TECHNICAL-OPERATIONAL DOCUMENTATION. FIRE SAFETY VALVES type V370 and RK370

Similar documents
TECHNICAL-OPERATIONAL DOCUMENTATION RK370M FIRE SAFETY VALVES

7/S5 FIRE DAMPER FD40. v 2.9 (en)

7/S1 FIRE DAMPER PPZEN. v 2.5 (en)

FIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS

7/S6 FIRE DAMPER FDC40. v 2.9 (en)

PKIR3G, PKIS, PKIS3G and PKIS3GA

TPM 075/09. Valid from 1/2/2016 EN 15650: FIRE DAMPER FDMB

TPM 075/09-DK VALID FROM: 15/1/2012 FIRE DAMPER AND FIRE DAMPER-SMOKE FDMB, FDMB-SRD

MULTICOMPARTMENT SMOKE CONTROL DAMPERS DKISMA

(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm.

Systemair Fire Dampers

Fire damper BKA-EN. with general technical approval Z tested according to DIN EN

ETPS-EI Fire Damper EI 60 S / EI 120 S Instructions for Installation, Operation and Maintenance

PKI-C Cartridge Fire Dampers

NEO. Fire Damper. air handling intelligence FIRE SAFETY FUNCTION

BX-1H. Fire Valve FIRE SAFETY FUNCTION APPLICATION DESCRIPTION. in libraries of

Systemair Fire Dampers

FDR - Fire Damper for Rectangular and Circular Ducts. Halton FDR. Fire Damper for Rectangular and Circular Ducts

DKISMA. Systemair multicompartment rectangular smoke control dampers. Ordering codes. Description. Design. Fire safety products 1 / 8.

SMOKE CONTROL DAMPERS

Bevent Rasch BSK Fire /04/2017

Fire Dampers. Types FKA FRL FRK 4/1/EN/1

Fire damper FK120/FK90 TECHNICAL DATA

Bevent Rasch BSK6. - Fire /04/2017

Fire and Smoke Damper Actuator product overview

TECHNICAL PRODUCT DOCUMENTATION

Mounting and Operating Instructions EB 5868/5869 EN

Power consumption In operation At rest For wire sizing

Smoke damper EKO-SRB1

D10 Page. Contents. Complete Equipment with Scope of Supplies 2. Accessories 3

SERIES 2000 GAS SAFETY SHUT OFF VALVE

BSK-EN Fire damper INSTALLATION, MOUNTING AND OPERATING INSTRUCTIONS

Fire/smoke damper EKO-SRBG1

Fire/smoke damper EKO-JBG2

Heights up to 1000 mm Fire resistance period up to 120 minutes

Actuators for Fire and Smoke Protection Dampers

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

Fire Dampers. Type FDF. Compliant to SABS (193:2004) SA/6/1/EN/3

Electrical data Nominal voltage AC V / DC V Nominal voltage frequency

PK-I-Ex. Fire resistance class Circular: EI60S, EI90S, EI120S Square: EI90S, EI120S. Systemair Fire Dampers for Explosive Areas.

Electromotoric Actuators

VA-7450 Series. Electric Valve Actuators

Laminar ceilings, exhaust columns, exhaust grilles

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

1 Product Description System Layout Safety Instructions Intended Use Installation... 3

RUC industrial relays of small dimensions

Actuators for Fire and Smoke Protection Dampers

Fire Dampers Catalogue

MC2500. Installation and Operation Manual

Operating manual LPS. Humidifies and Cools. ÁLPS.ENzÈ LPS.EN

D58 Series Brake Instructions

For installation into ductwork

Technical documentation

Type NAK. Gas-tight shut-off damper with pneumatic actuator

FK120/FK90 FIRE DAMPER» INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE

Power consumption In operation At rest For wire sizing. Functional data Torque Motor Spring return. Rated impulse voltage Control pollution degree 3

Power consumption In operation At rest For wire sizing

Minimum 27 in-lb torque

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

Type 2511/12. Type Type 2030 Cable plug. ASI cable plug. Dosing control. General technical data Orifice Type 6518

N05, N10 SERIES NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND TWO-POSITION CONTROL

SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS

Product card User manual. KP Strong Safe

Liv-Elir d.o.o. Contact Info: Tel/Fax.: Mob.: Mail: REPAIR AND SERVICE / PRODUCTION

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

LCU DX Efficient cooling with no loss of space

3/2 and 4/2 directional seat valves with solenoid actuation

USERS MA UAL Bellow sealed valve Fig.229, 230, 234, 235 Edition: 1/2008

Operating and Installation Instructions

Rectangular smoke damper (remote controlled)

ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE

Actuators for Fire Protection Dampers

Power consumption In operation At rest For wire sizing. Torque Inhibiting torque. 150 s / C Sound power level Motor

BAH series Use and Maintenance Manual

CFSD Series. Product Description

M9208-Bxx-3 Series On/Off Electric Spring Return Actuators

Holtumsweg 13, D Weeze, Tel /9134-0, Fax /1444

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

Additional operating instructions according to ATEX 94/9/EC Volumetric flow controller VM-PRO-Ex

Power consumption In operation At rest For wire sizing. Connection Motor. Auxiliary switch

Minimum 27 in-lb Torque

Solar Thermal. Grant Solar Pump Station Installation & Servicing Instructions

Parking space border or support. Drive axis 15 L

Product bulletin for: ST2 Ball valves with two-way and three-way BSPP threaded fittings

Electromotoric Actuators

Cytotoxic Safety Cabinets ENVAIR eco safe Plus

E07 -Heavy Duty- Lifting Platform Technical Data Lifting system for a person with limited locomotory capacity

0 = 0 mm rear cover panel edging (standard) Number = rear cover panel edging according to table

Versatile and Powerful

Actuators for Fire and Smoke Protection Dampers

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

INSTRUCTION MANUAL (ATEX / IECEx)

Operating manual Separator

INSTRUCTION MANUAL MAGNA RAIL

Parking space border or support. Drive axis 15 L

Electromotoric Actuators

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1

Rectangular fire damper TFER 30. pag. C-10

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1

Transcription:

TECHNICAL-OPERATIONAL DOCUMENTATION FIRE SAFETY VALVES type V370 and RK370 MANUFACTURER: FRAPOL Spółka z o.o. 30-832 Kraków, ul. Mierzeja Wiślana 8 Phone: (012) 653-27-66, 653-27-67, 653-26-92 fax (012) 653-27-89 MARCH 2013

List of contents 1. INTRODUCTION... 3 2. GENERAL CHARACTERISTICS... 3 3. VERSIONS... 4 4. PRINCIPLES FOR INSTALLATION OF FIRE VALVES... 6 5. PRINCIPLES FOR FIRE VALVES MAINTENANCE... 16 6. PERIODICAL MAINTENANCE... 18 7. LIST OF SPARE PARTS... 19 8. TECHNICAL DATA OF ACTUATORS AND SOLENOIDS... 19 9. FIRE VALVE INSPECTION DOCUMENT... 20

1. INTRODUCTION Rectangular V370 and round RK 370 fire safety valves with fire resistance class EI 120 (ve i o) S are manufactured by FRAPOL Sp. z o.o. in Krakow and are intended for use in the construction industry as elements closing ventilation ducts during the fire within vertical fire barrier to prevent permeation of hot gases and fire smokes via this way to zones not covered by the fire. The fire safety valves feature: EC Certificate of Conformity No. 1488-CPD-0352/W EC Certificate of Conformity No. 1488-CPD-0353/W Issued by: Building Research Institute 00-950 Warszawa, ul. Filtrowa 1 For conformity with harmonised European standard: PN-EN 15650:2010 Ventilation for buildings. Fire dampers They also feature: Hygienic Attestation HK/B/1539/01/2012 issued by: National Institute of Public Health National Institute of Hygiene 00-791 Warszawa, ul. Chocimska 24 2. GENERAL CHARACTERISTICS V370 and RK370 fire valves comprise a two-part steel body (casing), which is rectangular in the case of V370 and round in the case of RK370, cut-off partition of PROMATECT boards, placed at the joint of both parts of the body, elements distancing (insulating) both parts of the body, and additional securing elements carrying out the fundamental task of stopping the air flow in the event of fire, namely: elements retaining and setting the mobile partition in the open or closed position (lever-spring mechanism or a BELIMO actuator), thermal trigger (mechanical or electrical thermal element). Valves can be furnished with a thermal trigger adjusted to actuation at the temperatures of 72±5 C or 90±5 C. For V370 valves, both parts of the body are terminated on both sides with flanges with the height of 30 mm, made as a whole with the body, by bending a part of body plate at the straight angle, while in the case of RK370 valves, this is a muff connection. Valve partition drive is located outside its rotating shaft. The valve is basically placed in the fire barrier (wall or ceiling). In the case of a different flap situation against the fire barrier, continuity of fire resistance must be preserved at the section from the fire barrier to the surface crossing the valve, as marked on the assembly diagrams. V370 valves are manufactured in variants HO; HE; MR and ER. Valve sizes are made of combination of sizes BxH for: B = 150; 200; 250; 300; 350; 400; 450; 500; 560; 630; 750; 800; 900; 1000; 1100; 1200, 1250, 1300, 1400 and 1500 mm H = 200; 250; 300; 350; 400; 450; 500; 600; 700, 800, 900 and 1000 mm. On special request, valves can also be made with intermediate B and H dimensions. In the event where the width of the valve (dimension B) is greater than 1500mm, or the height of the valve (dimension H) is greater than 1000 mm, the valve with the required dimension is made as a battery of valves, comprising standard valves. The length of rectangular valves amounts to 370 mm regardless of their size. RK370 valves are manufactured in variants HO; HE; MR and ER. Sizes of such valves are 400; 500; 560 and 630 mm. Total length of RK370 valves amounts to 370 mm.

3. VERSIONS Depending on the type of the applied element that keeps the valve s partition in the open position, as well as furnishing, there are the following versions of the fire safety valves: 3.1. HO version with lever-spring mechanism, opened manually. Opening of the valve occurs by turning the manual lever, during which the return spring is stretched. The cut-off partition of the valve is kept open by the band, manual lever and release element suspended on the peg of the mechanical thermal element. Closure of the cut-off valve can occur as a result of: - automatically due to increase in the temperature of the flowing air to the temperature where the heat-responsive device of the thermal trigger breaks (gets unsoldered (standard 72±5 C). - Manually as a result of release of manual lever from the trigger this allows for periodical closure of the partition to control valve operation. The operation of the thermal trigger (mechanical heat-responsive device) involves air stream flowing round the thermal element (glass ball or soldered metal plates) causes heating of the liquid inside the ball (or solder), which causes breaking of the glass cover (or dissolution of solder), and as a consequence the valve closes when the air flowing through the installation achieves the temperature of ~72 C. V370/HO RK370/HO The actuation of the heat-responsive device releases the peg of the mechanical thermal element based on it, and the latter, by moving backwards, triggers the element blocking the partition of the valve blocking it in the open position. The spring mounted on drive shaft, via the lever system, closes and keeps the valve closed, pressing it to the resistance angle bars. 3.2. HE version with lever-spring mechanism, opened manually. The structure and operation of the valve in this variant is identical as in the case of HO variant. HE valves have a micro-switch installed, which via relevant electrical system allows for signalling the position of the valve partition, and makes it possible to use it in control systems (e.g. switching off the fan when the valve is closed).

V370/HE RK370/HE 3.3. Version with the solenoid 3.3.1. MR version In the MR version, the drive system comprises manual lever with a return spring and a solenoid controlled with power gap. Opening of the valve occurs by turning the manual lever, during which the return spring is stretched. The cut-off partition is kept open by the keeper of solenoid powered with 24V DC, connected to the power installation via micro-switch on the heat-responsive device. On request of the ordering party, a valve of this type can be furnished with a rectifier transformer powered with 230V AC. Closure of the cut-off valve can occur as a result of: - automatically, as a result of increase in air temperature to the temperature where the heatresponsive device of the electrical thermal element is actuated and contacts of the trigger micro-switch are switched, and power supply to the solenoid is disrupted, or as a result of disconnection of solenoid power supply by the control unit as a result of signals from other sensors connected in the control system. - manually by disconnecting power supply for the solenoid by a switch from the fire safety control unit to periodically control valve operation. Breaking (unsoldering) of the heat-responsive device in the trigger causes withdrawal of micro-switch keeper and disrupting power supply to the solenoid. The spring installed on the drive shaft is released and, via the lever system, causes closure of the partition. Additionally installed limit micro-switch, via relevant electrical system allows for signalling the position of the valve partition, and makes it possible to use it in control systems. Regardless of the type, valves with a return spring made of wire with diameter of 3 mm are furnished with solenoid with keeper holding strength of 120 N. Valves with a return spring made of wire with diameter of 3.5 mm are furnished with solenoid with keeper holding strength of 200N N. 3.4. ER version Opening and keeping the valve partition in the open position in this version, as well as its closing, is performed by one of electrical actuators of BF series (including digital actuators) or BLF series by Swiss company BELIMO, specially adjusted to operate fire safety valves. The actuators can be powered with 24 V DC and AC voltage or with 230 V AC voltage. BLF type actuators are applied in fire safety valves with the width not greater than 800 mm and height not greater than 500 mm. Closure of the valve partition occurs automatically as a result of gap in power supply to the actuator. Gap in power supply to the actuator can be caused by: - increase in air temperature to the temperature where heat-responsive device of electric thermal element is actuated and disconnects power supply to the actuator. - disruption of power supply to the actuator from the signal from fire safety control unit. Depending on the actuator type applied, the heat-responsive device is used, the operation of which is identical as in the case of MR type fire safety valve, or some actuator types are manufacturerfurnished with their own trigger BAE72-S or BAE72. Electric actuator kept live all the time maintains the valve in the open position. Upon a gap in power supply, the return spring on the drive shaft, using its accumulated mechanical energy, via the drive system, closes the partition and keeps it closed. In the case of valve closure caused by power shortage, reconnection of power will cause valve opening. If power shortage, however, was caused by actuation of the electrical thermal element, reopening of

fire safety valves can only be possible after replacement of the thermal element, on condition no other elements of the valve have been damaged. BELIMO actuators feature installed micro-switches that signal drive shaft rotation by 5 and 85 (position signalling), hence it is not required to install additional micro-switches informing about position of the partition. BF24TL-T-ST (digital) actuator is connected to the communication bus, which allows for monitoring of the valve by the centralised system. The above drive types refer to both round and rectangular fire safety valves. 4. PRINCIPLES FOR INSTALLATION OF FIRE VALVES 4.1. GENERAL REMARKS Before starting the installation of fire valves, do the following: 4.1.1. Check for conformity of the device supplied with the design (type, variant, size and power supply voltage). 4.1.2. Check whether there are no visible signs of damage during transport or storage at the site. 4.1.3. Check for completeness of the device, and its operation in justified cases, and prepare the valve for installation. Checking valve operation comprises their opening and closing, and observation of the valve during these activities. All valves are supplied in the closed position. Valves in HO and HE versions By turning the manual lever (item 1 Fig. 1a or 2a) clockwise for V370 valves and anti-clockwise for RK370 valves, switch the cut-off partition of the valve from "closed" to "open" position, at the same time stretching the closing spring. After turning the lever to full opening of the valve, hook the lever on manual trigger (item 23 Fig. 1a or 2a), wire protruding from the thermal element (item 3 Fig. 1a or 2a) so as to keep the valve open. After releasing the manual lever from the catch, the stretched spring shifts the partition from open to closed position. Movement of the partition when opening and closing must be smooth, without stops, binds, and excess resistance. Valve partition must adhere to ventilation seals on resistance profiles on the entire circumference. Valves in MR version Checking the operation of the valves (Fig. 1b; 1d and 2b) is analogical as in the case of HE and HE versions, except for holding and releasing the manual lever. In order to check these valve versions, connect relevant voltage to the solenoid (Fig. 1b; 1d and 2b item 3) or transformer (Fig. 1b; 1d and 2b item 4) via switch allowing for switching the power supply on or off. While checking, switch off power supply and manually open the valve, contacting the keeper (Fig. 1b and 2b item 2) with the solenoid (Fig. 1b; 1d and 2b item 3). Valve partition must be kept open by the solenoid. Then disconnect the solenoid s power supply. The partition should move to the closed position. Movement of the partition when opening and closing must be smooth, without stops, binds, and excess resistance. Valve partition must adhere to ventilation seals on resistance profiles on the entire circumference.

Valves in ER version Valve in this version, without connected power supply of the solenoid, is in the closed position (Fig. 1c and 2c item 1). By turning the crank at the BELIMO actuator in the direction marked on the actuator, we open the partition. After complete opening, when the crank is released, the spring wound on the actuator shaft should automatically close the partition and keep it in this position. Similarly as in the case of other versions, movement of the partition when opening and closing must be smooth, without stops, binds, and excess resistance, and valve partition must adhere to ventilation seals at the entire circumference. Type V370 Version HO, HE Version MR Version ER Type RK370 Fig. 1a Fig. 1b Fig. 1c Version HO, HE Version MR Version ER Fig. 2a Fig. 2b Fig. 2c 4.1.4. Check for the size and shape of openings prepared in the walls to set the valves acc. to section 4.2. 4.1.5. Check whether after valve installation it will be possible to open them and access them from the maintenance side (valve drive) to allow for possible replacement of elements or periodical check. 4.1.6. If discrepancies are found, take explanatory measures and achieve conformity with the requirements. 4.2. REQUIREMENTS FOR THE SIZE AND SHAPE OF OPENINGS FOR FIRE VALVE ASSEMBLY DEPENDING ON THE TYPE OF THE WALL. 4.2.1. Requirements for the size and shape of openings for valve installation in the brick wall. For round valves RK370 For rectangular valves V370 Valve height Opening height Valve width Opening width

The axis of the opening made must be in the axis of the ventilation duct installed. 4.2.2. Requirements for the size and shape of openings for valve installation in the wall of cardboardplaster boards. For rectangular valves RK370 For round valves V370 Bearing profile plaster wall Bearing profile plaster wall Plaster boards Plaster boards 4.3. PRINCIPLES FOR INSTALLATION OF FIRE VALVES 4.3.1. Assembly of the valves must correspond to one of the installation variants acc. to section 4.4. 4.3.2. The partition s rotation axis can be horizontal or vertical for V370 valves. 4.3.3. Air flow direction via the valve is of no significance for its assembly method (before or after the partition). 4.3.4. Valves in standard version cannot be exposed to weather conditions or chemically aggressive environment. 4.3.5. Valve installation can be performed in a vertical fire barrier. 4.3.6. The applied assembly materials and the suspension method must prevent unintentional change of the valve position against the fire barrier. 4.3.7. The valve must be connected to the ventilation installation without any tensions, in a durable and leak-proof manner. 4.3.8. In the closed position, the partition must adhere to the resistance angle bars inside the casing on the entire circumference. 4.3.9. On both sides of the valve partition inside the ventilation duct, there must be free space to allow for its opening. 4.3.10. Electrical installation of the signalisation and powering of the drive elements must be made according to the schematic diagrams for the relevant valve version, according to section 4.5. 4.3.11. After installation of the element in the fire barrier (depending on the version, valve or duct), sealing must be provided between the fire barrier and the element installed, according to the adopted version. After sealing, check for correct operation of the valve and whether the elements of the valve drive have not become dirty. If so, clean them. 4.3.12. After installation of the fire valve and test operation, perform the commissioning confirmed with acceptance document. CAUTION: When assembling joint valves (valve batteries), apply all the same principles as for single valves. 4.4. FIRE VALVE INSTALLATION VARIANTS. Depending on the designed valve situation as regards the fire barrier, there are the following installation variants: - in the fire barrier, - remote from the fire barrier. A special case of valve situation against the fire barrier is the installation on the surface of the barrier. For fire barrier class EI120, required thickness G amounts to:

- barrier made of concrete - 115 mm, - barrier made of cellular concrete blocks or full brick - 115 mm, - light barrier, e.g. of plaster board - 125 mm. 4.4.1. The valves installed inside the opening in a concrete or brick fire barrier acc. to diagram in Fig. 6a and 6b. 4.4.1.1. Place the valve in the fire barrier, in the previously prepared opening acc. to section 4.2.1. In fire barriers of class EI120 (walls or ceilings) made of concrete, brick, cellular concrete blocks or full brick with the above thickness G (Fig. 6a and 6b), the cut-off partition of the valve should remain within the axis of the partition. Assembly of the valves in this version in fire barriers class EI120, but with greater thicknesses must be made observing partition depth acc. to Fig. 6a and 6b, flange distance from the partition on the side without the drive must not be greater than values in Table 1. Table 1 Fire barrier made of: concrete cellular concrete blocks full brick Flange distance from partition for valves V370 and RK370 32.5 mm 32.5 mm 32.5 mm This requirement means that valves of V370 or RK370 type should protrude from the wall on the drive side to the distance not greater than B=222.5 mm. 4.4.1.2. Connect the valves with the suspended ventilation ducts on both sides of the fire barrier.

Type V370 Type RK370 duct valve duct valve drive Drive board Fire barrier Cement, lime-cement mortar or promastop MG III Cement, lime-cement mortar or promastop MG III Fire barrier Fig. 6a Fig. 6b 4.4.1.3. The gap between the valve casing and the fire barrier must be carefully filled with cement, lime-cement mix or PROMASTOP MG III fire-protective mortar. It is prohibited to force in any pieces of brick or concrete while sealing, as this might lead to deformation of the casing (particularly in cases of valves with large cross-sections), and thus prevent free rotation of the partition and its closure (friction in slide bearings, or friction between the partition and the casing). 4.4.2. Valves installed in a light fire barrier made of plaster and cardboard boards acc. to diagram in Fig. 7a and 7b. 4.4.2.1. Place the valve in the fire barrier opening prepared acc. to section 4.2.2. so that, for barrier with class EI120 and thickness of 125 mm, the cut-off partition of the valve should remain in the axis of barrier thickness. Valves of V370 type must protrude from the wall on the drive side to the distance of 218 mm, while valves of RK370 type must protrude from the wall on the drive side to the distance of 213 mm. Assembly of valves in this version in fire barriers with lower fire resistance classes must be made observing valve setting against the barrier acc. to the data in Table 2. 4.4.2.2. Connect the valves with the suspended ventilation ducts on both sides of the fire barrier. 4.4.2.3. After appropriate valve setting in the fire barrier, seal it with mineral wool with thickness of min. 100 kg/m 3 and cover the wall with plaster boards acc. to Fig. 7a; 7b and 7c.

Type V370 Plaster boards Plaster board 12.5mm 4 layers Metal profile of plaster wall Angle bar metal strip 50x25x1 Cut-off partition Mineral wool with thickness of min. 100kg/m 3 or fire-safety foam e.g. PROMAFOAM Suspended ventilation duct Plaster boards Steel profile of plaster Bilateral sealing of the valve and wall with fire-safety mass e.g. PROMASEAL-Mastic drive drive Fire-safety foam e.g. PROMAFOAM Mineral wool min. 100kg/m 3 Plaster board 12.5mm Screws for plaster Mineral wool min. 100kg/m 3 Suspended ventilation duct Valve installation before assembly of ventilation ducts. Fig. 7a Valve installation ventilation ducts. with simultaneous assembly of Fig. 7b

Type RK370 Plaster boards Screw 3.5x25mm Steel profile of plaster w. Detail Fig. 7c Fixing clamps 4 items Mineral wool Valve RK370 Bilateral sealing of valve and wall with fire-safety mass e.g. PROMASEAL- Mastic drive Plaster board12,5mm overlay Mineral wool Plaster boards around Mineral wool Plaster boards around Mineral wool min. 100kg/m 3 Fig. 7c 4.4.3. Valve installed remote from the fire barrier acc. to diagram in Fig. 8a and 8b. 4.4.3.1. Distance from the fire barrier is marked as length X of ventilation duct protruding from the wall constituting the fire barrier acc. to Fig. 8a and 8b. 4.4.3.2. Place the duct in the fire barrier in the previously prepared opening acc. to section 4.2. at the appropriate length X, ensuring the designed distance of the valve from the fire barrier. 4.4.3.3. Assemble the valve with the duct so that its drive remains outside the insulation (cf. Fig. 8a and 8b). 4.4.3.4. Install ventilation ducts to the valve on one side and to the duct in the fire barrier on the other, suspending them at a distance not greater than 3 m from the fire barrier axis. 4.4.3.5. Such suspended duct with the valve after relevant setting in the fire barrier must be sealed with insulation meeting the requirements of fire insulation of the barrier, e.g. conlit. 4.4.3.6. Section (X +120) mm of the duct and valve type V370 acc. to Fig. 8a, and section (X + 100) mm of the duct and valve type RK370 acc. to Fig. 8b, must be insulated with PROMATECT L 500 boards with 52 mm thickness. At the joint of the valve with the fire barrier, at the entire circumference, make an additional band of PROMATECT L or L 500 boards with the thickness of 52 mm acc. to Fig. 8a or 8b. Such an insulation coating must be closed from the head with PROMATECT L 500 board with the thickness of 30 mm. Before the frontal closure of the insulation coating, tightly fill the gaps between the valve body and the internal circumference of the coating with stripes of mineral wool with the cross-section 10x28 mm, and place a layer of PROMASTOP on it. 4.4.3.7. Frontal closure of the insulation coating for valves of V370 type must be made with stripes of PROMATECT L or L500 board with thickness of 30 mm, width 81 mm and lengths allocated according to cross dimensions of the valve installed, so that along sides B, there are stripes by 2.5 mm longer than nominal dimension, and along sides H, there should be stripes by 164 mm longer than nominal dimension of the side. Stripes of the board along side B can have cuts of 3 mm each on both ends along dimension B, and 30 mm along the width of the stripe (81mm). In turn, in the case of valve of RK370 type, as frontal closing, make a blind of PROMATECT L or L 500 board with thickness of 30 mm in the form of square with dimensions Dn + 176 mm with opening cut in the axis, with diameter Dn + 2.5 mm. The blind installed at the circumference of the valve body must be sealed with PROMASTOP COATING and MG III, and to the casing coating after prior gluing.

4.4.3.8. Particular elements of the valve installation must be glued with PROMAT K84 and screwed at the spacing of ~150 mm with screws 6.0 x 90 for plaster boards. 4.4.3.9. The insulated duct with the valve must be suspended at sites marked in Fig. 8a and 8b. Mineral wool Promatect L500 Fire valve Duct Suspension axis drive Suspension axis Fire barrier RK370 Type V370 Fig. 8a Promatect L500 Mineral wool min. 100 kg/m^3 Promatect L500 Fire valve Fire barrier Duct Suspension axis drive Suspension axis suspension Fire barrier Promatect L or plaster boards Fig. 8b 4.4.4. Valves installed on the surface of fire barrier. 4.4.4.1. Valves installation in this manner is a special case of remote valve installation, where value (X) of valve distance amounts to 0 mm, acc. to Fig. 8c and 8d. 4.4.4.2. Further procedure is analogical as in the case of section 4.4.2. except for number of valve suspensions. Mineral wool min. 100 kg/m^3 Duct Suspension axis Promatect L500 drive Fire valve Duct Suspension axis Mineral wool min. 100 kg/m^3 Promatect L500 Drive board Fire valve Fire barrier Fire barrier Fig. 8c Fig. 8d

4.5. DIAGRAMS OF ELECTRICAL CONNECTIONS OF FIRE VALVES. NORMAL STATE Control cabinet transformer Control cabinet Thermal el. Thermal el. solenoid solenoid Limit switch Limit switch FIRE SIGNALLING FROM SAP Thermal el. Control cabinet Power shortage Thermal el. transformer Control cabinet Power shortage solenoid solenoid Limit switch Limit switch ACTUATION OF THERMAL ELEMENT Control cabinet transformer Control cabinet Thermal el. Thermal el. solenoid solenoid Limit switch Limit switch Control diagram for valve with solenoid

ER (BLF) ER (BLF-T) Thermal element Control cabinet 24/48V DC or 230V AC Control cabinet 24/48V DC or 230V AC actuator actuator Conceptual diagram of electric installations for valves in the ER version with BLF actuator 4.6. EXEMPLARY SYSTEMS FOR FIRE VALVE CONNECTIONS IN SIGNALLING AND CONTROL SYSTEMS If, in the rooms ventilated, there is fire alarm installation, it is recommended that the actuator of the ER fire valve and the solenoid of MR fire valve should be powered via contact controlled directly from the fire safety unit. 4.6.1. Diagram of connections of the actuator of fire valve version ER. Legend for connections of control and signalling circuits: Control cabinet 24/48V DC or 230V AC Signalling of fire valve closure circuit a" (lamp, switch, sound alarm, switching off the ventilation). Signalling of fire valve opening circuit c" (lamp, switch, ventilation switched on). Control of fire valve opening (lamp) actuator In the case of connecting BLF24-ST or BF24-ST actuators via BKN230-24, connect clamps 1 and 3 of thermal element with limit switch to clamps 1 and 2 on the BKN230-24 device (in place of the keeper, which must be removed). 4.6.2. Diagram of connections of solenoid of fire valve version MR for installation powered with 24/48V DC thermal el. solenoid Limit switch conductor 1 Control cabinet 24/48V DC or 230V AC Legend for connections of control and signalling circuits: Signalling of safety thermal element actuation circuit a" (lamp, switch, sound alarm, switching off the ventilation). Signalling of fire valve closure circuit b" (lamp, switch, sound alarm, switching off the ventilation). Signalling of fire valve opening circuit c" (lamp, switch, ventilation switched on). Solenoid conductor in the MR version must be connected to closed contact in the electrical thermal element.

4.6.3. Diagram of connections of the limit switch of fire valve Limit switch c. 3 c. 2 conductor 1 Control cabinet 24/48V DC or 230V AC 5. PRINCIPLES FOR FIRE VALVES MAINTENANCE Legend for connections of control and signalling circuits: Signalling fire calve closure: connection a signals valve closure (depending on the control system, lamp is on, sound signal is on, ventilation is switched off). Signalling of fire valve opening connection b" (lamp or sound alarm is off, ventilation switched on). CAUTION: Before performing activities related to electrical connections or replacement of elements in the valves powered with voltage higher than safe, disconnect power supply. 5.1. Replacement of mechanical thermal element or melting fuse. Mechanical glass thermal element for valves type RK370 and V370 Fig. to section 5.1. Mechanical soldered thermal element for valves type RK370 &V370 After unscrewing two M5 screws (item 9 Fig. to section 5.1.) (optionally nut M6), remove the entire mechanical thermal element from the valve, item 1, together with plate, item 2. In order to replace the thermal element (item 3), unscrew the nut (item 4), press the spring (item 7) with the element, and after the element item 1 is bent to the side, remove the glass element (item 3) from the steel clip (item 6), or remove the protection (item 10) and remove the soldered element from the shank (item 11). After placing the glass element in the socket in the brass element (item 5), so that the elongated part of the insert is inside the element, or after placement of soldered element on the shank, assemble the thermal element in reverse order, not forgetting to place a sealing cushion (item 8) under the thermal element plate. The glass element must be set precisely in the socket and opening of the elements (item 6). The shank of the thermal element (item 11) must block the protrusion of the wired catch of the lever from the thermal element.

5.2. Replacement of electrical thermal element. Electrical glass thermal element for valves type RK370M Electrical soldered thermal element for valves type RK370M Fig. to section 5.2. Disconnect the trigger from electric installation and disconnect connections of the trigger at the valve. After unscrewing two M5 screws (item 4 Fig. to section 5.3.) (optionally nut M6), remove the entire electrical thermal element from the valve with the plate (item 1), as presented in the drawing below. In order to replace the thermal element (item 2), unscrew the brass cylinder or nut (item 3), place new thermal element in the opening or onto the shank (as presented in the drawing), and again screw on the cylinder on the micro-switch shank (item 5). Assemble the whole to the valve in the reverse order, not forgetting to place the sealing cushion (item 6). Connect the trigger to the electric installation and open the valve. 5.3. Replacement of the spring. Before replacing the spring, unscrew the screw (Fig. to section 5.4., item 3) fixing the manual lever on the drive shaft, set the valve partition in the closed position so that the spring tension is minimum (lever item 1 resting on the limiter, item 4), and next remove lever (item 1) and damaged spring (item 2). Place the spring on the middle opening in the manual lever and place the whole on drive shaft, item 5. During placement on drive shaft, manual lever must be set vertically, namely it should rest on the limiter on the drive board. Set the manual lever in the appropriate distance from the drive board and screw the screw fixing the lever on the drive shaft. Hook the spring on one of the catches (item 6) on the drive board, and assess the strength with which the partition is closed. If necessary, change the spring hooking on the drive board or manual lever, and again assess correct closing of the valve. Repeat these activities until your assessment is positive. Correct valve closure occurs where valve partition freely closes, and the manual lever meets resistance on the drive board without excess noise. After replacement of the manual lever, depending on valve version, reassemble the previously removed elements, and check for their correct operation. Fig. to s.5.3.

6. PERIODICAL MAINTENANCE The need for and the required frequency of maintenance results from analogical requirements of the installation including RK370 or V370 valves. If no specific requirements have been defined for periodical maintenance of the installation, or if the periods between particular checks are longer than six months, check the RK370 or V370 valves at least once every six months. This is the responsibility of the Facility Owner. Periodical maintenance of RK370 or V370 valves comprises the Close assessment of their physical condition, and correct operation using the Inspection Document at the end of this Documentation. Open It is also recommended to assess the condition of the device using the Inspection Document after the end of assembly works and launch of the installation including the RK370 or V370 valves. In order to check correct valve operation, do the following: Open Closed Fig. 13 6.1. HO and HE versions release manual lever (item 1 Fig. 13) from the catch (item 2 Fig. 13) keeping the valve open. After releasing the lever, it moves freely from the open to closed position, closing the valve partition. Next, manually open the valve, and hook the manual lever (item 1) at the element (item 2). For valves in HE version, during the test, observe correct signalling by micro-switch (item 3) of cut-off partition's position. If irregularities are found, set the micro-switch actuation point (item 3). 6.2. MR version disconnect power supply to the solenoid. The partition should move to the closed position. Then disconnect the solenoid s power supply. In MR version, manually turn the manual lever, leading to contact of the keeper and the solenoid. After the partition achieves open position, the manual lever will be blocked by resistance of the keeper against solenoid coil, and valve partition will remain open, kept by the solenoid. During the test, in both cases, observe correct signalling by microswitch of cut-off partition's position. In the event of problems with sustaining the partition, check for cleanliness of keeper and solenoid surface. 6.3. ER version disconnect power supply to the BELIMO actuator. The valve must close (signalled by the steel arrow installed at the actuator axle at 0 position of the scale (Fig. 15 item 1). Fig. 15 Operation of the air-handling installation with dysfunctional fire valves bears the high risk of their non-performance in the event of a fire, and makes the installation user liable.

7. LIST OF SPARE PARTS 1. BELIMO actuators types acc. to table in section 8.1. 2. Solenoid type acc. to section 8.2. 3. Rectifier transformer AC 230 / DC 24 4. Mechanical thermal element. 5. Electrical thermal element. 6. ESTI thermal element. 7. Soldered thermal element for mechanical trigger. 8. Soldered thermal element for electrical trigger. 9. Micro-switch Z-15GW4. 10. Closing spring wire 03, 03.5 and 0.4 mm. The valves do not feature wearing or recommended parts. 8. TECHNICAL DATA OF ACTUATORS AND SOLENOIDS 8.1. Technical data of BELIMO actuators. Actuator type with release spring Parameters BF24(-ST) Supply voltage Power consumption While opening While keeping open position BFT24 BF24-T 24V~ ±20%, 50/60Hz BF230 BFT230 BF230-T BLF24(-ST) BLF24-T-(-ST) AC 230 V 50/60Hz AC 24V, 50/60Hz BLF 230 BLF 230-T AC 230 V 50/60Hz 7 W 8 W 5 W 5 W 7 W 2 W 3 W 2.5 W 3 W 2 W BF 24TL-T-ST AC 24 V 50/60Hz DC 24V Rated power 10VA 12.5VA 7 VA 7 VA 10 VA Protection class III II III II III Protection level IP42 IP42 IP54 IP54 IP54 Auxiliary 2xEPU 6(3)A, 2xEPU 6(3)A, 2xSPDT 6(1.5)A, switch 250V 250V AC250V 2xSPDT 6(1.5)A, AC 250V Connection point 5, 80 5, 80 5, 80 5, 80 Movement time Actuator 140s ~16s 140s ~40 75s (0 4Nm) ~40 75s (opening) (@ tamb=20 C) ~16s ~20s at -20 (0+4Nm) Spring (@ tamb=20 o C) +50 o C; ~20s at -20 max 60s at +50 o C +50 o C; max 60s at +50 o C (closing) Position indicator Ambient temperature Noise intensity Mechanical with indicator Mechanical with indicator Mechanical with indicator Mechanical with indicator Socket to connect BKN230-24LON or BKN230-24MP ~140 s ~16 s at ambient temperature 20 o C; Mechanical with indicator -30 +50 o C -30 +50 o C -30 +50 o C -30 +50 o C -30 +50 o C Motor max.45db(a); Spring ~62dB(A) Durability min. 60 000 settings Maintenance Maintenancefree 8.2. Technical data of solenoids Motor max. 45dB(A); Spring ~62dB(A) min. 60 000 Motor max.45db(a); spring ~62dB(A) Motor max.45db(a); Spring ~62dB(A) min. 60 000 Motor max.45db(a); Spring ~62dB(A) min. 60 000 min. 60 000 settings settings settings settings Maintenance-free Maintenance-free Maintenance-free Maintenancefree Types holding when power supply is on (MR) Type 5.80.15 P.5.12.44 Supply voltage 24 V DC 24 V DC Holding force 120 N 200 N

9. FIRE VALVE INSPECTION DOCUMENT To be downloaded from www.frapol.com.pl Parameter / Function 1. Valve checked 2. Date of check 3. Optical valve condition (mechanical damage, openings, rust, dents) 4. Valve cleanliness - cleaning if necessary 5. Assessment of the condition of conductors powering the actuator, solenoid, and limit switches 6. Assessment of the condition of the partition and the seals expansion and ventilation seal 7. Check of correct closing of valve partition 8. Physical check of valve response to OPEN / CLOSE control signals 9. Check of return signal from the valve (limit switches) 10. Check of functioning acc. to fire scenario 11. Leaving the valve in the normal operating condition Result Performed by: