Rotary Heat Wheel (Rotary Enthalpy Wheel)

Size: px
Start display at page:

Download "Rotary Heat Wheel (Rotary Enthalpy Wheel)"

Transcription

1 Rotary Heat Wheel (Rotary Enthalpy Wheel) Introduction SAIVER cooperates with Heatex a leading Sweden Heat Exchanger Specialist to provide a compact and high efficiency rotary heat wheel for our worldwide clients. This document would cover a lot of information about rotary heat wheel. operation manual as well as some useful hints. It includes technical data, Selection of Rotary Heat Wheel To select the heat wheel, several parameters are needed to consider at the same time Efficiency Efficiency is an important consideration when using rotary heat wheel. However, there are three different efficiency terms are commonly used together with rotary heat wheel. a. Temperature efficiency calculated based on temperature b. Humidity efficiency calculated based on moisture content c. Enthalpy efficiency calculated based on enthalpy Usually, temperature efficiency is the highest one. The temperature efficiency should be higher than 60%. Please take note that exhaust side efficiency is different from supply side. The efficiency is related to face velocity as well as the contact area of wheel. efficiency, a bigger wheel or a wheel with a smaller channel height is needed. Efficiency Size of Wheel Channel Height To achieve higher Version: 2 Page 1 of 7

2 Pressure Drop Pressure drop will affect the bearing life as well as the fan power consumption. The recommended pressure drop is 100 to 200Pa. The pressure drop is related to face velocity. To minimize the pressure drop, a bigger wheel or a wheel with a higher channel height is recommended. Size of Wheel Channel Height Pressure Drop Design Consideration There are some few points must be noted when selecting heat wheel: a) Exhaust air volume should be equal to supply air volume To achieve the best performance, return air volume should be equal to supply air volume. Due to air balancing, it is not always achievable to have an equal return and exhaust air volume. In such case, supply air volume should not be less than 70% or more than 150% of exhaust air volume. b) Cross-contamination is possible Cross-contamination is a general term when either or both carryover and leakage occurs. Carryover occurs as air is entrained within the volume of the wheel and is carried into the other airstream. Usually carryover from exhaust to supply is unwanted, a purge section can be installed to reduce this phenomenon. Leakage occurs because the differential static pressure across the two airstreams drives air from a higher to a lower static pressure region. Therefore, pressure potential of supply air should be larger than exhaust air. It can be minimized by placing the fans so that they promote leakage of supply air to exhaust air. The best arrangement is draw-through for both air streams. Version: 2 Page 2 of 7

3 Controls There are two common control methods to control heat wheel. a) Variable wheel rotational speed control The wheel rotational speed can regulate the energy recovery rate. Various motor speed control methods are applicable. Using frequency inverter is getting popular because frequency inverter is getting cheaper. Transfer Efficiency Heat Transfer Moisture Transfer EA T r RA T F Ts FA SA Wheel Rotation Speed (RPM) b) Supply air bypass control Bypass Damper Supply air bypass control requires a supply air bypass damper to regulate a certain amount of supply air bypass Wheel (Face) Dampe Tr the wheel to achieve the desirable the supply air EA RA temperature. The bypass duct branch must have the Damper Actuator same pressure drop as the wheel and associated duct system in order to avoid air FA To Ts SA flow rate balancing problems. Version: 2 Page 3 of 7

4 Control Strategies There are several common control strategies to control heat wheel. a) Supply air temperature (T s ) control It is the simplest control strategy. A supply air temperature is set and one temperature sensor is needed to provide a feedback. The wheel speed increases and decrease until the desired temperature is reached or until the wheel reaches its minimum / maximum speed. b) Temperature comparison (T o & T r ) Two temperature sensors are used to measure the outer air and the exhaust air. The temperature differential ensures that the wheel only operates when the wheel is economically beneficial for treating the supply air. When the temperature of the outer air is lower than temperature of the exhaust air and cooling is needed, the wheel will stop. c) Enthalpy comparison (h o & h r ) When humidity control is considered, two enthalpy sensors are needed. When the enthalpy of the outer air is lower than enthalpy of the exhaust air and cooling is needed, the wheel will stop. Technical Information To, ho Ts Fresh air Supply air Tr, hr Extract air Return air The Heatex Model W is a rotary heat wheel for HVAC heat recovery application. Significant for the Model W is, the well achieved roundness / balance of the wheels. Also to be noted, are the smooth and leveled air in- and outlet sides. In order to prevent unwrapping, the Model W is as standard provided with spokes. The performance of the Model W is integrated with SAIVER state-of-the-art selection program. Model W is available in four different standard materials: aluminium, aluminium with epoxy coating, aluminium with hygroscopic surface and aluminium with sodium silicate coating. Version: 2 Page 4 of 7

5 Three different channel heights are available: 1.5mm high efficiency but higher pressure drop 2.0mm standard 2.5mm suitable for more polluted exhaust air Wheel outer Power supply Casing dimension Motor power (W) Weight (kg) diameter (mm) (mm) W/o coating With coating 1.5mm / 2.0mm / 2.5mm V/1Φ/50Hz 600 x 600 x / 32 / V/1Φ/50Hz 700 x 700 x / 39 / V/1Φ/50Hz 800 x 800 x / 45 / V/1Φ/50Hz 900 x 900 x / 53 / V/1Φ/50Hz 1000 x 1000 x / 62 / V/3Φ/50Hz 1100 x 1100 x / 71 / V/3Φ/50Hz 1200 x 1200 x / 108 / V/3Φ/50Hz 1350 x 1350 x / 130 / V/3Φ/50Hz 1450 x 1450 x / 144 / V/3Φ/50Hz 1550 x 1550 x / 159 / V/3Φ/50Hz 1650 x 1650 x / 174 / V/3Φ/50Hz 1750 x 1750 x / 191 / V/3Φ/50Hz 1850 x 1850 x / 212 / V/3Φ/50Hz 1950 x 1950 x / 230 / V/3Φ/50Hz 2050 x 2050 x / 249 / V/3Φ/50Hz 2150 x 2150 x / 268 / V/3Φ/50Hz 2250 x 2250 x / 289 / V/3Φ/50Hz 2350 x 2350 x / 310 / V/3Φ/50Hz 2450 x 2450 x / 332 / V/3Φ/50Hz 2550 x 2550 x / 355 / V/3Φ/50Hz 2650 x 2650 x / 379 / 340 Version: 2 Page 5 of 7

6 The Wheel Material and dimensions Rotating wheels are available in four different standards: aluminum, epoxy coated aluminum, aluminum with a hygroscopic surface and aluminum with sodium silicate coating The depth of the wheel is 200mm Maximum diameter is 2500mm Wheels in epoxy coated aluminum have edges that are self sealed in corrosive environment Aluminum and epoxy coated aluminum wheels are recommended to rotate 10rpm Aluminum with a hygroscopic surface and aluminum with sodium silicate coating wheels are recommended to rotate 17rpm Wrap and hub are manufactured in aluminum Lifetime for a ball bearing is 50,000hr Casing General For wheels from 1101mm in diameter there is an extra girder mounted which makes the casing looks like a T viewing it from the back and front side Brush sealant is assembled at the wheel pressing on the casing from the inside to minimize the cross contamination Brush sealant is assembled at the girder as well which separate the two air streams at the back and the front of the casing to minimize the cross contamination Casing material is galvanized iron Purge Sector (Option) The purpose of the purge sector is to clean the wheel from the exhaust air before it turns over to the supply air side The purge sector is made in the size of 5 with start at center of the wheel At the purge sector is brush sealant assembled at the upper side and at the lower side At order please fill in position of purge sector according to enclosed guideline. The position is fixed based on the direction of the wheel as well as the directions of the supply/exhaust air. Version: 2 Page 6 of 7

7 Drive Motors for constant speed are as standard delivered in two types. - 1 x 230V - 3 x 380V Casings up to and including 999mm in square are delivered with 1x220V motor. Casings from 1000mm in square are delivered with 3x380V motor Maintenance and Cleaning of Rotating Heat Exchangers Maintenance Of The Wheel To secure the function and performance, the face of the wheel has to be inspected regularly for dust and dirt. This dirt or/and dust is recommended to be removed by different techniques. For only a small amount of easy removable dirt use a vacuum cleaner is recommended. For heavier dirt it is also possible to use compressed air but with caution. Finally, firmly dirt at the wheel are easiest removed by using hot water and a mild detergent. Maintenance Of Drive Unit Tension of the V-belt must be checked after the first 100 hours in operation to secure the rotational function of the wheel. To adjust tension check the belt tensioner as first step and adjust it as much as possible. As second step shortening the V-belt. The V-belt is put together with an easy removable mechanical lock but do not forget to adjust the belt tensioner after this operation. The round belt is self tensioned and should not be needed to adjust. Maintenance Of Brush Tightness between brush sealants and casing has to be checked during inspection. The brush sealants are easily adjusted by loosen the screws and move the brush sealant into the right position. V-belt, Round belt and brush sealants are all available as spare parts. Version: 2 Page 7 of 7

AIR-TO-AIR HEAT EXCHANGERS MODEL E INSTALLATION & MAINTENANCE

AIR-TO-AIR HEAT EXCHANGERS MODEL E INSTALLATION & MAINTENANCE AIR-TO-AIR HEAT EXCHANGERS MODEL E INSTALLATION & MAINTENANCE ENGLISH TEC-1301-V.8-201802-EN ADDRESS AND CONTACT DATA Heatex AB Bronsyxegatan 13 S-213 75 MALMÖ Sweden Telephone: +46 410 710 500 info@heatex.com

More information

AIR-TO-AIR HEAT EXCHANGERS MODEL E INSTALLATION & MAINTENANCE

AIR-TO-AIR HEAT EXCHANGERS MODEL E INSTALLATION & MAINTENANCE AIR-TO-AIR HEAT EXCHANGERS MODEL E INSTALLATION & MAINTENANCE ADDRESS AND CONTACT DATA DECLARATION OF INCORPORATION DISCLAIMER Heatex AB Bronsyxegatan 3 S-3 75 MALMÖ Sweden Telephone: +46 40 70 500 info@heatex.com

More information

AIR-TO-AIR HEAT EXCHANGERS MODEL Q2 TECHNICAL SPECIFICATION

AIR-TO-AIR HEAT EXCHANGERS MODEL Q2 TECHNICAL SPECIFICATION AIR-TO-AIR HEAT EXCHANGERS MODEL Q2 TECHNICAL SPECIFICATION ADDRESS AND CONTACT DATA Heatex AB Bronsyxegatan 13 S-213 75 MALMÖ Sweden Telephone: +46 410 710 500 info@heatex.com www.heatex.com DISCLAIMER

More information

Rotary heat exchangers

Rotary heat exchangers Rotary heat exchangers Introduction Among the available energy recovery systems, the rotary heat exchangers ensure the best efficiency, ranging from 60% to 90%, depending upon operating conditions. This

More information

THE PROMISE THE PROOF HEATEX AIR-TO-AIR HEAT EXCHANGERS

THE PROMISE THE PROOF HEATEX AIR-TO-AIR HEAT EXCHANGERS EQ THE PROMISE THE PROOF HEATEX AIR-TO-AIR HEAT EXCHANGERS ROTARY HEAT EXCHANGERS Heatex offers a broad range of rotary heat exchangers covering the complete application span from small residential installations

More information

AIR-TO-AIR HEAT EXCHANGERS MODEL E TECHNICAL SPECIFICATION

AIR-TO-AIR HEAT EXCHANGERS MODEL E TECHNICAL SPECIFICATION AIR-TO-AIR HEAT EXCHANGERS MODEL E TECHNICAL SPECIFICATION TEC-1310-V.10-201801-EN ADDRESS AND CONTACT DATA Heatex AB Bronsyxegatan 13 S-213 75 MALMÖ Sweden Telephone: +46 410 710 500 info@heatex.com www.heatex.com

More information

ROTARY HEAT EXCHANGER

ROTARY HEAT EXCHANGER ROTARY HEAT EXCHANGER Energy Recovery Ventilation Specialist Beijing Holtop Artificial Environment Technology Co., Ltd ISO9001 CE EUROVENT COMPANY BRIEF INTRODUCTION TO COMPANY ENERGY RECOVERY VENTILATION

More information

AIR-TO-AIR HEAT EXCHANGERS MODEL EQ TECHNICAL SPECIFICATION

AIR-TO-AIR HEAT EXCHANGERS MODEL EQ TECHNICAL SPECIFICATION AIR-TO-AIR HEAT EXCHANGERS MODEL EQ TECHNICAL SPECIFICATION ENGLISH TEC-1575-V.5-201807-A4 ADDRESS AND CONTACT DATA Heatex AB Bronsyxegatan 13 S-213 75 MALMÖ Sweden Telephone: +46 410 710 500 info@heatex.com

More information

AIR-AIR ENERGY CONSERVATION MODULE

AIR-AIR ENERGY CONSERVATION MODULE AIR-AIR ENERGY CONSERVATION MODULE BC-ECW SERIES INDOOR/OUTDOOR INSTALLATION MANUFACTURED BY TABLE OF CONTENTS BC-ECW - Description...3 Components and fabrication details...3-4 Frost prevention & selection

More information

D1M L1 T2 TB DATA SHEET A1-1130H-1400W. PANELS / FRAME Panels PART CODE Insulation

D1M L1 T2 TB DATA SHEET A1-1130H-1400W. PANELS / FRAME Panels PART CODE Insulation 19/04/11 08/06/11 P 1 / 12 08A72185 Example 02 RDH 400 R - 1607-2. 08 FA DAMPER 930 x 30 mm 09 P40-16AC 1/2R-24T-30A-4.0Pa Cu/Al 11 G4+F7 12 HA10-30-060-2EOO-1-1-2-1250 x 1250 15 P40-16AC 1/2R-22T-0A-2.5Pa

More information

Resolair 64 and 68. Comfort air conditioning unit with highly efficient regenerative heat storage packages. AIR VOLUME FLOW: 3,900 23,100 m³/h

Resolair 64 and 68. Comfort air conditioning unit with highly efficient regenerative heat storage packages. AIR VOLUME FLOW: 3,900 23,100 m³/h Comfort air conditioning unit with highly efficient regenerative heat storage packages 68 10 01 - simplified illustration Automatically selects the most economical operating mode! 64 and 68 AIR OLUME FLOW:

More information

CH5000 Heat Recovery Ventilator

CH5000 Heat Recovery Ventilator ADVANCED COMMERCIAL Heat Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 3500-5500 CFM CASING Double-wall cabinet White exterior paint, 22-gauge galvanized steel -gauge

More information

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile Centrifugal Cabinet s BCF Belt Drive Low-Profile November 204 BCF Centrifugal Cabinet Contents Standard Construction Features... 3 Options and Accessories... 4 Filter and Mixing Box Data... 5 Typical Installations...

More information

CENTAXIAL TUBULAR CENTRIFUGAL FANS. BIA Airfoil Blade Design Direct Drive & Belt Driven Model CBD / CDD (Class I, II & III) Model CBD Belt Driven

CENTAXIAL TUBULAR CENTRIFUGAL FANS. BIA Airfoil Blade Design Direct Drive & Belt Driven Model CBD / CDD (Class I, II & III) Model CBD Belt Driven Model CBD Belt Driven Model CDD Direct Drive CENTAXIAL TUBULAR CENTRIFUGAL FANS BIA Airfoil Blade Design Direct Drive & Belt Driven Model CBD / CDD (Class I, II & III) CATALOG 337 February 2004 Centaxial

More information

HPR. Heat recovery units. from 700 to m³/h R410A HIGH EFFICIENCY WITH ENTHALPY EXCHANGER AND BUILT-IN HEAT PUMP SYSTEM

HPR. Heat recovery units. from 700 to m³/h R410A HIGH EFFICIENCY WITH ENTHALPY EXCHANGER AND BUILT-IN HEAT PUMP SYSTEM 1 Lmf Clima 216 FERRARO GROUP HPR Heat recovery units HIGH EFFICIENCY WITH ENTHALPY EXCHANGER AND BUILT-IN HEAT PUMP SYSTEM from 7 to 23. m³/h Supporting structure in extruded aluminium profiles and curtain

More information

SARAVEL CENTRIFUGAL FANS For Airconditioning & Industrial Application

SARAVEL CENTRIFUGAL FANS For Airconditioning & Industrial Application CAT.NO. 120-97 SARAVEL CENTRIFUGAL FANS For Airconditioning & Industrial Application TABLE OF CONTENTS Introduction......3 Selection Examples......4-5 Correction Factors......6 Rating Tables.........7-17

More information

Sand Trap Louvers OSTL 300 SERIES. Sand Trap Louvers

Sand Trap Louvers OSTL 300 SERIES. Sand Trap Louvers Model : OSTL GI 341 Description: OPTIMA make Sand Trap Louver is used as pre-filter for the protection of air conditioning plants in area exposed to extreme levels of industrial pollution. It has a high

More information

Rotary Heat Exchangers

Rotary Heat Exchangers Rotary Heat Exchangers INSTALLATION AND OPERATING INSTRUCTIONS XPXR 12/2009 Contents General Information... 2 Use... 3 Operating Conditions... 3 Design... 3 Handling and Transport... 3 Installation Site...

More information

FOR AIR CONDITIONING AND VENTILATING APPLCATIONS

FOR AIR CONDITIONING AND VENTILATING APPLCATIONS PANELS FOR AIR CONDITIONING AND VENTILATING APPLCATIONS KLEENFLO for your average filter problem A permanent, all-metal, cleanable, viscous-impingement filter, the KLEENFLO provides excellent efficiency

More information

DAMPERS FOR COMMERCIAL & INDUSTRIAL APPLICATIONS IN HEATING, VENTILATING & AIR CONDITIONING

DAMPERS FOR COMMERCIAL & INDUSTRIAL APPLICATIONS IN HEATING, VENTILATING & AIR CONDITIONING PUB. NO. 732-3 DAMPERS FOR COMMERCIAL & INDUSTRIAL APPLICATIONS IN HEATING, VENTILATING & AIR CONDITIONING The most widely used dampers in commercial HVAC applications Control Dampers - Extruded Aluminum

More information

Air Handling Unit Construction Checklist

Air Handling Unit Construction Checklist Air Handling Unit Construction Checklist Project: Date: AHU Tag: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

CONTROL DAMPERS. Models 1810 & Model Model Model 1370

CONTROL DAMPERS. Models 1810 & Model Model Model 1370 CONTROL DAMPERS CONTROL DAMPERS MODELS 1810 & 1820 MANUAL ALANCING DAMPERS STEEL Models 1810 and 1820 have been engineering and designed for manual balancing applications in low to medium pressure and

More information

Page 1 of 14 Oil Pan Removal & Installation 4.2L Engine 4WD Vehicles To Remove: 1. Before servicing the vehicle refer to the precautions at the beginning of this section. 2. Raise and support the vehicle.

More information

Bulletin ACF 103 AIRFOIL CENTRIFUGAL FANS DESIGN 10A

Bulletin ACF 103 AIRFOIL CENTRIFUGAL FANS DESIGN 10A Bulletin ACF 103 AIRFOIL CENTRIFUGAL FANS DESIGN 10A Quieter, More Efficient Airfoil Fans for Commercial and Light Industrial Applications Design 10A Fans with Airfoil Wheels Fourteen Sizes to 80" Volumes

More information

Tubular Centrifugal Fans

Tubular Centrifugal Fans Tubular Centrifugal Fans Model TCB Inline - Horizontal or Vertical Roof Upblast and Roof Supply March 2007 Tubular Centrifugal Fans The TCB series of inline centrifugal fans is designed for ducted inline,

More information

E N V E N T U S Heat exchanger

E N V E N T U S Heat exchanger E N V E N T U S E N E R G Y R E C O V E R Y Heat exchanger Rotary heat exchanger Technical descripton Dimensions Variable drive equipment Constant drive equipment Capacity / Calucation program Purge air

More information

Issue 4 (Record Only) Job #: Innovent Submittal Date: October 30, 2012 Project: Location: Columbus, OH Innovent Job #: Submittal Issue: 4 (Record Only) Engineer: Contractor: Tag Innovent Model # AHU-BG-01

More information

Air Handling Units. Geniox. Accessories

Air Handling Units. Geniox. Accessories Air Handling Units Geniox Accessories The right accessories are important to optimise your Geniox air handling unit to the task at hand. SystemairCAD provides you with a wide selection of accessories.

More information

TECHNICAL PRODUCT DOCUMENTATION

TECHNICAL PRODUCT DOCUMENTATION Page: 1 POSITIONER TYPE A703 Page: 2 CONTENTS 1. APPLICATION 3 2. TECHNICAL DESCRIPTION 3 2.1. Construction 3 2.2. Working rules 4 2.3. Dimensions of the positioner and types of performances 6 3. TECHNICAL

More information

Product Guide. Energy Transfer Effectiveness. Non-Sectioned. Ten Inch Deep Corrugated Aluminum Construction. Low Pressure Drop

Product Guide. Energy Transfer Effectiveness. Non-Sectioned. Ten Inch Deep Corrugated Aluminum Construction. Low Pressure Drop Energy Transfer Effectiveness up to 85% Non-Sectioned Ten Inch Deep Corrugated Aluminum Construction Low Pressure Drop Product Guide Practically No Cross- Contamination with Purge Sector Factory Installed

More information

ERU ENERGY RECOVERY UNIT

ERU ENERGY RECOVERY UNIT TECHNICAL GUIDE ERU ENERGY RECOVERY UNIT TGERU-1 Energy Recovery Technical Guide When you need outside air that s clean and dry, Sierra delivers. When you need that same performance each and every day

More information

Calculation of external available Pressure. 1. Criterion flow velocity (Ref. 20 C) Do not design units in conditions acc. to white areas!

Calculation of external available Pressure. 1. Criterion flow velocity (Ref. 20 C) Do not design units in conditions acc. to white areas! Page 1 Standard Series Size: 3 Air flow volume Calculation of external available Pressure [m³/h] 3 4 5 55 6 65 7 75 8 9 1 11 12 1. Criterion flow velocity (Ref. 2 C) Do not design units in conditions acc.

More information

Series HCD Airfoil Control Damper

Series HCD Airfoil Control Damper Series HCD Airfoil Control Damper Model: HCD-1 The Holyoake HCD-1 is a precisely made volume and pressure control device with extremely low leakage when closed, (in the range of 0.003m 3 /s at 100 Pa).

More information

XeteX, Inc. All Rights Reserved.

XeteX, Inc. All Rights Reserved. Model XC Indoor or outdoor mounted, simple, in-case aluminum flat plate exchanger with options for frost control. Ideal for inline installations: in duct-work systems, in built-up units, or in modular

More information

Swimming Pool CSR2 Heat Recovery Equipment

Swimming Pool CSR2 Heat Recovery Equipment Swimming Pool CSR2 Heat Recovery Equipment LIFETIME WARRANTY OVER 90% HEAT RECOVERY LOW CARBON British manufacturing at its best EcoAir Box is a trademark of IPT +44 (01527) 492770 www.ecoairbox.co.uk

More information

T Series Direct Drive Operation, Startup and Maintenance Manual

T Series Direct Drive Operation, Startup and Maintenance Manual T Series Direct Drive Operation, Startup and Maintenance Manual Engineered for Reliability & Performance Project Name: Shipping Date: Model Number Serial Number Table of Contents Introduction and Definitions...

More information

1. Inspection and Maintenance

1. Inspection and Maintenance 1. and Maintenance Mandatory Be sure to inspect the inverter regularly and periodically to prevent it from breaking down because of the environment of use, such as temperature, humidity, dust and vibration,

More information

Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils

Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils Please consult your local representative or the factory for warranty issues. July 2017 DRS Marlo Coil Customer

More information

MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER

MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER MODEL TUB MODEL FEATURES Exhaust air up to 60,116 CFM in static pressure applications up to 1 w.g. Straight-through air flow design results in maximum exhaust efficiency Motor and drives are located outside

More information

ARROW INDUSTRIAL PRODUCTS

ARROW INDUSTRIAL PRODUCTS IP-2R ARROW INDUSTRIAL PRODUCTS For Applications in Industrial, Power Plant & Commercial Projects ARROW UNITED INDUSTRIES ARROW UNITED INDUSTRIES has specialized in the manufacturing of air control products

More information

Greater Cairo Foundries. Concentric Rubber Lined Butterfly Valves

Greater Cairo Foundries. Concentric Rubber Lined Butterfly Valves Greater Cairo Foundries مسابك القاهرة الكبرى Concentric Rubber Lined Butterfly Valves GCF Double Flanged Butterfly Valve Series 7100 for Water Works Application GCF butterfly Valve Series 7100 is a ductile

More information

CEILING CONCEALED LOSSNAY LGH-50RX3

CEILING CONCEALED LOSSNAY LGH-50RX3 LGH-RX3 VOLUME SIGN Control signal Heat recovery system Heat recovery module material Cladding Heat insulating material Motor Blower Filter material Operating environment (Supply air) Functions Weight

More information

HCD-230 Industrial Control Damper

HCD-230 Industrial Control Damper Application and Design Model is a heavy duty industrial control damper with a flanged frame. It is designed to control airflow and provide shut off in HVAC or industrial process control systems. A variety

More information

A. NU2035 HRV Specifications NU2035

A. NU2035 HRV Specifications NU2035 A. NU2035 HRV Specifications NU2035 B. Available Options CUSTOMIZATION: This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details

More information

This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details that follow.

This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details that follow. NU1030 HRV Specifications Available Options CUSTOMIZATION: This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details that follow.

More information

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile Centrifugal Cabinet s BCF Belt Drive Low-Profile May 2007 BCF Belt Drive Cabinet s Greenheck belt drive low-profile cabinet fans, BCF, are designed for efficiency and reliability in supply, exhaust or

More information

VAG Non-Return Valves

VAG Non-Return Valves VAG Non-Return Valves VAG SKR Slanted Seat Tilting disk Check Valve Shaft Bearing bush Disk Seat Nominal pressures PN 10, 16 Nominal diameters DN 200 1400 Fields of application: drinking water, preclarified

More information

Laboratory Exhaust Systems

Laboratory Exhaust Systems Laboratory Exhaust Systems Vektor -MH and Vektor -MD Mixed Flow High Plume and High Plume Dilution Blower August 2013 Vektor-MH High Plume and High Plume Dilution Blower Greenheck s Vektor-MH high plume

More information

CHBE320 LECTURE III ACTUATOR AND CONTROL VALVE SELECTION. Professor Dae Ryook Yang

CHBE320 LECTURE III ACTUATOR AND CONTROL VALVE SELECTION. Professor Dae Ryook Yang CHBE320 LECTURE III ACTUATOR AND CONTROL VALVE SELECTION Professor Dae Ryook Yang Spring 2018 Dept. of Chemical and Biological Engineering 3-1 Visit Actuator Road Map of the Lecture III + - Controller

More information

HEAT-RECOVERY UNITS WITH ENTHALPY/ROTARY HEAT EXCHANGER TECHNICAL MANUAL

HEAT-RECOVERY UNITS WITH ENTHALPY/ROTARY HEAT EXCHANGER TECHNICAL MANUAL UT REC - R HEAT-RECOVERY UNITS WITH ENTHALPY/ROTARY HEAT EXCHANGER TECHNICAL MANUAL 1 CONTENTS GENERAL FEATURES... 3 Scope of the unit... 3 Available configurations... 3 Description of the components...

More information

Tube Axial Inline Fans

Tube Axial Inline Fans Tube Axial Inline Fans Models TDI & TBI-CA Level 3 with Cast Aluminum Propeller Direct & Belt Drive Clean Air or Fume Exhaust July 2011 Features Tube Axial Inline Fans Greenheck s tube axial fans are the

More information

Baked Enamel, Epoxy, Hi Pro Polyester, Industrial Epoxy, Kynar/Hylar (70%) Permatector. Single or Reverse Flange 8 x 6 (203 x 178)

Baked Enamel, Epoxy, Hi Pro Polyester, Industrial Epoxy, Kynar/Hylar (70%) Permatector. Single or Reverse Flange 8 x 6 (203 x 178) Application and Design The is an extremely low leakage damper designed to meet the highest standards established for commercial control dampers. The is intended for application in medium to high pressure

More information

AMD-42V Air Measuring Station with VCD-42V Control Damper

AMD-42V Air Measuring Station with VCD-42V Control Damper Application and Design Construction Standard Optional Frame Material Galvanized Steel - Frame Material Thickness 16 ga. (1.5mm) 12 ga. (2.7mm) 14 ga. (2mm) Frame Type 5 in. x 1 in. hat channel - Blade

More information

AMD-42 Air Measuring Station with VCD-42 Control Damper

AMD-42 Air Measuring Station with VCD-42 Control Damper Application and Design W x H Construction Standard Optional Frame Material Galvanized Steel - Frame Material Thickness External Minimum Size 16 ga. (1.5mm) Internal Single Section Maximum Size Multiple

More information

FBV-43. Vertical Face & Bypass Control Damper Ultra Low Leakage Aluminum Frame Construction. Application and Design. Size Limitations.

FBV-43. Vertical Face & Bypass Control Damper Ultra Low Leakage Aluminum Frame Construction. Application and Design. Size Limitations. Application and Design The is a vertical style face and bypass low leakage damper. This model is intended for application in medium to high pressure and velocity systems. Smooth profile extruded aluminum

More information

Installation, Operating and Maintenance Instructions Retractable Door / Art.-Nr.:

Installation, Operating and Maintenance Instructions Retractable Door / Art.-Nr.: Installation, Operating and Maintenance Instructions Retractable Door 06.2008 / Art.-Nr.: 1 818 024 ENGLISH CONTENTS PAGE 1 SAFETY REQUIREMENTS 3 1.1 Symbols and key words used 3 1.2 Designated use 3 1.3

More information

Chapter 11: Valves and Actuators with the NAMUR-interface

Chapter 11: Valves and Actuators with the NAMUR-interface Right of authorship: the content of the training (wording, drawings, pictures) are owned by the author. Any utilization except for individual use is allowed only after permission of the author. Valves

More information

Zero Leakage Isolation Damper

Zero Leakage Isolation Damper SPECIFICATION The damper casing is formed from 3.0 mm thick sheet steel into a rigid channel section to ensure proper alignment of blades and shafts. Where circular dampers are required, additional spigot

More information

Fire Block and Pressed Steel Grilles

Fire Block and Pressed Steel Grilles September 2010 Fire Block and Pressed Steel Grilles Fire Block FB60 Sodium silicate based intumescent material. Provides the lowest activation temperature of any intumescent material at degrees C. It is

More information

VAV TERMINAL UNITS. VVD VAV Diffusers

VAV TERMINAL UNITS. VVD VAV Diffusers Introduction ASLI VAV diffusers, VVD are variable air volume diffuser for supply air in variable air volume system. In many conventional HVAC systems, multiple work spaces are controlled by a single thermostat.

More information

WE GUIDE AIR LOUVERS

WE GUIDE AIR LOUVERS WE GUIDE AIR LOUVERS index >> SAND TRAP LOUVERS - STL / STLC 01-02 >> 2 INCH EXHAUST AIR LOUVERS - EAL - 2 03 >> 4 INCH EXHAUST AIR LOUVERS - EAL - 4 04 >> GRAVITY AIR LOUVERS - GAL 05 >> FRESH AIR LOUVERS

More information

Laminar ceilings, exhaust columns, exhaust grilles

Laminar ceilings, exhaust columns, exhaust grilles Laminar ceilings, exhaust columns, exhaust grilles 1 Table of Contents: 1. Laminar ceilings general information... 3 2. Laminar ceilings design and operation principles... 4 3. Parameters of air in the

More information

This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details that follow.

This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details that follow. NU2540 ERV Specifications Available Options CUSTOMIZATION: This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details that follow.

More information

AIR-TO-AIR HEAT EXCHANGERS MODEL EQ INSTALLATION & MAINTENANCE

AIR-TO-AIR HEAT EXCHANGERS MODEL EQ INSTALLATION & MAINTENANCE AIR-TO-AIR HEAT EXCHANGERS MODEL EQ INSTALLATION & MAINTENANCE ENGLISH TEC-1574-V.3-201806-EN ADDRESS AND CONTACT DATA Heatex AB Bronsyxegatan 13 S-213 75 MALMÖ Sweden Telephone: +46 410 710 500 info@heatex.com

More information

MODELS UBB & UBX UPBLAST PROPELLER ROOF EXHAUSTERS BELT AND DIRECT DRIVE

MODELS UBB & UBX UPBLAST PROPELLER ROOF EXHAUSTERS BELT AND DIRECT DRIVE BELT AND DIRECT DRIVE MODEL FEATURES Exhaust air up to 78,000 CFM in static pressure applications up to 1/2 w.g. Straight-through air flow design results in maximum exhaust efficiency Belt drives permit

More information

AIR-TO-AIR HEAT EXCHANGERS MODEL Q2 INSTALLATION & MAINTENANCE

AIR-TO-AIR HEAT EXCHANGERS MODEL Q2 INSTALLATION & MAINTENANCE AIR-TO-AIR HEAT EXCHANGERS MODEL Q2 INSTALLATION & MAINTENANCE ENGLISH TEC-1337 Ver 2-2016-06-10 ADDRESS AND CONTACT DATA Heatex AB Bronsyxegatan 13 S-213 75 MALMÖ Sweden Telephone: +46 410 710 500 info@heatex.com

More information

AIR-TO-AIR HEAT EXCHANGERS MODEL EQ INSTALLATION & MAINTENANCE

AIR-TO-AIR HEAT EXCHANGERS MODEL EQ INSTALLATION & MAINTENANCE AIR-TO-AIR HEAT EXCHANGERS MODEL EQ INSTALLATION & MAINTENANCE ADDRESS AND CONTACT DATA DECLARATION OF INCORPORATION DISCLAIMER Heatex AB Bronsyxegatan 13 S-213 75 MALMÖ Sweden Telephone: +46 410 710 500

More information

SECTION CONTROL DAMPERS

SECTION CONTROL DAMPERS SECTION 23 09 13.43 - CONTROL DAMPERS PART I - GENERAL 1.1 SECTION INCLUDES A. Airfoil Dampers, Heavy Duty Galvanized Steel B. Thermally Insulated Dampers, Heavy Duty Galvanized Steel C. Airfoil Dampers,

More information

Type TVT FOR NORMAL AND HIGH VOLUME FLOW RATE RANGES AND LOW-LEAKAGE SHUT-OFF

Type TVT FOR NORMAL AND HIGH VOLUME FLOW RATE RANGES AND LOW-LEAKAGE SHUT-OFF Type TVT FOR NORMAL AND HIGH VOLUME FLOW RATE RANGES AND LOW-LEAKAGE SHUT-OFF Rectangular VAV terminal units for standard applications regarding the supply air or extract air control in variable air volume

More information

Exhaust hose reels. Diversified Air Systems, Inc. Superior technology generating substantial operating savings. Car and truck dealerships

Exhaust hose reels. Diversified Air Systems, Inc. Superior technology generating substantial operating savings. Car and truck dealerships Diversified Air Systems, Inc. Exhaust hose reels Car and truck dealerships RV, off-road maintenance shops Motorcycle and snowmobile dealerships Diesel fumes and smoke exhaust Spring operation or motorized

More information

MODEL UBSRD REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTER

MODEL UBSRD REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTER MODEL UBSRD REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTER MODEL FEATURES Exhaust air up to 52,000 CFM in static pressure applications up to 3/4 w.g. Motor and drives are located outside of the exhaust

More information

Sidewall Propeller Fans Direct Drive. Exhaust / Supply

Sidewall Propeller Fans Direct Drive. Exhaust / Supply Sidewall Propeller Fans Direct Drive / February 2009 Sidewall Propeller Fans Greenheck s sidewall propeller fan line is the ideal choice for factory and warehouse applications where high volumes of air

More information

Laboratory Exhaust Systems

Laboratory Exhaust Systems Laboratory Exhaust Systems Vektor -HS, Vektor -MS and Vektor -CS with Variable Geometry Nozzle September 017 Vektor -HS, Vektor -MS and Vektor -CS Greenheck s Variable Geometry Nozzle exhaust systems allow

More information

Rotary heat exchanger EURA, 20 53

Rotary heat exchanger EURA, 20 53 Rotary heat exchanger EURA, 0 5 Fig. Adjustment At a constant speed, check that the rotor is rotating in the right direction. The direction of rotation is indicated on the casing. If the purging sector

More information

ROTARY EXCHANGERS FOR HEAT RECOVERY

ROTARY EXCHANGERS FOR HEAT RECOVERY KASTT spol. s r. o. phone: +420 495 404 011 air conditioning design, production, installation and servicing 495 404 010 air conditioning, M&R, technological units fax: +420 495 406 544 Jižní 870, 500 03

More information

MODELS STXD & STXDe DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS

MODELS STXD & STXDe DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS MODELS & e DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS MODEL DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER MODEL FEATURES Exhaust air up to 4,780 CFM in high static pressure applications up to 1-1/2 w.g. Attractive

More information

CONTROL DAMPERS. Model Model 1370CB. Model 1380CB. Model 1390CB B7

CONTROL DAMPERS. Model Model 1370CB. Model 1380CB. Model 1390CB B7 CONTROL DAMPERS MODEL 1380 HIGH PERFORMANCE ACKDRAFT DAMPER EXTRUDED ALUMINUM HEAVY DUTY Model 1380 is a high performance extruded aluminum gravity operated backdraft damper for use in medium to heavy

More information

Exhaust hose reels. Diversified Air Systems, Inc. Superior technology generating substantial operating savings. Car and truck dealerships

Exhaust hose reels. Diversified Air Systems, Inc. Superior technology generating substantial operating savings. Car and truck dealerships Diversified Air Systems, Inc. Exhaust hose reels Car and truck dealerships RV, off-road maintenance shops Motorcycle and snowmobile dealerships Diesel fumes and smoke exhaust Spring operation or motorized

More information

Introduction to Johnson Controls Dampers

Introduction to Johnson Controls Dampers Damper and Actuator Product Guide 268.1 Damper Engineering Section Product Bulletin Issue Date 1297 Introduction to Johnson Controls Dampers For over 100 years, Johnson Controls has been the industry leader

More information

AMD-42-TD. Thermal Dispersion Air Measuring Station with VCD-42 Control Damper. Application and Design. Ratings. Features and Control Options

AMD-42-TD. Thermal Dispersion Air Measuring Station with VCD-42 Control Damper. Application and Design. Ratings. Features and Control Options Application and Design Thermal Dispersion Air Measuring Station with VCD-42 Control Damper The combines the functionality of a highly accurate thermal dispersion airflow measuring station and a low leakage

More information

POWERS Controls No. 4 Pneumatic Damper Actuator

POWERS Controls No. 4 Pneumatic Damper Actuator POWERS Controls No. 4 Pneumatic Damper Actuator Technical Instructions Document No. 155-032P25 AP 331-2 Actuator Assembly 331-2929 Typical Actuator Assembly 331-2904 Typical Actuator Assembly 331-3000

More information

Axial Propeller Panel Fans, PAF-Series

Axial Propeller Panel Fans, PAF-Series Axial Propeller Panel Fans, PAF-Series TABLE OF CONTENTS 3 Introduction 4 Certifications & Listings 4 Options & Accessories 9 Motor Availability 11 Direct Drive Dimensional & Performance Data 14 Belt Drive

More information

MODULAR AIR HANDLING UNITS GAH SERIES

MODULAR AIR HANDLING UNITS GAH SERIES MODULAR AIR HANDLING UNITS GAH SERIES 15 Models with Air Flows from 2,250 Cu.m/hr upto 77,800 Cu.m/hr Suitable for both Standard and District Cooling Applications GAH-TC-10-13 CONTENTS Design 2 Various

More information

GEA filter program for turbo-machines. Gas turbines, compressors, motors and intake systems. Application brochures

GEA filter program for turbo-machines. Gas turbines, compressors, motors and intake systems. Application brochures GEA filter program for turbo-machines Gas turbines, compressors, motors and intake systems Application brochures engineering for a better world GEA Heat Exchangers Pressure drop Efficiency Air Eco2nomy

More information

Calculation of external available Pressure. [m/s] 0,41 0,62 0,82 1,03 1,23 1,44 1,64 1,85 2,05 2,47 2,88 3,29 3,7

Calculation of external available Pressure. [m/s] 0,41 0,62 0,82 1,03 1,23 1,44 1,64 1,85 2,05 2,47 2,88 3,29 3,7 Calculation of external available Pressure Page 1 Size: 1 Air flow volume [m³/h] 4 6 8 1 12 14 16 18 2 24 28 32 36 1. Criterion flow velocity (Ref. 2 C) Do not design units in conditions acc. to white

More information

VCD-23. Flange Options. Size Limitations

VCD-23. Flange Options. Size Limitations Application and Design The series is a ruggedly built low leakage control damper intended for application in low to medium pressure and velocity systems. A wide range of electric and pneumatic actuators

More information

Variable Air Volume Dampers

Variable Air Volume Dampers OVAV 2000 SERIES OPTIMA VAV DAMPERS Overview OPTIMA make Variable Air Volume (OVAV) box is a part of an Air Conditioning system. It is located inside the duct work. VAV Dampers are designed to control

More information

ELTAFANTECH Air Handling Unit 700 up to 42,000 CFM

ELTAFANTECH Air Handling Unit 700 up to 42,000 CFM an ELTA GROUP company ELTAFANTECH 700 up to 42,000 CFM INNOVATIVE Design & Performance INTRODUCTION There are 24 standard sizes of optimally engineered s to handle air volumes from 700 CFM to 42,000CFM.

More information

Roof Upblast and Sidewall Exhaust

Roof Upblast and Sidewall Exhaust XRUB, XRUD, XSEB, XSED, and XRUBS models are listed for electrical (UL/C-UL US 705) File no. E40001 and for grease removal (UL/C-UL US 762) File no. MH11745. Accurex, LLC certifies model XRUB, XRUD, XSEB,

More information

Fire Block and Pressed Steel Grilles

Fire Block and Pressed Steel Grilles Catalogue Fire Block and Pressed Steel Grilles Fire Block FB60 Fire Block FB120 www.air-diffusion.co.uk sales@air-diffusion.co.uk Fire Block FB60 Features Fits directly into ducts, doors or wall apertures

More information

ULTRA LOW ENERGY. VHR Void Series W/I/s TOTAL SFP Typical. Made in the UK. VHR Void Mounted Heat Recovery Units VHR PERFORMANCE OVERVIEW:

ULTRA LOW ENERGY. VHR Void Series W/I/s TOTAL SFP Typical. Made in the UK. VHR Void Mounted Heat Recovery Units VHR PERFORMANCE OVERVIEW: VHR Void Mounted Heat Recovery Units TM.72 W/I/s TOTAL SFP Typical General: Units shall be manufactured from high quality galvanized sheet steel with stainless steel drain trays, acoustic, non-hygroscopic

More information

High Performance Axial Fans

High Performance Axial Fans High Performance Axial Fans Model RA Standard and High Temperature High Efficiencies Low Sound January 2014 High Performance Axial Fans Greenheck s model RA, high performance, direct-driven axial fans,

More information

Industry best 5 year fan housing warranty, 1 year motor warranty

Industry best 5 year fan housing warranty, 1 year motor warranty MEL FEATURES Exhaust air up to 28,000 CFM in high static pressure applications up to 1-1/4 w.g. Attractive spun aluminum exterior Belt drives permit easy performance adjustments when needed Non-overloading

More information

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

VAV terminal units. Type TVM. For dual duct systems PD TVM 1 X X testregistrierung VAV terminal units Type Variant -S Rectangular connection on the room end For dual duct systems VAV dual duct terminal units for dual duct systems with variable volume flows in buildings

More information

Turbogenerators. With Top Performance for Steam and Gas Applications. Specifically tailored 4-pole Synchronous Turbogenerators

Turbogenerators. With Top Performance for Steam and Gas Applications. Specifically tailored 4-pole Synchronous Turbogenerators Turbogenerators With Top Performance for Steam and Gas Applications Specifically tailored 4-pole Synchronous Turbogenerators siemens.com / automation 2 Top Performance Turbogenerators for Steam and Gas

More information

NH 3. Evaporator. Ammonia Applications Tons MANP

NH 3. Evaporator. Ammonia Applications Tons MANP NH 3 Evaporator Ammonia Applications 12-108 Tons > > Used for medium TO large Industrial Ammonia applications Manufactured with Stainless steel tubes. The Global Leader In Heat Exchange Technology With

More information

CEILING CONCEALED LOSSNAY LGH-25RX3

CEILING CONCEALED LOSSNAY LGH-25RX3 VOLUME SIGN Control signal Heat recovery system Heat recovery module material Cladding Heat insulating material Motor Blower Filter material Operating environment (Supply air) Functions Weight Serial single

More information

PVHRU Max Quiet. Engineering Solutions. Packaged Void Heat Reclaim Unit. Acoustic Testing Laboratory College of Science & Technology

PVHRU Max Quiet. Engineering Solutions. Packaged Void Heat Reclaim Unit. Acoustic Testing Laboratory College of Science & Technology AIR HANDLERS LTD PVHRU Max Quiet Packaged Void Heat Reclaim Unit 1262 Acoustic Testing Laboratory College of Science & Technology Engineering Solutions The Company Air Handlers has been trading since May

More information

Combustion gas damper EKO-JB

Combustion gas damper EKO-JB EKO-JB Description The EKO-JB combustion is a Class E6 type-approved damper intended to prevent the spread of combustion gases in ventilation ducting that penetrates fire rated compartment wall or floor

More information

Installation, Operation and Maintenance Instructions. ERV1500e ERV2000e ERV3000e

Installation, Operation and Maintenance Instructions. ERV1500e ERV2000e ERV3000e Installation, Operation and Maintenance Instructions ERV500e ERV000e ERV000e ERV000e ERV500e ERV000e Table of Contents Safety Considerations..................................................................

More information