Technical Data. Sizes 2 in. to 24 in. (DN50 to DN600) Approvals UL and ULC Listed FM Approved
|
|
- Violet Bennett
- 5 years ago
- Views:
Transcription
1 Worldwide Contacts Model TJP Resilient-Seated Gate Valves with Vertical or Cross Wall Post Indicator General Description TYCO Model TJP Resilient-Seated Gate Valves with Vertical and Cross Wall Indicators are used in fire protection systems for on/off operation. End connection configurations including Flange by Flange, Flange by Groove, and Groove by Groove are available. The ductile iron body weighs approximately 50% less than conventional cast iron valves, which allows easier handling on site and reduced shipping costs. The fully encapsulated EPDM ductile iron wedge ensures drop-tight sealing. Valve components are either inherently corrosion-resistant or protected with fusion-bonded epoxy resin coating for a long, reliable service life and enhanced UV protection in exposed installations. This valve is one of the lightest, most durable gate valves on the market today. Its design features and material selection criteria fulfill the need for a reliable, long life and easy to operate gate valve. These valves are available with either Vertical Indicators for underground water supplies or Cross Wall Indicators for interior water systems. Both indicators provide external visual indication of the open or shut valve condition as well as a locking mechanism to secure a particular wedge position. NOTICE Never remove any piping component nor correct or modify any piping deficiencies without first de-pressurizing and draining the system. Failure to do so may result in serious personal injury, property damage, and/or impaired device performance. It is the designer s responsibility to select products suitable for the intended service and to ensure that pressure ratings and performance data are not exceeded. Material and gasket selection should be verified for compatibility with the specific application. Always read and understand the installation instructions. TYCO Gate Valves described herein must be installed and maintained in compliance with this document, in addition to the standards of any other authorities having jurisdiction. Failure to do so may result in serious personal injury or impair the performance of these devices. The owner is responsible for maintaining their mechanical system and devices in proper operating condition. The installing contractor or device manufacturer should be contacted with any questions. Technical Data Sizes 2 in. to 2 in. (DN50 to DN600) Approvals UL and ULC Listed FM Approved UL, ULC and FM Maximum Working Pressure 2 in. to in. (DN0 to DN300): 300 psi (,7 bar) 1 in. to 2 in. (DN350 to DN600): 250 psi (17,2 bar) Flanges ASME B.1/ASME B.2 EN /ISO / Drilled to ANSI Class 150, PN, or AS 29 (Table E) Materials of Construction See individual valve and indicator parts lists, Figures 1,, and 6. IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Page 1 of JANUARY 19
2 Page 2 of FIGURE 1 POST INDICATOR GATE VALVE ASSEMBLY No. Description Qty. Material 1 Body ASTM A Wedge... 1 EPDM 3 Stem AISI SS20 Bonnet... 1 ASTM A Half-Ring ASTM C Seal Seat ASTM A Disc Nut ASTM B62 C3600 Seal Ring EPDM 9 O-Ring... 2 EPDM 10 Dust Cap EPDM 11 Hex Socket Cap Screw Rating Wench Nut... 1 ASTM A Washer... 1 ASTM SS30 1 Hex Socket Cap Screw Rating 15 Plug... 2 ASTM SS30 Gasket... 1 EPDM 17 Hex Socket Cap Screw ASTM SS30 1 Post ASTM A536 Flange Washer... 2 Carbon Steel Galvanized Spring Carbon Steel Washer... 2 Galvanized 21 Hex Socket Cap Screw Rating Valve Size Dimensions in (mm) ANSI DN Dim. A ANSI Class 150 Dim. B Qty. N Dim. A ISO PN Dim. B Qty. N Dim. A AS 29 (Table E) Dim. B Qty. N 2 DN50.75 (1,7) 0.75 (19,0).92 (5,0) 0.75 (19,0).9 (11,0) 0.71 (1,0) DN (190,5) 0.75 (19) 7.09 (10,0) 0.75 (19) 7.00 (17,0).071 (1,0) 6 DN150 DN (21,5) (29,5) 0. (22) 0. (22) 9.5 (20,0) (295,0) 0. (23) 0. (23) 9.25 (235,0) (292,0) 0.7 (22,0) 0.7 (22,0) Dim. A Bolt Circle Diameter 10 DN250 DN300 1 DN350 DN (362,0) (32,0) 1.75 (76,3) (539,) 1.00 (25) 1.00 (25) 1.13 (2,6) 1.13 (2,6) 13.9 (355,0).1 (10,0) 1.5 (70,0).67 (525,0) 1.13 (2) 1.13 (2) (2) 1.22 (31) 1.02 (356,0) 15.9 (06,0) 1.50 (70,0).51 (521,0) 0.7 (22,0) 1.02 (26,0) 1.02 (26,0) 1.02 (26,0) Dim. B Bolt Hole Diameter Qty. N Number of Bolt Holes 1 DN (577,9) 1.26 (32,0) (55,0) 1.22 (31) 19. (50,0) 1.02 (26,0) DN (635,0) 1.26 (32,0) (650,0) 1.3 (3) 25.2 (61,0) 1.02 (26,0) 2 DN (79,5) 1.37 (35,0) (770,0) 1.6 (37) (756,0) 1.30 (33,0) TABLE A GATE VALVE SELECTION FLANGE DRILLING SPECIFICATIONS
3 Page 3 of Valve Size ANSI DN Pipe Size O.D. (mm) Dimensions (mm) L CL P Tapping Boss Size ANSI Inch NPT Approx. Weight F x F Lbs. (kg) Approx. Weight F x G Lbs. (kg) Approx. Weight G x G Lbs. (kg) 2 DN (60,3) 7.00 (17) 10.9 (279) 25.0 (11,3) 2.1 (10,92) (10,9) DN100 DN (11,3) (5,1) 9.00 (229) (267) (332) (36) 1/ (35) (50) 73.5 (33,) () 50. (23.1) 101. (6,1) 6 DN (,3) (267) (36) (50) () 101. (6,1) DN0.625 (219,1) (292).7 (5) 3/ 12.6 (3) 1. () 17 (5) 10 DN (273,1) (330) 2.1 (6) (3,5) (1) (11,5) DN (323,9) 1.00 (356) 26.3 (670) 36.1 (175,5) 37. (172) (,5) 1 DN (355,6) (31,0) 33.9 (62) (230) DN (06,) 15.9 (06,0) (93) 1 7. (32) 1 DN (57,2) (32,0) 1.61 (1057) 96 (0) DN (50,0) (57,0).96 (112) (63) 2 DN (609,6).0 (50,0) 50.9 (95) 10 () CL P L FLANGE x FLANGE L FLANGE x GROOVE FIGURE 2 POST INDICATOR GATE VALVE NOMINAL DIMENSIONS L GROOVE x GROOVE
4 Page of BURY LINE No. Description Qty. Material 1 Locking Wrench ASTM A6B 2 Operating Nut... 1 ASTM B62 3 Hex Cap Screw... 2 ASTM A105 Hex Nut ASTM A105 5 Snap Ring... 1 AISI Target Carrier Yoke... 1 ASTM B62 7 Target... ASTM B10 Hex Cap Screw... ASTM A105 9 Window Glass... 2 Lexan-UN 10 Window Glass Gasket... 2 PTFE 11 Hex Cap Screw... ASTM A105 Hex Nut..... ASTM A Upper Post... 1 ASTM A536 1 Hex Cap Screw... 6 ASTM A Hex Nut ASTM A105 Mounting Flange... 1 ASTM A6B 17 Hex Cap Screw... ASTM A105 1 Hex Nut..... ASTM A Connection Tube Coupling ASTM A536 Cotter Pin AISI Inner Pipe... 1 ASTM A53 22 Connection Tube... 1 AISI Plug... 1 AISI 30 2 Cap ASTM A6B 25 Phillips Head Screw... 1 AISI Lock Hasp... 1 ASTM 307B FIGURE 3 VERTICAL INDICATOR POST ASSEMBLY
5 Page 5 of B SUPERVISORY SWITCH (NOT INCLUDED) C A INDICATOR WINDOW WRENCH LOCK (NOT INCLUDED) WRENCH UPPER POST INDICATOR MARK RING FINISHED GRADE LINE OUTER POST INNER PIPE BOTTOM FLANGE* MOUNTING BOLTS AND NUTS Post Type Type A Type B Valve Size Inch DN 2 DN50 DN100 6 DN150 DN0 10 DN250 DN300 1 DN350 DN00 1 DN50 DN500 2 DN600 A Valve CL to Finished Grade (mm) Minimum Maximum (7) (791) (92) 3.3 (975) 2.31 (1075) 5.50 (1156) 50.7 (92) 53.2 (1367) 5.5 (17) 61.9 (1572) 67.7 (172) (1) 65.3 (61) 69.3 (1762) (15) (195) (26) (022) 1.30 (097) 6.02 (217) 9.37 (302) (5) B (mm) 9.50 (20) (27) C (mm) (760) NOTE: * Type B Post bottom flange features reducing gear for compatibility with 1 in. (DN350) and larger valve sizes. GATE VALVE INDICATOR MATING FLANGE FIGURE VERTICAL INDICATOR POST FEATURES AND NOMINAL INSTALLATION DIMENSIONS
6 Page 6 of Installation Vertical Indicator Post, in. to in. (DN100 to DN300) Valves Step 1 Step 2 Step 3 Step 1. Rotate gate valve top cap clockwise to fully open gate valve. Step 2. Remove indicator wrench and cap bolts and nuts. Step 3. Remove cap assembly from body cavity. Step Step 5 Step 6 th NOTCH T 5 IN. (7 mm) VALVE SIZE IN. (DN) (DN100) 6 (DN150) (DN0) 10 (DN250) (DN300) DIM. T IN. (mm) 1.1 (30) 1.77 (5) 2.36 (60) 2.95 (75) 3.7 (95) Step. Rotate target carrier assembly around operating nut stem to adjust distance between top surface of carrier yoke and bottom flange of cap to 5 in. (7 mm). Step 5. Engage middle tooth (centerline) of OPEN target in fourth notch in serrated edge from top surface of carrier yoke. Locate SHUT target per Dimension T in table. Step 6. Temporarily engage connection tube coupling onto gate valve top cap and attach indicator to gate valve mounting flange with bolts and nuts. Step 7 Step Step 9 CUT LINE 1-1/2" (0 mm) Step 7. Loosen jam nuts and bolts to free indicator outer pipe from inner pipe. Adjust outer pipe bury line even with finished grade. Step. Tighten bolts and jam nuts to secure outer pipe onto inner pipe. Step 9. Mark cut line on connection tube 1-1/2 in. (0 mm) above top flange of body.
7 Page 7 of Step 10 Step 11 Step CUT LINE Step 10. Remove connection tube from body and cut at cut line. Step 11. Temporarily detach indicator from gate valve and raise to gain access to gate valve top cap. Engage connection tube coupling onto gate valve top cap. Step. Secure indicator to gate valve with bolts and nuts. Step 13 Step 1 Step 15 Step 13. Insert cap assembly into body cavity, aligning carrier yoke keyway slots with body keys and square hole in operating nut stem with connection tube. Step Step 1. Secure cap to body with bolts and nuts. Note: Adjust position of targets on carrier yoke as necessary if conditions in Steps 15 and are not achieved. Gate valve must prevent flow when indicator displays SHUT condition. Similarly, gate valve must allow full flow when indicator displays OPEN condition. Step 15. Attach wrench to operating nut and rotate counter-clockwise. Observe gate valve waterway to verify wedge in fully SHUT position. Observe indicator to verify SHUT targets centered in windows. Step. Rotate wrench clockwise. Observe gate valve waterway to verify wedge in fully OPEN position. Observe indicator to verify OPEN targets centered in windows.
8 Page of Installation Vertical Indicator Post, 1 in. to 2 in. (DN350 to DN600) Valves Step 1 Step 2 Step 3 Step 1. Rotate gate valve top cap clockwise to fully open gate valve. Step 2. Remove top cap from gate valve. Step 3. Remove indicator wrench and cap bolts and nuts. Step Step 5 Step 6 th NOTCH Step. Remove cap assembly from body cavity. 6-1/2 IN. (5 mm) Step 5. Rotate target carrier assembly around operating nut stem to adjust distance between top surface of carrier yoke and bottom flange of cap to 6-1/2 in. (5 mm). VALVE SIZE IN. (DN) 1 (DN50).72 (1) (DN500) 2 (DN600) DIM. T IN. (mm) 1 (DN350) 3.72 (9,5) (DN00).25 (10) 5. (132) 5.91 (150) Step 6. Engage middle tooth (centerline) of OPEN target in fourth notch in serrated edge from top surface of carrier yoke. Locate SHUT target per Dimension T in table. T Step 7 Step Step 9 Step 7. Temporarily attach indicator to gate valve mounting flange with bolts and nuts. Ensure connection tube coupling remains engaged onto reducing gear top cap. Step. Loosen jam nuts and bolts to free indicator outer pipe from inner pipe. Adjust outer pipe bury line even with finished grade. Step 9. Tighten bolts and jam nuts to secure outer pipe onto inner pipe.
9 Page 9 of Step 10 CUT LINE 1-1/2" (0 mm) Step 11 Step CUT LINE Step 10. Mark cut line on connection tube 1-1/2 in. (0 mm) above top flange of body. Step 11. Remove connection tube from body and cut at cut line. Step. Temporarily detach indicator from reducing gear and raise to gain access to reducing gear top cap. Engage connection tube coupling onto reducing gear top cap. Step 13 Step 1 Step 15 Step 13. Secure indicator to reducing gear with bolts and nuts. Step 1. Insert cap assembly into body cavity, aligning carrier yoke keyway slots with body keys and square hole in operating nut stem with connection tube. Step 15. Secure cap to body with bolts and nuts. Step Step 17 Note: Adjust position of targets on carrier yoke as necessary if conditions in Steps and 17 are not achieved. Gate valve must prevent flow when indicator displays SHUT condition. Similarly, gate valve must allow full flow when indicator displays OPEN condition. Step. Attach wrench to operating nut and rotate counter-clockwise. Observe gate valve waterway to verify wedge in fully SHUT position. Observe indicator to verify SHUT targets centered in windows. Step 17. Rotate wrench clockwise. Observe gate valve waterway to verify wedge in fully OPEN position. Observe indicator to verify OPEN targets centered in windows.
10 Page 10 of No. Description Qty. Material 1 Lifting Eye Bolt ASTM A307B 2 Hex Nut ASTM A307B 3 Washer... 1 ASTM A307B Handwheel... 1 ASTM A536 5 Operating Nut... 1 ASTM B62 6 Hex Cap Screw... 2 ASTM A307B 7 Hex Nut ASTM A307B Snap Ring... 1 AISI Target Carrier Yoke... 1 ASTM B62 No. Description Qty. Material 10 Target... ASTM B10 11 Hex Cap Screw... ASTM A307B Window Glass... 2 Lexan-UN 13 Window Glass Gasket... 2 PTFE 1 Hex Cap Screw... ASTM A307B 15 Hex Nut..... ASTM A307B Body ASTM A Stand Pipe... 1 ASTM A53 No. Description Qty. Material 1 Connection Tube... 1 AISI Cotter Pin AISI 30 Connection Tube Coupling ASTM A Plug... 1 Malleable Iron 22 Cap ASTM A6B 23 Phillips Head Screw... 1 AISI 30 2 Lock Hasp... 1 ASTM 307B FIGURE 5 CROSS WALL INDICATOR POST ASSEMBLY
11 Page 11 of Valve Size Inch DN A Valve CL to Exterior Wall (mm) Minimum Maximum Valve Size Inch DN A Valve CL to Exterior Wall (mm) Minimum Maximum 2 DN (273) 9.36 (2500) DN0.19 (513) (273) DN (325) (2550) 10 DN (615) (20) 6 DN (22) (267) DN (700) (2925) A -1/" (51 mm) GATE VALVE ANCHORING HARDWARE (NOT INCLUDED) GATE VALVE TOP CAP WALL 10-1/2" (267 mm) SQUARE SPACED -5/" (3 mm) SUPERVISORY SWITCH (NOT INCLUDED) INDICATOR BODY CONNECTION COUPLING 1-3/" DIA. (375 mm) SYSTEM PIPE AND CONNECTING HARDWARE (NOT INCLUDED) SQUARE CONNECTION TUBE STANDPIPE -1/2" O.D. (11,3 mm) HANDWHEEL LOCK AND CHAIN (NOT INCLUDED) FIGURE 6 CROSS WALL INDICATOR POST FEATURES AND NOMINAL INSTALLATION DIMENSIONS HANDWHEEL TARGET WINDOW
12 Page of Installation Wall Indicator Post, 2 in. to in. (DN100 to DN300) Valves Step 1 Step 2 Step 3 Step 1. Rotate gate valve top cap clockwise to fully open gate valve. Step 2. Remove indicator cap bolts and nuts. Step 3. Remove cap assembly from body cavity. Step Step 5 th NOTCH Step 6 T 5 IN. (7 mm) VALVE SIZE IN. (DN) DIM. T IN. (mm) VALVE SIZE IN. (DN) 2 (DN50) 0.79 () (DN0) (DN100) 6 (DN150) 1.1 (30) 1.77 (5) 10 (DN250) (DN300) DIM. T IN. (mm) 2.36 (60) 2.95 (75) 3.7 (95) -1/2" (11,3 mm) DIA. 10-1/2" (267 mm) SQUARE Step. Rotate target carrier assembly around operating nut stem to adjust distance between top surface of carrier yoke and bottom flange of cap to 5 in. (7 mm). Step 5. Engage middle tooth (centerline) of OPEN target in fourth notch in serrated edge from top surface of carrier yoke. Locate SHUT target per Dimension T in table. Step 6. Prepare wall for standpipe penetration and indicator mounting. Step 7 Step Step 9 CUT LINE CUT LINE 1-1/2" (0 mm) Step 6. Insert standpipe through bored hole, mount indicator body and temporarily engage connection tube coupling onto gate valve top cap. Step. Mark cut line on connection tube 1-1/2 in. (0 mm) beyond end flange of body. Step 9. Remove connection tube from body and cut at cut line.
13 Page 13 of Step 10 Step 11 Step Step 10. Insert connection tube through body and standpipe and engage coupling onto gate valve top cap. Step 11. Insert cap assembly into body cavity, aligning carrier yoke keyway slots with body keys and square hole in operating nut stem with connection tube. Step. Secure cap to body with bolts and nuts. Step 13 Step 1 Note: Adjust position of targets on carrier yoke as necessary if conditions in Steps 13 and 1 are not achieved. Gate valve must prevent flow when indicator displays SHUT condition. Similarly, gate valve must allow full flow when indicator displays OPEN condition. Step 13. Rotate handwheel counterclockwise. Observe gate valve waterway to verify wedge in fully SHUT position. Observe indicator to verify SHUT targets centered in windows. Step 1. Rotate handwheel clockwise. Observe gate valve waterway to verify wedge in fully OPEN position. Observe indicator to verify OPEN targets centered in windows.
14 Page 1 of FLOW RATE IN LITRES PER MINUTE (LPM) (1 GPM = 3,75 LPM) ,0 NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI) INCH (DN50) INCH (DN100) 6 INCH (DN150) INCH (DN0) 10 INCH (DN250) INCH (DN300) FLOW RATE IN GALLONS PER MINUTE (GPM) GRAPH A GATE VALVE FRICTION LOSS 0,010 0,009 0,00 0,007 0,006 0,005 0,00 NOMINAL PRESSURE DROP IN BAR (1 PSI = 0,0695 BAR) Care and Maintenance The TYCO Resilient-Seated Gate Valves with Vertical or Cross Wall Post Indicators must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained for the proper authorities and notify all personnel who may be affected by this action. After placing a fire protection system in service, notify the proper authorities and advise those responsible for monitoring proprietary and/or central station alarms. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association for example, NFPA 25 in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified inspection service in accordance with local requirements and/or national codes. Gate Valve Debris lodged in the sealing area of the wedge may cause the valve to close hard. Backing off the indicator wrench or handwheel and closing it again, several times if necessary, can correct this problem. The valve should never be forced to seat by applying a wrench or extension to the lever, as it may distort the valve components or score the sealing surfaces. All replacement parts must be obtained from the manufacturer to assure proper operation of the valve. Vertical Indicator Post It is recommended that Vertical Indicator Posts used to operate fire protection system water control valves be locked in the fully open position using the wrench. The locks must be sturdy and resistant to breakage except by heavy bolt cutters. It is recommended that a visual inspection be carried out on a monthly basis to ensure: the Post Cap, Upper Barrel, and windows have not been damaged the Targets indicate that the valve is open the Wrench is in place on the Post and is securely locked It is further recommended that on a quarterly basis, the Vertical Indicator Post should be closed two turns and then reopened to verify that the PIV is in the fully open position and properly engages with the Post. Where a Supervisory Switch is installed, a check should be undertaken to ensure that the contacts are working properly. Any missing or damaged parts should be immediately replaced. Cross Wall Indicator Post It is recommended that Cross Wall Indicator Posts used to operate fire protection system water control valves be locked in the fully open position using the Handwheel. The locks must be sturdy and resistant to breakage except by heavy bolt cutters. It is recommended that a visual inspection be carried out on a monthly basis to ensure: the Post body, Handwheel, and windows have not been damaged the Targets indicate that the valve is open the Post is properly locked open It is further recommended that on a quarterly basis, the Cross Wall Indicator Post should be closed two turns and then reopened to verify that the PIV is in the fully open position and properly engages with the Post and that the Supervisory Switch contacts are working properly. Any damaged parts should be immediately replaced.
15 Page 15 of Valve Size ANSI DN 2 DN50 DN100 6 DN150 DN0 10 DN250 DN300 1 DN350 DN00 1 DN50 DN500 2 DN600 Pipe Size O.D. (mm) (60,3).500 (11,3) (,3).625 (219,1) (273,1).750 (323,9) 1,0 (355,6),0 (06,) 1,0 (57,2),0 (50,0) 2,0 (609,6) Flange x Flange ANSI Class 150 Flange x Flange ISO PN Flange x Groove ANSI Class 150 Part Number Flange x Groove ISO PN Flange x Flange AS 29 (Table E) Groove x Groove TJPX TJPX TJPT TJPT TJPX TJPX TJPX TJPX TJPT TJPT TJPX TJPX10011 TJPX TJPX TJPT1503 TJPT1501 TJPX TJPX150 TJPX00003 TJPX00001 TJPT02193 TJPT02191 TJPX00005 TJPX0219 TJPX TJPX TJPT TJPT TJPX TJPX TJPX TJPX TJPT TJPT TJPX TJPX30032 TJPX TJPX TJPX TJPX TJPX TJPX TJPX TJPX TJPX TJPX TJPX TJPX TJPX TJPX TJPX TABLE B POST INDICATOR GATE VALVE PART NUMBERS Indicator Post Vertical Type A Vertical Type B Cross Wall Part Number TJUPA TJUPB TJWP TABLE C VERTICAL AND CROSS WALL INDICATOR POST PART NUMBERS Limited Warranty For warranty terms and conditions, visit Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). Refer to Table B for Gate Valve part numbers and Table C for Vertical and Cross Wall Indicator Post part numbers. Replacement Vertical Indicator Post Wrench All Vertical Indicator Post types feature a removable wrench for operating the PIV. Replace as necessary. Specify: Vertical Indicator Post Wrench, P/N TJWPWRENCH
16 Page of 100 Pennbrook Parkway, Lansdale, PA 196 Telephone Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association
with the specific application. Always read and understand the installation
Worldwide Contacts www.tyco-fire.com Resilient-Seated Gate Valves Outside Screw and Yoke General Description TYCO Resilient-Seated Gate Valves are used in Fire Protection Systems for on/off operation.
More informationResilient-Seated Gate Valves with Vertical or Cross Wall Post Indicator
Worldwide ontacts www.tyco-fire.com Resilient-Seated Gate Valves with Vertical or ross Wall Post Indicator General Description TYO Resilient-Seated Gate Valves with Vertical and ross Wall Indicators are
More informationResilient-Seated Gate Valves with Vertical or Cross Wall Post Indicator
Worldwide ontacts www.tyco-fire.com Resilient-Seated Gate Valves with Vertical or ross Wall Post Indicator General Description TYO Resilient-Seated Gate Valves with Vertical and ross Wall Indicators are
More informationModel CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data
Worldwide Contacts www.tyco-fire.com Model CV-FR Grooved-End Riser Check Valves Inch to Inch (DN0 to DN00) General Description The TYCO Model CV-FR Grooved- End Riser Check Valve is a compact and rugged
More informationGRINNELL Model B303 Grooved End Butterfly Valves with Gear Operators or Lever-Lock Operators General Description
Worldwide Contacts www.grinnell.com GRINNELL Model B Grooved End Butterfly Valves with Gear Operators or Lever-Lock Operators General Description The GRINNELL Model B Butterfly Valves provide for efficient
More informationGRINNELL Model B302 and Model BN302 Grooved End Butterfly Valves with Gear Operators or Lever-Lock Operators General Description
Worldwide Contacts www.grinnell.com GRINNELL Model B0 and Model BN0 Grooved End Butterfly Valves with Gear Operators or Lever-Lock Operators General Description The GRINNELL Model B0 and Model BN0 Butterfly
More informationFire Protection Indicator Post
The 813 Series Indicator Post is designed to operate non-rising stem gate valves used in the control of underground water supply for automatic sprinklers, water spray deluge, foam-water deluge, and standpipe
More informationTechnical Data. Sizes 2 12 Inch (DN50 DN300)
Worldwide Contacts www.tyco-fire.com Model BFV-/BFV-C Butterfly Valve Grooved End General Description The TYCO Models BFV- and BFV- C Grooved End Butterfly Valves are indicating type valves designed for
More information1-1/2 Inch (DN40) 9 lb (4,1 kg) Groove Groove 1 8 lb (3,6 kg) Flange Groove 1 N/A N/A. Flange Flange N/A N/A
Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Diaphragm Style General Description The TYCO 1-1/2 inch to inch (DN40 to DN200), DV-5 Deluge Valves are diaphragm type valves designed for vertical
More informationWorldwide Contacts. Technical Data
Worldwide Contacts www.tyco-fire.com Model BFV-/BFV-C Butterfly Valve Grooved End General Description The TYCO Models BFV- and BFV- C Grooved End Butterfly Valves are indicating type valves designed for
More informationDV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description
Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description The TYCO Aluminum Bronze DV-5 Deluge Valves are available to provide an alternative material
More informationINSTALLATION, OPERATION, and MAINTENANCE GUIDE NIBCO Wall Mount Indicator Posts Series NIP-2AW
INSTALLATION, OPERATION, and MAINTENANCE GUIDE NIBCO Wall Mount Indicator Posts Series NIP-2AW PATENT #US 9,541,218 NIBCO Series NIP-2AW Wall Mount Indicator Posts are designed and manufactured to: Operate
More informationGRINNELL Model B302 and Model BN302 Grooved End Butterfly Valves with Gear Operators or Lever-Lock Operators General Description
Technical Services -00- +-0--0 www.grinnell.com GRINNELL Model B0 and Model BN0 Grooved End Butterfly Valves with Gear Operators or Lever-Lock Operators General Description The GRINNELL Models B0 and BN0
More informationWorldwide Contacts.
Worldwide Contacts www.tyco-fire.com DV-5 Remote-Resetting, Pressure-Reducing Deluge Valve, Limited Space Valve Cabinet General Description The TYCO DV-5 Remote-Resetting, Pressure-Reducing Deluge Valve,
More informationDV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description
Worldwide Contacts www.tyco-fire.com DV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to Inch (DN40 to DN200) General Description The TYCO DV-5A Automatic
More informationBS 5163 Resilient Wedge Gate Valve
BS 516 Resilient Wedge Gate Valve BS 516 Flanged Resilient OS&Y Gate Valve, Type A, (XZ41X), /16, Gate valves serve to cut the medium flow in the piping system, widely used in the field of potable water,
More informationModel RM-1 Riser Manifold Commercial and Residential General Description
Worldwide Contacts www.tyco-fire.com Model RM- Riser Manifold Commercial and Residential General Description The TYCO commercial and residential Model RM- Riser Manifold provide the necessary waterflow
More informationTechnical Data. UL Listing is based on the following criteria:
Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve with Trim Inch and 6 Inch (DN1 and DN15) General Description The TYCO DV-5 Deluge Valve with Trim is a diaphragm-style valve that depends upon water
More informationType D3S PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP804
Worldwide Contacts www.tyco-fire.com Type D3S PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description The Type D3S Protectospray Nozzles are open (non-automatic) directional
More informationDirectional Spray Nozzles, Open, with Strainers High Velocity General Description
Worldwide Contacts www.tyco-fire.com Model FS Through F3S Mulsifyre Directional Spray Nozzles, Open, with Strainers High Velocity General Description The Model FS through F3S Mulsifyre Nozzles are open
More informationGrinnell Grooved Fire Protection Products Grooved Fittings
Technical Services: Tel: (800) 38-932 / Fax: (800) 79-5500 www.tyco-fire.com Grinnell Grooved Fire Protection Products Grooved Fittings General Description LPCB Vd S The grooved fittings provide an economical
More informationDV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description
Worldwide Contacts www.tyco-fire.com DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/ Inch to Inch (DN40 to DN00) General Description The TYCO DV-5a Automatic
More informationSWING CHECK VALVES SERIES 52-SC SERIES 600
SWING CHECK VALVES SERIES 52-SC SERIES 600 FEATURES/BENEFITS/SPECIFICATIONS AMERICAN Flow Control Series 52-SC Swing Check Valves incorporate design features to help increase service life for water and
More informationDV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description
Worldwide Contacts www.tyco-fire.com DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to Inch (DN40 to DN200) General Description The TYCO DV-5a Automatic
More informationEasy Riser swing check valve Models E-1 & F-1
Page 1 of 7 1. DESCRIPTION The Viking Easy Riser Swing Check Valve is a general purpose rubber-faced approved for use in fire service systems. The valve is for use in wet system risers, preaction system
More informationTECHNICAL DATA OBSOLETE
August 31, 2006 Check Valve 815a 1. PRODUCT NAME Viking Easy Riser Swing Check Valve Model E-1: Available since 1992 Model F-1: Available since 1994 2. MANUFACTURER The Viking Corporation 210 N. Industrial
More informationApproved Branded Traceable Fire Protection & Waterworks Valves
Approved Branded Traceable Fire Protection & Waterworks Valves (800) 766-0076 www.smithcooper.com Los Angeles, CA Atlanta, GA Vancouver, WA Chicago, IL AWWA C515 Compliant CONSIDER Your Options Tamper
More informationND = Double Door, SEAT NBR ES = Center Guided Silent Check / EPDM NS = Center Guided Silent Check / NBR. Butterfly Valves, Seat in body.
MAS-WDI-1118 MAS W-Series Water Works / Fire Protection Valves ORDERING CODES Series XX = Valve Type X = CWP XX = Design Type XX = End Connection W = AWWA/UL/FM, 10 = Gate Valve A = 300 CWP RS = Rising
More informationMEDALLION HYDRANT. clowvalve.com AWWA C502 UL LISTED FM APPROVED NSF 61/372 CERTIFIED 250 PSI WORKING PRESSURE 10-YEAR LIMITED WARRANTY
clowvalve.com MEDALLION HYDRANT AWWA C50 UL LISTED FM APPROVED NSF 6/37 CERTIFIED 50 PSI WORKING PRESSURE 0-YEAR LIMITED WARRANTY Clow Valve, A Division of McWane, Inc. MEDALLION HYDRANT FIRE PROTECTION
More informationINSTALLATION & MAINTENANCE GUIDE
BUTTERFLY VALVES INSTALLATION & MAINTENANCE GUIDE L-1 GLOBE BUTTERFLY VALVE INSTALLATION AND MAINTENANCE GUIDE Table of Contents Page Design Requirements and Installation Care and Maintenance GL175T GL175G
More informationDV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description
Worldwide Contacts www.tycofire.com DV Deluge Valve, Diaphragm Style, / thru Inch (DN0 thru DN00), Deluge System Wet Pilot Actuation General Description The DV Deluge Valve (described in Technical Data
More informationADMIRAL HYDRANT. clowvalve.com
clowvalve.com ADMIRAL HYDRANT AWWA C502 UL LISTED FM APPROVED NSF 61/372 CERTIFIED 250 PSI WORKING PRESSURE 350 PSI WORKING PRESSURE AVAILABLE 10-YEAR LIMITED WARRANTY Clow Valve, A Division of McWane,
More informationValves. BS Standard JINAN MEIDE CASTING CO., LTD.
Valves BS Standard JINAN MEIDE CASTING CO., LTD. Resilient Wedge Gate Valve XZ81X Grooved Resilient OS&Y Gate Valve Page 11 XZ51X Flanged x Grooved Resilient OS&Y Gate Valve Page 12 Z85X Grooved Resilient
More information4077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE FAX
Butterfly Valves 4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 FAX 989-846-9231 www.globesprinkler.com FEBRUARY 2010 L-1 BULLETIN BUTTERFLY REV# 4 GLOBE BUTTERFLY VALVE INSTALLATION AND
More informationModel DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation
Deluge Valve DV-5 Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation GeneralDescription The Model DV-5 Deluge Valve (described in Technical
More information516509_tabs 11/16/10 4:55 AM Page 1 FIRE HYDRANTS
Date Printed: November 2010 FIRE HYDRANTS or Tyton (6"),6, or 8" A EDDY FIRE HYDRANTS PARTS LIST WORKING PRESSURE: 150 PSI Note: Discontinued For Reference Only 350 PSI Working Pressure
More informationQ= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications
1 of 9 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can be used to facilitate manual
More informationType EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description
Worldwide Contacts www.tyco-fire.com Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description IMPORTANT Always refer to Technical Data Sheet TFP700 for the INSTALLER
More informationSUBMITTAL PACKAGE FIRE PROTECTION VALVES
SUBMITTAL PACKAGE FIRE PROTECTION VALVES Butterfly Valves Ductile Iron Grooved...pg 2-5 Grooved Check Valves...pg 6-8 OS&Y Valves...pg 9-12 ARGCO.com 800-854-1015 Updated 2/27/2017 ARGCO GROOVED BUTTERFLY
More informationOPTIMAL VALVE SOLUTIONS FOR OIL AND GAS PLANTS
AVK FLOW CONTROL OPTIMAL VALVE SOLUTIONS FOR OIL AND GAS PLANTS InterApp World Valve Wouter Witzel TEC artec AVK 1 2 AVK FLOW CONTROL l OIL & GAS PLANTS CONTENT: AVK FLOW CONTROL 4-5 OFFSHORE PRODUCTION
More informationGBV-G Balancing Valves
Ductile Iron ASTM A6, Grade 6-4-2 The Series GBV is a multi-turn, Y-style globe valve designed for accurate determination and control of fluid flow to circuits requiring precise balancing. Max. Working
More informationFIREFLO - MODEL F-06 INSPECTION, INSTALLATION & MAINTENANCE MANUAL. Item No.s/Description
FIREFLO - MODEL F-06 INSPECTION, INSTALLATION & MAINTENANCE MANUAL Item No.s/Description Item No. Description Material Specification HYDRANT Qty. Req d Item No. Description Material Specification 1 Operating
More informationRESILIENT SEATED BUTTERFLY VALVES. Howell Valve & Automation. Toll Free: Howellvalve.com
RESILIENT SEATED BUTTERFLY VALVES Howell Valve & Automation Toll Free: 1-888-469-3557 Howellvalve.com TABLE OF CONTENTS Description Page Index 2 Resilient Standard Features 3 ST Boot Series with BUNA-N
More informationGRINNELL MODEL CB800 CIRCUIT BALANCING VALVE INSTALLATION & SETTING HANDBOOK
Technical Services 866-500-4768 +-40-78-8220 GRINNELL MODEL CB800 CIRCUIT BALANCING VALVE INSTALLATION & SETTING HANDBOOK AUGUST 20 IH-4500 Table of Contents Contents General Description.... 3 Dimensional
More informationmh-valve.com 129 HYDRANT AWWA C502 NSF 61/372 CERTIFIED UL LISTED FM APPROVED 250 PSI WORKING PRESSURE 10-YEAR LIMITED WARRANTY
mh-valve.com 129 HYDRANT AWWA C502 NSF 61/372 CERTIFIED UL LISTED FM APPROVED 250 PSI WORKING PRESSURE 10-YEAR LIMITED WARRANTY 129 HYDRANT YESTERDAY, TODAY, & TOMORROW For more than 85 years, the M&H
More informationWater Distribution Solutions
Water Distribution Solutions Table of Contents WaterMaster 5CD250 Fire Hydrants 6 WaterMaster 5BR250 Fire Hydrants 8 FlowMaster Resilient Wedge Gate Valves 11 Valve Boxes 17 Meter Boxes 22 Table of Contents
More informationMILLCENTRIC FULL/100% POR T ECCENTRIC PLUG VALVE
ISO 9001 CERTIFIED MILLCENTRIC FULL/100% POR T ECCENTRIC PLUG VALVE Suggested Specifications The Milliken criteria of quality, reliability, safety and value are embodied in the Millcentric Eccentric valve,
More informationModel F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description
Technical Services: Tel: () 31-931 / Fax: () 791-55 Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and
More informationNEECO INDUSTRIES INC. INSTRUCTION MANUAL 7 1/16 10K SLAB GATE BODY
INSTRUCTION MANUAL 7 1/16 10K SLAB GATE BODY INTRODUCTION The NF-700 type gate valves provided by Neeco Industries are full-bore through conduit non-rising stem manually (w/ball screw) operated valves.
More informationA Zy-Tech Global Industries Product
A Zy-Tech Global Industries Product Worm & evel Gear Operators Another quality product from Zy-Tech Global Industries, Inc. Zy-Gear gear operators are designed for long lasting dependable service in oil
More informationKENNEDY VALVE KS-RW RESILIENT WEDGE VALVES
KENNEDY VALVE KS-RW RESILIENT WEDGE VALVES KENNEDY VALVE AWWA C515 Resilient Wedge Gate Valves Meet or Exceed the Requirements of AWWA Standard C515 UL-262/FM-1120/1130 ULC-Underwriters of Canada 2 1/2
More informationFivalco. General Information
General Information Fivalco is a US company in our 16 th year of manufacturing Fire Protection Valves of uncompromising quality for our discerning customers. All our products are FM or UL approved and
More informationTECHNICAL DATA. Inlet Type Outlet Type OBSOLETE 6 (DN150)
January 13, 2006 Deluge Valves 211 a 1. PRODUCT NAME Viking Model E-1 Deluge Valve 3 (DN80) Available since 1985 4 (DN100) Available since 1985 6 (DN150) Available since 1984 2. MANUFACTURER THE VIKING
More informationSeries 800 AWWA Butterfly Valves
Series 800 AWWA Butterfly Valves Valve and Gate Group A Century of Experience GA valves are known for long term reliability in the most demanding water and wastewater applications. Whether a simple check
More informationPROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA
The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate requirements that are optional depending
More informationSeries 756 FireLock Dry System Check Valve
R IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS Series FireLock Dry System Check Valve Grooved X Grooved and Flanged X Grooved 0.0 VICTAULIC IS AN ISO 900 CERTIFIED COMPANY PRODUCT DESCRIPTION The Victaulic
More informationWater Distribution Solutions
Water Distribution Solutions Table of Contents WaterMaster 5CD250 Fire Hydrants 6 WaterMaster 5BR250 Fire Hydrants 8 FlowMaster Resilient Wedge Gate Valves 11 Valve Boxes 17 Meter Boxes 22 Table of Contents
More informationISO RESILIENT WEDGE GATE VALVE. Engineering Creative Solutions for Fluid Systems Since 1901
ISO RESILIENT WEDGE GATE VALVE Engineering Creative Solutions for Fluid Systems Since 1901 TABLE OF CONTENTS ISO RESILIENT WEDGE GATE VALVE Scope of Line...1 Features and Benefits...1 Suggested Specification...2
More informationAMERICAN AVK COMPANY AVK SERIES 34 WALL MOUNTED & TELESCOPIC POST INDICATORS, UL LISTED, FM APPROVED FIELD MAINTENANCE AND INSTRUCTION MANUAL
AMERICAN AVK COMPANY AVK SERIES 34 WALL MOUNTED & TELESCOPIC POST INDICATORS, UL LISTED, FM APPROVED FIELD MAINTENANCE AND INSTRUCTION MANUAL TABLE OF CONTENTS EXPLODED ASSEMBLY / PARTS LIST INTRODUCTION
More informationTECHNICAL DATA 2-1/2-8 (dn65 - dn200)
1 of 13 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can be used to facilitate manual
More informationUniwat. Resilient Seated Gate Valves
Uniwat Resilient Seated Gate Valves www.comeval.es Resilent Seated Gate Valves - UNIWAT 504/507 Copyright COMEVAL VALVE SYSTEMS - Data subject to revision - Regularly updated data on www.comeval.es - DS01
More informationGENERAL FEATURES / SPEC M&H AWWA C502 FIRE HYDRANTS Style 929 Traffic Model 250 PSI Working Pressure 500 PSI Hydrostatic Test AWWA UL / FM Approval Type: Compression type, opening against line pressure.
More informationSuggested Specifications
ISO 9001 Certified Suggested Specifications The Milliken criteria of quality, reliability, safety and value are embodied in the Millcentric Eccentric valve, setting higher standards for dependable performance
More informationMUELLER ECCENTRIC PLUG VALVE
MUELLER INSTALLATION, OPERATING and MAINTENANCE INSTRUCTIONS 1 MUELLER System Design The life of the valve is dependent on its application, frequency of use and freedom from misuse. The properties of the
More informationAMERICAN AVK COMPANY AVK SERIES 34 WALL MOUNTED & TELESCOPIC POST INDICATORS, UL LISTED, FM APPROVED FIELD MAINTENANCE AND INSTRUCTION MANUAL
AMERICAN AVK COMPANY AVK SERIES 34 WALL MOUNTED & TELESCOPIC POST INDICATORS, UL LISTED, FM APPROVED FIELD MAINTENANCE AND INSTRUCTION MANUAL TABLE OF CONTENTS EXPLODED ASSEMBLY / PARTS LIST INTRODUCTION
More informationSentinel 250 Fire Hydrant
Maintenance Instructions manual table of contents PAGE Sentinel 250 Fire Hydrant Inspection and Lubrication 2 Rotating Hydrant to Face Desired Direction 3 Installing Extension Section 3-6 Restoring Service
More informationDIMENSIONS (approximate)
Page 1 of 8 a NRS GATES OS&Y GATES company Model 48 Resilient Wedge Gate Valve SPECIFICATION SUBMITTAL SHEET FEATURES Sizes: 2 1/2" 3" 4" 6" 8" 10" 12" Maximum working water pressure 200 PSI Maximum working
More informationModel-1 Natural Gas Valves
Flanged End 285 Screwed Weld End Locking Devices KEROTEST Model-1 s Short Weld End Long Weld End Weld x Flange 500 / 740 Flanged End 500 / 740 Weld x Flange 285 Model-1 Short Weld End Standard Welding
More informationKunkle Models 91/218/228 liquid relief valves Safety and relief products
Cast iron liquid relief valves with bronze trim including models UL and FM approved for fire pump installations Model 228 Features Bolted bonnet allows easy inspection and servicing without removal from
More informationGD N (not shown) No Switches. GD N Grooved 2¹ ₂", 3", 4", 6", 8", 10"
300 PSI WWP UL/FM Butterfly Valves Designed for normally open position monitoring Elastomer Encapsulated Disc Accepts Internal Supervisory Switches Compatible with IPS Pipe 300 PSI/20.7 Bar Non-Shock Cold
More informationKunkle Models 91/218/228 liquid relief valves Safety and relief products
Cast iron liquid relief valves with bronze trim including models UL and FM approved for fire pump installations Model 8 Features Bolted bonnet allows easy inspection and servicing without removal from
More informationGT-200 GATE VALVES PN16, Screwed end
Document No. : MD-QO-04-281 Date : 2009/07 /17 Version : 1.0 GT-200 GATE VALVES PN16, Screwed end USER MANUAL Modentic Industrial Corporation 14F-1,No.57Taya Rd.,Taichung,Taiwan,R.O.C. Email:modentic@ms9.hinet.net
More informationInstallation, Operation and Maintenance Guide II NIBCO High Performance Butterfly Valves Series 6822 and 7822
Installation, Operation and Maintenance Guide II NIBCO High Performance Butterfly Valves Series 6822 and 7822 Statements: NIBCO High Performance Butterfly Valves, Series 6822 and 7822, have been designed
More informationFIG Gruvlok Flanges
Gruvlok Flanges The Gruvlok Fig. 7012 Flange allows direct connection of Class 125 or Class 150 flanged components to a grooved piping system. The two interlocking halves of the 2" thru 12" sizes of the
More informationData Sheet Issue A
General Description The Rapidrop Fig 601/602 dry barrel post / flushing fire hydrant is designed to be a trouble free, easy to maintain hydrant. The Fig 601/602 fire hydrant is rated for a working pressure
More informationRESILIENT SEATED GATE VALVE FAF 6200
PRODUCTION STANDARTS DN40 DN800 PN 10-16 Design EN 1171 / EN 1074 Connection Face to Face EN 1092-2 / ISO 7005-2 - Flanged EN 558 Series 15 / DIN 3202 F5 Marking EN 19 Tests EN 12266-1 Corrosion Protection
More informationSECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING
SECTION 220523 - GENERAL-DUTY VALVES FOR PLUMBING PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More information1. Valves shall conform to the latest version of AWWA Standard C-509 covering Resilient Seated gate Valves for Water Supply Service.
KENNEDY KENNEDY VALVE MODEL VALVE KS-RW 1. Valves shall conform to the latest version of AWWA Standard C-509 covering Resilient Seated gate Valves for Water Supply Service. 2. The valves shall have a cast
More informationThe SWL Series Swing Check Valves Meets AWWA C Standards (Full Waterway) Accepts Air Cushions Cost-effective Swing Check Valve Solution
The Series Meets AWWA C-508-01 Standards (Full Waterway) Accepts Air Cushions Cost-effective Swing Check Valve Solution Crispin Since 1905 Crispin Multiplex Manufacturing Co. 600 Fowler Avenue Berwick,
More informationThe applicable material specifications for ductile iron and rubber gaskets apply:
72 COUPLINGS - Grinnell Copper Grooved System is designed for joining copper tube size components 2" to 8" (54,0mm to 206,4mm) type K, L, M and DWV. All couplings and fittings are rated for working pressures
More informationAmerican Flow control 5 1/4 B-62-B-5
American Flow control 5 1/4 B-62-B-5 Fire Hydrant FLOW CONTROL Construction Fully complies with AWWA C502 and is available UL Listed and FM Approved in applicable configurations. one-piece bronze OPERATING
More informationAVK SAUDI VALVES MANUFACTURING COMPANY
AVK SAUDI VALVES MANUFACTURING COMPANY AVK SERIES 24 - HIGH PRESSURE, WET BARREL HYDRANT FIELD MAINTENANCE AND INSTRUCTION MANUAL TABLE OF CONTENTS EXPLODED ASSEMBLY / PARTS LIST INTRODUCTION / DESCRIPTION
More informationBUTTERFLY VALVES KENNEDY 140 YEARS AWWA C504 CLASS 150B & 250B CERTIFICATIONS ISO 9001 ISO BS OHSAS
KENNEDY BUTTERFLY S CERTIFICATIONS ISO 9001 ISO 14001 BS OHSAS 18001 AWWA C504 CLASS 150B & 250B STYLE 4500 3-24 STYLE 1450 30-54 CONSULT KENNEDY FOR SIZES LARGER THAN 54 INCHES. 140 YEARS WWW.KENNEDY.COM
More informationSECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING
SUNY GENESEO 220523-1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationAMERICAN FLOW CONTROL 4"-48" SERIES 2500 TAPPING VALVES
AMERICAN FLOW CONTROL 4"-48" SERIES 2500 TAPPING VALVES FEATURES/SPECIFICATIONS/MAINTENANCE FEATURES AMERICAN provides tapping valves for sizes 4 in. 48 in. rated at 250 psig pressure. Tapping valves 4
More informationAMERICAN FLOW CONTROL 5 1/4 B-84-B-5 FIRE HYDRANT
AMERICAN FLOW CONTROL 5 1/4 B-84-B-5 FIRE HYDRANT CONSTRUCTION Fully complies with ANSI/AWWA C502 and is available Listed by Underwriters Laboratories, Inc. and Approved by FM Approvals in applicable configurations.
More informationTECHNICAL DATA. model f-1 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA. Page 1 of 11
Page 1 of 11 1. DESCRIPTION The Viking Model F-1 Dry Pipe Valve is a latching differential valve used to separate the water supply from the dry pipe sprinkler system. The valve combines a positive latching
More informationBUTTERFLY VALVE 17 SERIES Gearbox
DN H1 H2 H3 BUTTERFLY VALVE 17 SERIES Gearbox FIGURE: 17234ER: 17234BR: 17234VR: Seat in EPDM, with gearbox Seat in Buna, with gearbox Seat in Viton, with gearbox B ØR L DIMENSIONS: (mm) DN L B XR H1 H2
More informationHIGH PERFORMANCE BUTTERFLY VALVE
Figure HPA BUTTERFLY VALVES Features: Bi-directional Bubble-tight Shutoff Suitable for Saturated Steam Service to 150 PSI Angled Disc Available in Wafer (3 to 12 ) or Lug (3 to 24 ) Stocked in Carbon by
More informationTypical Properties. Technical Data
Worldwide Contacts www.tyco-fire.com LFP Antifreeze Agency Listed Solution for Fire Sprinkler Systems General Description LFP antifreeze is a pre-mixed freeze protection solution designed and listed for
More informationAvailable End Connections & Size Range
ECCENTRIC PLUG VALVES Size Range 3"-24" Water Working Hydrostatic Size Range Pressure psi Test psi 3"-12" 175 350 14"-24" 150 300 Available End Connections & Size Range Figure No. Flanged 3"-24" F-5412
More informationProduct Submittals for Project
Product Submittals for Project May 011-1 Couplings Figure 577 Light Weight Rigid Coupling For Fire Protection Pressure Rating and Listing / Approval information contact Tyco Fire Suppression & Building
More informationACE VALVE COMPANY LIMITED
Gate & Globe Valves ACE COMPANY LIMITED ttp://www.acevalve.co.kr Mangdeokri, Juchonmyun, Gimhae, Gyeongnam, Korea. TEL +000 FAX +0~ Email acevalve@acevalve.co.kr omepage www.acevalve.co.kr 0.0. ACE CATALOG
More informationSECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION. A. Pipe, fittings, valves, and connections for sprinkler systems.
SECTION 210500 - COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, valves, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS A. Section 099000
More informationGrooved Fire Protection. Installation Handbook
Grooved Fire Protection Installation Handbook October 2016 Grooved Fire Protection Installation Handbook OCTOBER 2016 IH-1000FP Worldwide Contacts www.tyco-fire.com GLOBAL HEADQUARTERS 1400 Pennbrook
More informationThe GACHOT V501 gate valve offer the most possible reliability for process and critical applications
The GACHOT V501 gate valve offer the most possible reliability for process and critical applications Features Construction complies with NF EN 1984 Straight-through flow and full port Cast body (investment
More informationGROOVED COUPLINGS - STANDARD FLEXIBLE Model 101
GROOVED COUPLINGS - STANDARD FLEXIBLE Model 101 Available Sizes 1" through 12" (25 through ) Pipe Material Carbon steel, Schedule 10, Schedule 40. For use with alternative materials and wall thicknesses
More informationAMERICAN FLOW CONTROL 5 1/4 B-62-B-5 FIRE HYDRANT
AMERICAN FLOW CONTROL 5 1/4 B-62-B-5 FIRE HYDRANT CONSTRUCTION Fully complies with ANSI/AWWA C502 and is available UL Listed and Approved by FM Approvals in applicable configurations. ONE-PIECE BRONZE
More informationAmerican Flow control Series 2500
American Flow control 14-66 Series 2500 Resilient wedge gate valve FLOW CONTROL Construction Ductile iron operating nut Provides strength and durability. Lifting DEVICES 14-66 Valve is constructed of high-strength
More informationSeptember 2012 / M&H C502 / Model 129
GENERAL FEATURES / GENERAL SPEC M&H AWWA C502 FIRE HYDRANTS Model 129 Traffic Model 250 PSI Working Pressure 500 PSI Hydrostatic Test AWWA UL / FM Approved Type: Compression type, opening against line
More information