I nstallation I nstruction Heatshrink Term ination For 3 Core Polym eric Cables 7.2 kv to 3 6 kv

Similar documents
Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV

Installation Instruction EPP /92

INSTALLATION INSTRUCTION

Installation Instruction EPP /02. Terminations for Screened Single Core Polymeric Insulated Cables up to 24 kv without Armour

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

HVS S 15kV Class

QT-III Cold Shrink Silicone Rubber

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

(K),(M),(P)489TB/G Up to 42 kv

BBIT/BPTM 5-35kV Class. High Voltage, Heat-shrinkable Bus Insulation Tubing

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

(K),(M)430TB/G Up to 36 kv

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

Cold Shrink QS T Trifurcating Transition Splice Kit

3M Cold Shrink QT-III Silicone Rubber Termination

INSTALLATION INSTRUCTION PEM1093ENG ENGLISH

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

INSTALLATION INSTRUCTION PEM1121ENG ENGLISH

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

H e a t s h r i n k P r o d u c t G u i d e

Heat-Shrink Indoor and Outdoor Termination SKSE

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

WRSS Wraparound Repair Sleeve Installation Instructions

MEDIUM VOLTAGE TERMINATIONS

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

MV TERMINATIONS. INDOOR SINGLE CORE TERMINATION - ELTI-1C for polymeric cables - Slip-on termination - Modular type APPLICATION STANDARDS

INSTALLATION INSTRUCTION PEM1367ENG ENGLISH

QTII (X) Series Silicone Rubber Cold Shrink Termination Kits

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

Heatshrink Terminations 7.2 to 36kV

Medium Voltage. Joints & Terminations

CS Fiber Optic Splice Case. Instruction

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

a Nexans company Catalogue 2008

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

HTP PTP/ PTJ Power Connection Kit for Pipes

Cold-shrinkable Silicone 12 kv - 24 kv - 36 kv

EMK-XP ElectroMelt Power Connection and End Seal Kit Installation Instructions

SRK02 Hard Wire Power Connection Kit. Installation, Operation and Maintenance Instructions

ELB ES. Product Installation Instructions

3M Cold Shrink Splice Kits, QS T Series

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

February Heat shrinkable tubing Insulate, identify and protect your cables

Installation instruction PEM1150ENG

High Voltage Joints and Terminations up to 72,5 kv 145 kv

Installation Instructions

C Power Connection Kit

Power & Control Cable IEC

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

3 TM Cold Applied Barrier Boot System

Power & Control Cable IEC

Heat Shrinkable Tubing

OFFSHORE WIND FEASIBILITY STUDY APPENDICES Appendix C.2 Subsea Cable Data Sheets

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

POWERHEAT TYPE AHT TERMINATION INSTRUCTIONS. Ref TK/AHT Issue C Date 16 August 1999

RG7H1R-1,8/3 26/45 kv RG7H1OR-1,8/3 18/30 kv

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

Nexans Network Solutions Div. Euromold

AutoMatrix Power Connection Kit. (1) This type 4X enclosure is intended for indoor or outdoor use primarily to. (2) May be required (see step 1).

QUICKTERM TERMINATION KIT

3 Reenterable Encapsulated PST Dome Closure

Installation Instructions

600/1000V, PVC Insulated Cables according to IEC

Product Number

WORLDWIDE GUARDWIRE ACCESSORIES INSTALLATION MANUAL PROVEN PERIMETER PROTECTION

Construction and Wiring Guidelines for Ergon Energy Substation Panels

BEST PRACTICE for the installation of medium voltage cable accessories

WARNING. This product uses High Brightness LEDs. Direct viewing of the SMD LEDs at close range should be avoided. Keep product away from children.

ELB ELB

HARNESS KIT 3 PORT ISOLATION MODULE LIGHT SYSTEM

power cable accessories

Tapecoat. Application Guideline

SLiC Aerial Terminal and Spiral End Seal for use with AMP* Quiet Front Terminal Blocks

HARNESS KIT 3 PORT ISOLATION MODULE LIGHT SYSTEM

CORDAFLEX(SMK) (N)SHTÖU Tough Rubber-Sheathed Reeling Cables

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)

HARNESS KIT 3 PORT ISOLATION MODULE LIGHT SYSTEM. w/projector-style VEHICLE LIGHTING. Parts List and Installation Instructions CAUTION

3M Electrical Markets Division. Rubber, Mastic and Specialty Tapes Application Guide. Choose the. Right Tape. for your. Electrical Project

ET-PWR-END-KIT Installation Instructions (part #JSR00)

HARNESS KIT 3-PORT ISOLATION MODULE LIGHT SYSTEM

HARNESS KIT 3 PORT ISOLATION MODULE LIGHT SYSTEM. Parts List and Installation Instructions CAUTION

a Nexans company Catalogue 2007

Data sheet chainflex CF240

Transcription:

I nstallation I nstruction Heatshrink Term ination For 3 Core Polym eric Cables 7.2 kv to 3 6 kv I NDOOR OUTDOOR ISSUE DATE: 05.01.11

General Fitting I nstructions * I t is highly recom m ended that a tool suitable for the rem oval of the sem i- conductive screen is used to provide a reliable discharge free term ination screen point * Use a propane gas torch w ith a soft flam e * Avoid a pencil like blue flam e w hich is caused by unregulated supply * Keep the flam e on the m ove to ensure even shrinkage of all the m aterials and also helps to reduce scorching * Ensure that all com ponents are kept clean and grease free during installation * Allow to cool before applying any m echanical strain Rem ove Outer Cable Sheath: VOLTAGE INDOOR L OUTDOOR L 7.2kV 650mm 650mm 12kV 650mm 650mm LENGTH OF LUG 17.5kV 650mm 650mm BARREL + 10% 24kV 650mm 800mm 36kV 800mm 800mm Table 1 Note:- Dimension L is a guide only. The actual length is determined by the overall geometry of the equipment. 3 Core Cable W ith Arm our If the cable is armoured, bonding of the armours must be completed using the appropriate armour earthing kit. A) For indoor terminations (cable end box) - Order kits Ref: SPS 180, SPS 193 * B) For outdoor terminations (pole top) - Please advise conductor size and voltage. 2 * SPS 180-16-95mm at 7.2 to 17.5kV 2 SPS 193-120-300mm at 7.2 to 17.5kV (For other voltages see selection chart in general catalogue) IMPORTANT NOTICE TO PURCHASER:- Sellers and Manufacturere s only obligation shall be to replace such quantity of the product proved to be defective. Neither the Seller nor Manufacturer shall be liable for any injury, loss or damage, direct or consequential, arising out of the use or inability to use the product. Before using, User shall determine the suitability of the product for his or her intended use and User assumes all risk and liability whatsoever in connection therewith.

Bushing centre L 100mm Bedding 100mm Armours 1. I nstallation Prepare the cable as shown. Note:- The L dimension should not be longer than the distance between bushing centres and base plate. De-grease and abrade the cable for a distance of 100mm below the outer sheath cut. Note:- User may wish to alter bedding and armour dimensions to suit the type of gland/earthing arrangement to be used. 30mm 2. Screen Preparation Copper W ire Screen Apply one layer of sealant tape around the outer cable sheath 30mm below the sheath cut. Bend back each screen wire and press them into the sealant tape. Apply another layer of tape over the bent back wires. SEALANT TAPE ROLL SPRINGS SEALANT TAPE COPPER TAPE SCREEN 100mm Copper Tape Screen Secure the earth braids to the copper tape screens so that the solder block is positioned upon the cable bedding. A turn of mastic tape should be applied beneath and on top of the solder block. If a constant force spring is used to connect the earth braids, the spring should preferably be positioned above the fingers of the breakout boot. COPPER BRAIDS

A Remove the copper tape screen to length A+ as indicated in Table 2. Note:- If the cores are to be crossed the copper screen should be removed after the initial setting of the cores. It may be necessary to temporarily secure the copper tapes to prevent them from unwinding. VOLTAGE A B 7.2kV 130mm 110mm 12kV 185mm 165mm LUG BARREL 17.5kV 185mm 165mm LENGTH 24kV 310mm 290mm +5MM 36kV 460mm 440mm Table 2 B B 3. Conductive Layer Treatm ent Extruded Conductive Screen Layer Remove the semi-conductive screen layer using a suitable tool to dimension B+ as indicated in Table 2. Note:- It is very important that the screen is removed leaving a clean straight cut and that no scoring or damage is done to the primary insulation. We highly recommend the use of approved screen removal tools (please ask for details). It is good practice to flame brush the primary insulation and conductive screen cut. This has the effect of removing any minor surface irregularities or burrs that may be present. YELLOW STRESS CONTROL TAPE Apply Stress Control Tape 1 0 m m 1 0 m m COPPER TAPE SCREEN De-grease the insulation and screen using the solvent tissues provided. Remove the release paper from the Yellow Stress Control Tape (TS31785Y). Stretch to approx. 50% width and apply the tape around the end of each core screen to cover the copper tape (If present) and insulation by 10mm either way.

4. Stress Control Tubes Position the stress control tubes onto each core so that the bottom of each tube is covering the yellow stress control mastic by approx 10mm. Starting at the end closest to the cable crutch, Shrink each tube one at a time keep the flame on the move to ensure an even wall thickness. 5. I nstalling Cable Lugs Remove the insulation from each core to the dimension in Table 1. Install cable lug and remove any burrs or sharp points that may be present. Preheat each lug and wrap two layers of red sealant tape over the lug barrel and extend onto the insulation by approx 10mm. ROLL SPRINGS 6. I nstalling The Breakout Boot Slide the three legged boot over the cores and push down into the crutch of the cable. Shrink from the shoulder of the breakout and down to the cable sheath, then from the shoulder to the cores. Apply a turn of red sealant tape around each breakout turret as shown. ANTI-TRACK TUBE RED SEALANT TAPE 7. I nstalling The Anti-Track Tube Position the anti-track tubes so that they cover the turrets of the breakout boot and the barrels of the lugs. Starting from the cable crutch area, Shrink the tubes in place. Keeping the flame moving to ensure an even wall thickness, ensure the tubes are fully recovered and wrinkle free. Allow the tubes to cool to hand hot and trim at the lug end with a sharp knife if necessary.

AIR CLEARANCE TO LOCAL SPEC I ndoor Term inations d E d To ensure long term performance of medium voltage terminations, certain separation distances are required as indicated in Table 3. DISTANCE (d) PHASE/PHASE TOP OF STRESS TUBE & PHASE/GROUND TO LUG BARREL VOLTAGE d (mm) E 7.2kV 15mm 30mm 12kV 20mm 50mm 17.5kV 20mm 75mm 24kV 40mm 95mm 36kV 50mm 250mm Table 3 Note:- Bushing protection boots will be required for the majority of installations. If it is necessary to cross the cores, the cross MUST be in a screened area as shown. d = SEE TABLE 4 80mm 200mm 8. I nstallation Of Rain Sheds On outdoor terminations the sheds should be fitted from the bottom up as indicated in the drawing opposite. Indoor 36kV terminations are supplied with one shed per phase and four sheds per phase for outdoor. NUMBER OF SHEDS PER PHASE VOLTAGE INDOOR OUTDOOR 7.2kV - 1 12kV - 2 17.5kV - 2 24kV - 3 36kV 1 4 Table 4 The first shed should be fitted at a distance 200mm from the lower edge of the anti-track tube to the edge of the shed. All subsequent sheds should be fitted at a distance of 80mm from edge to edge. Note:- It is advisable not to position rain sheds at the top of stress control tubes, re-position if necessary.

I nverted Connections If a termination is to mounted for connection from above the equipment i.e in the inverted position, sheds should be installed through 180 as shown MIN BENDING RADIUS r = 15xD Cable Bending Radius During installation care should be taken not to over bend the cable. In cold condition it may be necessary to gently heat the cable to prevent damage whilst D