Operating Instructions for Models Cobra and Lynx Air and Duct Leakage Testers: (Inlet Damper and Digital Gauges)

Size: px
Start display at page:

Download "Operating Instructions for Models Cobra and Lynx Air and Duct Leakage Testers: (Inlet Damper and Digital Gauges)"

Transcription

1 Operating Instructions for Models Cobra and Lynx Air and Duct Leakage Testers: (Inlet Damper and Digital Gauges)

2 Table of Contents Introduction Introduction.. 2 Safety Precautions Safety Precautions. 2 Assembly Assembly - Included parts 3 Assembly - Installing orifice plate. 3 Assembly - Joining orifice tube sections.. 4 Assembly - Connecting pressure tubing.. 5 Assembly - Calibration certificate. 5 Duct Leakage Testing Operating the Equipment Pre-test Checklist. 6 Extension Cord Requirements... 6 Orifice Plate Flow Ranges.. 7 Preparing Duct System for Testing 8 Connect Flexible Duct to Orifice Tube.. 8 Connect Flexible Duct to Duct System. 8 System Test Pressure Connection. 8 Duct Leakage Test Setup (SUPPLY). 9 Duct Leakage Test Setup (RETURN/EXHAUST)... 9 Zero the Pressure Gauges.. 10 Starting the Blower 10 Obtaining System Test Pressure. 11 Determining Leakage Rate Troubleshooting Zero reading on DUCT SYSTEM gauge Zero reading on ORIFICE TUBE gauge.. 15 Can t obtain system test pressure ORIFICE TUBE gauge reading maxed out

3 Introduction These operating instructions are for ORIFLOW models Cobra and Lynx duct leakage testers outfitted with the optional digital gauges. Both models are exactly the same as the standard Cobra and Lynx testers with the exception that both are outfitted with digital pressure gauges instead of Magnehelic gauges. Your duct leakage tester requires minimal assembly which is described in the next section. Safety Precautions Before operating the tester, read the following safety precautions: DO NOT operate the tester in the rain, DO NOT operate the tester while it is near or in water, DO NOT operate the tester with a damaged electrical cord or plug, DO NOT remove the inlet safety screen, DO NOT touch the blower wheel when the unit is plugged in, DO NOT look into the discharge end of the tester when the unit is plugged in, DO NOT use the tester as a ladder or step stool, DO NOT allow children near the tester, DO use an extension cord of the proper gauge (see Table 2), DO use the proper voltage and line frequency listed on the motor nameplate, DO lock the caster when the tester is positioned horizontally, DO use the tester on level ground, DO secure the tester when transporting it, DO wear proper hearing protection, safety glasses and work gloves, DO seek assistance when lifting the tester (e.g., loading onto truck, going up or down stairs). 2

4 Assembly Included Parts Upon arrival, your Cobra or Lynx leak tester will come preassembled except for the top half of the orifice tube. See Table 1 for the individual items that are included with your tester. Table 1 List of Loose Parts Item Quantity Comment Leak tester 1 Orifice tube section 1 Hardware wing nuts 6 Hardware - bolts 6 Fully assembled except for orifice and orifice tube section. Section will be loose and wrapped to protect during shipment. Must attach to bottom half of orifice tube using included wing nuts and bolts. See instructions in steps below. Use with included bolts to join the two sections of orifice tube together. Use with included wing nuts to join the two sections of orifice tube together. Calibration certificate 1* This should be already mounted to the front of your testers. Flex-duct 12.5 ft This will be coiled around the rear of the tester. Worm gear clamp 1 Use this to connect flex-duct to orifice tube end. * you will receive as many calibration certificates as the number of orifice plates ordered; one certificate goes with each orifice plate (testers come with choice of one orifice plate; other plates may be purchased separately). Assembly - Place orifice plate between tube sections as shown in Figure 1 and Figure 2. Figure 1 Placing Orifice Plate 3

5 Figure 2 Install tube section Using the included wing nuts and bolts, join the two orifice tube halves together. Figure 3 Joining Orifice Tube Sections together Connect the pressure tubing from the pressure gage marked ORIFICE TUBE to the pressure tap marked P2 located on the top half of the orifice tube (see Figure 4). Notice that the other pressure tubing from this gauge will already be connected to the bottom half of the orifice tube on the pressure port marked P1. 4

6 P2 Figure 4 Connecting Loose Tubing to Pressure Tap Finally, refer to the correct calibration certificate that matches the orifice plate that was installed. Each plate has an engraved serial number that matches the serial number listed on the corresponding calibration certificate. You are now ready to perform a duct leakage test. See the next section for the proper steps to perform duct leakage testing. 5

7 Duct Leakage Testing Operating the Equipment Pretest Checklist Go through the following list BEFORE transporting equipment to the jobsite: 1. Do you have adequate voltage and amperage for your tester? 110V/20A is preferred but 110V/15A is adequate (see Starting the Blower section). 2. If you need an extension cord, is it the proper gauge? See Table 2 below for typical requirements for a blower requiring 15 amps of current at 110 volts. Table 2 Recommended Extension Cord Gauge Extension Cord Required Gauge Length (feet) Make sure you have enough flexible-duct with your tester for the job. Each tester includes 12.5 feet, which is enough for most applications. Extra lengths of flexible-duct are available at 4. Determine the allowable leakage for the project using data given. To help with your calculations, use ORIFLOW s free online programs to make these calculations ( Calculations are done for either of the two typical specifications: percentage of system flow, or leakage class. 5. After determining the allowable leakage, make sure that value is located on your included calibration certificate. If not, you probably will need a different orifice plate. See the following tables to see the capacities of each orifice plate with both leak testers (Cobra and Lynx). 6

8 Table 3 Tester Capacities using the 1-inch Orifice Plate COBRA System Static Minimum LYNX Tester Tester Pressure Flow Rate* Maximum Maximum (in.wg.) (cfm) Flow Rate Flow Rate (cfm) (cfm) Table 4 Tester Capacities using the 2-inch Orifice Plate COBRA System Static Minimum LYNX Tester Tester Pressure Flow Rate* Maximum Maximum (in.wg.) (cfm) Flow Rate Flow Rate (cfm) (cfm) Table 5 Tester Capacities using the 3-inch Orifice Plate COBRA System Static LYNX Tester Minimum Tester Pressure Maximum Flow Rate* Maximum (in.wg.) Flow Rate (cfm) Flow Rate (cfm) (cfm) Table 6 Tester Capacities using the 4-inch Orifice Plate COBRA LYNX Tester System Static Minimum Tester Maximum Pressure Flow Rate* Maximum Flow Rate (in.wg.) (cfm) Flow Rate (cfm)

9 Preparing Duct System for Testing Cap off all ends of system using clear plastic and duct tape or duct end caps. Make sure you test the part of the duct system that leakage testing is required. Usually, this is from the system fan up to, but not including, the VAV boxes (terminal units). Connect Flexible Duct to Orifice Tube See the figures below for securing one end of the flexible duct to the orifice tube. Note that the worm-gear clamp should be slid over the duct before connecting it to the orifice tube. Slide the flexible duct so that it overlaps the orifice tube1 to 2 inches, and tighten clamp using a 5/16-inch nut driver. Figure 5 Installing Flex-Duct on Tube Figure 6 Tightening Clamp Connect Flexible Duct to Duct System Find a convenient location in the duct system where the flexible duct from the leakage tester will connect to. Make sure that the connection where you connect the flexible duct is a sturdy, sealed tight connection. You don t want to create a leaky connection right where the tester is supplying air into the system. System Test Pressure Connection So that you know what static pressure the system is being tested at, you need to drill a hole at least 3 feet away from the flex-duct connection. Drill a 3/8-inch diameter hole and insert the pressure tubing from the gauge marked Duct System. Note both testers come with at least 20 feet of pressure tubing. Insert the pressure tubing from the DUCT SYSTEM gauge so that 6 to 12 inches of tubing is inside the duct system. Using putty or duct tape, seal the connection. See Figure 7 showing a duct leakage test setup for SUPPLY systems. Refer to Figure 8 for the test setup required to measure air leakage of a RETURN/EXHAUST system. 8

10 Figure 7 Duct Leakage Test for a SUPPLY System Figure 8 Duct Leakage Test for a RETURN/EXHAUST System 9

11 Zero the Pressure Gauges Before you run the tester, make sure both gauges read zero pressure when the unit is off and there is no pressure being applied to the digital gauges. If either gauge requires zeroing, follow these steps: With the gauge reading pressure (home position), press and hold the MENU button, Press the button until the display shows the AdU MENU, Press the E button to show the submenu, Auto ZERO, For accurate zeroing of the gauge, do not apply any pressure, With the display reading Auto ZERO, press the E button, the display will blink, Press the E key again to complete the auto-zero function. Starting the Blower Before operating your duct leakage tester, make sure you have access to 110V, 15A power. Doing this before starting the blower will insure that the blower sees the least amount of load upon startup. Note that you may trip the circuit breaker the time you turn the blower on. A simple way around this is to spin the impeller of the fan before turning the blower on. DO NOT use fingers or hand. Before switching the blower on, make sure the inlet damper is fully closed. Figure 9 Shut damper closed before starting blower (Cobra shown). 10

12 Obtaining System Test Pressure Adjust fan Inlet slowly to obtain system test pressure. Keep your eye on the DUCT SYSTEM gauge while opening the fan inlet. When you have reached the required system static pressure, lock or set the inlet damper. See Figures 10 through 12. Figure 10 adjust inlet damper until test pressure is reached (Cobra shown) Figure 11 pay attention to DUCT SYSTEM gauge reading while adjusting inlet damper 11

13 Determining the Leakage Rate Now that you have obtained the system test pressure and have the inlet damper locked in position (Figure 12), note the pressure reading of the ORIFICE TUBE gauge (Figure 13). Refer to your calibration certificate to determine the leakage rate that corresponds to the gauge reading. An example of a calibration certificate is shown in Figure 14; it is for informational purposes only and used in the example shown on the next page. Always refer to the calibration certificate that came with your calibrated orifice plate. Figure 12 set and lock the position of the inlet damper when you reach test pressure (Cobra shown) Figure 13 ORIFICE TUBE gauge reading 12

14 SAMPLE CALIBRATION CHART TABE BELOW FOR EXAMPLE ONLY USE YOUR CHART Figure 14 Use calibration certificate table to convert gauge reading to leakage Note there every calibration chart always has an equation you can use that is given below the table Example For an ORIFICE TUBE gauge reading of 1.1 in.wg., the leakage rate is cfm. For an exact value, use the equation that comes with every calibration certificate. It will look like this: Leakage = x, where the value of is a constant and will be specific to the orifice plate used (every plate has its own value; yours will be different). Using a calculator or spreadsheet, take the square root of the gauge reading first, and then multiply by the constant for your orifice plate. 13

15 Troubleshooting Zero reading on DUCT SYSTEM gauge If the gauge reading is zero, refer to the table below to fix this problem. Perform troubleshooting steps in the order shown in the Table 7 below. Table 7 Troubleshooting steps when DUCT SYSTEM gauge is zero Step Scenario What to do Inlet damper was left shut, cutting off air to the system. Pressure tubing connected to gauge incorrectly Plugged fitting or malfunctioning gauge. Open inlet damper slowly. Look at the P1 and P2 stickers that are located on the orifice tube and gauges. Make sure tubing from P1 tap matches the P1 tap on the ORIFICE TUBE gauge. Gently blow through other end of pressure tubing from DUCT SYSTEM gauge, and watch needle increase pressure reading. Check for these other sources of leakage: 4 System is leaking too much air. Rectangular duct joints (check and seal corners), Fire or smoke dampers, Duct joints (pay particular attention to flex-duct joints if they are part of the leak test), VAV boxes (pay particular attention to parallel box back draft dampers), Built-up air handlers, Plenums, Uncured duct sealant blow-thru (follow manufacturer instructions for cure time), Improperly sealed or un-sealed joints, Hot water coils and electric heaters, Open duct end that was supposed to be sealed/capped-off for the leak test. 14

16 Zero reading on ORIFICE TUBE gauge If the gauge reading is zero, refer to the table below to fix this problem. Perform troubleshooting steps in the order shown in Table 8 below. Table 8 Troubleshooting steps when ORIFICE TUBE gauge is zero Step Scenario What to do 1 Inlet damper was left shut, cutting off air to the system. 2 Plugged pressure taps. 3 Orifice plate too large for application. Open inlet damper slowly. Remove pressure tubing from ORIFICE TUBE gauge, and blow through each end to make sure the pressure taps on the orifice tube are clear. If you are using a 4-inch ID orifice plate, and the system is leaking 40 cfm, you probably won t even notice the gauge needle moving. This can happen to other orifice plates too. You need to purchase an orifice plate with a smaller bore diameter so that a small amount of airflow/leakage will result in a bigger pressure drop. 4 4 System is leaking very little air. Pressure tubing connected incorrectly. You ll know if this is true if the fan inlet is almost shut. Not likely unless system is small. Fix is to use plate with smaller bore. Look at the P1 and P2 stickers that are located on the orifice tube and gauges. Make sure they match. 5 Malfunctioning gauge. 6 Not sure Remove the clear pressure tubing from the lower pressure tap on the orifice tube and blow through the end of the tubing. The needle should move in response. If not, the gauge is faulty. The best way to make sure that your tester is working properly is to disconnect the flex duct from the system and turn the blower on, and slowly open the inlet damper. If you feel a lot of air coming out of the tube end, you should see a pressure reading on the gauge ORIFICE TUBE. Can t obtain system test pressure This happens when the system is leaking too much air. Make sure all outlets are sealed. Check corners of rectangular duct for excessive leakage. Inspect all duct and fitting joints for leakage. Make sure you seal all suspect joints and allow to cure 24 to 48 hours. Always refer to duct sealant manufacturer s instructions. Check for these other sources of leakage: Rectangular duct joints (check and seal corners), Fire or smoke dampers, Duct joints (pay particular attention to flex-duct joints if they are part of the leak test), VAV boxes (pay particular attention to parallel box back draft dampers), Built-up air handlers, Plenums, 15

17 Uncured duct sealant blow-thru (follow manufacturer instructions for cure time), Improperly sealed or un-sealed joints, Hot water coils and electric heaters, Open duct end that was supposed to be sealed/capped-off for the leak test. A non-toxic smoke machine is an excellent tool for locating significant sources of leakage. Call ORIFLOW at or online at for more information. ORIFICE TUBE gauge reading maxed out Scenario 1: The system is leaking too much air. Make sure all outlets are sealed. Check corners of rectangular duct for excessive leakage. Inspect all duct and fitting joints for leakage. Make sure you seal all suspect joints and allow curing time of 24 to 48 hours. Always refer to duct sealant manufacturer s instructions. Scenario 2: orifice plate bore could be too small, causing a high pressure drop at low to moderate flows. You need an orifice plate with a larger bore. ORIFLOW LLC Clearwater, Florida (phone) 8am to 5pm PST (fax) sales@oriflow.com engineering@oriflow.com 16

Copyright 2017 ORIFLOW LLC. Operating Instructions for Cobra and Lynx Duct Leakage Testers

Copyright 2017 ORIFLOW LLC. Operating Instructions for Cobra and Lynx Duct Leakage Testers Operating Instructions for Cobra and Lynx Duct Leakage Testers Table of Contents Introduction Introduction.. 2 Safety Precautions Safety Precautions READ FIRST!... 2 Prior to Testing Are You Using the

More information

KEES, INC. BALANCING MANUAL

KEES, INC. BALANCING MANUAL KEES, INC. Products for Sheet Metal HVAC, Food Service, & Architectural Construction Industries 400 S. INDUSTRIAL DRIVE ELKHART LAKE, WISCONSIN 53020 920 876-3391 FAX 920 876-3065 FORWARD: BALANCING MANUAL

More information

OPERATION, INSTALLATION, & MAINTENANCE MANUAL. Aircon BRS Below-Roof Separator. and. BRV Below-Roof Valve

OPERATION, INSTALLATION, & MAINTENANCE MANUAL. Aircon BRS Below-Roof Separator. and. BRV Below-Roof Valve OPERATION, INSTALLATION, & MAINTENANCE MANUAL for Aircon BRS Below-Roof Separator and BRV Below-Roof Valve Aircon Corporation P.O. Box 80446 2873 Chelsea Avenue Memphis, TN 38108-0446 Telephone: (901)

More information

Self Cleaning Hood System Installation, Operation, and Maintenance Manual

Self Cleaning Hood System Installation, Operation, and Maintenance Manual Self Cleaning Hood System Installation, Operation, and Maintenance Manual RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and if found, report it immediately to

More information

NSGV PT-1000 PORTABLE WELDING STATION I, O & M MANUAL

NSGV PT-1000 PORTABLE WELDING STATION I, O & M MANUAL APPLICATION OF DUST CONTROL EQUIPMENT: CAUTION - Warning Improper operation of dust control system may contribute to conditions in the work area or facility that could result in severe personal injury

More information

MANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved.

MANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved. MANUAL ECM Motor ECM / ECM-DX Series v100 Issue Date: 08/15/17 2017 Price Industries Limited. All rights reserved. ECM MOTOR TABLE OF CONTENTS ECM Motor Background...1 ECM Motor Power and Control Connectors...2

More information

FAN POWERED TERMINAL UNITS

FAN POWERED TERMINAL UNITS Benefits: Fan powered terminals are typically used for heating and cooling of perimeter zones. Operating cost savings can be achieved through the use of waste heat recovery from the ceiling plenum and

More information

FAN POWERED TERMINAL UNITS

FAN POWERED TERMINAL UNITS Benefits: Fan powered terminals are typically used for heating and cooling of perimeter zones. Operating cost savings can be achieved through the use of waste heat recovery from the ceiling plenum and

More information

SINGLE DUCT AIR TERMINAL UNITS

SINGLE DUCT AIR TERMINAL UNITS AIR terminal units AIR TERMINAL UNITS MODEL NUMBER LEGEND XXXXX XXX -XXXX Model TH TL THECO Inlet Size (04, 05, 06, etc.) Generation 5, 6, 7 The METALAIRE single duct terminal units are at the core of

More information

Catalog Air Terminal Units. Models MQTH, MQFCI and MQFVI. Model MQTH. Model MQFCI. Model MQFVI

Catalog Air Terminal Units. Models MQTH, MQFCI and MQFVI. Model MQTH. Model MQFCI. Model MQFVI Air Terminal Units Models MQTH, MQFCI and MQFVI Catalog 903-1 Model MQTH Model MQFCI Model MQFVI Table of Contents Single Duct Air Terminal Units.... 3 Introduction....3 MQTH-500 Single Duct Air Terminal

More information

TWO-STAGE HYDRAULIC PUMP. RWP55-IBT-Air

TWO-STAGE HYDRAULIC PUMP. RWP55-IBT-Air ORIGINAL INSTRUCTIONS Form No.1000458 5 SPX Corporation 5885 11th Street Rockford, IL 61109-3699 USA Tech. Services: (800) 477-8326 Fax: (800) 765-8326 Order Entry: (800) 541-1418 Fax: (800) 288-7031 Internet

More information

Phone: Fax: ILD Series. Troubleshooting: ILD Column Lift

Phone: Fax: ILD Series. Troubleshooting: ILD Column Lift 15939 Piuma Avenue Cerritos, CA 90703 ILD Series Troubleshooting: ILD Column Lift Table of content: Page 1) Gate overview...2 2) Single Motor Setup overview. 3 3) Dual Motor Setup overview....4 4) Gate

More information

Safety & Installation Instructions

Safety & Installation Instructions Model 8120A & 8126A Digital Ventilation Controller Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Safety Instructions... 3 Specifications... 4 Overview... 4 Mounting

More information

MANUAL INSTALLATION. Active Chilled Beam Linear. ACBL Series. v101 Issue Date: 04/10/ Price Industries Limited. All rights reserved.

MANUAL INSTALLATION. Active Chilled Beam Linear. ACBL Series. v101 Issue Date: 04/10/ Price Industries Limited. All rights reserved. MANUAL INSTALLATION Active Chilled Beam Linear ACBL Series v11 Issue Date: 4/1/18 218 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview Before You Start...1 Maintenance...1

More information

Refinery Supply Company, Inc.

Refinery Supply Company, Inc. Refinery Supply Company, Inc. OPERATING INSTRUCTIONS Super Pressure Dead Weight Tester Catalog No. 35260 Serving the Oil & Gas Industry since 1923 9133-A East 46th Street Tulsa, Oklahoma 74145-4823 Voice

More information

Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate.

Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate. FEATURES Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate. Silicon diodes with inherent surge protection operated at a conservative percentage

More information

TABLE OF CONTENTS INTRODUCTION.. 3. A/C Ducting Installation. Power Kit Installation (Batteries)...5 OPERATION MANUAL 7-8 TOOLS LIST..

TABLE OF CONTENTS INTRODUCTION.. 3. A/C Ducting Installation. Power Kit Installation (Batteries)...5 OPERATION MANUAL 7-8 TOOLS LIST.. 585457 1 TABLE OF CONTENTS SECTION PAGE INTRODUCTION.. 3 INSTALLATION PROCEDURES Air Conditioner Location...4 Air Conditioner Mounting 4 A/C Ducting Installation...5 Power Kit Installation (Batteries)...5

More information

Solutions from SPTT-3

Solutions from SPTT-3 Solutions from SPTT-3 System Principle Of Operation Sdhv 21 60000 BTU 9 9 2000 BTU 10 2 Conventional D/T/R Diffusion, Throw & Return. Air change. Works for heating OR cooling, NOT BOTH. Aspiration Static

More information

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting READ AND SAVE THESE INSTRUCTIONS INSTALLATION, OPERATING INSTRUCTIONS & PARTS MANUAL Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting Electrical wiring and connections should be done

More information

X100P Load Bank. Read all instructions before using the load bank. Contents

X100P Load Bank. Read all instructions before using the load bank. Contents X100P Load Bank Read all instructions before using the load bank Contents 1. Components... 3 Total Assembly... 3 2) Specifications... 4 a) X100P Load Bank... 4 3) Receiving... 4 4) Safety... 5 a) Grounding...

More information

Centrifugal Pumps (Part Nos. PS2SS PS73SS) PS2SS

Centrifugal Pumps (Part Nos. PS2SS PS73SS) PS2SS Centrifugal Pumps (Part Nos. PS2SS PS73SS) PS2SS Part No. Serial Number Date Purchased Table of Contents Page Safety Messages...2 Pump Curves...2 Pump End Assembly...3 Disassembly...3 Installation...4

More information

PHOENIX GUARDIAN H. E. P. A. SYSTEM

PHOENIX GUARDIAN H. E. P. A. SYSTEM PHOENIX GUARDIAN H. E. P. A. SYSTEM Therma-Stor Products Box 8050 Madison, WI 53708 Toll Free 1-800-533-7533 Local 1-608-222-5301 PHOENIX GUARDIAN Operation & Service Instructions Table of Contents 1.

More information

WELDING FUME EXHAUSTERS & ARMS

WELDING FUME EXHAUSTERS & ARMS WELDING FUME EXHAUSTERS & ARMS The Ace 75 Series is our flexible and effective line of welding fume exhausters and extraction arms for shops that elect to exhaust their weld fumes outdoors instead of through

More information

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P MANUAL NUMBER P-EFS-1 MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P TRAC Regulator Company Inc. 160 South Terrace Avenue Mount Vernon, New York USA 10550-2408 Phone: (914)

More information

User s Manual D-Series Blowers and Exhausters

User s Manual D-Series Blowers and Exhausters User s Manual D-Series Blowers and Exhausters D05-1 ½ HP TEFC 115/230 VOLTS, 1 PH D05-3 ½ HP TEFC 208/230/460 VOLTS, 3 PH D10-1 1 HP TEFC 115/230 VOLTS, 1 PH D10-3 1 HP TEFC 208/230/460 VOLTS, 3 PH D15-1

More information

PH SERIES SINGLE DUCT ATU PERFORMANCE DATA

PH SERIES SINGLE DUCT ATU PERFORMANCE DATA PH SERIES SINGLE DUCT ATU PERFORMAE DATA The Performance Aire PH Series is the simplest and most widely used VAV terminal unit. Its basic components are an insulated sheet metal box, round inlet damper,

More information

Installation Instructions for John Deere cotton picker models: 9986 & 2-row and All-row systems included.

Installation Instructions for John Deere cotton picker models: 9986 & 2-row and All-row systems included. Ag Leader Technology Cotton Picker Installation Installation Instructions for John Deere cotton picker models: 9986 & 9996 2-row and All-row systems included. IMPORTANT: Ensure the model numbers shown

More information

Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils

Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils Please consult your local representative or the factory for warranty issues. July 2017 DRS Marlo Coil Customer

More information

Pro Island Ventilation Hoods

Pro Island Ventilation Hoods INSTALLATION GUIDE Pro Island Ventilation Hoods READ AND SAVE THESE INSTRUCTIONS Contents Wolf Pro Island Ventilation Hoods................. 3 Safety Instructions............................ 4 Installation

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Universal Air Series!! NOTE!! Covers the following model: 6000 Series 85-0100B-AZ Rev 0 5/07 To ensure that the system is installed properly, provide your electrician with these

More information

H2O-C14 AAA FINE FINISH SERIES PUMP OUTFIT

H2O-C14 AAA FINE FINISH SERIES PUMP OUTFIT PRODUCT INFORMATION H2O-C14 AAA FINE FINISH SERIES PUMP OUTFIT The H2O-C14 AAA pump system is an air assisted airless unit which combines airless and conventional or HVLP air atomization technologies to

More information

LT Charging Cart for Laptops

LT Charging Cart for Laptops Built with Anthro-DNA LT Charging Cart for Laptops Owners Manual This unit has been tested to Underwriters Laboratories U.S. and Canadian (Bi-National) Standard for Safety of Informational Technology Equipment,

More information

MANUAL INSTALLATION. Venturi FX. VFX Series. v100 Issue Date: 11/22/ Price Industries Limited. All rights reserved.

MANUAL INSTALLATION. Venturi FX. VFX Series. v100 Issue Date: 11/22/ Price Industries Limited. All rights reserved. MANUAL INSTALLATION Venturi FX VFX Series v100 Issue Date: 11/22/16 2016 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview Safety Precautions... 1 Caution to Contractors...1

More information

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone. INSTALLATION & OPERATION MANUAL Fan Powered Terminals VAV TERMINALS IOM FAN POWERED TERMINALS Receiving Inspection After unpacking the terminal, check it for shipping damage. If any shipping damage is

More information

P RO W ALL V ENTILATION H OODS INSTALLATION INSTRUCTIONS

P RO W ALL V ENTILATION H OODS INSTALLATION INSTRUCTIONS P RO W ALL V ENTILATION H OODS INSTALLATION INSTRUCTIONS CONTACT INFORMATION Wolf Customer Service: 800-332-9513 Website: wolfappliance.com As you follow these instructions, you will notice WARNING and

More information

D-Series Blowers and Exhausters

D-Series Blowers and Exhausters Operation and Maintenance Manual D-Series MONOXIVENT - SOURCE CAPTURE SYSTEMS - info@ Oct. - 2015 MONOXVENT BLOWERS AND EXHAUSTERS D05-1 D05-3 D10-1 D10-3 D15-1 D15-3 D20-1 D20-3 D30-1 D30-3 ½ HP TEFC

More information

Installing Your 220v J-POD Kit

Installing Your 220v J-POD Kit Installing Your 220v J-POD Kit NOTE: There are two J-POD versions depending on your pump voltage - 110 volt and 220 volt. MAKE SURE YOU HAVE THE RIGHT VOLTAGE J-POD FOR YOUR. Using software and hardware

More information

READ AND SAVE THESE INSTRUCTIONS. High Velocity Restaurant-Duty Utility Set Belt Driven for Roof Mounting

READ AND SAVE THESE INSTRUCTIONS. High Velocity Restaurant-Duty Utility Set Belt Driven for Roof Mounting READ AND SAVE THESE INSTRUCTIONS INSTALLATION, OPERATING INSTRUCTIONS & PARTS MANUAL High Velocity Restaurant-Duty Utility Set Belt Driven for Roof Mounting Electrical wiring and connections should be

More information

for Untempered - Make-Up Air Units

for Untempered - Make-Up Air Units Part # 457646 Installation, Operation, and Maintenance Instructions for Untempered - Make-Up ir Units Table of Contents Installation............................. 2-5 Troubleshooting..........................

More information

MODEL MC1500 Installation and Operation Manual Important:

MODEL MC1500 Installation and Operation Manual Important: MODEL MC1500 Installation and Operation Manual Important: This manual contains specific cautionary statements relative to worker safety. Read this manual thoroughly and follow as directed. It is impossible

More information

Variable Air Volume Dampers

Variable Air Volume Dampers OVAV 2000 SERIES OPTIMA VAV DAMPERS Overview OPTIMA make Variable Air Volume (OVAV) box is a part of an Air Conditioning system. It is located inside the duct work. VAV Dampers are designed to control

More information

PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST MUSTANG

PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST MUSTANG specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic vehicle PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST 1969-70 MUSTANG CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect

More information

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw Small Packaged Products 2 to 5 Tons Accessory Electric Heaters Cancels: IIK 564A-24-2 IIK 564A-24- -02 Installation Instructions Electric Heaters 5 20 kw NOTE: Read the entire instruction manual before

More information

6-54 HEPA Filter Assembly

6-54 HEPA Filter Assembly 6-54 HEPA Filter Assembly Dust Collector Fan Outlet Dust Collector Fan HEPA Filter Inlet Elbow Dust Collector Outlet Elbow HEPA Filter Assembly Caster Mounting Brackets HEPA Filter Support Legs 1 The Blastrac

More information

Model: SE-4020-CA Automatic Battery Charger

Model: SE-4020-CA Automatic Battery Charger OWNERS MANUAL Model: SE-4020-CA Automatic Battery Charger PLEASE SAVE THIS OWNERS MANUAL AND READ BEFORE EACH USE. This manual will explain how to use the battery charger safely and effectively. Please

More information

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST BELT TYPE IMPORTANT PLEASE MAKE CERTAIN THAT THE PERSON WHO IS TO USE THIS EQUIPMENT CAREFULLY READS AND UNDERSTANDS THESE INSTRUCTIONS BEFORE STARTING

More information

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES FAN TERMINAL UNIT SPECIFIABLE FEATURES Galvanized steel casing, mechanically sealed for low leakage construction NEMA TYPE 1 rated hinged control enclosure with standoff to prevent penetration of casing

More information

BCE3V PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER APPLICATION INSTALLATION CABINET COMPONENTS ACCESSORIES WARRANTY

BCE3V PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER APPLICATION INSTALLATION CABINET COMPONENTS ACCESSORIES WARRANTY PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER FORM NO. -100 (03/2017) APPLICATION 1.5-5 ton systems Upflow and horizontal Sequenced for demand management External access to heater circuit breakers INSTALLATION

More information

TECHNICAL NOTE #4 Revised May 24, BOGART ENGINEERING Two Bar Road, Boulder Creek, CA (831)

TECHNICAL NOTE #4 Revised May 24, BOGART ENGINEERING Two Bar Road, Boulder Creek, CA (831) TECHNICAL NOTE #4 Revised May 24, 2004 BOGART ENGINEERING 19020 Two Bar Road, Boulder Creek, CA 95006 (831) 338-0616 TROUBLESHOOTING the TriMetric battery monitor Revised for the TM-2020 TriMetric What

More information

Rev: Flow Max 115V AC Fluid Pump

Rev: Flow Max 115V AC Fluid Pump Flow Max 115V AC Fluid Pump by Duraself Installation and Owner s Manual (For Aftermarket Applications) Table of Contents Introduction... 2 Parts List... 2 Resources Required... 3 Installation... 3 General

More information

TABLE OF CONTENTS INTRODUCTION 3. INSTALLATION PROCEDURES Air Conditioner Location 4. A/C Ducting Installation 5

TABLE OF CONTENTS INTRODUCTION 3. INSTALLATION PROCEDURES Air Conditioner Location 4. A/C Ducting Installation 5 585474 1 TABLE OF CONTENTS SECTION PAGE INTRODUCTION 3 INSTALLATION PROCEDURES Air Conditioner Location 4 Air Conditioner Mounting 4 A/C Ducting Installation 5 Power Kit Installation (Batteries). 5 Separator...

More information

& 76 CHEVROLET NOVA HEATER ONLY

& 76 CHEVROLET NOVA HEATER ONLY specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic hi l PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST 1969-74 & 76 CHEVROLET NOVA HEATER ONLY CONTROL & OPERATING INSTRUCTIONS The controls on

More information

The Mark V Air/Fuel Controller - Technical Manual -

The Mark V Air/Fuel Controller - Technical Manual - Neutronics Enterprises Inc. The Mark V Air/Fuel Controller - Technical Manual - For Technical Information contact: Neutronics Enterprises Inc. 11421 West Bernardo Court. San Diego, CA. 92127 (858) 674-2250

More information

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410. PART 1 - GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

OPERATING SERVICE MAINTENANCE MANUAL

OPERATING SERVICE MAINTENANCE MANUAL OPERATING SERVICE MAINTENANCE MANUAL ALL-STAR ROCKING PISTON COMPRESSOR AND VACUUM PUMP Registered by one or more of these standards agency ISO RoHS 9001 Compliant CE Read through carefully and understand

More information

Jeep Wrangler TJ 4.0 LITER Installation instructions

Jeep Wrangler TJ 4.0 LITER Installation instructions www.jeepair.com 2000-2001 Jeep Wrangler TJ 4.0 LITER Installation instructions Important information about your system, and warranty DO NOT ADD ANY OIL TO ANY PART OF THE SYSTEM. DO NOT USE THE SIGHT GLASS

More information

Installation Instructions

Installation Instructions 010A00 011A00 014A00 SMALL ROOFTOP UNITS TWO POSITION OUTDOOR AIR DAMPER 2to15TONS (50/60 Hz) Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 PACKAGE USAGE... 1 SAFETY CONSIDERATIONS...

More information

Horizontal and Vertical Belt Drive Blower Coil Units (Models AHI and AVI)

Horizontal and Vertical Belt Drive Blower Coil Units (Models AHI and AVI) Technical Bulletin Issue Date December 6, 2004 Horizontal and Vertical Belt Drive Blower Coil Units (Models AHI and AVI) Model AHI Horizontal and Model AVI Vertical Belt Drive Blower Coils are designed

More information

IAQ. ROUND DUCT RETROFIT Model ARR

IAQ. ROUND DUCT RETROFIT Model ARR Non Fan Powered Units ROUND DUCT RETROFIT Model ARR IAQ External Insulation Standard The Carnes Model ARR offers low pressure drop, low sound levels, and valve characteristics which create stable control

More information

PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST FORD FAIRLANE & CROWN VICTORIA

PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST FORD FAIRLANE & CROWN VICTORIA PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST 1955-56 FORD FAIRLANE & CROWN VICTORIA CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect Fit system, offer complete comfort capabilities in virtually

More information

NSGV EVE-ER I, O, & M MANUAL

NSGV EVE-ER I, O, & M MANUAL TABLE OF CONTENTS Rail Layout.. Page 1 Support Placement...Page 1 Rail Assembly.Page 1 Rail Duct Connections.. Page 2 Rubber Lip Installation.. Page 3 Pneumatic End Stop. Page 4 End Stop. Page 4 End Cap..

More information

Air Handling Unit Construction Checklist

Air Handling Unit Construction Checklist Air Handling Unit Construction Checklist Project: Date: AHU Tag: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

TURBODYNO **WARNING**

TURBODYNO **WARNING** TURBODYNO **WARNING** It is dangerous to work in the vicinity of a lead-acid battery since they generate explosive gases during normal battery operation, To prevent an explosion when using a lead-acid

More information

Instruction Sheet. 1/2 HP Portable Electric Pumps SAFETY FIRST. L2062 Rev. F 02/ IMPORTANT RECEIVING INSTRUCTIONS 2.

Instruction Sheet. 1/2 HP Portable Electric Pumps SAFETY FIRST. L2062 Rev. F 02/ IMPORTANT RECEIVING INSTRUCTIONS 2. Instruction Sheet 1/2 HP Portable Electric Pumps L2062 Rev. F 02/12 Index: English:...................................... 1-7 Français:.................................... 8-14 Deutsch:...................................

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS MODELS 600HS, 1200HS, 2000HS PLUS HVAC 600HS L Housing 600HS S Housing 1200/2000HS S Housing 1200/2000HS L Housing 1 ASSEMBLY INSTRUCTIONS HVAC VERSION STEP 1. STEP 2. STEP 3.

More information

Flow Max. by Duraself. Flow Max by Duraself. Fluid Pump. Installation and Owner s Manual (For Aftermarket Applications)

Flow Max. by Duraself. Flow Max by Duraself. Fluid Pump. Installation and Owner s Manual (For Aftermarket Applications) Flow Max Installation and Owner s Manual (For Aftermarket Applications) Table of Contents Introduction... 2 Parts List... 2 Resources Required... 3 Installation... 3 General Installation Instructions...

More information

IMPORTANT! DO NOT THROW AWAY THE SHIPPING CARTON AND PACKING MATERIAL

IMPORTANT! DO NOT THROW AWAY THE SHIPPING CARTON AND PACKING MATERIAL Operator s Manual IMPORTANT! DO NOT THROW AWAY THE SHIPPING CARTON AND PACKING MATERIAL ii Table of Contents Operator Safety... 1 Introduction... 2 Unpacking and Setup... 3 Unpacking... 3 Setup... 4 ROCKET

More information

348002K/348012K Manifold Block Style Service Manual 12/2000

348002K/348012K Manifold Block Style Service Manual 12/2000 348002K/348012K Manifold Block Style Service Manual 12/2000 Service Manual 348002K/348012K Manifold Block Style Recovery/Recycling/Recharging Unit For R-12 or R-134a Only TABLE OF CONTENTS: Theory of Operation

More information

Rev. 0 - March Air System Diagnostics Kit Instructions.indd 1

Rev. 0 - March Air System Diagnostics Kit Instructions.indd 1 Air System Diagnostics Kit Instructions Rev. 0 - March 2016 Air System Diagnostics Kit Instructions.indd 1 Air System Diagnostics Kit Instructions.indd 2 Table of Contents Table of Contents...1 Introduction...2

More information

SECTION AIR INTAKE SYSTEM

SECTION AIR INTAKE SYSTEM 09-500.295/ 1 2007AL05 SECTION 09-500.295 AIR INTAKE Air for the engine is taken in through a grille located on the upper-rear, left-hand side of the vehicle. See Figure 1. Air passes through a chamber,

More information

COLDWATER LAKE FACILITIES DUPLEX PUMP STATION

COLDWATER LAKE FACILITIES DUPLEX PUMP STATION COLDWATER LAKE FACILITIES DUPLEX PUMP STATION TROUBLESHOOTING GUIDE REFERENCE: Operation Instructions Ladder Schematic Diagrams SCOPE The following troubleshooting guide has been specifically prepared

More information

MMA 160S ARC/MMA WELDER OPERATION INSTRUCTIONS

MMA 160S ARC/MMA WELDER OPERATION INSTRUCTIONS www.r-techwelding.co.uk MMA 160S ARC/MMA WELDER OPERATION INSTRUCTIONS 2 Thank you for selecting the R-Tech MMA160S Inverter Arc Welder. The MMA160S has many benefits over traditional Arc welders, including

More information

5.5 FT PRE-LIT SERBIAN SPRUCE TREE

5.5 FT PRE-LIT SERBIAN SPRUCE TREE ITEM #0674086 Holiday Living & Design is a registered trademark of LF, LLC. All Rights Reserved. 5.5 FT PRE-LIT SERBIAN SPRUCE TREE MODEL #W14D0225 Español p. 8 ATTACH YOUR RECEIPT HERE Serial Number Purchase

More information

HVF110, 210, 310, 410HD

HVF110, 210, 310, 410HD 342 N. Co. Rd. 400 East Valparaiso, IN 46383 219-464-8818 Fax 219-462-7985 www.heatwagon.com Installation and Maintenance Manual Please retain this manual for future reference. HVF110, 210, 310, 410HD

More information

B14 AAA FINE FINISH SERIES PUMP OUTFIT

B14 AAA FINE FINISH SERIES PUMP OUTFIT PRODUCT INFORMATION B14 AAA FINE FINISH SERIES PUMP OUTFIT The B14 AAA pump system is an air assisted airless unit which combines airless and conventional or HVLP air atomization technologies to produce

More information

SINGLE DUCT TERMINAL UNITS

SINGLE DUCT TERMINAL UNITS www.igcaire.com SINGLE DUCT TERMINAL UNITS Direct Digital Control, Pressure Independent FEATURES 22 Gauge Galvanized Steel Casing Construction with a 20 Gauge Casing Option that Provides Strength and Product

More information

LABORATORY ZERO AIR GENERATOR MODEL N-GC1500 USER S MANUAL

LABORATORY ZERO AIR GENERATOR MODEL N-GC1500 USER S MANUAL LABORATORY ZERO AIR GENERATOR MODEL N-GC1500 USER S MANUAL Content 1. Introduction...2 2. Important safety instruction...3 3. System component...4 4. Engineering design overview...5 5. Installation...6

More information

COOKSON OWNER'S MANUAL

COOKSON OWNER'S MANUAL COOKSON OWNER'S MANUAL FDO-A10 INDUSTRIAL DUTY FIRE DOOR OPERATOR R L I S T E D 3040233 US CONTROL PANEL SERIAL# OPERATOR SERIAL# 9001.DWG ECN 0959 REV 4 SPECIFICATIONS MOTOR TYPE:...INTERMITTENT HORSEPOWER:...1/8

More information

ON-VEHICLE INSPECTION

ON-VEHICLE INSPECTION Last Modified: 4-26-2007 Service Category: Engine/Hybrid System 1.6 G Section: Engine Mechanical Model Year: 2007 Model: 4Runner Doc ID: RM0000017L8004X Title: 1GR-FE ENGINE MECHANICAL: ENGINE: ON-VEHICLE

More information

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc.

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc. ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT 15 Metal Industries, Inc. BENEFITS: Fan powered terminals are typically used for heating and cooling of perimeter zones.

More information

OPERATING INSTRUCTIONS. Note: 6V Charging. Requires Manual Shut Off.

OPERATING INSTRUCTIONS. Note: 6V Charging. Requires Manual Shut Off. Requires Manual Shut Off. 6 / 2 AMP,, DUAL RATE BATTER TTERY CHARGER 45005 OPERATING INSTRUCTIONS E224783 E224783 Note: 6V Charging Due to continuing improvements, actual product may differ slightly from

More information

XS500 Load Bank. Read all instructions before using the load bank. Contents

XS500 Load Bank. Read all instructions before using the load bank. Contents XS500 Load Bank Read all instructions before using the load bank Contents Contents... 2 1) Receiving... 4 a. Load Bank... 4 b. Manual... 4 2) Specifications... 5 a. Mechanical... 5 i. Lifting... 5 ii.

More information

ft. ft Signature Balsam Fir Tree ITEM Item 68607

ft. ft Signature Balsam Fir Tree ITEM Item 68607 7.5 7.5 ft. ft Signature Balsam Fir Tree ITEM Item 68607 PARTS LIST A. BOTTOM B. MIDDLE C. TOP D. TREE STAND NUMBER OF PERSONS RECOMMENDED FOR ASSEMBLY: 2 SKU 68607 7.5 Signature Balsam Fir 2114 TIPS STANDARD

More information

I Fan Powered Terminal Unit

I Fan Powered Terminal Unit I Fan Powered Terminal Unit VARIABLE VOLUME PARALLEL FLOW Fan Powered Terminal Unit Variable volume parallel flow Product Overview Variable Volume/Parallel Flow Fan Powered Terminal Units Honeywell parallel

More information

PORSCHE V r Valve Timing Instructions. Copyright 2009 Written by Mike Frye Edited my Adam G.

PORSCHE V r Valve Timing Instructions. Copyright 2009 Written by Mike Frye Edited my Adam G. PORSCHE 928 32V r Valve Timing Instructions Copyright 2009 Written by Mike Frye Edited my Adam G. Sections: Overview.3 Disclaimer/warnings/things to watch for 4 Terms and naming conventions used in this

More information

PRODUCT INFORMATION BULLETIN #3365 DIGITAL MOTOR CONTROL PLATTER SYSTEMS For Serial Number and After

PRODUCT INFORMATION BULLETIN #3365 DIGITAL MOTOR CONTROL PLATTER SYSTEMS For Serial Number and After PRODUCT INFORMATION BULLETIN #3365 DIGITAL MOTOR CONTROL PLATTER SYSTEMS For Serial Number 28640996 and After Record Platter System Identification Numbers Here: Model # Serial # Table of Contents Program

More information

RELEASING PRESSURE IN THE HYDRAULIC SYSTEM,

RELEASING PRESSURE IN THE HYDRAULIC SYSTEM, Testing And Adjusting Introduction NOTE: For Specifications with illustrations, make reference to SPECIFICATIONS for 225 EXCAVATOR HYDRAULIC SYSTEM, Form No. SENR7734. If the Specifications are not the

More information

ARTICLE BEGINNING SERVICE PRECAUTIONS

ARTICLE BEGINNING SERVICE PRECAUTIONS Page 1 of 96 ARTICLE BEGINNING SERVICE PRECAUTIONS WARNING: WARNING: CAUTION: When performing any inspection or service procedure on this vehicle, ensure following service precautions are followed to prevent

More information

RETROFIT TERMINAL UNITS

RETROFIT TERMINAL UNITS GENERAL PROUCT OVERVIEW Retrofit Terminal s Convert Constant Air Volume Systems to Variable Air Volume. Convert Constant Volume ual uct Systems to Variable Air Volume. Convert Multizone Systems to Variable

More information

OPERATION INSTRUCTIONS

OPERATION INSTRUCTIONS www.r-techwelding.co.uk Email: sales@r-techwelding.co.uk Tel: 01452 733933 Fax: 01452 733939 ProArc 175 INVERTER ARC WELDER OPERATION INSTRUCTIONS Version 2017-10 2 3 Thank you for selecting the R-Tech

More information

TrueGyde Microcoil. Author: Marcel Berard Co-Author: Philippe Berard

TrueGyde Microcoil. Author: Marcel Berard Co-Author: Philippe Berard Author: Marcel Berard Co-Author: Philippe Berard Introduction TrueGyde Steer supports the microcoil as an alternate magnetic source to the standard coil. This document describes how to build and use a

More information

Installation Instructions

Installation Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment

More information

ATTACH YOUR RECEIPT HERE ITEM # FT. PRE-LIT DOUGLAS FIR TREE. MODEL #DF-75C85 Español p. 8

ATTACH YOUR RECEIPT HERE ITEM # FT. PRE-LIT DOUGLAS FIR TREE. MODEL #DF-75C85 Español p. 8 ITEM #0776 7. FT. PRE-LIT DOUGLAS FIR TREE MODEL #DF-7C8 Español p. 8 ATTACH YOUR RECEIPT HERE Serial Number Purchase Date Questions, problems, missing parts? Before returning to your retailer, call our

More information

Installation Vertical Pump: Installation 'CM' and 'CDM' Style: Operation:

Installation Vertical Pump: Installation 'CM' and 'CDM' Style: Operation: Installation Vertical Pump: Gusher vertical end suction pumps with integral shaft is easily installed and put into service. With the one piece shaft design there is no couplings to align, no shims or no

More information

Don Searles Check List For Dredging Equipment Surveys

Don Searles Check List For Dredging Equipment Surveys Don Searles Check List For Dredging Equipment Surveys 1. General 1.1. Take pictures of everything important. Take pictures showing the side of the dredge 1.2. Inspect logs and maintenance records. Get

More information

HOW - TO WIRING & LIGHTING

HOW - TO WIRING & LIGHTING HOW - TO WIRING & LIGHTING Tool And Material Checklist Test Light Service Manual Penetrating Oil Long-Nose Pliers T-Square or Right Angle Screwdriver Black Electrical Tape Fuses Fuse Puller Cloth or Paper

More information

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw Small Packaged Products to 5 Tons Accessory Electric Heaters Cancels: IIK 564A--1 IIK 564A-- 11-01 Installation Instructions Electric Heaters 5 0 kw NOTE: Read the entire instruction manual before starting

More information

INSTALLATION AND OPERATIONS MANUAL FUEL POLISHING MODULE (FPM)

INSTALLATION AND OPERATIONS MANUAL FUEL POLISHING MODULE (FPM) INSTALLATION AND OPERATIONS MANUAL FUEL POLISHING MODULE (FPM) Models 60M, 90M, 180M DIESEL ENGINES ONLY Don t Leave Shore Without It. IMPORTANT READ BEFORE INSTALLING THE INSTALLATION AND SETUP SHOULD

More information

BCE5V PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER APPLICATION INSTALLATION CABINET COILS COMPONENTS ACCESSORIES WARRANTY

BCE5V PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER APPLICATION INSTALLATION CABINET COILS COMPONENTS ACCESSORIES WARRANTY PRODUCT SPECIFICATIONS APPLICATION 1 1/2-5 ton systems Sequenced for demand management External access to heater circuit breakers FORM NO. -100 (12/2018) INSTALLATION 1 piece design Smaller profile for

More information

500-YH SINGLE DUCT AIR TERMINAL UNIT FORM EG1 (1101)

500-YH SINGLE DUCT AIR TERMINAL UNIT FORM EG1 (1101) 500-YH SINGLE DUCT AIR TERMINAL UNIT FORM 130.12-EG1 (1101) Table of Contents General Description.......................................................................3 500-YH Features........................................................................4-5

More information