Instruction Manual Series 70CV2000 Chloromatic TM Valve used with Series & FX4400 Gas Dispensing Systems
|
|
- Christina Gaines
- 5 years ago
- Views:
Transcription
1 Instruction Manual Series 70CV2000 Chloromatic TM Valve used with Series & FX4400 Gas Dispensing Systems
2 These instructions describe the installation, operation and maintenance of the subject equipment. Failure to strictly follow these instructions can lead to an equipment rupture that may cause signifi cant property damage, severe personal injury and even death. If you do not understand these instructions, please call De Nora Water Technologies for clarifi cation before commencing any work at and ask for a Field Service Manager. De Nora Water Technologies, Inc. reserves the rights to make engineering refinements that may not be described herein. It is the responsibility of the installer to contact De Nora Water Technologies, Inc. for information that cannot be answered specifically by these instructions. Any customer request to alter or reduce the design safeguards incorporated into De Nora Water Technologies equipment is conditioned on the customer absolving De Nora Water Technologies from any consequences of such a decision. De Nora Water Technologies has developed the recommended installation, operating and maintenance procedures with careful attention to safety. In addition to instruction/operating manuals, all instructions given on labels or attached tags should be followed. Regardless of these efforts, it is not possible to eliminate all hazards from the equipment or foresee every possible hazard that may occur. It is the responsibility of the installer to ensure that the recommended installation instructions are followed. It is the responsibility of the user to ensure that the recommended operating and maintenance instructions are followed. De Nora Water Technologies, Inc. cannot be responsible deviations from the recommended instructions that may result in a hazardous or unsafe condition. De Nora Water Technologies, Inc. cannot be responsible for the overall system design of which our equipment may be an integral part of or any unauthorized modifi cations to the equipment made by any party other that De Nora Water Technologies, Inc. De Nora Water Technologies, Inc. takes all reasonable precautions in packaging the equipment to prevent shipping damage. Carefully inspect each item and report damages immediately to the shipping agent involved for equipment shipped F.O.B. Colmar or to De Nora Water Technologies for equipment shipped F.O.B Jobsite. Do not install damaged equipment. De Nora Water Technologies, COLMAR OPERATIONS COLMAR, PENNSYLVANIA, USA IS ISO 9001: 2008 CERTIFIED
3 GENERAL The Series 70CV2000 Chloromatic TM Valve used inside the Gas Dispenser Cabinet is a minor variation of the Valve discussed in Instruction Bulletin The most obvious difference, is the mounting orientation, which is 180 from that shown in the printed bulletin; that is, the valve is at the top as shown in Figure 1. The Chloromatic Valve is factory installed, wired and tested prior to shipment therefore there is no installation requirement. All customer wiring for the basic unit is shown in Instruction Bulletin This contains retransmission and alarm options for which wiring diagrams are included. Also included is a wiring diagram for the optional hand-automatic control station (no customer wiring required if factory installed). GAS FLOW CAPACITY The gas fl ow capacity of the Series & FX4400 Gas Dispensing Systems is shown in Table A. Gas fl ow capacities to 500 lb/d (chlorine) use the valve shown in the printed bulletin with 1/2" NPT connections. Above 500 lb/d a larger capacity valve with 1" pipe fi tting is used. The internals of the valve are essentially the same; up to 500 lb/d a 3/8" orifi ce is used and a 1/2" orifi ce above that capacity. Figure 2 shows the two size valve plugs used; the valve orifi ce is sized accordingly. Figure 2 - Valve Plugs Figure 1 - Component Identification Chlorine (CL2), Sulfur Dioxide (SO 2 ) Table 1 - Flow Ranges Ammonia (NH 3 ) lb/d g/h kg/h lb/d g/h kg/h OPTIONAL FEATURES I. Retransmission Additional circuits, on the option circuit board, provide for retransmission of a 4-20 ma dc signal that is directly proportional to the valve position and thus to gas fl ow rate. In order to prevent transmission of false signals, the retransmission signal is interlocked with two vacuum switches. One switch measures the vacuum created by the ejector while the other switch measures the pressure in the gas container(s). Either a loss of ejector vacuum (low vacuum) or an empty gas container(s) (high vacuum) will open a contact to break the retransmission circuit. If either switch opens, a 4 ma current will be retransmitted. The additional customer wiring required for this feature is shown in Figure 3. This wiring is in addition to the basic wiring shown in Instruction Bulletin The retransmission output connects to the RO terminal on the option circuit board and returns to the COM terminal on the main circuit board. A load between 0 and 800 ohms is permissible; avoid running the signal lines in the same conduit as the power lines
4 The vacuum switches are factory installed in the cabinet and wired by DNWT. Figure 5A shows the wiring diagram for future troubleshooting purposes. The same vacuum switches are used for the optional alarms and are discussed in Section II, that follows. See section titled Functional Description for details regarding the electronic circuits used for retransmission. II. Alarms Vacuum switches may be furnished to provide an electrical alarm contact. Note: if the retransmission option is selected, the same vacuum switches are used for dual purposes (see Section I, preceding). Alarms are defined as follows and either one or both may be furnished. 1. Loss of Vacuum (low vacuum). This switch monitors the vacuum produced by the ejector. The loss of water to the ejector or a disconnected gas line could result in a loss of vacuum causing the alarm contacts to close. 2. Excess Vacuum (high vacuum). This switch monitors the gas cylinder or container. The closing of the shutoff valve at the cylinder or an empty container will produce a high vacuum. Either action will cause the alarm contacts to close. Figure 3 shows the additional customer wiring required if the alarm option is specifi ed. Figure 5B shows the factory wiring of these switches for future troubleshooting. III. Hand-Auto Station Operation of the Chloromatic TM Valve in the Series & FX4400 Gas Dispensing Systems is identical to that discussed in Instruction Bulletin The dosage adjustment (with its on-off power switch) and the 3-position "1, D, 2" switch (optional) are mounted on the valve case. The optional hand-auto station mounted on the cabinet is used by operator to select either the "manual" or "automatic" mode of operation. Figure 4 shows the legend plate of this station which is mounted on the face of the cabinet, to aid in its understanding. If the "manual" mode is selected, the valve motor is inoperative and will stay in the last position selected. To change gas fl ow through the valve, the operator turns the 3-position switch to either (+) or (-); the switch is spring returned to its normal or off position. As long as the switch is held in the (+) or (-) position, the valve motor is running. It takes approximately seconds for the valve to run full scale. From the front of the cabinet, one can observe the fl owmeter reading as an indication of valve position. If the switch is held in the (+) position, the valve moves open; in the (-) position, the valve moves shut. If the "automatic" mode is selected, the valve is automatically positioned as directed by the input signal(s). In the automatic mode, the (+) and (-) switch positions are inoperative. This hand-auto station is factory installed and wired. Figure 5A shows the wiring diagram used for installation, for future troubleshooting purposes only. Figure 3 - Additional Customer Wiring for Retransmission and/or Alarm Output
5 Figure 4 - Legend Plate for Hand-Auto Switch FUNCTIONAL DESCRIPTION I. Retransmission Option The retransmission signal is taken directly from the feedback potentiometer buffer and is converted from a voltage to a current. Adjustments are provided for zero and span. The current signal provides direct output for customer use and an adjustable current limit; both to be discussed. The V/I converter functions by balancing the feedback voltage and an intermediate voltage signal (which is generated by an intermediate current). Pins 5, 6 & 7 of amplifi er U201B receive the summation of the feedback signal through resistor R21B and zero adjust potentiometer R220 thru R219. This signal is balanced against the intermediate feedback voltage on the wiper of the span adjustment R225. Span and zero potentiometers are adjusted so that a 5 V drop occurs across R224 for a 20 ma output and a 1 V drop at 4 ma output. The amplifi er U201B and Q201 serve the function of shifting signal level to the +24 V supply. Amplifi er U201C (pins 8, 9 & 10) is used to drive the output transistor, Q203. The intermediate voltage signal of R224 on pin 9 is matched at pin 10 by the voltage drop across R227 (negative feedback signal). This voltage drop is the result of current drawn by R236 and Q203. Current limiting is provided through FET transistor Q202, R230 and the limit adjustment potentiometer R231. The limit potentiometer is adjusted so that Q202 begins shutting off when more than 4 ma attempts to pass through the limit circuit. Externally mounted vacuum switches are used with the retransmission option. The switches are wired in series and connect across terminals TB & 16. The switch contacts are closed when there is 1) gas in the cylinder and 2) water to the ejector to create suffi cient vacuum. Under this condition, current will fl ow to the RO terminal as dictated by the feedback potentiometer through the V/I converter. If either vacuum switch opens, only the 4 ma allowed by the current limit circuit can fl ow to the RO terminal. Note: Resistors R221 and R228 are inserted if the retransmission circuit is omitted. The resistors prevent the amplifi ers from oscillating and disturbing the other amplifiers. II. Alarm Option The alarm option consists of either one or two vacuum switches, as specifi ed. The switches are mounted within a metal enclosure which has a terminal barrier strip for customer connection of the alarm(s). If retransmission was also specified, the switches serve a dual function where the other set of contacts are used as a gating circuit. All piping and wiring required for the alarm(s) is completed by the factory; no adjustments are required. III. Hand-Automatic Station The Hand-Auto Station consists of two switches that mount on the face of the cabinet. The upper 2-position switch selects the Automatic or Hand mode of operation. The lower 3-position switch is operative in the hand mode and is used to operate the valve motor. With the switch held in the (+) position, the open winding of the valve motor is energized. Conversely, with the switch in the (-) position, the close winding of the motor is energized. If the 2-position switch is placed in the Automatic mode, the (+) (-)switch is de-activated. Here, the signals from the motor logic and motor drive sections operate the motor. PARTS LIST All parts shown in Parts List Bulletin are valid. Parts listed here are additional parts used with the Chloromatic TM Valve when used in the Series & FX4400 Gas Dispensing Systems. The valve body, cover, orifice and plug (identified as Keys 55, L 59 in Parts List Bulletin ) are valid for 500 PPD Cl 2 or less. Higher capacities use a 1/2" orifi ce & 1/2" valve plug; also the valve body and cover are connected with rigid pipe that is solvent welded. Part numbers are as follows: Key Qty Part Description Part Number 55 1 Valve Plug Assembly --- CL2 & SO2 Service 1000 PPD or 20 kg/h 668B143U PPD or 40 kg/h 668B143U PPD or 60 kg/h 668B143U20 NH3 Services 500 PPD or 10 kg/h 668B143U PPD or 20 kg/h 668B143U Valve Body 668B157U Orifi ce 433F239U Valve Cover 433B062U
6 Figure 5A - Modifi cations & Additional Wring Design improvements may be made without notice. Represented by: De Nora Water Technologies 3000 Advance Lane Colmar, PA ph fax web: mail: info.dnwt@denora.com SEP Registered Trademark All Rights Reserved.
Instruction Manual Series 70CV2000 Chloromatic TM Valve used with Series & FX5500 Gas Dispensing Systems
Instruction Manual Series 70CV2000 Chloromatic TM Valve used with Series 70-5500 & FX5500 Gas Dispensing Systems - 1-100.6620.6 These instructions describe the installation, operation and maintenance of
More informationBaumann Series Flexsleev Control Valve Instructions
Instruction Baumann 86000 Series Instructions Baumann 86000 Series Flexsleev Control Valve Instructions Contents Introduction...1 Scope...1 Safety Precautions...1 Maintenance...2 Installation...3 Air Piping...3
More informationHigh Pressure Solenoid Valves
High Pressure Solenoid Valves Available for Quick Delivery Controls the flow of Gases & Liquids up to 15,000 PSIG Natural Gas, Hydrogen & other High Pressure Gases High Pressure Cryogenics Flammable Liquids
More informationINSTRUCTIONS FOR THE RELIANCE Fast/Tran TM ARL0909 & ARL0909R
INSTRUCTIONS FOR THE RELIANCE Fast/Tran TM ARL0909 & ARL0909R THE RELIANCE Fast/Tran IS NOT FOR "DO-IT-YOURSELF" INSTALLATION. It must be installed by a qualified electrician thoroughly familiar with all
More informationBLD75-1. Bilevel Step Motor Driver. User s Guide. 910 East Orangefair Lane, Anaheim, CA
BLD75-1 Bilevel Step Motor Driver User s Guide A N A H E I M A U T O M A T I O N 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.com (714) 992-6990 fax: (714) 992-0471 website:
More informationDMC mA Positioner
DMC-100 4-20mA Positioner TELEPHONE: +1-859-727-7890 TOLL FREE: +1-800-662-9424 FAX: +1-859-727-4070 E-MAIL: DVOGES@INDELAC.COM MROBINSON@INDELAC.COM TCAYWOOD@INDELAC.COM SHIPPING ADDRESS: 6810 POWERLINE
More informationGEN 5.0 Generator Service Manual
GEN 5.0 Generator Service Manual IMPORTANT: Read all safety precautions and instructions carefully before operating equipment. Refer to operating instruction of equipment that this engine powers. Ensure
More informationPROCESS ELECTRONICS CORPORATION
MINIVERTER MANUAL PROCESS ELECTRONICS CORPORATION 100 BRICKYARD ROAD MOUNT HOLLY, NORTH CAROLINA 28120 TELEPHONE (800) 421-9107 FAX (704) 827-9595 SALES@PECRECTIFIER.COM WWW.PECRECTIFIER.COM SOLID STATE
More informationFSAF24(-S) US, FSAF120(-S) US
FSAF4(-S) US, FSAF10(-S) US On/Off, Spring Return, Meets 50 F [11 C] for Half Hour, 75 Seconds Torque min. 133 in-lb, for control of air dampers Technical Data FSAF4(-S) US, FSAF10(-S) US Power supply
More informationTM4500. Track Mounted Step Motor Driver. User s Guide. CE Certified and RoHS Compliant #L010060
TM4500 Track Mounted Step Motor Driver User s Guide CE Certified and RoHS Compliant A N A H E I M A U T O M A T I O N 4985 E. Landon Drive Anaheim, CA 92807 e-mail: info@anaheimautomation.com (714) 992-6990
More informationVA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators
FIG:mntpos_H2O_app VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions Part No. 14-1336-15, Rev. C Issued July 6, 2011 Supersedes December 28, 2007 Applications The
More informationPEAKTRONICS DMC-101 ADDITIONAL FEATURES. DC Motor Controller, 5A DMC-101
PEAKTRONICS The Peaktronics DC Motor Controller is used for proportional positioning of actuators that use either DC motors or DC solenoids. The wide operating range of the (10 to 30 VDC and loads up to
More informationTechnical Data Sheet SEVO 1230 Clean Agent Cylinders
SEVO 1230 Clean Agent Cylinders 140057, 140069, 140079, 140107, 14817, 14813 U lizing 3M TM Novec TM 1230 Fire Protec on Fluid The agent storage cylinder is a steel pressure vessel manufactured, tested
More informationType I/P & E/P Transducers
Type 1500 I/P & E/P Transducers Type 1500 Description The T-1500 is a new series of electro-pneumatic transducers that convert an electrical signal to a proportional pressure output. It provides precision
More informationModel 930 Power Control System Instruction Manual
Model 930 Power Control System Instruction Manual Publication No. A105328-001 Rev A December 2000 Another quality product from: 7128 Shady Oak Rd, Eden Prairie MN 55344 Phone: (952) 949-9009 Fax: (952)
More informationMinimum 18 in-lb Torque
CM Series Direct Coupled Actuator Minimum 18 in-lb Torque For damper areas up to 6.8 sq-ft* Actuators in bold have BDCM CMB Series - At A Glance CMB24-3 (p. 311) CMB24-3-T (p. 311) CMB120-3 (p. 313) CMB24-SR-R
More informationINSTRUCTION MANUAL AND PARTS LIST FOR 3E CANNED MOTOR PUMPS
TM INSTRUCTION MANUAL AND PARTS LIST FOR 3E CANNED MOTOR PUMPS WARNING This Special Instruction Manual and General Instructions Manual, CA-1, should be read thoroughly prior to pump installation, operation
More information2/2 way Globe Control Valve, threaded connection, 3/8" 3"
2/2 way Globe Control Valve, threaded connection, 3/8" 3" Complete Burkert system using Type 2712 with TopControl 8630 New generation with interchangeable trims, 3 to 5 Cvs value per connection port Excellent
More informationUltrasonic Two-Wire Point Level Control
Ultrasonic Two-Wire Point Level Control General Instructions The Ultrasonic Point Level Control indicates liquid presence/absence within a sensor cavity. Two piezoelectric crystals face each other across
More informationVA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service
VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service Installation Instructions VA-908x Code No. LIT-12011566 Issued August 24, 2009 Applications The VA-908x Series Electric
More informationMaintenance Manual 13 AMPERE POWER SUPPLY 19A704647P1-P3. Mobile Communications LBI-31801C
C Mobile Communications 13 AMPERE POWER SUPPLY 19A704647P1-P3 CAUTION THESE SERVICING INSTRUCTIONS ARE FOR USE BY QUALI- FIED PERSONNEL ONLY. TO AVOID ELECTRIC SHOCK DO NOT PERFORM ANY SERVICING OTHER
More informationProduct Instruction. Door Control Board: Board 1Ø4 for PM/SSC (R3)
Door Control Board: Board 1Ø4 for PM/SSC 61111-149 (R3) 2000-08-31 2000, 1992 KONE Inc. Unpublished work. All rights reserved. No portion of this volume may be used or reproduced in any manner without
More information12 Series Linear Actuators. Operation & Maintenance Manual, Analog Positioner Installation
12 Series Linear Actuators Operation & Maintenance Manual, Analog Positioner Installation 6810 POWERLINE DR.-FLORENCE, KY. 41042 - TELEPHONE 859-727-7890, TOLL FREE 1-800-662-9424 FAX. 859-727-4070, E-MAIL:
More informationESD5100 Series Speed Control Unit PART NUMBER ESD5120 ESD (127)
ESD5100 Series Speed Control Unit 1 INTRODUCTI The ESD5100 Series speed control unit is an all electronic device designed to control engine speed with fast and precise response to transient load changes.
More informationMount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)
EFB and EFX Series Spring Return Direct Coupled Actuator Minimum 70 in-lb Torque For damper areas up to 66 sq-ft* (For lower torque, see AFB, AF, NFB, LF, or TF series) Applications New standard clamp
More informationPCCA POWER CONNECT CARD. DS200PCCAG1A thru DS200PCCAG10A
(Supersedes GEI-100161A) PCCA POWER CONNECT CARD DS200PCCAG1A thru DS200PCCAG10A These instructions do not purport to cover all details or variations in equipment, nor to provide every possible contingency
More informationSAN ANTONIO WATER SYSTEM PURCHASING DEPARTMENT
SAN ANTONIO WATER SYSTEM PURCHASING DEPARTMENT Issued By: D. Anthony Rubin Date Issued: June 22, 2017 BID NO.: 17-17061 FORMAL INVITATION FOR BIDS FOR THE PURCHASE OF TEN (10) AUTOMATIC VALVE SHUTOFF CONTROL
More informationMPV1 INSTALLATION & MAINTENANCE INSTRUCTIONS
MPV1 INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION / IDENTIFICATION The MPV1 series valve uses Proportion- Air closed loop technology for pressure control. It gives an output pressure proportional
More informationMPV1 INSTALLATION & MAINTENANCE INSTRUCTIONS
MPV1 INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION / IDENTIFICATION The MPV1 series valve uses Proportion- Air closed loop technology for pressure control. It gives an output pressure proportional
More informationApplication. Additional Features. Description. Features
1199 Series Packaged Valve and Motor Assemblies Bulletin 1199 January 2010 Direct coupled / packaged assembly no linkage to adjust. Easy setup. Accurate, consistent response. Wide selection of valve types
More informationAPCO ASR-400/450 SEWAGE AIR RELEASE VALVES
APCO ASR-400/450 SEWAGE AIR RELEASE VALVES Instruction D12005 December 2012 Instructions These instructions provide installation, operation and maintenance information for the APCO ASR- 400/450 Sewage
More informationMobile Cylinder Div. Standard Build Series. Catalog HY /US Rev C
Mobile Cylinder Div. Standard Build Series Catalog HY18-0014/US Rev C WARNING - USER RESPONSIBILITY FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE
More informationUltra Compact UHP Liquid Flow Controllers
Ultra Compact UHP Liquid Flow Controllers Model U803 & U804 INTEGRATED LIQUID FLO-CONTROLLERS UHP LIQUID APPLICATION IDEAS Upgrading peristaltic-pump based chemical delivery systems Automated online blending,
More informationWARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES
FILE 29-900 Instructions for Combination Bypass Isolation and Transfer Switches 100-1000 Amps APPLICATION The Cutler-Hammer combination Bypass Isolation and Transfer Switches are listed under Underwriters
More informationSignal Conditioner WEB CONTROL PRODUCTS SC100 FORM NO. L B User Manual. MTY (81)
WEB CONTROL PRODUCTS User Manual Signal Conditioner SC100 FORM NO. L-63-B-0304 1 FORM NO. L-63-B-0304 In accordance with Nexen s established policy of constant product improvement, the specifications contained
More informationBasic Characteristics Data
Basic Characteristics Data Basic Characteristics Data Model Circuit method Switching frequency [khz] Input current [A] Rated input fuse Inrush current protection Material PCB/Pattern Series/Redundancy
More informationOil pump type RSA. Catalogue 1. Burner Components
Burner Components Catalogue 1 Contents Application... page 2 Construction... page 3 Function... page 4 Technical data... page 6 Capacity and operating torque RSA 28... page 7 Capacity and operating torque
More informationNorth American Automatic Manual Reset and Motorized Valves
Combustion North American Automatic Manual Reset and Motorized Valves 1516 Manual Reset 1517 Motorized 1516/1517 Automatic Oil Shutoff Valves Agency approvals: UL, FM, CSA Proof-of-Closure Switch High
More informationTroubleshooting Bosch Proportional Valves
Troubleshooting Bosch Proportional Valves An Informative Webinar Developed by GPM Hydraulic Consulting, Inc. Instructed By Copyright, 2009 GPM Hydraulic Consulting, Inc. TABLE OF CONTENTS Bosch Valves
More informationModel GD-K8A Diffusion Detector Head Operator s Manual
Model GD-K8A Diffusion Detector Head Operator s Manual Part Number: 71-0081RK Revision: 0 Released: 4/25/02 RKI Instruments, Inc. 1855 Whipple Rd. Hayward, CA 94544 (510) 441-5656 Product Warranty RKI
More informationMBD Enhanced Step Motor Driver. User s Guide #L East Orangefair Lane, Anaheim, CA
MBD45021-75 Enhanced Step Motor Driver User s Guide A N A H E I M A U T O M A T I O N 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.com (714) 992-6990 fax: (714) 992-0471 website:
More informationSPECIFICATIONS ATTENTION OPERATION DESCRIPTION
EMP-5 Installation Manual - P/N 80103 - Ed. 01/09 EMP-5 Current or Voltage Input Drive Modulating Actuator Installation Instructions 1 7 SPECIFICATIONS The EMP-5 series actuators provide damper control
More informationValcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual
Valcom Failsafe Unit 1620ESv2 SERIES Operation and Maintenance Manual Table of Contents Section Title Page 1. - Introduction.. 2. - Unpacking the Failsafe unit. 3. - Installation 3.1 - Auto / Timed UPS
More informationRF Point Level Control with Sensor Monitor
The 681 Point Level Control utilizes DPDT relays to provide switching for peripheral devices (such as pumps) in level applications. A sensor attached to the control acts as an antenna to transmit the process
More informationMM1/MM2 INSTALLATION & MAINTENANCE INSTRUCTIONS
MM1/MM2 INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION / IDENTIFICATION The MM series proportional control valves utilize ProportionAir's unique closed loop control technology for superior control
More informationCopeland Screw TM Compressors
Copeland Screw TM Compressors Mechanical Guidelines for SHL & SHM Models using ESC-201 Control System Contents: Start-Up Procedure Operating Specifications Maintenance Trouble Shooting Guidelines Start-up
More informationPRO6.4, PRO6.4E, PRO9.0, PRO9.0E Generator Service Manual
PRO6.4, PRO6.4E, PRO9.0, PRO9.0E Generator Service Manual IMPORTANT: Read all safety precautions and instructions carefully before operating equipment. Ensure equipment is stopped and level before performing
More informationPRESSURE INDEPENDENT CONTROL VALVES (epiv & PICCV )
7 PRESSURE INDEPENDENT CONTROL VALVES (epiv & PICCV ) Pressure independent valves compensate for pressure variations, performing a continual balancing function to maintain system performance at varying
More informationKEYSTONE F777/778 ELECTRIC ACTUATORS
The compact electric actuator for quarter turn (90 ) valve operation providing a torque range from 35 to 4500 Nm Features Aluminium housing with ESPC coating Optimized mounting interface for direct mounting
More informationMinimum 18 in-lb Torque. Applications. TF Series At A Glance. TF Series Spring Return Direct Coupled Actuator. For damper areas up to 4.
TF Series Spring Return Direct Coupled Actuator Minimum 18 in-lb Torque For damper areas up to 4.5 sq-ft* Applications Cost effective quality and performance for a range of applications including: Classroom
More informationSecoVac * Ground & Test Device
GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6
More informationSD Bendix SV-1 Synchro Valve SV-3 & SV-4 Trailer Release Valve CONTROL CONTROL EXHAUST EXHAUST DELIVERY DELIVERY SUPPLY SUPPLY
SD-03-4020 Bendix SV-1 Synchro Valve SV-3 & SV-4 Trailer Release Valve BENDIX SV-3 BENDIX SV-4 PISTON PISTON PISTON PISTON 1/8" P.T. BODY 1/8" P.T. GUIDE BODY GUIDE CHECK DETAIL OF BENDIX SV-3 DETAIL OF
More informationSKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function
SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function Document No. 155-752 SKP25 U.. Description Only when assembled to Series VG Gas valves SKP25 pressure regulating
More informationTension Control Unit Type Product Manual EUROTHERM DRIVES. Copyright Eurotherm Drives Limited Printed in England HA Issue 3
EUROTHERM DRIVES Control Unit Type 5525 Product Manual Copyright Eurotherm Drives Limited 2003 All rights strictly reserved. No part of this document may be stored in a retrieval system, or transmitted
More information3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics
/-, 5/- 5/-way Solenoid Valves for process pneumatics Type 658 stard High flow-rate capacity Reduced power consumption Single or manifold mounting stard Type 658/659 can be combined with... Stard-, EEx
More information2/2 way Globe Control Valve, flange connection, 1/2" 4"
2/2 way Globe Control Valve, flange connection, 1/2" 4" Complete Burkert system using Type 2712 with TopControl 8630 New generation with interchangeable trims, 3 to 5 Cvs value per connection port Excellent
More information1800/1000 Frame RC Snubber Board IS200RCSAG1A
GEI-100303 g GE Industrial Systems 1800/1000 Frame RC Snubber Board IS200RCSAG1A Safety Symbol Legend Indicates a procedure or condition that, if not strictly observed, could result in personal injury
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL
SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationVOG Series VOG15.01xU1 Oil Safety Shut-off Valves with Proof of Closure (POC)
VOG Series VOG15.01xU1 Oil Safety Shut-off Valves with Proof of Closure (POC) Document No. 129-464 VOG15 March 30, 2010 Description Oil Safety Shutoff Valve The VOG15 is an electro-hydraulically actuated
More informationFincor Series 2230 MKII/2240
Fincor Series 2230 MKII/ Fincor Series 2200 regenerative drives are ideal for your more demanding applications. They feature flexibility with ratings up to 5 horsepower. The Series 2230 MKII offers new
More informationClif Mock. CD20 (12VDC) Sampler Drive. User Manual. Manual No A
Clif Mock CD20 (12VDC) Sampler Drive User Manual Manual No. 20165008A 2004 NuFlo Technologies, Inc. All information contained in this publication is confidential and proprietary property of NuFlo Technologies,
More informationVacuum Circuit Breakers (Vehicle)
Vacuum Circuit Breakers (Vehicle) Type AMR For Allis Chalmers 5kV Instructions Installation Operation Maintenance E50001-U229-A289-X-US00 Hazardous voltages and high-speed moving parts. Will cause death,
More informationMAGNETO-INDUCTIVE POSITION DETECTORS
MAGNETO-INDUCTIVE POSITION DETECTORS Series 88 Type 2 wires APPLICATION This four-wire proximity sensor will monitor stroke end and intermediate positions of pneumatic cylinders equipped with built-in
More informationINSTRUCTION MANUAL ACTUATOR CLASSE I TYPE MA, MB
ACTUATOR CLASSE I TYPE MA, MB CONTENTS Page : 2/13 PRODUCT DESCRIPTION General description 3 Product specification 5 INSTALLATION Storage 6 Unpacking 7 Handling 7 Installation : Mechanical 7 Installation
More informationVA-715x Electric Valve Actuator
Product/Technical Bulletin VA-7150 Issue Date 0513 VA-715x Electric Valve Actuator The VA-715x Series synchronous motor-driven actuator provides incremental (three wire), incremental with feedback, or
More information5001TCP SPEED CONTROLLER
VARIABLE SPEED DRIVE CONTROLLER INSTALLATION AND SETTING UP MANUAL 5001TCP SPEED CONTROLLER With PC101 Torque Limit Control WARNING Disconnect all incoming power before working on this equipment. Follow
More informationREGAL SMARTVALVE Models 7001 and 7006
INSTRUCTION BULLETIN 17000 1044 SE Dixie Cutoff Road, Stuart, Florida 34994 USA Phone: (772) 288-4854 Fax: (772) 287-3238 www.regalchlorinators.com Email: regal@regalchlorinators.com REGAL SMARTVALVE Models
More informationTBS100FC CASE SEALER DESCRIPTION AND SET UP PROCEDURES
INTRODUCTION In order to achieve maximum production and reliability from this system, it is necessary to be familiar with its capabilities. Knowledge of installation, components and set up are essential
More informationG3 (D) 3-way Globe Valve, Bronze Trim
G3 (D) 3-way Globe Valve, Bronze Trim pplication This valve is typically used in ir Handling Units on heating or cooling coils and Fan Coil Unit heating or cooling coils. Some other common applications
More informationCD-20A Sample Probe Controller User Manual
CLIF MOCK CD-20A Sample Probe Controller User Manual Class I Groups C and D Hazardous Locations Manual No. 2350753-01, Rev. 02 Symbols and Terms Used in this Manual Important Safety Information! WARNING:
More informationSERIES 300V 115 and 230 VOLT AC FUEL TRANSFER PUMP Owner's Operation & Safety Manual Models FR300V, FR301V, FR310V & FR311V
SERIES 300V 115 and 230 VOLT AC FUEL TRANSFER PUMP Owner's Operation & Safety Manual Models FR300V, FR301V, FR310V & FR311V SAFETY INSTRUCTIONS To ensure safe and effi cient operation, it is essential
More informationVE VVG Series Electronic Two-way Valves Normally Closed
VE VVG Series Electronic Two-way s Normally Closed Document No. 155-112P25 VE VVG-1 Description The VE VVG electronic two-way valves control the flow of water or glycol solutions. The electronic actuator
More informationInstallation, Operation and Maintenance Manual
HQ 005. ELECTRIC ACTUATORS QUARTER-TURN ELECTRIC ACTUATORS Installation, Operation and Maintenance Manual s Version Ver. 1 Revision Rev. 1 Document No. HKQI-611 Small & Compact Design High corrosion resistance
More informationType 2511/12. Type Type 2030 Cable plug. ASI cable plug. Dosing control. General technical data Orifice Type 6518
3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics Type 658 standard standard High flow-rate capacity Reduced power consumption Single or manifold mounting Standard-, EEx m and EEx i versions
More informationValve Positioners Offer Improved Control Valve Performance White Paper
spiraxsarco.com Valve Positioners Offer Improved Control Valve Performance White Paper V a l v e P o s i t i o n e r s Contents 1.0 Executive Summary 2.0 Control Valve Basics 3.0 Valve Positioner 3.1 Faster
More information3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics
/2-, 5/2-5/-way Solenoid Valves for process pneumatics Type 658 stard High flow-rate capacity Reduced power consumption Single or manifold mounting stard Type 658/659 can be combined with... Stard-, EEx
More information5001TCP SPEED CONTROLLER
INSTALLATION AND SETTING UP MANUAL 5001TCP SPEED CONTROLLER WARNING Disconnect all incoming power before working on this equipment. Follow power lockout procedures. Use extreme caution around electrical
More informationProportional pressure relief valve, pilot operated
Electric Drives and Controls Hydraulics Linear Motion and ssembly Technologies Pneumatics Service Proportional pressure relief valve, pilot operated R 29160/04.05 Replaces: 06.98 1/10 Model DE(M) and DE(M)E
More informationOpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc
Document No. 155-187P25 EA GDE/GLB-1 OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc Description The OpenAir direct coupled 24 Vac non-spring
More informationQuarter Master Chief Series 92 Actuator
Quarter Master Chief Series 92 Actuator Installation, Operation and Maintenance Manual File: Series 92 O & M manual Rev. V 4/22/2013 Page 1 of 13 Table of Contents Series 92 Electric Actuator Introduction...
More informationSentry Battery Charger. Installation and Operations Manual Section 75
Sentry Battery Charger Installation and Operations Manual 00-02-0616 03-03-08 Section 75 In order to consistently bring you the highest quality, full featured products, we reserve the right to change our
More informationJ1 Plug Pin Identification
D D8 D D D D ART_8 J 8 D D0 R R R R TB 80 D D D D D D J Plug Pin Identification PIN # WIRE # SIGNAL FUNCTION 0 INPUT Drive Reverse INPUT Drive Forward OUTPUT Brake, Decel Valve signal 8 INPUT Steer Left
More informationGE Sensing & Inspection Technologies
GE Sensing & Inspection Technologies Modus Model RPM-1 Room Pressure Monitor Installation and Setup Guide 1. GENERAL The RPM-1 monitors either positive or negative room pressures (see the Datasheet for
More informationBOSTON TOWER MERCHANDISER ILLUMINATION KIT (P/N ) INSTALLATION INSTRUCTIONS
BOSTON TOWER MERCHANDISER ILLUMINATION KIT (P/N 629097072) INSTALLATION INSTRUCTIONS Release Date: May 12, 2011 Publication Number: 629097072INS Revision Date: March 17, 2014 Revision: D Visit the Cornelius
More informationSignet 2760 DryLoc ph/orp Preamplifier
Signet 2760 DryLoc ph/orp Preamplifier *3-2760.090* 3-2760.090 Rev. H 05/11 English English SAFETY INSTRUCTIONS 1. Depressurize and vent system prior to installation or removal. 2. Confi rm chemical compatibility
More informationType Type 1001 Transducers. I/P & E/P Transducers
Type 1001 I/P & E/P Description The Type 1001 is a patented family of electropneumatic instruments that is used to reduce a supply pressure to a regulated output pressure which is directly proportional
More informationIsolation Switch (behind barrier & inspection window) Power Fuses. Load Cable Connection Box. Contactor. Control Power Transformer Secondary Fuse
Instruction Bulletin Class 8198 ISO-FLEX Medium Voltage Controller Model 3, Series B Installation and Maintenance Bulletin No. 50006-376-01 August, 1995 Raleigh, NC, USA TABLE OF CONTENTS Introduction...
More informationI-BFV.KIT Butterfly Valve Gear Operator Replacement
SERIES 5, 05,, and 0C WARNING Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic piping products. Depressurize and drain the piping system before
More informationUL/cUL FILE NUMBER E CE See last page of manual for CE Declaration of Conformity.
INSTALLATION, OPERATION and MAINTENANCE MANUAL MODEL SCPF1 15, 25, 40 & 65 AMP SCR POWER CONTROLS UL/cUL FILE NUMBER E151547 CE See last page of manual for CE Declaration of Conformity. AMETEK HDR POWER
More informationModel 1100 Turbine Flow Meter
Model 1100 Turbine Flow Meter INSTALLATION & INSTRUCTION MANUAL 8635 Washington Avenue Racine, Wisconsin 53406 Tel: 800-433-5263 or 262-639-6770 Fax: 800-245-3569 or 262-639-2267 www.hedland.com TABLE
More informationT21 Thermal Differential Switch
T21 Thermal Differential Switch General Instructions The T21 Point Level Switch is a state-of-the-art in liquid level and interface measurement and control. Level detection is accomplished by using a high-resolution
More informationPower thyristor units. 460 series. Control of single-phase resistive and inductive loads. User Manual
Power thyristor units 460 series Control of single-phase resistive and inductive loads User Manual Copyright Eurotherm Automation 1996 All rights reserved. All reproduction or transmission in any form
More informationBIG BLASTER XHV Air Cannon Retrofit with MARTIN TORNADO Exhaust Valve
BIG BLASTER XHV Air Cannon Retrofit with MARTIN TORNADO Exhaust Valve Go to BIG BLASTER XHV Air Cannon Retrofit with MARTIN TORNADO Exhaust Valve web page MARTIN TORNADO Exhaust Valves Retrofit Internal
More informationFAIRCHILD T5420 DIGITAL-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions
FAIRCHILD T5420 DIGITAL-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions Figure 1. T5420 Outline Dimensions. INSTALLATION The Model T5420 can be mounted directly onto a flat surface
More informationJ1 Plug Pin Identification
D5 D8 D7 D4 D5 D ART_8 J 4 8 D D0 7 R R R R4 TB 80 D D D D4 D D J Plug Pin Identification PIN # WIRE # SIGNAL FUNCTION 0 INPUT Drive Reverse INPUT Drive Forward OUTPUT Brake, Decel Valve signal 4 8 INPUT
More informationYaskawa Electric America Unit Troubleshooting Manual Section One: Introduction & Checks Without Power GPD 506/P5 and GPD 515/G5 (0.
Yaskawa Electric America Unit Troubleshooting Manual Section One: Introduction & Checks Without Power GPD 506/P5 and GPD 515/G5 (0.4 ~ 160kW) Page 1 Introduction This manual is divided into three sections:
More informationNEOTECHA NTB-NTC BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS
Before installation these instructions must be fully read and understood 2 SAFETY Please also read through these notes carefully. 2.1 General potential danger due to: a. Failure to observe the instructions
More informationESD5500E Series Speed Control Unit
ESD5500E Series Speed Control Unit 1 SPECIFICATIONS INTRODUCTION PERFORMANCE Isochronous Operation ± 0.25% or better Speed Range / Governor 1-7.5 KHz Continuous Speed Drift with Temperature ±1% Maximum
More informationDIAMOND POINT VIBRATING PROBES
DIAMOND POINT VIBRATING PROBES DP130 DP120 DP140 DP150 Instruction Manual Third revision, April 2016 Hycontrol Ltd., Larchwood House, Orchard Street, Redditch, Worcestershire, B98 7DP, U.K. Tel: + 44 (0)1527
More informationMDC Series
MDC050-050051 Series 50V, 5A Brushless Controller User s Guide A N A H E I M A U T O M A T I O N 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.com (714) 992-6990 fax: (714)
More information