3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

Similar documents
3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

QT-III Cold Shrink Silicone Rubber

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

3M Cold Shrink QT-III Silicone Rubber Termination

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

Cold Shrink QS T Trifurcating Transition Splice Kit

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

3M Mechanical Shearbolt Connectors, QCI Series

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

3M Locator Plate

Branch Splice QS-2001B

QTII (X) Series Silicone Rubber Cold Shrink Termination Kits

Cable Ties. Data Sheet

3M Locator Plate

3M Cold Shrink Splice Kits, QS T Series

SLiC Aerial Terminal and Spiral End Seal for use with AMP* Quiet Front Terminal Blocks

ELB ELB

3M Cross-Connect Cabinets 4220SVC and 4220SVE Tall Skirt Installation Guide

3M Ladder Kit 3M710/MS 2 -TMK-LK

ELB ES. Product Installation Instructions

3M Products for Electrical Networks Wind Farm Capabilities. Leading Edge. Electrical Solutions for. Wind Farms

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

3M Pleated Foil I/O Cable Assemblies MDR Series

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

Installation Instructions

3M Mini D Ribbon (MDR) Cable Assembly.050 High Speed Video Data Transmission System, 50 Position 14X50-SZWB-XXX-0NC

Data Sheet July For RoHS information, please visit

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)

3M Closure System 2-Type Cover (505)

3 Reenterable Encapsulated PST Dome Closure

710 Splicing Rig. Instructions. January E

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900 µm Instructions

Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

C Power Connection Kit

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900-µm. Instructions. October C

3M Fiber Dome Closure FDC 10

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

(K),(M)430TB/G Up to 36 kv

Cold Shrink Silicone Rubber Termination Kit QT-III 7620-S, 7690-S and 7680-S Series kv

I nstallation I nstruction Heatshrink Term ination For 3 Core Polym eric Cables 7.2 kv to 3 6 kv

3M No Polish LC/APC Connector SM, Angle Splice, 250/900 µm 8830-APC/AS

(K),(M),(P)489TB/G Up to 42 kv

3M Electrical Tapes Product Selection Guide. Insulate & Protect. with Quality Tapes. Preliminary

3M Electrical Markets Division. Rubber, Mastic and Specialty Tapes Application Guide. Choose the. Right Tape. for your. Electrical Project

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

High Voltage Joints and Terminations up to 72,5 kv 145 kv

3M Cable Ties Product Guide. Made in USA. & Plenum Rated

Door Edge Protection Film 36 inch

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

GM Specification Annual Test Data

3M No Polish LC Connector SM and MM, Flat Splice, 250/900 µm

K SERIES PUSH ON & BULLET TERMINALS

Installation Instructions

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

GM Specification Annual Test Data

3M Cushion-Mount Plus Plate Mounting Tapes with Easy Mount Adhesive

POWERHEAT TYPE AHT TERMINATION INSTRUCTIONS. Ref TK/AHT Issue C Date 16 August 1999

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

CS Fiber Optic Splice Case. Instruction

INSTALLATION INSTRUCTION

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

3M Textool Test and Burn-In Sockets for 1.0 mm Area Array Packages Including Ball Grid Array and Land Grid Array

3M Connector System 0.050" x 0.100" Pitch. 3M Tripolarized Wiremount Socket - Series 820 3M 4-Wall, Tripolarized Header - Series 810

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

SLiC Aerial Closures

HVS S 15kV Class

Installation Instruction EPP /92

3M CP2 Press-Fit Headers and Sockets, 2 mm

3 740 Wrist strap + shoe tester

Kompensator External Low Voltage Heating Cable System

Repair Method for 3M Resilient Floor Protection System


Transcription:

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series For 3-Conductor Copper Tape Shield Cables without Ground Wires Instructions IEEE Std. No. 48 Class 1 Termination CAUTION Working around energized electrical systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product. September 2008 78-8127-6974-9

Kit Contents 1 Cold Shrink Silicone Rubber Breakout Boot Assembly 3 Silicone Rubber Phase Re-jacketing Sleeve Assembly 3 Cold Shrink Silicone Rubber Termination Assembly 1 Roll Tinned Copper Ground Braid 3 Constant-Force Spring (Small) 1 Constant-Force Spring (Large) 3 Copper Foil Tape, 1/2" x 10" 2 Mastic Seal Strips 1 Roll Vinyl Tape 1 Cable Preparation Kit 1 Installation Instructions Termination Application Ranges (Final determining factor is cable insulation diameter. Listed insulation ranges allow +2.54 mm (0.10") for shielding.) Kit Number BIL (kv) Cable Insulation Range [inch (mm)] 3.3 kv IEC 3.3 kv JIS 5.0 kv (AWG) AEIC 6.6 kv JIS 6.6 kv IEC 8.7 kv (AWG) AEIC 7620-S2-3W 95 8.40 12.7 (0.33 0.50) 16 35 8 22 8 2 16 25 6 4 7621-S2-3W 95 12.7 17.8 (0.50 0.70) 50 95 38 60 1 3/0 35 70 2 2/0 10 50 10 kv IEC 7622-S2-3W 110 17.8 23.4 (0.70 0.92) 120 185 100 150 4/0 400 60 100 95 150 3/0 350 70 150 7691-S4-3W 150 12.7 17.8 (0.50 0.70) 50 95 38 60 1 3/0 35 70 2 2/0 10 50 7692-S4-3W 150 17.8 23.4 (0.70 0.92) 120 185 100 150 4/0 400 60 100 95 150 3/0 350 70 150 7693-S4-3W 150 23.4 30.0 (0.92 1.18) 240 300 200 250 500 750 150 250 185 300 400 600 185 300 7695-S4-3W 150 30.0 38.6 (1.18 1.52) 300 325 800 1000 300 325 750 1000 7685-S8-3W 200 30.0 38.6 (1.18 1.52) 300 325 800 1000 300 325 750 1000 Kit Number BIL (kv) Cable Insulation Range [inch (mm)] 15 kv IEC 15 kv (AWG) AEIC 20 kv IEC 25/28 kv (AWG) AEIC 30 kv IEC 7620-S2-3W 95 8.40 12.7 (0.33 0.50) 7621-S2-3W 95 12.7 17.8 (0.50 0.70) 16 25 7622-S2-3W 110 17.8 23.4 (0.70 0.92) 35 95 1/0 4/0 7691-S4-3W 150 12.7 17.8 (0.50 0.70) 16 25 7692-S4-3W 150 17.8 23.4 (0.70 0.92) 35 95 1/0 4/0 25 70 2 1/0 7693-S4-3W 150 23.4 30.0 (0.92 1.18) 120 185 250 450 95 185 2/0 250 7695-S4-3W 150 30.0 38.6 (1.18 1.52) 200 325 500 750 240 300 300 500 35 kv (AWG) AEIC 7685-S8-3W 200 30.0 38.6 (1.18 1.52) 200 325 500 750 240 300 300 500 95 240 4/0 500 Table 1 2 78-8127-6974-9

1.0 Prepare Cable 1.1 Determine cable jacket removal length required for correct phase spacing and bolted terminal lug connections ([A] + [B] Figure 1, based on the longest phase to be connected). Allow for dimension [C] as needed. Note: Individual phase length and separation dimensions vary according to specific installation and equipment design requirements. They must, therefore, be determined by the installer and must conform to accepted engineering practices. 1.2 Remove cable jacket, armor, bedding (inner sheath) and core fillers according to Figure 1 dimensions. Secure each copper tape shield end with a temporary band of vinyl tape (1 Figure 1). 1.3 Using light tension, wrap a mastic seal strip around cable jacket 25 mm (1.0") below the cut edge ( 2 Figure 1). Figure 1 78-8127-6974-9 3

2.0 Attach Metallic Shield Grounding Braids 2.1 Cut supplied tinned copper grounding braid into three equal 2' (610 mm) lengths. Expand each braid end for a distance of 12" (300 mm) (2 Figure 2). 12" (300 mm) Figure 2 2.2 Position each expanded ground braid end over cable as shown in Figure 3. Using vinyl tape bands, secure upper braid end to copper tape shielding 200 mm (8.0") beyond armor edge (jacket edge for non-armored cable) (➃ Figure 3). Secure to cable jacket 15 mm (0.60") below mastic seal strip (➄ Figure 3). Figure 3 4 78-8127-6974-9

2.3 Connect ground braid upper ends to copper tape shield using small constant force spring ( ➅ Figure 3). Armored cables: Connect three ground braids to cable armoring using one large constant force spring (➆ Figure 3). Following application, cinch (twist with hand) each spring to tighten. 2.4 Apply a second mastic seal strip over ground braids and previously-applied mastic strip ( 8 Figure 3). 2.5 Apply two highly stretched half-lapped layers vinyl tape over mastic seal strips and constant force springs (9 Figure 3). 3.0 Install Cold Shrink Silicone Rubber Breakout Boot Assembly 3.1 Inspect boot assembly and confirm that all loose plastic core ends are free as shown ( 1 and 2 Figure 4). Figure 4 3.2 To ensure that the breakout boot can be fully seated into the breakout area of the cable, it will be necessary to unwind a few turns of each finger core. Caution: Do not unwind too far such that boot fingers begin to collapse. 3.3 Hold loose neck-end core ribbon 2 to one side so that it can not become trapped between cable phases. Slide boot assembly over cable end, guiding individual cable cores through boot assembly fingers. Hint: View end of cable through finger cores to ease cable phase insertion. 3.4 Slide breakout boot assembly onto cable as far as it will go. Large neck-end should fully extend over cable jacket. Hint: Spread cable phases while sliding boot assembly to ease the installation. 3.5 Remove large neck-end core. Grasping loose core ribbon end 2, pull and unwind counter clock-wise around cable. Remove each finger core. Grasping loose core ribbon end 3.6 1, pull and unwind counter clock-wise around each cable phase leg. 78-8127-6974-9 5

4.0 Install Silicone Rubber Re-jacketing Sleeves 4.1 From the chart below, determine the correct A dimension for the termination product being installed. Kit Number 7620-S2-3W 7621-S2-3W 7622-S2-3W 7691-S4-3W 7692-S4-3W 7693-S4-3W 7695-S4-3W 7684-S8-3W 7685-S8-3W 7686-S8-3W Dimension A 6 3/4" (171 mm) 7" (178 mm) 9" (229 mm) 16 1/4" (413 mm) 4.2 Place a vinyl tape marker on each cable phase leg at dimension X ( 1 Figure 5). Note: X = A (From chart above) + B (Lug barrel depth). Allow for crimp growth when using aluminum lugs. Figure 5 4.3 Determine required phase re-jacketing sleeve length (S - 1" (25 mm) Figure 5). 4.4 Using scissors, trim re-jacketing sleeve assembly to length required ( Figure 6). Cut tubing and inner braid together. Note: Inner polyester braid should extend approximately 3" (75 mm) beyond re-jacketing tube end before cutting. There is no need for termination-end braid exposure. Figure 6 6 78-8127-6974-9

4.5 Guide one re-jacketing sleeve assembly over each cable phase leg ( Figure 7). Push sleeve assembly from above. Continuously guide the free end maintaining sleeve-to-cable-core alignment. Figure 7 4.6 Slide re-jacketing sleeve until inner polyester braid is adjacent to breakout boot finger ( 2 Figure 8). 4.7 Fold outer silicone tubing back on itself for 1" (25 mm) and trim off exposed polyester braid ( 3 Figure 8). Note: Do not damage silicone tubing while cutting. Sleeve assembly may be rotated to ease trimming. When doing so, rotate in the direction of the cable copper tape shield wrap. Figure 8 4.8 Slide re-jacketing sleeve assembly down until folded tube contacts edge of breakout boot finger ( ➃ Figure 8). 4.9 Pull folded silicone tube section down onto breakout boot finger ( ➄ Figure 8). Note: Re-jacketing tube end should align with upper edge of installed marker tape (➅ Figure 8). Minor tube adjustments can be made as needed. 78-8127-6974-9 7

5.0 Install 3M Cold Shrink Termination QT-III Assemblies 5.1 Prepare cable phase legs according to dimensions shown ( Figure 9). Figure 9 Kit Number Dimension A Dimension B Dimension C Dimension D 7620-S2-3RJS 6.7" (170 mm) Lug Depth* 2.0" (51 mm) 1.2" (30 mm) 7621-S2-3RJS 7622-S2-3RJS 7.1" (180 mm) Lug Depth* 3.0" (76 mm) 1.2" (30 mm) 7691-S4-3RJS 7692-S4-3RJS 7693-S4-3RJS 9.1" (231 mm) Lug Depth* 3.0" (76 mm) 1.2" (30 mm) 7695-S4-3RJS 7684-S8-3RJS 7685-S8-3RJS 7686-S8-3RJS 16.3" (414 mm) Lug Depth* 3.0" (76 mm) 1.2" (30 mm) *Allow for crimp growth when using aluminum lugs and connectors. 5.2 Secure cable copper tape shield ends with copper foil tape ( Figure 10). Copper Foil Tape Figure 10 5.3 Secure re-jacketing sleeve with two half-lapped layers of vinyl tape ( Figure 11). Start taping 0.8" (20 mm) over re-jacketing sleeve, extend 0.2" (5 mm) over cable metallic shield and return to starting point. Note: Do not cover copper foil tape. Figure 11 8 78-8127-6974-9

5.4 Place a termination installation marker tape at position [M] ( Figure 12). [M] Marker Tape Figure 12 Kit Number 7620-S2-3G 7621-S2-3G 7622-S2-3G 7691-S4-3G 7692-S4-3G 7693-S4-3G 7695-S4-3G 7684-S8-3G 7685-S8-3G 7686-S8-3G Dimension M 3.0" (76 mm) 4.9" (125 mm) 4.9" (125 mm) 4.9" (125 mm) 5.5 Install terminal lugs. Note: Special Case When lug spade dimension is larger than inside diameter of white plastic termination core, position termination assemblies over cable phase legs prior to installing lugs. Remove inner red shipping core from each termination assembly by pulling and unwinding the loose red core ribbon. Position one termination over each cable phase leg. Each termination assembly must be positioned with its loose white core ribbon end directed toward the open (cut) end of the cable. Continue with lug installations. (a.) For Aluminum Conductors - Thoroughly wire brush conductor strands to remove aluminum oxide layer. Immediately insert conductor into terminal lug barrel as far as it will go. (b.) Ensure that each lug face is parallel to equipment bushing or lug connection interface (Figure 13). Last Crimp First Crimp Figure 13 (c.) Crimp terminal lug according to manufacturer recommendations. Start at the upper end as shown (Figure 13). Remove all traces of oxide inhibitor that may have come out of lug barrel during crimping. 78-8127-6974-9 9

(d.) Thoroughly clean primary insulation and lug barrel area using solvent wipe from supplied cable preparation kit. Note: Avoid solvent contact with cable semi-conductive screen. 5.6 Install 3M Cold Shrink Termination QT-III assemblies. (a.) Remove the inner red shipping core from the termination assembly by pulling and unwinding the loose red core end. (b.) Position the termination assembly with the loose white core ribbon directed toward the terminal lug. (c.) Align the base of the termination (not the plastic core) with the installation marker tape as shown (Figure 14). (d.) Grasp the loose white core ribbon. Pull and unwind counter clock-wise around cable end (Figure 14). Note: After the silicone rubber termination makes adequate contact (approximately 1.0 ), release the assembly and continue unwinding the core. Do not pull or push on the assembly while unwinding. (e.) Remove the installation marker tape. Figure 14 5.7 Connect shield braid tails and cable ground wire to system ground (earth) according to normal practice. 10 78-8127-6974-9

78-8127-6974-9 11

3M is a trademark of 3M Company. Important Notice All statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use. Any statements related to the product which are not contained in 3M's current publications, or any contrary statements contained on your purchase order shall have no force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M. Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture at the time of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M's option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of the legal theory asserted. 3 Electrical Markets Division 6801 River Place Blvd. Austin, TX 78726-9000 800-245-3573 Fax 800-245-0329 www.3m.com/electrical Please Recycle. Printed in USA. 3M 2008. All Rights Reserved. 78-8127-6974-9