Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description

Size: px
Start display at page:

Download "Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description"

Transcription

1 Worldwide Contacts Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description The TYCO Model QRS Electronic Accelera tor is a quick opening device intended to reduce the operating time of a dry pipe valve in a dry pipe system or an automatic control valve (deluge valve) in a double interlock electric/ electric preaction system. The control panel for the QRS may be used with up to four QRS switches for one to four system risers using one of the following dry pipe valves: TYCO in. & in. (DN00/0) Model DPV- Dry Pipe Valves Central in. (DN80) Model AF or Central in. & in. (DN00/0) Model AF/AG Dry Pipe Valves Gem in. & in. (DN00/0) Model F0/F0 Dry Pipe Valves Star in. & in. (DN00/0) Models A or A- Dry Pipe Valves The control panel for the QRS may be used with one QRS switch for one system riser using the following automatic control valve (deluge valve) used in a double interlock electric/electric preaction system: TYCO -/ in. thru 8 in. (DN0 thru DN00) DV- Deluge Valve The Model QRS Electronic Accelera tor (Ref. Figure ) utilizes a unique system air pressure monitoring device (UL and C-UL Listed, as well as FM Approved, Model QRS Extinguishing System Attachment) that continuously samples air pressure twice per sec ond. When the air pressure is deter mined to have a sustained drop ex ceeding a rate of 0. psi (0,00 bar) per second as verified by three con secutive samplings, the QRS signals the Releasing Panel (Model PFC 0-RC) via its Panel Input initiating zone circuit, which energizes the Sole noid Valve. IMPORTANT Refer to Technical Data Sheet TFP00 for warnings pertaining to regulatory and health information. In the case of a dry pipe valve, the energized Solenoid Valve introduces system air pressure to the intermediate chamber of the dry pipe valve. This pressure neutralizes the differential pressure holding the dry pipe valve closed and permits it to open. In the case of a double interlock electric/electric preaction system, the energized Solenoid Valve releases diaphragm pressure from the automatic control valve (deluge valve) to permit the automatic control valve (deluge valve) to open. The Model QRS Electronic Accelerator automatically adjusts to both small and slow changes in system pressure, but trips when there is a steady drop in pressure (as in the case of sprinkler operation). The QRS Electronic Accelerator features the following: Operation of a dry pipe or preaction valve within four seconds independent of various combinations of system initial air pressures, system volumes, or sprinkler K-factors One Releasing Panel can control up to four dry pipe systems or one double interlock preaction system Built-in low pressure and high pressure alarm supervision Proven electric release technology as used for electrically operated del uge and preaction systems Battery back-up in the event of primary power failure NOTICE The Model QRS Electronic Accelerator described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PRO- TECTION ASSOCIATION, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of this de vice. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. Contact the installing contractor or sprinkler manufacturer with any questions. The QRS uses electronic components to monitor the system air pressure. Keep all radio transmitters or RF sources at least one foot from the QRS. Failure to do so could result in an unintended operation of the dry pipe or preaction system. For additional information please refer to the Potter Electric Signal Company Data Sheet # for the QRS Quick Release Switch and/or Manual #00 for the PFC-0RC Releasing Panel. Technical Data Approvals UL Listed: The Model QRS Electronic Accelerator is UL Listed per UL8 for a maximum system capacity of 90 gallons (9 litters) for a single nominal. K-factor sprinkler and a maximum working water pressure of psi (, bar). FM Approved: The Model QRS Electronic Accelerator is FM Approved based on the sensitivity criteria provided in Graph A and a maximum working water pressure of 0 psi (, bar). Listings and Approvals are under the name of Potter Electric Signal Com pany. Page of AUGUST 08 TFP00

2 TFP00 Page of NOTICE Quick operation of the Electronic Ac celerator does not ensure that the fire protection system will meet the water delivery time requirement of the authority having jurisdiction (following opening of the Inspector s Test Connection). The sprinkler system designer must be knowledgeable that water delivery time is primarily determined by the configuration and volume of the piping network, system air pressure at time of Accelerator trip, number and orifice size of open sprinklers, and water supply characteristics. In the case of a double interlock preaction system, water delivery is also based on the electric detection system operating before the first sprinkler activates. Dry Pipe Valve Compatibility The Model QRS Electronic Accelerator is UL Listed and FM Approved for use with the following dry pipe valves: in. and in. (DN 00/0) TYCO DPV- in. (DN80) Central AF in. and in. (DN00/0) Central AF/AG in. and in. (DN00/0) Gem F0/F0 in. and in. (DN00/0) Star Model A in. and in. (DN00/0) Star Model A- Preaction System Compatibility The Model QRS Electronic Accelera tor is UL Listed and FM Approved for use with the -/ in. thru 8 in. (DN0 thru DN00) DV- Double Inter lock Electric/Electric Preaction Sys tem. Refer to TFP. Maximum Working Air Pressure 0 psi (,8 bar) Pressure Decay For Trip Rating 0. psi/sec. (0,00 bar/s) High/Low Pressure Settings Refer to Table A. Environmental Specifications The QRS Quick Release Switch is for indoor use only (NEMA /IP0). Battery Back-Up Battery back-up for dry pipe systems is provided by two BT-0 ( AH) batteries or two (optional) BT-80 (8 AH) batteries. (See Ordering Procedure for details.) The two BT-0 batteries provide: 0 hours in standby with four QRS s; With four QRS s connected, with one in alarm and the solenoid activated continuously, the batteries will provide additional hours of standby; With three QRS s connected, with one in alarm and the solenoid activated continuously, the batteries will provide additional hours of standby; With two QRSs connected, with one in alarm and the solenoid activated continuously, the batteries will provide additional hours of standby. For double interlock preaction systems, battery calculations must be performed by the system designer to determine adequacy of the two batteries to meet the requirements of the authority having jurisdiction. A battery calculation form can be accessed on the Potter web site at batterytools/php Installation The TYCO Model QRS Electronic Accelera tor must be installed in accordance with this section: Step. The QRS Electronic Accelera tor Riser Components (P/N -- 00) must be installed per Figure or 8 as applicable; the DV- Double Interlock Preaction Trim with Electric/Electric Actuation and Model QRS Electronic Accelerator must be installed per Figure A or B; the solenoid valve must be installed with its flow direction arrow as indicated; and, pipe thread sealant is to be applied sparingly to male threads only. Step. The Releasing Panel is to be located in a dry and protected area; however, it should be located in close proximity to the valve riser(s). (In the case of one panel being used for multiple dry pipe valve risers, it is recommended that a single panel only be used when the multiple risers are ad jacent to each other. Otherwise, difficulty may be encountered when performing the resetting procedure.) Step. The QRS Quick Release Switch, Solenoid Valve, and Releasing Panel must be wired per Figure or, as applicable. All electrical connections are to meet the requirements of NFPA. NOTICE Figure provides the wiring connections for dry pipe systems using the PFC-0RC Standard Program #. Figure provides the wiring connections for a double interlock elec tric/ electric preaction system using the PFC-0RC Standard Program #. In the case of Figure, the EOLR for the supervisory circuit is located in the last QRS Quick Release Switch. In the case of Figure, the EOLR for the supervisory zone is located at the QRS and the Orange and Yellow wires are not used. Any tamper switches for sys tem shut off valves required for double interlock preaction systems should be connected to Zone of the PFC-0 RC releasing panel which is pro grammed as a Tamper Zone. Refer to PFC-0RC Manual #00. All QRS wiring must be terminated (landed) while the PFC-0RC is deenergized. Failure to do so may result in unseen damage to the QRS, rendering it inoperable. To de-energize the PFC-0RC, disconnect the stand-by batteries, then disconnect the A/C input. Reverse this process to re-energize the panel. For additional PFC-0RC Releasing Panel information (e.g., power and battery connections, programming, basic operation, etc.) refer to the Potter Electric Signal Company Manual #00. Step. As a function of the nominal air pressure to be maintained in the sprin kler system, set the 0 position, high/low level, rotary switch setting of the QRS Quick Release Switch using the information provided in Table A on Page, as well as inside the cover of the QRS Quick Release Switch. Step. To complete the installation, the cover of the QRS Quick Release Switch must be securely fastened to the base to ensure metal-to-metal contact, and the PFC-0RC Releasing Panel must be programmed using Standard Program # or #, as ap plicable. Programming instructions are provided in Potter Electric Signal Company Manual #00.

3 TFP00 Page of MODEL QRS QUICK RELEASE SWIT P/N IN (DN00) MODEL DPV- DRY PIPE WITH TRIM SHOWN 0 VAC VDC (NORMALLY CLOSED UNTIL ENERGIZED) P/N MODEL QRS ELECTRONIC ACCELERATOR TRIM P/N FIGURE MODEL QRS ELECTRONIC ACCELERATOR TYPICAL ARRANGEMENT SHOWN ON ONE DRY PIPE MODEL PFC-0-RC RELEASING PANEL, P/N 0, WITH: MODEL BT-0 BATTERY BACK-UP, P/N 08; OR MODEL BT-80, BATTERY BACK-UP, P/N 0 Switch Setting Low Air Threshold psi (bar) (0,8) (0,8) (,0) (,0) 0 (,8) (,) 0 (,0) (,) (,0) (,9) Nominal Pressure psi (bar) 0 (0,9) (,0) 0 (,8) (,) 0 (,0) (,) 0 (,) (,0) (,9) (,8) TABLE A HIGH/LOW PRESSURE SETTINGS FOR THE MODEL QRS QUICK RELEASE SWIT High Air Threshold psi (bar) (,0) 0 (,8) (,) 0 (,0) (,) 0 (,) (,0) 0 (,) 0 (,) 0 (,8)

4 TFP00 Page of 800 (098) 00 (98) K. 00 (908) K=8.0 MAXIMUM SYSTEM CAPACITY, GALLONS (LITRES) 00 (8) 000 (0) 800 (8) 00 (0) 00 (99) K=. K=. 00 () 000 (8) NOTES 800 (08) (0,) (,) (,) (,8) (,) (,) MINIMUM SYSTEM AIR PRESSURE, PSI (BAR). Quick operation of the Electronic Accelerator does not ensure that the fire protection system will meet the water delivery time requirement of the authority having jurisdiction (following opening of the Inspector s Test Connection). The sprinkler system designer has to be aware that water delivery time is primarily determined by the configuration and volume of the piping network, system air pressure at time of Accelerator trip, number and orifice size of open sprinklers, and water supply characteristics.. The sensitivity criteria for the Model QRS Electronic Accelerator is a function of its pressure decay for trip rating of 0. psi (0,00bar) per second, as well as the system volume, the K-factor of the sprinklers being utilized, and the minimum initial air pressure. The larger the system volume combined with smaller sprinkler K-factor or lower initial air pressure results in a slower air decay rate upon the first sprinkler operation. Conversely, a smaller system volume combined with a larger sprinkler K-factor or higher initial air pressure results in a faster air decay rate.. When the sprinkler system has been designed with in the criteria provided by Graph A, operation of the Model QRS Electronic Accelerator and subsequent operation of the associated dry pipe or preaction valve can be expected within four seconds. In the case of the double interlock preaction system, operation is based on the electric detection system operating before a first sprinkler operation.. The minimum system air pressure must be the greater of that required for the dry pipe / preaction valve as a function of the maximum expected water supply pressure or per Graph A when using the Model QRS Electronic Accelerator.. When multiple sprinkler operations are being considered as in the case of using a dry system water delivery design per the 00 edition of NFPA, Section...9, use the. K-factor and larger curve as referenced in Example. EXAMPLES. Assuming a system volume of 00 gallons (80 liters) and the use of sprinklers having a K-factor of., the minimum system air pressure must be 8. psi (, bar).. Assuming a system volume of 000 gallons (0 liters) and the use of sprinklers having a K-factor of 8.0, the minimum system air pressure must be.0 psi (, bar).. Assuming the use of a dry system water delivery design per the 00 edition of NFPA, Section..., where in the operation of two. K-factor sprinklers might be anticipated (and the effective K-factor is then.), the. K-factor and larger curve can be utilized. Consequently, assuming a system volume of 00 gallons (908 liters), the minimum system air pressure must be. psi (0,8 bar). GRAPH A MODEL QRS ELECTRONIC ACCELERATOR SENSITIVITY CRITERIA BASED ON FM APPROVAL

5 TFP00 Page of /" NPT ACCELERATOR TRIM CONNECTION TO AIR SUPPLY PORT -/ or IN (DN or DN80) /" NPT ACCELERATOR TRIM CONNECTION TO INTERMEDIATE AMBER /" NPT ACCELERATOR TRIM CONNECTION TO AIR SUPPLY PORT 8 9 QUICK RELEASE SWIT 0 /" CONDUIT CONNECTION TO RELEASING PANEL QUICK RELEASE SWIT 8 NO DESCRIPTION QTY P/N Quick Release Switch, Model QRS Solenoid Valve /" Union /" Tee /" 90 Elbow /" x Close Nipple..... /" x -/" Nipple /" x -/" Nipple for - and Inch Valves.. /" x -/" Nipple for for and Inch Valves.. 9 /" x -/" Nipple for - and Inch Valves.. /" x -/" Nipple for Inch Valves /" x " Nipple for Inch Valves /" x " Nipple for - and Inch Valves.. /" x 9-/" Nipple for Inch Valves /" x 8-/" Nipple for Inch Valves /" NPT ACCELERATOR TRIM CONNECTION TO AIR SUPPLY PORT : Common Hardware QUICK RELEASE SWIT 8 /" NPT ACCELERATOR TRIM CONNECTION TO INTERMEDIATE AMBER 9 0 /" CONDUIT CONNECTION TO RELEASING PANEL /" NPT ACCELERATOR TRIM CONNECTION TO INTERMEDIATE AMBER 9 0 /" CONDUIT CONNECTION TO RELEASING PANEL IN (DN00) IN (DN0) FIGURE MODEL QRS ELECTRONIC ACCELERATOR RISER COMPONENTS INSTALLATION DIAGRAM FOR THE AND IN MODEL DPV- DRY PIPE S (PN ---00)

6 TFP00 Page of NO. DESCRIPTION QTY. P/N 00 psi/ 000 kpa Water Pressure Gauge /" Gauge Test Valve Model MC- Manual Control Station Model AD- Automatic Drain Valve Model ASV- Automatic Shut-Off Valve Waterflow Pressure Alarm Switch, Model PS /" Ball Valve /" Spring Loaded Check Valve /" Y-Strainer /" Swing Check Valve /" Angle Valve Drip Funnel Connector Drip Funnel Bracket Drip Funnel /" Vent Fitting /" x 8" Tubing /" Tubing Connector /" x " Tubing /" Plug /" Plug /" Union /" Union /" 90 Elbow /" 90 Elbow /" 90 Elbow /" x /" 90 Elbow /" Tee /" x /" x /" Tee /" Tee /" x /" x /" Tee NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N /" x Close Nipple /" x Close Nipple /" x -/" Nipple /" x " Nipple /" x -/" Nipple /" x " Nipple /" x " Nipple Select Nipple per Table Select Nipple per Table /" x -/" Nipple /" x " Nipple /" x " Nipple P 0 psi/ 0 kpa Air Pressure Gauge P /" Gauge Test Valve P Item No. Not Used P /" Pressure Relief Valve P /" Swing Check Valve P /" Globe Valve P /" Angle Valve P8 /" Plug P9 /" x /" Reducing Bushing P0 /" Union P /" 90 Elbow P /" Cross P /" x /" x /" Tee P " x /" x /" Tee P /" x " Nipple /" x -/" Nipple P /" x -/" Nipple P8 /" x -/" Nipple P9 " x " Nipple E Item No. Not Used E /" Tubing Connector E /" x " Tubing E /" x -/" Nipple Q Model QRS Quick Release Switch Q Releasing Panel, Model PFC-0RC Q Battery Back-Up, Model BT COMPONENTS INCLUDED ONLY IN PRE-TRIMMED ASSEMBLIES: A Model CV-FR Check Valve, " (DN0) A Butterfly Valve, Power Ball 00: -/" (DN0) A " (DN0) A A Figure Coupling: -/" (DN0) ACP " (DN0) ACP A Coupling for -/" (DN0) DV-: Figure Reducing Coupling, " x -/".. 0ES Coupling for " (DN0) DV-: Figure Coupling, " ACP A Solenoid Valve Nipple Number 8 9 Select Appropriate Nipple Sizes per DV- Deluge Valve Size -/" (DN0) /" x Close /" x " " (DN0) /" x " /" x -/" 0 FOR OPTIONAL ELECTRICALLY SUPERVISED N.O. ALARM CONTROL P NOTES:. Supervised Double Interlock Preaction Trim with Electric/ Electric Release is comprised of Items - plus Items P-P9 and Items E-E. Items A-A included only in pre-trimmed valve assemblies as applicable; otherwise ordered separately.. All Fittings and Nipples are galvanized (Standard Order).. : Common Hardware. (GREEN TINT) 0 P 9 0 P8 0 P0 0 P P 9 P 0 0 P Q P9 P P P9 0 P8 PLUG UNUSED PORTS P8 P8 P 0 8 " (DN0) GROOVE x GROOVE DV- DELUGE SHOWN P A A P A A P NOTES:. See Figure of TFP0 for Deluge Valve Port identification.. Route all Tubing to Drip Funnel, Item. FIGURE A (PART OF ) EXPLODED VIEW OF -/ AND IN (DN0 AND DN0) DV- DELUGE S DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/ELECTRIC ACTUATION SEMI-PREASSEMBLED TRIM (-8--8Q) WITH MODEL QRS ELECTRONIC ACCELERATOR, POTTER PFC-0RC PANEL AND BT0 BATTERIES E E Q A E Q

7 TFP00 Page of NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N 00 psi/ 000 kpa Water Pressure Gauge /" 90 Elbow P -/" Angle Valve /" Gauge Test Valve Model MC- Manual Control Station Model AD- Automatic Drain Valve Model ASV- Automatic Shut-Off Valve... Waterflow Pressure Alarm Switch, Model PS /" Ball Valve /" Spring Loaded Check Valve /" Y-Strainer /" Swing Check Valve /" Angle Valve /" Tee /" x /" x /" Tee /" Tee /" x /" x /" Tee /" x Close Nipple /" x Close Nipple /" x -/" Nipple /" x -/" Nipple /" x -/" Nipple /" x " Nipple /" x -/" Nipple P8 /" Plug P9 /" x /" Reducing Bushing P0 /" Union P /" 90 Elbow P /" Cross P /" x /" x /" Tee P -/" x -/" x /" Tee P /" x " Nipple /" x -/" Nipple P -/" x " Nipple P8 -/" x " Nipple Drip Funnel Connector /" x " Nipple E Item No. Not Used Drip Funnel Bracket /" x -/" Nipple E /" Tubing Connector Drip Funnel /" x " Nipple E /" x " Tubing /" Vent Fitting /" x -/" Nipple E /" x -/" Nipple /" x 8" Tubing /" x " Nipple /" Tubing Connector /" x " Nipple Q Model QRS Quick Release Switch /" x 8" Tubing /" x " Nipple Q Releasing Panel, Model PFC-0RC /" Plug Q Battery Back-Up, Model BT /" Plug P 0 psi/ 0 kpa Air Pressure Gauge P /" Gauge Test Valve COMPONENTS INCLUDED ONLY IN /" Union /" Union P Item No. Not Used PRE-TRIMMED ASSEMBLIES: /" 90 Elbow P /" Pressure Relief Valve A Model CV-FR Check Valve, " (DN80) /" 90 Elbow /" x /" 90 Elbow P /" Swing Check Valve P /" Globe Valve A Model BFV-N Butterfly Valve, " (DN80)... A Figure Coupling, " (DN80) F00N 0ACP A Solenoid Valve FOR OPTIONAL ELECTRICALLY SUPERVISED N.O. ALARM CONTROL 0 8 NOTES:. Supervised Double Interlock Preaction Trim with Electric/ Electric Release is comprised of Items - plus Items P-P8 and Items E-E. Items A-A included only in pre-trimmed valve assemblies as applicable; otherwise ordered separately.. All Fittings and Nipples are galvanized (Standard Order).. : Common Hardware. P (GREEN TINT) 0 8 P 9 P 0 P0 9 P P P P9 P P Q P8 P P PLUG UNUSED PORTS P8 P8 8 " (DN80) GROOVE x GROOVE DV- DELUGE SHOWN P8 P P A A A A NOTES:. See Figure of TFP0 for Deluge Valve Port identification.. Route all Tubing to Drip Funnel, Item. FIGURE A (PART OF ) EXPLODED VIEW OF IN (DN80) DV- DELUGE DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/ELECTRIC ACTUATION SEMI-PREASSEMBLED TRIM (-8--Q) WITH MODEL QRS ELECTRONIC ACCELERATOR, POTTER PFC-0RC PANEL AND BT0 BATTERIES E E Q A E Q

8 TFP00 Page 8 of NO. DESCRIPTION QTY. P/N 00 psi/ 000 kpa Water Pressure Gauge /" Gauge Test Valve Model MC- Manual Control Station Model AD- Automatic Drain Valve Model ASV- Automatic Shut-Off Valve Waterflow Pressure Alarm Switch, Model PS /" Ball Valve /" Spring Loaded Check Valve /" Y-Strainer /" Swing Check Valve Item No. Not Used " Angle Valve Drip Funnel Connector Drip Funnel Bracket Drip Funnel /" Vent Fitting /" x " Tubing /" Tubing Connector /" x " Tubing /" Plug /" Plug /" Union " Union /" 90 Elbow /" 90 Elbow /" Tee /" x /" x /" Tee /" x /" x /" Tee " x /" 90 Elbow " x /" x " Tee " 90 Elbow /" x Close Nipple /" x Close Nipple NO. DESCRIPTION QTY. P/N /" x -/" Nipple /" x -/" Nipple /" x " Nipple /" x " Nipple /" x " Nipple /" x " Nipple Select Nipple per Table Select Nipple per Table Select Nipple per Table /" x -/" Nipple /" x " Nipple Select Nipple per Table " x Close Nipple " x " Nipple Item No. Not Used 9 " x " Nipple /" x 9" Nipple P 0 psi/ 0 kpa Air Pressure Gauge P /" Gauge Test Valve P Item No. Not Used P /" Pressure Relief Valve P /" Swing Check Valve P /" Globe Valve P " Angle Valve P8 /" Plug P9 /" x /" Reducing Bushing P0 /" Union P /" 90 Elbow P /" Cross P /" x /" x /" Tee P " x " x /" Tee P /" x " Nipple /" x -/" Nipple P " x " Nipple NO. DESCRIPTION A Model CV-FR Check Valve: " (DN00) " (DN0) " (DN00) A Model BFV-N Butterfly Valve: " (DN00) " (DN0) " (DN00) A Figure Coupling: " (DN00) " (DN0) " (DN00) A Solenoid Valve Nipple No. " 0 (DN00) /" x -/" /" x " /" x -/" /" x -/" QTY. P/N E Item No. Not Used E /" Tubing Connector E /" x " Tubing E /" x -/" Nipple Q Model QRS Quick Release Switch Q Releasing Panel, Model PFC-0RC Q Battery Back-Up, Model BT COMPONENTS INCLUDED ONLY IN PRE-TRIMMED ASSEMBLIES: Select Appropriate Nipple Sizes per DV- Deluge Valve Size F00N 900F00N 900F080N 0ACP 0ACP 80ACP " 8" (DN0) (DN00) /" x -/" /" x 8 -/" /" x " /" x -/" /" x -/" /" x 9" /" x -/" /" x -/" FOR OPTIONAL ELECTRICALLY SUPERVISED N.O. ALARM CONTROL 8 0 P NOTES:. Supervised Double Interlock Preaction Trim with Electric/ Electric Release is comprised of Items -0 plus Items P-P and Items E-E. Items A-A included only in pre-trimmed valve assemblies as applicable; otherwise ordered separately.. All Fittings and Nipples are galvanized (Standard Order).. : Common Hardware. (GREEN TINT) P 8 P 9 P 0 0 P P0 P P 9 P9 P 0 P Q 9 P P P8 " (DN00) GROOVE x GROOVE DV- DELUGE SHOWN P8 PLUG UNUSED PORTS P8 P P 9 0 NOTES:. See Figure of TFP0 for Deluge Valve Port identification.. Route all Tubing to Drip Funnel, Item. FIGURE A (PART OF ) EXPLODED VIEW OF,, AND 8 IN (DN00, DN0, AND DN00) DV- DELUGE S DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/ELECTRIC ACTUATION SEMI-PREASEMBLED TRIM (-8--Q) WITH MODEL QRS ELECTRONIC ACCELERATOR, POTTER PFC-0RC PANEL AND BT0 BATTERIES A A A A 9 8 E 8 E Q 9 A E 8 Q

9 TFP00 Page 9 of NOTES:. Use only " (DN0) Model CV-FR Riser Check Valve in -/" (DN0) and " (DN0) assemblies. Use CV-FR Valve size equal to mating DV- Valve in larger assemblies.. Nipples - vary in length relative to DV- size. Select per table. All other nipples packed unassembled shall be installed per appropriate trim exploded view, Figure A Part,, or.. Install subassemblies in alphabetical order.. See Figure of TFP0 for Deluge Valve Port identification.. Route all Tubing to Drip Funnel. / IN NPT CONNECTION FOR WATER MOTOR ALARM FOR OPTIONAL ELECTRICALLY SUPERVISED N.O. ALARM CONTROL WATERFLOW PRESSURE ALARM SWIT NIPPLE MAIN DRAIN (NORMALLY CLOSED) SYSTEM WATER SUPPLY PRESSURE GAUGE ALARM TEST (NORMALLY CLOSED) NIPPLE B SYSTEM MAIN DRAIN CONNECTION (SIZED PER TABLE) SYSTEM MAIN DRAIN (NORMALLY CLOSED) C Nipple Number Main Drain Size -/" (DN0) /" x Close /" x Close /" x " /" x -/" Select Appropriate Nipple Sizes per DV- Deluge Valve Size " (DN0) /" x " /" x Close /" x -/" /" x -/" " (DN80) /" x -/" /" x -/" /" x " /" x -/" " (DN00) /" x -/" /" x " /" x -/" /" x -/" " (DN0) /" x -/" /" x " /" x -/" /" x -/" /" NPT /" NPT -/" NPT " NPT " NPT 8" (DN00) /" x 8-/" /" x -/" /" x 9" /" x -/" System Main Drain /" NPT /" NPT -/" NPT " NPT " NPT " NPT Size VENT FITTING (GREEN TINT) AUTOMATIC DRAIN E MAIN DRAIN CONNECTION (SIZED PER TABLE) SYSTEM AIR SUPPLY CONTROL (NORMALLY OPEN) DRIP FUNNEL WITH -/ IN NPT CONNECTION TO DRAIN PLUG UNUSED PORTS A F " (DN00) FLANGE x GROOVE DV- DELUGE SHOWN QUICK RELEASE SWIT / IN NPT CONNECTION FOR SYSTEM AIR SUPPLY SYSTEM AIR SUPPLY PRESSURE GAUGE RISER ECK (NOTE ) AUTOMATIC SHUT-OFF (NORMALLY OPEN) RELEASING PANEL WITH BATTERY BACK-UP (NORMALLY CLOSED) DIAPHRAGM AMBER SUPPLY CONTROL (NORMALLY / IN NPT OPEN) CONNECTION FROM WATER SUPPLY D NIPPLE NIPPLE FIGURE B -/ THRU 8 IN (DN0 THRU DN00) DV- DELUGE S DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/ELECTRIC ACTUATION TRIM WITH MODEL QRS ELECTRONIC ACCELERATOR OPERATIONAL COMPONENTS MANUAL CONTROL STATION " NPT DIAPHRAGM AMBER PRESSURE GAUGE

10 TFP00 Page 0 of -/ & IN (DN & DN80) S -/" (8, mm) 9-/" (90, mm) IN (DN00) -/8" (,9 mm) 0" (08,0 mm) IN (DN0) -/" (8, mm) -/" (, mm) FIGURE MODEL DPV- DRY PIPE INSTALLATION DIMENSIONS, PRE-TRIMMED

11 TFP00 Page of JUMPER JUMPER LAST JUMPER TAMPER ALARM HIGH/ VDC QRS TAMPER ALARM HIGH/ VDC LOW LOW EOLR AIR EOLR SWIT AIR JUMPER GREEN VIOLET BLUE BROWN ORANGE YELLOW TYPICAL WIRING FOR QRS, OR (ALL BUT LAST) FIRST, SECOND OR THIRD QRS SWIT GREEN VIOLET BLUE WIRING FOR LAST QRS ONLY BROWN EOLR. K EOLR LOCATE AT LAST QRS ORANGE YELLOW NOT USED ON LAST QRS IF OPTIONAL SHIELDED CABLE IS USED DO NOT CONNECT SHIELD OPTIONAL BUT NOT REQUI: ALPHA WIRE TYPE 98C OR EQUIVALENT IF OPTIONAL SHIELDED CABLE IS USED DO NOT CONNECT SHIELD OPTIONAL BUT NOT REQUI: ALPHA WIRE TYPE 98C OR EQUIVALENT SYSTEM SYSTEM SYSTEM SYSTEM SHIELD SHIELD SHIELD SHIELD GREEN VIOLET ORANGE YELLOW BLUE BROWN GREEN VIOLET ORANGE YELLOW BLUE BROWN GREEN VIOLET ORANGE YELLOW BLUE BROWN GREEN VIOLET ORANGE YELLOW BLUE BROWN NOT USED ON LAST QRS VNR DC AUX. POWER VR DC ABORT SUP + SUP - SUPERVISORY ZONE ZONE ZONE ZONE GND. OUTPUT OUTPUT OUTPUT OUTPUT PFC-0RC PANEL REFERENCE WIRING DIAGRAM PROGRAM #.K RELEASING S S S S END OF LINE DIODE ASS'Y PART #000 INSTALL AT.K RELEASING END OF LINE DIODE ASS'Y PART #000 INSTALL AT RELEASING SYSTEM SYSTEM SYSTEM SYSTEM.K END OF LINE DIODE ASS'Y PART #000 INSTALL AT FIGURE WIRING DIAGRAM FOR THE MODEL QRS ELECTRONIC ACCELERATOR FOR DRY PIPE (S).K RELEASING END OF LINE DIODE ASS'Y PART #000 INSTALL AT

12 TFP00 Page of JUMPER JUMPER TAMPER ALARM HIGH/ LOW EOLR AIR VDC 8 9 QRS SWIT GREEN VIOLET BLUE BROWN EOLR. K EOLR LOCATE AT QRS ORANGE YELLOW NOT USED IF OPTIONAL SHIELDED CABLE IS USED DO NOT CONNECT SHIELD OPTIONAL BUT NOT REQUI: ALPHA WIRE TYPE 98C OR EQUIVALENT SYSTEM DETECTION SEE POTTER MANUAL #0 SHIELD GREEN VIOLET ORANGE YELLOW BLUE BROWN NOT USED SEE POTTER MANUAL #0 VNR DC AUX. POWER VR DC ABORT SUP + SUP - SUPERVISORY ZONE ZONE ZONE ZONE GND. OUTPUT OUTPUT OUTPUT OUTPUT PFC-0RC PANEL REFERENCE WIRING DIAGRAM PROGRAM # SEE POTTER MANUAL #0.K S SYSTEM RELEASING END OF LINE DIODE ASS'Y PART #000 INSTALL AT FIGURE WIRING DIAGRAM FOR THE MODEL QRS ELECTRONIC ACCELERATOR FOR DOUBLE INTERLOCK ELECTRIC/ELECTRIC PREACTION SYSTEMS SEE POTTER MANUAL #0

13 TFP00 Page of Setting Procedure (Dry Pipe System) The Dry Pipe System and the TYCO Model QRS Electronic Accelerator must be reset and restored to service as soon as possible after an operation. NOTICE The system must be completely drained before proceeding. In the case of one panel serving multiple risers, whenever the Program Switch is set to the PROGRAM position (Steps and ), the QRS Electronic Accelerators are taken out of service for all connected system risers. Therefore, the proper authorities and all personnel who may be affected must be notified. In the event of a fire and where a QRS Electronic Accelerator has been taken out of service, an increased time in water delivery can be expected. Step. If desired and until the system is to be set for service, the internal audible buzzer may be silenced by momentarily pressing the Buzzer Silence button (Figure ). Step. Locate all of the system s low point drain valves to help facilitate resetting of the system. Step. Follow the resetting procedure for the Dry Pipe Valve using the instructions provided in the technical data sheet for the Dry Pipe Valve. When the procedure calls for the system piping to be pressurized with air, proceed with Step. Step. Momentarily press the System Reset button (Figure ) and then set the Program Switch to the PROGRAM position. The display will read OK to charge system. Begin applying air pressure to the system. At this point the solenoid valve will be de-ener gized and allowed to close to enable pressurization of the system piping, and a 0 minute countdown to repres surize the system will be displayed. NOTICE If within 0 minutes, the Program Switch is not returned to the RUN position during the upcoming Step, the Releasing Panel will automatically re vert to a normal condition. If at least 8 psi has not been reached, the solenoid valve will be energized and open. If at least the low air pressure threshold of Table A has not been reached, a supervisory condition will occur. If more than 0 minutes is required, the counter can be restarted before the 0 minutes has elapsed. In order to reset the counter, the system must be pressurized to at least 8 psi, at which time the Program Switch can be set to the RUN position and then quickly back to the PROGRAM position. A 0 minute countdown will then be restarted. Step. When the system reaches an air pressure of approximately 0 psi and while the system is in process of reaching its intended pressure, blowdown each drain valve one at a time (including the low body drain or priming level valve) at the dry pipe valve and the Inspector s Test Connection by opening each drain valve until water ceases to drain and then closing the drain valve. The blow-down procedure that will assure complete draining of the system will be more easily ac complished with 0 psi air pressure in the system. Step. When the system reaches the intended pressure and the pressure is stabilized, return the Program Switch (Figure ) to the RUN position. Step. After waiting at least 0 seconds, open the Inspector s Test Connection, wait seconds, and then close the Inspector s Test Connection. Verify that the time to Accelerator trip is essentially the same as in previous tests. A momentary burst of air from a dry pipe valve s Automatic Drain Valve indicates that the QRS has tripped. In addition, the Display on the Operating Interface of the Releasing Panel will indicate operation. This procedure will also allow any scale and debris to be cleared from the pipe and nipples that are connected to the solenoid valve. Momentarily press the System Reset button and then set the Program Switch to the PROGRAM position. The display will read OK to charge system. At this point, once again, the solenoid valve will be de-energized and allowed to close to enable pressurization of the system piping. Allow the system to automatically return to its intended pressure via its automatic air supply, and, after waiting for the pressure to stabilize, return the Program Switch to the RUN position. Step 8. Partially open the Main Control Valve. Slowly close the system s Main Drain Valve as soon as water discharges from the drain connection. Depress the plunger on the dry pipe valve s Automatic Drain Valve to make sure that it is open and that no water discharges. The absence of water discharge from the Automatic Drain Valve is an indication of a properly set water seat within the dry pipe valve. If water is discharging, refer to the Care and Maintenance section within the Technical Data Sheet for the dry pipe valve to determine/correct the cause of the leakage problem. If there are no leaks, the system s Main Control Valve must be fully opened. The system is now set for service. NOTE: After setting a fire protection system, notify the proper authorities and advise those responsible for monitoring proprietary and/or central station alarms. Setting Procedure (Preaction System) The Double Interlock Electric/Electric Preaction System and the Model QRS Electronic Accelerator must be reset and restored to service as soon as possible after an operation. Follow the Valve Setting Procedure instructions provided in the Technical Data Sheet TFP. When Step 0 calls for resetting the actuation system, momentarily press the System Reset button (Figure ), and assuming that the Zone Alarm and Zone Low Air Alarm clear, proceed with the remaining instructions provided in TFP. NOTE: After setting a fire protection system, notify the proper authorities and advise those responsible for monitoring proprietary and/or central station alarms. Care and Maintenance The following procedures and inspections should be performed as indicated, in addition to any specific requirements of the NFPA, and any impairment must be immediately corrected. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (e.g., NFPA ), in addition to the standards of any authority having jurisdiction. Contact the installing contractor or product manufacturer with any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service.

14 TFP00 Page of OUTPUT LED STEADY: ABORT ZONE OUTPUT ZONE OUTPUT ZONE OUTPUT ZONE OUTPUT PROGRAM MODE RUN MODE RUN PROGRAM AC POWER POWER TBL SYSTEM TBL SUP TBL GROUND FAULT SUP /ABORT SUPERVISORY COMMON ALARM ALARM SILENCE STEADY: DISARGED FLASHING: PRE- DISARGE SET SCROLL-UP BUZZER SILENCE LAMP TEST SCROLL-DOWN BUZZER SILENCE SELECT SIGNAL SILENCE FUNCTION SYSTEM RESET VIEWING ANGLE FIGURE OPERATING INTERFACE FOR THE MODEL PFC-0RC RELEASING PANEL The Model QRS Electronic Accelerator must be maintained and serviced in accordance with this section. NOTICE The QRS uses electronic components to monitor the system air pressure. Keep all radio transmitters or RF sources at least one foot from the QRS. Failure to do so could result in an unintended operation of the dry pipe or preaction system. Before closing a fire protection system main control valve for inspection or maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. If an Accelerator is to be temporarily taken out of service, the proper authorities and all personnel who may be affected must be notified. Model QRS Electronic Accelerator Testing Procedure It is recommended that the following Accelerator test procedure be performed quarterly. Step. When operation of the dry pipe/ preaction valve is not intended during the Accelerator trip test, close the system s Main Control Valve and open the system s Main Drain Valve to relieve the supply pressure to the dry pipe/ preaction valve. Otherwise proceed as follows. Step. For a dry pipe system, open the Inspector s Test Connection. Verify that the time to Accelerator trip is essentially the same as in previous tests. A momentary burst of air from a dry pipe valve s Automatic Drain Valve indicates that the Accelerator has tripped. In addition, the Display on the Operating Interface of the Releasing Panel will indicate operation. For a double interlock electric/electric preaction system, first operate the detection system and then open the Inspector s Test Connection. Verify that the time to Accelerator trip is essentially the same as in previous tests. Release of the DV- diaphragm pressure though the open solenoid valve indicates that the Accelerator has tripped. In addition, the Display on the Operating Interface on the Releasing Panel will indicate operation. Step. Reset the Model QRS Electronic Accelerator in accordance with the appropriate Setting Procedure Section. Releasing Panel and Batteries Inspect, test, and maintain per the instructions provided for the Model PFC-0RC Releasing Panel.

15 TFP00 Page of NOTES:.. Installation notes are typical of all Dry Pipe Valve models shown. Some items provided with the Model QRS Trim (P/N ---00) are not used for the purposes of retrofit and may be discarded. Field fabrication of additional materials will be required to facilitate connection to the existing system riser accelerator connection. NO DESCRIPTION QTY P/N Quick Release Switch, Model QRS Solenoid Valve /" Union /" Tee /" x Close Nipple..... : Common Hardware FLOW FIELD FABRICATE TO SUIT FROM /" NPS PIPE AND FITTINGS /" NPT ACCELERATOR TRIM CONNECTION TO INTERMEDIATE RIGHT SIDE VIEW RIGHT SIDE VIEW AMBER LEFT SIDE VIEW Refer to Data Sheets: Refer to Data Sheets: Refer to Data Sheet: Central Inch Model AF, 0-. (-9), Star Model A Gem & Inch and & Inch Model AF/AG, -..0 (-9) Inch Model F0/F (-9) or 0-.0 (-9), -..0 (-9) Inch TD0 (-9) Star Model A- -.. (-00) Inch -.. (-00) Inch FLOW /" NPT SYSTEM RISER ACCELERATOR CONNECTION FIGURE 8 MODEL QRS ELECTRONIC ACCELERATOR RISER COMPONENTS INSTALLATION DIAGRAM WITH DRY PIPE S MANUFACTU BY TYCO OTHER THAN THE MODEL DPV- DRY PIPE FLOW

16 TFP00 Page of Limited Warranty For warranty terms and conditions, visit Ordering Procedure Dry Pipe Valve Electronic Accelerator Package with AH Battery Backup Required components for one dry pipe valve riser Includes the following (ref. Fig. ): Model QRS Electronic Accelerator Trim, P/N Model PFC-0RC Releasing Panel, P/N 0. Model BT-0 AH Battery, P/N 08 (Qty. of provided) Specify: Model QRS Electronic Accelerator Package, AH Battery Backup, P/N ---0 Dry Pipe Valve Electronic Accelerator Package with 8AH Battery Backup Required components for one dry pipe valve riser Includes the following (ref. Fig. ): Model QRS Electronic Accelerator Trim, P/N Model PFC-0RC Releasing Panel, P/N 0 Model BT-80 8AH Battery, P/N 0, (Qty of provided) Specify: Model QRS Electronic Accelerator Package, 8AH Battery Backup, P/N ---0 Dry Pipe Valve Electronic Accelerator Trim One each required for each additional dry pipe riser up to three additional dry pipe risers Specify: Model QRS Electronic Accelerator Trim, P/N Replacement Trim Parts (Specify description) for use with Model QRS Electronic Accelerator Dry Pipe Valve, P/N (specify, ref. Fig. ) DV- Deluge Valve Double Interlock Preaction with Electric/Electric Activation Trim with Model QRS Quick Release Switch Refer to Technical Data Sheet TFP for additional details. Includes the following (ref. Fig. A): Model QRS Quick Release Switch Model PFC-0RC Releasing Panel, P/N 0. Model BT-0 AH Battery, P/N 08 (Qty. of provided) Specify: (specify size), Galvanized, Semi-Preassembled Double Interlock Preaction System with Electric/Electric Actuation Trim and Model QRS Electronic Accelerator for DV- Deluge Valves, P/N (specify): -/ in. & in. Galvanized...P/N -8--8Q in. Galvanized...P/N -8--Q in., in.& 8 in. Galvanized...P/N -8--Q DV- Deluge Valve Pre-Trimmed Double Interlock Electric/Electric Actuation Assembly with Butterfly Valve and Model QRS Switch NOTE: Does not include Potter PFC- 0RC Panel and BT0 batteries. Specify: (specify size), G x G End Connection, Pre-Trimmed DV- Assembly with Butterfly Valve, and Model QRS Quick Release Switch, P/N (specify): -/ in. G x G...P/N APQ in. G x G...P/N APQ in. P G x G... P/N APQ in. G x G... P/N APQ in. G x G... P/N APQ 8 in. G x G... P/N APQ DV- Deluge Valve Pre-Trimmed Double Interlock Electric/Electric Actuation Assembly with Model QRS Switch NOTE: Does not include Potter PFC- 0RC Panel and BT0 batteries. Specify: (specify size), F x G End Connection, Pre-Trimmed DV- Assembly and Model QRS Quick Release Switch, P/N (specify): in. F x G...P/N -98--APQ in. F x G...P/N -98--APQ in. F x G...P/N -98--APQ 8 in. F x G...P/N APQ Replacement Trim Parts (Specify description) for use with Model QRS, DV- Electric/Electric Preaction, P/N (specify, ref. Fig. A) 00 Pennbrook Parkway, Lansdale, PA 9 Telephone Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description Worldwide Contacts www.tycofire.com DV Deluge Valve, Diaphragm Style, / thru Inch (DN0 thru DN00), Deluge System Wet Pilot Actuation General Description The DV Deluge Valve (described in Technical Data

More information

Preaction System with DV-5 Deluge Valve Double Interlock Electric/Electric Actuation. General Description. Page 1 of 14 DECEMBER 2014 TFP1465

Preaction System with DV-5 Deluge Valve Double Interlock Electric/Electric Actuation. General Description. Page 1 of 14 DECEMBER 2014 TFP1465 Worldwide Contacts www.tycofire.com Preaction System with DV5 Deluge Valve Double Interlock Electric/Electric Actuation General Description The TYCO DV5 Double Interlock Preaction System with Electric/Electric

More information

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation Deluge Valve DV-5 Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation GeneralDescription The Model DV-5 Deluge Valve (described in Technical

More information

Model CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data

Model CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data Worldwide Contacts www.tyco-fire.com Model CV-FR Grooved-End Riser Check Valves Inch to Inch (DN0 to DN00) General Description The TYCO Model CV-FR Grooved- End Riser Check Valve is a compact and rugged

More information

DV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description Worldwide Contacts www.tyco-fire.com DV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to Inch (DN40 to DN200) General Description The TYCO DV-5A Automatic

More information

DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description Worldwide Contacts www.tyco-fire.com DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/ Inch to Inch (DN40 to DN00) General Description The TYCO DV-5a Automatic

More information

DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description Worldwide Contacts www.tyco-fire.com DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to Inch (DN40 to DN200) General Description The TYCO DV-5a Automatic

More information

1-1/2 Inch (DN40) 9 lb (4,1 kg) Groove Groove 1 8 lb (3,6 kg) Flange Groove 1 N/A N/A. Flange Flange N/A N/A

1-1/2 Inch (DN40) 9 lb (4,1 kg) Groove Groove 1 8 lb (3,6 kg) Flange Groove 1 N/A N/A. Flange Flange N/A N/A Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Diaphragm Style General Description The TYCO 1-1/2 inch to inch (DN40 to DN200), DV-5 Deluge Valves are diaphragm type valves designed for vertical

More information

Worldwide Contacts.

Worldwide Contacts. Worldwide Contacts www.tyco-fire.com DV-5 Remote-Resetting, Pressure-Reducing Deluge Valve, Limited Space Valve Cabinet General Description The TYCO DV-5 Remote-Resetting, Pressure-Reducing Deluge Valve,

More information

Model RM-1 Riser Manifold Commercial and Residential General Description

Model RM-1 Riser Manifold Commercial and Residential General Description Worldwide Contacts www.tyco-fire.com Model RM- Riser Manifold Commercial and Residential General Description The TYCO commercial and residential Model RM- Riser Manifold provide the necessary waterflow

More information

Technical Data. UL Listing is based on the following criteria:

Technical Data. UL Listing is based on the following criteria: Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve with Trim Inch and 6 Inch (DN1 and DN15) General Description The TYCO DV-5 Deluge Valve with Trim is a diaphragm-style valve that depends upon water

More information

DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description

DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description The TYCO Aluminum Bronze DV-5 Deluge Valves are available to provide an alternative material

More information

with the specific application. Always read and understand the installation

with the specific application. Always read and understand the installation Worldwide Contacts www.tyco-fire.com Resilient-Seated Gate Valves Outside Screw and Yoke General Description TYCO Resilient-Seated Gate Valves are used in Fire Protection Systems for on/off operation.

More information

MODEL RCW NON-INTERLOCK PREACTION SYSTEM

MODEL RCW NON-INTERLOCK PREACTION SYSTEM GENERAL DESCRIPTION The Globe Model RCW non-interlock preaction valve is a hydraulically operated external resetting differential latching style valve designed for use where quickopening and total flooding

More information

TECHNICAL DATA 1-1/2 (dn40)

TECHNICAL DATA 1-1/2 (dn40) July 1, 2011 Deluge Valves 209a DESCRIPTION The Viking Model E-3 1-1/2 Deluge Valve is a quick-opening, differential type flood valve with a rolling diaphragm clapper. The deluge valve is used to control

More information

TECHNICAL DATA. Q= C v P Cv = Flow Factor (GPM/1 PSI P)

TECHNICAL DATA. Q= C v P Cv = Flow Factor (GPM/1 PSI P) 1 of 9 1. DESCRIPTION The Viking 2 (DN50) is a quick-opening, differential diaphragm, flood valve with one moving part. The deluge valve is used to control water flow in deluge and preaction sprinkler

More information

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet)

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet) Flow Control 500a DESCRIPTION The Viking 1-1/2 is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The can be used to facilitate manual or automatic on/off

More information

TECHNICAL DATA. Q= C v P S

TECHNICAL DATA. Q= C v P S 1 of 9 1. DESCRIPTION The Viking Model E-1 Deluge Valve is a quick-opening, differential diaphragm, flood valve with one moving part. The deluge valve is used to control water flow in deluge and preaction

More information

Q= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications

Q= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications 1 of 9 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can be used to facilitate manual

More information

MODEL RCW DELUGE SYSTEM ELECTRIC, WET PILOT, AND DRY PILOT ACTUATION

MODEL RCW DELUGE SYSTEM ELECTRIC, WET PILOT, AND DRY PILOT ACTUATION 0 Airpark Dr. Standish, MI 868 989-86-8 www.globesprinkler.com Technical Support 989--00 techservice@globesprinkler.com MODEL RCW DELUGE SYSTEM ELECTRIC, WET PILOT, AND DRY PILOT ACTUATION GENERAL DESCRIPTION

More information

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE 6 (DN150)

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE 6 (DN150) January 13, 2006 Deluge Valves 211 a 1. PRODUCT NAME Viking Model E-1 Deluge Valve 3 (DN80) Available since 1985 4 (DN100) Available since 1985 6 (DN150) Available since 1984 2. MANUFACTURER THE VIKING

More information

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim Actuated Valve with LPCB Approved Preaction Trim 104g/01 with: - Electric Activation with Redundant Solenoid Valve - Electric Activation with Redundant Solenoid Valve and AutoConvert Dry Trim - Double

More information

Technical Data. Sizes 2 12 Inch (DN50 DN300)

Technical Data. Sizes 2 12 Inch (DN50 DN300) Worldwide Contacts www.tyco-fire.com Model BFV-/BFV-C Butterfly Valve Grooved End General Description The TYCO Models BFV- and BFV- C Grooved End Butterfly Valves are indicating type valves designed for

More information

Worldwide Contacts. Technical Data

Worldwide Contacts.  Technical Data Worldwide Contacts www.tyco-fire.com Model BFV-/BFV-C Butterfly Valve Grooved End General Description The TYCO Models BFV- and BFV- C Grooved End Butterfly Valves are indicating type valves designed for

More information

Type D3S PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP804

Type D3S PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP804 Worldwide Contacts www.tyco-fire.com Type D3S PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description The Type D3S Protectospray Nozzles are open (non-automatic) directional

More information

TECHNICAL DATA. Trimpac 249a. September 16, 2013

TECHNICAL DATA. Trimpac 249a. September 16, 2013 September 16, 2013 Trimpac 249a 1. DESCrIpTION DESCRIPTION TRIMPAC Model B-4, B-4B & B-4S is a factory assembled trim package for a single interlocked with a pneumatic release module in a metal enclosure.

More information

Technical Data. Sizes 2 in. to 24 in. (DN50 to DN600) Approvals UL and ULC Listed FM Approved

Technical Data. Sizes 2 in. to 24 in. (DN50 to DN600) Approvals UL and ULC Listed FM Approved Worldwide Contacts www.tyco-fire.com Model TJP Resilient-Seated Gate Valves with Vertical or Cross Wall Post Indicator General Description TYCO Model TJP Resilient-Seated Gate Valves with Vertical and

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Model H Deluge Riser Assembly Bulletin 507 Rev. D Bulletin 507 Rev. D Instructions for Installation, Operation, Care and Maintenance 1 1 / 2 (40mm) Size Electric Actuation The Reliable Automatic Sprinkler

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Bulletin 407 Rev. T Model E Alarm Check Valve Bulletin 407 Rev. T Instructions for Installation, Operation, Care and Maintenance 4 (100 mm), 6 (150 mm), 8 (200 mm) Sizes With Model E3 Trim Listed by Underwriters

More information

TECHNICAL DATA CONCENTRATE CONTROL VALVE APPLICATIONS, PRIMING CONNECTIONS, AND TRIMS 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS.

TECHNICAL DATA CONCENTRATE CONTROL VALVE APPLICATIONS, PRIMING CONNECTIONS, AND TRIMS 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS. Page 1 of Telephone: 29-95-9501 Technical Services: 877-38-5 Fax: 29-818-180 Email: techsvcs@vikingcorp.com 1. GENERAL DESCRIPTION The Halar Coated Concentrate Control (CCV) is utilized in Viking foam

More information

TECHNICAL DATA. Trimpac 244a. April 15, 2011

TECHNICAL DATA. Trimpac 244a. April 15, 2011 April 15, 2011 Trimpac 244a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-1 and B-1B is a factory-assembled trim package with an electric release module in a metal enclosure. The standard trim normally required

More information

Directional Spray Nozzles, Open, with Strainers High Velocity General Description

Directional Spray Nozzles, Open, with Strainers High Velocity General Description Worldwide Contacts www.tyco-fire.com Model FS Through F3S Mulsifyre Directional Spray Nozzles, Open, with Strainers High Velocity General Description The Model FS through F3S Mulsifyre Nozzles are open

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Bulletin 59 Model DDX Deluge Valve (50 mm), ½ (65 mm), (80 mm), 76 mm, 4 (00 mm), 6 (50 mm), 65 mm & 8 (00 mm) Bulletin 59 Instructions for Installation, Operation, Care and Maintenance Wet Pilot Line,

More information

TECHNICAL DATA TRIMPAC MODEL B-4, B-4B & B-4S SINGLE INTERLOCK PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA TRIMPAC MODEL B-4, B-4B & B-4S SINGLE INTERLOCK PREACTION SYSTEM WITH PNEUMATIC RELEASE Page 1 of 20 1. DESCRIPTION TRIMPAC Model B-4, B-4B & B-4S is a factory assembled trim package for a single interlocked preaction system with a pneumatic release module in a metal enclosure. The standard

More information

DELUGE VALVE DATA SHEET

DELUGE VALVE DATA SHEET FIRE FIGHTING EQUIPMENT DATA SHEET DELUGE VALVE DATA SHEET JOB NO. : RFQ. NO. : ISSUE : SHEET OF 01 CUSTOMER : ITEM NO. : 02 PROJECT : QUANTITY : 03 LOCATION : SERVICE : FIRE WATER AND / OR FOAM SYSTEM

More information

TotalPac 3 Deluge, Electric release Remote controlled system

TotalPac 3 Deluge, Electric release Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a deluge system trim totally preassembled, pre-wired and factory tested. All electrical and

More information

TotalPac 3 Deluge system Pneumatic release

TotalPac 3 Deluge system Pneumatic release (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a deluge system trim totally preassembled, pre-wired and factory tested. All electrical and

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Model H Deluge Riser Assembly Bulletin 507 Rev.C Bulletin 507 Rev.C Instructions for Installation, Operation, Care and Maintenance 1 1 2 (40mm) Size Electric Actuation The Reliable Automatic Sprinkler

More information

Instructions for Installation, Operation, Care, and Maintenance

Instructions for Installation, Operation, Care, and Maintenance Bulletin 750 Rev. B Model DDX Double Interlock Preaction System Type D 2 (50 mm), 2½ (65 mm), 3 (80 mm), 76 mm, 4 (00 mm), 6 (50 mm), 65 mm & 8 (200 mm) Bulletin 750 Rev. B Instructions for Installation,

More information

DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : VALVE OPERATION TRIM DESCRIPTION DESCRIPTION PRESSURE THREADED OPENING

DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : VALVE OPERATION TRIM DESCRIPTION DESCRIPTION PRESSURE THREADED OPENING DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : NOMINAL SIZE MATERIAL MAXIMUM SERVICE PRESSURE 200, 150, 100, 80 & 50NB Cast Iron 12 Bar (175 PSI) THREADED OPENING MOUNTING FACTORY HYDROSTATIC TEST PRESSURE

More information

Wet pipe low flow foam/water manifold system

Wet pipe low flow foam/water manifold system December 6, 2010 Foam 15a 1. Description With the Wet Pipe Low Flow Foam/Water Manifold System, multiple risers can be supplied from a single proportioning device. A riser manifold is installed with various

More information

TotalPac 3 Firecyle III Wet pipe Remote controlled system

TotalPac 3 Firecyle III Wet pipe Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a Firecycle III system trim totally preassembled, pre-wired and factory tested. All electrical

More information

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Remote controlled system

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

TECHNICAL DATA CAUTION

TECHNICAL DATA CAUTION Page 1 of 6 1. DESCRIPTION The Viking Model D-2 Accelerator is a quick-opening device, with an integral anti-flood assembly, used to increase the operating speed of a differential type dry pipe valve.

More information

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL J-2 HALAR COATED 1-1/2 & 2 (DN40 & DN50) 1. DESCRIPTION

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL J-2 HALAR COATED 1-1/2 & 2 (DN40 & DN50) 1. DESCRIPTION Page 1 of 9 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can be used to facilitate manual

More information

TotalPac 3 Double interlock Preaction, Electric/Pneumatic release Remote controlled system

TotalPac 3 Double interlock Preaction, Electric/Pneumatic release Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description

Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description Worldwide Contacts www.tyco-fire.com Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description IMPORTANT Always refer to Technical Data Sheet TFP700 for the INSTALLER

More information

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4 Page 1 of 5 Model F Dry Valve with Trim Valve Size Part Number 3 13764PTR 4 13765PTR 6 13766PTR Standard Trim Sets include galvanized nipples and fittings. 4 Dry Valve Shown General Notes: Notes: For use

More information

TotalPac 3 Non interlock Preaction system Pneumatic release

TotalPac 3 Non interlock Preaction system Pneumatic release (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

TotalPac 3 Non interlock Preaction, Electric release Remote controlled system

TotalPac 3 Non interlock Preaction, Electric release Remote controlled system (Optional) Description This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

Q= C v P S. Flow control valve Model j-2 Halar coated

Q= C v P S. Flow control valve Model j-2 Halar coated October 22, 2010 Flow Control 507a 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can

More information

MODEL UM UNIVERSAL MANIFOLD ASSEMBLY (With or Without Control Valve) 1¼", 1½", 2", 2½", 76.1mm, 3", 4", 6",165.1mm, 8"

MODEL UM UNIVERSAL MANIFOLD ASSEMBLY (With or Without Control Valve) 1¼, 1½, 2, 2½, 76.1mm, 3, 4, 6,165.1mm, 8 4077 Airpark Dr. Standish, MI 48658 989-846-4583 www.globesprinkler.com Technical Support 989-414-2600 techservice@globesprinkler.com MODEL UM UNIVERSAL MANIFOLD ASSEMBLY (With or Without Control Valve)

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Model D Dry Pipe Valve Bulletin 350 Rev. S Bulletin 350 Rev. S Instructions for Installation, Operation, Care and Maintenance 4 (100mm) 6 (150mm) Valve With Model D Trimmings Listed by Underwriters Laboratories,

More information

Fire Protection Products Technical Data Book Table of Contents January 2019

Fire Protection Products Technical Data Book Table of Contents January 2019 Worldwide Contacts www.tyco-fire.com Fire Protection Products Technical Data Book Table of Contents January 2019 SECTION 1 - STANDARD SPRAY SPRINKLERS DATE SHEET Series TY-L Pendent, Recessed Pendent,

More information

FireLock NXT Deluge Valve. With Deluge Trim Grooved x Grooved. System No. Submitted By Spec Sect Para Location Date Approved Date

FireLock NXT Deluge Valve. With Deluge Trim Grooved x Grooved. System No. Submitted By Spec Sect Para Location Date Approved Date MEA: 248-98-E CSFM: 7770-0531-117 The patent-pending Victaulic Series 769 FireLock NXT controls the water supply entry into the deluge system piping and open sprinklers. The Series 769 is a low differential,

More information

Instructions for Installation, Operation Care and Maintenance

Instructions for Installation, Operation Care and Maintenance Model A Dry Pipe Valve Bulletin 353 Rev.K Bulletin 353 Rev.K Instructions for Installation, Operation Care and Maintenance 2 1 2 (65mm) Valve With Model A Trim Listed by Underwriters Laboratories, Inc.

More information

TECHNICAL DATA 2-1/2-8 (dn65 - dn200)

TECHNICAL DATA 2-1/2-8 (dn65 - dn200) 1 of 13 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can be used to facilitate manual

More information

Fire Protection Products Technical Data Book Table of Contents June 2018

Fire Protection Products Technical Data Book Table of Contents June 2018 Worldwide Contacts www.tyco-fire.com Fire Protection Products Technical Data Book Table of Contents June 2018 SECTION 1 - STANDARD SPRAY SPRINKLERS DATE SHEET Series TY-L Pendent, Recessed Pendent, and

More information

TotalPac 3 Double interlock Firecyle III Preaction Remote controlled system

TotalPac 3 Double interlock Firecyle III Preaction Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a Firecycle III system trim totally preassembled, pre-wired and factory tested. All electrical

More information

CJ=TN=- FRONT DELUGE VALVE, EXTERNAL RESETTING. MODEL F470 MULTIMATIW - 4 and 6 INCH (100 and 150 mm) a P il

CJ=TN=- FRONT DELUGE VALVE, EXTERNAL RESETTING. MODEL F470 MULTIMATIW - 4 and 6 INCH (100 and 150 mm) a P il DELUGE VALVE, EXTERNAL RESETTING MODEL F470 MULTIMATIW - 4 and 6 INCH (100 and 150 mm) The 4 and 6 inch (100 and 150 mm), Model F470 External Resetting Multimatic Deluge Valves are differential latch type

More information

Section O Preaction Systems

Section O Preaction Systems Section O TABLE OF CONTENTS Model G. O-1 Single Interlocked Pneumatic Release...O-2 O-3 Single Interlocked Electric Release...O-4 O-5 Double Interlocked Pneumatic/Pneumatic Release...O-6 O-7 Double Interlocked

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Bulletin 727 Rev. G Single Interlock Preaction System 4 (00mm), 6 (50mm) & 65mm Sizes Bulletin 727 Rev. G Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,4 bar) Pneumatic Supervising

More information

AGCX Bulletin 519 C/Alfoz de Bricia nº4 P.l. Villalonquéjar Burgos (Spain) Tlfno: PAG 1 de 50

AGCX Bulletin 519 C/Alfoz de Bricia nº4 P.l. Villalonquéjar Burgos (Spain) Tlfno: PAG 1 de 50 Instructions for Installation, Operation, Care and Maintenance Model AGCX Deluge Valve (50 mm), ½ (65 mm), 3 (80 mm), 4 (00 mm), 6 (50 mm), 8 (00 mm) Wet Pilot Line, Dry Pilot Line, and Electric Actuation

More information

FireFlex DUAL Single Interlock, Remote controlled system

FireFlex DUAL Single Interlock, Remote controlled system FireFlex DUAL description The FireFlex DUAL integrated system consists of an integrated single interlock Electric release preaction automatic sprinkler system combined with a clean agent fire extinguishing

More information

Series 769 FireLock NXT Deluge Valve

Series 769 FireLock NXT Deluge Valve IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS Series 79 FireLock NXT Deluge Valve With Deluge Trim Grooved X Grooved 30.81 VICTAULIC IS AN ISO 9001 CERTIFIED COMPANY PRODUCT DESCRIPTION The patent-pending

More information

Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,14 bar) Pneumatic Supervising Pressure with Electric Actuation

Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,14 bar) Pneumatic Supervising Pressure with Electric Actuation Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,14 bar) Pneumatic Supervising Pressure with Electric Actuation Single Interlock Electric Release Preaction System 8 (200 mm) Size

More information

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description Technical Services: Tel: () 31-931 / Fax: () 791-55 Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and

More information

TECHNICAL DATA. Q= C v P S. Table 1 - Valve Part Numbers and Specifications

TECHNICAL DATA. Q= C v P S. Table 1 - Valve Part Numbers and Specifications June 24, 2011 Flow Control 504a 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The Flow Control Valve can

More information

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL H-2 HALAR COATED 2 (DN50) - 6 (DN150)

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL H-2 HALAR COATED 2 (DN50) - 6 (DN150) 1 of 12 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The Flow Control Valve can be used to facilitate manual

More information

Series 758 FireLock Actuated System Valve

Series 758 FireLock Actuated System Valve R IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS Series 58 FireLock Actuated System Valve With Deluge Trim Grooved X Grooved and Flanged X Grooved 30.04 VICTAULIC IS AN ISO 9001 CERTIFIED COMPANY PRODUCT

More information

TECHNICAL DATA P S. Q= Cv MODEL E-2 DELUGE VALVE HALAR COATED ANGLE STYLE

TECHNICAL DATA P S. Q= Cv MODEL E-2 DELUGE VALVE HALAR COATED ANGLE STYLE 1 of 13 1. DESCRIPTION Viking Deluge Valves are quick opening, differential diaphragm flood valves with one moving part. The Viking Model E-2 Halar Coated Deluge Valve is identical to the Viking Model

More information

Series 756 FireLock Dry System Check Valve

Series 756 FireLock Dry System Check Valve R IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS Series FireLock Dry System Check Valve Grooved X Grooved and Flanged X Grooved 0.0 VICTAULIC IS AN ISO 900 CERTIFIED COMPANY PRODUCT DESCRIPTION The Victaulic

More information

MODELS F822 THRU F834

MODELS F822 THRU F834 MULSIFYRE@ NOZZLES MODELS F822 THRU F834 *PASSES A 4s PARTICLE 1 /(6 (27mm) ACROSS WRENCH FLATS FIGURE A MODELS F822 THRU F834 MULSIFYRE NOZZLES GENERAL DESCRIPTION The Mulsifyre Nozzles are open (nonautomatic)

More information

PCVS Series Control Valve Supervisory Switch

PCVS Series Control Valve Supervisory Switch Features NEMA 4X* (IP 65) and 6P (IP 67) *Enclosure is 4X. For additional corrosion protection of mounting hardware, use model PCVS-2 CRH -40º to 140º (-40ºC to 60ºC) operating temperature range Visual

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE August 31, 2006 Check Valve 815a 1. PRODUCT NAME Viking Easy Riser Swing Check Valve Model E-1: Available since 1992 Model F-1: Available since 1994 2. MANUFACTURER The Viking Corporation 210 N. Industrial

More information

FireLock NXT Actuated Valve with Preaction Trim. System No. Submitted By Spec Sect Para Location Date Approved Date

FireLock NXT Actuated Valve with Preaction Trim. System No. Submitted By Spec Sect Para Location Date Approved Date VNIIPO ME: 248-98-E CSFM: 7770-0531-117 The patent-pending Victaulic Series 769 FireLock NXT Preaction Valve controls the water supply entry into the Preaction system piping and sprinklers. The Preaction

More information

Typical Properties. Technical Data

Typical Properties. Technical Data Worldwide Contacts www.tyco-fire.com LFP Antifreeze Agency Listed Solution for Fire Sprinkler Systems General Description LFP antifreeze is a pre-mixed freeze protection solution designed and listed for

More information

TECHNICAL DATA. Table 1: Model F1 Dry Valve Part Numbers and Specifications

TECHNICAL DATA. Table 1: Model F1 Dry Valve Part Numbers and Specifications Page 1 of 11 1. DESCRIPTION The Viking Model F-2 Dry Pipe Valve is a latching differential valve used to separate the water supply from the dry pipe sprinkler system. The valve combines a positive latching

More information

Model DDX Deluge Valve 8 (200mm) Features

Model DDX Deluge Valve 8 (200mm) Features Model DDX Deluge Valve 8 (200mm) Bulletin 514 Bulletin 514 Features 1. Differential Latch-type, lightweight, dependable construction. 2. Easily trimmed for releasing by: Manual pull stations Wet pilot

More information

TECHNICAL DATA. model f-1 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA. Page 1 of 11

TECHNICAL DATA. model f-1 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA. Page 1 of 11 Page 1 of 11 1. DESCRIPTION The Viking Model F-1 Dry Pipe Valve is a latching differential valve used to separate the water supply from the dry pipe sprinkler system. The valve combines a positive latching

More information

Features 1. Differential Latch-type, lightweight, dependable

Features 1. Differential Latch-type, lightweight, dependable Bulletin 516 Rev. B Model DDX-SS Deluge Valve (100mm), (150mm) & (200mm) Bulletin 516 Rev. B Features 1. Differential Latch-type, lightweight, dependable construction. 2. Easily trimmed for releasing by:

More information

Model DDX Deluge Valves 4" (100 mm), 6" (150 mm) and 165 mm Sizes

Model DDX Deluge Valves 4 (100 mm), 6 (150 mm) and 165 mm Sizes Features 1. Differential-type, lightweight, dependable construction. 2. Easily trimmed for releasing by: Manual pull stations Wet pilot sprinklers Dry pilot actuators Solenoid valves 3. Drop in seat &

More information

Section L Wet Pipe Systems

Section L Wet Pipe Systems Section L TABLE OF CONTENTS Easy Riser System... L-1 Alarm Check Valve / Trim... L-2 Special Valves and Trim (Halar coated valves, brass trim, etc.)... L-3 Components and Accessories... L-4 Alarm Devices...

More information

TECHNICAL DATA OBSOLETE. Inlet Type Outlet Type in mm. Thread Thread in. ANSI B Flanged Flanged in.

TECHNICAL DATA OBSOLETE. Inlet Type Outlet Type in mm. Thread Thread in. ANSI B Flanged Flanged in. August 19, 2003 Flow Control 504 a 1. PRODUCT NAME Viking Model H-2 Halar Coated Flow Control Valve 2" (50mm), 3" (80mm), 4" (100mm), 6" (150mm) Halar Coating Manufactured 1994-2. MANUFACTURER THE VIKING

More information

Section M Dry Pipe Systems

Section M Dry Pipe Systems Section M Dry Pipe Systems TABLE OF CONTENTS Dry Pipe System (Model G)... M-1 Dry Pipe System (Model F)... M-2 Accelerators / Air Maintenance Devices... M-3 Accessories and Components... M-4 Notes 1. Refer

More information

OSYSU Series Outside Screw and Yoke Valve Supervisory Switch

OSYSU Series Outside Screw and Yoke Valve Supervisory Switch Features NEMA 4X* (IP 65) and 6P (IP 67) *Enclosure is 4X. For additional corrosion protection of mounting hardware, use model OSYSU-2 CRH -40º to 140º (-40ºC to 60ºC) operating temperature range Visual

More information

SHORTER. LIGHTER. MORE VERSATILE. 1 VALVE 10 TRIM CONFIGURATIONS 4" AND 6" MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS

SHORTER. LIGHTER. MORE VERSATILE. 1 VALVE 10 TRIM CONFIGURATIONS 4 AND 6 MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS SHORTER. LIGHTER. MORE VERSATILE. " AND 6" MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS Globe is proud to introduce the new Model RCW Water Control Valve for dry pipe, preaction

More information

Easy Riser swing check valve Models E-1 & F-1

Easy Riser swing check valve Models E-1 & F-1 Page 1 of 7 1. DESCRIPTION The Viking Easy Riser Swing Check Valve is a general purpose rubber-faced approved for use in fire service systems. The valve is for use in wet system risers, preaction system

More information

Section N Deluge Systems

Section N Deluge Systems Section N Deluge Systems TABLE OF CONTENTS Deluge System Pneumatic Release...N-1 N-2 Deluge System Hydraulic Release...N-3 N-4 Deluge System Electric Release...N-5 N-6 Components and Accessories (general)...n-7

More information

Grinnell Grooved Fire Protection Products Grooved Fittings

Grinnell Grooved Fire Protection Products Grooved Fittings Technical Services: Tel: (800) 38-932 / Fax: (800) 79-5500 www.tyco-fire.com Grinnell Grooved Fire Protection Products Grooved Fittings General Description LPCB Vd S The grooved fittings provide an economical

More information

Solenoid Operated Block Valves A2800 Series

Solenoid Operated Block Valves A2800 Series Solenoid Operated Block Valves A2800 Series Installation and Parts Liquid Controls An IDEX Fluid & Metering Business Installation: M400-40 Table of Contents Introduction Safety Procedures... 3 A2800 Series

More information

Materials. Contact Ratings. Conduit Entrances

Materials. Contact Ratings. Conduit Entrances Features NEMA 1, 3, 4, 4X, 6, 6P, 9 & 13 IP66 and 67 Water tight, dust tight and corrosion resistant for outdoor use For use in hazardous locations: Class I, Div. 1 & 2, Groups C, D Class II, Div. 1 &

More information

Section R Foam Systems

Section R Foam Systems Section R TABLE OF CONTENTS... R-1 R-3 Concentrate Control Valves and Trim... R-4 Valve Trim for Premixed... R-4 Release Trim Packages... R-4 Foam Concentrates... R-5 Accessories, Foam Concentrates...

More information

Section R Foam Systems

Section R Foam Systems Section R TABLE OF CONTENTS... R-1 R-3 Concentrate Control Valves and Trim... R-4 Valve Trim for Premixed... R-4 Release Trim Packages... R-4 Foam Concentrates... R-5 Accessories, Foam Concentrates...

More information

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 227b - d

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 227b - d April 15, 2011 Deluge Trim 227a Order Deluge Valve Separately This Trim Chart is for use with the following Viking Trim Sets Valve Size Galvanized Trim Part No. Brass Trim Part No. 3 (DN80) 14631-1 14631-2

More information

Section P Flow Control and Pressure Regulation

Section P Flow Control and Pressure Regulation Section P TABLE OF CONTENTS Flow Control System... P-1 P-2 Pressure Regulation System... P-3 Alarm Devices... P-4 Pilot Operated Pressure Control Valves / Trim... P-5 P-6 Special Valves and Trim (Halar

More information

FIRE PROTECTION EQUIPMENT 2017 DATA SHEETS BSP FIRE RESERVES THE RIGHT TO ALTER INFORMATION CONTAINED IN THIS CATALOGUE AT ANY TIME.

FIRE PROTECTION EQUIPMENT 2017 DATA SHEETS BSP FIRE RESERVES THE RIGHT TO ALTER INFORMATION CONTAINED IN THIS CATALOGUE AT ANY TIME. FIRE PROTECTION EQUIPMENT 2017 DATA SHEETS BSP FIRE RESERVES THE RIGHT TO ALTER INFORMATION CONTAINED IN THIS CATALOGUE AT ANY TIME. DATA SHEET INDEX 36m x 19mm FIRE HOSE REEL RISER INSTALLATION DETAIL

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve Technical Bulletin TB-ACV-LFF11RFP LEAD FREE * LFF11RFP Flood Protection Shut Down Valve Installed upstream of Reduced Zone Backflow Preventer. Normally Open Valve - Closes when continuous discharge from

More information

GRINNELL Model B303 Grooved End Butterfly Valves with Gear Operators or Lever-Lock Operators General Description

GRINNELL Model B303 Grooved End Butterfly Valves with Gear Operators or Lever-Lock Operators General Description Worldwide Contacts www.grinnell.com GRINNELL Model B Grooved End Butterfly Valves with Gear Operators or Lever-Lock Operators General Description The GRINNELL Model B Butterfly Valves provide for efficient

More information