Mounting and Operating Instructions EB 5894 EN. Electric control valves with jet pump. Flanged version of valve with jet pump

Similar documents
Mounting and Operating Instructions EB 5863 EN. Electric Control Valves. Pneumatic Control Valve

Mounting and Operating Instructions EB 8111/8112 EN. Series V2001 Valves Type 3321 Globe Valve

Mounting and Operating Instructions EB 5868/5869 EN

Mounting and Operating Instructions EB 8111/8112 EN. Valve Series V2001 Globe Valve Type 3321

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil

Mounting and Operating Instructions EB 8053 EN. Series 250 Type and Type Pneumatic Control Valves

Mounting and Operating Instructions EB 8097 EN. Type and Type Pneumatic Control Valves

Mounting and Operating Instructions EB 8039 EN. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve

Mounting and Operating Instructions EB 8097 EN. Pneumatic Control Valves Type and Type

Strainers with flanged connections Type 2 N Type 2 NI. Type 2 N/2 NI Strainers. Mounting and Operating Instructions EB 1015 EN

Mounting and Operating Instructions EB 8048 EN. Type and Type Pneumatic Control Valves Type 3249 Aseptic Angle Valve

Globe Valve Type Fig. 1 Type 3241 Globe Valve. Mounting and Operating Instructions EB EN

Series 240 Type and Type Pneumatic Control Valves Type 3244 Three-way Valve

Series 240 Electric Control Valve Type 3241/3274 Globe Valve Type 3241 Electric Control Valve Type 3244/3274 Three-way Valve Type 3244

Mounting and Operating Instructions EB 8091 EN. Pneumatic Control Valve Type and Type Type with 120 cm 2 actuator

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

Series 250 Pneumatic Control Valves Type and

Series 240 Pneumatic Control Valve Type and Type Three-way Valve Type 3244

Series 240 Pneumatic On-off Valve Type 3351

Series 42 Self-operated Regulators. Type RS Check Valve (backflow protection)

Valve Series V2001 Three-way Valve Type 3323

ANSI version. The valve closes when the differential pressure rises

Mounting and Operating Instructions EB 8227 EN. Pneumatic Control Valve Type 3331/BR 31a Special version Type 3331/3278. Type 3331 Butterfly Valve

Series 240 Pneumatic Control Valves Type and Type Three-way Valve Type 3244

Series 240 Pneumatic Control Valve Type and Type Globe Valve Type 3241

Series 240 Type Gas and Type Gas Automatic Shut-off Valves for Gases (valve class D)

Series W&T Pneumatic Control Valve Type RVG Globe valve and angle valve

Series 240 Type 3351 Pneumatic On/off Valve

Valve Series V2001 Globe Valve Type 3321 with Pneumatic or Electric Actuator

Data Sheet T EN

Series 240 Pneumatic Control Valve Type and Type Globe Valve Type 3241

T 8053 EN Type and Type Pneumatic Control Valves Type 3252 High-pressure Valve

Mounting and operating instructions EB 8093 EN. Series 240 Pneumatic Control Valve for Cryogenic Temperatures. Type and

Typetested for liquid fuels and liquefied petroleum gas (LPG) in the liquid phase (see Data Sheet T 8022 EN) Version according to ANSI standards

Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil with pneumatic or electric actuator

Mounting and operating instructions EB EN. Differential Pressure and Temperature Regulator with Flow Limiter Type 2479/2430 K

Series 240 Type and Type Pneumatic Control Valves Type 3248 Cryogenic Valve

Pneumatic Shut-off Butterfly Valve Type 3335/BR 31a

Series 250 Pneumatic Control Valve Type and Type High Pressure Valve Type 3252

Pressure Reducing Valve Type 2114/2415

Series V2001 Valves Clean Tech Type 3321CT Globe Valve with pneumatic actuator

Series 240 Types PSA, -7 PSA, -9 PSA Pneumatic Control Valves Type 3241 PSA Globe Valve

Series 46 Self-operated Regulators Differential Pressure and Flow Limiters Type 46-5 Type 46-6

Series V2001 Valves Type 3531 Globe Valve for Heat Transfer Oil with pneumatic or electric actuator

Type and Type Pneumatic Control Valves Type 3510 Micro-flow Valve

Pneumatic Control Valve Type and Type Micro-flow Valve Type 3510

Self-operated Pressure Regulators Type Universal Excess Pressure Valve

Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil with pneumatic or electric actuator

Series 240 Type and Type Pneumatic Control Valves Type 3248 Cryogenic Valve

Series 240 Pneumatic Control Valve Type DWA, -7 DWA, -9 DWA Globe Valve Type 3241 DWA

Self-operated Pressure Regulators Type Universal Excess Pressure Valve

Type 3271 Pneumatic Actuator. Actuator area: cm². Mounting and Operating Instructions EB EN

Type 3273 Hand-operated Actuator Type 3273 Side-mounted Handwheel

Series V2001 Valves Type 3531 Globe Valve for Heat Transfer Oil with pneumatic or electric actuator

Series 240 Type and Type Pneumatic Control Valves Type 3347 Hygienic Angle Valve

EB EN. Type 3372 Electropneumatic Actuator. Translation of original instructions

Series 3331 Pneumatic Control Butterfly Valve Type 3331/BR 31a

Typetested versions With Type 3213 Globe Valve, unbalanced. With Type 3214 Globe Valve, balanced

Pneumatic Butterfly Valve Type 3335 / AT

Mounting and operating instructions EB Pneumatic Control Valve Type and Type Globe Valve Type 3522 ANSI Class 300

Self-operated Pressure Regulators Universal Pressure Reducing Valve Type 41-23

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

Lined Butterfly Valve Pfeiffer Type BR 10a

Pneumatic Controller for Temperature. Type Pneumatic Controller for Temperature. Type Mounting and Operating Instructions EB 7065 EN

Self-operated Temperature Regulators Temperature Regulator Type 1u

Type 3379 Pneumatic Actuator. Mounting and Operating Instructions EB 8315 EN

Self-operated Temperature Regulators Type 1u Temperature Regulator

Series 240 Type 3349/3379 Pneumatic Control Valve Type 3349 Aseptic Angle Valve

Mounting and operating instructions EB 5801 EN. Electric Actuators Type 5801 (Rotary Actuator) Type 5802 (Linear Actuator)

Pneumatic Butterfly Valve Pfeiffer Type BR 14b/AT

Self-operated Temperature Regulators Type 1u Temperature Regulator

Mounting and Operating Instructions EB 8256 EN. Type 3286 Steam Conditioning Valve

Mounting and Operating Instructions EB 8392 EN. Series 3710 Type 3710 Reversing Amplifier

Pneumatic Rotary Actuator Type 3278

Maxifluss Rotary Plug Valve. VETEC Type 72.1/R, Type 72.3/R and Type 72.4/R

Pneumatic Control Valve Assembly Type 3331/3278

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

Pressure relief controller V22 D28

T EN Type 3347/3379 Pneumatic Control Valve Type 3347 Hygienic Angle Valve

Mounting and operating instructions EB 8220 EN. Pneumatic Butterfly Valve Type 3335/AT and Type 3335/3278. Fig. 2 Type 3335/AT

Maxifluss Rotary Plug Valves VETEC Types 73.3/M and 73.7/M

Self-operated Pressure Regulators Type Universal Pressure Reducing Valve

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

Series 240 and 250 Valves with perforated plug

T EN Type 3349 Aseptic Angle Valve With USP-VI diaphragm

Combined Self-operated Regulators Regulators for Differential Pressure, Flow Rate and Temperature

Type 3761 Pneumatic or Electropneumatic Positioner for Rotary Actuators. Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Maxifluss Rotary Plug Valves VETEC Types 72.3/R and 72.4/R

Mounting and Operating Instructions EB 3913 EN. Electropneumatic Converters i/p Converter Type

In combination with an actuator, e.g. a SAMSON Type 3271 or Type 3277 Pneumatic Actuator

Maxifluss Rotary Plug Valve. VETEC-Type 72.1/AT, Type 72.3/AT and Type 72.4/AT

Pneumatic or Electropneumatic Positioner for Rotary Actuators Type Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Company Standard Mounting Instructions for Type Valves with Type AT Actuator

Mounting and Operating Instructions EB 8252 EN. Type 3281 Steam Conditioning Valve

System 6000 Electropneumatic Converter for Direct Current Signals i/p Converter Type 6126

Mounting and Operating Instructions EB 8052 EN. Type 3251 Valve

Control valve - 3-way with flanges (3-way mixing valve / 3-way diverting valve) DN 200 and 250

Type 3271 and Type 3277 Pneumatic Actuators. Actuator areas: 175 and 750 cm². Type 3271 Type Mounting and Operating Instructions EB EN

ARI-STEVI 450 / 451 (DN15-150) Control valve - 3-way-form (mixing/diverting valve) (optional with screwed seat ring)

Transcription:

Electric control valves with jet pump Type 3267/5824, Type 3267/5825, Type 3267/3374, Type 3267/3274 Pneumatic control valves with jet pump Type 3267-1, Type 3267-7 Flanged version of valve with jet pump Fig. 1: Type 3267/3274 Fig. 2: Type 3267/5824 Mounting and Operating Instructions EB 5894 EN Edition June 2013

Definition of the signal words used in these mounting and operating instructions DANGER! indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING! indicates a hazardous situation which, if not avoided, could result in death or serious injury. NOTICE indicates a property damage message. Note: Supplementary explanations, information and tips 2 EB 5894 EN

Contents 1 General safety instructions...5 2 Design and principle of operation...6 2.1 Versions...8 2.1.1 Control valve with jet pump...8 2.1.2 Flanged version of Type 3267 Valve...8 2.2 Possible combinations: Flanged version of Type 3267...9 2.3 Technical data: Flanged version of Type 3267...9 2.4 Nameplate: Flanged version of Type 3267...12 2.5 Customer inquiries...12 3 Installation...13 3.1 Mounting position...14 3.2 Strainer...14 3.3 Additional mounting instructions...14 4 Mounting, connecting and configuring the actuator...15 4.1 Attachment...16 4.2 Connection...19 4.3 Configuration...19 5 Jet pump adjustment...22 6 Dimensions and weights...24 EB 5894 EN 3

General safety instructions 1 General safety instructions For your own safety, follow these instructions concerning the mounting, start up and operation of the device: The control valves with jet pump must be mounted, started up or serviced by fully trained and qualified personnel only; the accepted industry codes and practices are to be observed. Make sure employees or third persons are not exposed to any danger. All safety instructions and warnings given in these mounting and operating instructions, particularly those concerning installation, start-up and maintenance, must be strictly observed. To ensure appropriate use, only use the control valve in applications where the operating pressure and temperatures do not exceed the specifications used for sizing the valve at the ordering stage. The manufacturer does not assume any responsibility for damage caused by external forces or any other external factors. Any hazards that could be caused in the valve by the process medium, the operating pressure, the signal pressure or by moving parts are to be prevented by taking appropriate precautions. For installation and maintenance, make sure the relevant section of the pipeline is depressurized and, depending on the process medium, drained as well. Depending on the field of application, allow the valve to cool down or heat up to reach ambient temperature before starting any work on it. The actuators are designed for use in low voltage installations. For wiring and maintenance, you are required to observe the relevant safety regulations. Take necessary measures to ensure that the power supply cannot be reconnected inadvertently. Take care while performing adjustment work on live parts. Never remove any covers! To avoid damage to any equipment, the following also applies: Proper shipping and storage are assumed. Note: The control valves comply with the requirements of the European Pressure Equipment Directive 97/23/EC. Valves with a CE marking have a declaration of conformity which includes information about the applied conformity assessment procedure. The declaration of conformity is available on request. EB 5894 EN 5

Design and principle of operation 2 Design and principle of operation Control valves with jet pumps are used in control circuits, especially in district heating supply plants. They assume both the function of a valve for temperature control and that of a circulation pump for the heating water circuit. Configured as mixing valves, they replace the reducing valve and circulation pump usually installed. The control valves with jet pumps consist of a valve body (1) with jet nozzle (2) and plug (3), mixing nozzle (1.1) and diffuser (1.2). The variable cross-sectional area between the valve plug and jet nozzle determines the jet stream Q 1. The jet stream Q 1 is accelerated in the jet nozzle and flows to the mixing nozzle at high speed. The exiting jet draws the partial flow Q 2 with it. In the mixing nozzle, the two flows are mixed together. During the mixing process, the jet stream releases a portion of its kinetic energy to the intake flow. This exchange of energy causes an increase in pressure and, at the same time, a decrease in jet stream velocity. In the downstream diffuser, the velocity is further reduced, and the pressure increases to the output value p 3. The turbulence in both the mixing chamber and the mixing nozzle does not only cause the exchange of energy described above, but also causes an exceptionally thorough mixing of the supplied process media. This improved mixing effect guarantees a homogenous condition of the output flow directly downstream of the diffuser. NOTICE The plant data used to size the jet pump must match the actual plant data to allow the jet pump to fully function. The jet pump is sized by SAMSON AG based on the specifications made in the questionnaire for determining the operating conditions (TV-SK 8852). 6 EB 5894 EN

Design and principle of operation Q 1 p 1 t 1 t 3 p 3 6 AB Q 3 B A Q 2 p 2 t 2 8 8.2 8.1 7 9 6 4 3 2 1 1.1 1.2 Type 3267/5824 Q 1 p 1 t 1 t 3 p 3 6 AB Q 3 B A Q 2 p 2 t 2 8 8.2 8.1 7 9 6.4 7 6.1 5 6 4 3 2 1 1.1 1.2 Type 3267/5824 for temperatures up to 220 C 1 Valve body 1.1 Mixing nozzle 1.2 Diffuser 2 Jet nozzle 3 Plug 4 Plug stem sealing 5 Yoke 6 Plug stem 6.1 Stem connector nut and lock nut 6.4 Adapter rod 7 Stem connector between actuator stem and plug stem (also travel indicator) 8 Actuator 8.1 Actuator stem 8.2 Coupling nut 9 Adapter Fig. 3: Control valve with jet pump EB 5894 EN 7

Design and principle of operation 2.1 Versions 2.1.1 Control valve with jet pump Electric control valves with jet pump Type 3267/5824 PN 16/25 DN 15 to 80 2) Type 3267/5825 1) PN 16/25 DN 15 to 80 2) Type 3267/3374 1) PN 16/25 DN 15 to 80 2) Type 3267/3274 1) PN 16/25 DN 65 to 80 2) Pneumatic control valves with jet pump Type 3267-1 (Type 3271 Actuator) PN 16/25 DN 15 to 80 2) Type 3267-7 (Type 3277 Actuator) PN 16/25 DN 15 to 80 2) 1) With fail-safe action tested according to DIN EN 14597. Register number available on request. 2) Nominal inlet size Control valves with handwheel can be used as jet pumps with handwheel when equipped with a Type 3273 Hand-operated Actuator (see u T 8312 EN). 2.1.2 Flanged version of Type 3267 Valve Nominal size, K VS coefficients, body materials DN Characteristic 1: K VS Characteristic 2: K VS Travel PN/material 15 0.25 to 1.6 0.25 to 0.63 20 0.5 to 3.2 0.5 to 1.25 25 0.8 to 5.0 0.8 to 2.0 32 2.0 to 8.0 2.0 to 3.2 40 3.2 to 12.5 3.2 to 5.0 50 5.0 to 20 5.0 to 8.0 65 8.0 to 32 8.0 to 12.5 80 12.5 to 50 12.5 to 20 7.5 mm 15 mm PN 16/EN-JL1040 PN 25/EN-JS1049 PN 25/1.0619 PN 16/EN-JL1040 PN 16/EN-JS1049 PN 25/EN-JS1049 PN 25/1.0619 8 EB 5894 EN

Design and principle of operation 2.2 Possible combinations: Flanged version of Type 3267 Electric actuators Electrohydraulic actuators Pneumatic actuators Hand-operated actuator Type For details, refer to Nominal size 1) 15 20 25 32 40 50 65 80 5824-30 u EB 5824 EN 5825-30 3374-15 u EB 8331 EN 3374-26 3274-11 u EB 8340 EN 3274-21 3271 u EB 8310-x EN 3277 u EB 8311 EN 3273 u T 8312 EN 1) The nominal inlet sizes are listed. The nominal outlet size is always one size larger than the nominal inlet size. 2.3 Technical data: Flanged version of Type 3267 Nominal size 1) 15 20 25 32 40 50 65 80 Nominal pressure PN 16 (type of connection depending on material acc. to DIN EN 1092-1/-2) 2) PN 25 (type of connection acc. to DIN EN 1092-1) Rated travel 7.5 mm 15 mm Permissible temperatures 10 to 220 C 3) Seat/plug seal Characteristic Leakage rate according to IEC 60534-4 Metal seal Linear Class III ( 0.01 % of K VS coefficient) 1) The nominal inlet sizes are listed. The nominal outlet size is always one size larger than the nominal inlet size. 2) Type of connection according to DIN EN 1092-1 with material 1.0619 Type of connection according to DIN EN 1092-2 with materials EN-JL1040 and EN-JS1049 3) Type 3267/5824 and Type 3267/5825: Use an additional yoke for medium temperatures from 130 to 220 C. EB 5894 EN 9

Design and principle of operation Materials Nominal size 1) 15 20 25 32 40 50 65 80 Body EN-JL1040 EN-JS1049 1.0619 Diffuser EN-JS1049 Mixing nozzle CW602N CW617N EN-JS1049 Jet nozzle 1.4006 Plug and plug stem 1.4404 Guide bushing (packing chamber) CW617N Packing/stem sealing V-ring packing: PTFE with carbon Spring: 1.4310 Body gasket Graphite on metal core 1) The nominal inlet sizes are listed. The nominal outlet size is always one size larger than the nominal inlet size. Permissible differential pressures All pressures stated in bar (gauge) The permissible differential pressures stated are nominal values. They are limited by the pressure-temperature diagram and the pressure ratings. In the closed position, the leakage rate indicated in Technical data is not exceeded. Pneumatic control valves can only be used without a positioner in the 0.2 to 1.0 bar signal pressure range. For all other cases, a positioner is required. Electric actuators Type 5824-30 5825-30 3374-15 3374-26 3274-11 3274-21 Positioning force K VS 0.7 kn 0.28 kn 2.5 kn 0.5 kn 1.8 kn Δp H [bar] 0.25 to 0.4 25 25 25 25 0.5 to 0.8 25 25 25 25 1.0 to 1.6 25 25 25 25 Signal pressure Pneumatic actuators Actuator [cm 2 ] 3271/3277 0.2 to 1 bar 0.4 to 2 bar Δp H [bar] 80 14 240 25 80 14 240 25 80 14 240 25 10 EB 5894 EN

Design and principle of operation Electric actuators Type 5824-30 5825-30 3374-15 3374-26 3274-11 3274-21 Positioning force K VS 0.7 kn 0.28 kn 2.5 kn 0.5 kn 1.8 kn Δp H [bar] 2.0 to 3.2 25 16.5 25 25 4.0 to 5.0 25 10 25 25 6.3 and 8.0 23 5 25 15 10 and 12.5 14 2.5 25 8.5 16 and 20 8 1.0 25 4.5 25 and 32 4 23 2.0 15.5 40 and 50 2.5 15 1.0 10.0 Signal pressure Pneumatic actuators Actuator [cm 2 ] 3271/3277 0.2 to 1 bar 0.4 to 2 bar Δp H [bar] 80 14 240 25 25 80 10 240 25 25 80 5.4 240 13 25 80 3.1 240 6.7 19 80 1.9 240 3.5 11 240 3.9 8.2 350 5.8 12.1 240 2.6 5.7 350 3.9 8.1 EB 5894 EN 11

Design and principle of operation 2.4 Nameplate: Flanged version of Type 3267 2 3 4 1 1 Model number 2 Order number 3 K vs coefficient 4 Version 2.5 Customer inquiries Please submit the following details: Type designation Model number Order number 12 EB 5894 EN

Installation 3 Installation NOTICE The mounting position of the jet pump must be lower than the position of the consumer (radiator, air heater etc.). This ensures that the circulation is intensified at small loads by the thermal conditions. Otherwise, difficulties may arise while the plant is in operation. If air heaters are used, we recommend mounting the jet pumps directly to them. Keep the mixing line AB (Fig. 4) as short as possible. Do not install check valves or shut-off valves in this line. Refer to the installation schematic drawing (Fig. 4) for the arrangement of the jet pump with the required additional instruments. Thermometers and pressure gauges must be installed in the generator and consumer flow pipe and in the return flow pipe. A manually operated throttle valve or balancing valve (4) is absolutely necessary in the plant s return flow pipe. When using the jet pump in ventilation systems, it is absolutely necessary to include a soft-start for winter conditions! Flush the pipelines thoroughly before installation. Boiler or district heating connection Q 1 p 1 t 1 2 3 A 2 3 M p H = 1 B p 1 p 2 AB p h = 2 3 p 3 p 2 Q 3 p 3 t 3 1 Control valve with jet pump 2 Pressure gauge 3 Thermometer 4 Balancing valve 4 Q 2 p 2 t 2 Fig. 4: Required pressure gauges and thermometers EB 5894 EN 13

Installation 3.1 Mounting position The Type 3267 Valve with Jet Pump must be installed with the diffuser in the horizontal position. NOTICE The flow direction of ports A, B and AB must match those specified in the plant schematics (Fig. 4). Choose a place of installation that allows you to freely access the control valve even after the entire plant has been completed. Make sure the valve body is installed free of stress. If necessary, support the pipelines near the connections. Do not attach supports directly to the jet pump or actuator. 3.3 Additional mounting instructions We recommend installing a hand-operated shut-off valve upstream of the strainer and downstream of the control valve to be able to shut down the plant for cleaning and maintenance, and when the plant is not used for longer periods of time. 3.2 Strainer Install a strainer (e.g. SAMSON Type 2 NI) at the valve inlets to prevent any sealing parts, weld spatter and other impurities carried along by the process medium impairing the proper functioning of the valve, above all the tight shut-off. NOTICE The direction of flow must correspond to the arrow on the body. The filter element must be installed to hang downwards. Remember to leave enough space to remove the filter element. 14 EB 5894 EN

Mounting, connecting and configuring the actuator 4 Mounting, connecting and configuring the actuator NOTICE The instructions to mount the valve onto the actuator, to perform electrical or pneumatic connections as well as to configure the actuator are described in detail in the Mounting and Operating Instructions (EB): Type 5824 Electric Actuator u EB 5824 EN Type 5825 Electric Actuator u EB 5824 EN Type 3374 Electric Actuator u EB 8331 EN Type 3274 Electrohydraulic Actuator u EB 8340 EN Type 3271 Pneumatic Actuator u EB 8310-x EN Type 3277 Pneumatic Actuator u EB 8311 EN Read the actuator's mounting and operating instructions! EB 5894 EN 15

Mounting, connecting and configuring the actuator 4.1 Attachment Mounting Types 3374, 3274, 3271, 3277 and 3273 Actuators (Fig. 5) The actuator is mounted onto the valve using a yoke (which yoke is to be used depends on the actuator and the nominal size of the valve). Refer to Fig. 8 and Fig. 9. 1. Place yoke (5) on the valve body (1) and fasten them together. 2. Place stem connector rod (6.3) on the plug stem (6) and fasten using the threaded pins. 3. Press the plug together with the plug stem (6) firmly into the seat. 4. If necessary, remove stem connector (7) and ring nut (8.3) from the actuator. 5. Slide ring nut (8.3) over the stem connector rod (6.3). 6. Place actuator (8) onto the yoke (5) and fasten them together using the ring nut (8.3). 7. Extend the actuator stem (8.1) as far as it will go. 8. Screw on the stem connector nut (6.1) by hand until it touches the actuator stem. Then turn it a further ¼ turn and secure this position with the lock nut (6.2) 9. Position clamps of the stem connector (7) and screw them tight. Align travel indicator scale with the tip of the stem connector. 8 5 8.3 8.1 7 6.1 6.2 6.3 6 1 1 Valve body 5 Yoke 6 Plug stem 6.1 Stem connector nut 6.2 Lock nut Fig. 5: Attaching the yoke 6.3 Stem connector rod 7 Stem connector 8 Actuator 8.1 Actuator stem 8.3 Ring nut 16 EB 5894 EN

Mounting, connecting and configuring the actuator Mounting Type 5824 and Type 5825 Actuators (Fig. 6) The actuator is mounted onto the valve using an adapter (9) (which adapter is to be used depends on the nominal size). Refer to Fig. 8. 1. Place adapter (9) on the valve body (1) and fasten using the threaded pins. 2. Place stem connector rod (9.3) on the plug stem and fasten using the threaded pins 3. Press the plug together with the plug stem (6) firmly into the seat. 4. Place actuator (8) on the adapter (9) and fasten together using the coupling nut (8.2) (tightening torque: 20 Nm). 5. Extend the actuator stem (8.1) until it touches the stem connector rod (9.3). 8 8.2 8.1 7 9.3 9 6 1 1 Valve body 7 Stem connector 6 Plug stem 8 Actuator 8.1 Actuator stem 8.2 Coupling nut 9 Adapter 9.3 Stem connector rod 6. Position clamps of the stem connector (7) and screw them tight. Fig. 6: Adapter attachment EB 5894 EN 17

Mounting, connecting and configuring the actuator For Type 5824 and Type 5825 Actuators as well as medium temperatures above 130 C, a yoke (1070-6127) needs to be attached between the adapter and valve (Fig. 7). 1. Place yoke (5) on the valve body (1) and fasten them together. 2. Place stem connector rod (6.3) on the plug stem (6) and fasten using the threaded pins. 3. Push the plug together with the plug stem (6) firmly into the seat. 4. Insert adapter rod (6.4) from the top through the yoke. 5. Place adapter (9) on the yoke and fasten using the threaded pins. 6. Place stem connector rod (9.3) on the adapter rod (6.4) and fasten using the threaded pins. 7. Place actuator (8) on the adapter (9) and fasten together using the coupling nut (8.2) (tightening torque: 20 Nm). 8. Extend the actuator stem (8.1) as far as it will go. 9. Screw on the stem connector nut (6.1) by hand until it touches the bottom of the adapter rod (6.4) and until the top of the adapter rod (6.4) touches the actuator stem (8.1). Turn it a further ¼ turn and secure it with the lock nut (6.2). 10. Position clamps of both stem connectors (7) at the top and bottom of the adapter rod (6.4) and screw them tight. Align travel scale with the tip of the stem connector. 8 8.2 8.1 7 9.3 9 5 6.4 7 6.1 6.2 6.3 6 1 1 Valve body 5 Yoke 6 Plug stem 6.1 Stem connector nut 6.2 Lock nut 6.3 Stem connector rod 6.4 Adapter rod 7 Stem connector 8 Actuator 8.1 Actuator stem 8.2 Coupling nut 9 Adapter 9.3 Stem connector rod Fig. 7: Attaching the adapter and yoke 18 EB 5894 EN

Mounting, connecting and configuring the actuator 4.2 Connection Perform the electrical or pneumatic connection of the actuator as described in the corresponding mounting and operating instructions. 4.3 Configuration The electric actuator versions with positioner can be adapted to the control task. Configure the actuator as described in the corresponding mounting and operating instructions. EB 5894 EN 19

Mounting, connecting and configuring the actuator Type 5824/5825 Type 3374 Type 3274 DN 15 to 50 DN 65 and 80 1400-7833 1400-7415 130 C > 130 C 1070-6127 1070-8470 1070-6129 Fig. 8: Adapting actuators (electric control valves) 20 EB 5894 EN

Mounting, connecting and configuring the actuator Type 3271 Type 3277 Type 3273 DN 15 to 50 80/240 cm² DN 65/80 80/240 cm² DN 15 to 50 350 cm² Type 3273 DN 65/80 350/700 cm² Type 3273 1070-8469 1170-2174 1070-8470 1070-6129 Fig. 9: Adapting actuators (pneumatic control valves) EB 5894 EN 21

Jet pump adjustment 5 Jet pump adjustment Sizing The jet pump is sized by SAMSON AG based on the specifications made in the questionnaire for determining the operating conditions (TV-SK 8852). The plant data specified in the questionnaire must match the actual plant data to allow the jet pump to fully function. Adjustment NOTICE To adjust the jet pump, the pressure gauges and thermometers shown in Fig. 10 are absolutely necessary. The required temperature t 3 in the consumer plant results from the ratio of the flows Q 1, Q 2 and Q 3 as well as the differential pressures Δp H and Δp h across the plant. If the temperature t 3 in the consumer plant (at full rated travel H 100 ) is not achieved with the network pressure Δp H available, the differential pressure Δp h across the balancing valve (4) must be adjusted. To do this, proceed as follows: Boiler or district heating connection Q 1 p 1 t 1 2 3 A 2 3 M p H = 1 B p 1 p 2 AB p h = 2 3 p 3 p 2 Q 2 p 2 t 2 Q 3 p 3 t 3 4 1 Control valve with jet pump 2 Pressure gauge 3 Thermometer 4 Balancing valve Q 1 Flow rate in network flow Q 2 Flow rate in network return flow Q 3 Flow rate in output flow p 1 Pressure in network flow p 2 Pressure in network return flow p 3 Pressure in output flow t 1 Temperature in network flow t 2 Temperature in network return flow Temperature in output flow t 3 Fig. 10: Jet pump adjustment 22 EB 5894 EN

Jet pump adjustment 1. Determine the flow rate ratio m 100 from the temperatures t 1, t 2 and t 3 (read off at the thermometers) using the following equation: m 100 = Q 1 = t 3 t 2 Q 3 t 1 t 2 2. Determine the pressure ratio ε 100 0 from the pressures p 1, p 2 and p 3 (read off at the pressure gauges) using the following equation: ε 100 = Δp h p = 3 p 2 Δp H p 1 p 2 3. Enter the flow rate ratio m 100 and pressure ratio ε 100 on the operating diagram (Fig. 11). The point of intersection (operating point) must be within the grayshaded operational area. If not, the jet pump has been incorrectly sized. 4. For optimal operation, the operating point lies on the marked limit. Shift the determined point of intersection horizontally (same flow rate ratio m 100 ) until it reaches the limit and read off the corresponding pressure ratio ε 100. 5. Using the value read from the diagram for ε 100 and the known network pressure Δp H, the plant differential pressure Δp h can be calculated: Δp h = Δp H ε 100 6. Adjust the balancing valve until the calculated differential pressure Δp h is achieved or until the correct temperature ratio is achieved. m 100 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 Operational area Version 1 Limit Version 2 0 0.1 0.2 0.3 0.4 0.5 0.6 ε 100 The flow ratio m 100 and the pressure ratio ε 100 are based on the full rated travel H 100. Fig. 11: Operating diagram: Flanged version of Type 3267 Valve with Jet Pump EB 5894 EN 23

Dimensions and weights 6 Dimensions and weights Electric control valves with jet pump in flanged version Nominal size A, AB DN 15 20 25 32 40 50 65 80 Connection size B DN 20 25 32 40 50 65 80 100 Overall length L1 mm 130 150 160 180 200 230 290 310 Length L2 mm 155 190 245 300 375 480 590 735 Height H1 mm 240 265 290 Height H2 mm 85 110 135 Height H3 (minimum height) Weight Type 5824/5825 mm 400 430 610 Type 5824/5825 with yoke mm 560 585 769 Type 3374 mm 700 725 750 Type 3274 1) mm 760 Without actuator kg (approx.) 5.8 7.6 9.1 13.3 16.3 27.3 52.3 64.6 With yoke kg (approx.) 6.5 8.3 9.8 14 17 28 53 65 1) Values for actuators with electric override. For version with mechanical override, H3 increases by 92 mm. Electric actuators Type 5824 5825 3274 3374 Weight kg (approx.) 1.5 12 4 With handwheel kg (approx.) 1.3 13 24 EB 5894 EN

Dimensions and weights H3 200 H2 L2 Type 3267/5824-30: DN 15 to 80 Type 3267/5825-30: DN 15 to 80 146x103 A B L1 AB H3+159 200 H1 L2 Type 3267/5824-30: DN 15 to 80 Type 3267/5825-30: DN 15 to 80 Version for temperatures from 130 to 220 C 146x103 A B L1 AB H3 204 H1 L2 Type 3267/3374: DN 15 to 80 193x120 60 A B L1 AB H3 320 Pg 13.5 H1 A L2 B Type 3267/3274: DN 65 to 80 235x125 L1 AB EB 5894 EN 25

Dimensions and weights Pneumatic control valves with jet pump in flanged version Nominal size A, AB DN 15 20 25 32 40 50 65 80 Connection size B DN 20 25 32 40 50 65 80 100 Overall length L1 mm 130 150 160 180 200 230 290 310 Length L2 mm 155 190 245 300 375 480 590 735 Height H1 mm 240 265 290 Height H3 (minimum height) Weight Type 3271/3277 mm 320 + H 1) 345 + H 1) 370 + H 1) Without actuator kg (approx.) 5.8 7.6 9.1 13.3 16.3 27.3 52.3 64.6 With yoke kg (approx.) 6.5 8.3 9.8 14 17 28 53 65 1) Refer to Data Sheet T 8310-1 EN for dimension H Pneumatic actuators Type 3271 3277 Effective area cm² 80 240 350 700 240 350 355 700 Diaphragm D mm 150 240 280 390 240 280 280 290 Height H mm 62 62 82 134 65 82 121 135 Signal pressure connection G 1 /4 G 1 /4 G 3 /8 G 3 /8 G 1 /4 G 3 /8 G 3 /8 G 3 /8 Weight kg (approx.) 2 5 8 22 9 12 19 26 With handwheel kg (approx.) 9 13 27 13 17 31 Control valve with jet pump and handwheel Nominal size A, AB DN 15 20 25 32 40 50 65 80 Connection size B DN 20 25 32 40 50 65 80 100 Overall length L1 mm 130 150 160 180 200 230 290 310 Length L2 mm 155 190 245 300 375 480 590 735 Height H1 mm 240 265 290 Height H3 mm 455 483 500 Weight Without actuator kg (approx.) 5.8 7.6 9.1 13.3 16.3 27.3 52.3 64.6 With yoke kg (approx.) 6.5 8.3 9.8 14 17 28 53 65 Hand-operated actuator Type 3273 Weight kg (approx.) 2 26 EB 5894 EN

Dimensions and weights H3 Type 3267-1: DN 15 to 80 a H H1 A L2 B ØD L1 AB H3 Type 3267-7: DN 15 to 80 a H H1 A L2 B ØD L1 AB Type 3267/3273: DN 15 to 80 H3 130 H1 L2 A B Ø180 L1 AB EB 5894 EN 27

SAMSON AG MESS- UND REGELTECHNIK Weismüllerstraße 3 60314 Frankfurt am Main Germany Phone: +49 69 4009-0 Fax: +49 69 4009-1507 Internet: http://www.samson.de EB 5894 EN 2013-09-16