QT-III Cold Shrink Silicone Rubber

Similar documents
3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

Cold Shrink QS T Trifurcating Transition Splice Kit

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

3M Cold Shrink QT-III Silicone Rubber Termination

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

QTII (X) Series Silicone Rubber Cold Shrink Termination Kits

3 Reenterable Encapsulated PST Dome Closure

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

CS Fiber Optic Splice Case. Instruction

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

8400 Series Fiber Distribution System

ELB ELB

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

SLiC Aerial Terminal and Spiral End Seal for use with AMP* Quiet Front Terminal Blocks

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

DOCUMENT OBSOLETE. Volition. VF-45 Socket Termination and Maintenance Cleaning Kits COOL HAND TOOLS. CLEAN UP YOUR ACT. VF-45 Socket Termination Kit

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

3M Mechanical Shearbolt Connectors, QCI Series

C Power Connection Kit

ELB ES. Product Installation Instructions

Branch Splice QS-2001B

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

Installation Instructions

3M Cold Shrink Splice Kits, QS T Series

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

3 TM Cold Applied Barrier Boot System

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

POWERHEAT TYPE AHT TERMINATION INSTRUCTIONS. Ref TK/AHT Issue C Date 16 August 1999

I nstallation I nstruction Heatshrink Term ination For 3 Core Polym eric Cables 7.2 kv to 3 6 kv

3M Locator Plate

3M Locator Plate

(K),(M)430TB/G Up to 36 kv

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

3M Products for Electrical Networks Wind Farm Capabilities. Leading Edge. Electrical Solutions for. Wind Farms

Installation Instructions

(K),(M),(P)489TB/G Up to 42 kv

3M Cushion-Mount Plus Plate Mounting Tapes with Easy Mount Adhesive

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

3M Mini D Ribbon (MDR) Cable Assembly.050 High Speed Video Data Transmission System, 50 Position 14X50-SZWB-XXX-0NC

Cold Shrink Silicone Rubber Termination Kit QT-III 7620-S, 7690-S and 7680-S Series kv

Effective May 2017 Supersedes December 2004 (S )

Effective November 2016 Supersedes February 2012 (S )

3M Closure System 2-Type Cover (505)

Kompensator External Low Voltage Heating Cable System

3M Cross-Connect Cabinets 4220SVC and 4220SVE Tall Skirt Installation Guide

Cable Ties. Data Sheet

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN


COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

3M Pleated Foil I/O Cable Assemblies MDR Series

HVS S 15kV Class

Installation Instruction EPP /92

Product Number

3M Ladder Kit 3M710/MS 2 -TMK-LK

3M Fiber Dome Closure FDC 10

INSTALLATION INSTRUCTION

Industrial, Heavy Insulated Mono-Tape. and Duo-Tape

Instructions for Wire Mesh Pulling Grips on Outside Plant and Indoor/Outdoor Fiber Optic Cable Best Practices

WRSS Wraparound Repair Sleeve Installation Instructions

Loadbreak Apparatus Connectors

Installation instruction PEM1150ENG

High Voltage Joints and Terminations up to 72,5 kv 145 kv

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900 µm Instructions

Operating voltage up to 5 kvdc Operating current up to 4,5 A 2-6 high voltage contacts Quick and easy assembling Protection class IP68 acc.

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

Transcription:

QT-III Cold Shrink Silicone Rubber 7600-T-3RJS Series 3/C Cabinet Termination Instructions Kit Contents: 3ÑSilicone Rubber Phase Re-jacketing Sleeve Assembly 3ÑCold Shrink Silicone Rubber Termination Assembly 1ÑRoll Tinned Copper Ground Braid 3ÑConstant-Force Spring 1ÑRoll Vinyl Tape 1ÑCable Preparation Kit 1ÑInstallation Instructions Termination Application Ranges (Final determining factor is cable insulation diameter. Listed insulation ranges allow +2.54 mm (0.10") for shielding.) Kit Number BIL Cable Insulation 3.3 kv 3.3 kv 5.0 kv 6.6 kv 6.6 kv 8.7 kv 10 kv 15 kv 15 kv 20 kv 25/28 kv (kv) Range [inch (mm)] (mm 2 ) (mm 2 ) (AWG) (mm 2 ) (mm 2 ) (AWG) (mm 2 ) (mm 2 ) (AWG) (mm 2 ) (AWG) IEC JIS AEIC JIS IEC AEIC IEC IEC AEIC IEC AEIC 7620-T95-3RJS 95 0.33 0.50 (8.40 12.7) 16 35 8 22 8 2 16 25 6 4 7621-T95-3RJS 95 0.50 0.70 (12.7 17.8) 50 95 38 60 1 3/0 35 70 2 2/0 10 50 16 25 7623-T95-3RJS 95 0.70 0.92 (17.8 23.4) 120 185 100 150 4/0 400 95 150 3/0 350 70 150 35 95 7624-T95-3RJS 95 0.92 1.18 (23.4 30.0) 240 300 200 250 500 750 185 300 400 600 185 300 120 185 7625-T95-3RJS 95 1.18 1.52 (30.0 38.6) 300 325 800 1000 750 1000 200 325 7621-T110-3RJS 110 0.50 0.70 (12.7 17.8) 50 95 38 60 1 3/0 14 38 35 70 2 2/0 10 50 16 25 2 1 7622-T110-3RJS 110 0.70 0.92 (17.8 23.4) 120 185 100 150 4/0 400 60 100 95 150 3/0 350 70 150 35 95 1/0 4/0 7624-T110-3RJS 110 0.92 1.18 (23.4 30.0) 240 300 200 250 500 750 150 250 185 300 400 600 185 300 120 185 250 450 7625-T110-3RJS 110 1.18 1.52 (30.0 38.6) 300 325 800 1000 300 325 750 1000 200 325 500 750 7622-T125-3RJS 125 0.70 0.92 (17.8 23.4) 120 185 100 150 4/0 400 60 100 95 150 3/0 350 70 150 35 95 1/0 4/0 25 70 7624-T125-3RJS 125 0.92 1.18 (23.4 30.0) 240 300 200 250 500 750 150 250 185 300 400 600 185 300 120 185 250 450 95 185 7625-T125-3RJS 125 1.18 1.52 (30.0 38.6) 300 325 800 1000 300 325 750 1000 200 325 500 750 240 300 7693-T150-3RJS 150 0.70 0.92 (17.8 23.4) 120 185 100 150 4/0 400 60 100 95 150 3/0 350 70 150 35 95 1/0 4/0 25 70 2 1/0 7694-T150-3RJS 150 0.92 1.18 (23.4 30.0) 240 300 200 250 500 750 150 250 185 300 400 600 185 300 120 185 250 450 95 185 2/0 250 7695-T150-3RJS 150 1.18 1.52 (30.0 38.6) 300 325 800 1000 300 325 750 1000 200 325 500 750 240 300 300 500 3/C Copper Tape Shield Cable 3/C Copper Tape Shield Armored Cable 3M Cold Shrink Silicone Rubber Cabinet-Mount Termination for 3/C Copper Tape Shield Cables with or without Ground Wires 78-8124-4070-5-A

1.0 Prepare Cable. 1.1 Determine phase (core) lengths required for correct phase spacing and bolted terminal lug connections ([A] + [B] Figure 1, according to the longest phase to be connected). Allow for dimension [C] as needed. Note: Individual phase length and separation dimensions vary according to specific installation and equipment design requirements. They must, therefore, be determined by the installer and must conform to accepted engineering practices. 1.2 Strip back cable jacket and armor according to equipment entrance bushing and cabinet configuration requirements. 1.3 Remove bedding (inner sheath), if present, and any remaining core fillers. Secure each copper tape shield end with a temporary band of vinyl tape (1 Figure 1). Figure 1 2 78-8124-4070-5-A

2.0 Attach Metallic Shield Grounding Braids. Figure 2,, yy zz 2.1 Cut supplied tinned copper grounding braid into three equal 2.0' (610 mm) lengths. Expand each braid end for a distance of 2.0" (51 mm) (2 Figure 2). 2.2 Attach shield ground braids: A. Position each expanded ground braid end over phase shielding as shown in Figure 3. B. Using vinyl tape bands, secure upper braid end to copper tape shielding 8.0" (203 mm) beyond cable breakout point. C. Connect expanded ground braid ends to copper tape shields using supplied constant-force springs. Following application, cinch (twist with hand) each spring to tighten. Figure 3 z 2.3 Apply two half-lapped layers vinyl tape over constant force springs and ground strap ends (➂ Figure 4). Figure 4,yz{ 78-8124-4070-5-A 3

3.0 Install Silicone Rubber Re-jacketing Sleeves. 3.1 From the chart below, determine the correct [A] dimension for the QT-III product being installed. Dimension [A] (According to QT-III Termination Product Number) 7620-T95-3RJS 7621-T95-3RJS 7623-T95-3RJS 7624-T95-3RJS 7625-T95-3RJS 7621-T110-3RJS 7622-T110-3RJS 7624-T110-3RJS 7625-T110-3RJS 7622-T125-3RJS 7624-T125-3RJS 7625-T125-3RJS 7693-T150-3RJS 7694-T150-3RJS 7695-T150-3RJS 6.25" (159 mm) 8.5" (216 mm) 7.0" (178 mm) 12.0" (305 mm) 3.2 Place a vinyl tape marker on each cable phase leg at dimension [X] (1 Figure 5). Note: [X] = [A] (From chart above) + [B] (Lug barrel depth). Allow for crimp growth when using aluminum lugs. Figure 5,yz 3.3 Determine required phase re-jacketing sleeve length ([S] Figure 5). 3.4 Using scissors, trim re-jacketing sleeve assembly to length required (Figure 6). Cut tubing and inner braid together. Note: Inner polyester braid should extend approximately 75 mm (3.0") beyond re-jacketing tube end before cutting. There is no need for termination-end braid exposure. Figure 6 4 78-8124-4070-5-A

3.5 Guide one re-jacketing sleeve assembly over each cable phase leg (Figure 7). Push sleeve assembly from above. Continuously guide the free end maintaining sleeve-to-cable-core alignment. Figure 7 3.6 Slide re-jacketing sleeve until inner polyester braid is within 2" (51 mm) of desired final location (near cable entrance gland). 3.7 Fold outer silicone tubing back on itself for 1" (25.4 mm) and trim off exposed polyester braid (Figure 8). Note: Do not damage silicone tubing while cutting. Sleeve assembly may be rotated to ease trimming. When doing so, rotate in the direction of the cable copper tape shield wrap. Figure 8 z 3.8 Slide re-jacketing sleeve assembly into desired final position. Pull folded sleeve section down onto cable phase shielding. Note: Re-jacketing sleeve upper end should now align with upper edge of previously-installed marker tape (2 Figure 9). Minor tube adjustments can be made as needed. Figure 9 z 78-8124-4070-5-A 5

4.0 Install QT-III Cold Shrink Termination Assemblies. 4.1 Prepare cable phase legs according to dimensions shown (Figure 10). Figure 10 7620-T95-3RJS 7621-T95-3RJS 7623-T95-3RJS 7624-T95-3RJS 7625-T95-3RJS 7621-T110-3RJS 7622-T110-3RJS 7624-T110-3RJS 7625-T110-3RJS 7622-T125-3RJS 7624-T125-3RJS 7625-T125-3RJS 7693-T150-3RJS 7694-T150-3RJS 7695-T150-3RJS A 6.25" (159 mm) 8.5" (215 mm) 7.0" (179 mm) 12.0" (305 mm) B Lug Depth* Lug Depth* Lug Depth* Lug Depth* C 1.5" (38.1 mm) 2.5" (64 mm) 1.5" (38.1 mm) 2.5" (64 mm) D 0.75" (19.1 mm) 1.25" (32 mm) 0.75" (19.1 mm) 1.25" (32 mm) *Allow for crimp growth when using aluminum lugs and connectors. 4.2 Secure re-jacketing sleeve and cable copper tape shield ends with two half-lapped layers of vinyl tape (1 Figure 11). Start taping.75" (19 mm) over re-jacketing sleeve, extend.25" (6 mm) over cable semi-con and return to starting point. Note: Do not exceed.25" (6 mm) semi-con overlap. Figure 11 6 78-8124-4070-5-A

4.3 Place a termination installation marker tape at position [M] (Figure 12). Figure 12 7620-T95-3RJS 7621-T95-3RJS 7623-T95-3RJS 7624-T95-3RJS 7625-T95-3RJS 7621-T110-3RJS 7622-T110-3RJS 7624-T110-3RJS 7625-T110-3RJS 7622-T125-3RJS 7624-T125-3RJS 7625-T125-3RJS 7693-T150-3RJS 7694-T150-3RJS 7695-T150-3RJS M 4.0" (102 mm) 5.0" (127 mm) 4.0" (102 mm) 5.0" (127 mm) 4.4 Install terminal lugs. Note: Special Case When lug spade dimension is larger than inside diameter of white plastic termination core, position termination assemblies over cable phase legs prior to installing lugs. Remove inner red shipping core from each termination assembly by pulling and unwinding the loose red core ribbon. Position one termination over each cable phase leg. Each termination assembly must be positioned with its loose white core ribbon end directed toward the open (cut) end of the cable. Continue with lug installations. A. For Aluminum ConductorsÑThoroughly wire brush conductor strands to remove aluminum oxide layer. Immediately insert conductor into terminal lug barrel as far as it will go. B. Ensure that each lug face is parallel to equipment bushing or lug connection interface (➂ Figure 13). Figure 13 C. Crimp terminal lug according to manufacturer recommendations. Start at the upper end as shown (➃ Figure 13). Remove all traces of oxide inhibitor that may have come out of lug barrel during crimping. D. Thoroughly clean primary insulation and lug barrel area using solvent wipe from supplied cable preparation kit. Note: Do not allow solvent contact with cable semi-conductive screen. 78-8124-4070-5-A 7

4.5 Install QT-III Termination assemblies. A. Remove the inner red shipping core from the termination assembly by pulling and unwinding the loose red core end. B. Position the termination assembly with the loose white core ribbon directed toward the terminal lug. C. Align the base of the termination (not the plastic core) with the installation marker tape as shown (➄ Figure 14). D. Grasp the loose white core ribbon. Pull and unwind counter clock-wise around cable phase end (➅ Figure 14). Note: After the silicone rubber termination makes adequate contact (approximately 1.0" or 25 mm), release the assembly and continue unwinding the core. Do not pull or push on the assembly while unwinding. E. Remove the installation marker tape. 4.6 Connect cable ground wires and shield-grounding braids to system ground (earth) according to normal practice. Figure 14 3M is a registered trademark of 3M. IMPORTANT NOTICE All statements, technical information and recommendations related to the Seller s products are based on information believed to be reliable, but the accuracy or completeness thereof is not guaranteed. Before utilizing the product, the user should determine the suitability of the product for its intended use. The user assumes all risks and liability whatsoever in connection with such use. Any statements or recommendations of the Seller which are not contained in the Seller s current publications shall have no force or effect unless contained in an agreement signed by an authorized office of the Seller. The statements contained herein are made in lieu of all warranties, expressed or implied, including but not limited to the implied warranties of merchantability and fitness for a particular purpose which warranties are hereby expressly disclaimed. SELLER SHALL NOT BE LIABLE TO THE USER OR ANY OTHER PERSON UNDER ANY LEGAL THEORY, INCLUDING BUT NOT LIMITED TO NEGLIGENCE OR STRICT LIABILITY, FOR ANY INJURY OR FOR ANY DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES SUSTAINED OR INCURRED BY REASON OF THE USE OF ANY OF THE SELLER S PRODUCTS. Electrical Products Division 6801 River Place Blvd. Austin, TX 78726-9000 1-800-245-3573 Printed on 50% recycled paper Litho in USA www.3m.com/elpd with 10% post-consumer 3M 1998 78-8124-4070-5-A