I/P CONVERTER INSTRUCTION MANUAL (E)IM-TE100/00-R5

Similar documents
Type 500X. Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions. Ordering Information.

Installation, Operation and Maintenance Instructions Output Range Part Number Input psi bar Impedance Output Range

Electro-Pneumatic Linear Positioner Installation and Operation Instructions B GB

SP-20 Input. Installation and Operating Instructions Electro-Pneumatic Linear Positioner. Description of Device. Part Number System

The Series I/P Current to Pressure Transducer

OM Field-Type I/P Converter Model : KUX113 User's Manual

Type Installation, Operation and Maintenance Instructions. Ordering Information. Contents CA20 -

Installation and Operating Instructions Electro-Pneumatic Rotary Positioner SP-21. Description of Device. Part Number System

Moniteur INSTALLATION & OPERATING INSTRUCTIONS. SERIES 40 Positioners. Installation and Operating Instructions Series 40 Positioners.

ITVX Series. Stepless control of air pressure proportional to an electrical signal. Supply pressure: 5.0 MPa

Fisher 546 Electro Pneumatic Transducer

Electro-Pneumatic Positioner Series 830/831-WP/EX. Operation & Maintenance Manual

PMV P36C AND P41C POSITIONERS ACTUATORS

Type Type 1001 Transducers. I/P & E/P Transducers

Electro-Pneumatic Positioner YT-1000 / 1050 SERIES

Miniature I/P, E/P Transducer for Electronic Air Pressure Control

Type 500X. Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions. Ordering Information.

LIMIT SWITCH Hawkeye - HX Magnetic Solid State Proximity Sensors Installation, Maintenance and Operating Instructions (HX )

Vacuum pump system type

The T5220 Series Electro-Pneumatic Transducer converts a DC current or voltage input signal to a directly proportional pneumatic output.

m WARNING! READ m BEFORE INSTALLATION

WARNING! READ BEFORE INSTALLATION

FAIRCHILD T5200 SERIES ELECTRO-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

Miniature I/P, E/P Transducer for Electronic Air Pressure Control

SMART VALVE POSITIONER 4 to 20 ma + HART Digital Communication. smar B87

Electro-Pneumatic Positioner YT-1000 / 1050 SERIES

Table of Contents. Proportional & Precision Regulator Instrumentation

Type 2000 Transducer Product Instructions

Pneumatic Positioner RTX - Series USER S MANUAL. ROTEX P/P Ver. 0.1 Dated: MAY / 2009 REV 01: SEP/2010 Page 1 of 16

Fisher 3660 and 3661 Positioners

P200 P/I Transducer. Installation, Operation, and Maintenance Instructions INTRODUCTION

Digital display Pressure range ON/OFF output Linear output Model

T-1001 TYPE 1001 I/P & E/P TRANSDUCERS

FAIRCHILD T8001 SERIES STANDARD RANGE MINIATURE TWO-WIRE, P/I PRESSURE TRANSDUCER. Installation, Operation and Maintenance Instructions

Pneumatic Positioner PNY Series USER'S MANUAL. Max-Air Technology. Version 1.0

Series ITV0000. Compact Electro-Pneumatic Regulator ITV N Q. IITV00 02 n. How to Order. For single unit and single unit for manifold

User s Manual. Pneumatic Positioner. Series 58. J Flow. Series 58. J Flow

RTX1000 SERIES ELECTRO-PNEUMATIC POSITIONER

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

ER100 Series OUT. Specifications. Working fluid Working pressure range Control pressure range. Input voltage 2 wire Input impedance.

Series 60. New Smart Positioner. Compact design Convenient & powerful function Enhanced reliability

Precision Regulators.

TZIM. Electropneumatic Analog Positioner 10/ EN

Fisher 3660 and 3661 Positioners

Fisher i2p 100 Electro Pneumatic Transducer

Electro-Pneumatic Regulators. Electronic Vacuum Regulators

Compact Proportional Solenoid Valve

Kimray reserves the right to modify or improve the designs or specifications of such products at any time without prior notice Kimray Inc.

Fisher 3710 and 3720 Positioners and 3722 Electro-Pneumatic Converter

Electro-Pneumatic Regulators. Electronic Vacuum Regulators

Electro-Pneumatic Regulators. Electronic Vacuum Regulators

Type Type I/P & E/P Transducers

Control Valves Positioner

Control Valves Positioner

Features. Flexibility

Differential Pressure Transmitter

Related vacuum products

Valtek Beta Positioner. Valtek Beta Positioners. for Control Valves

Non-Contact Sensor for Workpiece Placement Verification

POWERS CONTROL RC 195 Multiple Input Receiver- Controller

Electro-Pneumatic Regulator Electronic Vacuum Regulator

Fisher 3610J and 3620J Positioners and 3622 Electro-Pneumatic Converter

Smart Valve Positioner 100 Series Model AVP100/102

TECHNICAL BULLETIN. Logix 510si Series Digital Positioner. Experience In Motion FCD LGENTB /09

Miniature I/P, E/P Transducer

XP100. Concentric Rotary Motion/Back lever type. SSS Co., Ltd.

User s Manual OM th edition

M-3025CB-AV Fuel Pump

AP ATEX AIRPOWER POSITIONERS AP2000 FEATURES AP1000 & AP1200 FEATURES OPTIONS OPTIONS

Operation Manual Electro-Pneumatic Positioner Model: NT-1000R (Rotary Type) NUTORK CORPORATION

2-Color Display Digital Pressure Switch. Rated Pressure Metal Body Type (ISE75H) 2-color digital. Functions

Positive displacement flowmeter for continuous flow measurement

System 6000 Electropneumatic Converter for Direct Current Signals Type 6116 i/p Converter

Fisher 3710 and 3720 Positioners and 3722 Electro Pneumatic Converter

2-Color Display High-Precision Digital Pressure Switch


EV2000 Series. Specifications. Descriptions Working fluid Max. working pressure Min. working pressure Withstanding pressure

Instruction. MI June E69F Current-to-Pneumatic Signal Converter

Installation Manual OPEN. For Corrosive Service. The ONYX integrates electronic sensors and pneumatic valving into a vapor tight enclosure.

Smart Valve explorer Smart Valve Positioner for Rotary Valve. Model SVX100 / SVX102

V200 Series Positioners

Numatics 2003 Rev. 11/03 PDFPRECISION-1

Features and Benefits

Mounting and Operating Instructions EB 3913 EN. Electropneumatic Converters i/p Converter Type

Series 10-ZSE40A(F)/10-ISE40A

Series ZSE30/ISE30. High Precision, 2-color Display Digital Pressure Switch. With One-touch fittings are newly introduced. PSE

Model 5000 Level Controller

POSITIONERS and Controls for Complete Valve Automation

Smart Valve Positioner 700 Series with HART Communication Protocol

ITVH Series. 3.0 MPa Maximum Supply Pressure High Pressure Electro-Pneumatic Regulator. 3.0 MPa 0.2 to 2.0 MPa. 3 W or less L /min (ANR)*

10 switches simultaneously. The settings of the master sensor (source of copy) can be copied to the slave sensors. Reducing setting labor

Valtek XL Series High Performance Positioner. for Control Valves

Pressure sensor for liquid and gaseous media QBE620-P...

MULTISTAGE MICRO EJECTORS CONTENTS ACCESSORIES GENERAL CATALOG AIR TREATMENT, AUXILIARY, VACUUM, AND FLUORORESIN PRODUCTS. Caution

Digital Flow Switch (Sensor Part) Operation Manual

Electro-Pneumatic Positioner RTX - Series USER S MANUAL. ROTEX E/P Ver. 0.1 Dated: dd / mm / yy Page 1 of 18

2-Color Display High-Precision Digital Pressure Switch Series ZSE40A(F)/ISE40A

2-Color Display Digital Pressure Switch. NPN/PNP open collector 2 outputs added. Cut-to-zero display function added. Rated Pressure Metal Body Type

MULTISTAGE MICRO EJECTORS

Type I/P & E/P Transducers

Transcription:

TE100 100,200 I/P CONVERTER INSTRUCTION MANUAL (E)IM-TE100/00-R5

Safety Precautions Always read these instructions before using the I/P converter.! WARNING:Indicates instructions that, if not followed correctly, may lead to death or serious injury.! Warnings Install the flame-proof version in compliance with the New Guidelines for Industrial Electrical Equipment Explosion-Proofing 1979 issued by the Industrial Safety Institute of the Ministry of Labor and in accordance with technical procedures that comply with international standards. The flame-proof version and Intrinsically Safe version and Nonincendive may not be installed or used for hazardous applications using gases other than those applicable to the explosion-proofing grade of the I/P converter. Perform adjustment (zero and span adjustment) of the flame-proof version in a non-hazardous environment or after making the environment non-hazardous. Always turn off the power before removing the terminal box cover or main cover. If intending to remove or disassemble the pressure gauge for maintenance or other purposes, always turn off the supply pressure and wait for the pressure in the pneumatic circuit to drop to zero before undoing any screws or other fittings used to attach parts. Always turn off the supply pressure before switching between auto and manual or replacing the pilot relay unit.! CAUTION:Indicates instructions that, if not followed correctly, may cause a fault or other physical damage.! Cautions Fit the I/P converter in the orientation shown in section 3.2 As drain fluid or dirt in the supply pressure line may block the fixed orifice or cause misoperation, fit a 5[micro]m or finer air filter (such as an SSS Mini-Set filter) and use a dryer or similar to ensure a clean air supply. Using a lubricator on the supply side may cause a blockage in the fixed orifice or nozzle. Never use a lubricator with this I/Pconverter. 0-0

- Table of Contents - 1.Usage 1-1 1-1 Check the I/P Converter Specifications 1-1 1-2 Transport 1-1 1-3 Storage Precautions 1-1 1-4 Install Location 1-1 2.Overview 2-1 2-1 Features 2-1 2-2 Principle of Operation 2-2 2-3 Specifications 2-3 2-4 Model Codes 2-3 2-5 Dimensions 2-4 2-6 Name of Parts 2-5 3.Design and Installation 3-1 3-1 Design 3-1 3-1-1 Flame-Proof Version 3-1 3-1-2 Intrinsically Safe Version 3-1 3-1-3 Nonincendive Version 3-1 3-2 Installation 3-2 3-2-1 Pipe Mounting 3-2 3-2-2 Wall Mounting 3-2 3-3 Pneumatic and Electrical Installation 3-2 3-3-1 Pneumatic Installation 3-2 3-3-2 Electrical Installation 3-3 (1)Flame-Proof Version 3-3,4 (2)Standard (Non-Explosion-proof)/Intrinsically Safe version 3-5 4.Operation 4-1 4-1 Auto/Manual Switchover Function(option) 4-1 4-2 Zero and Span Adjustment 4-2,3 4-3 Width of Range Adjustment 4-3 5.Maintenance 5-1 5-1 Maintenance of Flame -Proof Models 5-1 5-2 Periodic Inspection 5-1 5-3 Replacing the pilot Relay Unit 5-2 5-4 Replacement Parts 5-2 6.Troubleshooting 6-1 0-1

1 Usage 1-1 Check the I/P converter Specifications On receiving the I/P converter, check that the information on the nameplate on the front of the I/P converter matches what you ordered and confirm that the model code is correct. 1-2 Transport To prevent damage during transport, leave the I/P converter in its packing until ready to install and use. 1-3 Storage Precautions Store the I/P converter in a location that satisfies the following criteria. Not subject to rain or moisture Not subject to shock or other impact Normal room temperature and humidity 1-4 Install Location To maintain the working life and performance of the transducer, observe the following precautions when using the I/P converter. (1) Ambient temperature If using in a location subject to heat radiation or large variations in temperature, consider fitting thermal insulation. (2) Atmosphere Try to select a well-ventilated location and avoid corrosive atmospheres. 1-1

2 Overview The TE100 and TE200 I/P converters convert an electrical signal (4 to 20mA DC) output from a controller or similar to a pneumatic pressure. The I/P converters feature a compact design and high accuracy, making them suitable for adjuster valve and similar instrumentation applications. 2-1 Features 2-1 Features Ultra light-weight, compact design at 1.6kg (1.8 kg with reducing valve fitted), the I/P Converters are significantly lighter than previous models. This makes them easy to use. High accuracy The I/P Converters use a high-accuracy sensor and the latest technology to achieve a high level of conversion accuracy. Built-in reducing valve A model is available that incorporates a small dedicated reducing value (Mini-Set XR100). This eliminates the need for pneumatic supply piping. Optimum mounting Both pipe mounting and wall mounting are available by well designed bracket. These enable the I/P Converters to be used in locations where space is limited. 100 and 200 series models are available Both 100 series (with terminal box) and 200 series (no terminal box) models are available, allowing you to select a model that best suits 2-1

2-2 Principle of Operation <Transducer Operation Schematic> As shown in the above schematic, the operation of the I/P Converter is controlled by applying a 4 to 20mA DC signal to the input which causes the internal circuit to generate a voltage. A drive current is also supplied to the torque motor which represents the circuit load to operate the overall system. If the level of the input signal increases, the current to the torque motor [1] increases and the flapper [2] moves so as to cover the nozzle [3] and raise the pressure in the pilot relay (pneumatic valve) nozzle back-pressure chamber [4]. The increased nozzle back-pressure causes a displacement in the diaphragm assembly [5] in the pilot relay, opening the port s [6] inlet valve seat [7]. This increases the output air pressure from the pilot relay. The output air pressure is also applied to the solid state sensor [8] and converted into an electrical signal proportional to the pressure. This electrical signal is then returned to the control circuit where it is used as a feedback signal. The control circuit compares the sensor signal against the input signal to control the output air pressure to match the input signal. 2-2

2-3 Specifications Series Parameter TE100 (with terminal box) TE200 (no terminal box) Supply pressure 140kPa(1.4kgf/cm 2 ) Output pressure 20~100kPa(0.2~1kgf/cm 2 ) Input signal 4~20mADC Accuracy Accuracy ±5% Linearity ±0.2%, Hysteresis 0.2%, Repeatability 0.1% Output air approx. 40Nl/min Air consumption approx. 3Nl/min(4Nl/min approx. with Mini-set fitted) Standard version (non-explosion-proof) : -20~80 Ambient temperature S Flame-proof: Intrinsically safe (FM): -20~60 Intrinsically safe (FM):-20~60 Standard version (non-explosion-proof) : -40~60 L Intrinsically safe (FM):-40~60 Air connection Rc1/4(NPT1/4) Electrical G1/2(NPT1/2) Standard :dustproof and weather-proof (conforms to IP54, or JIS C0920-1993) Intrinsically safe (FM):Class Ⅰ,Ⅱ,Ⅲ,Division 1,Groups A-G Housing Non-incendive(FM):Class Ⅰ,Ⅱ,Ⅲ,Divitsion2 Groups A,B,C,D,F,G Temp.class:T4 NEMA 4X. Vmax=29V,Imax,96.1mA,Pmax=0.7W,Ci=0μF,Li=50μH Flame-proof:ExdⅡBT6(TC13351) Weight approx. 1.6kg(1.8kg with a Mini-set approx. 1.3kg(1.5kg with a Mini-set integrated) Material (Primary) Aluminum Diecastings(Special Anodize) 2-4 Model Codes 1 2 3 4 5 6 7 8 9 10 TE - / 〇 〇 〇 〇 TE:I/P Converters models 2 3 4 5 6 Series Housing Pneumatic and Electrical Connections 1 100Series 0 Standard 1 Rc1/4 G1/2 2 200series 2 Intrinsically safe 3 NPT1/4 G1/2 5 Flame- proof 5 NPT1/4 NPT1/2 S L Ambient Temperature AM Function Standard version (non-explosion-proof) -20~80 A NO Flame proof & Intrinsically safe ( FM) -20~60 M YES Standard (non-explosion-proof) -40~60 Intrinsically safe ( FM) -40~60 7 8 9 10 Pressure Units Pressure Gauge Input Signal Mini set Pneumatic Coupling K2 200kPa G0 NONE M1 4~20mA R1 Rc1/4 M2 0.2MPa G1 OUT-side only M2 4~12mA N1 NPT1/4 P2 30psi SUP-side M3 12~20mA G2 B2 2bar OUT-side M4 Special Note :Contact SSS for details of items indicated by. 2-3

2-5 Dimensions <TE100> <TE200> For Output <Bracket> 2-4

2-6 Name of Each Part <TE100> <TE200> 2-5

3 Design and Installation 3-1 Design 3-1-1 Flame proof Do not use the I/P Converter in hazardous environments containing gases other than those applicable to the explosion-proofing grade of the transducer. Use the I/P Converter with the ambient temperature in the range -20 to 60[deg]C. 3-1-2 Intrinsically Safe version(installation Diagram) Intrinsically safe Hazardous( classified ) Location Class Ⅰ,Ⅱ,Ⅲ Division 1 Groups A,B,C,D,E,F,G (Note 2) TE100 or TE200 + - Non hazardous Location Associated Apparatus ( Note 5) ( Note 6) Control Equipment (Note 3) Entity Parameters: Vmax =29V Imax=96.1mA Pmax=0.7W Ci=0μF Li=50μH Note : 1. 7.53V<Voc<Vmax, Isc or It<Imax, Ca>Ci+Ccable, La>Li+Lcable 2. Dust-tight conduit seal must be used when installed in ClassⅡand ClassⅢ environments. 3. Control equipment connected to the Associated Apparatus must not use or generate more than 250 Vrms or Vdc. 4. Installation should be in accordance with ANSI/ISA RP12.6 Installation of Intrinsically Safe Systems for Hazardous(Classified) Locations" and the National Electrical Code. 5. The configuration of associated apparatus must be FMRC Approved under Entity Concept. 6. Associated apparatus manufacturer s installation drawing must be followed when installing this equipment. 7. No revision to drawing without prior FMRC approval. 3-1-3 Nonincendive version(installation Diagram) Nonincendive Hazardous( classified ) Location Class Ⅰ,Ⅱ,Ⅲ Division 2 Groups A,B,C,D,F,G (Note 2) Unclassified Location TE100 or TE200 + - Control Equipment (Note 2 ) Nonincendive Field Wiring Parameters: Vmax =29V Pmax=0.7W Ci=0μF Li=50μH Functional Rtaings These ratings do not supersede hazardous location values. Normal current =4-20 ma Note : 1. Vmax>=Voc or Vt>=7.53V, Ca>=Ci+Ccable, La>=Li+Lcable 2. Control equipment connected to the TE model series must not use more than 250 Vrms or Vdc. 3. Installation shall be in accordance with the National Electrical Code ANSI/NFPA 70. 4. Dust-tight conduit seal must be used when installed in ClassⅡand ClassⅢ environments. 5. No revision to drawings without prior FM Approvals authorisation. 6. The nonincendive field wiring circuit allows interconnection of nonincendive field wiring apparatus with associated nonincendive field wiring apparatus using any of the wiring methods permitted for unclassified locations. 7. For this current controlled circuit, the parameter(imax)is not required and need not be aligned with parameter (Isc of It)of the barrier or associated nonincendive field wiring apparatus. 3-1

3-2 Installation 3-2-1 Pipe Mounting 3-2-2 Wall-Mounting 3-3 Pneumatic and Electrical Installation 3-3-1 Pneumatic Installation The I/P Converter requires a clean and dry air supply. Provide a system able to deliver such an air supply. 1The I/P Converter can be ordered with either Rc1/4 or NPT1/4 couplings. Ensure you use the correct couplings to match those on I/P Converter. 2Connect the piping using the appropriate procedure depending upon whether a reducing valve (Mini-Set XR100) is fitted or not. If a reducing valve is not fitted, connect to the SUPPLY inlet on the I/P Converter. If a reducing valve (Mini-Set XR100) is fitted, connect to the P1 coupling on the Mini-Set unit. 3Ensure you fully purge the piping before connection to prevent any particles of dirt or foreign material from entering the system. 4Adjust the supply pressure to deliver a 140kPa (1.4kgf/cm[2]) air supply. If using a Mini-Set, turn the adjustment knob on the Mini-Set to set the pressure to 140kPa (1.4kgf/cm[2]). 3-2

3-3-2 Electrical Installation (1) Flame-proof version When performing electrical installation, never remove the terminal box cover or attempt to connect the wiring while the electrical power is still connected. (Similarly, do not open the main cover.) 1 Cabling Use insulated cables able to withstand temperatures of 75[deg]C or higher for the external cabling. 2 External conductor cabling The following two methods can be used for conductor cabling on the Flame-proof version (Exd II BT6). Cable pipe with threaded pressure coupling method Use a G1/2 thick steel cable pipe (PF1/2 equivalent) with a lock nut to provide a full threaded coupling. Alternatively, use a sealing fitting. Pressure-proof packing method Use a cable gland. (The table below lists the applicable cable diameters.) (Cable glands with the part numbers listed below are available as optional extras. Please specify when ordering.) Model Standard Rating Number TE15 ExdⅡBT6 TC13351 Applicable Cable Diameters φ8~φ10 φ9~φ11 φ10~φ12 Cable Gland Part No. KHB-0-16/PK1610 KHB-0-16/PK1611 KHB-0-16/PK1612 3-3

3 Connecting the cables To connect the cables, remove the terminal box cover and use the insulated crimping terminals on the terminal block. Connect by crimping the + input terminal to the + terminal (red) and the - input terminal to the - terminal (blue). (See Figure 3-1) * To remove the cover, undo the locking screws (hex set screws) Figure 3-1 4 Locking After partially attaching the terminal box cover, lock the cover in place using the locking screw. 5 Other details All other aspects of the installation should be carried out in compliance with the New Guidelines for Industrial Electrical Equipment Explosion-Proofing 1979 issued by the Industrial Safety Institute of the Ministry of Labor and in accordance with technical procedures that comply with international standards. 3-4

(2) Standard (non-explosion-proof) / Intrinsically Safe version 1 Cabling If the ambient temperature is 60[deg]C or less, use 600V vinyl or better stranded cable. (If the temperature is above 60[deg]C, select cable with an appropriate tolerance for the conditions.) 2 Connecting the cables TE100 (with terminal box) To connect the cables, remove the terminal box cover and use the insulated crimping terminals on the terminal block. Connect by crimping the + input terminal to the + terminal (red) and the - input terminal to the - terminal (blue). (See Figure 3-1) TE200 (no terminal box) Remove the main cover and connect to the terminal block on the circuit board as described above. The terminal polarities are indicated on the protective plate. (See Figure 3-2) Figure 3-2 4 Operation 3-5

4-1 Auto/Manual Switchover Function (Option) The I/P Converter is shipped set to automatic operation. To operate the transducer manually, use the following procedure to switch to manual operation. (See Figure 4-1) (The auto/manual switch is located on the left side of the I/P Converter unit.) Auto/Manual Switch Figure 4-1 <Changing to MANUAL> [1] Undo the screw and slide the protective plate so that the M becomes visible. Partially retighten the screw in this position. [2] Next, use a screwdriver to rotate the AM switch shaft as far as it will go in the direction of the arrow on the plate (MANU direction). [3] Adjust the reducing valve used to control the air supply to set the I/P Converter output pressure. The output pressure is indicated on the output pressure gauge. <Restoring to AUTO> [1] To set back to AUTO, rotate the AM switch shaft as far as it will go in the AUTO direction. [2] Slide the protective plate so that the A becomes visible again, then fasten in place. 4-2 Zero and Span Adjustment (1) Set the AM switch function to AUTO and set the supply pressure to 140kPa 4-1

(1.4kgf/cm[2]). (2) Remove the main cover. On the Flame-proof version, the main cover cannot be removed while the power is on. Move to a non-hazardous location before removing the main cover. (3) Zero and span adjustment (a) Apply a 0% (4mA) input signal Rotate the zero trimmer to set the 0% output (20kPa, 0.2kgf/cm[2]). Rotating clockwise increases the output and rotating counter-clockwise reduces the output. (See Figure 4-2) (b)next, apply a 100% (20mA) input signal Rotate the span adjustment trimmer to set the 100% output (100kPa, 1.0kgf/cm[2]). Rotating clockwise increases the span and rotating counter-clockwise reduces the span. (See Figure 4-2) (c)repeat the above adjustments two or three times to set the zero and span settings. (d) After you have finished setting the zero and span adjustment, apply a step input (25%, for example) and check that the output is correct. <Figure 4-2> 4-2 (4)1/2 split-range version The I/O specifications for the 1/2 split range version are listed below. Adjust the zero and span settings using the same procedure as for the standard range

version. Range 0% 100% 4~12mA 4mA 12mA 12~20mA 12mA 20mA 4-3 Width of Range Adjustment The table below shows the width of the zero and span adjustment bands. You can set the range to be different to the standard 0 to 100% output provided you stay within these limits. Zero adjustment width Span adjustment width -10%~+10% +75%~+125% 5 Maintenance 4-3 5-1 Maintenance of Flame-Proof version.

1.When performing maintenance on Flame-proof version, never remove the terminal box cover or main cover while the power is connected. 2. Always turn off the power before performing any maintenance or repair work. 5-2 Periodic Inspection Performing periodic inspection and maintenance of the I/P Converter will help reduce the incidence of faults and extend the working life of the unit. <Supply pressure filter> A metal mesh is fitted inside the SUPPLY coupling. Use a pair of tweezers or similar to remove any sealing tape or dirt particles caught in the mesh. <Fixed orifice assembly> The fixed orifice plays an important role in supplying the air to the nozzle. If no nozzle back pressure is present, this may indicate a blocked orifice. Take off the exhaust cover, then remove the fixed orifice assembly from the pilot relay unit and replace with a spare assembly. (See Figure 5-1) If you do not have a spare fixed orifice assembly, use [phi]0.3 piano wire or similar to clean the blocked orifice. Then use clean air to blow off any remaining dirt. When finished cleaning, screw the assembly back into its original position. Take care to ensure that the O-ring is positioned correctly in the body of the pilot relay unit. 5-3 Replacing the Pilot Relay 図 5-1 5-1 To remove the pilot relay unit, remove the exhaust cover from the bottom of the I/P Converter and undo the two screws. (See Figure 5-2)

figure 5-2 * When replacing the pilot relay unit, insert the new relay unit. 5-4 Replacement Parts Circuit board Pilot relay unit Name Part No. Quantity TE100: TE100-500-11A TE200: TE100-500-11B 1 TE100-200 1 Filter for reducing valve XR100-109 1 5-2 6 Troubleshooting Refer to the table below in the event of problems with the I/P Converter. If the action described below does not restore the transducer to normal operation, replace the I/P Converter with a spare and contact SSS Co. Ltd.

Symptom Cause Action I/P Converter does not operate when an input signal is applied. Output is unstable. Large output error Fixed orifice is blocked. I/P Converter is set to manual operation. Polarity of input signal wiring is reversed. No air supply Pilot relay is faulty. Large fluctuation in air supply pressure The pressure leakage (volume) on the output circuit side is fluctuating. Pilot relay is faulty. Zero and span settings are out of adjustment. Large fluctuation in ambient temperature Clean or replace fixed orifice. Change to Auto (A) operation. Check wiring and connections. Supply 140kPa (1.4kgf/cm[2]) Inspect and/or replace pilot relay. Ensure air supply pressure is constant. Check for pressure leaks. Inspect and/or replace pilot relay. Re-adjust zero and span settings. Fit thermal insulation or similar. Pressure leak in output circuit Fix pressure leak. 6-1