C A Heating Cable Gland Kit Installation Instructions

Similar documents
C A HEATING CABLE GLAND KIT INSTALLATION INSTRUCTIONS

JBS-100-STB Single Entry Power Connection with Junction Box Installation Instructions

PMKG-JS POLYMATRIX SPLICE CONNECTION KIT INSTALLATION INSTRUCTIONS

PMKG-J2LP PolyMatrix Powered Splice Kit Installation Instructions

JBM-100-STB NEMA 4X-rated connection kit Installation Instructions

JBS-100-A, A6 SINGLE ENTRY POWER CONNECTION WITH JUNCTION BOX INSTALLATION INSTRUCTIONS

SPC-P Smart Power Connection with Temperature Monitoring Transmitter Pipe Mounted Installation Instructions

AutoMatrix Power Connection Kit. (1) This type 4X enclosure is intended for indoor or outdoor use primarily to. (2) May be required (see step 1).

EMK-XP ElectroMelt Power Connection and End Seal Kit Installation Instructions

Power-Limiting Cables

HAK-C-100 CONNECTION KIT FOR DIVISION 1 HAZARDOUS LOCATIONS INSTALLATION INSTRUCTIONS

Power Connection Kit installation instructions

Product Overview. Application

Modified polyolefin (-CR) or fluoropolymer (-CT) outer jacket

ET-PWR-END-KIT Installation Instructions (part #JSR00)

HAK-C-100 CONNECTION KIT FOR DIVISION 1 HAZARDOUS LOCATIONS INSTALLATION INSTRUCTIONS

H900 WinterGard Power Connection Kit with End Seal Installation Instructions

MI Heating Cable. HDPE jacketed, copper sheathed MI cable. For surface snow melting in concrete, asphalt, and pavers. MI Heating Cable Configuration

HTP PTP/ PTJ Power Connection Kit for Pipes

WarmlyYours ET-SR Series Heating Cable Installation Manual for Roof & Gutter Deicing

SRK02 Hard Wire Power Connection Kit. Installation, Operation and Maintenance Instructions

PRO-Tect Pipe Freeze Protection Self-Regulating Heating Cable Install Manual (PT-Series)

C Power Connection Kit

PIPE FREEZE PROTECTION AND FLOW MAINTENANCE XL-TRACE SYSTEM

Self-regulating cables

SELF-REGULATING CABLES

XMI-L STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES

QUICKTERM TERMINATION KIT

Self-Regulating Cables

Power Connection Kit Installation Instructions. Terminator ZP-M for use with TEK and HTEK series constant watt heating cables

MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE. For commercial and industrial applications. Heating cable construction

Terminator DP/FAK-2 and FAK-2L. Elbow Splice Kit for Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES

Power Connection Kit Installation Instructions. Terminator DP-M for use with TEK and HTEK series constant watt heating cables

TSRT TSRT Tee Splice Kit Installation Instructions

Nuheat WEATHER-READY HEAT TRACE PIPE FREEZE PROTECTION SYSTEM. Self-Regulating Heating Cable Installation Guide. UV Resistant Polyolefin Outer Jacket

Terminator DL-S for use with BSX *, HTSX, KSX self-regulating, HPT power-limiting, and FP constant watt heating cables

HWAT System INSTALLATION AND OPERATION MANUAL FOR HOT WATER TEMPERATURE MAINTENANCE SYSTEMS FOR THERMALLY INSULATED PIPES

Terminator DP/FAK-4LHT Kit for In-Line Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES

Terminator ZP/FAK-4L Kit Electrically Heated TubeTrace Bundles

Terminator DP/FAK-4 and FAK-4L for In-Line Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES

Terminator DP/FAK-5LHT Kit for Tee Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES

Terminator DP/FAK-5 and FAK-5L

MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE. For heat loss replacement, floor heating and radiant space heating

STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES

UPC Power Connection Kit

Ecoflex potable PEX plus pre-insulated pipe system Installation guide

Terminator ZP/FAK-5 and 5L

VITALink Taped Splice Pigtail Crimp

Terminator ZP/FAK-1 Kit Electrically Heated TubeTrace Bundles

UES-LL End Termination Kit

Installation & Operation Instructions. Type USL Signal Light Kit for Self-Regulating Constant Wattage Heating Cables. Constant Wattage Grommet

Installation Instructions

SERGE BARIL HA-S HAZARDOUS AREA SEAL KIT

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

XL-Trace System. Installation and Operation manual for pipe freeze protection and flow maintenance

WRSS Wraparound Repair Sleeve Installation Instructions

AquaLumin III - Nicheless Light Installation Guide IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

Type LT Self-Regulating Heater Cable For use in Ordinary (Unclassified) and Hazardous (Classified) Locations

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

DEVI EasyConnect Heating Cable Connection System

HTSB system System overview

COYOTE LCC (Low Count Closure)

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

PETK Power and End Termination Kit

POWERHEAT TYPE AHT TERMINATION INSTRUCTIONS. Ref TK/AHT Issue C Date 16 August 1999

IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

Selection Guide. Freeze Protection Heating Cable. Thermwire - Wrap. Thermwire - Wrap Pre-Assembled. Thermwire - Comp. Thermwire - Melt.

ElectroMelt System INSTALLATION AND OPERATION MANUAL FOR SURFACE SNOW MELTING AND ANTI-ICING SYSTEMS

3M Self Regulating Heating Cables

Type LT Self-Regulating Heater Cable For use in Ordinary and Hazardous (Classified) Locations

IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

CS Fiber Optic Splice Case. Instruction

WARNING. Important Notice

In-Line / T-Splice Kit Installation Instructions. Terminator DS-L for use with RSX, TSX, VSX self-regulating heating cables

Self-Regulating Freeze Protection Heating Cable

INSTALLATION GUIDES DekaFlex Connectors DEKAFLEX MC-HL CONNECTOR INSTALLATION GUIDE FOR HAZARDOUS LOCATIONS

Assembly Instruction EL OCHITO WHITE CONTACTS 1000BASE-T/10GBASE-T TYPE I: PIN /SKT CABLE: S/FTP

Air Conditioner for M915 A0/A1 Truck

FIST-GMS2. FIST Generic Mixed Shelf MK2. Contents. 1 Introduction. 5 Termination of the pigtails. 2 General. 6 Splicing + fiber storage

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

NAMSR SELF-REGULATING FREEZE PROTECTION HEATING CABLE SELECTION

Environmental Distribution Center (EDC-06P-NH)

Termination Procedure for Subminiature SolderTacts Contacts for Coaxial Cable: D & D D & D

SLiC Aerial Terminal and Spiral End Seal for use with AMP* Quiet Front Terminal Blocks

Type HLT Self-Regulating Heater Cable For use in Ordinary and Hazardous (Classified) Locations

FIST-GSS2 FIST-GSS3. Fist Generic Splicing Shelf. Contents. 1 Introduction. 2 General. 3 Installation of the shelf. 5 Termination of the pigtails

Heating Cable. Description

Micro Motion F-Series Coriolis Flow and Density Sensors. Installation Manual , Rev CC December 2010

120/240 Volts 3 Watt Floor Heating Cable System

Terminator. DP Power Connection Kit INSTALLATION PROCEDURES

Heating Cable. Description

MARCH COYOTE 9.5 x 19 (292 mm x 509 mm) Terminal Dome Closure Kits

Heating Cable. Cut to Length in Field. Description

Heating Cable. Description

Introduction to Heat Trace Cable Systems

C15C C15C. Page 1 of 20

Frost protection for pipes. 16 Technical handbook. Thermostat with line or ambient temperature sensor

Termination Procedure for 723 Series SolderTacts Contacts for Coaxial Cable: D , D

Transcription:

C75-100-A Heating Cable Gland Kit Installation Instructions Description The C75-100-A is a NEMA 4X-rated gland kit used to transition heating cables into a junction box when making connections off of a pipe, tank or roof. It may be used for power, splice, or tee connections. The C75-100-A is for use with Raychem BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT(1), LBTV2-CT(2), VPL-CT industrial parallel heating cables and GM-X and GM-XT roof and gutter de-icing heating cables. The kit does not include the junction box, flexible tubing, or tape, which are required to make a complete connection. For technical support call Pentair Industrial Heat Tracing Solutions at (800) 545-6258. Approvals Hazardous Locations Class I, Div. 2, Groups A, B, C, D Class II, Div. 2, Groups F, G Class III (1) (2) Ex e II T - WS 877Z (1) T-Rating, same as heating cable (2) Certified for use only when used with a CSA certified Zone 1 enclosure & DIN rail mounted terminal block - WS - WS GM-XT heating cable system Class I, Div. 2, Groups A, B, C, D Kit Contents Item Qty Descript ion A 1 Red grommet B 1 Gland with threaded inserts C 1 Gland with screws D 1 Gland gasket E 1 Locknut F 1 Green/yellow tube G 1 CS-100 core sealer H 1 Terminal block Nonhazardous Locations for GM-X and GM-XT Heating Cable Systems De-icing and snow melting equipment Tools Required Utility knife Needle nose pliers Wire cutters Adjustable pliers Marker Wire stripper (for VPL) 3/16 in (4 mm) or smaller slotted screwdriver No. 2 Phillips or 1/4 in (6 mm) slotted screwdriver For LBTV2-CT only: Heat gun or mini-torch Additional Materials Required Agency approved NEMA 4X-rated junction box with 3/4-in NPT threaded entry or through hole. Tape: GT-66 Installation temperature above 40 F (5 C) GS-54 Installation temperature above 40 F ( 40 C) One length of flexible tubing, 6 ft (1 3/4 m) maximum, Raychem HCTE-1000-0 P/N 3679754004 (1) For KTV-CT only: Order PMK-GP-10 grommet P/N 700823 (2) For LBTV2-CT only: HCS-100-A heat shrink core sealer P/N 257649-000 and PMK-GK-10 grommet P/N 222724-000 For CSA Zone 1 Hazardous Locations: Zone 1 certified enclosure & DIN rail mounted terminal block. A B C D H G F E WARNING: This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all of the installation instructions. To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of Pentair, agency certifications, and the national electrical codes, ground-fault equipment protection must be used. Arcing may not be stopped by conventional circuit breakers. Component approvals and performance are based on the use of Pentair-specified parts only. Do not use substitute parts or vinyl electrical tape. The black heating cable core is conductive and can short. They must be properly insulated and kept dry. Damaged bus wires can overheat or short. Do not break bus wire strands when scoring the jacket or core. Keep components and heating cable ends dry before and during installation. Use only fire-resistant insulation materials, such as fiberglass wrap or flame-retardant foam. CAUTION: Health Hazard: Prolonged or repeated contact with the sealant in the core sealer may cause skin irritation. Wash hands thoroughly. Overheating or burning the sealant will produce fumes that may cause polymer fume fever. Avoid contamination of cigarettes or tobacco. Consult MSDS VEN0058 for further information. CHEMTREC 24-hour emergency telephone: (800) 424-9300 Non-emergency health and safety information: (800) 545-6258. Industrial heat tracing solutions EN-RaychemC75100A-IM-H56343 01/16 1 / 12

Heating cable types VPL-CT Insulated bus wire Bus wire connection Clear jacket Braid Inner jacket Heating element Outer jacket Bus wire BTV-CR, BTV-CT, LBTV2-CT, QTVR-CT, GM-X, GM-XT Inner jacket Conductive core Braid XTV-CT Outer jacket Spacer Fluoropolymer outer jacket (-CT) Tinned-copper braid Fluoropolymer inner jacket Self-regulating polymeric-fiber heating element Nickel-plated copper bus wire 1 Select correct grommet from the chart below. Heating Cable Grommet GM-X, GM-XT, BTV-CR, BTV-CT, QTVR-CT, VPL-CT, XTV-CT Red LBTV2-CT K* KTV-CT P * Order separately WARNING: Use of the wrong grommet can result in leaks, cracked components, shock or fire, and will invalidate approvals and certifications. For LBTV2-CT a separate heat-shrinkable core sealer is required. Order one HCS-100 heat shrink core sealer. 2A For threaded junction boxes For VPL heating cables only: Cut heating cable 12 in (30 cm) from the center of the first indentation. Mount box on wall or bracket. Install gland with threaded inserts into hub. Slide parts onto heating cable. 12 in (30 cm) minimum Indentation (bus wire connection) Note: Use junction box with 3/4-in NPT entry, only. Fully tighten gland into box and orient inserts to plane of heater, as shown. 15 in (40 cm) Slide heating cable through gland and box until it extends 15 in (40 cm) beyond outside edge of box as shown. Use correct grommet (see Step 1) Flexible tube Industrial heat tracing solutions EN-RaychemC75100A-IM-H56343 01/16 2 / 12

2B For through hole junction boxes For VPL heating cables only: Cut heating cable 12 in (30 cm) from the center of the first indentation. Mount box on wall or bracket. Install gland with gasket into box wall; secure with locknut. Slide parts onto heating cable. Lock nut 3/4-in NPT hole in box =1.080 in diameter 12 in (30 cm) minimum Indentation Slide heating cable through (bus wire connection) gland and box until it extends 15 in (40 cm) beyond outside edge of box as shown. Gasket Gland with inserts 15 in (40 cm) Use correct grommet (see step 1) Flexible tube 2C For GM-X, GM-XT and threaded junction boxes (outdoor location) Note: If your installation requires that the heating cable be installed in flexible conduit as shown in 14b, add the appropriate amount of heating cable. WARNING: Prevent mechanical damage. When installed as shown, the junction box is supported by a nonmetallic mounting gland. This method may only be used where the box is not exposed to mechanical stress, static loads, or impact. Protect it with a shield or mount it out of the reach of people or moving equipment. Thread the cap of the Y fitting with 3/4-in NPT entry. Thread the gland fitting without the captive screws into the cap of the Y fitting. Slide parts onto heating cable. 15 in (40 cm) Slide heating cable through gland and box until it extends 15 in (40 cm) beyond outside edge of box as shown. Thread junction box onto gland fitting. Use correct grommet (see Step 1) Y fitting See 14b for details Industrial heat tracing solutions EN-RaychemC75100A-IM-H56343 01/16 3 / 12

2D For GM-X, GM-XT and through hole junction boxes (indoor dry location) Note: If your installation requires that the heating cable be installed in flexible conduit as shown in 14C, add the appropriate amount of heating cable. WARNING: Prevent mechanical damage. When installed as shown, the junction box is supported by a nonmetallic mounting gland. This method may only be used where the box is not exposed to mechanical stress, static loads, or impact. Protect it with a shield or mount it out of the reach of people or moving equipment. Slide parts onto heating cable in the sequence and orientation shown. Bring the Y fitting part together and tighten the two screws. Slide the gasket threaded end with captive screw. Insert thread end into box entry hole and loosely tighten lock nut. Lock nut 3/4-in NPT hole in box =1.080 in diameter Gasket Gland with captive screws Use correct grommet (see step 1) 15 in (40 cm) Slide heating cable through gland and box until it extends 15 in (40 cm) beyond outside edge of box as shown. Tighten lock nut to junction box on gland fitting. Y fitting See 14c for details 3 Lightly score outer jacket around and down as shown. Bend heating cable to break jacket at score, then peel off jacket. Do not cut braid 7 1/2 in (190 mm) 15 in (40 cm) Industrial heat tracing solutions EN-RaychemC75100A-IM-H56343 01/16 4 / 12

4 5A VPL VPL Go to Step 5A Push braid back and bunch as tight as possible. GM-X, GM-XT, BTV, QTVR, LBTV2 Go to Step 5B XTV Go to Step 5C Lightly score inner jacket around and down as shown. 6 in (152 mm) Peel off inner jacket. Unwind heating element, cut and remove as shown. Lightly score clear jacket around and down as shown. 6 in (152 mm) Bend heating cable to break jacket at the score then peel off jacket. Push braid forward. Use a screwdriver to open braid as shown. Bend heating cable and work it through opening in braid. Remove insulation from ends of bus wires. Pull braid tight to make pigtail. 1/2 in (13 mm) Go to Step 6 Industrial heat tracing solutions EN-RaychemC75100A-IM-H56343 01/16 5 / 12

5B GM-X, GM-XT, BTV, QTVR, LBTV2 5C XTV Push braid back to create a pucker. Push braid back to create a pucker. At pucker use a screwdriver to open braid. Bend heating cable and work it through opening in braid. At pucker use a screwdriver to open braid. Bend heating cable and work it through opening in braid. 6 1/2 in (165 mm) Lightly score base jacket around and down as shown. 6 1/2 in (165 mm) Lightly score base jacket around and down as shown. Peel off base jacket. Peel off base jacket. Notch core. Peel bus wire from core. 1/4 in (5 mm) Notch core. Cut and remove all fiber strands. Score core between bus wires at inner jacket. Score and remove center spacer. Bend and snap core. Bend and snap core. Peel core from bus wire. Remove any remaining core material from bus wires. Pull braid tight to make pigtail. Remove any remaining fiber material from bus wires. Pull braid tight to make pigtail. Go to Step 6 Go to Step 6 Industrial heat tracing solutions EN-RaychemC75100A-IM-H56343 01/16 6 / 12

6 7 Mark the jacket as shown. Caution: Health Hazard. Wash hands after contact with sealant. Consult material safety data sheet VEN0058. If needed, re-twist and straighten bus wires, then insert into the guide tubes as shown. Make sure all strands go into the tubes. Tubes 5/8 in (15 mm) 8 Push core sealer onto the heating cable to the mark made in Step 6. Extra force may be required for larger cables or at lower temperatures. 9 Remove the guide tubes and dispose of them in a plastic bag. Make sure the bus wires do not kink, bunch, or crossover. 10 1 in (25 mm) Apply 3 wraps of glass tape (Raychem GT-66 or GS-54). Slip the green/yellow tube onto the braid. Heat shrinking is not required. Industrial heat tracing solutions EN-RaychemC75100A-IM-H56343 01/16 7 / 12

11A For threaded hole junction boxes Pull cable back through gland and box until tape is located just inside hub. Seat grommet in gland as shown. Position gland with screws next to grommet and tighten screws. Thread flexible tube onto gland. Install conduit and pull in power and ground wires for power connections. Tape (hidden) Grommet Flexible tube Gland with screws Gland with Inserts 11B For through hole junction boxes Pull cable back through gland and box until tape is located just inside gland with inserts. Seat grommet in gland as shown. Position gland with screws next to grommet and tighten screws. Thread flexible tube onto gland. Install conduit and pull in power and ground wires for power connections. Tape (hidden) Grommet Flexible tube Gland with screws Gland with inserts Industrial heat tracing solutions EN-RaychemC75100A-IM-H56343 01/16 8 / 12

12 13 Note the following instructions on bus wire preparation: For tee, install two wires in one terminal: - Twist appropriate wire pair together. - Trim twisted wires to 1/2 in (13 mm). Otherwise, trim single wires to 3/8 in (10 mm). 1/2 in (13 mm) 3/8 in (10 mm) Connect bus wires and braid to terminal block. Connect power wires and ground wire to terminal block for power connections. This connection must be protected by a ground-fault equipment protection device. Note: For CSA Zone 1 hazardous locations, discard terminal block supplied with the C75-100-A kit & use a CSA certified Zone 1 DIN rail mounted terminal block. Note: For CSA certified Zone 1 DIN rail mounted terminal blocks, install bus wire in accordance with manufacturer s specifications. 14A Stow wires in box and install lid. Secure flexible tube with tape (Raychem GT-66 or GS-54). Pentair recommends the use of a conduit drain to prevent water condensation build-up. Water tight conduit seal Flexible tube (HCTE-1000-0) Weather seal 6 feet maximum (1 3/4 m) Heating cable Thermal insulation Tape Industrial heat tracing solutions EN-RaychemC75100A-IM-H56343 01/16 9 / 12

14B For GM-X, GM-XT and threaded junction boxes (outdoor location) Install the junction box either directly to the gland fitting in the cap of the Y fitting or to the end of the flexible conduit as shown below. Stow wires in box and install lid. WARNING: Prevent mechanical damage. When installed as shown, the junction box is supported by a nonmetallic mounting gland. This method may only be used where the box is not exposed to mechanical stress, static loads, or impact. Protect it with a shield or mount it out of the reach of people or moving equipment. Pentair recommends the use of a conduit drain to prevent water condensation build-up. 14C For GM-X, GM-XT and through hole junction boxes (indoor dry location) Install the junction box either directly to the gland fitting in the cap of the Y fitting or to the end of the flexible conduit as shown below. Stow wires in box and install lid. WARNING: Prevent mechanical damage. When installed as shown, the junction box is supported by a nonmetallic mounting gland. This method may only be used where the box is not exposed to mechanical stress, static loads, or impact. Protect it with a shield or mount it out of the reach of people or moving equipment. Industrial heat tracing solutions EN-RaychemC75100A-IM-H56343 01/16 10 / 12

14D For installation in instrument enclosures Install the power junction box either directly to the instrument enclosure or to the end of the flexible conduit. Install C75-100-A and associated heat-tracing cable inside the instrument enclosure and close the lid. Heat-tracing cable C75-100-A Power junction box Industrial heat tracing solutions EN-RaychemC75100A-IM-H56343 01/16 11 / 12

WWW.PENTAIRTHERMAL.COM NORTH AMERICA Tel: +1.800.545.6258 Fax: +1.800.527.5703 Tel: +1.650.216.1526 Fax: +1.650.474.7711 thermal.info@pentair.com Europe, Middle East, Africa Tel: +32.16.213.511 Fax: +32.16.213.603 thermal.info@pentair.com Asia Pacific Tel: +86.21.2412.1688 Fax: +86.21.5426.2937 cn.thermal.info@pentair.com Latin America Tel: +1.713.868.4800 Fax: +1.713.868.2333 thermal.info@pentair.com Pentair, BTV, LBTV, QTVR, VPL and XTV are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. 1998-2016 Pentair. PN 391663-000 Industrial heat tracing solutions EN-RaychemC75100A-IM-H56343 01/16 12 / 12