1 C A HEATING CABLE GLAND KIT INSTALLATION INSTRUCTIONS DESCRIPTION The C A is a NEMA 4X-rated gland kit used to transition heating cables into a junction box when making connections off of a pipe, tank or roof. It may be used for power, splice, or tee connections. The C A is for use with Raychem BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT(1), LBTV2-CT(2), VPL-CT industrial parallel heating cables and GM-X and GM-XT roof and gutter de-icing heating cables. The kit does not include the junction box, flexible tubing, or tape, which are required to make a complete connection. For technical support call Pentair Thermal Management at (800) APPROVALS Hazardous Locations Class I, Div. 2, Groups A, B, C, D Class II, Div. 2, Groups F, G Class III Ex e II T (1) (2) (1) T-Rating, same as heating cable (2) Certified for use only when used with a CSA certified Zone 1 enclosure & DIN rail mounted terminal block GM-XT heating cable system Class I, Div. 2, Groups A, B, C, D Nonhazardous Locations for GM-X and GM-XT Heating Cable Systems 877Z De-icing and snow melting equipment TOOLS REQUIRED ADDITIONAL MATERIALS REQUIRED threaded entry or through hole. (1) (2) DIN rail mounted terminal block. KIT CONTENTS Item Qty Descript ion A 1 Red grommet B 1 Gland with threaded inserts C 1 Gland with screws D 1 Gland gasket E 1 Locknut F 1 Green/yellow tube G 1 CS-100 core sealer A B C D H G F E WARNING: This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all of the installation instructions. if the heating cable is damaged or improperly installed, and to comply with the requirements of Pentair Thermal Management, agency certifications, and the national electrical codes, groundfault equipment protection must be used. Arcing may not be stopped by conventional circuit breakers. Pentair Thermal Management-specified parts only. Do not use substitute parts or vinyl electrical tape. must be properly insulated and kept dry. strands when scoring the jacket or core. installation. wrap or flame-retardant foam. CAUTION: HEALTH HAZARD: Prolonged or repeated contact with the sealant in the core sealer may cause skin irritation. Wash hands thoroughly. Overheating or burning the sealant will produce fumes that may cause polymer fume fever. Avoid contamination information.. 1 / 12

2 Heating cable types VPL-CT Insulated bus wire Bus wire connection Clear jacket Braid Inner jacket Heating element Outer jacket Bus wire BTV-CR, BTV-CT, LBTV2-CT, QTVR-CT, GM-X, GM-XT Inner jacket Conductive core Braid Outer jacket Spacer Nickel-plated copper bus wire XTV-CT (for dry environments only) Fluoropolymer outer jacket (-CT) Tinned-copper braid Fluoropolymer inner jacket Self-regulating polymeric-fiber heating element 1 Heating Cable Grommet GM-X, GM-XT, BTV-CR, BTV-CT, QTVR-CT, VPL-CT, XTV-CT Red LBTV2-CT K* KTV-CT P WARNING: Use of the wrong grommet can result in leaks, cracked components, shock or fire, and will invalidate approvals and certifications. 2A For threaded junction boxes center of the first indentation. wall or bracket. threaded inserts into hub. heating cable. 12 in (30 cm) minimum Indentation (bus wire connection) Note: Use junction box with 3/4-in NPT entry, only. Fully tighten gland into box and orient inserts to plane of heater, as shown. 15 in (40 cm) gland and box until it extends 15 in (40 cm) beyond outside edge of box as shown. Use correct grommet (see Step 1) Flexible tube 2 / 12

3 2B For through hole junction boxes center of the first indentation. wall or bracket. gasket into box wall; secure with locknut. heating cable. Lock nut 3/4-in NPT hole in box =1.080 in diameter 12 in (30 cm) minimum Indentation (bus wire connection) gland and box until it extends 15 in (40 cm) beyond outside edge of box as shown. Gasket Gland with inserts 15 in (40 cm) Use correct grommet (see step 1) Flexible tube 2C For GM-X, GM-XT and threaded junction boxes (outdoor location) Note: If your installation requires that the heating cable be installed in flexible conduit as shown in 14b, add the appropriate amount of heating cable. WARNING: Prevent mechanical damage. When installed as shown, the junction box is supported by a nonmetallic mounting gland. This method may only be used where the box is not exposed to mechanical stress, static loads, or impact. Protect it with a shield or mount it out of the reach of people or moving equipment. the Y fitting with fitting without the into the cap of the Y fitting. heating cable. 15 in (40 cm) gland and box until it extends 15 in (40 cm) beyond outside edge of box as shown. gland fitting. Use correct grommet (see Step 1) Y fitting See 14b for details

4 2D For GM-X, GM-XT and through hole junction boxes (indoor dry location) Note: If your installation requires that the heating cable be installed in flexible conduit as shown in 14C, add the appropriate amount of heating cable. WARNING: Prevent mechanical damage. When installed as shown, the junction box is supported by a nonmetallic mounting gland. This method may only be used where the box is not exposed to mechanical stress, static loads, or impact. Protect it with a shield or mount it out of the reach of people or moving equipment. heating cable in the sequence and orientation shown. part together and tighten the two screws. threaded end screw. into box entry hole and loosely tighten lock nut. Lock nut 3/4-in NPT hole in box =1.080 in diameter Gasket Gland with captive screws Use correct grommet (see step 1) 15 in (40 cm) gland and box until it extends 15 in (40 cm) beyond outside edge of box as shown. box on gland fitting. Y fitting See 14c for details 3 jacket. Do not cut braid 7 1/2 in (190 mm) 15 in (40 cm) 4 / 12

5 4 5A VPL VPL Go to Step 5A bunch as tight as possible. GM-X, GM-XT, BTV, QTVR, LBTV2 Go to Step 5B XTV Go to Step 5C jacket around and down as shown. 6 in (152 mm) - shown. jacket around and down as shown. 6 in (152 mm) to break jacket at the score then peel off jacket. to open braid as shown. work it through opening in braid. ends of bus wires. make pigtail. 1/2 in (13 mm) Go to Step 6 5 / 12

6 5B GM-X, GM-XT, BTV, QTVR, LBTV2 5C XTV back to create a pucker. a pucker. - work it through opening in braid. - work it through opening in braid. 6 1/2 in (165 mm) jacket around and down as shown. 6 1/2 in (165 mm) around and down as shown. 1/4 in (5 mm) all fiber strands. wires at inner jacket. center spacer. core material from bus wires. pigtail. fiber material from bus wires. make pigtail. Go to Step 6 Go to Step 6 6 / 12

7 6 7 Caution: Health Hazard. Wash hands after contact with sealant. Consult material safety data sheet VEN0033. If needed, re-twist and straighten bus wires, then insert into the guide tubes as shown. Make sure all strands go into the tubes. Tubes 5/8 in (15 mm) 8 Push core sealer onto the heating cable to the mark made in Step 6. or at lower temperatures. 9 bag. Make sure the bus wires do not kink, bunch, or crossover in (25 mm) not required. 7 / 12

8 11A For threaded hole junction boxes just inside hub. screws. connections. Tape (hidden) Grommet Flexible tube Gland with screws Gland with Inserts 11B For through hole junction boxes just inside gland with inserts. screws. connections. Tape (hidden) Grommet Flexible tube Gland with screws Gland with inserts 8 / 12

9 12 13 Note the following instructions on For tee, install two wires in - Twist appropriate wire pair together. - Trim twisted wires to 1/2 in (13 mm) 3/8 in (10 mm) for power connections. This connection must be protected Note: For CSA Zone 1 hazardous locations, discard terminal block supplied with the C A kit & use a CSA certified Zone 1 DIN rail mounted terminal block. Note: For CSA certified Zone 1 DIN rail mounted terminal blocks, install bus wire in accordance with manufacturer s specifications. 14A (Raychem GT-66 or GS-54). Pentair Thermal Management recommends the use of a conduit drain to prevent water condensation build-up. Water tight conduit seal Flexible tube (HCTE ) Weather seal 6 feet maximum (1 3/4 m) Heating cable Thermal insulation Tape

10 14B For GM-X, GM-XT and threaded junction boxes (outdoor location) the cap of the Y fitting or to the end of the flexible conduit as shown below. WARNING: Prevent mechanical damage. When installed as shown, the junction box is supported by a nonmetallic mounting gland. This method may only be used where the box is not exposed to mechanical stress, static loads, or impact. Protect it with a shield or mount it out of the reach of people or moving equipment. Pentair Thermal Management recommends the use of a condensation build-up. 14C For GM-X, GM-XT and through hole junction boxes (indoor dry location) the cap of the Y fitting or to the end of the flexible conduit as shown below. WARNING: Prevent mechanical damage. When installed as shown, the junction box is supported by a nonmetallic mounting gland. This method may only be used where the box is not exposed to mechanical stress, static loads, or impact. Protect it with a shield or mount it out of the reach of people or moving equipment. 10 / 12

11 14D For installation in instrument enclosures instrument enclosure or to the end of the flexible conduit. the instrument enclosure and close the lid. Heat-tracing cable C A Power junction box 11 / 12

12 NORTH AMERICA Tel: Fax: Tel: Fax: EUROPE, MIDDLE EAST, AFRICA Tel: Fax: ASIA PACIFIC Tel: Fax: LATIN AMERICA Tel: Fax: Pentair, BTV, LBTV, QTVR, VPL and XTV are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice Pentair. PN / 12

C A Heating Cable Gland Kit Installation Instructions

C A Heating Cable Gland Kit Installation Instructions C75-100-A Heating Cable Gland Kit Installation Instructions Description The C75-100-A is a NEMA 4X-rated gland kit used to transition heating cables into a junction box when making connections off of a

More information

JBM-100-STB NEMA 4X-rated connection kit Installation Instructions

JBM-100-STB NEMA 4X-rated connection kit Installation Instructions JBM-100-STB NEMA 4X-rated connection kit Installation Instructions Power Connection, Powered Splice, Powered Tee, Dual Power Connection, Splice or Tee with Junction Box Approvals Hazardous Locations CLI,

More information

JBS-100-A, A6 SINGLE ENTRY POWER CONNECTION WITH JUNCTION BOX INSTALLATION INSTRUCTIONS

JBS-100-A, A6 SINGLE ENTRY POWER CONNECTION WITH JUNCTION BOX INSTALLATION INSTRUCTIONS JBS-100-A, A6 SINGLE ENTRY POWER CONNECTION WITH JUNCTION BOX INSTALLATION INSTRUCTIONS DESCRIPTION The JBS-100-A and JBS-100-A6 are NEMA 4X-rated power connection kit. It is designed for use with Raychem

More information

JBS-100-STB Single Entry Power Connection with Junction Box Installation Instructions

JBS-100-STB Single Entry Power Connection with Junction Box Installation Instructions JBS-100-STB Single Entry Power Connection with Junction Box Installation Instructions Description The JBS-100-STB is a NEMA 4X rated power connection kit. It is designed for use with Raychem BTV-CR, BTV-CT,

More information

PMKG-J2LP PolyMatrix Powered Splice Kit Installation Instructions

PMKG-J2LP PolyMatrix Powered Splice Kit Installation Instructions PMKG-J2LP PolyMatrix Powered Splice Kit Installation Instructions Description The PolyMatrix PMKG-J2LP is a NEMA 4X rated connection kit for use with Raychem BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT and

More information

PMKG-JS POLYMATRIX SPLICE CONNECTION KIT INSTALLATION INSTRUCTIONS

PMKG-JS POLYMATRIX SPLICE CONNECTION KIT INSTALLATION INSTRUCTIONS PMKG-JS POLYMATRIX SPLICE CONNECTION KIT INSTALLATION INSTRUCTIONS DESCRIPTION The PolyMatrix PMKG-JS is a NEMA 4X rated splice connection kit for use with Raychem BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT

More information

SPC-P Smart Power Connection with Temperature Monitoring Transmitter Pipe Mounted Installation Instructions

SPC-P Smart Power Connection with Temperature Monitoring Transmitter Pipe Mounted Installation Instructions SPC-P Smart Power Connection with Temperature Monitoring Transmitter Pipe Mounted Installation Instructions SPC-P with Pyrotenax MI heating cable using required MI cable grounding kit SPC-P with Raychem

More information

AutoMatrix Power Connection Kit. (1) This type 4X enclosure is intended for indoor or outdoor use primarily to. (2) May be required (see step 1).

AutoMatrix Power Connection Kit. (1) This type 4X enclosure is intended for indoor or outdoor use primarily to. (2) May be required (see step 1). R AMG-BC-III AutoMatrix Power Connection Kit Description The AMG-BC-III is a copper free aluminum (maximum 4/10 of 1% copper) NEMA 4X (1) rated power connection kit for single or dual heating cable entry.

More information

EMK-XP ElectroMelt Power Connection and End Seal Kit Installation Instructions

EMK-XP ElectroMelt Power Connection and End Seal Kit Installation Instructions EMK-XP ElectroMelt Power Connection and End Seal Kit Installation Instructions Description The ElectroMelt EMK-XP Power Connection and End Seal Kit is for use with ElectroMelt EM2-XR and EM3-XR heating

More information

Power-Limiting Cables

Power-Limiting Cables Power-Limiting Cables This section provides general design guidelines for power-limiting heat-tracing systems installed on insulated metal pipes. For other applications or design assistance, contact your

More information

HAK-C-100 CONNECTION KIT FOR DIVISION 1 HAZARDOUS LOCATIONS INSTALLATION INSTRUCTIONS

HAK-C-100 CONNECTION KIT FOR DIVISION 1 HAZARDOUS LOCATIONS INSTALLATION INSTRUCTIONS HAK-C-100 CONNCTION KIT FO DIVISION 1 HAZADOUS LOCATIONS INSTALLATION INSTUCTIONS APPOVALS Hazardous Locations (1) (1) xcept VPL. KIT CONTNTS Class I, Div. 1, Groups B, C, D Class II, Div. 1, Groups, F,

More information

Product Overview. Application

Product Overview. Application Self-Regulating SC, SC/H Series-resistance heating cables for longline systems Electrical freeze protection for long pipelines in both nonhazardous and hazardous locations Power-Limiting Mineral Insulated

More information

Modified polyolefin (-CR) or fluoropolymer (-CT) outer jacket

Modified polyolefin (-CR) or fluoropolymer (-CT) outer jacket SELF-REGULATING HEATING CABLE For pipe freeze protection and flow maintenance Heating cable construction Tinned-copper braid Modified polyolefin (-CR) or fluoropolymer (-CT) outer jacket Modified polyolefin

More information

Power Connection Kit installation instructions

Power Connection Kit installation instructions Operating instructions & Parts Manual ET00 Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and

More information

MI Heating Cable. HDPE jacketed, copper sheathed MI cable. For surface snow melting in concrete, asphalt, and pavers. MI Heating Cable Configuration

MI Heating Cable. HDPE jacketed, copper sheathed MI cable. For surface snow melting in concrete, asphalt, and pavers. MI Heating Cable Configuration MI Heating Cable HDPE jacketed, copper sheathed MI cable For surface snow melting in concrete, asphalt, and pavers Pipe Freeze Protection and Flow Maintenance Fire Sprinkler System Freeze Protection MI

More information

Self-regulating cables

Self-regulating cables Self-Regulating Self-regulating cables This step-by-step design guide provides the tools necessary to design a selfregulating heat-tracing system for insulated pipes and tubing. For other applications

More information

SELF-REGULATING CABLES

SELF-REGULATING CABLES Self-Regulating SELF-REGULATING CABLES This step-by-step design guide provides the tools necessary to design a selfregulating heat-tracing system for insulated pipes and tubing. For other applications

More information

HAK-C-100 CONNECTION KIT FOR DIVISION 1 HAZARDOUS LOCATIONS INSTALLATION INSTRUCTIONS

HAK-C-100 CONNECTION KIT FOR DIVISION 1 HAZARDOUS LOCATIONS INSTALLATION INSTRUCTIONS HAK-C-100 CONNCTION KIT FO DIVISION 1 HAZADOUS LOCATIONS INSTALLATION INSTUCTIONS APPOVALS Hazardous Locations (1) (1) xcept VPL. KIT CONTNTS Class I, Div. 1, Groups B, C, D Class II, Div. 1, Groups, F,

More information

Self-Regulating Cables

Self-Regulating Cables Self-Regulating 1. Self- Regulating 2. Power- Limiting This step-by-step design guide provides the tools necessary to design a self-regulating heat-tracing system for insulated pipes and tubing. For other

More information

H900 WinterGard Power Connection Kit with End Seal Installation Instructions

H900 WinterGard Power Connection Kit with End Seal Installation Instructions H900 WinterGard Power Connection Kit with End Seal Installation Instructions Power connection for H311, H611, and H621 Power connection for H612 and H622 Description The WinterGard power connection kit

More information

PIPE FREEZE PROTECTION AND FLOW MAINTENANCE XL-TRACE SYSTEM

PIPE FREEZE PROTECTION AND FLOW MAINTENANCE XL-TRACE SYSTEM PIPE FREEZE PROTECTION AND FLOW MAINTENANCE XL-TRACE SYSTEM This step-by-step design guide provides the tools necessary to design a Raychem XL-Trace pipe freeze protection or flow maintenance system. For

More information

ET-PWR-END-KIT Installation Instructions (part #JSR00)

ET-PWR-END-KIT Installation Instructions (part #JSR00) (part #JSR00) Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety

More information

XMI-L STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES

XMI-L STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES XMI-L STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES cable construction Corrugated stainless steel 316L outer sheath Insulation (magnesium oxide) conductors (dual)

More information

MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE. For commercial and industrial applications. Heating cable construction

MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE. For commercial and industrial applications. Heating cable construction MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE For commercial and industrial applications Heating cable construction Insulation (magnesium oxide) Heating conductor Copper sheath HDPE

More information

WarmlyYours ET-SR Series Heating Cable Installation Manual for Roof & Gutter Deicing

WarmlyYours ET-SR Series Heating Cable Installation Manual for Roof & Gutter Deicing WarmlyYours ET-SR Series Heating Cable Installation Manual for Roof & Gutter Deicing Free Design Service 24/7 Installation Support (800) 875-5285 www.warmlyyours.com Assembly Tools Needed Utility knife

More information

Terminator DP/FAK-2 and FAK-2L. Elbow Splice Kit for Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES

Terminator DP/FAK-2 and FAK-2L. Elbow Splice Kit for Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES Elbow Splice Kit for Electrically Heated TubeTrace Bundles The following installation procedures are suggested guidelines for the installation of the Kit. Receiving, Storing and Handling 1. Inspect materials

More information

HTP PTP/ PTJ Power Connection Kit for Pipes

HTP PTP/ PTJ Power Connection Kit for Pipes HTP 1548-40PTP/1548-40PTJ Power Connection Kit for Pipes For use with Dekoron 2700 and 2300 Families of Heating Cables. 1548-81HTJ/81HTP for use with 2000 Series Heating Cables. Installation Instructions

More information

Terminator ZP/FAK-4L Kit Electrically Heated TubeTrace Bundles

Terminator ZP/FAK-4L Kit Electrically Heated TubeTrace Bundles Terminator ZP/ Kit Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES Listed Cable System 137M Terminator ZP/ The following installation procedures are suggested guidelines for the installation

More information

C Power Connection Kit

C Power Connection Kit 1548-4000C Power Connection Kit For use with Dekoron 2700 Family of Heating Cables Installation Instructions Kit Description The Dekoron 1548-4000C electrical connection kit distirbuted by Heat-Line is

More information

QUICKTERM TERMINATION KIT

QUICKTERM TERMINATION KIT PYROTENAX QUICKTERM TERMINATION KIT INSTALLATION INSTRUCTIONS FOR TERMINATING SINGLE CONDUCTOR COPPER SHEATHED MINERAL INSULATED CABLE DESCRIPTION This termination kit is used to terminate #6 AWG and larger

More information

Terminator DP/FAK-5LHT Kit for Tee Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES

Terminator DP/FAK-5LHT Kit for Tee Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES Terminator DP/FAK-5LHT Kit for Tee Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES Terminator DP/FAK-5LHT The following installation procedures are suggested guidelines for the

More information

Power Connection Kit Installation Instructions. Terminator ZP-M for use with TEK and HTEK series constant watt heating cables

Power Connection Kit Installation Instructions. Terminator ZP-M for use with TEK and HTEK series constant watt heating cables Power Connection Kit Installation Instructions Terminator ZP-M for use with TEK and HTEK series constant watt heating cables For Power Connection (1 Cable), In-Line Splice Connection, or End Termination

More information

Terminator DP/FAK-4 and FAK-4L for In-Line Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES

Terminator DP/FAK-4 and FAK-4L for In-Line Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES for In-Line Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES The following installation procedures are suggested guidelines for the installation of the Terminator DP/FAK-4 and FAK-4L

More information

PRO-Tect Pipe Freeze Protection Self-Regulating Heating Cable Install Manual (PT-Series)

PRO-Tect Pipe Freeze Protection Self-Regulating Heating Cable Install Manual (PT-Series) PRO-Tect Pipe Freeze Protection Self-Regulating Heating Cable Install Manual () Free Design Service 24/7 Installation Support (800) 875-5285 www.warmlyyours.com Assembly Tools Needed Utility knife Wire

More information

HWAT System INSTALLATION AND OPERATION MANUAL FOR HOT WATER TEMPERATURE MAINTENANCE SYSTEMS FOR THERMALLY INSULATED PIPES

HWAT System INSTALLATION AND OPERATION MANUAL FOR HOT WATER TEMPERATURE MAINTENANCE SYSTEMS FOR THERMALLY INSULATED PIPES HWAT System INSTALLATION AND OPERATION MANUAL FOR HOT WATER TEMPERATURE MAINTENANCE SYSTEMS FOR THERMALLY INSULATED PIPES THERMAL MANAGEMENT SOLUTIONS WWW.THERMAL.PENTAIR.COM Important Safeguards and Warnings

More information

TSRT TSRT Tee Splice Kit Installation Instructions

TSRT TSRT Tee Splice Kit Installation Instructions TSRT TSRT Tee Splice Kit Installation Instructions Description The TSRS Splice Connection Kit is for use with all versions of EasyHeat s self regulating heater cables smaller than 0.44 (11mm) in diameter.

More information

Nuheat WEATHER-READY HEAT TRACE PIPE FREEZE PROTECTION SYSTEM. Self-Regulating Heating Cable Installation Guide. UV Resistant Polyolefin Outer Jacket

Nuheat WEATHER-READY HEAT TRACE PIPE FREEZE PROTECTION SYSTEM. Self-Regulating Heating Cable Installation Guide. UV Resistant Polyolefin Outer Jacket Nuheat WEATHER-READY HEAT TRACE PIPE FREEZE PROTECTION SYSTEM Self-Regulating Heating Cable Installation Guide Tinned Copper Braid UV Resistant Polyolefin Outer Jacket 16 AWG Bus Wire Polyolefin Inner

More information

SRK02 Hard Wire Power Connection Kit. Installation, Operation and Maintenance Instructions

SRK02 Hard Wire Power Connection Kit. Installation, Operation and Maintenance Instructions SRK02 Hard Wire Power Connection Kit Installation, Operation and Maintenance Instructions IMPORTANT: Save These Instructions! Item Qty Description A 1 Black heat shrink tube (1/2 dia. x 1 length) B 2 Black

More information

Terminator DP/FAK-4LHT Kit for In-Line Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES

Terminator DP/FAK-4LHT Kit for In-Line Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES Terminator DP/HT Kit for In-Line Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES Terminator DP/HT The following installation procedures are suggested guidelines for the installation

More information

Power Connection Kit Installation Instructions. Terminator DP-M for use with TEK and HTEK series constant watt heating cables

Power Connection Kit Installation Instructions. Terminator DP-M for use with TEK and HTEK series constant watt heating cables Power Connection Kit Installation Instructions Terminator DP-M for use with TEK and HTEK series constant watt heating cables For Power Connection (1 Cable), In-Line Splice Connection, or End Termination

More information

Terminator DP/FAK-5 and FAK-5L

Terminator DP/FAK-5 and FAK-5L for T-Splice of Electrically Heated TubeTrace Bundles INSTALLATION PROCEDURES The following installation procedures are suggested guidelines for the installation of the Terminator DP/FAK-5 and FAK-5L:

More information

STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES

STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES Insulation (magnesium oxide) conductors (dual) Corrugated stainless steel 316L outer sheath Alloy 825 sheath cable

More information

Terminator ZP/FAK-1 Kit Electrically Heated TubeTrace Bundles

Terminator ZP/FAK-1 Kit Electrically Heated TubeTrace Bundles Terminator ZP/ Kit Electrically Heated TubeTrace Bundles Listed Cable System 17M Terminator ZP/ The following installation procedures are suggested guidelines for the installation of the Terminator ZP/

More information

DEVI EasyConnect Heating Cable Connection System

DEVI EasyConnect Heating Cable Connection System Installation Instructions DEVI EasyConnect Heating Cable Connection System IP 68 0 mm 10 20 30 40 50 60 70 80 90 100 110 120 Standards: DIN VDE 0606 T200, DIN EN 61984 (VDE 0627), VDE 0110 IEC 60999; CSA:

More information

Terminator DL-S for use with BSX *, HTSX, KSX self-regulating, HPT power-limiting, and FP constant watt heating cables

Terminator DL-S for use with BSX *, HTSX, KSX self-regulating, HPT power-limiting, and FP constant watt heating cables Lighted Power Connection / Lighted End Termination Kit Installation Instructions Terminator DL-L for use with RSX, TSX, VSX self-regulating heating cables Terminator DL-S for use with BSX *, HTSX, KSX

More information

HTSB system System overview

HTSB system System overview HTSB system System overview Easy planning of heating circuits Simple installation on site Wide operating temperature range The BARTEC HTSB heating system covers a wide range of applications in trace heating.

More information

Terminator ZP/FAK-5 and 5L

Terminator ZP/FAK-5 and 5L for of Electrically Heated TubeTrace Bundles Listed Cable System 17M Ordinary & Hazardous Locations Class I, Division, Groups A, B, C & D Class II, Division, Groups F & G, Class III Class I, Zone 1, AEx

More information

SERGE BARIL HA-S HAZARDOUS AREA SEAL KIT

SERGE BARIL HA-S HAZARDOUS AREA SEAL KIT INSTRUCTIONS DESCRIPTION The HA-S Hazardous Area Seal Kit provides the cable termination and explosion proof seal parts needed to make all in-line electrical splice connections associated with Serge Baril

More information

Type LT Self-Regulating Heater Cable For use in Ordinary (Unclassified) and Hazardous (Classified) Locations

Type LT Self-Regulating Heater Cable For use in Ordinary (Unclassified) and Hazardous (Classified) Locations F, G ;, Class I, Class Groups F, G; Operating Principle The parallel bus wires apply voltage along the entire length of the heater cable. The conductive core provides an infinite number of parallel conductive

More information

UPC Power Connection Kit

UPC Power Connection Kit Installation Instructions UPC Power Connection Kit For Self-Regulating & Constant Wattage Heating Cables PJ495-5 161-562581-029 January 2017 2 UPC Power Connection Kit Self-Regulating & Constant Wattage

More information

UES-LL End Termination Kit

UES-LL End Termination Kit Installation Instructions UES-LL End Termination Kit for Series Long Line Heating Cables 1 PJ950 161-562681-022 July 2015 UES-LL End Termination Kit Kit Contents Item Qty Description Item Qty Description

More information

Type LT Self-Regulating Heater Cable For use in Ordinary and Hazardous (Classified) Locations

Type LT Self-Regulating Heater Cable For use in Ordinary and Hazardous (Classified) Locations A, I, A, Operating Principle The parallel bus wires apply voltage along the entire length of the heater cable. The conductive core provides an infinite number of parallel conductive paths permitting the

More information

XL-Trace System. Installation and Operation manual for pipe freeze protection and flow maintenance

XL-Trace System. Installation and Operation manual for pipe freeze protection and flow maintenance XL-Trace System Installation and Operation manual for pipe freeze protection and flow maintenance Thermal building solutions WWW.PENTAIRTHERMAL.COM Important Safeguards and Warnings WARNING: FIRE AND SHOCK

More information

Ecoflex potable PEX plus pre-insulated pipe system Installation guide

Ecoflex potable PEX plus pre-insulated pipe system Installation guide Ecoflex potable PEX plus pre-insulated pipe system Installation guide Ecoflex potable PEX plus pre-insulated pipe system installation guide l 1 Uponor Ecoflex potable PEX plus pre-insulated pipe system

More information

MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE. For heat loss replacement, floor heating and radiant space heating

MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE. For heat loss replacement, floor heating and radiant space heating MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE For heat loss replacement, floor heating and radiant space heating MI Configuration Type SUA Design A Heated length lead length PRODUCT

More information

In-Line / T-Splice Kit Installation Instructions. Terminator DS-L for use with RSX, TSX, VSX self-regulating heating cables

In-Line / T-Splice Kit Installation Instructions. Terminator DS-L for use with RSX, TSX, VSX self-regulating heating cables In-Line / T-Splice Kit Installation Instructions Terminator DS-L for use with RSX, TSX, VSX self-regulating heating cables Terminator DS-S for use with BSX *, HTSX, KSX self-regulating, HPT power-limiting,

More information

PETK Power and End Termination Kit

PETK Power and End Termination Kit Power and End Termination Kit -1 for BSX, RSX, VSX - for KSX, HTSX - for HPT, FP --ECM for HPT, FP --ZT for HPT, FP Order separately to be used in conjunction with Thermon connection kits Receiving, Storing

More information

Installation Instructions

Installation Instructions K-Series Constant-Wattage Heating Cable Installation Instructions Read and understand this material before installing this heater. Failure to understand how to safely install the heater could result in

More information

VITALink Taped Splice Pigtail Crimp

VITALink Taped Splice Pigtail Crimp A Marmon Wire & Cable Berkshire Hathaway Company VITALink Taped Splice Pigtail Crimp 1 Hour Fire-Rated Splice VITALink MC Cables, UL FHIT 120 Installation Instructions Description The VITALink Taped Splice

More information

PETK Power and End Termination Kit

PETK Power and End Termination Kit PETK Power and End Termination Kit INSTALLATION PROCEDURES Made in USA PETK-1 for BSX, RSX, VSX PETK- for KSX, HTSX PETK- for HPT, FP PETK--ECM for HPT, FP Order separately to be used in conjunction with

More information

3M Self Regulating Heating Cables

3M Self Regulating Heating Cables 2 Construction & Function 3M Self Regulating Heating Cables Introduction: 3M Canada and Thermon Manufacturing Company have entered into a strategic alliance to market the commercial line of heat tracing

More information

Selection Guide. Freeze Protection Heating Cable. Thermwire - Wrap. Thermwire - Wrap Pre-Assembled. Thermwire - Comp. Thermwire - Melt.

Selection Guide. Freeze Protection Heating Cable. Thermwire - Wrap. Thermwire - Wrap Pre-Assembled. Thermwire - Comp. Thermwire - Melt. Thermwire Freeze Protection Heating Cable Selection Guide Thermwire - Wrap Pipe Freeze Protection Heating Cable Thermwire - Wrap Pre-Assembled Pipe Freeze Protection Heating Cable with Attached Cord &

More information

Type HLT Self-Regulating Heater Cable For use in Ordinary and Hazardous (Classified) Locations

Type HLT Self-Regulating Heater Cable For use in Ordinary and Hazardous (Classified) Locations E, I, E, Description Nelson s Type HLT self-regulating heater cable is a parallel circuit electric heater strip. A conductive fluoropolymer core material is extruded over the multi-stranded, nickel-plated,

More information

COYOTE LCC (Low Count Closure)

COYOTE LCC (Low Count Closure) PLP Feature Focus 2009 Preformed Line Products OCTOBER 2012 Film available at www.preformed.com COYOTE LCC (Low Count Closure) Be sure to read and completely understand this procedure before applying product.

More information

XL-Trace. Self-regulating conductive core. Nickel-plated copper bus wire

XL-Trace. Self-regulating conductive core. Nickel-plated copper bus wire Visit www.tycothermal.com for more information on our ten-year extended warranty. Raychem XL-Trace is designed for pipe freeze protection and flow maintenance in the following applications: Freeze protection

More information

120/240 Volts 3 Watt Floor Heating Cable System

120/240 Volts 3 Watt Floor Heating Cable System WA-3CWC 120/240 Volts 3 Watt Floor Heating Cable System Warm Cable floor heating system combines the highest comfort levels with maximum energy efficiency. It is a proven technology that is safe, reliable

More information

TubeTrace Tubing Bundles

TubeTrace Tubing Bundles for Custom CEMS and Analytical Umbilicals English Units Receiving, Storing and Handling... 1. Inspect materials for damage incurred during shipping. Report damages to carrier for settlement. 2. Identify

More information

Heating Cable. Description

Heating Cable. Description Single Entry Power Connection Kit NEMA 4X Entry for 1 Cable 3/4 Conduit Hub Opening Lighted or Non-Lighted Multiple Entry Connection Box NEMA 4X Entry for up to 3 Cables Power, Splice or Tee Connection

More information

Self-Regulating Freeze Protection Heating Cable

Self-Regulating Freeze Protection Heating Cable D PDS SRF Self-Regulating Freeze Protection Heating Cable E C B A Output Self-Regulating, Energy Efficient Cost Effective for Contractor/Construction Freeze Protection Application Freeze Protection of

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TABLE OF CONTENTS GENERAL...2 SPECIFICATIONS...2 PACKAGE CONTENTS...2 PACKAGE CONTENTS: ACCESSORIES...3 REQUIRED TOOLS...3 ADD-ON COMPONENTS...3 CLOSURE MOUNTING...3 LOCK AND UNLOCK EXTERIOR DOOR...3 CABLE

More information

FLX TM Self-Regulating Winterization/Freeze Protection INSTALLATION PROCEDURES

FLX TM Self-Regulating Winterization/Freeze Protection INSTALLATION PROCEDURES FLX TM Self-Regulating Winterization/Freeze Protection INSTALLATION PROCEDURES FLX TM Self-Regulating Refer to the FLX Cable Testing Report for required recording of test data and circuit information.

More information

POWERHEAT TYPE AHT TERMINATION INSTRUCTIONS. Ref TK/AHT Issue C Date 16 August 1999

POWERHEAT TYPE AHT TERMINATION INSTRUCTIONS. Ref TK/AHT Issue C Date 16 August 1999 STOCKPORT, ENGLAND, TEL: 0161-430 8333 POWERHEAT TYPE AHT TERMINATION INSTRUCTIONS PLEASE READ THE INSTRUCTIONS BEFORE PROCEEDING Recommended Tools ANNEX B Ref TK/AHT Issue C Date 16 August 1999 Heavy

More information

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits 3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits With High-K Stress Relief For 3-Conductor Type G (Ground Wire), Copper Tape Shield, Armored Cables 7600-S-3G Series Instructions IEEE Std.

More information

AquaLumin III - Nicheless Light Installation Guide IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

AquaLumin III - Nicheless Light Installation Guide IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS 16 1 AquaLumin III - Nicheless Light Installation Guide IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS Section Contents 1. Installing a mounting bracket and light

More information

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination 3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination Instructions IEEE Std. No. 48 Class 1 Termination CAUTION Working around energized electrical systems may

More information

Heating Cable. Cut to Length in Field. Description

Heating Cable. Cut to Length in Field. Description Self-Regulating Freeze Protection D E C B A Self-Regulating, Energy Efficient Designed for Freeze Protection Max. Exposure Temp. 185 F Temperature Cost Effective for Commercial Construction Freeze Protection

More information

Heating Cable. Description

Heating Cable. Description 203312 Single Entry Connection Box NEMA 4X Entry for 1 Cable 3/4 Conduit Hub Opening Multiple Entry Connection Box NEMA 4X Entry for up to 3 Cables Power or Tee Connection 3/4 Conduit Hub Opening End Seal

More information

ElectroMelt System INSTALLATION AND OPERATION MANUAL FOR SURFACE SNOW MELTING AND ANTI-ICING SYSTEMS

ElectroMelt System INSTALLATION AND OPERATION MANUAL FOR SURFACE SNOW MELTING AND ANTI-ICING SYSTEMS ElectroMelt System INSTALLATION AND OPERATION MANUAL FOR SURFACE SNOW MELTING AND ANTI-ICING SYSTEMS THERMAl MANAGEMENT WWW.PENTAIRTHERMAl.COM Important Safeguards and Warnings WARNING: FIRE AND SHOCK

More information

Frost protection for pipes. 16 Technical handbook. Thermostat with line or ambient temperature sensor

Frost protection for pipes. 16 Technical handbook. Thermostat with line or ambient temperature sensor Frozen pipes can be a costly problem. When pipes are exposed to subzero temperatures they can burst, leading to considerable damage and disruption. The Raychem frost protection system provides an efficient

More information

Heating Cable. Description

Heating Cable. Description 203312 Single Entry Connection Box NEMA 4X Entry for 1 Cable 3/4 Conduit Hub Opening Multiple Entry Connection Box NEMA 4X Entry for up to 3 Cables Power or Tee Connection 3/4 Conduit Hub Opening End Seal

More information

Micro Motion F-Series Coriolis Flow and Density Sensors. Installation Manual , Rev CC December 2010

Micro Motion F-Series Coriolis Flow and Density Sensors. Installation Manual , Rev CC December 2010 Micro Motion F-Series Coriolis Flow and Density Sensors Installation Manual 20002298, Rev CC December 2010 Safety and approval information This Micro Motion product complies with all applicable European

More information

IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS 1 AQUALUMIN III NICHELESS POOL LIGHT INSTALLATION GUIDE IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS Section Contents 1. Installing a mounting bracket and light

More information

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526 Product HVS Series Cable Splice Shim Kit for 1/C Extruded Dielectric (Poly/EPR) Power Cables: Metallic Tape, Wire Shield, UniShield, LC Shield, Lead Sheath or Concentric Neutral URD Cables UniShield is

More information

NAMSR SELF-REGULATING FREEZE PROTECTION HEATING CABLE SELECTION

NAMSR SELF-REGULATING FREEZE PROTECTION HEATING CABLE SELECTION Self-Regulating, Energy Efficient Cost Effective for Contractor/Construction Freeze Protection Application Industrial Grade, 16 AWG Buss Wire Standard Braid with Overjacket Circuit Lengths to 460 Feet

More information

Heating Cables. For Industry Tracing

Heating Cables. For Industry Tracing Heating Cables For Industry Tracing FATI-FFHT-X 1/2 FFHT-X Features Energy efficient, automatically varies its power output in response to pipe temperature changes. Easy to install, can be cut to any length

More information

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit 3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit With High-K Stress Relief For 3-Conductor Copper Tape Shield Cables with or without Ground Wires 7600-T-3RJS Series Instructions

More information

SCTK INSTALLATION PROCEDURES. Splice Connection Termination Kit. SCTK-1 for BSX, RSX, VSX SCTK-2 for KSX, HTSX SCTK-3 for HPT, FP

SCTK INSTALLATION PROCEDURES. Splice Connection Termination Kit. SCTK-1 for BSX, RSX, VSX SCTK-2 for KSX, HTSX SCTK-3 for HPT, FP Splice Connection Termination Kit INSTALLATION PROCEDURES SCTK- for BSX, RSX, VSX SCTK- for KSX, HTSX SCTK- for HPT, FP To be used in conjunction with Thermon Connection kits Receiving, Storing and Handling....

More information

FAK-7HTS High Temperature Tubing Bundle End Seal Kit INSTALLATION PROCEDURES

FAK-7HTS High Temperature Tubing Bundle End Seal Kit INSTALLATION PROCEDURES High Temperature End Seal Kit The following procedures are guidelines for the installation of the FAK-7HTS High Temp. End Seal Kit. Receiving, Storing and Handling... 1. Inspect materials for damage incurred

More information

Introduction to Heat Trace Cable Systems

Introduction to Heat Trace Cable Systems Introduction Introduction to Heat Trace Cable Systems Tempco s Heat Trace Cables are used to counteract the effects of heat dissipation from process pipe and equipment through its insulation (if any).

More information

PETK Power and End Termination Kit

PETK Power and End Termination Kit Power and End Termination Kit PETK-1D PETK-2D PETK-D for BSX, RSX, VSX for KSX, HTSX for HPT, FP Order separately to be used in conjunction with Thermon connection kits Receiving, Storing and Handling...

More information

Termination Procedure for Subminiature SolderTacts Contacts for Coaxial Cable: D & D D & D

Termination Procedure for Subminiature SolderTacts Contacts for Coaxial Cable: D & D D & D Print 12-Jun-03 1 of 11 Termination Procedure for Subminiature SolderTacts Contacts for Coaxial Cable: D-602-0218 & D-602-0219 D-602-0278 & D-602-0279 1. Scope This standard contains the termination procedures,

More information

Industrial, Heavy Insulated Mono-Tape. and Duo-Tape

Industrial, Heavy Insulated Mono-Tape. and Duo-Tape Industrial, Heavy Insulated Mono-Tape and Duo-Tape Description: HTS/Amptek AWD and AWM Heating Tapes are Single and Double Duo-Tapes designed for use in high temperature applications. AWD and AWM Heating

More information

Assembly Instruction EL OCHITO WHITE CONTACTS 1000BASE-T/10GBASE-T TYPE I: PIN /SKT CABLE: S/FTP

Assembly Instruction EL OCHITO WHITE CONTACTS 1000BASE-T/10GBASE-T TYPE I: PIN /SKT CABLE: S/FTP AI85112-02 Assembly Instruction EL OCHITO WHITE CONTACTS 1000BASE-T/10GBASE-T TYPE I: PIN 858-003-02/SKT 858-032-02 CABLE: 963-033-26 S/FTP Revision History Rev Date Initiated By Approved 1 07/05/18 WLL

More information

COPPER SHEATHED, MINERAL INSULATED FIRE-RATED WIRING CABLE

COPPER SHEATHED, MINERAL INSULATED FIRE-RATED WIRING CABLE PYOTENAX SYSTEM 1850 COPPE SHEATHED, MINEAL INSULATED FIE-ATED IING CALE Cable construction Magnesium oxide (MgO) insulation Solid copper conductors HDPE jacket (optional) Seamless copper sheath PODUCT

More information

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions Class I Indoor Termination Voltage Designation: 12/20(24) kv Kit Contents: 1 HeatShrinkBreakoutBootAssembly 3 HeatShrinkBindingSleeves

More information

ALLOY 825 SHEATHED, MINERAL INSULATED, FIRE-RATED WIRING CABLE

ALLOY 825 SHEATHED, MINERAL INSULATED, FIRE-RATED WIRING CABLE PYOTENAX SYSTEM 2000 ALLOY 825 SHEATHED, MINEAL INSULATED, FIE-ATED IING CALE Cable construction Seamless Alloy 825 metal sheath Magnesium oxide (MgO) insulation Solid nickel-clad copper conductors PODUCT

More information

MARCH COYOTE 9.5 x 19 (292 mm x 509 mm) Terminal Dome Closure Kits

MARCH COYOTE 9.5 x 19 (292 mm x 509 mm) Terminal Dome Closure Kits MARCH 2012 COYOTE 9.5 x 19 (292 mm x 509 mm) Terminal Dome Closure Be sure to read and completely understand this procedure before applying product. Be sure to select the proper PREFORMED product before

More information

Installation & Operation Instructions. Type USL Signal Light Kit for Self-Regulating Constant Wattage Heating Cables. Constant Wattage Grommet

Installation & Operation Instructions. Type USL Signal Light Kit for Self-Regulating Constant Wattage Heating Cables. Constant Wattage Grommet Chromalox Installation & Operation Instructions DIVISION 4 SALES REFERENCE DATE SERVICE REFERENCE SECTION RT (Supersedes PF477-1) PJ937 161-562581-032 DECEMBER, 2007 Type USL Kit for Self-Regulating Constant

More information

CS Fiber Optic Splice Case. Instruction

CS Fiber Optic Splice Case. Instruction 3 2179-CS Fiber Optic Splice Case Instruction 2179-CS Fiber Optic Splice Case Description 1.0 General 1.1 The 3M 2179-CS Fiber Optic Splice Cases are closures that can be used in buried, underground, aerial,

More information

Kompensator External Low Voltage Heating Cable System

Kompensator External Low Voltage Heating Cable System External Low Voltage Heating Cable System LOW VOLTAGE Installation Instructions General Information Kit Contents Qty Description 1 heating cable at pre-determined length Table of Contents General Information........................

More information