Stage Rotary Vane Vacuum
More information331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH
331-SV User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER Ashland, OH 800-363-5842 WWW.PRIMEXCONTROLS.COM Warranty void if panel is modified. Call factory with servicing
More informationR & D SPECIALTIES ROTROL I USER'S MANUAL
R & D SPECIALTIES ROTROL I USER'S MANUAL TABLE OF CONTENTS INTRODUCTION...2 SPECIFICATIONS...2 CONTROLS AND INDICATORS...3 TIME DELAYS...4 INSTALLATION...5 SYSTEM OPERATION...9 TROUBLESHOOTING...13 OPTIONAL
More informationINSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS 377 Float Cage / 326L & 322L lever Valves TABLE OF CONTENTS Overview... Cover General Information... Cover Operation... 4 Installation...4-6 Maintenance...
More informationInstallation, Operation & Maintenance Instructions
Installation, Operation & Maintenance Instructions 377 Float Cage / 326L & 322L lever Valves TABLE OF CONTENTS Overview... Cover General Information... Cover Operation... 4 Installation...4-6 Maintenance...
More informationLEAD FREE * LFF113RFP Flood Protection Shut Down Valve
Technical Bulletin TB-ACV-LFF11RFP LEAD FREE * LFF11RFP Flood Protection Shut Down Valve Installed upstream of Reduced Zone Backflow Preventer. Normally Open Valve - Closes when continuous discharge from
More informationTechnical Data TYPE A SERIES AIR ADJUSTED PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4011 OPERATING PRINCIPLE
Technical Data SD 4011 SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE A SERIES AIR ADJUSTED PILOT PRINTED IN U.S.A. SD 4011/9504 Type A or A83 (wt 6 lb) Type A53 or A 85
More informationSERVICE PARTS LIST SPECIFY CATALOG NO. AND SERIAL NO. WHEN ORDERING PARTS 13 HP DIRECT DRIVE PRESSURE WASHER CATALOG NO
SPECIFY CATALOG NO. AND SERIAL NO. WHEN ORDERING PARTS HP DIRECT DRIVE PRESSURE WASHER CATALOG NO. 555-22 SERVICE PARTS LIST STARTING SERIAL NUMBER B06A REVISED BULLETIN PAGE OF BULLETIN NO. 5-20-000 DATE
More informationSECOND GENERATION Use this guide with unit serial number prefix beginning with BWF using Terra Power separator.
Technical Information and Diagnostic Guide for SECOND GENERATION Use this guide with unit serial number prefix beginning with BWF using Terra Power separator. This guide will assist you in becoming more
More informationINSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM)
INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM) IOM-1088 03-16 Model 1088 Vacu-Gard Blanketing Valve ISO Registered Company SECTION I I. DESCRIPTION AND SCOPE The Model 1088 Vacu-Gard is a tank blanketing
More informationTECHNICAL DATA 1-1/2 (dn40)
July 1, 2011 Deluge Valves 209a DESCRIPTION The Viking Model E-3 1-1/2 Deluge Valve is a quick-opening, differential type flood valve with a rolling diaphragm clapper. The deluge valve is used to control
More informationI & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1/2-1 )
I & M Mark 8 Series 30 Wasson Road Cincinnati, OH 4509 USA Phone 53-533-5600 Fax 53-8-005 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark 8 Control Valves (/ -
More informationMaintenance Manual Reduced Pressure Assembly Models 860 & 880V 2 1 /2" 10"
IOM-F-860_880V INSTALLATION, OPERATION, MAINTENANCE Maintenance Manual Reduced Pressure Assembly Models 860 & 880V 2 1 /2" 10" 860 880V Standard Configuration 880V Vertical Configuration INDEX Vandalism..............................................
More informationModel &
PumpAgents.com - Click here for Pricing/Ordering Model 31765-0092 & 31765-0094 Dual Sensor Max VSD WATER PRESSURE SYSTEM AUTOMATIC TWO STAGE WATER SYSTEM WITH PUMPGARD STRAINERS IDEAL FOR PLEASURE AND
More informationCopeland Screw TM Compressors
Copeland Screw TM Compressors Mechanical Guidelines for SHL & SHM Models using ESC-201 Control System Contents: Start-Up Procedure Operating Specifications Maintenance Trouble Shooting Guidelines Start-up
More informationSINGLE ACTING ALTITUDE VALVE
SINGLE ACTING ALTITUDE VALVE INSTRUCTIONS Installation - Operation - Inspection - Maintenance 4" - 36" ROSS MODEL - 40AWR THROTTLING, SINGLE ACTING ALTITUDE VALVE Globe Flat Seat Style ROSS VALVE Mfg.
More informationDO NOT INSULATE BELOW THIS LINE. * For sizes 1/2" to 1 1/2" add 2 1/2" to 'C' dimension.
428 Jones Boulevard Limerick Airport Business Center Pottstown, PA 19464 Phone: (610)495-5131 ax: (610)495-5134 www.watsonmcdaniel.com PAGE 28 INSTRUCTION PART NO. 2315400 C.R.3500 REV. 10 SIZE C B CENTER
More informationHeating and Gas Installations - December 2014
This is an example of good practice maintenance specifications. It is not exhaustive and should only be used to assist with facilities management or specification of a maintenance contract. Emergency Gas
More informationDSTP20: Fuel Transfer Pump
DSTP20: Fuel Transfer Pump Up To 20 GPM Integral inlet screen 2 Male NPT On Bung Adapter Security: Pump equipped for padlocking Ball Bearing Construction, No Lubrication Required Dimensions: 14" wide x
More informationINSTALLATION AND SERVICE INSTRUCTIONS AND REPAIR PARTS LIST FOR MODELS K4RP & K4VP SUBMERSIBLE SOLIDS-HANDLING SEWAGE PUMPS
471 US Hwy 250 East, Ashland, Ohio 44805 PH: 419-207-9400 FX: 419-207-8031 INSTALLATION AND SERVICE INSTRUCTIONS AND REPAIR PARTS LIST FOR MODELS K4RP & K4VP SUBMERSIBLE SOLIDS-HANDLING SEWAGE PUMPS 10/2014
More informationNECO Pumping Systems
INSTALLATION OPERATION & MAINTENANCE INSTRUCTIONS For Your NECO Pumping Systems PACKAGED CIRCULATING SYSTEM THIS COMPLETELY ASSEMBLED, TESTED, PACKAGED CIRCULATING SYSTEM IS OF THE HIGHEST QUALITY AND
More informationESE Series Cast Iron Sewage Pumps
Owner s Manual ESE Series Cast Iron Sewage Pumps TABLE OF CONTENTS General Safety.................... 2 Specifications..................... 3 Installation.................... 4 & 5 Troubleshooting...................
More informationI & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1-1/2-2 )
I & M Mark 8 Series 0 Wasson Road Cincinnati, OH 4509 USA Phone 5-5-5600 Fax 5-8-005 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark 8 Control Valves (-/ - ) Warning:
More informationSTOP CITY PRESSURE BOOSTER PUMP INSTRUCTION MANUAL
CITY PRESSURE BOOSTER PUMP INSTRUCTION MANUAL MODEL #VP05, VP10 C US NSF/ANSI 372 255405 For loose, missing or damaged parts, or if the unit does not seem to be operating properly, please call before returning
More informationPROCESS ELECTRONICS CORPORATION
MINIVERTER MANUAL PROCESS ELECTRONICS CORPORATION 100 BRICKYARD ROAD MOUNT HOLLY, NORTH CAROLINA 28120 TELEPHONE (800) 421-9107 FAX (704) 827-9595 SALES@PECRECTIFIER.COM WWW.PECRECTIFIER.COM SOLID STATE
More informationTechnical Data SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 1520 SERIES 2000 DIRECT & REVERSE ACTING
Technical Data SD 520 PRINTED IN U.S.A. SD 520/98 SPENCE ENGINEERING COMPANY, INC. 50 COLDENHAM ROAD, WALDEN, NY 2586-205 SERIES 2000 DIRECT & REVERSE ACTING DIRECT & REVERSE ACTING DIMENSIONS inches (mm)
More informationTechnical Data TYPE T124 & T134 TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4512A
WATTS INDUSTRIES, INC. Technical Data SD 4512A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 PRINTED IN U.S.A. SD 4512A/9806 T124/T134 PILOT FRONT VIEW 2 1 /16 F 5 7 /8 2 3
More informationSTEP-BY-STEP INSTALLATION GUIDE
Battery Backup System STEP-BY-STEP INSTALLATION GUIDE Operating Instructions & Parts Manual ESP25 Please read and save these instructions. Read carefully before attempting to assemble, install, operate
More informationI & M 8000 Series. Ideal Installation Schematic. Preferred Installation. Trouble Shooting
I & M 8000 Series 3170 Wasson Road Cincinnati, OH 45209 USA Phone 513-533-5600 Fax 513-871-0105 lowflow@richardsind.com www.lowflowvalve.com Installation & Maintenance Instructions for 8000 Series Low
More informationAIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST
AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST BELT TYPE IMPORTANT PLEASE MAKE CERTAIN THAT THE PERSON WHO IS TO USE THIS EQUIPMENT CAREFULLY READS AND UNDERSTANDS THESE INSTRUCTIONS BEFORE STARTING
More informationM-3025CB-AV Fuel Pump
SAVE THESE INSTRUCTIONS M-3025CB-AV Fuel Pump Owner s Manual TABLE OF CONTENTS General Information... 2 Safety Instructions... 2 Installation... 3 Operation... 4 Maintenance... 4 Repair... 5 Troubleshooting...
More informationHydraulic Pumping System
Hydraulic Pumping System Easy-Kleen Pressure Systems LTD. 41 Earnhardt Road Sussex Corner, NB E4E 6A1 1 800 315 5533 1 HD SERIES PUMPING SYSTEM WITH HYDRAULIC MOTOR: OPERATION 1. Place unit on level and
More informationDUST COLLECTOR (BOTTOM REMOVAL BAG & CAGE) INSTALLATION AND OPERATING INSTRUCTIONS
4080 SE International Way. Suite B110, Milwaukie, OR 97222 (503) 654-0867 Fax: (503) 654-4671 email: ftech@filtertechnologyltd.com www.filtertechnologyltd.com DUST COLLECTOR (BOTTOM REMOVAL BAG & CAGE)
More informationCUSTOM COMBINATION AIR VALVE
INSTALLATION / OPERATION / MAINTENANCE CUSTOM COMBINATION AIR VALVE INTRODUCTION This manual will provide you with the information to properly install and maintain this valve to ensure a long service life.
More informationDeep Well Pump Control Valve
MODEL 61-02 661-02 Deep Well Pump Control Valve Prevent Surges in Pipelines Simple Hydraulic Operation Adjustable Opening & Closing Speeds Solenoid Control Can Be Operated Manually Proven Reliable Design
More informationVERTICAL MULTI-STAGE CENTRIFUGAL PUMPS
Installation and Operating Instructions VERTICAL MULTI-STAGE CENTRIFUGAL PUMPS Models 1, 3, 5, 10, 15, 20, 32, 45, 64, 90 1. Model numbering and nameplate format 1.1 Model numbering Example: SBI / SBN
More informationOPEN/CLOSE SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION
SERIES 1000-X OPEN/CLOSE SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION Publication S1000X-110 VER0215-1 For information on this product and
More informationFloat Dynamic Steam Trap J10
172-65237MA-01 (J10) 12 June 2015 ISO 9001/ ISO 14001 Manufacturer Kakogawa, Japan is approved by LRQA LTD. to ISO 9001/14001 Float Dynamic Steam Trap J10 Copyright 2015 by TLV CO., LTD. All rights reserved
More informationCV Control Valves Installation and Operation Manual
CV1500 - Control Valves Installation and Operation Manual 652-EN Overview Warning: This bulletin should be used by experienced personnel as a guide to the installation of the Armstrong CV1500 Control Valve.
More informationWelker Sampler. Installation, Operation, & Maintenance Manual. Model GSS-4HP
Installation, Operation, & Maintenance Manual Welker Sampler Model GSS-4HP The information in this manual has been carefully checked for accuracy and is intended to be used as a guide to operations. Correct
More informationPAGE Both power cords must be connected & powered to operate the E-TES 120.
PAGE 1 This document outlines questions to ask and components to check during E-TES 120 troubleshooting. More detailed troubleshooting procedures are available in the E-TES 120 Troubleshooting Guide. 1.
More informationGP-2000 : Trouble Shooting. Cause of problems
VOL: MA-GP2000-2 Troubleshooting GP-2000 Technical Knowledge GP-2000 : Trouble Shooting Cause of problems 1: s related to other factors 2: s on the pressure reducing valve A : Reduced pressure exceed specified
More informationINSTALLATION/OPERATION/MAINTENANCE INSTRUCTIONS FOR ARCHON MODELS WD2010L, WD2010, WD2010H WASHDOWN STATIONS. ARCHON Industries, Inc.
ARCHON Industries, Inc. Washdown Stations Models WD2010L, WD2010, WD2010H Installation / Operation / Maintenance Instructions 1 This manual has been prepared as an aid and guide for personnel involved
More informationDISCONTINUED. Installation. Aerada 900 Series Futura Faucet. With Accu-Zone (AZ) Infrared Control
Aerada 900 Series Futura Faucet With Accu-Zone (AZ) Infrared Control BRADLEY SC A S53-141 4" Centerset S53-148 4" Centerset, no Solenoid Valve S53-186 4" Centerset with 8" Trim Plate S53-285 Centershank
More informationTECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet)
Flow Control 500a DESCRIPTION The Viking 1-1/2 is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The can be used to facilitate manual or automatic on/off
More informationINSTRUCTION MANUAL INSTALLATION OPERATION TROUBLESHOOTING MAINTENANCE PRESSURE RELIEF VALVE WITH SURGE ANTICIPATION (HYDRAULIC) FEATURE MODEL 50RWR-A
INSTRUCTION MANUAL INSTALLATION OPERATION TROUBLESHOOTING MAINTENANCE PRESSURE RELIEF VALVE WITH SURGE ANTICIPATION (HYDRAULIC) FEATURE MODEL 50RWR-A Please reference the valve Serial Number whenever ordering
More informationProposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.
Model RPHBM Hydrant Backflow Meter Installation Testing Maintenance Instructions CAUTION: Installation of Backflow Preventers must be performed by qualified, licensed personnel. The installer should be
More informationOn Board Diagnostics II A PCED
Page 1 of 8 HX18 DTC P0446 OR P1450: CHECK FOR VISUAL CAUSES OF EXCESSIVE FUEL TANK VACUUM Continuous Memory Diagnostic Trouble Code (DTC) P0446 or P1450 indicates that Self-Test has detected the Evaporative
More informationOperation and Maintenance Manual
BM / BMA Hydrometers ½ Operation and Maintenance Manual i This manual is intended for use by the users of this equipment. The information contained herein is the property of the Arad Ltd. Dalia and may
More informationIndustrial Turbo Meters, Sizes 2" through 6"
Industrial Turbo Meters Sizes 2" through 6" TUR-UM-00530-EN-19 (October 2014) User Manual Industrial Turbo Meters, Sizes 2" through 6" User Manual CONTENTS Scope of the Manual 5 Specifications 5 Product
More informationINSTRUCTION MANUAL IM245. RGS2012E1 S or E Retrofit Kit SUBMERSIBLE GRINDER PUMP INSTALLATION, OPERATION AND TROUBLESHOOTING MANUAL
INSTRUCTION MANUAL IM245 RGS2012E1 S or E Retrofit Kit SUBMERSIBLE GRINDER PUMP INSTALLATION, OPERATION AND TROUBLESHOOTING MANUAL SAFETY INSTRUCTIONS TO AVOID SERIOUS OR FATAL PERSONAL INJURY OR MAJOR
More informationMODEL SCA Installation and Operation Manual Important:
MODEL SCA Installation and Operation Manual Important: This manual contains specific cautionary statements relative to worker safety. Read this manual thoroughly and follow as directed. It is impossible
More informationFABER BURNER ROUTINE MAINTENANCE
FABER BURNER ROUTINE MAINTENANCE Version 2016 The Faber burner is designed for minimal maintenance; however, the frequency and quantity of maintenance that is required depends upon many factors which vary
More informationQ= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications
1 of 9 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can be used to facilitate manual
More informationTECHNICAL INSTRUCTIONS #11 REGULATOR Single Seat - Bronze Trim - Composition Disc
Page 1 TI595CD A Watts Industries Co. TECHNICAL INSTRUCTIONS #11 REGULATOR Single Seat - Bronze Trim - Composition Disc VALVE DESCRIPTION TABLE OF CONTENTS The Powers #11 Regulator is a self-actuating
More information