Instructions for Installation, Operation, Care and Maintenance

Size: px
Start display at page:

Download "Instructions for Installation, Operation, Care and Maintenance"

Transcription

1 Bulletin 59 Model DDX Deluge Valve (50 mm), ½ (65 mm), (80 mm), 76 mm, 4 (00 mm), 6 (50 mm), 65 mm & 8 (00 mm) Bulletin 59 Instructions for Installation, Operation, Care and Maintenance Wet Pilot Line, Dry Pilot Line, and Electric Actuation Trims The Reliable Automatic Sprinkler Co., Inc., 0 Fairview Park Drive, Elmsford, New York 05

2 General The Reliable Model DDX Deluge Valve is a hydraulically operated, differential latching clapper-type valve designed for use as primary control valve in deluge, preaction, or special types of fire protection systems. Following operation, the valve is easily reset externally (see Fig.). The Wet Pilot Line Trim set is connected to the push rod chamber outlet and provides a one and one quarter inch main drain on (50mm), ½ (65mm), 76mm and (80mm) valve sizes or a two inch main drain on 4 (00mm), 65mm, 6 (50mm) and 8 (00mm) valve sizes, alarm test, supply pressure gauge, and the push rod chamber supply connections. Releasing devices that can be used are wet pilot line detectors (Model F-FTR) or hydraulic manual emergency stations/pull boxes (Models A & B). Two alternate actuation trim sets, Dry Pilot Line or Electric Actuation, are available when dry pilot sprinklers or solenoid valves are used for releasing. Actuation by solenoid valves enables a full range of electrical detectors to be used for remote sensing. Listings & Approvals: (Only when used with Reliable s Trim Sets.). Listed by Underwriters Laboratories, Inc. and UL certified for Canada (culus).. Certified by Factory Mutual Approvals (FM).. NYC MEA 58-9-E 4. LPCB (4 (00mm), 65mm, 6 (50mm) & 8 (00mm) only) 5. CE 6. VdS Schadenverhütung GmbH Valve Operation The Reliable Model DDX Deluge Valve is shown in both closed and open positions in Fig.. In the closed position, the supply pressure acts on the underside of the clapper and also on the push rod through the push rod chamber s inlet restriction. The resultant force due to the supply pressure acting on the push rod is multiplied by the mechanical advantage of the lever and is more than sufficient to hold the clapper closed against normal supply pressure surges. When a fire is detected, a releasing device vents the push rod chamber to atmosphere through the chamber s outlet. Since the pressure cannot be replenished through the inlet restriction as rapidly as it is vented, the push rod chamber pressure falls instantaneously. When the push rod chamber pressure approaches approximately one-third of the supply pressure, the upward force of the supply pressure acting beneath the clapper overcomes the lever-applied force thereby opening the clapper. Once the clapper has opened, the lever acts as a latch, preventing the clapper from returning to the closed position. Water from the supply flows through the Deluge Valve into the system piping. Water also flows through the Deluge Valve alarm outlet to the alarm devices. After system shutdown, resetting the Model DDX Deluge Valve is quite simple. Doing so only requires pushing in and turning the reset knob at the rear of the valve (see Fig.). The external reset feature of the Model DDX Deluge Valve provides a means for simple, economical system testing, which is one essential facet of a good maintenance program. The external reset feature does not, however, eliminate another important facet of good maintenance, namely, periodic cleaning and inspection of the internal valve parts. In the event that water builds up inside the valve due to condensate from the air supply system or water left inside from valve system testing, a drain is available for venting. After closing the main supply valve, a small valve over the drain cup can be opened slightly until the water inside the valve body and the main pipe column has drained. Whenever ambient temperature conditions are high, the water temperature in the Model DDX Deluge Valve s pushrod chamber could possibly increase, thereby increasing the pressure in the chamber to values exceeding the rated pressure of the system. In an indoor installation where standard room temperatures are exceeded, a pressure relief kit may be needed. Pressure relief kit, P/N , can be installed into the pushrod chamber s release line to limit the pressure to 50 psi (7, bar). Reliable Model DDX Deluge Valve with associated trim sizes (50 mm), ½ (65 mm), 76 mm, (80 mm), 4 (00 mm), 65 mm, 6 (50 mm) and 8 (00 mm) are rated for use at a minimum water supply pressure of 0 psi (,4 bar) and a maximum water supply pressure of 50 psi (7, bar) for (50mm), / (65mm), (80mm), 76mm and 8 (00mm) valve sizes and 00 psi (0,7 bar) for 4 (00mm), 6 (50mm) and 65mm valve sizes). Water supplied to the inlet of the valve and to the push rod chamber must be maintained between 40 F(4 C) and 40 F(60 C). Pressurizing Line Connection The water supply for the push-rod chamber must be provided by connection of its inlet pressurizing line to the water supply piping. Pressurizing lines for multiple Model DDX Deluge Valve push-rod chambers must never be manifolded together, having only a single tap on the water supply piping. Each Model DDX Deluge Valve must have its own push-rod chamber pressurizing line connection. This connection must be made on the supply side of the water supply control valve (see Fig. 4 or Fig. 5). This can be accomplished by: Using a tapped connection directly below or next to the main water supply control valve using a welded outlet or the appropriate mechanical fittings. A grooved-end outlet coupling is one way to achieve this; or Using a water supply control valve that has an available threaded (NPT) supply-side tap design to allow for a direct water supply connection to the Model DDX Deluge Valve s push-rod chamber. Caution: Reliable s DDX valve is designed with an inlet restriction built into the pushrod chamber. It is important not to introduce additional restrictions into the direct water supply connection or the discharge from the pushrod chamber by installing additional valves or improperly installing the copper lines used in the trim of the valve..

3 Fig. Hydrostatic Testing of DDX Valves and DDX Systems As required by NFPA, fire sprinkler systems with working pressures up to and including 50 psi are to be hydrostatically tested at a water pressure of 00 psi and maintain that pressure without loss for two hours. Fire sprinkler systems with working pressures above 50 psi are required to be hydrostatically tested at 50 psi above the system working pressure and maintain that pressure without loss for two hours. In addition to the hydrostatic tests described above, dry pipe and double interlock preaction systems require an additional low pressure air test. In some cases, hydrostatic testing (in accordance with the NFPA requirements noted above) will result in pressures that exceed the working pressure of the valve and trim kit for the two-hour test period. The valve and applicable trim kit have been tested, approved and listed under these conditions and as such, hydrostatic testing in accordance with NFPA is acceptable. In addition, the clapper can remain in the closed position and the trim kit need not be isolated, as each has been designed to withstand hydrostatic testing as required by NFPA. Hydrostatically testing the valve and trim to pressures higher than their rating is limited to the hydrostatic test as referenced by NFPA. It does not address the occurrence(s) of a water hammer effect, which can indeed damage the valve. A water hammer in the water supply piping of the valve can create pressures in excess of the rated pressure and should be avoided by all necessary means. This condition may be created from improper fire pump settings, underground construction work, or an improper venting of trapped air in the water supply piping. Engineering Specification (50 mm), ½ (65 mm), 76 mm, (80 mm), 4 (00 mm), 65 mm, 6 (50 mm) and 8 (00 mm) Model DDX Deluge Valve Deluge valve shall be a [ (50 mm)][½ (65 mm)][76 mm] [ (80 mm)][4 (00 mm)][65 mm][6 (50 mm][8 (00 mm] [culus Listed] [Factory Mutual Approved] hydraulically operated, differential latching clapper type valve. Deluge valve construction shall be of lightweight, ductile iron construction with either a screw in stainless steel seat and clapper assembly or drop in bronze seat and clapper assembly. Stainless steel or Bronze seat shall have O-ring seals to resist leakage and corrosion. Clapper facing shall be pressure actuated, providing a limited compression seat for the sealing force between the clapper rubber facing and the valve seat. Deluge valve shall have an external reset knob for resetting the clapper without requiring the removal of the valve face plate. Push-rod chamber design shall consist of a stainless steel piston/ push-rod and spring assembly with diaphragm seal secured to the casting through a push-rod guide constructed of a synthetic engineering plastic to resist corrosion. Casting shall have a bleeder hole located on the pushrod chamber for air/water leakage indication. Trip ratio shall be approximately a : force differential. Deluge valve shall be of the straight through design to minimize friction loss. Deluge valve shall be activated by [hydraulic wet-pilot][low pressure, pneumatic dry-pilot][electric] actuation trim. Inlet restriction orifice shall be factory installed into the inlet port of the deluge valve push-rod cover plate and not be a separate part of the deluge valve trim. End connection style to be [ (50 mm)].

4 [½ (65 mm)][76 mm] [ (80 mm)][4 (00 mm)][65 mm] [6 (50 mm)][8 (00mm)] grooved per ANSI/AWWA C606 or flanged per ASME 6.5 or ISO Deluge valve shall have a rated working pressure of 50 psi (7, bar) for (50mm), ½ (65mm), (80mm), 76mm and 8 (00mm) valve sizes or 00 psi (0,7 bar) for 4 (00mm), 6 (50mm) and 65mm valve sizes and shall be factory hydrostatic tested at 500 psi (4,5 bar) for (50mm), ½ (65mm), (80mm), 76mm and 8 (00mm) valve sizes or 600 psi (4,4 bar) for 4 (00mm), 6 (50mm) and 65mm valve sizes. Deluge valve to be [ (50 mm)][½ (65 mm)][76 mm] [ (80 mm)][4 (00 mm)][65 mm][6 (50 mm][8 (00 mm)] Reliable Model DDX Deluge Valve (Bulletin 59). Wet Pilot Line Trim Deluge valve wet pilot line trim shall be either galvanized or black pipe and include a ¼ main drain on (50 mm), ½ (65 mm), 76 mm and (80 mm) valve sizes or a main drain on 4 (00 mm), 65 mm, 6 (50 mm) and 8 (00 mm) valve sizes, alarm line test, water pressure gauges, pushrod chamber supply connections, manual emergency release valve, connection for wet pilot line of detectors, and 4 diameter drip cup assembly. Condensate drain trim shall also be included to prevent water columning above the clapper. The wet pilot line detection piping shall be ½ schedule 40 galvanized pipe and extend from the deluge valve push-rod chamber outlet to the protected area. Maximum wet pilot line length and height shall be in accordance with manufacturer s guidelines (see Fig. ). Wet pilot line shall utilize Reliable Model F-FTR fixed temperature release pilot line detectors spaced and positioned in accordance with the device listing or in accordance with NFPA 7 as fixed temperature heat detectors. Dry Pilot Line Trim Dry pilot line trim to be used in areas: Where ambient temperatures are expected to exceed 50 F (65 C) Subject to freezing Maximum wet pilot line height and/or length are exceeded Deluge valve dry pilot line trim shall be either galvanized or black pipe and include Model LP Dry Pilot Line Actuator, a ¼ main drain on (50 mm), ½ (65 mm), 76 mm and (80 mm) valve sizes or a main drain on 4 (00 mm), 65 mm, 6 (50 mm) and 8 (00 mm) valve sizes, alarm line test, air and water pressure gauges, push-rod chamber supply connections, manual emergency release valve, pressure relief valve, low air pressure switch, connections for dry pilot line of detectors and 4 diameter drip cup assembly. Condensate drain trim shall also be included to prevent water from columning above the clapper. Dry pilot line detection piping shall be ½ schedule 40 galvanized pipe and extend from the deluge valve push-rod chamber outlet to the protected area. Dry pilot line shall utilize Reliable Model F-FTR fixed temperature release pilot line detectors spaced and positioned in accordance with the device listing or in accordance with NFPA 7 as fixed temperature heat detectors. 4. Electric Actuation Trim Deluge valve electric trim shall be either galvanized or black pipe and include a normally closed, powered open electric solenoid valve, a ¼ main drain on (50 mm), ½ (65 mm), 76 mm and (80 mm) valve sizes or a main drain on 4 (00 mm), 65 mm, 6 (50 mm) and 8 (00 mm) valve sizes, alarm line test, water pressure gauges, push-rod chamber supply connections, manual emergency release valve, and 4 diameter drip cup assembly. Condensate drain trim shall also be included to prevent water from columning above the clapper. Standard Solenoid Valve Specifications: Skinner Model 78BN4UNLVN0CC Rated working pressure: 75 psi (, bar) Voltage: 4 VDC Power: 0 Watts Current: 0.4 Amps Holding Enclosure Coil: NEMA 4X Pipe Size: ½ NPT Female Cv Factor: 4.0 Alternate Solenoid Valve Specifications: Skinner Model 7BN4TNLVN0CC Rated working pressure: 00 psi (0,7 bar) Voltage: 4 VDC Power: Watts Current: 0.8 Amps Holding Enclosure Coil: NEMA 4X Pipe Size: ½ NPT Female Cv Factor:.8 Model DDX Deluge Valve Description. Rated working pressure: Valve & System - 50 psi (7. bar) for (50mm), ½ (65mm), (80mm), 76mm and 8 (00mm) valve sizes or 00 psi (0,7 bar) for 4 (00mm), 6 (50mm) and 65mm valve sizes).. Factory tested to a hydrostatic pressure of 500 psi (4,5 bar) for (50mm), ½ (65mm), (80mm), 76mm and 8 (00mm) valve sizes or 600 psi (4,4 bar) for 4 (00mm), 6 (50mm) and 65mm valve sizes). (Valve only). End and trim connections: ANSI/AWWA C606 grooved inlet and outlet Nominal Pipe Size (50 mm) ½ (65 mm) 76 mm (80 mm) 4 (00 mm) 65 mm 6 (50 mm) 8 (00 mm) Outlet Diameter.75 (60mm).875 (7mm).000 (76mm).500 (89mm) (4mm) (65mm) 6.65 (68mm) 8.65 (9mm) Groove Diameter.50 (57mm).70 (69mm).845 (7mm).44 (85mm) 4.4 (0mm) 6.0 (6mm) (64mm) 8.44 (4mm) Groove Width / (9.0mm) / (9.0mm) / (9.0mm) / (9.0mm) /8 (9.5mm) /8 (9.5mm) /8 (9.5mm) 7/6 (mm) Outlet Face to Groove 5/8 (6mm) 5/8 (6mm) 5/8 (6mm) 5/8 (6mm) 5/8 (6mm) 5/8 (6mm) 5/8 (6mm) /4 (9mm)

5 Threaded openings Per ANSI B. Flange Dimensions Flange Type: AMSE B6.5 Class 50 ISO PN6 AMSE B6.5 Class 50 ISO PN6 AMSE B6.5 Class 50 ISO PN6 Nominal Pipe Size 4 (00mm) 4 (00mm) 6 (50mm) 6 (50mm) 8 (00mm) 8 (00mm) Bolt Circle Diameter 7½ (9mm) 7 / (80mm) 9½ (4mm) 9 7 / 6 (40mm) ¾ (98mm) 5 / 8 (95mm) 4. Valve Exterior s Color: Bolt Hole Diameter ¾ (9mm) ¾ (9mm) 7 8 / (mm) 9 / (mm) 7 8 / (mm) 9 / (mm) Flange Outside Diameter 9 (9mm) 9 (9mm) (79mm) (79mm) ½ (4mm) ½ (4mm) Flange Number Thickness of Bolts 5 / 6 (4mm) 5 / 6 (4mm) 5 6 / (4mm) 5 6 / (4mm) (5.4mm) (5.4mm) Valve Size Color (50 mm) Black or Red ½ (65 mm) Black or Red 76 mm Red (80 mm) Black or Red 4 (00 mm) Black or Red 65 mm Red 6 (50 mm) Black or Red 8 (00 mm) Black or Red 5. Face to face dimensions: Valve Size: End Connection: End to End: " (50mm), ½" (65mm), 76mm & " (80mm) Groove/ Groove ½" (8mm) Groove/ Groove 4" (56mm) 4" (00mm) Flange/ Groove 6" (406mm) Flange/ Flange 6" (406mm) Groove/ Groove 6" (406mm) 6" (50mm) & 65mm Flange/ Groove 9" (48mm) Flange/ Flange 9" (48mm) 8" (00mm) Groove/ Groove 9 / 8 (49mm) Flange/ Flange ¼" (540mm) 6. Valve Shipping Weight: Valve Size: End Connection: Weight: " (50mm), ½" (65mm), 76mm & " (80mm) Groove/ Groove 4 lbs (5 kg) 4" (00mm) 6" (50mm) & 65mm Groove/ Groove Flange/ Groove Flange/ Flange Groove/ Groove Flange/ Groove Flange/ Flange Groove/ Groove 8" (00mm) Flange/ Flange 7. Trim Shipping Weight: Trim Configuration " (50 mm), ½" (65 mm), " (80 mm) & 76 mm lbs (9 kg 79 lbs (6 kg) 9 lbs (4 kg) 95 lbs (4 kg) lbs (56 kg) 8 lbs (69 kg) 48 lbs (67 kg) 97 lbs (90 kg) 4" (00 mm), 6" (50 mm), 8" (00 mm) & 65 mm Wet Pilot Deluge lbs (4 kg) 7 lbs (7 kg) Dry Pilot Deluge 9 lbs (8 kg) 50 lbs ( kg) Electric Actuation Deluge lbs (5 kg) 8 lbs (7 kg) Friction loss (Expressed in equivalent length of Schedule 40 pipe, based on Hazen & Williams formula: Valve Size: Equivalent Length: C = 0 C = 00 Cv " (50mm) 4.4 ft (, m). ft (,0 m) 0 ½" (65mm) 6.0 ft (,8 m) 4. ft (, m) 6 76mm 7.7 ft (, m) 5.5 ft (,7 m) 4 " (80mm).6 ft (,8 m) 9.0 ft (,7 m) 54 4" (00mm) 4 ft (4, m) 0 ft (,0 m) mm 9.4 ft (9,0 m) 0.9 ft (6,4 m) 886 6" (50mm) 9.4 ft (9,0 m) 0.9 ft (6,4 m) 886 8" (00mm) 5.5 ft (6, m) 8. ft (,6 m) Installation position: Vertical Trim Descriptions The trims for the Reliable Model DDX Deluge Valve are arranged for rapid, easy, and compact attachment, and serve as connection points to Reliable Model C Mechanical Alarms and other devices. The available Model DDX Deluge Valve trim sets are: Wet Pilot Trim Dry Pilot Trim Electric Actuation Trim All three trim configurations can be ordered as individual parts, in time-saving segmentally assembled kit forms, or fully assembled to the Model DDX Deluge Valve (with or without a control valve). The Model B Hydraulic Manual Emergency Station (see Fig. 9) is a standard item of all Deluge Valve trim sets. It consists of an aluminum nameplate mechanically attached to a ball valve. The valve handle in its OFF position is guarded against accidental turning to the ON position (and system discharge) by a nylon cable tie provided with each trim kit. The cable tie is inserted, as shown in Fig. 9, after the system has been restored for operation. The nylon cable tie is designed to allow, in case of an emergency, forceful turning of the valve handle to the ON position. As an alternative to the Model B Hydraulic Manual Emergency Station, the Model A Hydraulic Manual Emergency Pull Box (see Bulletin 506) is also available and can be provided as an option. Model F-FTR fixed temperature pilot line detectors and spacing requirements are described in Bulletin 80. Wet Pilot Line Trim Wet pilot line operation is the simplest method of Deluge Valve Actuation. The trim is a basic one and its components are included in all other Reliable Model DDX Deluge Valve Trims regardless of application. Shown in Figures 4 & 5, it contains components required on all installations, such as a one and one quarter main drain on (50 mm), ½ (65 mm), 76 mm and (80 mm) valve sizes or a two inch main drain on 4 (00 mm), 65 mm, 6 (50 mm) and 8 (00 mm) valve sizes, alarm test, supply and push rod chamber pressure gauges, and push rod chamber connections. The wet pilot line consists of a line of closed detectors (Model F-FTR) located over the area to be protected. This line contains water under pressure and is connected to the outlet of the push rod chamber of the Deluge Valve. When one of the pilot line detectors actuates, the push rod chamber is vented and the Deluge Valve operates. The Deluge Valve can also be operated manually by opening the ball

6 0 WET PILOT LINE HEIGHT VS LENGTH PSI MAXIMUM PILOT LINE HEIGHT (ft) PSI SUPPLY PRESSURE 00 PSI 75 PSI 50 PSI 75 PSI 5 PSI 00 PSI 80 PSI PSI 40 PSI 40 PSI 0 PSI 60 PSI 80 PSI valve of the Model B Hydraulic Manual Emergency Station (see Fig. 9) or the optional Model A Hydraulic Manual Emergency Pull Box (see Reliable Bulletin 506). The wet pilot line is only a detection system and does not contribute to controlling the fire. Its installation is subject to the following restrictions: a) It is not to be installed in an area subject to freezing. b) It is not to be installed in an area where temperatures in excess of 50 F (65 C) are anticipated. c) NFPA 7 or the authority having jurisdiction should be consulted for spacing and elevation requirements. d) Maximum wet pilot line length and height must comply with data provided in Fig.. Wet Pilot Trim installation on Model DDX Deluge Valves uses eight tapped openings for trim connections. Each opening and its function are indicated on Fig. 4 or Fig. 5. Using Fig. 4 or Fig. 5 as reference, the recommended trim installation is as follows:. Install ½ nipple (#, Fig. 4 or #7, Fig. 5) in the tapped opening marked TEST. Note: If interference occurs between the supply gauge and the control valve, the /4 plug (#48, Fig. 4 or #50, Fig. 5) in the opening marked SUPPLY may be swapped with: the /4 nipple (#, Fig. 4), angle valve (#9, Fig. 4) and gauge (#60, Fig. 4) for the (50mm), -/ (65mm), 76mm and (80mm) valve sizes; /4 nipple (#, Fig. 5), /4 elbow (#, Fig. 5), /4 nipple (#, Fig. 5), -way valve (#6, Fig. 5) and the gauge (#6, Fig. 5) for the 4 (00mm), 65mm and 6 (50mm) valve sizes; /4 nipple (#, Fig. 5), -way valve (#6, Fig. 5) and the gauge (#6, Fig. 5) for the 8 (00mm) valve size, in the trim installed in the opening marked TEST. Fig PSI 5 PSI 50 PSI 00 PSI 50 PSI 5 PSI PIPING EQUIVALENT LENGTH (ft). Install ½ nipple (#5, Fig. 4 or #4, Fig. 5) in the tapped opening marked ALARM and connect balance of this trim line.. Install ¼ plug (#48, Fig. 4 or #50, Fig. 5) in the tapped opening marked SUPPLY. Note: If interference occurs between the supply gauge and the control valve, the /4 plug (#48, Fig. 4 or #50, Fig. 5) in the opening marked SUPPLY may be swapped with: the /4 nipple (#, Fig. 4), angle valve (#9, Fig. 4) and gauge (#60, Fig. 4) for the (50mm), -/ (65mm), 76mm and (80mm) valve sizes; /4 nipple (#, Fig. 5), /4 elbow (#, Fig. 5), /4 nipple (#, Fig. 5), -way valve (#6, Fig. 5) and the gauge (#6, Fig. 5) for the 4 (00mm), 65mm and 6 (50mm) valve sizes; /4 nipple (#, Fig. 5), -way valve (#6, Fig. 5) and the gauge (#6, Fig. 5) for the 8 (00mm) valve size, in the trim installed in the opening marked TEST. 4. Install ½ nipple (#, Fig. 4 or #4, Fig. 5) in the tapped opening marked OUT and connect balance of this trim line. 5. Install ¼ inline check valve (#5, Fig. 4 or #4, Fig. 5) in the tapped opening marked IN and connect balance of this trim line. Caution: Over tightening check valve can cause a restriction in flow that may prevent the valve from setting up. 6. Install ¼ Nipple (#40, Fig. 4) or nipple (#4, Fig. 5) in the tapped drain opening and connect balance of this trim line. 7. Install ¾ x ¼ reducing coupling (#44, Fig. 4 or #46, Fig. 5) in the lower-most tapped opening at the rear of the Deluge Valve and connect the balance of this trim line. 8. Install ¾ pipe plug (#50, Fig. 4 or #5, Fig. 5) in the upper-most tapped opening at the rear of the Deluge Valve.

7 PRESSURE LOSS (BAR) MODEL DDX HYDRAULIC FRICTION LOSS GRAPH FLOW RATE (L/SEC) INCH (50 MM) & 65 MM 8 INCH (00 MM) 4 INCH (00 MM) INCH (80 MM) -/ INCH (65 MM) & 76 MM INCH (50 MM) INCH (00 MM) 6 INCH (50 MM) & 65 MM 4 INCH (00 MM) -/ INCH (65 MM) & 76 MM INCH (80 MM) INCH (50 MM) FLOW RATE (GPM) Fig. PRESSURE LOSS (PSI) 7.

8 Small DDX Wet Pilot Line Trim (Refer to Fig. 4) Item No. 4 Galvanized Part No. Black Pipe G G G G G0500 7G Description Valve Assembly, " (50mm) - For " Assembly Only Valve Assembly, ½" (65mm) - For ½" Assembly Only Valve Assembly, 76mm - For 76mm Assembly Only Valve Assembly, " (80mm) - For " Assembly Only Butterfly Valve, " - For " Assembly Only Butterfly Valve, ½" - For ½" Assembly Only Butterfly Valve, " - For " Assembly Only Rigid Coupling, " - For " Assembly Only Rigid Coupling, ½" - For ½" Assembly Only Rigid Coupling, " - For " Assembly Only Outlet Spool, " - For " Assembly Only Outlet Spool, ½" - For ½" Assembly Only Outlet Spool, " - For " Assembly Only Manual Emergency Station Assembly QTY Valve Caution Station Assembly Ball Drip Valve, ½" Adhesive Pad Angle Valve, ¼" Angle Valve, ¼" Ball Valve, ¼" NPTF x ¼" NPTM Check Valve, ¼" NPTM x ¼" NPTF Check Valve, Horizontal Swing, ½" NPT Check Valve, Horizontal Swing, " NPT Check Valve, Inline Poppet, ¼" Compression Connector, / 8" ID Tube x ¼" NPT Compression Connector, Elbow / 8" ID Tube x ¼" NPT Connector, / 8" ID Tube x ½" NPT Connector, Elbow, / 8" ID Tube x ¼" NPT Item Part No. No. Galvanized Black Pipe Description QTY Deluge Valve Nameplate Drain Cup, PVC Drain Hose Clip Elbow, ¼" Elbow, " Elbow, ¼" Flex Line, ½" Globe Valve, ¼" Globe Valve, ½" Nipple ¼" x ½" Nipple ¼" x 4" Nipple ½" x ½" Nipple ½" x " Nipple ½" x " Nipple ½" x Close Nipple ¾" x " Nipple " x " Nipple " x Close Nipple ¼" x " Nipple ¼" x 4" Nipple ¼" x Close Pipe Cross, ½" PVC Tubing, 8" / ID x 6 ft Reducer Bushing, ¾" x ¼" Reducer Bushing, ¾" x ½" Reducer Bushing, " Spigot x " NPTF, PVC Retaining Tie Square Head Plug, ¼" Square Head Plug, ½" Square Head Plug, ¾" Strainer, ¼" Street Elbow, ½" Tee, ½" Tee, ½" x ¼" x ½" Tee, ½" x ½" x ¼" Tee, ¾" Tee, ¾" x ½" x ½" Tee, ¼" x ¼" x " Union, ½" Valve, -way, ¼" Water Pressure Gauge (0-00 psi) Hose Clamp Copper Tubing, / 8" OD x ft. 8.

9 9. Fig. 4

10 Large DDX Wet Pilot Line Trim (Refer to Fig. 5) Item No. 4 Galvanized Part No. Black Pipe G G G G G0500 7G Description Valve Assembly, 4" (00mm) - For 4" Assembly Only Valve Assembly, 6" (50mm) - For 6" Assembly Only Valve Assembly, 65mm - For 65mm Assembly Only Valve Assembly, 8" (00mm) - For 8" Assembly Only Butterfly Valve, 4" - For 4" Assembly Only Butterfly Valve, 6" - For 6" Assembly Only Butterfly Valve, 8" - For 8" Assembly Only Rigid Coupling, 4" - For 4" Assembly Only Rigid Coupling, 6" - For 6" Assembly Only Rigid Coupling, 8" - For 8" Assembly Only Outlet Spool, 4" - For 4" Assembly Only Outlet Spool, 6" - For 6" Assembly Only Outlet Spool, 8" - For 8" Assembly Only Manual Emergency Station Assembly QTY Valve Caution Station Assembly Ball Drip Valve, ½" Adhesive Pad Angle Valve, " Ball Valve, ¼" NPTF x ¼" NPTM Check Valve, ¼" NPTM x ¼" NPTF Check Valve, Horizontal Swing, ½" NPT Check Valve, Horizontal Swing, " NPT Check Valve, Inline Poppet, ¼" Compression Connector, / 8" ID Tube x ¼" NPT Compression Connector, Elbow / 8" ID Tube x ¼" NPT Connector, / 8" ID Tube x ½" NPT Connector, Elbow, / 8" ID Tube x ¼" NPT Copper Tubing, / 8" OD x ft. Item Part No. No. Galvanized Black Pipe Description QTY Drain Cup, PVC Drain Hose Clip Elbow, ¼" Elbow, ¾" Elbow, " Elbow, " Flex Line, ½" Globe Valve, ¼" Globe Valve, ½" Nipple ¼" x ½" Nipple ¼" x ½" Nipple ¼" x " Nipple ¼" x 6" Nipple ½" x ½" Nipple ½" x " Nipple ½" x " Nipple ½" x ½" Nipple ¾" x Close Nipple " x ½" Nipple " x 6" Nipple " x Close Nipple " x ½" Nipple " x Close Pipe Cross, ½" PVC Tubing, 8" / ID x 6 ft Reducer Bushing, ¾" x ¼" Reducer Bushing, ¾" x ½" Reducer Bushing, " Spigot x " NPTF, PVC Retaining Tie Square Head Plug, ¼" Square Head Plug, ½" Square Head Plug, ¾" Strainer, ¼" Tee, ½" Tee, ½" x ¼" x ½" Tee, ½" x ½" x ¼" Tee, ¾" Tee, ¾" x ½" x ½" Tee, " x " x " Union, ½" Valve, -way, ¼" Water Pressure Gauge (0-00 psi) Hose Clamp Deluge Valve Nameplate 0.

11 . Fig. 5

12 Dry Pilot Line Trim Dry pilot line operation is used in areas which are subject to freezing conditions or to obtain installed sprinkler heights and pipe lengths greater than allowed for wet pilot line trim. Dry pilot operation uses a pilot line of closed sprinklers (Model F-FTR) containing air under pressure located in the area to be protected. This pressurized line is connected to a Model LP Dry Pilot Line Actuator. The dry pilot line actuator functions very much like a miniature dry pipe valve. In areas where moisture-laden air could cause freezing or other problems in the dry pilot line, the use of a cylinder of dry compressed gas such as nitrogen is suggested. Approved gas handling regulators and connections are then recommended. When one of the closed sprinklers on the dry pilot line actuates, the air pressure is reduced, thus opening the Model LP Dry Pilot Line Actuator, which releases the Deluge Valve. NFPA 7 or the Authority Having Jurisdiction should be consulted for spacing and elevation requirements of the pilot line sprinklers. The Dry Pilot Line Trim, shown in Figures 7 and 8, includes gauges to read the air and water pressure, a low air pressure switch, a pressure relief valve, a Model LP Dry Pilot Line Actuator, and connections for the dry pilot line of detectors. Dry Pilot Line Trim installation on Model DDX Deluge Valves uses eight tapped openings for trim connections. Each opening and its function are indicated on Fig. 7 and Fig. 8. Using Fig. 7 and Fig. 8 as reference, the recommended trim installation is as follows:. Install ½ nipple (#9, Fig. 7 or #4, Fig. 8) in tapped opening marked TEST. Note: If interference occurs between the supply gauge and the control valve, the /4 plug (#57, Fig. 7 or #58, Fig. 8) in the opening marked SUPPLY may be swapped with: the /4 nipple (#7, Fig. 7), angle valve (#, Fig. 7) and gauge (#7, Fig. 7) for the (50mm), -/ (65mm), 76mm and (80mm) valve sizes; /4 nipple (#7, Fig. 8), /4 elbow (#7, Fig. 8), /4 nipple (#8, Fig. 8), -way valve (#69, Fig. 8) and the gauge (#7, Fig. 8) for the 4 (00mm), 65mm and 6 (50mm) valve sizes; /4 nipple (#8, Fig. 8), -way valve (#69, Fig. 8) and the gauge (#7, Fig. 8) for the 8 (00mm) valve size, in the trim installed in the opening marked TEST.. Install ½ nipple (#4, Fig. 7 or #9, Fig. 8) in tapped opening marked ALARM and connect balance of this trim line.. Install ¼ plug (#57, Fig. 7 or #58, Fig. 8) in tapped opening marked SUPPLY. Note: If interference occurs between the supply gauge and the control valve, the /4 plug (#57, Fig. 7 or #58, Fig. 8) in the opening marked SUPPLY may be swapped with: the /4 nipple (#7, Fig. 7), angle valve (#, Fig. 7) and gauge (#7, Fig. 7) for the (50mm), -/ (65mm), 76mm and (80mm) valve sizes; /4 nipple (#7, Fig. 8), /4 elbow (#7, Fig. 8), /4 nipple (#8, Fig. 8), -way valve (#69, Fig. 8) and the gauge (#7, Fig. 8) for the 4 (00mm), 65mm and 6 (50mm) valve sizes; /4 nipple (#8, Fig. 8), -way valve (#69, Fig. 8) and the gauge (#7, Fig. 8) for the 8 (00mm) valve size, in. the trim installed in the opening marked TEST. 4. Install ½ nipple (#8, Fig. 7 or #9, Fig. 8) in tapped opening marked OUT and connect balance of this trim line. 5. Install ¼ inline check valve (#8, Fig. 7 or #7, Fig. 8) in tapped opening marked IN and connect balance of this trim line. Caution: Over tightening check valve can cause a restriction in flow that may prevent the valve from setting up. 6. Install ¼ Nipple (#47, Fig. 7) or nipple (#48, Fig. 8) in tapped drain opening and connect balance of this trim line. 7. Install ¾ x ¼ reducing bushing (#5, Fig. 7 or #5, Fig. 8) in the lower-most tapped opening at the rear of the Deluge Valve and connect the balance of this trim line. 8. Install ¾ pipe plug (#59, Fig. 7 or #60, Fig. 8) in the upper-most tapped opening at the rear of the Deluge Valve. Connect the air supply to the air inlet side of the Model LP Dry Pilot Line Actuator as shown in Fig. 7 or Fig. 8. Table A specifies the air pressure to be used in a dry pilot line. The level of air pressure is adjusted by removing the cap nut on the end of the Relief Valve (#55, Fig. 7 or #56, Fig. 8) and turning the now exposed slotted adjusting screw clockwise to increase pressure or counterclockwise to reduce it. Replace the cap nut after the correct pressure setting has been made at 5 psi above the maximum pilot line pressure required by Table A. An appropriate automatic pressure maintenance device must be used to safeguard against the Deluge Valve tripping due to air pressure leaks in the dry pilot line. See Bulletin 54 for pressure maintenance device information. Install the dry pilot line as required. Wire the low air pressure switch (#5, Fig. 7 or #5, Fig. 8) to an annunciating device or control panel. This low air pressure switch should be set to open at an air pressure which is slightly lower than the Not Less Than values found in Table A. Table A Water Pressure psi (bar) Pneumatic Pressure to be Pumped into Sprinkler System psi (bar) Maximum Not Les Than Not More Than 0 (.4) 0 (.7) 4 (.0) 50 (.4) (.8) 6 (.) 75 (5.) (.9) 7 (.) 00 (6.9) 5 (.) 9 (.) 5 (8.6) 6 (.) 0 (.4) 50 (0.) 7 (.) (.4) 75 (.) 8 (.) (.5) 00 (.8) 9 (.) (.6) 5 (5.5) (.4) 5 (.7) 50 (7.) (.5) 6 (.8) 75 (9.) (.6) 7 (.9) 00 (0.7) 4 (.7) 8 (.9) Note: During system set-up, a higher pneumatic pressure may be required in order to properly set the Model LP Dry Pilot Line Actuator.

13 Fig. 6 Model LP Dry Pilot Line Actuator Parts List P/N Item No. Part No. Description Qty. Required Lower Housing Upper Housing Seat Diaphragm Facing Plate Assembly Diaphragm Washer Facing Plate Nut Seat O-Ring Bolt Compression Spring Maintenance Model LP Dry Pilot Line Actuator Refer to Figs. 6 & 4 If water constantly flows through the Model LP Dry Pilot Line Actuator and into the drain, there is a leak in the seal of the Actuator s seat.. Close the main valve controlling water supply (Fig. 4) to the Dry Pipe Valve and close off the air/nitrogen supply to the sprinkler system. Close valve A (Fig. 4).. Drop pressure in the system by opening the ¼ angle valve, valve H (Fig. 4), and remove the Actuator from the system.. Remove all six bolts (#9, Fig. 6) holding the Actuator together. Clean or replace the facing plate assembly (#5, Fig. 6), seat (#, Fig. 6) and seat o-ring (#8, Fig. 6). 4. Reassemble the Actuator, using a torque of 8 ft-lbs on the facing plate nut (#7, Fig. 6) and ft-lbs on the six bolts (#9, Fig. 6). Use a cross-tightening pattern. Reinstall the Actuator. Set up the Model DDX Deluge Valve as per the section Resetting Model DDX Deluge Valve System..

14 Small DDX Dry Pilot Line Trim (Refer to Fig. 7) Item No. 4 5 Part No. Galvanized Black Pipe G G G G G0500 7G Description Valve Assembly, " (50mm) - For " Assembly Only Valve Assembly, ½" (65mm) - For ½" Assembly Only Valve Assembly, 76mm - For 76mm Assembly Only Valve Assembly, " (80mm) - For " Assembly Only Butterfly Valve, " - For " Assembly Only Butterfly Valve, ½" - For ½" Assembly Only Butterfly Valve, " - For " Assembly Only Rigid Coupling, " - For " Assembly Only Rigid Coupling, ½" - For ½" Assembly Only Rigid Coupling, " - For " Assembly Only Outlet Spool, " - For " Assembly Only Outlet Spool, ½" - For ½" Assembly Only Outlet Spool, " - For " Assembly Only Pressure Switch (EPS40-) (UL/FM) QTY. Pressure Switch (EPSA40-) (ULC) Model LP Pilot Line Actuator Manual Emergency Station Assembly Valve Caution Station Assembly Ball Drip Valve, ½" Adhesive Pad Angle Valve, ¼" Angle Valve, ¼" Ball Valve, ¼" NPTF x ¼" NPTM Ball Valve, ½" Check Valve, ¼" NPTM x ¼" NPTF Check Valve, Horizontal Swing, ½" NPT Check Valve, Horizontal Swing, " NPT Check Valve, Inline Poppet, ¼" Compression Connector, / 8" ID Tube x ¼" NPT Compression Connector, Elbow / 8" ID Tube x ¼" NPT Connector, / 8" ID Tube x ½" NPT Connector, Elbow, / 8" ID Tube x ¼" NPT Connector, Elbow, / 8" ID Tube x ½" NPT Item No. Part No. Galvanized Black Pipe Description QTY Copper Tubing, 8" / OD x ft Deluge Valve Nameplate Drain Cup, PVC Drain Hose Clip Elbow, ¼" Elbow, ½" Elbow, " Elbow, ¼" Flex Line, ½" Globe Valve, ¼" Globe Valve, ½" Nipple ¼" x ½" Nipple ¼" x " Nipple ¼" x 4" Nipple ½" x ½" Nipple ½" x " Nipple ½" x ½" Nipple ½" x " Nipple ½" x Close Nipple ¾" x " Nipple " x " Nipple " x Close Nipple ¼" x " Nipple ¼" x 4" Nipple ¼" x Close Pipe Cross, ½" PVC Tubing, 8" / ID x 6 ft Reducer Bushing, ½" x ¼" Reducer Bushing, ¾" x ¼" Reducer Bushing, ¾" x ½" Reducer Bushing, " Spigot x " NPTF, PVC Relief Valve, ½" NPT, psi Retaining Tie Square Head Plug, ¼" Square Head Plug, ½" Square Head Plug, ¾" Strainer, ¼" Street Elbow, ½" Tee, ½" Tee, ½" x ¼" x ½" Tee, ½" x ½" x ¼" Tee, ¾" Tee, ¾" x ½" x ½" Tee, ¼" x ¼" x " Union, ½" Valve, -way, ¼" Air Pressure Gauge (0-80 psi) Water Pressure Gauge (0-00 psi) Hose Clamp 4.

15 5. Fig. 7

16 Large DDX Dry Pilot Line Trim (Refer to Fig. 8) Item No. 4 5 Part No. Galvanized Black Pipe G G G G G0500 7G Description Valve Assembly, 4 (00mm) - For 4 Assembly Only Valve Assembly, 6 (50mm) - For 6 Assembly Only Valve Assembly, 65mm - For 65mm Assembly Only Valve Assembly, 8 (00mm) - For 8 Assembly Only Butterfly Valve, 4 - For 4 Assembly Only Butterfly Valve, 6 - For 6 Assembly Only Butterfly Valve, 8 - For 8 Assembly Only Rigid Coupling, 4 - For 4 Assembly Only Rigid Coupling, 6 - For 6 Assembly Only Rigid Coupling, 8 - For 8 Assembly Only Outlet Spool, 4 - For 4 Assembly Only Outlet Spool, 6 - For 6 Assembly Only Outlet Spool, 8 - For 8 Assembly Only Pressure Switch (EPS40-) (UL/FM) QTY. Pressure Switch (EPSA40-) (ULC) Model LP Pilot Line Actuator Manual Emergency Station Assembly Valve Caution Station Assembly Ball Drip Valve, ½ Adhesive Pad Angle Valve, Ball Valve, ¼ NPTF x ¼ NPTM Ball Valve, ½ Check Valve, ¼ NPTM x ¼ NPTF Check Valve, Horizontal Swing, ½ NPT Check Valve, Horizontal Swing, NPT Check Valve, Inline Poppet, ¼ Compression Connector, / 8 ID Tube x ¼ NPT Compression Connector, Elbow / 8 ID Tube x ¼ NPT Connector, / 8 ID Tube x ½ NPT Connector, Elbow, / 8 ID Tube x ¼ NPT Connector, Elbow, / 8 ID Tube x ½ NPT Item No. Part No. Galvanized Black Pipe Description QTY Copper Tubing, 8 / OD x ft Deluge Valve Nameplate Drain Cup, PVC Drain Hose Clip Elbow, ¼ Elbow, ½ Elbow, ¾ Elbow, Elbow, Flex Line, ½ Globe Valve, ¼ Globe Valve, ½ Nipple ¼ x ½ Nipple ¼ x ½ Nipple ¼ x Nipple ¼ x Nipple ½ x ½ Nipple ½ x Nipple ½ x ½ Nipple ½ x Nipple ½ x ½ Nipple ¾ x Close Nipple x ½ Nipple x Nipple x Close Nipple x ½ Nipple x Close Pipe Cross, ½ PVC Tubing, 8 / ID x 6 ft Reducer Bushing, ½ x ¼ Reducer Bushing, ¾ x ¼ Reducer Bushing, ¾ x ½ Reducer Bushing, Spigot x NPTF, PVC Relief Valve, ½ NPT, psi Retaining Tie Square Head Plug, ¼ Square Head Plug, ½ Square Head Plug, ¾ Strainer, ¼ Tee, ½ Tee, ½ x ¼ x ½ Tee, ½ x ½ x ¼ Tee, ¾ Tee, ¾ x ½ x ½ Tee, x x Union, ½ Valve, -way, ¼ Air Pressure Gauge (0-80 psi) Water Pressure Gauge (0-00 psi) Hose Clamp 6.

17 7. Fig. 8

18 Electric Actuation Trim Electric Actuation trim (see Figures 0 and ) combines a normally closed/powered-open solenoid valve with the Wet Pilot Trim for releasing the Deluge Valve. The solenoid valve used in the assembly is available in both a 75 psi (, bar) or 00 psi (0,7 bar) rating. Details on the electrical portion of this trim can be found in Reliable Bulletin 700, which describes Deluge and Preaction Systems. Caution: Repairs or disassembly of the solenoid valve should only be done by a trained technician. An improperly repaired or partially assembled solenoid valve could result in failure of the valve to operate. Electric Actuation Trim installation on Model DDX Deluge Valves uses eight tapped openings for trim connections. Each opening and its function are indicated on Fig. 0 or Fig.. Using Fig. 0 or Fig. as reference, the recommended trim installation is as follows:. Install ½ nipple (#5, Fig. 0 or #9, Fig. ) in tapped opening marked TEST. Note: If interference occurs between the supply gauge and the control valve, the /4 plug (#50, Fig. 0 or #5, Fig. ) in the opening marked SUPPLY may be swapped with: the /4 nipple (#, Fig. 0), angle valve (#0, Fig. 0) and gauge (#6, Fig. 0) for the (50mm), -/ (65mm), 76mm and (80mm) valve sizes; /4 nipple (#4, Fig. ), /4 elbow (#5, Fig. ), /4 nipple (#5, Fig. ), -way valve (#6, Fig. ) and the gauge (#64, Fig. ) for the 4 (00mm), 65mm and 6 (50mm) valve sizes; /4 nipple (#5, Fig. ), -way valve (#6, Fig. ) and the gauge (#64, Fig. ) for the 8 (00mm) valve size, in the trim installed in the opening marked TEST.. Install ½ nipple (#7, Fig. 0 or #6, Fig. ) in tapped opening marked ALARM and connect balance of this trim line.. Install ¼ plug (#50, Fig. 0 or #5, Fig. ) in tapped opening marked SUPPLY. Note: If interference occurs between the supply gauge and the control valve, the /4 plug (#50, Fig. 0 or #5, Fig. ) in the opening marked SUPPLY may be swapped with: the /4 nipple (#, Fig. 0), angle valve (#0, Fig. 0) and gauge (#6, Fig. 0) for the (50mm), -/ (65mm), 76mm and (80mm) valve sizes; /4 nipple (#4, Fig. ), /4 elbow (#5, Fig. ), /4 nipple (#5, Fig. ), -way valve (#6, Fig. ) and the gauge (#64, Fig. ) for the 4 (00mm), 65mm and 6 (50mm) valve sizes; /4 nipple (#5, Fig. ), -way valve (#6, Fig. ) and the gauge (#64, Fig. ) for the 8 (00mm) valve size, in the trim installed in the opening marked TEST. 4. Install ½ nipple (#4, Fig. 0 or #6, Fig. ) in tapped opening marked OUT and connect balance of this trim line. 5. Install ¼ inline check valve (#6, Fig. 0 or #5, Fig. ) in tapped opening marked IN and connect balance of this trim line. Supply line must be connected to the inlet of the control valve for each Deluge Valve as shown. Caution: Over tightening check valve can cause a restriction in flow that may prevent the valve from setting Fig. 9 up. 6. Install ¼ Nipple (#4, Fig. 0) or nipple (#44, Fig. ) in tapped drain opening and connect balance of this trim line. 7. Install ¾ x ¼ reducing bushing (#46, Fig. 0 or #48, Fig. ) in the lower-most tapped opening at the rear of the Deluge Valve and connect the balance of this trim line. 8. Install ¾ pipe plug (#5, Fig. 0 or #54, Fig. ) in the upper-most tapped opening at the rear of the Deluge Valve Maintenance Reliable Deluge Valves and associated equipment shall periodically be given a thorough inspection and test. NFPA 5 provides minimum requirements for inspection, testing and maintenance. The Deluge Valve should be tested, operated, cleaned, and inspected at least annually and parts replaced as required. 8.

19 Small DDX Electric Actuation Trim (Refer to Fig. 0) Item No. 4 5 Part No. Galvanized Black Pipe G G G G G0500 7G Description Valve Assembly, " (50mm) - For " Assembly Only Valve Assembly, ½" (65mm) - For ½" Assembly Only Valve Assembly, 76mm - For 76mm Assembly Only Valve Assembly, " (80mm) - For " Assembly Only Butterfly Valve, " - For " Assembly Only Butterfly Valve, ½" - For ½" Assembly Only Butterfly Valve, " - For " Assembly Only Rigid Coupling, " - For " Assembly Only Rigid Coupling, ½" - For ½" Assembly Only Rigid Coupling, " - For " Assembly Only Outlet Spool, " - For " Assembly Only Outlet Spool, ½" - For ½" Assembly Only Outlet Spool, " - For " Assembly Only Solenoid Valve, 75 psi Rated Solenoid Valve, 00 psi Rated Manual Emergency Station Assembly QTY Valve Caution Station Assembly Ball Drip Valve, ½" Adhesive Pad Angle Valve, ¼" Angle Valve, ¼" Ball Valve, ¼" NPTF x ¼" NPTM Check Valve, ¼" NPTM x ¼" NPTF Check Valve, Horizontal Swing, ½" NPT Check Valve, Horizontal Swing, " NPT Check Valve, Inline Poppet, ¼" Compression Connector, / 8" ID Tube x ¼" NPT Compression Connector, Elbow / 8" ID Tube x ¼" NPT Connector, / 8" ID Tube x ½" NPT Connector, Elbow, / 8" ID Tube x ¼" NPT Item No. Part No. Galvanized Black Pipe Description QTY Connector, Elbow, " ID Tube x ½" NPT Copper Tubing, " OD x ft Deluge Valve Nameplate Drain Cup, PVC Drain Hose Clip Elbow, ¼" Elbow, " Elbow, ¼" Flex Line, ½" Globe Valve, ¼" Globe Valve, ½" Nipple ¼" x ½" Nipple ¼" x 4" Nipple ½" x ½" Nipple ½" x " Nipple ½" x " Nipple ½" x Close Nipple ¾" x " Nipple " x " Nipple " x Close Nipple ¼" x " Nipple ¼" x 4" Nipple ¼" x Close Pipe Cross, ½" PVC Tubing, 8" / ID x 6 ft Reducer Bushing, ¾" x ¼" Reducer Bushing, ¾" x ½" Reducer Bushing, " Spigot x " NPTF, PVC Retaining Tie Square Head Plug, ¼" Square Head Plug, ½" Square Head Plug, ¾" Strainer, ¼" Street Elbow, ½" Tee, ½" Tee, ½" x ¼" x ½" Tee, ½" x ½" x ¼" Tee, ¾" Tee, ¾" x ½" x ½" Tee, ¼" x ¼" x " Union, ½" Valve, -way, ¼" Water Pressure Gauge (0-00 psi) Hose Clamp 9.

20 0. Fig. 0

21 Large DDX Electric Actuation Trim (Refer to Fig. ) Item No. 4 5 Part No. Galvanized Black Pipe G G G G G0500 7G Description Valve Assembly, 4" (00mm) - For 4" Assembly Only Valve Assembly, 6" (50mm) - For 6" Assembly Only Valve Assembly, 65mm - For 65mm Assembly Only Valve Assembly, 8" (00mm) - For 8" Assembly Only Butterfly Valve, 4" - For 4" Assembly Only Butterfly Valve, 6" - For 6" Assembly Only Butterfly Valve, 8" - For 8" Assembly Only Rigid Coupling, 4" - For 4" Assembly Only Rigid Coupling, 6" - For 6" Assembly Only Rigid Coupling, 8" - For 8" Assembly Only Outlet Spool, 4" - For 4" Assembly Only Outlet Spool, 6" - For 6" Assembly Only Outlet Spool, 8" - For 8" Assembly Only Solenoid Valve, 75 psi Rated Solenoid Valve, 00 psi Rated Manual Emergency Station Assembly QTY Valve Caution Station Assembly Ball Drip Valve, ½" Adhesive Pad Angle Valve, " Ball Valve, ¼" NPTF x ¼" NPTM Check Valve, ¼" NPTM x ¼" NPTF Check Valve, Horizontal Swing, ½" NPT Check Valve, Horizontal Swing, " NPT Check Valve, Inline Poppet, ¼" Compression Connector, / 8" ID Tube x ¼" NPT Compression Connector, Elbow / 8" ID Tube x ¼" NPT Connector, / 8" ID Tube x ½" NPT Connector, Elbow, / 8" ID Tube x ¼" NPT Connector, Elbow, / 8" ID Tube x ½" NPT Item Part No. No. Galvanized Black Pipe Description QTY Copper Tubing, 8" / OD x ft Deluge Valve Nameplate Drain Cup, PVC Drain Hose Clip Elbow, ¼" Elbow, ¾" Elbow, " Elbow, " Flex Line, ½" Globe Valve, ¼" Globe Valve, ½" Nipple ¼" x ½" Nipple ¼" x ½" Nipple ¼" x " Nipple ¼" x 6" Nipple ½" x ½" Nipple ½" x " Nipple ½" x " Nipple ½" x ½" Nipple ¾" x Close Nipple " x ½" Nipple " x 6" Nipple " x Close Nipple " x ½" Nipple " x Close Pipe Cross, ½" PVC Tubing, 8" / ID x 6 ft Reducer Bushing, ¾" x ¼" Reducer Bushing, ¾" x ½" Reducer Bushing, " Spigot x " NPTF, PVC Retaining Tie Square Head Plug, ¼" Square Head Plug, ½" Square Head Plug, ¾" Strainer, ¼" Tee, ½" Tee, ½" x ¼" x ½" Tee, ½" x ½" x ¼" Tee, ¾" Tee, ¾" x ½" x ½" Tee, " x " x " Union, ½" Valve, -way, ¼" Water Pressure Gauge (0-00 psi) Hose Clamp.

22 . Fig.

23 . Fig.

24 Model DDX (Screw-In Seat Configuration) Deluge Valves Parts List (Refer to Fig. ) Item Part No. No. " (50mm) ½" (65mm) 76mm " (80mm) 4" (00mm) 65mm 6" (50mm) 8" (00mm) Part Description QTY. Material Valve Body Groove/Groove Valve Body Flange/Groove Ductile Iron Valve Body Flange/Flange O-ring (Mounting Ring) Buna-N Pushrod Cover Assembly Ductile Iron & Brass C Hex Bolt ½"- x ¼" 6 Zinc Plated Steel Hex Bolt ½"- x ½" 6 Zinc Plated Steel Hex Bolt 5 /8"- x ¾" 6 Zinc Plated Steel Hex Bolt 5 /8"- x " 8 Zinc Plated Steel Mounting Ring Stainless Steel CF8 or CF8M Clapper Stainless Steel CF8 or CF8M Access Cover Ductile Iron Seal Assembly Stainless Steel 04 & EPDM Access Cover Gasket Buna-N or Neoprene Stainless Steel Bumpstop Assembly UNS S600 & EPDM Pushrod Guide Acetal Reset Shaft Brass UNS C Reset Housing Brass UNS C Reset Knob Aluminum Lever Stainless Steel UNS S Striker Aluminum Bronze C Piston Stainless Steel CF8M Diaphragm EPDM & Polyester Retaining Ring, /8" Shaft, Lever Pin Retaining Ring, ½" Shaft, Lever Pin Retaining Ring, 5 /8" Shaft, Lever Pin Stainless Steel 5-7 or Retaining Ring, ¾" Shaft, Lever Pin Retaining Ring, /8" Shaft, Hinge Pin Retaining Ring, ½" Shaft, Hinge Pin Stainless Steel 5-7 or Retaining Ring, ¾" Shaft, Hinge Pin O-Ring, Reset Housing ID Buna-N O-Ring, Reset Housing & Pushrod Guide OD Buna-N O-Ring, Pushrod Guide ID Buna-N O-Ring, Upper Seat Buna-N O-Ring, Lower Seat Buna-N Pushrod Stainless Steel UNS S Socket Head Screw, ¼"-0 x 5 /8" 6 Steel Flat Head Socket Cap Screw /8"-6 x ¾" Steel Socket Head Screw #6- x ½" Stainless Steel Socket Head Screw #0- x " Stainless Steel UNS S Seat Stainless Steel CF8M Stainless Steel UNS S0400 Hinge Pin Stainless Steel UNS S Stainless Steel UNS S7400 Lever Pin Stainless Steel UNS S Clapper Spacer Teflon or Acetal Stainless Steel UNS S0400 Lever Spring Stainless Steel UNS S Piston/ Reset Spring Stainless Steel UNS S Spring Lock Washer, #6 Stainless Steel Spring Lock Washer, #0 Stainless Steel UNS S Flat Head Socket Cap Screw ¼"-0 x ½" Stainless Steel Flat Head Socket Cap Screw ¼"-0 x ½" Stainless Steel UNS S Flat Head Socket Cap Screw ½"- x ¾" Stainless Steel UNS S Plug, ½" NPT Steel Knob Caution Label (Not Shown) Polystyrene Ball Chain, /8" (Not Shown) (Length is in Inches) 6 Nickel Plated Brass Clamping Link, Ball Chain (Not Shown) Nickel Plated Brass O-Ring Grease, Duponttm Krytox GPL-05 A/R Krytox 4.

25 5. Fig.

26 Model DDX (Drop-In Seat Configuration) Deluge Valves Parts List (Refer to Fig. ) Item Part No. No. 4" (00mm) 65mm 6" (50mm) Part Description QTY. Material Valve Body Ductile Iron Seat Brass UNS C Clapper Brass UNS C Access Cover Ductile Iron Seal Assembly Stainless Steel 04 & EPDM Access Cover Gasket Buna-N or Neoprene Lever Stainless Steel UNS S Pushrod Cover Assembly Ductile Iron & Brass UNS C O-Ring, Pushrod Guide ID Buna-N O-Ring, Reset Housing ID Buna-N O-Ring, Upper Seat Buna-N O-Ring, Lower Seat Buna-N O-Ring, Reset Housing OD Buna-N Clapper Gasket Buna-N or Neoprene Hinge Pin Stainless Steel UNS S Lever Pin Stainless Steel UNS S Threaded Stud, #0- x ¾" Stainless Steel Locking Pin (not shown) Stainless Steel UNS S Piston Stainless Steel CF8M Socket Plug /8-8 NPT (not shown) Steel Pushrod Stainless Steel UNS S Pushrod Guide Acetal Retaining Ring, /" Shaft Button Head Screw #0- x /8" Stainless Steel 5-7 or Hex Washer Head Screw #0- x /8" 4 Stainless Steel Hex Cap Screw ½"- x ½" Hex Cap Screw 5 /8"- x ¾" 6 Zinc Plated Steel Spring Lock Washer, #0 Stainless Steel UNS S Flat Head Socket Cap Screw /8"-6 x ¾" Steel Socket Head Screw #0- x " Stainless Steel UNS S Socket Head Screw, ¼"-0 x 5 /8" 6 Steel Reset Shaft Brass UNS C Lever Spring Stainless Steel UNS S Piston/ Reset Spring Stainless Steel UNS S Clapper Spacer Teflon Diaphragm EPDM & Polyester Bumper Disc SBR Rubber Reset Housing Brass UNS C Reset Knob Aluminum O-Ring Grease, Duponttm Krytox GPL-05 A/R Krytox Knob Caution Label (Not Shown) Polystyrene Ball Chain, /8" (Not Shown) (Length is in Inches) 6 Nickel Plated Brass Clamping Link, Ball Chain (Not Shown) Nickel Plated Brass 6.

27 Resetting Model DDX Deluge Valve Systems Refer to Figs. 7, 8,, & 4.. Close the valve controlling water supply to the Deluge Valve and close valve A (Fig. 4).. Open main drain valve B (Fig. 4) and drain system.. Open all drain valves and vents at low points throughout the system, closing them when flow of water has stopped. Open valve D (Fig. 4). 4. With valve G (Fig. 4) open, push in the plunger of ball drip valve E (Fig. 4), forcing the ball from its seat to verify that there is atmospheric pressure inside the main valve chamber. 5. Push in and rotate external reset knob (#4, Fig. or #8, Fig. ) clockwise, until you hear a distinct noise indicating that the clapper has reset. 6. Inspect and replace any portion of the detection system subjected to fire conditions. 7. Open valve A (Fig. 4) and allow water to fill the push rod chamber. Close valve D (Fig. 4). 8. Bleed all air from the actuation piping. A. Wet Pilot Trim bleed the entire wet pilot line until all air is removed at the most remote sprinkler. B. Electric Actuation Trim open the solenoid valve by operating a detector or an electric manual emergency station. While water is flowing through the solenoid valve, cause it to close. Refer to Bulletin 700, Special Hazards & Special Systems for details. C. Dry Pilot Trim open valve D (Fig. 4) allowing water to flow through the pilot line actuator. When all air has been expelled from the release line, and there is a solid flow of water into the drain cup J (Fig. 4), apply compressed air or nitrogen through the pressure maintenance device to close the pilot line actuator. Subsequently, close valve D (Fig. 4) and adjust the air or nitrogen pressure to the appropriate value in Table A as indicated on air pressure gauge (#7, Fig. 7 or #7, Fig. 8). 9. Check that valves D (Fig. 4) and F (Fig. 4) are closed and that valve G is open (Fig. 4). Open slightly the valve controlling water supply to the Deluge Valve, closing the main drain valve B (Fig. 4) when water flows. Observe if water leaks through ball drip valve E (Fig. 4), into drain cup J (Fig. 4), (Be sure that valve G (Fig. 4) is open). If no leak occurs the water seat is tight. Open slowly but fully the valve controlling water supply to the Deluge Valve. Verify that it is fully opened and properly monitored. 0. Valve A (Fig. 4) must remain open when the Deluge Valve has been reset, to maintain water pressure in the push rod chamber.. Verify that the Model B Manual Emergency Station, valve D (Fig. 4) is sealed in the OFF position with the appropriate nylon tie. Inspection and Testing Refer to Figs., & 4.. Water supply be sure the valves controlling water supply to the Deluge Valve are opened fully and properly monitored.. Alarm line be sure that valve G (Fig. 4) is opened and remains in this position.. Other trimming valves check that valve A (Fig. 4) is open, as well as all of the pressure gauge s ¼ -way valves. Valves D, F, & H (Fig. 4) should be closed. 4. Ball drip valve E (Fig. 4) Make sure valve G (Fig. 4) is open. Push in on the plunger to be sure ball check is off its seat. If no water appears, the Deluge Valve s water seat is tight. Inspect the bleed hole (see Fig. of Fig. ) on the underside of the push rod chamber for leakage. 5. Dry pilot trim check air gauge pressure for conformance to Table A. 6. Releasing device check outlet of the releasing device (i.e., the dry pilot line actuator, solenoid valve, or the hydraulic manual emergency station) for leakage. Also verify that tubing drain lines from releasing devices are not pinched or crushed which could prevent proper releasing of the Deluge Valve. 7. Testing alarms Make sure valve G (Fig. 4) is open. Open valve F (Fig. 4) permitting water from the supply to flow to the electric sprinkler alarm switch and to the mechanical sprinkler alarm (water motor). After testing, close this valve securely. Push in on the plunger of ball drip valve E (Fig. 4) until all of the water has drained from the alarm line. 8. Operation test Open the Model B Manual Emergency Station, valve D (Fig. 4). Note: An operational test will cause the Deluge Valve to open and flow water into the sprinkler system. 9. Secure the Model B Manual Emergency Station, valve D (Fig. 4), in the OFF position with nylon tie after Deluge Valve is reset. Testing Detection System Without Operating Deluge Valve Refer to Figs. 7, 8 & 4.. Close the valve controlling water supply to Deluge Valve and open the main drain valve B (Fig. 4).. Verify that valve A (Fig. 4) is open, allowing water to enter the push rod chamber.. Operate detection system A. Wet Pilot Trim open Model B Manual Emergency Station, valve D (Fig. 4). B. Dry Pilot Trim directly above the Model LP Dry Pilot Line Actuator, remove the ¼ pipe plug (#58, Fig. 7 or #59, Fig. 8) and open the ¼ three-way valve (#70, Fig. 7 or #70, Fig. 8). C. Electric Actuation refer to Bulletin Operation of the detection system must result in a sudden drop of water pressure in the push rod chamber. 5. Reset detection system reverse operations performed in step three above and then proceed according to the directions listed in the Resetting Model DDX Deluge Valve Systems section of this bulletin for resetting the Deluge Valve. 7.

28 Draining Excess/Condensate Water From System Refer to Fig. 4. Close the valve controlling water supply to Deluge Valve. Also close valve A and open main drain valve B.. Open condensate drain valve H until all water has drained. Close valve H.. Close main drain valve B. If system contains pressurized air, allow air pressure to come back up to specification (see table A). Open valve A and the valve controlling the water supply to the Deluge Valve. Maintenance Procedures - Model DDX Deluge Valve Refer to Figs. 7, 8,,, & 4.. Mechanical sprinkler alarm (water motor not shown) not operating: This is most likely caused by a clogged screen in the strainer of the water motor. Proceed as follows: Remove plug from the strainer. Remove and clean the screen. Replace the screen and the plug, and then tighten securely (Ref. Bulletin 6).. Leakage out of the ball drip valve E (Fig. 4). a. Water leakage due to water column in deluge systems: This condition can be caused by leakage past the system side of the Model DDX Deluge Valve s seal assembly (#8, Fig. or #5, Fig. ). Be sure that this surface is free of any type of debris. To eliminate leakage due to water column in a deluge system, refer to the section in this bulletin marked Draining Excess/Condensate Water From System. If the problem continues proceed to the following section. b. Leakage, air or water from the ball drip valve, E (Fig. 4): If system air is leaking out the ball drip valve, the problem is either damage to the airside of the Model DDX Deluge Valve s seal assembly (#8, Fig. or #5, Fig. ), seat (#9, Fig. or #, Fig. ), the upper seat o-ring(#, Fig. or #, Fig. ) or, on the 8 (00 mm) valve size only, the mounting ring o-ring (#, Fig. ). If supply water is leaking out the ball drip valve, the problem could be caused by damage to the Model DDX Deluge Valve s seal assembly (#8, Fig. or #5, Fig. ), seat (#9, Fig. or #, Fig. ), or lower seat O-ring (#4, Fig. or #, Fig. ). The following section provides instructions to correct both conditions: A) Shut down the valve controlling the water supply to the Deluge Valve and open the ¼ main drain valve on the (50mm), ½ (65mm), 76mm and (80mm) valve sizes or the main drain valve on the 4 (00mm), 65mm, 6 (50mm) and 8 (00mm) valve sizes, valve B (Fig. 4). Open the water column drain valve H (Fig. 4). Close the pushrod chamber supply valve A (Fig. 4) and open the Model B Manual Emergency Station, valve D (Fig. 4). B) Remove the Deluge Valve s front (handhold) cover (#7, Fig. or #4, Fig. ) and inspect the 8. seat (#9, Fig. or #, Fig. ), clapper (#6, Fig. or #, Fig. ), and seal assembly (#8, Fig. or #5, Fig. ) for damage. If inspection indicates damage to the seal assembly (#8, Fig. or #5, Fig. ), replace as follows: For Valve Sizes: (50mm), ½ (65mm), 76mm, (80mm), 8 (00mm) and 4 (00mm), 6 (50mm) & 65mm with Screw- In Seat only, Refer to Fig. 7, Fig. 8 & Fig. : Remove the bumpstop nuts (#0, Fig. ) and remove the seal assembly (#8, Fig. ). Install a new seal assembly (#8, Fig. ) and thread the bumpstop nuts (#0, Fig. ) onto the threaded studs of the seal assembly (#8, Fig. ) and tighten finger tight plus ¼ to ½ turn. If inspection indicates damage to the clapper (#6, Fig. ) only, then the clapper subassembly can be removed as follows: At the rear of the valve, disconnect the water column drain trim section starting with the elbow connector (#, Fig. 7 or #, Fig. 8). Then remove the ¼ globe valve (#, Fig. 7 or #, Fig. 8), followed by the ¾ x¼ reducing bushing (#5, Fig. 7 or #5, Fig. 8). Remove the retaining ring (condensate drain side for (50mm), ½ (65mm), (80mm), 76mm and 8 (00mm) valve sizes or hand hole cover side for 4 (00mm), 6 (50mm) and 65mm valve sizes) from the clapper hinge pin (#0, Fig. ) and push this pin through the hand hole opening (for (50mm), ½ (65mm), (80mm), 76mm and 8 (00mm) valve sizes or condensate drain side for 4 (00mm), 6 (50mm) and 65mm valve sizes) and remove the clapper subassembly. Replace the seal assembly as described previously. Inspect the clapper (#6, Fig. ) visually before reinstalling. Reinstall in the reverse order making sure the clapper spacers are in their proper position. If the seat (#9, Fig. ) is damaged or it is suspected that the leakage is through the lower O-ring (#4, Fig. ), the seat-clapper subassembly is easily removed as a unit as follows: Using Reliable P/N Seat Wrench for (50mm), ½ (65mm), 76mm and (80mm) valve sizes, Reliable P/N for 4 (00mm) valve size, Reliable P/N for the 6 (50mm) and 65mm valve sizes or Reliable P/N Seat Wrench for 8 (00mm) valve size, remove the seat by unscrewing. This will loosen the seatclapper-mounting ring subassembly. Reach into the valve and grasp the seat and remove it from the valve. Then remove the clappermounting ring subassembly from the valve. Visually examine all components of the seatclapper-mounting ring subassembly replacing any component that appears damaged. New O-rings (# & #4, Fig. and #, Fig. (8

29 (00mm) valve size only)) should always be used for reassembly. For Valve Sizes: 4 (00mm), 65mm, 6 (50mm) with Drop-In Seat Configuration only, Refer to Fig. 8 and Fig. : At the rear of the valve, disconnect the water column drain trim section starting with the elbow connector (#, Fig. 8). Then remove the ¼ angle globe (#, Fig. 8), followed by the ¾ x¼ reducing bushing (#5, Fig. 8). Remove the retaining ring (hand hole cover side) from the clapper hinge pin (#4, Fig. ) and push this pin through the condensate drain port and remove the clapper subassembly. Remove the four retaining screws (#4, Fig. ) holding the seal faceplate assembly (#5, Fig. ). Inspect the clapper (#, Fig. ) visually before installing. Apply a small amount of silicone based lubricant to the four retaining screws. Install a new seal faceplate assembly. Torque the retaining screws to approximately 40 inchpounds and reassemble. If the seat (#, Fig. ) is damaged or it is suspected that the leakage is through the lower o-ring (#, Fig. ), the seat-clapper subassembly is easily removed as a unit as follows: Using a 5/6 Allen wrench, remove the two /8 NPT pipe plugs (#9, (not shown) Fig. ) located on the side chamber side of the Model DDX deluge valve. The seat-clapper subassembly is retained by two locking pins (#7, (not shown) Fig. ). The centers of these pins have a ¼ -0 threaded hole. Remove the two locking pins by engaging them with a ¼ -0 screw and pulling them out (the two locking pins are not externally threaded, so turning them with the attached ¼ -0 screw or threaded rod is not recommended. A proven method is to use ¼ -0 threaded rod with a locknut on the unassembled end. Grab hold of the locknut with a pliers or vise-grips and tap the pliers or vise-grips in the direction away from the Deluge Valve. Doing so should pull the locking pins out of the Deluge Valve. With the clapper (#, Fig. ) in the closed position (not latched), dislodge the clapper-seat subassembly from the valve body by inserting two slotted screwdrivers under the lever and clapper mounting ears and pry up until the clapper-seat subassembly is free from its bore. Reach into the valve and grasp the clapper-seat subassembly from the sides. Making sure the clapper is in the closed position (see Fig. ), lift up and rotate the clapper-seat sub assembly clockwise 90 degrees so that the lever side of the assembly is facing up towards the outlet of the deluge valve. Next, rotate the clapper-seat sub assembly 90 degrees about the centerline of the valve so that the clapper is facing the hand hole open- ing and the lever is still facing the outlet of the deluge valve.. Then rotate the clapper-seat sub assembly 90 degrees, so that the clapper is now facing the outlet of the deluge valve and the lever is now facing the back of the valve. Pull the clapper-seat sub assembly out through the hand hole opening by the hinge pin side. Rotating the seat-clapper subassembly up as it is being removed will help it slide out more easily since the lever will prohibit it from sliding straight out. Visually examine all components of the clapper-seat subassembly replacing any component that appears damaged. New o- rings (#, Fig. ) should always be used for reassembly. Reassembly: For Valve Sizes: (50mm), ½ (65mm), 76mm, (80mm), 8 (00mm) and 4 (00mm), 6 (50mm) & 65mm with Screw- In Seat Configuration only, Refer to Fig. : Clean the bore of the valve body. Lubricate the bore with O-ring grease. Lubricate and install the O-rings (# & #4, Fig. ) onto the seat. Lubricate and install the mounting ring o-ring (#, Fig. ) into the body (8 (00mm) valve size only). Insert the clapper-mounting ring subassembly into the handhold opening of the Deluge Valve using caution to not damage or dislodge the mounting ring o-ring (#, Fig. ) (8 (00mm) valve size only). Align the mounting ring so that the Lever (#5, Fig. ) is near the pushrod (#5, Fig. ) and the mounting ring (#5, Fig. ) ears are between the tabs of the valve body (#, Fig. ). Insert the seat (#9, Fig. ) into the valve body (#, Fig. ) and through the clapper-mounting ring subassembly. Start to tread the seat (#9, Fig. ) into the body by hand, then tighten the seat (#9, Fig. ) with Reliable P/N Seat Wrench for (50mm), ½ (65mm), 76mm and (80mm) valve sizes, Reliable P/N Seat Wrench for 4 (00mm) valve size, Reliable P/N Seat Wrench for 6 (50mm and 65mm valve sizes or Reliable P/N Seat Wrench for 8 (00mm) valve size until it bottoms out on the mounting ring (#5, Fig. ).Verify that the seat-clappermounting ring subassembly is in the fully down position between the tabs of the body, and check to see that the lever (#5, Fig. ) lines up with the push rod (#5, Fig. ). Loosen and reassemble if necessary. Reassemble the handhold cover (#7, Fig. ) and set up the Model DDX Deluge Valve as per the section Resetting Model DDX Deluge Valve Systems. For Valve Sizes: 4 (00mm), 65mm, 6 (50mm) with Drop-In Seat Configuration only, Refer to Fig. : It is likely that the lower seat o-ring (#, Fig. ) 9.

30 has remained at the bottom of the Deluge Valve body s bore. Discard this o-ring and clean the bore. Lubricate the bore with o-ring grease and place the lower o-ring on the step at the bottom of the bore, verifying that it is in full contact with the bore. Lubricate the bottom step and upper o-ring (#, Fig. ) of the refurbished clapperseat subassembly. Insert the clapper-seat sub assembly into the hand hole opening, lever (#7, Fig. ) first and rotating the clapper-seat subassembly until the lever faces the outlet of the deluge valve. Next rotate the clapper-seat subassembly 90 degrees about the center axis of the valve until the bottom of the clapper-seat sub assembly faces the pushrod (#0, Fig. ). Then rotate the clapper-seat subassembly 90 degrees counterclockwise so that the clapper (#, Fig. ) is facing the outlet of the deluge valve and the lever (#7, Fig. ) is facing the pushrod (#0, Fig. ). Once the clapper seat subassembly is in this position simply slide the assembly into the bore of the valve, making sure it is straight to avoid binding of the seat in the bore. Slightly twisting the assembly will assist in getting the clapper-seat subassembly properly seated. Once it is verified that the clapper-seat sub assembly is in the fully down position and the lever (#7, Fig. ) is aligned with the pushrod (#0, Fig. ), clean and lubricate the two locking pins (#7, (not shown) Fig. ) with o-ring lubricant. Slide the two locking pins into the deluge valve body to lock the seat in place. Slightly twisting and pressing down on the clapper-seat subassembly will help the pins to slide in more easily. Then reinstall the /8 NPT pipe plugs (#9, (not shown) Fig. ). Reassemble the hand hole cover (#4, Fig. ) and set up the Model DDX Deluge Valve as per the section Resetting Model DDX Deluge Valve Systems.. Leakage out of the push rod chamber vent hole: A small bleed hole is located on the underside of the push rod chamber (see Fig. or Fig. ). If there is air or water leakage coming out of this hole, do the following: a) Shut down the valve controlling water supply to the Deluge Valve. Relieve the inlet pressure by opening the ¼ main drain valve on the (50mm), ½ (65mm), 76mm and (80mm) valve sizes or the main drain valve on the 4 (00mm), 65mm, 6 (50mm) and 8 (00mm) valve sizes, valve B (Fig. 4). Close valve A (Fig. 4) that supplies water to the push rod chamber, and open the Model B Manual Emergency Station, valve D (Fig. 4). b) Remove the trim at the unions nearest to the push rod chamber cover (#, Fig. or #8, Fig. ). c) Take the push rod chamber cover (#, Fig. or #8, Fig. ) off by removing the six retaining screws (#6, Fig. or #9, Fig. ). CONDITION ONE (Water coming out of the bleed hole): Water coming out of the bleed hole is caused by a leaking diaphragm (#8, Fig. or #4, Fig. ). Visually inspect the push rod chamber cover (#, Fig. or #8, Fig. ), piston (#7, Fig. or #8, Fig. and bore of the body (#, Fig. or #, Fig. ) to determine what could have damaged the diaphragm and correct. Install a new diaphragm. NOTE: The diaphragm has two different surfaces; it is not bi-directional. It will fail if installed backwards! Roll the diaphragm so that the smooth surface (the pressure side) conforms to the inside of the push rod chamber cover and reassemble the six retaining screws (#6, Fig. or #9, Fig. ) with an installation torque of 5 foot-pounds. Set up the Model DDX Deluge Valve as per the section Resetting Model DDX Deluge Valve Systems. CONDITION TWO (System Air coming out of the bleed hole): System air coming out of the bleed hole is caused by a defective O-ring assembled to the push rod guide (#, Fig. or #, Fig. ). Remove the piston-push rod subassembly, push rod spring (#4, Fig. or #, Fig. ), and push rod guide (#, Fig. or #, Fig. ). Verify by hand turning, that the push rod cannot be unscrewed from the piston. Replace all O-rings and the push rod guide (#, # and #, Fig. or #9, # and #, Fig.). The correct installation torque for the pushrod guide is 5 inch-pounds. CAUTION: Do not over tighten the push rod guide. Reassemble the components that were initially removed. Re-install the diaphragm (#8, Fig. or #4, Fig. ) if it appears to be in good shape, otherwise, replace it also. NOTE: The diaphragm has two different surfaces; it is not bidirectional. It will fail if installed backwards! Roll the diaphragm so that the smooth surface (the pressure side) conforms to the inside of the push rod chamber cover and reassemble the six retaining screws (#6, Fig. or #9, Fig. ) with an installation torque of 5 foot-pounds. Set up the Model DDX Deluge Valve as per the section Resetting Model DDX Deluge Valve Systems. 0.

31 Fig. 4.

32 Ordering Information Specify: Valve Model & Size Valve Size & End Connection (50mm) Grv/Grv ½ (65mm) Grv/Grv Valve Part Numbers Flange Type Color Reliable Part Number Black Red Black Red Black (80mm) Grv/Grv Red mm Grv/Grv Red (00mm) Grv/Grv 4 (00mm) Flg/Grv 4 (00mm) Flg/Flg 6 (68mm) Grv/Grv 6 (68mm) Flg/Grv Black Red ASME Class 50 Black ASME Class 50 Red ISO PN6 Red ASME Class 50 Black ASME Class 50 Red ISO PN6 Red Black Red ASME Class 50 Black ASME Class 50 Red ISO PN6 Red ASME Class 50 Black (68mm) Flg/Flg ASME Class 50 Red ISO PN6 Red mm Grv/Grv Red mm Flg/Grv 8 (00mm) Grv/Grv 8 (00mm) Flg/Flg ASME Class 50 Red ISO PN6 Red Black Red ASME Class 50 Black ASME Class 50 Red ISO PN6 Red

33 Trim Wet Pilot Trim, Dry Pilot Trim, or Electric Actuation Trim. Each trim set is available in individual parts, in time-saving, segmentally assembled kit forms, or fully assembled to the Model DDX Deluge Valve with or without a control valve). The Electric Actuation trim is available with a 75 psi (, bar) or 50 psi (7, bar) rated solenoid valve. Wet Pilot Line Deluge Valve Size & End Connection Flange Type (50mm) Grv/Grv ½ (65mm) Grv/Grv Color Trim Part Numbers Individual Parts (Model DDX Valve Sold Seperately) Trim Configurations Segmentally Assembled (Model DDX Valve Sold Seperately) Fully Assembled to Model DDX Valve w/o Control Valve Fully Assembled to Model DDX Valve w/ Control Valve Black Red 6505A A0000 Black Red A A500 Black (80mm) Grv/Grv Red 6505A A mm Grv/Grv Red 6505A760 4 (00mm) Grv/Grv 4 (00mm) Flg/Grv 4 (00mm) Flg/Flg 6 (68mm) Grv/Grv 6 (68mm) Flg/Grv Black Red 6505A A4000 ASME Class 50 Black ASME Class 50 Red 6505A40 ISO PN6 Red 6505A440 ASME Class 50 Black ASME Class 50 Red 6505A470 ISO PN6 Red 6505A480 Black Red 6505A A6000 ASME Class 50 Black ASME Class 50 Red 6505A ISO PN6 Red 6505A640 ASME Class 50 Black (68mm) Flg/Flg ASME Class 50 Red 6505A670 ISO PN6 Red 6505A680 65mm Grv/Grv Red 6505A650 65mm Flg/Grv 8 (00mm) Grv/Grv 8 (00mm) Flg/Flg ASME Class 50 Red 6505A660 ISO PN6 Red 6505A690 Black Red 6505A A8000 ASME Class 50 Black ASME Class 50 Red 6505A870 ISO PN6 Red 6505A880.

34 Dry Pilot Deluge UL/FM{ ULC Valve Size & End Connection Flange Type Color Trim Part Numbers Trim Configurations Individual Parts Segmentally Assembled (Model DDX Valve Sold (Model DDX Valve Seperately) Sold Seperately) Fully Assembled to Fully Assembled to Model DDX Valve Model DDX Valve w/o Control Valve w/ Control Valve (50mm) Grv/Grv ½ (65mm) Grv/Grv Black Black Red Red 6505A A A A505 (80mm) Grv/Grv Black Red 6505A A mm Grv/Grv Red 6505A7606 Black (00mm) Grv/Grv Red 6505A A4005 ASME Class 50 Black (00mm) Flg/Grv ASME Class 50 Red 6505A406 ISO PN6 Red 6505A4406 ASME Class 50 Black (00mm) Flg/Flg ASME Class 50 Red 6505A4706 ISO PN6 Red 6505A (68mm) Grv/Grv Black Red 6505A A6005 ASME Class 50 Black (68mm) Flg/Grv ASME Class 50 Red 6505A ISO PN6 Red 6505A6406 ASME Class 50 Black (68mm) Flg/Flg ASME Class 50 Red 6505A6706 ISO PN6 Red 6505A mm Grv/Grv Red 6505A mm Flg/Grv ASME Class 50 Red 6505A6606 ISO PN6 Red 6505A (00mm) Grv/Grv Black Red 6505A A8005 ASME Class 50 Black (00mm) Flg/Flg ASME Class 50 Red 6505A8706 ISO PN6 Red 6505A8806 { Black (50mm) Grv/Grv Red 6505A A0007 ½ (65mm) Grv/Grv Black Red A A507 (80mm) Grv/Grv Black Red 6505A A mm Grv/Grv Red 6505A (00mm) Grv/Grv Black Red 6505A A4008 ASME Class 50 Black (00mm) Flg/Grv ASME Class 50 Red 6505A409 ISO PN6 Red 6505A4409 ASME Class 50 Black (00mm) Flg/Flg ASME Class 50 Red 6505A4709 ISO PN6 Red 6505A (68mm) Grv/Grv Black Red 6505A A6008 ASME Class 50 Black (68mm) Flg/Grv ASME Class 50 Red 6505A ISO PN6 Red 6505A6409 ASME Class 50 Black (68mm) Flg/Flg ASME Class 50 Red 6505A6709 ISO PN6 Red 6505A mm Grv/Grv Red 6505A mm Flg/Grv ASME Class 50 Red 6505A6607 ISO PN6 Red 6505A (00mm) Grv/Grv Black Red 6505A A8008 ASME Class 50 Black (00mm) Flg/Flg ASME Class 50 Red 6505A8709 ISO PN6 Red 6505A

35 Electric Actuation Deluge (Explosion Proof Solenoid Available Upon Request) { 75 PSI Valve Size & End Connection Flange Type (50mm) Grv/Grv ½ (65mm) Grv/Grv Color Trim Part Numbers Individual Parts (Model DDX Valve Sold Seperately) Trim Configurations Segmentally Assembled (Model DDX Valve Sold Seperately) Fully Assembled to Model DDX Valve w/o Control Valve Fully Assembled to Model DDX Valve w/ Control Valve Black Red 6505A A000 Black Red A5 6505A50 Black (80mm) Grv/Grv Red 6505A A000 76mm Grv/Grv Red 6505A76 4 (00mm) Grv/Grv 4 (00mm) Flg/Grv 4 (00mm) Flg/Flg 6 (68mm) Grv/Grv 6 (68mm) Flg/Grv Black Red 6505A A400 ASME Class 50 Black ASME Class 50 Red 6505A4 ISO PN6 Red 6505A44 ASME Class 50 Black ASME Class 50 Red 6505A47 ISO PN6 Red 6505A48 Black Red 6505A A600 ASME Class 50 Black ASME Class 50 Red 6505A ISO PN6 Red 6505A64 ASME Class 50 Black (68mm) Flg/Flg ASME Class 50 Red 6505A67 ISO PN6 Red 6505A68 65mm Grv/Grv Red 6505A65 65mm Flg/Grv 8 (00mm) Grv/Grv 8 (00mm) Flg/Flg ASME Class 50 Red 6505A66 ISO PN6 Red 6505A69 Black Red 6505A A800 ASME Class 50 Black ASME Class 50 Red 6505A87 ISO PN6 Red 6505A88 5.

36 Electric Actuation Deluge (Explosion Proof Solenoid Available Upon Request) -Continued { 50 PSI Valve Size & End Connection Flange Type (50mm) Grv/Grv ½ (65mm) Grv/Grv Color Trim Part Numbers Individual Parts (Model DDX Valve Sold Seperately) Trim Configurations Segmentally Assembled (Model DDX Valve Sold Seperately) Fully Assembled to Model DDX Valve w/o Control Valve Fully Assembled to Model DDX Valve w/ Control Valve Black Red 6505A A005 Black Red A A55 Black (80mm) Grv/Grv Red 6505A A005 76mm Grv/Grv Red 6505A766 4 (00mm) Grv/Grv 4 (00mm) Flg/Grv 4 (00mm) Flg/Flg 6 (68mm) Grv/Grv 6 (68mm) Flg/Grv Black Red 6505A A405 ASME Class 50 Black ASME Class 50 Red 6505A46 ISO PN6 Red 6505A446 ASME Class 50 Black ASME Class 50 Red 6505A476 ISO PN6 Red 6505A486 Black Red 6505A A605 ASME Class 50 Black ASME Class 50 Red 6505A ISO PN6 Red 6505A646 ASME Class 50 Black (68mm) Flg/Flg ASME Class 50 Red 6505A676 ISO PN6 Red 6505A686 65mm Grv/Grv Red 6505A656 65mm Flg/Grv 8 (00mm) Grv/Grv 8 (00mm) Flg/Flg ASME Class 50 Red 6505A666 ISO PN6 Red 6505A696 Black Red 6505A A805 ASME Class 50 Black ASME Class 50 Red 6505A876 ISO PN6 Red 6505A886 Note: For metric installations, a ¼ NPT x R¼. ISO 7/ x Close Nipple (Reliable P/N ) or a NPT x R. ISO 7/ x Close Nipple (Reliable P/N ) is sold separately as an adapter for the single drain outlet of the trims. Additional equipment Air compressors, electric detection, actuation equipment, and mechanical sprinkler alarms must be ordered separately. These devices are described in Bulletin

37 Nominal Pipe Size (50 mm) ½ (65 mm), (80 mm) & 76 mm 4 (00 mm) 6 (50 mm) & 65 mm 8 (00 mm) Installation Dimensions in Inches (mm) A B C D* D** D*** D**** E F G H J K L M N P Q R 8 (0) 8 (0) 7¼ (84) 7¼ (84) 7¼ (84) 7 (78) 7 (78) 7½ (9) 8½ (5) 9¼ (5) 9½ (4) 9½ (4) 0 (54) (80) ½ (9) ½ (8) ½ (8) 4 (56) 6 (406) 9 / 8 (49) ¼ (540) (559) 4¼ (66) 7½ (699) 0¼ (768) 6 (406) 9 (48) 6 (406) 9 (48) ¼ (540) (787) (787) (787) ½ (85) ¾ (857) 5 (65) 5 (65) 5 (65) 7½ (699) 7¾ (705) ½ (86) ½ (86) ½ (86) 5 (889) 5¼ (895) 6 (5) 6 (5) 7½ (9) 8 (0) 9 (9) ¾ (98) ¾ (98) ¼ (7) ¾ (49) 4¾ (75) 4¼ (08) 4¼ (08) 5½ (40) 5½ (40) 5½ (40) D* is total takeout for Fully Assembled to Grv/Grv DDX Valve w/o Control Valve Configurations D** is total takeout for Fully Assembled to Grv/Grv DDX Valve w/ Control Valve Configurations D*** is total takeout for Fully Assembled to Flg/Grv DDX Valve w/o Control Valve Configurations D**** is total takeout for Fully Assembled to Flg/Flg DDX Valve w/o Control Valve Configurations 5½ (40) 5½ (40) 8¼ (0) 8¼ (0) 8¼ (0) (79) (79) ½ (4) ¾ (49) 4½ (68) (76) (76) 5 (7) 4¾ () ½ (89) 4½ (4) 4½ (4) 6¾ (7) 6½ (65) 5¼ () 9¼ (5) 9¼ (5) ¾ (98) (05) ¾ (4) 0¼ (60) 0¼ (60) ¾ (98) ¼ () ¼ (7) 7.

38 SOLENOID VALVE INSPECTIONS, TESTS AND MAINTENANCE WARNING: THE OWNER IS RESPONSIBLE FOR MAINTAINING THE FIRE PROTECTION SYSTEM IN PROPER OPERATING CONDITION. ANY SYSTEM MAINTENANCE OR TESTING THAT INVOLVES PLACING A CON- TROL VALVE OR DETECTION SYSTEM OUT OF SERVICE MAY ELIMINATE THE FIRE PROTECTION OF THAT SYSTEM. PRIOR TO PROCEEDING, NOTIFY ALL AUTHORITIES HAVING JURISDICTION. CONSIDERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREA. WARNING: PRIOR TO OPERATING THE SOLENOID VALVE, BE SURE TO CLOSE THE SYSTEM CONTROL VALVE TO AVOID UNINTENTIONAL OPERATION OF THE DELUGE VALVE. Inspections: It is imperative that the system be inspected and tested in accordance with NFPA 5 on a regular basis. The frequency of the inspections may vary due to contaminated water supplies, corrosive water supplies, or corrosive atmospheres. In addition, the alarm devices, detection systems, or other connected trim may require a more frequent schedule. Refer to the system description and applicable codes for minimum requirements.. The valve must be inspected at least monthly for cracks, corrosion, leakage, etc., and cleaned, repaired, or replaced, or replaced as necessary.. If Leakage is suspected through the solenoid valve, the valve diaphragms and seat should be inspected and if necessary, repaired or replaced. WARNING: CLOSE SYSTEM CONTROL VALVE, TURN OFF POWER SUPPLY, AND DEPRESSURIZE VALVE BEFORE DISASSEMBLING VALVE. IT IS NOT NECESSARY TO REMOVE THE VALVE FROM THE PIPE LINE TO MAKE INSPECTIONS. 4. When lubricating valve components, use high grade silicone grease (Dow Corning Compound Lubricant or equal). 5. When reassembling, tighten parts to torque values indicated in the manufacturer s maintenance instructions (packed with valve). 6. After maintenance is completed, operate the valve a few times to be sure of proper operation. A metallic click signifies the solenoid is operating. 7. All service must be performed by qualified personnel. Upon completion of inspections or replacement of the valve, the entire system must be checked for proper operation. See appropriate system description and testing instructions for additional information. The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co., Inc. (800) Sales Offices (800) Sales Fax (94) Corporate Offices Internet Address Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 0/ P/N

AGCX Bulletin 519 C/Alfoz de Bricia nº4 P.l. Villalonquéjar Burgos (Spain) Tlfno: PAG 1 de 50

AGCX Bulletin 519 C/Alfoz de Bricia nº4 P.l. Villalonquéjar Burgos (Spain) Tlfno: PAG 1 de 50 Instructions for Installation, Operation, Care and Maintenance Model AGCX Deluge Valve (50 mm), ½ (65 mm), 3 (80 mm), 4 (00 mm), 6 (50 mm), 8 (00 mm) Wet Pilot Line, Dry Pilot Line, and Electric Actuation

More information

Model DDX Deluge Valves 4" (100 mm), 6" (150 mm) and 165 mm Sizes

Model DDX Deluge Valves 4 (100 mm), 6 (150 mm) and 165 mm Sizes Features 1. Differential-type, lightweight, dependable construction. 2. Easily trimmed for releasing by: Manual pull stations Wet pilot sprinklers Dry pilot actuators Solenoid valves 3. Drop in seat &

More information

Features 1. Differential Latch-type, lightweight, dependable

Features 1. Differential Latch-type, lightweight, dependable Bulletin 516 Rev. B Model DDX-SS Deluge Valve (100mm), (150mm) & (200mm) Bulletin 516 Rev. B Features 1. Differential Latch-type, lightweight, dependable construction. 2. Easily trimmed for releasing by:

More information

Model DDX Deluge Valve 8 (200mm) Features

Model DDX Deluge Valve 8 (200mm) Features Model DDX Deluge Valve 8 (200mm) Bulletin 514 Bulletin 514 Features 1. Differential Latch-type, lightweight, dependable construction. 2. Easily trimmed for releasing by: Manual pull stations Wet pilot

More information

Instructions for Installation, Operation, Care, and Maintenance

Instructions for Installation, Operation, Care, and Maintenance Bulletin 750 Rev. B Model DDX Double Interlock Preaction System Type D 2 (50 mm), 2½ (65 mm), 3 (80 mm), 76 mm, 4 (00 mm), 6 (50 mm), 65 mm & 8 (200 mm) Bulletin 750 Rev. B Instructions for Installation,

More information

Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,14 bar) Pneumatic Supervising Pressure with Electric Actuation

Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,14 bar) Pneumatic Supervising Pressure with Electric Actuation Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,14 bar) Pneumatic Supervising Pressure with Electric Actuation Single Interlock Electric Release Preaction System 8 (200 mm) Size

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Bulletin 407 Rev. T Model E Alarm Check Valve Bulletin 407 Rev. T Instructions for Installation, Operation, Care and Maintenance 4 (100 mm), 6 (150 mm), 8 (200 mm) Sizes With Model E3 Trim Listed by Underwriters

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Model D Dry Pipe Valve Bulletin 350 Rev. S Bulletin 350 Rev. S Instructions for Installation, Operation, Care and Maintenance 4 (100mm) 6 (150mm) Valve With Model D Trimmings Listed by Underwriters Laboratories,

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Bulletin 727 Rev. G Single Interlock Preaction System 4 (00mm), 6 (50mm) & 65mm Sizes Bulletin 727 Rev. G Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,4 bar) Pneumatic Supervising

More information

DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : VALVE OPERATION TRIM DESCRIPTION DESCRIPTION PRESSURE THREADED OPENING

DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : VALVE OPERATION TRIM DESCRIPTION DESCRIPTION PRESSURE THREADED OPENING DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : NOMINAL SIZE MATERIAL MAXIMUM SERVICE PRESSURE 200, 150, 100, 80 & 50NB Cast Iron 12 Bar (175 PSI) THREADED OPENING MOUNTING FACTORY HYDROSTATIC TEST PRESSURE

More information

TECHNICAL DATA. Q= C v P S

TECHNICAL DATA. Q= C v P S 1 of 9 1. DESCRIPTION The Viking Model E-1 Deluge Valve is a quick-opening, differential diaphragm, flood valve with one moving part. The deluge valve is used to control water flow in deluge and preaction

More information

TECHNICAL DATA. Q= C v P Cv = Flow Factor (GPM/1 PSI P)

TECHNICAL DATA. Q= C v P Cv = Flow Factor (GPM/1 PSI P) 1 of 9 1. DESCRIPTION The Viking 2 (DN50) is a quick-opening, differential diaphragm, flood valve with one moving part. The deluge valve is used to control water flow in deluge and preaction sprinkler

More information

DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description Worldwide Contacts www.tyco-fire.com DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/ Inch to Inch (DN40 to DN00) General Description The TYCO DV-5a Automatic

More information

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE 6 (DN150)

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE 6 (DN150) January 13, 2006 Deluge Valves 211 a 1. PRODUCT NAME Viking Model E-1 Deluge Valve 3 (DN80) Available since 1985 4 (DN100) Available since 1985 6 (DN150) Available since 1984 2. MANUFACTURER THE VIKING

More information

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim Actuated Valve with LPCB Approved Preaction Trim 104g/01 with: - Electric Activation with Redundant Solenoid Valve - Electric Activation with Redundant Solenoid Valve and AutoConvert Dry Trim - Double

More information

DELUGE VALVE DATA SHEET

DELUGE VALVE DATA SHEET FIRE FIGHTING EQUIPMENT DATA SHEET DELUGE VALVE DATA SHEET JOB NO. : RFQ. NO. : ISSUE : SHEET OF 01 CUSTOMER : ITEM NO. : 02 PROJECT : QUANTITY : 03 LOCATION : SERVICE : FIRE WATER AND / OR FOAM SYSTEM

More information

DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description Worldwide Contacts www.tyco-fire.com DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to Inch (DN40 to DN200) General Description The TYCO DV-5a Automatic

More information

TECHNICAL DATA 1-1/2 (dn40)

TECHNICAL DATA 1-1/2 (dn40) July 1, 2011 Deluge Valves 209a DESCRIPTION The Viking Model E-3 1-1/2 Deluge Valve is a quick-opening, differential type flood valve with a rolling diaphragm clapper. The deluge valve is used to control

More information

Q= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications

Q= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications 1 of 9 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can be used to facilitate manual

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Model H Deluge Riser Assembly Bulletin 507 Rev. D Bulletin 507 Rev. D Instructions for Installation, Operation, Care and Maintenance 1 1 / 2 (40mm) Size Electric Actuation The Reliable Automatic Sprinkler

More information

Instructions for Installation, Operation Care and Maintenance

Instructions for Installation, Operation Care and Maintenance Model A Dry Pipe Valve Bulletin 353 Rev.K Bulletin 353 Rev.K Instructions for Installation, Operation Care and Maintenance 2 1 2 (65mm) Valve With Model A Trim Listed by Underwriters Laboratories, Inc.

More information

Series 758 FireLock Actuated System Valve

Series 758 FireLock Actuated System Valve R IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS Series 58 FireLock Actuated System Valve With Deluge Trim Grooved X Grooved and Flanged X Grooved 30.04 VICTAULIC IS AN ISO 9001 CERTIFIED COMPANY PRODUCT

More information

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet)

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet) Flow Control 500a DESCRIPTION The Viking 1-1/2 is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The can be used to facilitate manual or automatic on/off

More information

FireLock NXT Deluge Valve. With Deluge Trim Grooved x Grooved. System No. Submitted By Spec Sect Para Location Date Approved Date

FireLock NXT Deluge Valve. With Deluge Trim Grooved x Grooved. System No. Submitted By Spec Sect Para Location Date Approved Date MEA: 248-98-E CSFM: 7770-0531-117 The patent-pending Victaulic Series 769 FireLock NXT controls the water supply entry into the deluge system piping and open sprinklers. The Series 769 is a low differential,

More information

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation Deluge Valve DV-5 Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation GeneralDescription The Model DV-5 Deluge Valve (described in Technical

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Model H Deluge Riser Assembly Bulletin 507 Rev.C Bulletin 507 Rev.C Instructions for Installation, Operation, Care and Maintenance 1 1 2 (40mm) Size Electric Actuation The Reliable Automatic Sprinkler

More information

MODEL RCW NON-INTERLOCK PREACTION SYSTEM

MODEL RCW NON-INTERLOCK PREACTION SYSTEM GENERAL DESCRIPTION The Globe Model RCW non-interlock preaction valve is a hydraulically operated external resetting differential latching style valve designed for use where quickopening and total flooding

More information

TECHNICAL DATA CONCENTRATE CONTROL VALVE APPLICATIONS, PRIMING CONNECTIONS, AND TRIMS 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS.

TECHNICAL DATA CONCENTRATE CONTROL VALVE APPLICATIONS, PRIMING CONNECTIONS, AND TRIMS 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS. Page 1 of Telephone: 29-95-9501 Technical Services: 877-38-5 Fax: 29-818-180 Email: techsvcs@vikingcorp.com 1. GENERAL DESCRIPTION The Halar Coated Concentrate Control (CCV) is utilized in Viking foam

More information

MODEL RCW DELUGE SYSTEM ELECTRIC, WET PILOT, AND DRY PILOT ACTUATION

MODEL RCW DELUGE SYSTEM ELECTRIC, WET PILOT, AND DRY PILOT ACTUATION 0 Airpark Dr. Standish, MI 868 989-86-8 www.globesprinkler.com Technical Support 989--00 techservice@globesprinkler.com MODEL RCW DELUGE SYSTEM ELECTRIC, WET PILOT, AND DRY PILOT ACTUATION GENERAL DESCRIPTION

More information

Series 769 FireLock NXT Deluge Valve

Series 769 FireLock NXT Deluge Valve IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS Series 79 FireLock NXT Deluge Valve With Deluge Trim Grooved X Grooved 30.81 VICTAULIC IS AN ISO 9001 CERTIFIED COMPANY PRODUCT DESCRIPTION The patent-pending

More information

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description Worldwide Contacts www.tycofire.com DV Deluge Valve, Diaphragm Style, / thru Inch (DN0 thru DN00), Deluge System Wet Pilot Actuation General Description The DV Deluge Valve (described in Technical Data

More information

TECHNICAL DATA. Trimpac 249a. September 16, 2013

TECHNICAL DATA. Trimpac 249a. September 16, 2013 September 16, 2013 Trimpac 249a 1. DESCrIpTION DESCRIPTION TRIMPAC Model B-4, B-4B & B-4S is a factory assembled trim package for a single interlocked with a pneumatic release module in a metal enclosure.

More information

TECHNICAL DATA. model f-1 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA. Page 1 of 11

TECHNICAL DATA. model f-1 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA. Page 1 of 11 Page 1 of 11 1. DESCRIPTION The Viking Model F-1 Dry Pipe Valve is a latching differential valve used to separate the water supply from the dry pipe sprinkler system. The valve combines a positive latching

More information

1-1/2 Inch (DN40) 9 lb (4,1 kg) Groove Groove 1 8 lb (3,6 kg) Flange Groove 1 N/A N/A. Flange Flange N/A N/A

1-1/2 Inch (DN40) 9 lb (4,1 kg) Groove Groove 1 8 lb (3,6 kg) Flange Groove 1 N/A N/A. Flange Flange N/A N/A Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Diaphragm Style General Description The TYCO 1-1/2 inch to inch (DN40 to DN200), DV-5 Deluge Valves are diaphragm type valves designed for vertical

More information

Series 756 FireLock Dry System Check Valve

Series 756 FireLock Dry System Check Valve R IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS Series FireLock Dry System Check Valve Grooved X Grooved and Flanged X Grooved 0.0 VICTAULIC IS AN ISO 900 CERTIFIED COMPANY PRODUCT DESCRIPTION The Victaulic

More information

TECHNICAL DATA. Trimpac 244a. April 15, 2011

TECHNICAL DATA. Trimpac 244a. April 15, 2011 April 15, 2011 Trimpac 244a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-1 and B-1B is a factory-assembled trim package with an electric release module in a metal enclosure. The standard trim normally required

More information

Easy Riser swing check valve Models E-1 & F-1

Easy Riser swing check valve Models E-1 & F-1 Page 1 of 7 1. DESCRIPTION The Viking Easy Riser Swing Check Valve is a general purpose rubber-faced approved for use in fire service systems. The valve is for use in wet system risers, preaction system

More information

Worldwide Contacts.

Worldwide Contacts. Worldwide Contacts www.tyco-fire.com DV-5 Remote-Resetting, Pressure-Reducing Deluge Valve, Limited Space Valve Cabinet General Description The TYCO DV-5 Remote-Resetting, Pressure-Reducing Deluge Valve,

More information

TECHNICAL DATA. Table 1: Model F1 Dry Valve Part Numbers and Specifications

TECHNICAL DATA. Table 1: Model F1 Dry Valve Part Numbers and Specifications Page 1 of 11 1. DESCRIPTION The Viking Model F-2 Dry Pipe Valve is a latching differential valve used to separate the water supply from the dry pipe sprinkler system. The valve combines a positive latching

More information

TECHNICAL DATA TRIMPAC MODEL B-4, B-4B & B-4S SINGLE INTERLOCK PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA TRIMPAC MODEL B-4, B-4B & B-4S SINGLE INTERLOCK PREACTION SYSTEM WITH PNEUMATIC RELEASE Page 1 of 20 1. DESCRIPTION TRIMPAC Model B-4, B-4B & B-4S is a factory assembled trim package for a single interlocked preaction system with a pneumatic release module in a metal enclosure. The standard

More information

TotalPac 3 Deluge, Electric release Remote controlled system

TotalPac 3 Deluge, Electric release Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a deluge system trim totally preassembled, pre-wired and factory tested. All electrical and

More information

TECHNICAL DATA 2-1/2-8 (dn65 - dn200)

TECHNICAL DATA 2-1/2-8 (dn65 - dn200) 1 of 13 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can be used to facilitate manual

More information

TotalPac 3 Firecyle III Wet pipe Remote controlled system

TotalPac 3 Firecyle III Wet pipe Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a Firecycle III system trim totally preassembled, pre-wired and factory tested. All electrical

More information

Preaction System with DV-5 Deluge Valve Double Interlock Electric/Electric Actuation. General Description. Page 1 of 14 DECEMBER 2014 TFP1465

Preaction System with DV-5 Deluge Valve Double Interlock Electric/Electric Actuation. General Description. Page 1 of 14 DECEMBER 2014 TFP1465 Worldwide Contacts www.tycofire.com Preaction System with DV5 Deluge Valve Double Interlock Electric/Electric Actuation General Description The TYCO DV5 Double Interlock Preaction System with Electric/Electric

More information

TotalPac 3 Non interlock Preaction, Electric release Remote controlled system

TotalPac 3 Non interlock Preaction, Electric release Remote controlled system (Optional) Description This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

Technical Data. UL Listing is based on the following criteria:

Technical Data. UL Listing is based on the following criteria: Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve with Trim Inch and 6 Inch (DN1 and DN15) General Description The TYCO DV-5 Deluge Valve with Trim is a diaphragm-style valve that depends upon water

More information

TotalPac 3 Deluge system Pneumatic release

TotalPac 3 Deluge system Pneumatic release (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a deluge system trim totally preassembled, pre-wired and factory tested. All electrical and

More information

GW MKIII DELUGE VALVE - ALUBRONZE EXTERNAL RESET, PNEUMATIC

GW MKIII DELUGE VALVE - ALUBRONZE EXTERNAL RESET, PNEUMATIC Jacking Bolts Outlet Connection to Release (dry pilot line) Connection to Alarm Line ANGUS GW DELUGE VALVE VALVE 2 Drain Port Note: All Other Connections ½ Inlet External resetting of clapper via hand

More information

TotalPac 3 Non interlock Preaction system Pneumatic release

TotalPac 3 Non interlock Preaction system Pneumatic release (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

TotalPac 3 Double interlock Preaction, Electric/Pneumatic release Remote controlled system

TotalPac 3 Double interlock Preaction, Electric/Pneumatic release Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description

DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description The TYCO Aluminum Bronze DV-5 Deluge Valves are available to provide an alternative material

More information

SHORTER. LIGHTER. MORE VERSATILE. 1 VALVE 10 TRIM CONFIGURATIONS 4" AND 6" MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS

SHORTER. LIGHTER. MORE VERSATILE. 1 VALVE 10 TRIM CONFIGURATIONS 4 AND 6 MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS SHORTER. LIGHTER. MORE VERSATILE. " AND 6" MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS Globe is proud to introduce the new Model RCW Water Control Valve for dry pipe, preaction

More information

Q= C v P S. Flow control valve Model j-2 Halar coated

Q= C v P S. Flow control valve Model j-2 Halar coated October 22, 2010 Flow Control 507a 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can

More information

FireLock NXT Actuated Valve with Preaction Trim. System No. Submitted By Spec Sect Para Location Date Approved Date

FireLock NXT Actuated Valve with Preaction Trim. System No. Submitted By Spec Sect Para Location Date Approved Date VNIIPO ME: 248-98-E CSFM: 7770-0531-117 The patent-pending Victaulic Series 769 FireLock NXT Preaction Valve controls the water supply entry into the Preaction system piping and sprinklers. The Preaction

More information

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL J-2 HALAR COATED 1-1/2 & 2 (DN40 & DN50) 1. DESCRIPTION

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL J-2 HALAR COATED 1-1/2 & 2 (DN40 & DN50) 1. DESCRIPTION Page 1 of 9 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can be used to facilitate manual

More information

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Remote controlled system

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

Wet pipe low flow foam/water manifold system

Wet pipe low flow foam/water manifold system December 6, 2010 Foam 15a 1. Description With the Wet Pipe Low Flow Foam/Water Manifold System, multiple risers can be supplied from a single proportioning device. A riser manifold is installed with various

More information

TECHNICAL DATA CAUTION

TECHNICAL DATA CAUTION Page 1 of 6 1. DESCRIPTION The Viking Model D-2 Accelerator is a quick-opening device, with an integral anti-flood assembly, used to increase the operating speed of a differential type dry pipe valve.

More information

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL H-2 HALAR COATED 2 (DN50) - 6 (DN150)

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL H-2 HALAR COATED 2 (DN50) - 6 (DN150) 1 of 12 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The Flow Control Valve can be used to facilitate manual

More information

DV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description Worldwide Contacts www.tyco-fire.com DV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to Inch (DN40 to DN200) General Description The TYCO DV-5A Automatic

More information

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4 Page 1 of 5 Model F Dry Valve with Trim Valve Size Part Number 3 13764PTR 4 13765PTR 6 13766PTR Standard Trim Sets include galvanized nipples and fittings. 4 Dry Valve Shown General Notes: Notes: For use

More information

TECHNICAL DATA P S. Q= Cv MODEL E-2 DELUGE VALVE HALAR COATED ANGLE STYLE

TECHNICAL DATA P S. Q= Cv MODEL E-2 DELUGE VALVE HALAR COATED ANGLE STYLE 1 of 13 1. DESCRIPTION Viking Deluge Valves are quick opening, differential diaphragm flood valves with one moving part. The Viking Model E-2 Halar Coated Deluge Valve is identical to the Viking Model

More information

BERMAD Waterworks. Pressure Relief/Sustaining Valve. Model: WW Series. Features and Benefits. Major Additional Features

BERMAD Waterworks. Pressure Relief/Sustaining Valve. Model: WW Series. Features and Benefits. Major Additional Features Pressure Relief/Sustaining Valve Prioritizing pressure zones Ensuring controlled pipeline fill-up Preventing pipeline emptying Pump overload & cavitation protection Safeguarding pump minimum flow Excessive

More information

PRESSURE RELIEF / SURGE ANTICIPATOR CONTROL VALVE

PRESSURE RELIEF / SURGE ANTICIPATOR CONTROL VALVE PROJECT NAME LOCATION PRESSURE RELIEF / SURGE ANTICIPATOR CONTROL VALVE INTRODUCTION This specification covers the design, manufacture, and testing of 2-1/2 in. (65 mm) through 18 in. (450 mm) Control

More information

TotalPac 3 Double interlock Firecyle III Preaction Remote controlled system

TotalPac 3 Double interlock Firecyle III Preaction Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a Firecycle III system trim totally preassembled, pre-wired and factory tested. All electrical

More information

Model CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data

Model CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data Worldwide Contacts www.tyco-fire.com Model CV-FR Grooved-End Riser Check Valves Inch to Inch (DN0 to DN00) General Description The TYCO Model CV-FR Grooved- End Riser Check Valve is a compact and rugged

More information

Series 751 FireLock European Alarm Check Valve Stations

Series 751 FireLock European Alarm Check Valve Stations R IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS Series FireLock European Alarm Check Valve Stations Grooved X Grooved 0.0 VICTAULIC IS AN ISO 00 CERTIFIED COMPANY PRODUCT DESCRIPTION The Victaulic Series

More information

PRESSURE RELIEF / SUSTAINING CONTROL VALVES

PRESSURE RELIEF / SUSTAINING CONTROL VALVES PROJECT NAME LOCATION PRESSURE RELIEF / SUSTAINING CONTROL VALVES INTRODUCTION This specification covers the design, manufacture, and testing of 1 in. (25 mm) through 36 in. (900 mm) Control Valves PART

More information

COMBINATION PRESSURE REDUCING AND SOLENOID SHUTOFF CONTROL VALVES 2.01 COMBINATION RESSURE REDUCING AND SOLENOID SHUTOFF CONTROL VALVE

COMBINATION PRESSURE REDUCING AND SOLENOID SHUTOFF CONTROL VALVES 2.01 COMBINATION RESSURE REDUCING AND SOLENOID SHUTOFF CONTROL VALVE PROJECT NAME LOCATION COMBINATION PRESSURE REDUCING AND SOLENOID SHUTOFF CONTROL VALVES INTRODUCTION This specification covers the design, manufacture, and testing of 1 in. (25 mm) through 36 in. (900

More information

SOLENOID CONTROL VALVE

SOLENOID CONTROL VALVE PROJECT NAME LOCATION SOLENOID CONTROL VALVE INTRODUCTION This specification covers the design, manufacture, and testing of 4 in. (100 mm) through 36 in. (900 mm) Control Valves PART 1 - GENERAL 1. Standard

More information

Grooved Piping System for Fire Protection Services

Grooved Piping System for Fire Protection Services Grooved Piping System for Fire Protection Services 1.01 General: A. Section Includes: 1. General 2. Materials: a. Pipe b. Victaulic Couplings c. Victaulic Fittings d. Hole and Branch Outlets e. Victaulic

More information

PRESSURE REDUCING CONTROL VALVES

PRESSURE REDUCING CONTROL VALVES PROJECT NAME LOCATION PRESSURE REDUCING CONTROL VALVES INTRODUCTION This specification covers the design, manufacture, and testing of 1 in. (25 mm) through 36 in. (900 mm) Control Valves PART 1 - GENERAL

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE August 31, 2006 Check Valve 815a 1. PRODUCT NAME Viking Easy Riser Swing Check Valve Model E-1: Available since 1992 Model F-1: Available since 1994 2. MANUFACTURER The Viking Corporation 210 N. Industrial

More information

TECHNICAL DATA. Q= C v P S. Table 1 - Valve Part Numbers and Specifications

TECHNICAL DATA. Q= C v P S. Table 1 - Valve Part Numbers and Specifications June 24, 2011 Flow Control 504a 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The Flow Control Valve can

More information

FRAME STYLE SPRAY NOZZLES TECHNICAL DATA

FRAME STYLE SPRAY NOZZLES TECHNICAL DATA Page 1 of 5 1. DESCRIPTION Viking Frame Style Spray Nozzles are small, directional spray nozzles for use on water spray systems. They are thermosensitive glass bulb style nozzles, however they may be ordered

More information

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve Technical Bulletin TB-ACV-LFF11RFP LEAD FREE * LFF11RFP Flood Protection Shut Down Valve Installed upstream of Reduced Zone Backflow Preventer. Normally Open Valve - Closes when continuous discharge from

More information

ALTITUDE CONTROL VALVES FOR ONE WAY FLOW

ALTITUDE CONTROL VALVES FOR ONE WAY FLOW PROJECT NAME LOCATION ALTITUDE CONTROL VALVES FOR ONE WAY FLOW INTRODUCTION This specification covers the design, manufacture, and testing of 2 in. (50 mm) through 36 in. (900 mm) Control Valves PART 1

More information

Deep Well Pump Control Valve

Deep Well Pump Control Valve MODEL 61-02 661-02 Deep Well Pump Control Valve Prevent Surges in Pipelines Simple Hydraulic Operation Adjustable Opening & Closing Speeds Solenoid Control Can Be Operated Manually Proven Reliable Design

More information

Section R Foam Systems

Section R Foam Systems Section R TABLE OF CONTENTS... R-1 R-3 Concentrate Control Valves and Trim... R-4 Valve Trim for Premixed... R-4 Release Trim Packages... R-4 Foam Concentrates... R-5 Accessories, Foam Concentrates...

More information

Section R Foam Systems

Section R Foam Systems Section R TABLE OF CONTENTS... R-1 R-3 Concentrate Control Valves and Trim... R-4 Valve Trim for Premixed... R-4 Release Trim Packages... R-4 Foam Concentrates... R-5 Accessories, Foam Concentrates...

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE April 13, 2007 Spray Nozzle 31a 1. DESCRIPTION Viking Frame Style Spray Nozzles are small, directional spray nozzles for use on water spray systems. They are thermosensitive glass bulb style nozzles, however

More information

TECHNICAL DATA OBSOLETE. Inlet Type Outlet Type in mm. Thread Thread in. ANSI B Flanged Flanged in.

TECHNICAL DATA OBSOLETE. Inlet Type Outlet Type in mm. Thread Thread in. ANSI B Flanged Flanged in. August 19, 2003 Flow Control 504 a 1. PRODUCT NAME Viking Model H-2 Halar Coated Flow Control Valve 2" (50mm), 3" (80mm), 4" (100mm), 6" (150mm) Halar Coating Manufactured 1994-2. MANUFACTURER THE VIKING

More information

LEAD FREE * LFF113RFP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology

LEAD FREE * LFF113RFP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology Technical Bulletin TB-ACV-LFF11RFP_SentryPlus LEAD FREE * LFF11RFP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology Installed upstream of Reduced Zone Backflow Preventer.

More information

FireFlex DUAL Single Interlock, Remote controlled system

FireFlex DUAL Single Interlock, Remote controlled system FireFlex DUAL description The FireFlex DUAL integrated system consists of an integrated single interlock Electric release preaction automatic sprinkler system combined with a clean agent fire extinguishing

More information

Grooved Piping System for Fire Protection Services

Grooved Piping System for Fire Protection Services Grooved Piping System for Fire Protection Services 1.01 General: A. Section Includes: 1. General 2. Materials: a. Pipe b. Victaulic Couplings c. Victaulic Fittings d. Hole and Branch Outlets e. Victaulic

More information

FLOAT CONTROL VALVES

FLOAT CONTROL VALVES PROJECT NAME LOCATION FLOAT CONTROL VALVES INTRODUCTION This specification covers the design, manufacture, and testing of 8 in. (200 mm) through 36 in. (900 mm) Control Valves PART 1 - GENERAL 1. Standard

More information

PRESSURE REDUCING CONTROL VALVE

PRESSURE REDUCING CONTROL VALVE PRESSURE REDUCING CONTROL VALVE 06/08 Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Reducing setpoint is adjustable 2 (AOS) X P/L Standard Components 1 Main

More information

Deluge Valves. Model 68 DE\ HM-MR. Hydraulically Actuated Manual-Reset Deluge Valve. Dorot Fire Protection Division

Deluge Valves. Model 68 DE\ HM-MR. Hydraulically Actuated Manual-Reset Deluge Valve. Dorot Fire Protection Division Dorot Fire Protection Division s Model 68 DE\ HM-MR Hydraulically Actuated Manual-Reset Certification & compliance by design ANSI FCI 70-2 Class VI seat leakage class UL listed under VLFT category Fire

More information

A. This Section includes natural gas piping, specialties, and accessories within the building.

A. This Section includes natural gas piping, specialties, and accessories within the building. SECTION 226313 NATURAL GAS PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

S v S e r i e s F M f i r e e x t i n g u i s h i n g s y s t e m

S v S e r i e s F M f i r e e x t i n g u i s h i n g s y s t e m Clean S v S e r i e s F M - 2 0 0 f i r e e x t i n g u i s h i n g s y s t e m Advantages The Sv Series Clean Agent Fire Extinguishing System utilizes FM-200 as the extinguishing medium. FM-200 is a colorless,

More information

MODULATING FLOAT CONTROL VALVE

MODULATING FLOAT CONTROL VALVE PROJECT NAME LOCATION MODULATING FLOAT CONTROL VALVE INTRODUCTION This specification covers the design, manufacture, and testing of 2 in. (50 mm) through 36 in. (900 mm) Control Valves PART 1 - GENERAL

More information

MARINE INERGEN 150-BAR SYSTEMS Component Sheet Library

MARINE INERGEN 150-BAR SYSTEMS Component Sheet Library MARINE INERGEN 150-BAR SYSTEMS Component Sheet Library One Stanton Street / Marinette, WI 54143-2542, USA / +1-715-735-7411 / www.ansul.com Copyright 2015 Tyco Fire Products LP. / All rights reserved.

More information

TECHNICAL DATA. Table Standard Materials

TECHNICAL DATA. Table Standard Materials Page 1 of 9 1. GENERAL DESCRIPTION The In-Line Balanced Pressure (ILBP) Proportioner is a foam proportioning device which is used to balance the higher foam concentrate pressure to the lower system water

More information

CJ=TN=- FRONT DELUGE VALVE, EXTERNAL RESETTING. MODEL F470 MULTIMATIW - 4 and 6 INCH (100 and 150 mm) a P il

CJ=TN=- FRONT DELUGE VALVE, EXTERNAL RESETTING. MODEL F470 MULTIMATIW - 4 and 6 INCH (100 and 150 mm) a P il DELUGE VALVE, EXTERNAL RESETTING MODEL F470 MULTIMATIW - 4 and 6 INCH (100 and 150 mm) The 4 and 6 inch (100 and 150 mm), Model F470 External Resetting Multimatic Deluge Valves are differential latch type

More information

50-01 (Full Internal Port) (Reduced Internal Port) Pressure Relief. & Pressure Sustaining Valve MODEL

50-01 (Full Internal Port) (Reduced Internal Port) Pressure Relief. & Pressure Sustaining Valve MODEL 50-01 650-01 & 1 Hytrol (Main ) 2 X42N-2 Strainer & Needle 3 CRL Control Accurate Pressure Control Optional Check Feature Fast Opening to Maintain Line Pressure Slow Closing to Prevents s Completely Automatic

More information

PRESSURE REDUCING VALVE

PRESSURE REDUCING VALVE Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Closes quickly when downstream pressure exceeds reduced pressure setpoint 3 PRESSURE REDUCING VALVE with SURGE

More information

ALARM CHECK VALVE 3", 4" & 6" MODEL H-1 FLANGE/FLANGE 3" & 4" MODEL H-2 GROOVE/GROOVE 3", 4" & 6" MODEL H-3 FLANGE/GROOVE

ALARM CHECK VALVE 3, 4 & 6 MODEL H-1 FLANGE/FLANGE 3 & 4 MODEL H-2 GROOVE/GROOVE 3, 4 & 6 MODEL H-3 FLANGE/GROOVE DESCRIPTION AND OPERATION The Globe Model H-1, H-2 and H-3 Alarm Check Valves are used in wet pipe fire sprinkler systems. They primarily serve a dual purpose in that they prevent a reverse flow of water

More information

NYLON & PVC VALVES MINING DIVISION PRESSURE REDUCING VALVES ENSURE DOWNSTREAM PRESSURE PVC NYLON

NYLON & PVC VALVES MINING DIVISION PRESSURE REDUCING VALVES ENSURE DOWNSTREAM PRESSURE PVC NYLON MINING DIVISION NYLON & PVC VALVES PRESSURE REDUCING VALVES ENSURE DOWNSTREAM PRESSURE NYLON For Gold Mines DESCRIPTION The valve maintains a preset downstream pressure, regardless of upstream pressure

More information

Electronic Control Valves

Electronic Control Valves MODEL 131 Series (Full Internal Port) 631 Series (Reduced Internal Port) Electronic Control Valves Model 131-01/631-01 Simple Proven Design Quality Solenoid Pilot Controls Ideal For SCADA Systems Multi-Function

More information

VB VALVES & AUTOMATION

VB VALVES & AUTOMATION Introduction to Valve What are Valves? Valves are mechanical device that controls the flow and pressure within a system or process. They are essential components of a piping system that conveys liquids,

More information