Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

Similar documents
3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

QT-III Cold Shrink Silicone Rubber

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

3M Cold Shrink QT-III Silicone Rubber Termination

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

Cold Shrink QS T Trifurcating Transition Splice Kit

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Mechanical Shearbolt Connectors, QCI Series

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

SLiC Aerial Terminal and Spiral End Seal for use with AMP* Quiet Front Terminal Blocks

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

QTII (X) Series Silicone Rubber Cold Shrink Termination Kits

ELB ELB

Branch Splice QS-2001B

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

3M Electrical Markets Division. Rubber, Mastic and Specialty Tapes Application Guide. Choose the. Right Tape. for your. Electrical Project

Installation Instruction EPP /92

Installation Instructions

3M Cold Shrink Splice Kits, QS T Series

(K),(M),(P)489TB/G Up to 42 kv

3M Locator Plate

Cable Ties. Data Sheet

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)

ELB ES. Product Installation Instructions

3M Locator Plate

3M Products for Electrical Networks Wind Farm Capabilities. Leading Edge. Electrical Solutions for. Wind Farms

I nstallation I nstruction Heatshrink Term ination For 3 Core Polym eric Cables 7.2 kv to 3 6 kv

(K),(M)430TB/G Up to 36 kv

3 Reenterable Encapsulated PST Dome Closure

3M Cross-Connect Cabinets 4220SVC and 4220SVE Tall Skirt Installation Guide

Installation Instruction EPP /02. Terminations for Screened Single Core Polymeric Insulated Cables up to 24 kv without Armour

3M Electrical Tapes Product Selection Guide. Insulate & Protect. with Quality Tapes. Preliminary

Door Edge Protection Film 36 inch

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900 µm Instructions

3M Ladder Kit 3M710/MS 2 -TMK-LK

710 Splicing Rig. Instructions. January E

INSTALLATION INSTRUCTION

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

HVS S 15kV Class

High Voltage Joints and Terminations up to 72,5 kv 145 kv

3M Cushion-Mount Plus Plate Mounting Tapes with Easy Mount Adhesive

Product Number

3M Closure System 2-Type Cover (505)

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900-µm. Instructions. October C

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

3M Cable Ties Product Guide. Made in USA. & Plenum Rated

3M Mini D Ribbon (MDR) Cable Assembly.050 High Speed Video Data Transmission System, 50 Position 14X50-SZWB-XXX-0NC

3M No Polish LC/APC Connector SM, Angle Splice, 250/900 µm 8830-APC/AS

Cold Shrink Silicone Rubber Termination Kit QT-III 7620-S, 7690-S and 7680-S Series kv

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

C Power Connection Kit

3M Pleated Foil I/O Cable Assemblies MDR Series

Installation Instructions

Repair Method for 3M Resilient Floor Protection System

GM Specification Annual Test Data

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

SLiC Aerial Closures

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

GM Specification Annual Test Data

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

K SERIES PUSH ON & BULLET TERMINALS

3M Fiber Dome Closure FDC 10

Data Sheet July For RoHS information, please visit

3 740 Wrist strap + shoe tester

Model 1100B CHG Terminator. Installation Instructions

Volition. VF-45 Quick Install kit. and Maintenance Cleaning Kit. 3Innovation

WRSS Wraparound Repair Sleeve Installation Instructions

3M No Polish LC Connector SM and MM, Flat Splice, 250/900 µm

POWERHEAT TYPE AHT TERMINATION INSTRUCTIONS. Ref TK/AHT Issue C Date 16 August 1999

CS Fiber Optic Splice Case. Instruction

Transcription:

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions Class I Indoor Termination Voltage Designation: 12/20(24) kv Kit Contents: 1 HeatShrinkBreakoutBootAssembly 3 HeatShrinkBindingSleeves 3 Heat Shrink Core Re-jacketing Sleeve Assembly 6 Tape Strip, Silicone 3 Cold Shrink Silicone Rubber Termination Assembly 9 Mastic Seal Strip 1 Roll Tinned Copper Ground Braid ( 2.25 M ) 1 Roll Vinyl Tape 6 Constant-Force Spring (Small) 1 Cable Preparation Kit 1 Constant-Force Spring (Large) 1 Installation Instructions Size Selection (X) Termination Assembly Body Size Cable Insulation O. D. Range mm ( Inch ) ( ) J 16 28 (0.64 1.12) ( ) K 21 35 (0.84 1.38) ( ) L 27 46 (1.08 1.80) ( ) M 33 53 (1.31 2.10) Final Determining Factor = Cable Insulation Diameter Table 1 CAUTION: Working around energized high voltage systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling high voltage electrical equipment. De-energize and ground all electrical systems before installing this product. 3M QTII Silicone Rubber Termination 3/C Copper Tape Shield Armored Cable

A. Prepare Cable 1. Determine cable jacket removal length required for correct core ( phase ) spacing and bolted terminal lug connections ( [A] + [B], Figure 1 ), based on the longest phase to be connected. Allow for dimension [C] as needed. Note: Individual core length and separation dimensions vary according to specific installation and equipment design requirements. They must, therefore, be determined by the installer and must conform to accepted engineering practices. Supplied materials allow for a maximum [A] + [B] dimension of 1.5 M. See your local 3M Representative for information regarding longer core length requirements. 2. Remove cable jacket, armor, bedding ( inner sheath ) and core fillers according to Figure 1 dimensions and equipment requirements. Secure copper tape shield ends with a temporary band of vinyl tape (! Figure 1 ). 3. Using light tension, apply one mastic seal strip around cable jacket 25 mm ( 1.0 ) below the cut edge ( " Figure 1 ). Figure 1 [C] [B]! Temporary Vinyl Tape Band Jacket Removal Length [A] + [B] Maximum 1.5 M [A] Copper Tape Shield 10 mm (0.40 ) Bedding Armor 50mm(2.0 ) 25 mm (1.0 ) Do not attach cable mounting bracket within 150 mm ( 6.0 ) of jacket edge. " Mastic Seal Strip 2

B. Attach Metallic Shield Grounding Braids 1. Cut supplied tinned copper grounding braid into three equal 750 mm ( 30.0 ) lengths. Expand each braid end for a distance of 300 mm ( 12.0 ) (! Figure 2 ). Figure 2 Expand! Ground Braid 300 mm ( 12.0 ) 2. Position one expanded ground braid end over each cable core shield as shown in Figure 3. Using vinyl tape bands, secure upper braid end to copper tape shielding 200 mm ( 8.0 ) beyond armor edge ( jacket edge for non-armored cable ) (! Figure 3 ). Secure to cable jacket 15 mm ( 0.60 ) below mastic seal strip ( " Figure 3 ). Figure 3 " 15 mm (0.60 ) 200 mm (8.0 ) Mastic Seal Strip Vinyl Tape Bands ( typical )! Ground Braid Over Copper Tape Shield No Vinyl Tape In This Area # Spring ( Small ) 2 nd Mastic Strip % $ Spring ( Large ) & Vinyl Tape 3. Connect ground braid ends to cable core metallic shields using small constant force springs ( # Figure 3 ). Armored cables: Connect three ground braids to cable armoring using one large constant force spring ( $ Figure 3 ). Following application, cinch ( twist with hand ) each spring to tighten. 4. Apply a second mastic seal strip over ground braids and previously-applied mastic strip ( % Figure 3 ). 5. Apply two highly stretched half-lapped layers vinyl tape over mastic seal strips and constant force springs ( & Figure 3 ). 3

C. Install Heat Shrink Breakout Boot 1. Inspect breakout boot interior. Remove any contaminants that may be present. 2. Apply a single band of mastic around vinyl tape at position shown (! Figure 4 ). Note: Disregard this step if using a breakout boot supplied with adhesive sealant. 3. Slide boot over cable as far as it will go ( " Figure 4 ). Using an appropriate torch, shrink breakout boot into final position. Figure 4 5mm(0.20 ) Mastic Band! Vinyl Tape " 4

D. Install Heat Shrink Core Insulating Sleeves 1. From the chart below, determine the correct [A] dimension for the QT-II Termination being installed. (X) QTII Termination Assembly Dimension [A] J4S 195 mm ( 7.7 ) K4S 195 mm ( 7.7 ) L4S 205 mm ( 8.1 ) M4S 205 mm ( 8.1 ) 2. Place a vinyl tape marker on each cable core shield at dimension [X] (! Figure 5 ). Note: [X] = [A] + [B] ( Lug depth ) as in Figure 5. 3. Determine distance [S] in Figure 5. Be sure to include breakout boot finger length in measurement ( ", Figure5). 4. If [S] is 450 mm ( 17.7 ) or less, continue with the installation at Step 5. For longer [S] dimensions, go to Step 11. Figure 5 [S] [X] Include in [S] Dimension " [A] [B] Vinyl Tape over Constant Force Spring! Marker Tape 5. Cut three phase re-jacketing sleeves to dimension [S]. Caution: Heat shrink sleeve end cuts must be straight and smooth ( No rough or jagged edges ). Figure 6 5mm(0.20 )! Mastic Band 6. Wrap a mastic sealing band around the end of one breakout boot finger (! Figure 6 ). 5

7. Position one heat shrink re-jacketing sleeve over one shielded cable core and breakout boot finger ( Figure 7 ). Note: Working on one core at a time will prevent unwanted adhesion between mastic sealing bands. Figure 7 Heat Shrink Sleeve 8. Repeat Steps 6. and 7. for the remaining two cable cores ( Figure 8 ). Figure 8 9. Align each re-jacketing sleeve end with a termination marker tape (! Figure 9 ) and shrink into position. Note: Maintain sleeve-to-marker tape edge alignment while shrinking. Shrink sleeves by progressing down from the marker tape edges to the breakout boot fingers. Never shrink both ends before moving to the center region of the heat shrink sleeve. Figure 9 Vinyl Tape Marker Under Heat Shrink Sleeve Heat Shrink Sleeve! Align Sleeve and Marker Tape Edges 10. Allow heat shrink re-jacketing sleeves to cool before proceeding. Go to Section E., Page 8. 6

11. For [S] dimensions longer than 450 mm ( 17.7 ) ( As measured in Figure 10 below ), add 100 mm ( 4.0 ) to [S]. 12. Cut three heat shrink re-jacketing sleeves to dimension [ S + 100 mm ( 4.0 ) ]. Caution: Heat shrink sleeve end cuts must be straight and smooth ( No rough or jagged edges ). 13. Wrap a single mastic band around the end of one breakout boot finger (! Figure 10 ). Figure 10 [S] 5mm(0.20 )! Mastic Band 14. Position one heat shrink re-jacketing sleeve over one breakout boot finger and shielded cable core. Note: Working on one core at a time will prevent unwanted adhesion between mastic sealing bands. 15. Repeat Steps 13. and 14. on remaining two cable cores ( Figure 11 ). Extended length re- Note: Position three phase re-jacketing sleeves completely over breakout boot fingers. jacketing sleeves will cover previously applied termination marker tapes. 16. Starting at the breakout boot fingers, shrink re-jacketing sleeves into final position. Note: Shrink from the lower end ( over breakout boot fingers ) to the upper end. Never shrink both ends before moving to the center region of the heat shrink sleeve. Figure 11 Sleeves Completely Cover Breakout Boot Fingers 17. Allow heat shrink sleeves to cool before proceeding. 7

18. Mark three installed re-jacketing sleeves at dimension [X]. Note: [X] = [A] + [B] ( Lug Depth ) as in Step D.1. and Figure 12. Remove excess sleeve length to dimension [X]. Caution: Do not cut into cable metallic shielding while removing excess re-jacketing sleeve material. Figure 12 [X] [A] [B] Mark Sleeves at Dimension [X] Remove E. Install QT-II Cold Shrink Termination Assemblies 1. Prepare cable phase ends according to dimensions shown ( Figure 13 ). Allow for crimp growth when using aluminum connectors or lugs. Figure 13 D C A B Re-jacketing Sleeve J-4S K-4S L-4S J-4S A 195 mm ( 7.7 ) 195 mm ( 7.7 ) 205 mm ( 8.1 ) 205 mm ( 8.1 ) B Lug Depth Lug Depth Lug Depth Lug Depth C 60 mm ( 2.4 ) 60 mm ( 2.4 ) 60 mm ( 2.4 ) 60 mm ( 2.4 ) D 40 mm ( 1.6 ) 40 mm ( 1.6 ) 40 mm ( 1.6 ) 40 mm ( 1.6 ) 8

2. Secure each metallic shield end with a single band of vinyl tape (! Figure 14 ). Center tape band on metallic shield edge. Note: Do not extend vinyl tape wrap beyond width of tape roll. 3. From the free end of each installed shield grounding braid, cut a single, 150 mm ( 6.0 ) long, piece. Note: In some kits, these shorter braid lengths may be supplied pre-cut. 4. Fully expand the diameter of each short braid. Slide one braid over each cable phase metallic shield ( " Figure 14 ). Figure 14! Vinyl Tape Band Re-jacketing Sleeve " Short Length Ground Braid 5. Secure ground braids to metallic shields using supplied constant force springs (! Figure 15 ). Note: Make sure braid and springs are applied over cable metallic shields ( Not over vinyl tape ). 6. Wrap a mastic seal strip band over applied ground braid 5mm ( 0.20 ) from re-jacketing sleeve edge ( " Figure 15 ). Figure 15! Constant Force Spring 5mm(0.20 ) Mastic Band " Applied Constant Force Spring 9

7. Apply two highly stretched half-lapped layers vinyl tape over springs and mastic bands ( Figure 16 ). Note: Do not extend vinyl tape wrapping more than 5 mm ( 0.20 ) beyond mastic band and ground braid leading edge (! and " Figure 16 ). Figure 16 Max. 5 mm ( 0.20 )! " Max. 5 mm ( 0.20 ) Vinyl Tape 8. Place a termination installation marker tape over each re-jacketing sleeve 100 mm from semi-con screen edge ( Figure 17 ). Figure 17 100 mm (3.9 ) Marker Tape Semi-con Screen 9. Position heat shrink binding sleeves over ends of applied ground braids (! Figure 18 ). Shrink sleeves into position. Figure 18! Heat Shrink Binding Sleeve 10

10. Special Applications For terminal lug pads that will not pass through the interior of the termination assembly support core. Slide the termination assemblies over the cable phase legs before installing the lugs. Position each termination assembly with it s loose core ribbon directed toward the open, lug end, of the cable ( Reference!, Figure21 as needed ). Continue with lug installations. Normal Applications Install Terminal Lugs: For Aluminum Conductors - Thoroughly wire brush conductor strands to remove aluminum oxide layer. Immediately insert conductor into terminal lug barrel as far as it will go. Ensure that each lug face is parallel to it s intended connection interface (! Figure 19 ). Figure 19 Last Crimp " First Crimp! 11. Crimp terminal lugs according to manufacturer recommendations. Start at the upper end as shown ( " Figure 19 ). Remove all traces of oxide inhibitor that may have come out of the lug barrels during crimping. Thoroughly clean primary insulation and lug barrel area using solvent wipes from supplied cable preparation kit. Note: Avoid wetting cable semi-conductive layer with solvent. 12. Fill step at cable semi-con cut edge with silicone grease (! Figure 20 ). Figure 20 Cable Semi-con! Silicone Grease 11

13. Install QT-II Termination Assemblies. (a.) Position each termination assembly with it s loose core ribbon end directed toward the terminal lug (! Figure 21 ). (b.) Align base of termination ( not the plastic support core ) with installation marker tape as shown ( " Figure 21 ). (c.) Grasp the loose core ribbon and pull while unwinding it counter clock-wise around the cable end (! Figure 21 ). Note: Once the silicone rubber termination body has made adequate contact ( Approx. 25 mm or 1.0 ), release the assembly and continue unwinding the core. Do not pull or push on the assembly while unwinding. (e.) Remove the installation marker tape. Figure 21 " Termination Base Aligned With Marker Tape Edge Marker Tape Loose Core Ribbon! 14. Seal termination body to terminal lug barrel by applying at least two half-lapped layers Scotch No.70SiliconeTapeas shown (! Figure 22 ). Start, and finish, tape wrapping at the upper end of the terminal lug barrel. Figure 22! Silicone Tape 15. Collect shield-grounding braids together and connect to system ground (earth) according to normal practice. 12

3M and Scotch are trademarks of 3M Important Notice Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use. Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture as of the date of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any loss or damage arising from this 3M product, whether direct, indirect, special, incidental or consequential regardless of the legal theory asserted. Electrical Products Division 6801 River Place Blvd. Austin, TX 78726-9000 http://www.3m.com/elpd 3M 2002 QTII(X)4S-32H 13