Installation Instructions

Similar documents
Installation Instructions

ELB ELB

ELB ES. Product Installation Instructions

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

3M Cold Shrink QT-III Silicone Rubber Termination

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

Cold Shrink QS T Trifurcating Transition Splice Kit

3M Cold Shrink Splice Kit QS-III 5536A

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

QT-III Cold Shrink Silicone Rubber

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

(K),(M),(P)489TB/G Up to 42 kv

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

(K),(M)430TB/G Up to 36 kv

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

Loadbreak Apparatus Connectors

Installation Instructions LINK---C

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

Assembly Instruction. EL OCHITO BLUE CONTACTS SuperSpeed USB TYPE I: PIN /SKT CABLE:

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

High Voltage Joints and Terminations up to 72,5 kv 145 kv

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

INSTALLATION PRODUCTION TESTS

PRODUCT SHEET. Elastimold advanced connection system (shear bolt)

Assembly Instruction EL OCHITO WHITE CONTACTS 1000BASE-T/10GBASE-T TYPE I: PIN /SKT CABLE: S/FTP

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

PRODUCT BROCHURE. Elastimold advanced connection system (shear bolt)

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

600 A 35 kv class BT-TAP deadbreak connector

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

25 kv class fused loadbreak elbow connector

Rejuvenation Instructions

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series


QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

600 A 25 kv class BT-TAP deadbreak connector

3M Cold Shrink Splice Kits, QS T Series

HVS S 15kV Class

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

Underground Bus Bar Distribution System 03 SEP 13 Rev B

Installation Instructions 15/25/35kV, 600/900 AMPERE

INSTALLATION INSTRUCTION PEM1093ENG ENGLISH

Application Specification Circular Plastic Connector (CPC) Series 45 System 05 AUG 14 Rev D

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

copper stud. If a 900 A rating is desired, specify a C as the 8th digit when determining your part number (See Table 3, page 3.)

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts

600A Deadbreak Elbow. K656LR Elbow Connector (with Test Point) Features:

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

600 A 35 kv class separable splices

JUL 14 Rev B

Installation instruction PEM1150ENG

UNSIGNED HARDCOPY NOT CONTROLLED

INSTALLATION INSTRUCTION PEM1367ENG ENGLISH

600 A 15 kv class T-OP II deadbreak connector

Product Number

Effective November 2016 Supersedes February 2012 (S )

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

POWER TRIPLE LOCK* Connector System

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

Coaxial Snap-Lock Connectors

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

FAKRA Automated In-Line Connector System

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

AUXILIARY BATTERY BOX INSTALLATION INSTRUCTIONS

LCT Shielded Primary UD EPR LCT Shielded Primary UD EPR Cable

Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV

600 A 35 kv class deadbreak accessories, tools, and replacement parts

INSTALLATION INSTRUCTION

FASTON* High Temperature Tab Terminals

Transcription:

517 Lyons Ave, Irvington, NJ 07111 Phone: 973-371-1771 Fax: 973-371-4304 Installation Instructions Deadbreak Elbow Applicable Current Ratings 600A (Aluminum) 900A (Copper) Applicable Catalog Prefix 35kV Class 63LCN- 63LCT- 73LCN- 73LCT- 93LCN- 93LCT- For Use With the Following Cable Types Jacketed Concentric Neutral (JCN) Longitudinally Corrugated Neutral (LC) Tape Shield Neutral Sheet 1 of 1

WAR WARNING WARNING System must be de-energized during installation or future operation of this product or its components. Do not touch or move energized connectors or components by hand. Excess distortion of the assembled connector may result in its failure. Failure to follow these instructions will result in damage to the connector and serious or fatal injury. This product should only be installed and/or operated by trained personnel in accordance with normal and safe work procedures. Variations in equipment or configuration or work procedures may not be covered in these instructions. Please contact Richards Manufacturing for any additional questions. KIT CONTENTS WARNING WARNING KIT CONTENTS Standard kits may include the following. Custom kits may vary. Check package contents to be sure they are complete, undamaged,and properly sized for the application. 4 3 1 0 19 18 17 16 15 14 13 T R Deadbreak Elbow Housing KIT CONTENTS P N KIT CONTENTS M Insulating Plug & Cap P635HIP P935HIP L Cable Adapter & Assembly Aid P635CA-W K J H 4 3 1 0 19 18 17 16 15 14 13 1 11 10 9 8 7 6 5 4 3 1 T T R R P P N N M M G L L K K F J J H H G G F F E E E D D Silicone Lubricant P6SL1 C B A D 4 3 1 0 19 18 Stud P635HIP-STUD P935HIP-STUD 17 16 15 14 13 1 11 C B UNLESS OTHERWISE SPECIFIED: FINISH: DIMENSIONS ARE IN MILLIMETERS SURFACE FINISH: Electro-Tin Plate TOLERANCES: LINEAR: ANGULAR: SIGNATURE NAME DEBURR AND BREAK SHARP EDGES DATE TITLE: CHK'D MFG MATERIAL: Q.A 8 7 6 5 4 WEIGHT: 0.06 35 kv Aluminum Stud DWG NO. 011-T3 or 6061-T6 9 REVISION 0.000-0.0004" Thick, Matte Finish DRAWN APPV'D 10 DO NOT SCALE DRAWING 3 CS-P635HIP-STUD SCALE:5:1 SHEET 1 OF 1 A A0 1 OR Shear Bolt Lug P6ALR-X Compression Lug P6AL-X P7ALCU-X P9CU-X C B Sheet of 1 1 11

TIP: Use To-Scale Cable Cutback Template as aid to prepare cable. NOTE: Certain items used, such as PVC tape, may not be included. 1 A. Straighten and train cable end. Cable should be free to move approximately " in either direction. B. Cut cable to dimensions shown. C. Clean cable jacket approximately 4" from end of cable. Positioning Cable 1 3 /4 Bushing or Mating Part A. Remove cable jacket to dimensions shown. B. Abrade area as shown. NOTE: Cable Shielding may be wires, straps, metallic tape, or LC tape. (Wires shown as example) Exposing Cable Shielding 1 / REF 1 13 3 /4 Cable Jacket Abraded area 3 A. Apply jacket mastic at position shown by stretching and wrapping with light tension fully around outer jacket. Applying Jacket Mastic 1 Cable Jacket Jacket Mastic 4 For Strap/Wire Shielded Cable Exposing Cable Semi-Conductive Shield For Metallic Tape/LC Shielded Cable A. Fold back strap/wire shields and press firmly into jacket mastic. B. Secure strap/wire shields to cable with PVC tape as shown. A. Wrap PVC tape at dimension shown to secure metallic shield. B. Remove metallic shield up to PVC tape. PVC Tape Semi-Conductive Shield 1 1 / 10 11 3 /4 1 / Jacket Mastic under strap/wire shield Jacket Mastic PVC Tape Metallic Shield Semi-Conductive Shield Sheet 3 of 1

5 For Strap/Wire Shielded Cable Exposing Cable Insulation For Metallic Tape/LC Shielded Cable A. Remove semi-conductive shield to dimensions shown. B. Place PVC tape marker at dimension shown. A. Remove semi-conductive shield to dimensions shown. B. Check that tape from previous step is 1 from the edge of the semiconductive shield as it will serve as a marker. WARNING: Do not nick or cut the cable insulation. WARNING: Do not nick or cut the cable insulation. 1 10 9 31 /4 / 1 10 9 3 /4 1 / Semi-Conductive Shield PVC Tape (marker) Cable Insulation PVC Tape (marker) Semi-Conductive Shield Cable Insulation 6 For Strap/ Wire Shielded Cable Proceed to next step For Metallic Tape/LC Shielded A. Position copper braid so that solder block rests on the jacket mastic. B. Wrap copper braid around metallic shield as shown. C. Wrap constant force spring over wrapped portion of copper braid. D. Wrap layers of PVC tape over constant force spring. E. Press solder block into jacket mastic. F. Secure braid to cable with PVC Tape. CHECK: Confirm that solder block is aligned with jacket mastic. Preparing Metallic Shield Jacket Mastic Cable Jacket Constant Force Spring Copper Braid around Tape Shield Metallic Shield Solder Block Tape Marker PVC Tape Securing PVC Tape 7 A. Remove cable insulation. Refer to instructions provided with lug for insulation cutback dimension. Cutback dimension should not exceed 4 3 /8". Exposing Conductor Insulation Cutback WARNING: Do not nick or cut the conductor strands. Cable Insulation Cable Conductor NOTE: Confirm all dimensions with To-Scale Cable Cutback Template before proceeding. Sheet 4 of 1

8 Parking Jacket Seal Tube A. Slide jacket seal tube onto cable as shown. If using a cold shrink tube, orient pull tab facing away from cable end. For Strap/Wire Shielded Cable Jacket Seal Tube Pull Tab For Metallic Tape/LC Shielded Cable Jacket Seal Tube Pull Tab 9 Installing Cable Adapter A. Slide cable adapter assembly aid up to insulation. B. Clean insulation with approved cleaning wipes by wiping in direction of semi-conductive shield. C. Apply silicone lubricant to cable insulation, cable adapter assembly aid, and inside of cable adapter as shown. D. Slide cable adapter onto cable until the cable adapter sits flush with the leading edge of the tape marker as shown. Tape Marker (From Step 5) Cable Adapter Assembly Aid Push Slide up to here Lubricate Lubricate (Internal Cavity) Push Cable Adapter E. Remove cable adapter assembly aid. F. Confirm cable adapter is positioned as shown below. Insulation may extend beyond adapter as long as both checks below are confirmed. Tape Marker (From Step 5) Cable Adapter Remove Cable adapter edge 4 7 /16 to 5 1 /8 CHECK: Confirm that edge of tape marker is flush with end of cable adapter as shown. CHECK: Confirm that dimension from end of conductor to cable adapter edge satisfies criteria shown above. Sheet 5 of 1

10 Installing Lug A. Clean conductor of any debris. For aluminum conductor, wire brush and immediately insert lug onto conductor. Slide lug until the conductor is fully seated within the lug barrel. B. Rotate lug so that spade is parallel to the contact face of the bus as shown. C. For Shear Bolt Connectors: Install lug using separate instructions provided with lug. For Crimp Connectors: Select correct tool and die using crimp chart supplied with lug. Crimp lug (min. number indicated in crimp chart) starting just below knurl line adjacent to pad. Carefully wipe any excess inhibitor from lug and cable insulation. Lug Ensure surfaces are parallel before installing lug Bushing Confirm that the distance from the end of the lug to the cable adapter after installing is as shown. Otherwise redo assembly. Cable Adapter Locate first crimp here Lug Knurl Line 7 1 / MAX Sheet 6 of 1

11 Installing Elbow A. Clean and lubricate (using supplied or approved silicone grease) entire surface of cable adapter and cable entrance of elbow. B. Without moving cable adapter, push elbow onto cable adapter and slide until lug is fully seated inside elbow. Confirm cable adapter has not shifted by observing tape marker. Cable adapter and tape marker should be aligned as they were in the "Installing Cable Adapter" step. Elbow Interface WARNING: Confirm cable adapter does not shift from proper positioning during installation of elbow housing. WARNING: Confirm the lug has fully seated into housing as shown. NOTE: If equipped with a capacitive test point, ensure test point is facing outwards for accessibility. Lug Hole Elbow Housing Clean and Lubricate (Internal Cavity) Lug Clean and Lubricate Ensure adapter does not shift during installation of Elbow Housing Sheet 7 of 1

1 Mounting Elbow A. Hand-tighten stud into the appropriate mating part or bushing. B. Clean and lubricate (using supplied or approved silicone grease) elbow interface and mating part interface as shown. C. Push elbow onto mating part, lining up the hole in the lug with the stud on the mating part. Clean and Lubricate (Internal Cavity) Mounting Part or Bushing Clean and Lubricate Stud Deadbreak Elbow Housing Sheet 8 of 1

13 A. Clean and lubricate (using supplied or approved silicone grease) the remaining elbow interface and mating part interface as shown. Installing Mating Component WARNING: Ensure stud is through lug hole as shown before tightening assembly. Clean and Lubricate (Internal Cavity) B. Insert mating part, engage threads, and hand-tighten. C. For Insulating Plugs: Engage hex nut and tighten to 50-60 ft lbs using appropriate tool. Lubricate interior of insulating plug cap and push on to install. For all other mating parts: Install mating part per manufacturer instructions. 1 Hex Nut Threaded stud through lug hole Clean and Lubricate Lubricate (Internal Cavity) Sheet 9 of 1

14 For Strap/Wire Shielded Cable Applying Sealing Mastic For Metallic Tape/LC Shielded Cable A. Apply sealing mastic over previously applied mastic and on top of folded back neutral wires by stretching and wrapping with light tension. B. Apply sealing mastic by stretching and wrapping with light tension fully around nose of cable adapter for a width of 1 as shown below. A. Apply sealing mastic over previously applied mastic and on top of solder block by stretching and wrapping with light tension. B. Apply sealing mastic by stretching and wrapping with light tension fully around nose of cable adapter for a width of 1 as shown below. Shield Wires 1 Copper Braid 1 Sealing Mastic (Step B) Sealing Mastic (Step A) Sealing Mastic (Step B) Sealing Mastic (Step A) 15 Applying Jacket Seal Tube A. Beginning with the side closer to the cable adapter, deploy the jacket seal in area shown below ensuring both mastics are completely covered. For Strap/Wire Shielded Cable Mastic Mastic Jacket Seal Tube For Metallic Tape/LC Shielded Cable Mastic Mastic Jacket Seal Tube Sheet 10 of 1

16 For Strap/Wire Shielded Cable Installing Drain Wire and Grounding Metallic Shield A. Secure neutrals with binding wire or zip tie 1" from jacket seal tube. B. Insert one end of a piece of wire (#14 AWG copper or larger) through one of the available grounding eyes and twist to make a small loop. Be sure not to damage grounding eye. C. Connect other end of wire to shield wires. D. Ground the cable shield according to appropriate/approved practice. Binding wire or zip tie 1 To Ground Ground Eye Drain Wire For Metallic Tape/LC Shielded A. Secure copper braid with binding wire or zip tie 1" from jacket seal tube. B. Insert one end of a piece of wire (#14 AWG copper or larger) through one of the available grounding eyes and twist to make a small loop. Be sure not to damage grounding eye. C. Connect other end of wire to copper braid. D. Ground the cable shield according to appropriate/approved practice. Binding wire or zip tie 1 To Ground Ground Eye Drain Wire Installation Complete Sheet 11 of 1

Sheet 1 of 1