FUSE PANEL. NTI-N NC(Y)/M3 NEBS Level 3 Certified NTI NCD(Y)/M3 Standard Panel with Diodes

Similar documents
FUSE PANEL Technical Practice FDP /20 GMT NEBS Level 3 Certified

Noran Tel. FUSE PANEL Technical Practice N21C110-NCY 5/5 GMT (20Amp GMT) NEBS Level 3 Certified

Noran Tel. a subsidiary of Westell Inc. Fuse Panel Technical Practice NPGMT /10 GMT NEBS Level 3 Verified

FUSE PANEL Technical Practice FDP /10 GMT NEBS Level 3 Certified

Noran Tel. Fuse Panel Technical Practice N NCY 4/4TPA & 6/6 GMT NEBS Level 3 Certified

FUSE PANEL Technical Practice N N-L34 20/20 GMT (23 panel) NEBS Level 3 Certified

FUSE PANEL. Technical Practice N N-L33 10/10 GMT Front Access NEBS Level 3 Certified

Westell FUSE PANEL. Technical Practice N Position Type VDC Floating

TPM/GMT Panel Installation Guide

TPM Fuse Panel Installation Guide. Document INS-727XXXXXXX This manual covers the following part numbers- Trimm 727XXXXXXX Family

GMT Fuse Panel Installation Guide

PowerWorx GMT Series Power Distribution Panel Uninterrupted (C-Source) Power User Manual

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

Dual-Feed 200A 4/5 TPA/GMT Fuse Alarm Panel. Model Installation Guide

Dual 100A 4/4-KLM & 4/4-GMT Fuse Panel. Model N Installation Guide

HMW Filtered Fuse Panel for GMT Fuses

DC Distribution Panel User Guide # S

DC to AC Power Inverters

OWNERS MANUAL JANUARY 2007 ISO

6170 Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

50A Dual-Feed 5/5 GMT Total Front Access Fuse Panel

OWNER'S MANUAL. Royal Sovereign International Inc. RET Desk Series

SB SWITCH CONTROL BOX

TD77-2 and ULB42-TD-2 TRAFFIC DIRECTOR CONTROL BOXES

DC to AC Power Inverters

In-Line Linear Actuator

ADI-125/750 ADI-125/1500 ADI-125/2500

n Operator s Manual n Redundant Control Unit FOR CFR UNINTERRUPTIBLE POWER SUPPLIES FROM ALPHA TECHNOLOGIES

Total Front Access Wall Mount Fuse Panel Installation Guide. Document INS This manual covers the following part numbers

MIL-24/2600Q MIL-24/3200DQ

Demarcation Fuse/Circuit Breaker Alarm Panel 125DM08. Installation Guide

Dimensions 12/800N 12/1200N D. DC to AC Power Inverters. OWNERS MANUAL for Models: OWNERS MANUAL April ISO 9001:2000 Certified Company

24/3000H-3PH 24/4500H-3PH 24/6000H-3PH

Power. On Your Terms.

CBC-160-1N and CBC-160-2N Clutch/Brake Controls

Safety Sentry Electronic Breakaway Switch

Installation & Operation Manual PWS1000R Rack Mount Power Supply

DC to DC Step Up Converter Model: VTC305

Fuse and Distribution Module

VP-4124/VP-4124-E 24/48 VOLT DC SWITCHING POWER SUPPLY

WARRANTY INFORMATION...

PowerWorx Power Distribution Products Select Series Circuit Breaker for ±24 or ±48 Vdc User Manual

10 Year Limited Warranty

The Power of Reliability INSTRUCTION MANUAL

This document describes:

TECHNICAL INFORMATION

VP-6124/VP-6124-E 24 VOLT DC SWITCHING POWER SUPPLY

Dual-Feed 600A Load Center Frame Power :: 600CB10 and 600CB12 User Manual

VTC610 Series Voltage Converter. Installation & Operation Manual

miconverter 18-Module Rack-Mount Power Chassis User Manual 38 Tesla, Irvine, CA USA Phone: (949) ; Fax: (949) Page 12

PowerWorx DSX Series GMT Fuse Panel User Manual

PD404-AN V analog control 4 Channel x 500 W Dimmer & Switch Packs ANALOG 0-10 V. Serial Number

INSTALLATION & OPERATION MANUAL

Infinitybox Express Road Race Car Kit Installation Guide

INVERTER HARNESS INSTALLATION FOR FREIGHTLINER CASCADIA

CBC-802 Plug-In Clutch/Brake Control with Solid State Switching

Innovative Circuit Technology Ltd.

Industry Compliance The cabinet and modules are Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc.

NT1-200, NT1-200/296 Battery Backup. NT1-200 Add-on Battery. Installation Instructions. Specifications. NT1-200, NT1-200/296 Battery Backup

Effective June 1, 2013 This guide supersedes all previous versions

OWNERS MANUAL JANUARY 2007 ISO

Transceiver Voltage Conditioner

37SCENE 46SCENE 79SCENE

IQS300 Series Quasi-Sine Inverter. Installation & Operation Manual

CurrentGuard. CurrentGuard. CurrentGuard. Plus. Surge Protective Devices. Installation,Operation and Maintenance Manual PN

DS1 Plug-In Digital Signal Cross-Connect (PIX-DSX-1) 19-Inch Shelf Kit Installation Instructions

INSTALLATION INSTRUCTIONS

VTC1000 Series Voltage Converter. Installation & Operation Manual

WARNINGS, CAUTIONS AND NOTES

SPC-PANEL Simplex, Single Phase Pump Control Panel

INSTALLATION & OPERATION MANUAL

Manual Installation & Operation

The function of this Dynamic Active Probe has divided into three preferences on the screen main Menus:

Installation and Operation Manual

Wiring Installation Instructions for : Pressure. Wiring Installation Instructions for : Temperature. 2 1/16 Spek Pro Professional Racing Gauge

Oil Pressure Display Gauges Part numbers: Analog Oil/Fuel SAE Pressure Gauge psi Analog Oil SAE Pressure Gauge.

Installing Power Components

CLEAN POWER TM CPS Series Operator s Manual

QSB (Q-Star) Electronics for QSE Electromagnetic Meter. Owner s Manual TABLE OF CONTENTS

TBX10A INSTALLATION/OWNER'S MANUAL 10" Sealed Enclosure with Built-in Amplifier

MOTORTRONICS Solid State AC Motor Control

AUTO ISOLATOR I AN AUTOMATIC LOSSLESS BATTERY ISOLATOR FOR DUAL BATTERY SYSTEMS

ENFORCER TM 6201-IQ ELECTRONIC SIREN

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls

A39 UNIVERSAL SCR CHARGER

CBC-802 Plug-In Clutch/Brake Control with Solid State Switching

Waterproof 4X Telephone Model WP80

Demarcation Fuse Alarm Panel

INSTALLATION & OPERATION MANUAL

BAK1500 INSTALLATION/OWNER'S MANUAL Compact Amplified Subwoofer

INSTALLATION INSTRUCTIONS THERMOCOUPLE EXPANSION MODULE

Instruction Manual. SaltDogg Spreader Hopper Poly Electrical 0.65 cubic yards. Table of Contents. General Information. Vehicle Requirements: WARNING

XLM 62V Energy Storage Module

This document describes:

Vandal Resistant Ringdown/Autodialer Telephone

WF-5100 Series True Sine Wave Inverters

TS69 TS65 TS55 TS45 TS5768 TS SERIES INSTALLATION/OWNER'S MANUAL

CDS-JOHN BLUE COMPANY

LED FLASHER GND CONTROL FPC4N

INSTRUCTION MANUAL FOR PC63 CAGE

Transcription:

0113-03K September 2, 2010 FUSE PANEL Technical Practice NTI-N250140-NC(Y)/M3 NEBS Level 3 Certified NTI-230140-NCD(Y)/M3 Standard Panel with Diodes FEATURES ƒ Negative (-) VDC input voltage, -24 or 48Vdc ƒ Without diodes this panel can operate at 200 Amps of output current per panel (100 Amps per Bus). ƒ With diodes the panel will operate at 60 Amps of output current per panel (30 Amps per Bus). ƒ 2 isolated groups of 20 GMT fuses each. ƒ 2 Isolated battery returns. ƒ Green power LEDs provided for each bus. ƒ Common (C), normally closed (NC), normally open (NO) alarm extensions (2 sets of dry form C contacts). ƒ Both GND and - BATTERY activated external alarms (alarms that originated outside panel). ƒ Single 1.75 mounting height (single panel space). ƒ Brackets supplied are reversible for both 19" and 23" racks and 1.75" mounting spaces. ƒ NEBS Certification is not available in diode equipped panels.

1. GENERAL DESCRIPTION 1.1. The NTI-250140-N/M3 Fuse Panels provide up to 40 circuits for the distribution of DC power to equipment. Each of the 40 circuits is individually protected by a GMT style telecommunication fuse located on the panel's faceplate. Alarm circuits are provided to indicate and extend alarm conditions when faults occur. 1.2. Input wiring is connected to a high current, 2-hole lug input block located at the rear of the panel. Each group of fuses or bus has its own completely isolated inputs, allowing the distribution of two battery voltages through the same panel. 1.3. The power is distributed to the load side equipment through GMT style fuses. There are 20 fuses per fuse group and two groups per panel. Each fuse position is available for installer connection at the rear of the panel. A designation card is provided for keeping records of which position is connected to which equipment and what amperage of fuse is to be used. 1.4. Alarm circuits are provided to alert service personnel of fault conditions. A Fuse alarm is caused when any of the GMT distribution fuses opens. A red LED on the faceplate will illuminate to signal a fuse alarm. These fuse panels have two sets of common (C), normally closed (NC), normally open (NO) contacts for Fuse Alarms or battery or ground activated external Alarms. 1.5. The NTI-250140-N/M3 Fuse Panels are made from 0.050" steel and painted off-white (see ordering options for other colors). Single rack height panels are shipped with universal brackets that will fit both 19" and 23" wide racks and use both 1 and 1.75" panel space. The panel has a clear L shaped lexan to protect the wiring connections on the back of the panel. 2. APPLICATION 2.1. The NTI-250140-N/M3 Fuse Panels are designed to be used in the distribution of DC power. They are rack mount panels that can provide fused DC power to up to 40 individual circuits (20/20 GMT), or 20 pieces of equipment, providing redundant battery feeds to each. 3. CIRCUIT DESCRIPTION 3.1. Power is connected to the fuse panel via plastic input blocks located at the rear of the panel, which are ¼ studs on 5/8 centers (Torque 5.5 ft-lbs). These inputs are high current stud blocks that supply current to the fuse panel. 3.2. Distribution of current from each bus is provided by GMT style fuses. Each bus has 20 fuse holders for distribution, fuses F1 to F20 for each Bus A and Bus B. Each fuse position is made available at the rear of the fuse panels. Maximum output current of each fused position is rated at 15 Amps, provided the maximum bus current is not exceeded. 3.3. Fuse alarm circuitry provides 2 sets of dry form C contacts. In the event of a fuse or external alarm, both sets of normally open contacts will close, providing a connection between NO and C terminals on each set. Note: Both sets of relay contacts operate together in the event of a fuse alarm or an external alarm. Page 2

4.2 INSTALLATION Please read completely before beginning. 4.1. Unpack and inspect the Fuse Panel for possible damage incurred during shipping. If damage is found, file a claim immediately with the carrier. 4.2. Once the panel is unpacked, verify that there are three mounting brackets. Fasten the mounting brackets to the sides of the fuse panel using the screws provided, such that it will fit the rack you wish to mount the panel in. Single rack height panels have a universal bracket that allows the panel to be mounted on either 19" or 23" wide equipment racks and can be installed for flush mounting of the fuse panel, or for a 5" offset mounting. 4.3. Mount the fuse panel on the equipment rack using the thread forming #12-24 rack mounting screws and lockwashers provided. WARNING: For safety reasons all wiring should be done with the power source removed (when possible). 4.4. Remove the distribution fuse feeding the input cables that are to be connected to the new panel. Using input cables specified by the Job Engineer, hook up the input cables to the input terminal block on the fuse panel. This panel has two sets of inputs. Torque ¼ steel nuts to 5.5 ft-lbs. Please be sure to observe the proper polarity. 4.5. The battery outputs are available at the terminals blocks at the rear of the panel. Each fuse position is numbered and that fused circuit is available at the terminal block position with the same number. 4.6. All battery return (ground) connections are terminated on the isolated battery return on the rear of the panel. Note that these returns are isolated from the chassis. 4.7. For this fuse panel you have common (C), normally closed (NC), normally open (NO) alarm extensions (two sets of dry C contacts). You have ground activated external alarm and battery activated external alarm (alarms that originated outside the panel). 4.8. CHASSIS GROUND; For safety reasons, and as recommended by NEBS, the chassis should be electrically connected to the rack ground. From step 4.3. the panel should already be ground to the rack via the #12-24 thread forming rack screws and outside tooth lock washers. In addition to grounding via the mounting brackets, it is recommended you ground the chassis using a ground cable and the #10 bolt and locks on side of chassis (#10 screw torque; 2ft/lbs or 2.7Nm). 4.9. Power up the panel by installing the distribution fuse supplying the panel. The panel should power up and have no red LEDs illuminated. Green power LEDs should be lit. 4.10. Install panel output distribution fuses as required. Use the provided designation card to keep a record of which equipment is connected to which circuit and what the fuse rating is. 4.11. If you wish to verify the Fuse alarm circuit, you can insert a blown or open fuse into one of the empty fuse holders. A red Fuse Alarm LED should light on the faceplate and the alarm extension relay should activate and extend appropriate alarm. If you wish to verify the EXT Alarms you can connect GND or -BAT and the red EXT Alarm should light on the faceplate and the alarm extension relay should activate and extend appropriate alarm. Note: If you have any questions, suggestions, or problems, please don't hesitate to call Noran Tel Technical Support at (306) 721-3535 or contact us through the Internet at http//www.norantel.com. Your input helps us in our ongoing product improvement process that benefits both of us. Thank You. Page 3

5. SPECIFICATIONS 5.1. Voltage -24 or -48 VDC Typical -22 to -55 VDC Maximum 5.2. Current/Fuse 15 Amps Maximum 5.3. Current/Bus 100(30*)Amps Max./Bus 5.4. Current/Panel 200 (60*)Amps 5.5. Output Fuse GMT Style Fuse Holders 5.6. Output/Bus 40 Fuses (20 per bus) 5.7. Output/Panel 2 Busses per Panel 5.8. Input Block** Two ¼ Stud on 5/8 center 5.9. Output Block #26 AWG to 14 AWG wire *If diode equipped **Torque = 5.5 ft-lbs 5.10. Relay Current 2 Amps Max. 5.11. Dimensions 1¾ H, 17 W,10½ D (excluding brackets) 5.12. Rack Mounting 19 and 23 Racks for 1 and 1.75 Panel Spaces 5.13.Weight 5.14.Operating Temp. Appx 8 Lbs -20 to +60 C (-5 to +140 F) 5.15. Color Off-White (or black)*** ***Ordering Options: NTI-N250140-NCY/M3: painted off white (standard panel) NTI-N250140-NCYB/M3: painted black (special order, minimum quantities apply) 6. WARRANTY This product manufactured by is warranted to be free from defects from workmanship and components for a period of two years from the date of shipment. During this period any defective products shipped prepaid to will be repaired or replaced at our discretion and returned at no further cost to the customer. shall not be liable for any consequential or indirect damage of any type or nature, nor for any cost of reinstallation. Any product that has been subject to improper installation, unauthorized alteration, accident or misuse is rendered void of warranty. also provides a repair service for products not covered by warranty. Charges will be levied for labor, components, and transportation. To return a unit for repair contact the Shipper/Receiver by telephone and obtain a Return Authorization Number. Be prepared to provide the following information. 1. Product Name 2. Product Model Number 3. Product Serial Number 4. Your contact person and phone number. 5. Your company name and return address Package the unit in its original shipping carton or adequate substitute, along with a description of the problem or defect. Clearly mark the outside of the carton with Return Authorization Number and send the unit to the address shown below: NORAN TEL 363 Maxwell Cres. Regina, Saskatchewan Canada, S4N 5X9 Phone: (306) 721-3535 Fax: (306) 721-3507 E-mail: info@norantel.com Internet: http://www.norantel.com Page 4

Mounting Options Page 5

FUSE PWR A BUS A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 OUTPUTS A RETURN BUS A 3 4 5 6 7 8 9 1 10 12 14 15 2 18 17 19 11 13 16 20 A BATTERY RETURNS BUS B www.norantel.com 1 2 4 3 5 6 7 8 9 10 11 12 16 13 14 15 17 18 19 20 OUTPUTS SET 1 B RETURN BAT IN NO NC 19 16 17 15 14 11 10 9 8 7 20 18 6 5 4 13 12 3 2 1 C BUS B GND IN B BATTERY SET 2 RETURNS Drawing Number: EXT PWR B Rev: Drawn with: AutoCAD by Autodesk Computer File: use only 0113-17B Page 6

Page 7 0113-27E.sch