3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

Similar documents
3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

3M Cold Shrink QT-III Silicone Rubber Termination

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

QT-III Cold Shrink Silicone Rubber

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

Cold Shrink QS T Trifurcating Transition Splice Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

3M Mechanical Shearbolt Connectors, QCI Series

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

Cable Ties. Data Sheet

Branch Splice QS-2001B

SLiC Aerial Terminal and Spiral End Seal for use with AMP* Quiet Front Terminal Blocks

ELB ES. Product Installation Instructions

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

3M Cold Shrink Splice Kits, QS T Series

3M Locator Plate

ELB ELB

Installation Instructions

3M Ladder Kit 3M710/MS 2 -TMK-LK

3M Locator Plate

HVS S 15kV Class

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

3M Closure System 2-Type Cover (505)

3M Cross-Connect Cabinets 4220SVC and 4220SVE Tall Skirt Installation Guide

QTII (X) Series Silicone Rubber Cold Shrink Termination Kits

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

3 Reenterable Encapsulated PST Dome Closure

Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV

3M Products for Electrical Networks Wind Farm Capabilities. Leading Edge. Electrical Solutions for. Wind Farms

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900 µm Instructions

710 Splicing Rig. Instructions. January E

Data Sheet July For RoHS information, please visit

I nstallation I nstruction Heatshrink Term ination For 3 Core Polym eric Cables 7.2 kv to 3 6 kv

High Voltage Joints and Terminations up to 72,5 kv 145 kv

3M Fiber Dome Closure FDC 10

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900-µm. Instructions. October C

3M Pleated Foil I/O Cable Assemblies MDR Series

3M Electrical Markets Division. Rubber, Mastic and Specialty Tapes Application Guide. Choose the. Right Tape. for your. Electrical Project

3M Mini D Ribbon (MDR) Cable Assembly.050 High Speed Video Data Transmission System, 50 Position 14X50-SZWB-XXX-0NC

CS Fiber Optic Splice Case. Instruction

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

3M No Polish LC/APC Connector SM, Angle Splice, 250/900 µm 8830-APC/AS

C Power Connection Kit

Installation Instructions

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

(K),(M)430TB/G Up to 36 kv

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

(K),(M),(P)489TB/G Up to 42 kv

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

8400 Series Fiber Distribution System

3M Electrical Tapes Product Selection Guide. Insulate & Protect. with Quality Tapes. Preliminary

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

INSTALLATION INSTRUCTION PEM1367ENG ENGLISH

Door Edge Protection Film 36 inch

3M Cushion-Mount Plus Plate Mounting Tapes with Easy Mount Adhesive

3M No Polish LC Connector SM and MM, Flat Splice, 250/900 µm

Cold Shrink Silicone Rubber Termination Kit QT-III 7620-S, 7690-S and 7680-S Series kv

3M Cable Ties Product Guide. Made in USA. & Plenum Rated

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

WRSS Wraparound Repair Sleeve Installation Instructions

INSTALLATION INSTRUCTION

Installation Instruction EPP /92

INSTALLATION INSTRUCTION PEM1093ENG ENGLISH

POWERHEAT TYPE AHT TERMINATION INSTRUCTIONS. Ref TK/AHT Issue C Date 16 August 1999

INSTALLATION INSTRUCTION PEM1121ENG ENGLISH

Product Number

Effective November 2016 Supersedes February 2012 (S )

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

GM Specification Annual Test Data

Transcription:

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits With High-K Stress Relief For 3-Conductor Type G (Ground Wire), Copper Tape Shield, Armored Cables 7600-S-3G Series Instructions IEEE Std. No. 48 Class 1 Termination F CAUTION Working around energized electrical systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product. April 2013 3 78-8127-6978-0 Rev C

Kit Contents 1 Cold Shrink Silicone Rubber Breakout Boot Assembly 1 Cold Shrink Silicone Rubber Jacket Seal Assembly 3 Silicone Rubber Phase Re-jacketing Sleeve Assemblies 3 Cold Shrink Silicone Rubber Termination Assemblies 1 Tinned Copper Ground Braid Assembly 3 Constant Force Springs (Small) 1 Constant Force Spring (Large) 3 3M EMI Copper Foil Shielding Tape 1181 Strips, 1/2 x 10 8 Strips Scotch Mastic Strip 2230 ( 2 per termination bag & 2 per breakout boot bag ) 1 Roll, Scotch Super 33+ Vinyl Electrical Tape - 3/4" 1 Roll, Scotch Super Vinyl Electrical Tape 88-1-1/2" 1 Roll, Copper Scotch Electrical Shielding Tape 24 1 3M Cable Cleaning Preparation Kit CC-2 1 Instruction Sheet Note: Do Not use knives to open plastic bags. Termination Application Ranges * Final Determining Factor is Cable Insulation Diameter. Kit Number BIL (kv) 7620-S-2-3G 95 7621-S-2-3G 95 7622-S-2-3G 110 7691-S-4-3G 150 7692-S-4-3G 150 7693-S-4-3G 150 7695-S-4-3G 150 7684-S-8-3G 150 7685-S-8-3G 200 Insulation Range Min Max Inch (mm) 0.33-0.50 (8,4-12,7) 0.50-0.70 (12,7-17,8) 0.70-0.92 (17,8-23,4) 0.50-0.70 (12,7-17,8) 0.70-0.92 (17,8-23,4) 0.92-1.18 (23,4-30,0) 1.18-1.52 (30,0-38,6) 0.92-1.18 (23,4-30,0) 1.18-1.52 (30,0-38,6) 7686-S-8-3G 200 Kit Number BIL (kv) 7692-S-4-3G 150 7693-S-4-3G 150 7695-S-4-3G 150 7684-S-8-3G 200 7685-S-8-3G 200 7686-S-8-3G 200 Insulation Range Min Max inch (mm) 0.70-0.92 (17,8-23,4) 0.92-1.18 (23,4-30,0) 1.18-1.52 (30,0-38,6) 0.92-1.18 (23,4-30,0) 1.18-1.52 (30,0-38,6) 1.53-1.81 (38,8-46,0) Cable O.D. Max* Inch (mm) 2.20 (55,8) 2.80 (71,1) 3.30 (83,8) 2.80 (71,1) 3.30 (83,8) 3.90 (99.1) 4.50 (114,3) 3.90 (99.1) 4.50 (114,3) 5.40 (137,2) Cable O.D. Max inch (mm) 3.30 (83,8) 3.90 (99.1) 4.50 (114,3) 3.90 ((99.1) 4.50 (114,3) 5.40 (137,2) Conductor Size Range 5 kv 8 kv 15 kv 100% 133% 100% 133% 100% 133% 8-2 6-4 6-4 6-4 1-3/0 2-2/0 2-2/0 2-2/0 2-1 4/0-350 3/0-350 3/0-350 3/0-350 1/0-4/0 2-3/0 1-3/0 2-2/0 2-2/0 2-2/0 2-1 4/0-350 3/0-350 3/0-350 3/0-350 1/0-4/0 2-3/0 400-500 400-500 400-500 400-500 250-350 4/0-350 700-1000 700-1000 700-1000 700-1000 500-750 500-750 250-350 4/0-350 500-750 500-750 1000 Conductor Size Range 25/28 kv 35 kv 100% 133% 100% 133% 1-1/0 2/0-250 1-4/0 350-500 250-500 2/0-250 1-4/0 1/0-3/0 350-500 250-500 4/0-500 1/0-350 750 500-750 500-750 350-750 Table 1 2 78-8127-6978-0 Rev C

1.0 Prepare Cable 1.1 Determine cable jacket removal length required for correct phase spacing and bolted terminal lug connections ([A] + [B] Figure 1; based on the longest phase to be connected). Allow for dimension [C] as needed. NOTE: Individual phase length and separation dimensions vary according to specific installation and equipment design requirements. They must, therefore, be determined by the installer and must conform to accepted engineering practices. Max phase length = 4 ft (121,9 cm)+ termination length (from table in Figure 18, page 13) 1.2 Remove cable jacket, armor, bedding (inner sheath) and core fillers according to Figure 1 dimensions. Secure each copper tape shield end with a temporary band of vinyl tape (Figure 1). Note: DO NOT DISCARD LEFTOVER JACKET MATERIAL. [C] [B] Temporary Bands of Vinyl Tape Ground Wire Jacket Removal Length [A] + [B] [A] Copper Tape Shield Armor 2" (51 mm) Figure 1 78-8127-6978-0 Rev C 3

2.0 Install Shield Grounding Braid Assembly & Re-route Cable Ground Wire(s) 2.1 Position ground braid assembly over cable with assembly connector aligned to edge of armor (Figure 2). Note: For single ground wire cables, apply assembly to side opposite cable ground wire. Assembly connector should not overlap armor. Hint: Use temporary vinyl tape wraps as needed to assist in holding braid assembly to cable (Figure 2). 2.2 Attach Ground Braid Assembly Legs to Cable Phase Metallic Shields (a.) Short (Center) Braid Tail Position ground braid assembly as shown (Figure 2). Wrap short, center ground braid tail around metallic shield of first cable core. Trim excess braid length to prevent overlap (Figure 2). Secure ground braid to cable metallic shield using small constant-force spring (Figure 2). Spring and braid leg should be wrapped in the same direction. Cinch (twist with hand) constant-force springs to tighten. (b.) Install Second & Third Ground Braid Tails - Wrap the second and third ground braids around core legs to adjust length. Position ground braid tails so all constant force springs are equal distance from the cable armor. 2.3 Apply two highly-stretched half-lapped layers of electrical grade vinyl tape over constant force springs (Figure 2). Vinyl Tape ( typical ) 7.0" (178 mm) Trim Here Metallic Shield Cable Armor Connector Braid Assembly Leg Constant Force Spring Scotch Super 33+ Vinyl Electrical Tape Figure 2 4 78-8127-6978-0 Rev C

2.4 Measure distance [J] (Figure 3). Retrieve previously removed cable jacket material. Cut a straight piece to dimension [J] and wrap it around cable phases beneath ground strap assembly and cable ground wire. Secure jacket section in place using Scotch Vinyl Electrical Tape Super 88 (wide vinyl tape) (Figure 3). Note: Temporarily remove vinyl tape wrap on ground braid. [J] Scotch Vinyl Electrical Tape Super 88 (Wide Vinyl Tape) Side View Ground Wire Bottom View Figure 3 78-8127-6978-0 Rev C 5

2.5 Fill one armor valley section with tightly-wrapped layers of Scotch Electrical Shielding Tape 24 (Figure 4). 2.6 Secure ground braid assembly to cable armor using large constant force spring (Figure 4). Once spring has been applied, cinch (twist with hand) to tighten. 2.7 Apply one half-lapped layer of electrical grade vinyl tape over large constant force spring and cable armor (Figure 4). Note: Apply Scotch Super 33+ Vinyl Electrical Tape to hold down ground strap (Figure 4). Scotch Electrical Shielding Tape 24 Fill to Level of Armor High Points Large Constant Force Spring or Tie Wire for 7686 Scotch Super 33+ Vinyl Electrical Tape Figure 4 2.8 Bind cable ground wire with four half-lapped layers of Scotch Vinyl Electrical Tape Super 88 (wide vinyl tape) (Figure 5). Limit width of tape wrapping to approximately 2-1/2 (63,5 mm). 2-1/2" (63,5 mm) Scotch Vinyl Electrical Tape Super 88 (wide vinyl tape) Bottom View Figure 5 6 78-8127-6978-0 Rev C

2.9 Loop cable ground wire back over armor (Figure 6). Adjust ground wire position over cable jacket to run parallel with tail of ground braid assembly. Note: Do not make sharp or tight bends in ground wire. Ground wire loop should not extend beyond edge of protective jacket section as shown. Do not extend wire loop beyond this edge Rotated View of Cable Figure 6 2.10 Apply two half-lapped layers of Scotch Vinyl Electrical Tape Super 88 (wide vinyl tape) over looped ground wire area (Figure 7). Scotch Vinyl Electrical Tape Super 88 (Wide Vinyl Tape) Figure 7 2.11 Wrap two strips of Scotch Mastic Strip 2230 (one on top of the other) over cable jacket. Locate the mastic strip directly under the shield braid solder block and ground wire (Figure 8). Note: It will be necessary to temporarily remove vinyl tape over ground braid tail to complete this step. Two Strips of Scotch Mastic Strip 2230 Under Ground Wire & Shield Braid Tail Figure 8 78-8127-6978-0 Rev C 7

2.12 Separate ground wire strands over Strips of Scotch Mastic Strip 2230 as shown (Figure 9). Hint: Directly over the mastic seal strips, lift and bend the ground wire 90. Reverse twist the ground conductor to open strands. Use a screwdriver to aid in separating the strands. On 19 strand wire with reverse twist innerconductors, twist ground wire in the opposite direction to aid in separating the inner-conductors. Flatten, straighten and re-position the separated ground conductors. Be careful not to damage ground wire. Separated Ground Wire Strands Wide Vinyl Tape Two Strips of Scotch Mastic Strip 2230 Figure 9 2.13 Apply one strip of Scotch Mastic Strip 2230 around ground wire strands (Figure 10). Apply one mastic seal strip around solder block section of ground braid tail. Align mastic seal strip wraps with previously applied mastic seal strip band around cable jacket. Note: Avoid crossing individual wires at mastic seal location. Scotch Mastic Strip 2230 Over Solder Block Section Wi de V inyl Tape Scotch Mastic Strip 2230 Over Ground Wire Strands Figure 10 8 78-8127-6978-0 Rev C

2.14 Wrap two additional strips of Scotch Mastic Strip 2230 directly over previously applied mastic. (Figure 11). 2.15 Cover mastic seal area with two highly stretched half-lapped layers of Scotch Vinyl Electrical Tape Super 88 (wide vinyl tape). Two Strips of Scotch Mastic Strip 2230 (Final Layer) Scotch Vinyl Electrical Tape Super 88 (Wide Vinyl Tape) Figure 11 2.16 Install cold shrink jacket extension assembly. Align the jacket seal tube (not the plastic support core) to overlap ground wire seal area by approximately 1/4 (6 mm). To install, pull loose core end, while unwinding counterclockwise around the cable. (Figure 12). 2.17 Bind cable ground wire and ground braid tail to cable jacket using Scotch Vinyl Electrical Tape Super 88 (wide vinyl tape) (Figure 12). Apply at least eight tape layers and wrap only to width of tape roll. 1/4" (6 mm) Scotch Vinyl Electrical Tape Super 88 Binding Pull Tab Figure 12 78-8127-6978-0 Rev C 9

3.0 Install Silicone Rubber Breakout Boot Assembly 3.1 Inspect breakout boot assembly and confirm that all loose plastic core ends are free as shown (Figure 13). Loose Core Ends Neck Core Boot Neck Loose Core End Finger Neck Loose Core End Loose Core End Boot Finger Finger Core Figure 13 3.2 To ensure that the breakout boot can be fully seated into the breakout area of the cable, it will be necessary to unwind a few turns of each finger core. Caution: Do not unwind too far such that boot fingers begin to collapse. 3.3 Hold loose neck-end core ribbon to one side so that it can not become trapped between cable phases. Slide boot assembly over cable end; guiding individual cable cores through boot assembly fingers. Hint: View end of cable through finger cores to ease cable phase insertion. 3.4 Slide breakout boot assembly onto cable as far as it will go. Large neck-end should fully extend over previously-installed jacket sealing assembly tube. Hint: Spreading cable phases while sliding the boot assembly can ease the installation. 3.5 Remove large neck-end core. Grasping loose core ribbon end, pull and unwind counter-clockwise around cable. 3.6 Remove each finger core. Grasping loose core ribbon end, pull and unwind counter-clockwise around each cable phase leg. 4.0 Install Silicone Rubber Re-jacketing Sleeves 4.1 From the chart below, determine the correct [A] dimension (Figure 14) for the termination being installed. Kit Number Dimension [A] 7620-S-2-3G 6.75" (171 mm) 7621-S-2-3G 7" (178 mm) 7622-S-2-3G 7691-S-4-3G 7692-S-4-3G 9" (229 mm) 7693-S-4-3G 7695-S-4-3G 7684-S-8-3G 7685-S-8-3G 16.25" (413 mm) 7686-S-8-3G 10 78-8127-6978-0 Rev C

4.2 Place a vinyl tape marker on each cable phase leg at dimension [X] (Figure 14). Note: [X] = [A] + [B]. Allow for crimp growth when using aluminum lugs. 4.3 Determine required re-jacketing sleeve length for each phase leg (Distance [S], Figure 14). Be sure to include 1.0" (25 mm) breakout boot finger overlap in measurement. [S] 1.0" (25 mm) Overlap [A] [X] [B] Marker Tape Figure 14 4.4 Using scissors, trim re-jacketing sleeve assembly to length required (Figure 15). Cut tubing and inner braid together. Note: Inner polyester braid should extend approximately 3.0 (76 mm) beyond re-jacketing tube end before cutting. There is no need for termination-end braid exposure. Trim Line Breakout Boot End Re-jacketing Sleeve Termination End Expose Approximately 3.0 (76 mm) [S] Figure 15 4.5 Guide one re-jacketing sleeve assembly over each cable phase leg (Figure 16). Push sleeve assembly from above. Continuously guide the free end-maintaining sleeve-to-cable-core alignment. Right Wrong Figure 16 78-8127-6978-0 Rev C 11

4.6 Slide re-jacketing sleeve until inner polyester braid is adjacent to breakout boot finger (Figure 17). 4.7 Fold outer silicone tubing back on itself for 1.0" (25 mm) (Figure 17) and trim off exposed polyester braid. Note: Do not damage silicone tubing while cutting. Sleeve assembly may be rotated to ease trimming. When doing so, rotate in the direction of the cable copper tape shield wrap. 1.0" (25 mm) Polyester Braid Silicone Tube Fold-back Step 4.7 Step 4.6 Re-jacketing Sleeve over Marker Tape Figure 17 4.8 Slide re-jacketing sleeve assembly down until folded tube contacts edge of breakout boot finger (Figure 17). 4.9 Pull folded silicone tube section down onto breakout boot finger (Figure 17). Note: Re-jacketing tube end should align with upper edge of installed marker tape (Figure 17). Minor tube adjustments can be made as needed. 12 78-8127-6978-0 Rev C

5.0 Install 3M Cold Shrink QT-III Silicone Rubber Termination Assemblies 5.1 Prepare cable phase legs according to dimensions shown (Figure 18). Note: It is imperative to remove all remnants of the semi-con layer, even if the semi-con layer comes off as one layer. there should not be any remaining black areas, or particles, on the cable insulation layer. D C A B Re-jacketing Sleeve Kit Number Dimension A Dimension B Dimension C Dimension D 7620-S-2-3G 6.75" (171 mm) Lug Depth* 2.0" (51 mm) 1.25" (32 mm) 7621-S-2-3G 7622-S-2-3G 7.0" (178 mm) Lug Depth* 3.0" (76 mm) 1.25" (32 mm) 7691-S-4-3G 7692-S-4-3G 7693-S-4-3G 9.0" (229 mm) Lug Depth* 3.0" (76 mm) 1.25" (32 mm) 7695-S-4-3G 7684-S-8-3G 7685-S-8-3G 7686-S-8-3G 16.25" (413 mm) Lug Depth* 3.0" (76 mm) 1.25" (32 mm) *Allow for crimp growth when using aluminum lugs and connectors. Figure 18 Aluminum Lug and Connector Growth Allowance 2-350 1/4 (6 mm) 400-650 1/2" (13 mm) 750 1000 3/4" (19 mm) 1250 2000 Field Determined 5.2 Secure cable copper tape shield ends with 3M EMI Copper Foil Shielding Tape 1181 Strips (Figure 19). Re-jacketing Sleeve 3M EMI Copper Foil Shielding Tape 1181 Strips Figure 19 5.3 Secure re-jacketing sleeve with two half-lapped layers of electrical grade vinyl tape (Figure 20). Start taping 0.75" (19 mm) over re-jacketing sleeve, extend 0.25" (6 mm) over cable metallic shield and return to starting point. Note: Do not fully cover the Copper Tape Shield or 3M Copper Foil Shielding Tape 1181 Strips. BE SURE TO LEAVE PART OF THE COPPER TAPE SHIELD EXPOSED. 0.75" (19 mm) 0.25" (6 mm) Re-jacketing Sleeve Electrical Grade Vinyl Tape Figure 20 78-8127-6978-0 Rev C 13

5.4 Place a termination installation marker tape at position [M] (Figure 21). [M] Marker Tape Figure 21 Kit Number 7620-S-2-3G 7621-S-2-3G 7622-S-2-3G 7691-S-4-3G 7692-S-4-3G 7693-S-4-3G 7695-S-4-3G 7684-S-8-3G 7685-S-8-3G 7686-S-8-3G Dimension M 3.0" (76 mm) 5.0" (127 mm) 5.0" (127 mm) 5.0" (127 mm) 5.5 Install terminal lugs. Note: Special Case When lug spade dimension is larger than inside diameter of white plastic termination core, position termination assemblies over cable phase legs prior to installing lugs. Remove inner red shipping core from each termination assembly by pulling and unwinding the loose red core ribbon. Position one termination over each cable phase leg. Each termination assembly must be positioned with its loose white core ribbon end directed toward the open (cut) end of the cable. DO NOT REMOVE CORE AT THIS TIME. Continue with lug installations. (a.) For Aluminum Conductors - Thoroughly wire brush conductor strands to remove aluminum oxide layer. Immediately insert conductor into terminal lug barrel as far as it will go. (b.) Ensure that each lug face is parallel to equipment bushing or lug connection interface (Figure 22). Last Crimp First Crimp Figure 22 (c.) Crimp terminal lug according to manufacturer recommendations. Start at the upper end as shown (Figure 22). Remove all traces of oxide inhibitor that may have come out of lug barrel during crimping. (d.) If abrasive must be used: 1. Use on insulation only. DO NOT USE ABRASIVE ON SEMI-CON INSULATION SHIELD! 2. Use only aluminum oxide abrasive; grit 120 or finer. 3. Be careful not to reduce the cable insulation diameter below that allowed by the kit. 14 78-8127-6978-0 Rev C

(e.) Thoroughly clean primary insulation and lug barrel area using a solvent wipe from supplied 3M Cable Cleaning Preparation Kit CC-2. Note: DO NOT ALLOW SOLVENT TO TOUCH SEMI-CON INSULATION SHIELD. 5.6 Install 3M Cold Shrink QT-III Silicone Rubber Termination assemblies. (a.) Remove the inner red shipping core from the termination assembly by pulling and unwinding the loose red core end. (b.) Position the termination assembly with the loose white core ribbon directed toward the terminal lug. (c.) Align the base of the termination (not the plastic core) with the installation marker tape as shown (Figure 23). (d.) Grasp the loose white core ribbon. Pull and unwind counter-clockwise around cable end (Figure 23). Note: Once the termination body makes contact, there is no need to continue supporting the assembly. DO NOT PULL OR PUSH ON THE TERMINATION ASSEMBLY WHILE UNWINDING THE CORE. (e.) Remove the installation marker tape. Termination Base Aligned With Marker Tape Edge Marker Tape Figure 23 5.7 Connect shield braid tail and cable ground wire to system ground (earth) according to normal practice. 78-8127-6978-0 Rev C 15

3M, Scotch and Super 33+ are trademarks of 3M Company. Important Notice All statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use. Any statements related to the product which are not contained in 3M's current publications, or any contrary statements contained on your purchase order shall have no force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M. Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture at the time of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M's option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of the legal theory asserted. 3 Electrical Markets Division 6801 River Place Blvd. Austin, TX 78726-9000 800.245.3573 Fax 800.245.0329 www.3m.com/electrical Please Recycle. Printed in USA. 3M 2013. All Rights Reserved. 78-8127-6978-0 Rev C