TWO STAGE PROGRESSIVE AND MODULATING GAS BURNERS RIELLO 40 GS/M SERIES GS 10/M 22/ kw GS 20/M 43/ kw

Similar documents
ONE STAGE GAS BURNERS RDBS SERIES

TWO STAGE GAS BURNER GULLIVER RSD SERIES RS5D 160/ kw

ONE STAGE GAS BURNER GULLIVER RSF SERIES RS5F kw

LOW NOx TWO STAGE GAS BURNERS GULLIVER BSD SERIES BS1D 16/19 52 kw BS2D 35/40 91 kw BS3D 65/ kw BS4D 110/ kw

ONE STAGE GAS BURNERS RS/1 SERIES RS 28/ kw RS 34/1 MZ kw RS 38/ kw RS 44/1 MZ kw

TWO STAGE GAS BURNERS

GULLIVER BSD SERIES. Low NOx Two Stage Gas Burners FIRING RATES. BS1D 16/19 52 kw BS2D 35/40 91 kw BS3D 65/ kw BS4D 110/ kw.

GULLIVER BS SERIES. Low NOx One Stage Gas Burners FIRING RATES. BS kw BS kw BS kw BS kw.

TWO STAGE PROGRESSIVE GAS BURNERS

RIELLO 40 GS SERIES. One Stage Gas Burners FIRING RATES. S kw S kw S kw S kw

RS Series Two Stage Progressive Gas Burners

RIELLO 40 FS SERIES. One Stage Gas Burners FIRING RATES. FS kw FS kw FS kw FS kw FS kw FS kw GAS

TECHNICAL DATA LEAFLET GAS. RS/1 Series. One Stage Gas Burners. RS 34/1 MZ kw RS 44/1 MZ kw.

RS/M SERIES. Modulating Gas Burners FIRING RATES

TWO STAGE LIGHT OIL BURNERS PRESS G SERIES

RS SERIES. Two Stage Progressive Gas Burners FIRING RATES

RS/1 SERIES. One Stage Gas Burners RS 34/1 MZ RS 44/1 MZ kw kw GAS

RS/E-EV MZ SERIES. Modulating Gas Burners FIRING RATES

RL/M BLU SERIES. Low NOx Modulating Light Oil Burners FIRING RATES. LOW NOx T. M 190/ kw M 223/ kw

DB Series. Technical Data Leaflet. Industrial Dual Block Oil, Gas and Dual Fuel Burners. Industrial TS0086UK00

RIELLO 40 F SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL. F kw F kw F kw

PRESS P/N - P/N ECO SERIES

RDB SERIES. One Stage Light Oil and Kerosene Burners FIRING RATES LIGHT OIL

RES G MRBLU SERIES. Low NOx One Stage Light Oil Burners FIRING RATES. LOW NOx LIGHT OIL

PRESS G SERIES. Two Stage Light Oil Burners FIRING RATES

RS/E BLU Series. Technical Data Leaflet. Low NOx Modulating Gas Burners. Low NOx Gas TS0087UK00

CODE MODEL TYPE PRESS GW 605 T80

KOLHAPUR FOUNDRY & ENGINEERING CLUSTER

Light oil - kerosene burner

Doing more for clean environment and energy saving

CODE MODEL TYPE G3BF 490T G5BF 492T G5BF 489T53

GREENOx BT LOW RETURN TEMPERATURE DUAL BT WITH TILED BOILERS. GREENOx BT COND LOW RETURN TEMPERATURE WITH CONDENSER

Oil - kerosene burner

GAS BURNERS BLU 3000 PR BLU 4000 PR

Installation- and maintenance instruction BENTOFLEX ST 108 PL

product Information on oil, gas and dual fuel burners Industrial burners 1,000 11,700 kw flexible and reliable

Kerosene - oil burner

burners with or without fan. It conforms to EN C). APPROVAL EU type test approval as per EU Gas Appliance Directive.

Oil, Gas and Dual Fuel Burners

Installation- and maintenance instruction ST120 S75/21

Weishaupt oil burners Sizes 30 to 70 1/2003 CA

Oil, gas and dual fuel burners. Burner series

822 NOVAMIX GAS FLOW RATE ADJUSTMENT AS A FUNCTION OF THE AIR FLOW GAS/AIR RATIO 1:1 DOUBLE AUTOMATIC SOLENOID SHUT-OFF VALVE

Emprendimiento Fénix Product Catalogue

Combination controls CG 10

product Digital dual fuel burners Weishaupt dual fuel burners WGL30-C and WGL40-A ( kw) Information on compact burners

ECONOMATIC REX/REXF REX/REXF DUAL STR

product Digital combustion technology Weishaupt oil burners, WL10 to WL40 ( kw) Information on compact burners

Weishaupt Monarch oil burners Sizes 5 to 11 1/2002 CA

product Digital combustion technology Weishaupt gas burners, WG10 to WG40 ( kw) Information on compact burners

OIL BURNERS MAIOR P 45 AB. techniques for energy saving MODEL. HYDRAULIC SYSTEM 220/380 V 60 Hz LB

Weishaupt Monarch oil burners Sizes 1 and 3 1/2002 GB

Installation- and maintenance instruction BENTOFLEX ST120KAV

S4562C 1085 COMBI BOARD APPLICATION. Contents PRODUCT HANDBOOK. General

GasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-300-VEF MBC-700-VEF MBC-1200-VEF

Mobile Diesel Heaters GRY-D / GRY-I Service Training Course

Weishaupt gas burners Sizes 30 to 70 Version NR (NO x reduced)

Installation- and maintenance instruction B20K-2

Weishaupt Monarch oil burners Sizes 5 to 11 1/2002 GB

highes flexibility technology performance security service

Installation- and maintenance instruction B80-2/3

Installation- and maintenance instruction B20KA/K

PRODUCT RANGE A COMPLETE RANGE OF BURNERS FROM 17 TO kw

P60 P72 MANUAL OF - INSTALLATION - OPERATING - MAINTENANCE GAS BURNERS TYPE: BURNERS BRULEURS BRENNER QUEMADORES BRUCIATORI.

G72x Series Direct Spark Ignition Controls

Compact System NRGS 11-2 NRGS Original Installation Instructions English

Differential Pressure Sensors

PRODUCT RANGE

Current consumption Auxiliary switch. Angle of rotation 90 (internal electrical stops) Running time

Installation- and maintenance instruction BENTOFLEX ST133KA/K

Valve monitoring system VDK 200 A S02

3 Edition Product brochure GB AGA

REX/REX F/REX K/REX K F REX DUAL/REX DUAL F

Installation- and maintenance instruction B20KAV/KV

Governor with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

CATALOGUE A complete range of burners for all fuels MONOBLOCK kw DUOBLOCK kw

QUOTATION BLADE 7 LX. Product code GEAL6S2BAA

MBC-300-SE MBC-700-SE MBC-1200-SE MBC-300-N MBC-700-N

EC 200 EC 300 GE 360 GE 400 GE 600 L-S BM

AMR. GB-Ganz Tüzeléstechnikai Kft. MODULATING DUOBLOCK BURNER FAMILY

available in battery up to 4 units for a total of 560 kw

G821L/G822L Series Integrated Function Direct Spark Ignition Controls

MBC-300-SE MBC-700-SE MBC-1200-SE MBC-300-N MBC-700-N

MODEL B360 E ILLUSTRATED PARTS BREAKDOWN UNIT 1. From Serial Number: Untill Serial Number: Edizione 2010 Rev. A. Cod

X4 Installation and Operation Manual - POWER FLAME INCORPORATED

VLF45... Hot Air Valves. Siemens Building Technologies HVAC Products

Installation- and maintenance instruction B20KA/K

Differential Pressure Switch QBM81-

Electronic Ignition Module

INDEX. The technical and dimensional data reported in this manual may be modified in view of any product improvement.

Updated technical data can be found in this document, supplemented by the Riello BX Burner Manual regarding commissioning checks and adjustments.

Boiler Management Unit (BMU)

Power consumption Wire/transformer sizing. Motor. Spring return. Motor. Spring return. EMC Low voltage directive

Gas Pressure Governors

Installation- and maintenance instruction BENTOFLEX ST133K

Current consumption Auxiliary switch. Angle of rotation 90 (internal electrical stops) Running time

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

VF VFH. elektrogas.com. Butterfly valves DN40 DN150 EE155-11/11

LKS 160 FOR AIR DAMPERS ON MULTI-STAGE AND MODULATING BURNERS

VGD20... VGD40... Double Gas Valves. Siemens Building Technologies Landis & Staefa Division

Transcription:

TWO STAGE PROGRESSIVE AND MODULATING GAS BURNERS RIELLO GS/M SERIES GS /M / 5 3/8 19 The Riello GS/M series of two stage progressive or modulating gas burners, is a complete range of products developed to respond to any request of gas burners for hot air generator according to EN. These new models complete the Riello gas series which prides itself on many years of experience in all the world in the field of residential heating and soft industrial applications. This series of burners is available in two different models with an output ranging from to 19, divided in two different structures. Basic version of these models has two stage progressive operation. A simple modification, adding a component, permits obtaining modulating operation with a rate 1 :. The burners are supplied air fuel ratio control gas trains. This more advanced version can better satisfy market needs for applications where modulation is requested to obtain highest plant efficiency. In developing these burners, special attention was paid to the ease of installation and adjustment, to maintaining the smallest size possible and obtaining high performance for modulating operation to fit into any sort of application available on the market. All the models are approved by the EN 7 European Standard and they conform to European Directives: Gas Appliances, EMC, Low Voltage and Boiler Efficiency. TS11UK

TECHNICAL DATA Model GS /M Approval Emissions Electrical data Fuel / air data Setting Servomotor Heat output type run time Working temperature Net calorific value G gas G gas density G gas delivery Net calorific value LPG gas LPG gas density LPG gas delivery Fan Air temperature Electrical supply Aux. electrical supply Control box Total electrical power Rated total current Protection level Motor supply Motor electrical power Rated motor current Motor start current Motor protection level Aux. electrical power Auxiliary rated current Ignition transformer Operation Sound pressure Sound output CO emissions NOx emissions Directives Conforming to: Certifications s Mcal/h C min./max. h/nm 3 kcal/nm 3 kg/nm 3 Nm 3 /h h/nm 3 kcal/nm 3 kg/nm 3 Nm 3 /h type max C Ph/Hz/V Ph/Hz/V type A IP Nfasi/V/Hz A A IP A db(a) W mg/h mg/h Modulating (with regulator and probes accessories) LANDIS 3 / 5 3/8 19 18,9/3,1 9,3 37/7,5 1,8-8.,71,/,,5,3/8, 19, 5,8,19,85/1,3,7 1,7/3,18 7,5 Forward blades 1/5/3 (±%) -- LMG,13,5,8 1 XD (IP ) 1/3/5 (±%),9,15,7 1,3,8 5,,,5 3V - 1x15 kv.a - 5mA Intermittent 5 7 -- 3 1 9/39/EEC, 89/33/EEC, 73/3/EEC, 9//EEC EN 7 CE-85BM53 Reference conditions: Temperature: C Pressure: 13 mbar Altitude: m a.s.l. Noise was measured in the boiler room behind the burner at a distance of 1 meter. Since the Company is constantly engaged in the production improvement, the aesthetic and dimensional features, the technical data, the equipment and the accessories can be changed. This document contains confidential and proprietary information of RIELLO S.p.A. Unless authorised, this information shall not be divulged, nor duplicated in whole or in part.

FIRING RATES 5 5 GS /M 3 3 1 mm H O hpa (mbar) -,5... 8.. 1. kcal/h 8 1 1 5 5 3 3 1 mm H O hpa (mbar) -,5... 8.. 1. 1. 1. 18. kcal/h 8 1 1 1 18 Useful working field for choosing the burner Modulation range Test conditions conforming to EN 7: Temperature: C Pressure: 13 mbar Altitude: m a.s.l.

Y FUEL SUPPLY GAS TRAIN The burners are set for fuel supply from either the right or left hand sides. Depending on the fuel output and the available pressure in the supply line, you should check the correct gas train to be adapted to the system requirements. The gas train is Multibloc type, containing the main components in a single unit. A valve seal control (as accessory) can be fitted to the Multibloc gas trains. MB-VEF 7-1 1 L1 3 L MULTIBLOC 7 8 P1 9 5 PF PL 11 1 Gas inlet Manual tip 3 Antivibrating joint Gas pressure gauge 5 Gas filter Min gas pressure switch 7 Safety gas valve 8 Gas valve 9 Gas regulator Adapter 11 Burner PF Impulse line combustion chamber PL Impulse line combustion head P1 Gas pressure gauge L Gas train to be ordered separately L1 Supplied by the installer The following table shows the dimensions of the gas trains which can be fitted to Riello GS/M burners, intake diameter and the coupling flange to the burner. Øo Ø Øo Z X Name Code Ø i Øo X mm Y mm Z mm MULTIBLOC MB-VEF 7 MB-VEF 1 397535 39753 Rp 3/ Rp 1 Rp 3/ Rp 3/ 3 5 3 55 1 15

PRESSURE DROP DIAGRAM The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can be combined with them; the value thus calculated represents the minimum required input pressure to the gas train. NATURAL GAS LPG GS /M GS /M P mbar combustion head + gas train combustion head G 8 MB-VEF 7 G5 1 8 P mbar combustion head + gas train combustion head LPG 8 MB-VEF 7 Pressure loss Pressure loss 18,9 3 5 7 8 9,3 kcal/h X 18,9 3 5 7 8 9,3 kcal/h X 3 5 7 9 1 5 3 5 7 9 1 5 Gas train MB-VEF 7 Code 397535 NATURAL GAS LPG P mbar G 1 G5 P mbar LPG 1 combustion head + gas train combustion head 1 1 8 MB-VEF 7 MB-VEF 1 18 1 1 1 8 combustion head + gas train combustion head 1 1 8 MB-VEF 7 MB-VEF 1 Pressure loss 3 37 5 7 8 9 1 1 13 1 15 1,8 18 kcal/h X Pressure loss 3 37 5 7 8 9 1 1 13 1 15 1,8 18 kcal/h X 3 5 7 9 1 13 15 17 3 19 3 5 7 9 1 13 15 17 3 19 Gas train MB-VEF 7 MB-VEF 1 * With natural gas. Code 397535 39753 Output - 1 * note For pressure levels different from those indicated above, please contact Riello Burners Technical Office.

3" SELECTING THE FUEL SUPPLY LINES The following diagram enables pressure drop in a pre-existing gas line to be calculated and to select the correct gas train. The diagram can also be used to select a new gas line when fuel output and pipe length are known. The pipe diameter is selected on the basis of the desired pressure drop. The diagram uses methane gas as reference; if another gas is used, conversion coefficient and a simple formula (on the diagram) transform the gas output to a methane equivalent (refer to figure A). Please note that the gas train dimensions must take into account the back pressure of the combustion chamber during operations. Control of the pressure drop in an existing gas line or selecting a new gas supply line. The methane output equivalent is determined by the formula fig. A on the diagram and the conversion coefficient. Once the equivalent output has been determined on the delivery scale ( V ), shown at the top of the diagram, move vertically downwards until you cross the line that represents the pipe diameter; at this point, move horizontally to the left until you meet the line that represents the pipe length. Once this point is established you can verify, by moving vertically downwards, the pipe pressure drop of on the botton scale below (mbar). By subtracting this value from the pressure measured on the gas meter, the correct pressure value will be found for the choice of gas train. Example: - gas used G5 - gas output 9.51 mc/h - pressure at the gas meter mbar - gas line length 15 m - conversion coefficient. (see figure A) - equivalent methane output V = 9.51 = 15.3 mc/h. - once the value of 15.3 has been identified on the output scale ( V ), moving vertically downwards you cross the line that represents 1" 1/ (the chosen diameter for the piping); - from this point, move horizontally to the left until you meet the line that represents the length of 15 m of the piping; - move vertically downwards to determine a value of 1. mbar in the pressure drop botton scale; - subtract the determined pressure drop from the meter pressure, the correct pressure level will be found for the choice of gas train; - correct pressure = ( -1. ) = 18. mbar 3 5 1 7 95 1 15 V 1 3 5 7 8 15,3 3 15 1 9 5 8 8 3 " PIPE LENGTH (m) " " 1/ " V = Gas output Nmc/h f 1" 1" 1/ 1" 1/ 3/ f 1 - G =, - G5 {1,18 - G31 1/ Figure A 1,,1,,3,,5,,7,8 1 3 5 PRESSURE DROP (mbar) PIPE DIAMETER

VENTILATION The different ventilation circuits always ensure low noise levels with high performance of pressure and air delivery, inspite of their compact size. The burners are fitted with an adjustable air pressure switch, conforming to EN 7 standards. Air suction Min and max air pressure switches COMBUSTION HEAD The combustion head in Riello GS/M Heater burners is the result of an innovative design, which allows combustion with low polluting emissions, while being easy to adapt to all the various types of boilers and combustion chambers. Simple adjustment allows the internal geometry of the combustion head to be adapted to the burner output. Combustion head Flange Dimensions of the flame Ø Flame length (m) 1 L max L min D max D min 1,5 Flame diameter (m) L 3 5 Burner output () Example: Burner thermal output = 35 ; L flame (m) = 1, m (medium value); D flame (m) =, m (medium value)

ADJUSTMENT BURNER OPERATION MODE All these models in standard version are two-stage progressive operation. Adding the output regulator device they are modulating operation. On two-stage progressive operation, the burner gradually adapts the output to the requested level, by varying between two pre-set levels (see figure A). On modulating operation, normally required in steam generators, in superheater boilers or diathermic oil burners, a specific regulator and probes are required. These are supplied as accessories that must be ordered separately. The burner can work for long periods at intermediate output levels (see figure B). Air damper adjustment Two-stage progressive operation Modulating operation Output Controlled variable C bar MAX MIN time Output Controlled variable C bar MAX MIN time time time Figure A Figure B Air damper motor Ignition transformer V1 START UP CYCLE Lock-out due to ignition failure TL M TR 1 nd 1 st,5 s 3 s s 5 s 5 s 11 s 3 s 3 s max Correct operation time (s) s s-,5s,5s-3,5s The burner begins the ignition cycle. Safety time. Progressive open of the air damper until the nd stage position. 3,5s-5,5s Pre-purge at the nd stage. 5,5s-77,5s The air damper closes until 1st stage position. 77,5s-8,5s Pre-purge at the 1st stage. 8,5s-88,5s The ignition transformer starts. 85,5s The solenoid opens. 88,5s-99,5s Ignition 1st stage. 99,5s Ignition nd stage. If the flame does not light within the safety limit (~3s) the burner locks-out. Lock-out is shown by a led on the appliance.

WIRING DIAGRAMS Electrical connections must be made by qualified and skilled personnel in conformity with the local regulations in force. The 7-pole socket is incorporated inside the burner, the - pole socket (for connecting the nd stage thermostat to the hour meter) and the -pole (for connection to the gas train) are already connected to the equipment and fixed to the inside of the burner. The 7 and -pin plugs are also supplied for connection to the boiler. Appliance fitted with 7-pole, -pole and -pole sockets TWO STAGE PROGRESSIVE OPERATION 8 9 MB B5 T T7 T8 X B S3 T T1 N L1 X7 3 1 N Ph X P P N V PS MB X7 X X h TR h1 S IN TL TS PG VR VS - Remote manual reset - Terminal block - 7 pin plug - pin plug - pin plug - nd stage hourcounter - High-low mode control device system - 1st stage hourcounter - Remote lock-out signal - Manual burner stop switch - Limit control device system - Safety control device system - Min. gas pressure switch - Adjustment valve - Safety valve PS h TR ϑ P h1 S IN TL ϑ P 1,5 mm TA PE N L ~ 5Hz 3V PG P TS ϑ P VR VS MODULATING OPERATION (WITH REGULATOR) RWF PS Q Y1 Y Q13 Q1 TE L1 N M1 I1 G1+ G- G+ PS MB X7 X BT BP - Remote manual reset - Terminal block - 7 pin plug - pin plug - Temperature probe - Pressure probe X B5 T T7 T8 T T1 X7 1 3 5 7 8 9 11 MB a b c d The following table shows the supply lead sections and types of fuse to be used. BT 3 7 MB Model F L A mm GS /M 3V T 1 3V T 1 BP 1 /ma F = Fuse L = Lead section

EMISSIONS The emission data have been measured in the various models at maximum output, in conformity with EN 7 standard. mg/h 13 1 1 9 8 7 NO EMISSIONS 5 GS /M mg/h 35 3 5 CO EMISSIONS 15 GS /M db(a) 7 7 7 8 58 5 SOUND EMISSIONS (sound pressure) GS /M Special attention has been paid to noise reduction. All models are fitted with sound-proofing material inside the cover.

OVERALL DIMENSIONS (mm) These models are distinguished by their reduced size, in relation to the outputs achieved, which means they can be fitted to any boiler actually on the market. BURNER A F E H D M I V Z N Model A D E F H I M N V Z GS /M 5 88 98 37 389 1 1 5 15 3 Rp 3/ Rp 3/ 1 7 1 15 33 33 BURNER-BOILER MOUNTING FLANGE GS /M F Q F R C Q R C C1 Q A1-B1 A-B Model A1 A B1 B C C1 F Q R GS /M - 155 - - 155-1 17 13-185 17 5 9 11 PACKAGING Z X Y Model GS /M X Y Z kg 55 5 9 535 33 375 17 17

INSTALLATION DESCRIPTION Installation, start up and maintenance must be carried out by qualified and skilled personnel. All operations must be performed as described in the technical handbook supplied with the burner. The burner is set in the factory on standard calibration (minimum output). If necessary adjustments can be made on the basis of the maximum output of the boiler. BURNER SETTING The gas flow rate for both high and low capacity must be done by using the screws V and N on the gas valve group. The air flow must be adjusted at maximum output by the air damper. V N If necessary it is possible to increase the minimum output by moving a cam of the air servomotor. In according to EN 7 and EN, the GS /M and are provided by two air pressure switches to be adjusted at the end of commissioning procedure. MAINTENANCE Particular care is given to the design of the burner to ensure ease of maintenance. The burner body is hinged to permit quick and easy access to the combustion head for maintenance and setting. To make friendly all the operations on the burner, the internal and external components are connected by plugs and sockets.

BURNER ACCESSORIES LPG kit For burning LPG gas, a special kit is available to be fitted to the combustion head on the burner, as shown in the following table: Burner GS /M LPG kit Kit code for standard head 388 388 Kit code for extended head 388 388 Extended head kit Standard head" burners can be transformed into "extended head" versions by using the special kit. Below the KITS available for the various burners are listed, showing the original and the extended lengths. Burner GS /M Standard head length (mm) 18 1 Extended head kit Extended head length (mm) 188 8 Kit code 38 3873 Accessories for modulating operation To obtain modulating setting, the GS/M series of burners requires a regulator. Regulator type RWF Regulator Regulator code 37 The relative temperature or pressure probes fitted to the regulator, must be chosen on the basis of the application. Probe Probe type Temperature PT Pressure ma Pressure ma Range ( C) (bar) - 5 C,5 bar 1 bar Probe code 31 313 31 7-pin plug kit If necessary a 7-pin plug kit is available (in packaging of n. 5 pieces). Burner All the models 7-pin plug kit Code 395

Ground fault interrupter kit A Ground fault interrupter kit is available as a safety device in case of electrical system fault. It is supplied with burners with pin plug. Burner All the models Ground fault interrupter kit Kit code 3118 SPECIFICATION A special index guides your choice of burners from the various models available in the GS/M series. Below there is a clear and detailed specification description of the product. DESIGNATION OF SERIES Series: G Fuel : Natural gas Size Operation mode: /M two stage progressive of fully modulating Special head for heater Electrical supply to the system: 1/3/5 1/3V/5Hz G S /M Heater 1/3/5 AVAILABLE BURNER MODELS GS /M Heater / 5 Heater 3/8 19

PRODUCT SPECIFICATION Burner Monoblock, gas burners, completely automatic, high/low progressive operation mode or fully modulating by using a regulator: - Ratio air/fuel controlled by checking both the air and the gas flows -Two pressure switches on the burner, to make sure the burner operation, detecting both the fan and the chimney fonctions - Remote reset available - Servomotor to drive the air damper to fully closed position at stand-by, low and high fire position -Turn down fire 1: - Fan with forward inclined blades - Metallic cover - Single phase electric motor 3 V, 5 Hz - Combustion head fitted with: - stainless steel head cone, resistant to high temperatures - ignition electrodes - ionisation probe - gas distributor - flame stability disk - additional device, to keep short the flame shape - Protection filter against radio interference - IP XD (IP ) electric protection level. Gas train Fuel supply line in the Multibloc configuration, fitted with: - Filter - Pressure stabiliser - Minimum gas pressure switch - Safety valve - One stage working valve - Self-adapting regulator, to adjust the gas flow following the air flow. Approval: - EN 7 standard - EN (Heaters). Conforming to European Directives: - 9/39/EEC (gas) - 73/3/EEC (low voltage) - 89/33/EEC (electromagnetic compatibility) - 9//EEC (efficiency). Standard equipment: - Hinge to turn the burner left-side or right-side for the maintenance position - Flange insulation screen - Screws and nuts for fixing the flange to the boiler - 7-pin plug with capacitor for EMC - -pin plug to connect the high-low thermostat - Instruction handbook for installation, use and maintenance - Spare parts catalogue. Available accessories to be ordered separately: - LPG kit -RWF for modulating operation - Ground fault interrupter kit - 7-pin plug kit - Extended head kit.

Lineagrafica ISO 91 Cert. n. 1 RIELLO S.p.A. - Via degli Alpini, 1-375 LEGNAGO (VR) Italy Tel. ++39.3111 - Fax ++39.198 Internet: http://www.rielloburners.com - E-mail: rburners@rielloburners.com Since the Company is constantly engaged in the production improvement, the aesthetic and dimensional features, the technical data, the equipment and the accessories can be changed. This document contains confidential and proprietary information of RIELLO S.p.A. Unless authorised, this information shall not be divulged, nor duplicated in whole or in part.