Compact System NRGS 11-2 NRGS Original Installation Instructions English

Similar documents
Level Electrode NRG NRG NRG NRG

Conductivity Switch LRGS Original Installation Instructions English

NRG 16-12, NRG 17-12, NRG 19-12

Installation Instructions Spector compact Conductivity Transmitter System LRGT 16-1

Condensate Drain Valve AK 45. Original Installation Instructions English

BA 46 BA 46-ASME BA 47 BA 47-ASME BAE BAE ASME BAE BAE ASME

PRS 9. Installation Instructions Cycling Timer PRS 9. A Siebe Group Product 1

UNA 13 UNA 15 UNA 15 Stainless Steel Design. Installation Instructions Steam Traps UNA 13, UNA 15

NRG Installation Instructions Level Probe Type NRG A Siebe Group Product 1

GESTRA. GESTRA Steam Systems MK 25/2 MK 25/2S. Installation Instructions Steam Traps MK 25..., DN 40-50

UNA 23 UNA 25 UNA 26 UNA 27

Mounting and Operating Instructions EB 5868/5869 EN

Electronic Ignition Module

PURE SINE WAVE DC TO AC POWER INVERTER

Operating Instructions (Translation)

Operating Instructions Mechanical Temperature Switches ML1H,MT1H,L2H,T2H,L1X/L1X-EX,T1X/T1X-EX,T2X/T2X-EX

BA 46 BA 46-ASME BA 47 BA 47-ASME BAE BAE ASME BAE BAE ASME

UNA 26h Stainless Steel Design. Installation Instructions Stainless Steel Steam Trap UNA 26h

Installation and Operating Instructions Magnetic Vibrator MR 1

Electronic Ignition Equipment

Installation and Operating Instructions Electric Vibrators HV/VFL Series

Instruction Manual. Sewage lifting station compli 300

DIAMOND POINT VIBRATING PROBES

Mounting and Operating instructions

Installation and Operational Instructions for ROBATIC -clutch Types _.0 and _.0 Sizes 3 7

Installation and Operating Instructions for ROBA-stop -Positioning Brake Type 80_.41_._ Sizes 3 11

Switching DC Power Supply

PA 46 PA 47 MPA 46 MPA 47

LKS 160 FOR AIR DAMPERS ON MULTI-STAGE AND MODULATING BURNERS

GESTRA. GESTRA Steam Systems ZK 313 ASME. Installation Instructions Control Valve ZK 313 ASME

Operating instructions Rotary actuators M135 M140 M150 M180. June 2012 / / EN

Type 3761 Pneumatic or Electropneumatic Positioner for Rotary Actuators. Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Level Sensor with G1/2" Thread Hygienic

Level Sensor with M12 Thread Hygienic

Operating and Installation Instructions Diaphragm Vacuum Pumps and Compressors

NEOTECHA NTB-NTC BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies

standards based cylinder DNCI Operating instructions e [ ]

User Manual Rittal PMC UPS 6kVA

Pressure chlorine changeover unit C 7520

Electromagnetic Flow Monitor magphant

Holtumsweg 13, D Weeze, Tel /9134-0, Fax /1444

Installation and Operational Instructions for ROBATIC -clutch Type and Type Sizes 3 9

Ex m Solenoid Operator Type 0519

BCV30 DN20 - Blowdown Control Valve Installation and Maintenance Instructions

These operating instructions apply for: NCX 380 NCZ 300 NCX 480 NCZ 370 NCX 580 L NCZ 480 NCX 660 K NCZ 560 NCZ 660 NCZ 800

SITRANS P measuring instruments for pressure

Operating instructions

Actuators for air dampers and control valves of oil burners

Operating Instructions

UZK12.261, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE BATTERY MODULE 12V, 26AH 1/10.

Operation & Maintenance Manual

These installation and maintenance instructions must be read in full and completely understood before the installation!

Solar Thermal. Grant Solar Pump Station Installation & Servicing Instructions

Pipe surface resistance thermometer, for clamping Model TR57-M, miniature design

VEM motors Thurm GmbH

Operating Instructions

Supplementary instructions. Air cooling - FIBERTRAC 31 with Conduit tube connection. Active air cooling system for radiation-based sensors

UNA 23 UNA 25 UNA 26 UNA 27

P U L S A R point 210

NEOTECHA NEOSEAL BUTTERFLY VALVE INSTALLATION AND MAINTENANCE INSTRUCTIONS

Differential Pressure Transmitter

Connection Accessories for small Burner Controls

MT50 & MT150 Electrical Multi-turn Valve Actuators

Pneumatic or Electropneumatic Positioner for Rotary Actuators Type Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Softstarter SAS SAS 11PUST, 22PUST Assembly- and Commissioning Instructions

Installation Instructions (Translation) Marking. Description. Danger, warning and note symbols. Technical data. ANTARES ExtSet.

Supplementary instructions. Air cooling - FIBERTRAC 31. Active air cooling system for radiation-based sensors. Document ID: 50339

Assembly and operating Instructions RA 60 / FA 60

Operating Instructions

Operating Instructions Garlock Butterfly Valves DN : mm / 2-24

FLENDER ARPEX Plate packs with close-fitting bolt connection. ARW-4 Sizes to Assembly instructions An 4239 en 12/2015.

Angle seat valve with piston actuator VZXA-...-K

FLUDEX - thermal switching equipment. Operating instructions BA en 04/2012. FLENDER couplings

Operating Instructions CYR52

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil

Solenoid Operator 0516 / 1216

OPERATING INSTRUCTIONS

Operating Instructions. VEGASWING 61, 63 with oscillator SW E60N (EX)

T R A N S L A T I O N Declaration of Conformity as per Directive 2014/68/EU

WATERFLUX 3070 Quick Start

Electromotoric Actuators

D58 Series Brake Instructions

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies

Appendix: Safety and application notes for... 15

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies

Mounting and Operating Instructions EB 8039 EN. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve

EN Operating manual. Motorised zone valve. Three-way, 22 mm & 28 mm 3PV2, 3PV8 & VRMH3

Thyristor power controller TE10A. Burst-firing Single-cycle Advanced Single-cycle

Actuators for air dampers and control valves of oil burners

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Pressure/vacuum switch (V)PE-1/8-...(-SW) PE-PK-...(-SW)

Series A Electric Linear Actuators

Float-operated condensate pump ARI Condensate pump (mechanical) Displacement: 16,5-20 litres. High temperature steel. Stainless steel.

ZB0050 / ZB0051 ZB0070 / ZB0071

Safety. Operating instructions Solenoid valve VGP DANGER. Contents WARNING CAUTION. Changes to edition Elster GmbH Edition 10.

Operating instructions Bedienungsanleitung Mode d emploi

EB EN. Type 3372 Electropneumatic Actuator. Translation of original instructions

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 07.15

Transcription:

Compact System NRGS 11-2 NRGS 16-2 EN English Original Installation Instructions 810366-05 1

Contents Important Notes Page Usage for the intended purpose...4 Safety note...4 LV (Low Voltage) Directive and EMC (Electromagnetic Compatibility)...4 ATEX (Atmosphère Explosible)...4 Note on the Declaration of Conformity / Declaration by the Manufacturer...4 Explanatory Notes Scope of supply...5 Function...5 Technical data NRGS 11-2, NRGS 16-2... 6-7 Name plate / marking...8 Dimensions...9 Design NRGS 11-2, NRGS 16-2...10 Key...12 Functional Elements NRGS 11-2, NRGS 16-2...11 Key...12 Installation NRGS 11-2, NRGS 16-2...13 Table Functions...13 Tools...14 Examples of installation...15 Key...16 2

Contents - continued - Electrical Connection Page NRGS 11-2, NRGS 16-2...17 Wiring diagram...17 Tools...18 Sensitivity of response Factory setting...19 Switch selection of response sensitivity...19 Tools...19 Commissioning Procedure Checking electrical connection...20 Switching on mains voltage...20 Checking assignation of switching functions...20 Checking low level (MIN) alarm...20 Operation Resetting low level (MIN) alarm...20 Operational malfunctions Fault finding list for troubleshooting...21 Exchanging the electronic insert, removing the compact system Exchanging the electronic insert...22 Removing and disposing of the compact system...22 3

Important Notes Usage for the intended purpose Use the compact system NRGS 11-2, NRGT 16-2 as water level controller / limiter in, e. g, steam boilers and (pressurised) hot water installations as well as in condensate and feedwater tanks. Safety note The equipment must only be installed and commissioned by qualified and competent staff. Retrofitting and maintenance work must only be performed by qualified staff who - through adequate training - have achieved a recognised level of competence. Danger When loosening the compact system steam or hot water might escape! This presents the risk of severe scalding all over the body! It is therefore essential not to dismantle the equipment unless the boiler pressure is verified to be 0 bar. The equipment becomes hot during operation. Risk of severe burns to hands and arms. Before carrying out installation and maintenance work make sure that the equipment is cold. The terminal strip of the NRGS 11-2, NRGS 16-2 is live during operation. This presents the danger of electric shock! Cut off power supply before mounting or removing the housing cover! Attention The name plate specifies the technical features of the equipment. Do not commission or operate any item of equipment that does not bear its specific name plate. LV (Low Voltage) Directive and EMC (Electromagnetic Compatibility) The equipment meets the requirements of the Low Voltage Directive 2014/35/EU and the EMC Directive 2014/30/EU. ATEX (Atmosphère Explosible) According to the European Directive 2014/34/EU the equipment must not be used in potentially explosive areas. Note on the Declaration of Conformity / Declaration by the Manufacturer For details on the conformity of our equipment according to the European Directives see our Declaration of Conformity or our Declaration of Manufacturer. The current Declaration of Conformity / Declaration of Manufacturer are available in the Internet under www.gestra./de/documents or can be requested from us. 4

Explanatory Notes Scope of supply NRGS 11-2 1 Compact system NRGS 11-2 1 Joint ring D 33 x 39 DIN 7603 1.4301, bright annealed 1 Installation manual NRGS 16-2 1 Compact system NRGS 16-2 1 Joint ring D 33 x 39 DIN 7603 1.4301, bright annealed 1 Installation manual Function The NRGS 11-2, NRGS 16-2 is a compact-type system consisting of a level electrode with four tips and an integrated level switching controller. For the correct functioning of the equipment the water must have a minimum conductivity of >0.5 µs/cm at 25 C. The length of the individual electrode tips determines the switchpoints for the respective water levels. The equipment monitors the water level by sensing whether the electrode tips are exposed or immersed and - by energizing or de-energizing the controller output contact - switches the feedwater pump on or off. The LED for pump is illuminated when the equipment switches the feedwater pump on. When the water level falls below the low level, the two MIN electrode tips are exposed and after the de-energizing delay the equipment switches the MIN output contacts. The safety circuit for the heating will be opened after the de-energizing delay and the two MIN LED are illuminated. A MIN alarm can be simulated by pressing the test button. The heating will be switched off and interlocked. To reset the interlock the MIN electrode tips must enter the water again and the button Reset must be pushed. Technical data NRGS 11-2, NRGS 16-2 Type approval no. TÜV WR/WB xx-392 Service pressure NRGS 11-2: 6 bar at 159 C, NRGS 16-2: 32 barg at 238 C Mechanical connection Screwed G 1, EN ISO 228-1 Materials Terminal box 3.2161 G AlSi8Cu3 Sheath 1.4301 X5 CrNi18-10 Screw-in body 1.4571 X6 CrNiMoTi17-12-2 Electrode tips 1.4571 X6 CrNiMoTi17-12-2 Insulation PTFE Spacer disc PTFE Electrode tips Lengths available: 500, 1000, 1500 mm 5

Technical Data - continued - NRGS 11-2, NRGS 16-2 - continued - Supply voltage 230 V +/ 10%, 50/60 Hz 115 V +/ 10%, 50/60 Hz 24 V +/ 10%, 50/60 Hz (optional) Power consumption 5 VA Fuse external 63 ma, slow-blow, at 230 V and 115 V, external 150 ma slow-blow at 24 V. internal thermal fuse T max = 102 C Response sensitivity (electrical conductivity of water at 25 C) >0.5...< 1000 µs/cm or >10...< 10 000 µs/cm (switch-selectable) Electrode voltage 10 V ss Output 2 volt-free relay contacts, 8 A 250 V AC / 30 V DC cos f = 1 De-energizing delay: 3 sec. (MIN alarm) 1 volt-free relay contact, 8 A 250 V AC / 30 V DC cos ϕ = 1 (e. g. feedwater pump ON). Provide inductive loads with RC combinations according to manufacturer s specification to ensure interference suppression. Indicators and adjustors 2 red LEDs for signalling Low water level, 1 green LED for Pump ON. 1 four-pole code switch for selecting the response sensitivity. 1 push button for testing the MIN (low-level) alarm. 1 Push button Reset Cable entry Cable gland with integral cable clamp M 16 (PG 9), M 20 (PG 16) Protection IP 65 to DIN EN 60529 Weight Approx. 0.8 kg Ambient temperature when system is switched on: 0... 70 C, during operation: -10... 70 C Transport temperature 20... +80 C (<100 hours), defrosting time of the de-energized equipment before it can be put into operation: 24 hours. Storage temperature 20... +70 C, defrosting time of the de-energized equipment before it can be put into operation: 24 hours. Relative humidity max. 95 %, no moisture condensation 6

Technical Data - continued - Name plate / marking Safety note Type approval no. Manufacturer XX Equipment designation Type of threaded end, material number Pressure rating Max. ambient temperature Protection Supply voltage Electrical specification Response sensitivity Disposal note CE Marking Operating note Fig. 1 7

Technical Data - continued - Dimensions 173 b = 70 42 7 0 9 8 40 1", DIN 228 N10 0.5 50 500, 1000, 1500 140 337.5 14 65-70 N8 Fig. 2 Fig. 3 8

Functional Elements NRGS 11-2, NRGS 16-2 a b c 5 6 1 2 3 4 Fig. 4 k j i g h f e d Fig. 5 5 6 9

Dimensions / Functional Elements - continued - Key 1 LED MIN alarm 2 LED MAX alarm 3 LED Pump ON 4 Code switch for Response sensititiy 5 Push button TEST 6 Push button RESET 7 Thermal insulation, provided on site, = 20 mm (outside of thermal insulation of steam boiler) 8 Seating surface 9 Joint ring D 33 x 39 DIN ISO 7603-1.4301, bright annealed 0 Screw-in thread G1, EN ISO 228-1 a Housing screws M4 b Cable gland PG 9 /PG 11 c Housing cover d Fixing screws for cover plate e Separating segment f Terminal strip g PE connection h Terminal strip for testing i Thermal fuse T max 102 C j Hexagon nut k Cover plate 10

Installation NRGS 11-2, NRGS 16-2 1. Determine required measuring lengths of electrode tips and enter data in table Functions. Fig. 3 2. Cut electrode tips 1, 2, 3 and 4 accordingly. The electrode tips 1 2 (low level limiter) must have the same length. 3. Deburr faces of electrode tips. 4. Strip off 50 mm of PTFE insulation from the ends of the electrode tips. 5. Check seating surfaces of threads or flange provided on vessel or boiler standpipe. Fig. 3. Place supplied joint ring 9 onto seating surface of the threaded standpipe or flange. Fig. 3 6. Use only the joint ring (D 33 x39 DIN 7603-1.4301, bright annealed) supplied with the electrode. 7. Apply a light smear of silicone grease to the electrode thread 0 (e. g. DOW Corning 111 Compound). 8. Screw compact system into threads or flange provided on vessel and tighten with a 41 mm open-end spanner. The torque required for tightening when cold is 140 Nm. Table Functions Function Function Electrode tip Length [mm] Low level alarm 1 Low level alarm 2 e. g. pump ON 3 e. g. pump OFF 4 Please enter data. Attention n Do not subject the electrode tips to shocks and do not bend the electrode tips when mounting. Use only the supplied joint ring D 33 x 39, form D, DIN 7603, made from 1.4301 (bright annealed). n Do not insulate screw-in thread with hemp or PTFE tape. n Do not lag electrode body above the hexagonal section. n Install compact system only in a vertical position! n The specified torques must be strictly observed. Note n For the approval of the boiler standpipe the relevant regulations must be considered. n Carry out the installation work in compliance with the installation examples given in this installation manual. Tools n Open-end spanner A. F. 41 mm n Hacksaw n Bolt cutter n Flat file, cut 2 11

Installation - continued - Examples of installation 1" DN 50 l m 1" DN 50 l m s o 20 20 n p q 1500 o 20 20 n p q 10 u 90 v 20 Fig. 6 Fig. 7 90 20 10 u v G ¾ 1" 1" l m l m DN 20 20 o n 20 20 DN 100 24.5 24.5 o 14 3000 p r s t Centre distance p 90 u w DN 20 20 u 20 12 Fig. 8 Fig. 9 DN 20

Installation - continued - Key l Flange PN 40, DN 50, DIN 2527 Flange PN 40, DN 100, DIN 2527 m For the approval of the boiler standpipe with connecting flange the relevant regulations must be considered. n Vent hole o High water HW p Electrode tip = 5 mm q Protection tube DN 80 r Protection tube DN 100 s Electrode distance 14 mm t Electrode distance 40 mm u Low water LW v Reducer DIN 2616, part 2 K K88. 9 x 3.2 242.4 x 2.6 W w Reducer DIN 2616, part 2 K K114. 3 x 3. 6 648.3 x 2.9 W 13

Electrical Connection NRGS 11-2, NRGS 16-2 For mains and control cables you can use multi-core flexible control cable (conductor size 0.75-1.5 mm²). 1. Unscrew housing screws a, remove housing cover c. Fig. 5 2. Unscrew union nuts of cable entries b. The terminal box can be turned through +/ 180. 3. Loosen hexagon nut j with 17 mm open-end spanner but do not remove! Fig. 6 4. Turn electrode terminal box into desired direction (+/ 180 ). 5. Tighten hexagon nut j slightly. 6. Remove terminal strips f from circuit board. 7. Connect terminal strip according to wiring diagram, establish PE connection g. 8. Plug in terminal strips f. 9. Install cable entry b. 10. Put housing cover c in place, insert and fasten housing screws a. Wiring diagram S1 Disconnector F1 Fuse Fig. 10 14

Electrical Connection - continued - Attention n The following relocations of cables with basic insulation are not permissible: Mains and control cables in low voltage areas. n To prevent the welding together of contacts provide an external slow-blow fuse T 2.5 A for the output contacts. n Provide inductive loads with RC combinations according to manufacturer s specification to ensure interference suppression. n Provide an external slow-blow fuse for the compact system: 63 ma for 230 V and 115 V or 150 ma for 24 V. n Install an easily accessible disconnecting switch for the compact system in the close proximity of the equipment (EN 61010-1). n Mark respective switch as disconnecting device for the compact system. Tools n Screwdriver for cross head screws, size 1 n Screwdriver for slotted screws, size 2.5, completely insulated according to VDE 0680 n Open-end spanner 17 mm A. F. 15

Sensitivity of response Factory settings The equipment features the following factory set default value: n Response sensitivity 10µS/cm 2 Switch selection of response sensitivity The response sensitivity can be switch selected between 0.5 µs/cm and 10 µs/cm by means of the code switch 4: 1. Unscrew housing screws a at the electrode terminal and remove cover c. Fig. 5, Fig. 6 2. Undo fixing screws d and remove cover plate k. Code switch 1 4 OFF Response sensitivity 0.5 µs/cm. Code switch 1 4 ON Response sensitivity 10 µs/cm. 3. Put cover plate k in place and fix it with screws d. 4. Put cover in place c and fasten housing screws a. Attention n Do not damage the electronic components when setting the code switch! n Do not use a graphitic pencil to set the code switch. Tools n Screwdriver for cross head screws, size 1 n Screwdriver for slotted screws, size 2.5, completely insulated according to VDE 0680 16

Commissioning Procedure Danger The terminal strip of the NRGS 11-2, NRGS 16-2 is live during operation. This presents the danger of electric shock! Cut off power supply before mounting or removing the housing cover! Checking electrical connection 1. Make sure that the system NRGS 11-2, NRGS 16-2 is wired in accordance with the wiring diagram. Fig. 11 2. Make sure that the supply voltage agrees with the specification on the name plate. Applying mains voltage 1. Apply supply voltage and check that all functions of the respective switchpoints work correctly. LEDs 1, 2, 3 are provided for visual check of switchpoints. Fig. 5 To check the correct functioning of the LEDs 1, 2, 3 remove the housing cover c. Fig. 4, Fig. 5 Checking assignation of switching functions 1. Check the switching function Low level (MIN) alarm of the electrode tips 1 and 2. For this test the level in the vessel must fall below the low level mark. The low level alarm must then be activated by the level switch after the de-energizing delay has elapsed. 2. Check the switching functions Pump ON and Pump OFF. See table Functions. Checking low level (MIN) alarm The function of the low level alarm can be simulated by pushing the button TEST 5. Fig. 5 Press button TEST. After the de-energizing delay a low level alarm must be raised. Operation Resetting low level alarm The heating will be switched off and interlocked. To reset the interlock the MIN electrode tips must enter the water again and the button Reset 6 must be pushed. Hold down the button Reset for at least 5 seconds. 17

Troubleshooting Fault finding list for troubleshooting Switchpoint Pump OFF exceeded no function Fault: Remedy: Fault: Remedy: Fault: Remedy: Fault: Remedy: Fault: Remedy: The electronic insert is defective. Replace the electronic insert with a new one. The screw-in body does not have earth connection to the vessel. Clean sealing surfaces and insert metal joint ring as shown in the drawing. Do not insulate compact system with hemp or PTFE tape! The compact system is not supplied with voltage. Switch on supply voltage. Wire equipment according to the wiring diagram. The thermal fuse has been triggered. The ambient temperature must not exceed 70 C. Replace thermal fuse. The electrical conductivity is too low. Set code switch 4 to 0.5 μs/cm. Level below switchpoint Low level no function Fault: Remedy: Fault: Remedy: Fault: Remedy: The vent hole in the protection tube does not exist, is obstructed or flooded. Check protection tube and, if necessary, provide vent hole. The isolating valves of the external measuring pot are closed. Open isolating valve. The electrode tips have earth contact. Check and, if necessary, change position of installation. Switchpoint has been reached incorrect function Fault: Remedy: The switching function has not been assigned correctly. Electrode tips have been cut to the wrong size. Identify electrode supply wires and reconnect the electronic insert accordingly. If faults occur that are not listed above or cannot be corrected, please contact our service centre or authorized agency in your country. 18

Exchanging the electronic insert, removing the compact system Danger When loosening the equipment steam or hot water might escape! This presents the risk of severe scalding all over the body! It is therefore essential not to dismantle the equipment unless the boiler pressure is verified to be 0 bar. The equipment becomes hot during operation. Touching the hot equipment presents the risk of severe burns to hands and arms. All installation, removal and maintenance work must only be performed when the system is cold. The terminal strips of the equipment are live during operation. This presents the danger of electric shock! Always cut off power supply to the equipment before mounting, removing or connecting the terminal strips! Exchanging the electronic insert Before exchanging the electronic insert take the compact system out of service and cut off its voltage supply. 1. Undo the housing screws a and remove the housing cover c. (Fig. 4, 5) 2. Pull the electrode wires off the terminal lugs on the electronic insert. Remove all terminal strips apart from terminal strip h. 3. Undo the PE connection g. 4. Unscrew the fixing screws of the electronic insert and take out the electronic insert. The electronic insert is available as spare part type NRV 1-45. 5. Install the new electronic insert in reverse order. Removing and disposing of the compact system Before removing the compact system take it out of service and cut off its voltage supply. 1. Undo the housing screws a and remove the housing cover c. (Fig. 5, 6) 2. Detach the connecting wires from the terminal strips and pull the wires out of the cable glands. 3. Undo the PE connection g. 4. Before removing the equipment make sure that is is neither hot nor under pressure. For the disposal of the equipment observe the pertinent legal regulations concerning waste disposal. Note When ordering spare parts or replacement equipment please state the material number indicated on the name plate. 19

Agencies all over the world: www.gestra.de GESTRA AG Münchener Straße 77 28215 Bremen Germany Telefon +49 421 3503-0 Telefax +49 421 3503-393 E-mail info@de.gestra.com Web www.gestra.de 810366-05/07-2017cm (808434-09) GESTRA AG Bremen Printed in Germany 20