3M Cold Shrink QT-III Silicone Rubber Termination

Similar documents
3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

Cold Shrink QS T Trifurcating Transition Splice Kit

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

QT-III Cold Shrink Silicone Rubber

3M Mechanical Shearbolt Connectors, QCI Series

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

High Voltage Joints and Terminations up to 72,5 kv 145 kv

Branch Splice QS-2001B

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)

ELB ELB

3M Cold Shrink Splice Kits, QS T Series

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

ELB ES. Product Installation Instructions

Cable Ties. Data Sheet

3M Locator Plate

3M Cross-Connect Cabinets 4220SVC and 4220SVE Tall Skirt Installation Guide

3 Reenterable Encapsulated PST Dome Closure

3M Products for Electrical Networks Wind Farm Capabilities. Leading Edge. Electrical Solutions for. Wind Farms

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

3M Ladder Kit 3M710/MS 2 -TMK-LK

Installation Instructions

3M Closure System 2-Type Cover (505)

3M Electrical Tapes Product Selection Guide. Insulate & Protect. with Quality Tapes. Preliminary

SLiC Aerial Terminal and Spiral End Seal for use with AMP* Quiet Front Terminal Blocks

3M Locator Plate

3M No Polish LC/APC Connector SM, Angle Splice, 250/900 µm 8830-APC/AS

Cold Shrink Silicone Rubber Termination Kit QT-III 7620-S, 7690-S and 7680-S Series kv

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900 µm Instructions

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900-µm. Instructions. October C

Data Sheet July For RoHS information, please visit

3M Electrical Markets Division. Rubber, Mastic and Specialty Tapes Application Guide. Choose the. Right Tape. for your. Electrical Project

HVS S 15kV Class

3M No Polish LC Connector SM and MM, Flat Splice, 250/900 µm

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

710 Splicing Rig. Instructions. January E

3M Cushion-Mount Plus Plate Mounting Tapes with Easy Mount Adhesive

Installation Instructions

3M Mini D Ribbon (MDR) Cable Assembly.050 High Speed Video Data Transmission System, 50 Position 14X50-SZWB-XXX-0NC

3M Pleated Foil I/O Cable Assemblies MDR Series

Door Edge Protection Film 36 inch

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

protect mask conduct reflect enhance 3M Specialty Tape Solutions

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

QTII (X) Series Silicone Rubber Cold Shrink Termination Kits

3M Cable Ties Product Guide. Made in USA. & Plenum Rated

3M Fiber Dome Closure FDC 10

Repair Method for 3M Resilient Floor Protection System

(K),(M),(P)489TB/G Up to 42 kv

Installation Instruction EPP /92

3M Cold Shrink QT-III Silicone Rubber Skirted and Inverted Skirted Termination Kits, 7640-S, 7650-S and 7660-S Series 5, 8, 15, 25/28 and 35 kv

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

Volition. VF-45 Quick Install kit. and Maintenance Cleaning Kit. 3Innovation

Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV

Product Number

Quick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description

GM Specification Annual Test Data

(K),(M)430TB/G Up to 36 kv

C Power Connection Kit

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

INSTALLATION INSTRUCTION

3M Textool Test and Burn-In Sockets for 1.0 mm Area Array Packages Including Ball Grid Array and Land Grid Array

GM Specification Annual Test Data

3M Connector System 0.050" x 0.100" Pitch. 3M Tripolarized Wiremount Socket - Series 820 3M 4-Wall, Tripolarized Header - Series 810

I nstallation I nstruction Heatshrink Term ination For 3 Core Polym eric Cables 7.2 kv to 3 6 kv

WRSS Wraparound Repair Sleeve Installation Instructions

Transcription:

3M Cold Shrink QT-III Silicone Rubber Termination For Tape-Over-Wire (TOW) or Wire-Over-Tape (WOT) Shielded Cable 7673-S-8(S)-TOW/WOT Instructions IEEE Std. No. 48 Class 1 Termination 69 kv Class, 350 kv BIL IEC 60840 72,5 kv F CAUTION Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product. May 2013 3 78-8141-5460-1 Rev B

Kit Contents 1 Silicone Rubber Lug Seal Insulator Assembly 1 High-K Stress Control Assembly 1 Silicone Rubber Ground Seal Assembly 1 Silicone Rubber Skirted Insulator Assembly 1 Pre-formed Ground Braid Assembly 3 Constant Force Springs 1 Roll Scotch Electrical Shielding Tape 24 4 Tubes 3M Red Compound P55/R (Non-Silicone Grease) 1 Roll 3M Scotch-Seal Mastic 2229, 1" (25 mm) wide 1 Roll Scotch Silicone Rubber Tape 70 1 Roll Scotch Super Vinyl Electrical Tape 88, 3/4" 66' 1 Roll Scotch Rubber Mastic Sealing Tape 2228, 2" x 10' 2 3M Cable Cleaning Pads CC-3 1 Strip 3M EMI Copper Foil Shielding Tape 1181, 15" long 3 Instruction Sheets ((1) Tape-Over-Wire (TOW) or Wire-Over-Tape (WOT) Shielded Cable; (2) Jacketed Concentric Neutral (JCN) Cable; (3) Tape Shield or Longitudinally Corrugated (LC) Shielded Cable) Note: Utility Colth (Aluminum Oxide) abrasive materials are required for cable preparation, but are NOT INCLUDED IN KIT. Required grits are P180, P240 and P320. Available 3M Utility Colth (Aluminum Oxide) Rolls UPC Codes are: P180: 51115-19788 P240: 51115-19786 P320: 51115-19784 Note: Do not use knives to open plastic bags. Kit Selection Table Note: Final determining factor is cable insulation diameter. Kit Number Primary Insulation O.D. Range 2.01"-2.87" (51,1-72,9 mm) Jacket O.D. Range 2.25"-3.45" (57,2-87,6 mm) Conductor Size Range* AWG (mm 2 ) 350-1500 (175-725) 7673-S-8(S) *Based on 650 mil insulation thickness Table 1 2 78-8141-5460-1 Rev B

Correct Installation of Termination Ground Seal Assembly Silicone Rubber Skirted Insulator Assembly Silicone Rubber Lug Seal Insulator Assembly Semi-con Stress Control Assembly Scotch Rubber Mastic Sealing Tape 2228 Cable Insulation Note: Check to insure that the Lug Seal Insulator Assembly tube will fit over the lug. If the lug will not fit through the tube core, contact 3M for an alternative installation procedure. 78-8141-5460-1 Rev B 3

I. Tape-Over-Wire (TOW) Shield Cable (For Wire-Over-Tape (WOT) Shield, go to Section II on page 9.) 1.0 Prepare Cable 1.1 Check to be sure the cable fits within the kit ranges as shown in Table 1. 1.2 Prepare cable using dimensions shown in Figure 1. BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG PLUS 0.5" (13 MM) PLUS CRIMP GROWTH. NOTE: Provide additional exposed conductor to allow for growth of aluminum lugs or connectors during crimping, as follows; Conductor Size 250-350 400-650 750-1000 1100-3000 Growth Allowance 0.25" (6 mm) 0.5" (13 mm) 0.75" (19 mm) Field Determined Table 2 1.2a SANDING OF THE INSULATION IS REQURIED. Start with P180 grit Utility Cloth (Aluminum Oxide), followed by P240 grit and finally P320 grit. DO NOT reduce the cable insulation diameter below that allowed by the kit (see Table 3). 1.2b Wipe the cable insulation per paragraph "5.0 Clean Cable Insulation Using Standard Practice" on page 13. 1.2c For cables that have a bonded semi-conductive (semi-con) insulation shield that does not peel squarely. The following steps describe how to square the semi-con cutback. NOTE: GRAPHITE SPRAY IS NOT PROVIDED IN THIS KIT. Semi-conductive Graphite Spray can be used to square the semi-con after insulation sanding has been completed. During cable preparation, remove additional cable semi-con to bring the highest point 1/8-1/4 (3-6 mm) past the instructions semi-con cutback dimension. Following insulation sanding, use tape and clean plastic wrap to cover/mask the cable insulation from the original semi-con cutback dimension to the end of the insulation and partially cover the cable semi-con leaving 0.5-1.0 (12-25 mm) exposed. Apply a coat of Graphite Spray (avoid runs caused by excessive spray) and let dry. Apply a second coat of Graphite Spray and let dry. Using soft towel, lightly buff the graphite to remove any loose material. Remove masking tapes and plastic wrap. 3.50" (90 mm) 3.25" (80 mm) 32.75" (830 mm) 26" (660 mm) Depth of lug +0.5" (13 mm) +crimp growth Semi-Con Insulation Conductor Cable Jacket Corrugated Tape Shield Shield Wires Figure 1 4 78-8141-5460-1 Rev B

Typical Conductor Size Kcmil (mm 2 ) Insulation OD after Preparation Inches (mm) 350-1500 (175-725) 2.01-2.87 (51,1-72,9) 2.0 Install Ground Braid Assembly Table 3 2.1 For longitudinally corrugated (LC) cables, fill the valleys on the longitudinally corrugated shield with several wraps of Scotch Electrical Shielding Tape 24. Half-hitch to tie off. (Figure 2) Corrugated Tape Shield Scotch Electrical Shielding Tape 24 Figure 2 2.2 Select the pre-formed ground braid assembly from the kit. Pass the end of the cable through the ground braid assembly loop, and position the ground braid assembly around the flat or corrugrated tape shield as shown. (Figure 3) Semi-Con Insulation Solder Block Ground Braid Assembly Corrugated Tape Shield Cable Jacket Edge Shield Wires Figure 3 78-8141-5460-1 Rev B 5

2.3 Select the 3 constant force springs from the kit. Starting at the loop of the ground braid assembly nearest the cable jacket edge, install the 3 constant force springs, one around each ground braid loop. Cinch (tighten) the springs after wrapping the final turn. Extend the ground braid tails down the cable jacket. (Figure 4) Constant Force Spring Cable Jacket Edge Solder Block Ground Braid Assembly Figure 4 2.4 Select the roll of 1" (25 mm) wide 3M Scotch-Seal Mastic Sealing Tape 2229 from the kit. Cut a length of the tape long enough to wrap around the cable jacket. Remove the release liner from the mastic and, using light tension, apply a SINGLE WRAP of mastic around the cable jacket, positioned under the ground braid solder blocks. (Figure 5) Semi-Con Constant Force Springs Solder Block 1st 3M Scotch-Seal Mastic Sealing Tape 2229 Strip (beneath solder blocks) Figure 5 6 78-8141-5460-1 Rev B

2.5 Cut four 1" (25 mm) lengths of 1" (25 mm) wide 3M Scotch-Seal Mastic Sealing Tape 2229. Remove the release liner and roll each mastic strip into a small roll. (Figure 6) Press the mastic rolls into place on either side of the ground braid solder blocks. (Figure 7) 1" (25 mm) Mastic Strip Mastic Rolled-Up Figure 6 Rolled 3M Scotch Seal Mastic Sealing Tape 2229 Strip (x4) Semi-Con Solder Block 1st 3M Scotch Seal Mastic Sealing Tape 2229 Strip (beneath solder blocks) Figure 7 2.6 Select the roll of 1" (25 mm) wide 3M Scotch-Seal Mastic Sealing Tape 2229 from the kit and cut a length of the mastic long enough to cover the ground braid solder blocks and previously applied mastic. Using light tension, apply a SINGLE WRAP of mastic around the cable jacket over the ground braid solder blocks and the previously applied mastic. Fold the shield wires, evenly spaced, back over the mastic. (Figure 8) 2nd 3M Scotch Seal Mastic Sealing Tape 2229 Strip (over solder blocks & mastic rolls) Figure 8 78-8141-5460-1 Rev B 7

2.7 Cut a third length of 3M Scotch-Seal Mastic Sealing Tape 2229 long enough to wrap a SINGLE WRAP over wires, applied mastic and solder blocks. Remove the release liner from the mastic and, using light tension, apply mastic over the shield wires and previously applied mastic. (Figure 9) 2.8 Secure the shield wires and the two tails of the ground braid assembly to the cable jacket approximately 6" (150 mm) from the cable jacket edge with several wraps of vinyl tape. (Figure 9) 6" (150 mm) (approx.) Vinyl Tape Wrap 3rd 3M Scotch-Seal Mastic Sealing Tape 2229 Strip (over shield wires & previous mastic) Figure 9 2.9 Wrap two half-lapped layers of highly-tensioned Scotch Vinyl Electrical Tape Super 88 over the mastic seal and constant force springs. Cover all exposed mastic, constant force springs and tape shield, overlapping 0.25" (6 mm) onto the exposed cable semi-con. (Figure 10) Note: Take care to leave 3.0" (76 mm) of exposed semi-con. This will be a marker tape location later. Overlap Semi-Con 0.25" (6 mm) Exposed Semi-Con Cable Jacket 3.0" (76 mm) Scotch Vinyl Electrical Tape Super 88 Figure 10 2.10 Proceed to paragraph "5.0 Clean Cable Insulation Using Standard Practice" on page 13. 8 78-8141-5460-1 Rev B

II. Wire-Over-Tape Shield Cable 3.0 Prepare Cable 3.1 Check to be sure the cable fits within the kit ranges as shown in Table 1. 3.2 Prepare cable using dimensions shown in Figure 11. BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG PLUS 0.5" (13 MM) PLUS CRIMP GROWTH. NOTE: Provide additional exposed conductor to allow for growth of aluminum lugs or connectors during crimping, as follows; Conductor Size 250-350 400-650 750-1000 1100-3000 Growth Allowance 0.25" (6 mm) 0.5" (13 mm) 0.75" (19 mm) Field Determined Table 4 3.2a SANDING OF THE INSULATION IS REQUIRED. Start with P180 grit Utility Cloth (Aluminum Oxide), followed by P240 grit and finally P320 grit. DO NOT reduce the cable insulation diameter below that allowed by the kit (see Table 3). 3.2b Wipe the cable insulation per paragraph "5.0 Clean Cable Insulation Using Standard Practice" on page 13. 3.2c For cables that have a bonded semi-conductive (semi-con) insulation shield that does not peel squarely. The following steps describe how to square the semi-con cutback. NOTE: GRAPHITE SPRAY IS NOT PROVIDED IN THIS KIT. Semi-conductive Graphite Spray can be used to square the semi-con after insulation sanding has been completed. During cable preparation, remove additional cable semi-con to bring the highest point 1/8-1/4 (3-6 mm) past the instructions semi-con cutback dimension. Following insulation sanding, use tape and clean plastic wrap to cover/mask the cable insulation from the original semi-con cutback dimension to the end of the insulation and partially cover the cable semi-con leaving 0.5-1.0 (12-25 mm) exposed. Apply a coat of Graphite Spray (avoid runs caused by excessive spray) and let dry. Apply a second coat of Graphite Spray and let dry. Using soft towel, lightly buff the graphite to remove any loose material. Remove masking tapes and plastic wrap. 3.50" (89 mm) 3.25" (82 mm) 32.75" (832 mm) 26" (660 mm) Depth of lug +0.5" (13 mm) +crimp growth Semi-Con Insulation Conductor Cable Jacket Tape Shield Figure 11 Shield Wires Typical Conductor Size Kcmil (mm 2 ) Insulation OD after Preparation Inches (mm) 350-1500 (175-725) 2.01-2.87 (51,1-72,9) Table 5 78-8141-5460-1 Rev B 9

4.0 Install Ground Braid Assembly 4.1 Fold the shield wires back along the cable jacket. Select the pre-formed ground braid assembly from the kit. Pass the end of the cable through the ground braid assembly loop, and position the ground braid assembly around the tape shield as shown. (Figure 12) Semi-Con Insulation Shield Wires Solder Block Ground Braid Assembly Tape Shield Cable Jacket Edge Figure 12 4.2 Select the 3 constant force springs from the kit. Starting at the loop of the ground braid assembly nearest the cable jacket edge, install the 3 constant force springs, one around each ground braid loop. Cinch (tighten) the springs after wrapping the final turn. Mark the solder block location on the cable jacket. (Figure 13) Constant Force Spring Cable Jacket Edge Solder Block Ground Braid Assembly Figure 13 10 78-8141-5460-1 Rev B

4.3 Select the roll of 1" (25 mm) wide 3M Scotch-Seal Mastic Sealing Tape 2229 from the kit. Cut a length of mastic long enough to wrap around the cable jacket. Lift the ground braid tails and shield wires. Remove the release liner from the mastic and using light tension, apply a SINGLE WRAP of mastic around the cable jacket positioned under the ground braid solder blocks and shield wires. Fold the shield wires, evenly spaced, back over the mastic. (Figure 14) Shield Wires Constant Force Springs Solder Block 1st 3M Scotch-Seal Mastic Sealing Tape 2229 Strip (beneath solder blocks & shield wires) Figure 14 4.4 Select the roll of 1" (25 mm) wide 3M Scotch-Seal Mastic Sealing Tape 2229 from the kit. Cut a length of mastic long enough to wrap over the shield wires and previously applied mastic. Fold the ground braid tails out of the way. Remove the release liner from the mastic and, using light tension, apply a SINGLE WRAP of mastic around the cable jacket, positioned over the shield wires and previously applied mastic. (Figure 15) Constant Force Springs Shield Wires 2nd 3M Scotch-Seal Mastic Sealing Tape 2229 Strip (over shield wires & previously applied mastic) Figure 15 78-8141-5460-1 Rev B 11

4.5 Cut four 1" (25 mm) lengths of 1" (25 mm) wide 3M Scotch-Seal Mastic Sealing Tape 2229. Remove the release liner and roll each mastic strip into a small roll. (Figure 16) Press the mastic rolls into place on either side of the ground braid solder blocks. (Figure 17) 1" (25 mm) Mastic Strip Mastic Rolled-Up Figure 16 Rolled 3M Scotch-Seal Mastic Sealing Tape 2229 Strip (x4) Solder Block 2nd 3M Scotch-Seal Mastic Sealing Tape 2229 Strip (beneath solder blocks) Figure 17 4.6 Cut a third length of 3M Scotch-Seal Mastic Sealing Tape 2229 Strip long enough to wrap a SINGLE WRAP over applied mastic and solder blocks. Remove the release liner from the mastic and, using light tension, apply mastic over the shield wires and previously applied mastic. (Figure 18) 4.7 Secure the shield wires and the two tails of the ground braid assembly to the cable jacket approximately 6" (150 mm) from the cable jacket edge with several wraps of vinyl tape. (Figure 18) 6" (150 mm) (approx.) Vinyl Tape Wrap 3rd 3M Scotch-Seal Mastic Sealing Tape 2229 Strip (over solder blocks & previous mastic) Figure 18 12 78-8141-5460-1 Rev B

4.8 Wrap two half-lapped layers of highly-tensioned Scotch Vinyl Electrical Tape Super 88 over the mastic seal and constant force springs. Cover all exposed mastic, constant force springs and tape shield, overlapping 0.25" (6 mm) onto the exposed cable semi-con. (Figure 19) Note: Take care to leave 3.0" (76 mm) of exposed semi-con. This will be a marker tape location later. Overlap Semi-Con 0.25" (6 mm) Exposed Semi-Con Cable Jacket 3.0" (76 mm) Scotch Vinyl Electrical Tape Super 88 Figure 19 5.0 Clean Cable Insulation Using Standard Practice 5.1 Use only aluminum oxide abrasive (320 grit or higher) to finish and polish insulation surface, if not already completed during Prepare Cable section. 5.2 Use abrasive only on cable insulation. DO NOT USE ON SEMI-CON. 5.3 When using abrasive, do not reduce the cable insulation diameter below that allowed by the kit. 5.4 Wipe the cable insulation clean with a cleaning pad from the included 3M Cable Cleaning Pads CC-3 or an approved solvent. DO NOT ALLOW THE SOLVENT TO TOUCH SEMI-CON INSULATION SHIELD OR GRAPHITE SPRAY, IF USED. Note: Remove any remaining solvent with 3M Cable Cleaning Pads CC-DRY (not supplied with kit) or lint-free cloth. 78-8141-5460-1 Rev B 13

6.0 Install Termination 6.1 Slide the ground seal assembly (this is the cold shrink tubular assembly on the larger core) onto the cable jacket, loose core end first. (Figure 20) Losse Core End Ground Seal Assembly Figure 20 6.2 Place a marker tape on the cable semi-con located 1.75 (45 mm) from the end of the semi-con. (Figure 21) 1.75" (45 mm) Marker Tape Figure 21 6.3 Apply 1 tube of 3M Red Compound P55/R starting at marker tape and continuing onto the cable insulation for approximately 8" (200 mm). (Figure 22) 8.0" (200 mm) Apply 3M Red Compound P55/R Figure 22 14 78-8141-5460-1 Rev B

6.4 Select the stress control assembly (this is the medium length, black colored, two-piece cold shrink tubular assembly on one medium size core) from the kit. Slide the stress control assembly over the cable with the loose core end toward the cable end. Align the stress control assembly tube (not the core) with the marker tape, and remove the core by pulling the loose core end while unwinding counter-clockwise. (Figure 23) Align with marker tape Unwind counter-clockwise Loose Core End Stress Control Assembly Figure 23 6.5 Apply 2 tubes 3M Red Compound P55/R to the exposed insulation and stress control assembly. Make certain to fill the steps of the stress control assembly, as indicated in figure 24, with the 3M Red Compound P55/R. (Figure 24) Coat with 3M Red Compound P55/R Fill steps with 3M Red Compound P55/R Figure 24 6.6 Slide the cold shrink silicone rubber skirted insulator assembly onto the cable. Align the assembly tube (not the core) with the end of the sealing mastic/constant force spring cover tape located 3.0" (76 mm) from the end of the cable semi-con. (Figure 25) Scotch Vinyl Electrical Tape Super 88 Align Cold Shrink Silicone Rubber Skirted Insulator Assembly with this edge Figure 25 78-8141-5460-1 Rev B 15

6.7 Remove the core by pulling the loose core end while unwinding counter-clockwise. (Figure 26) Unwind counter-clockwise Silicone Rubber Skirted Insulator Assembly 7.0 Install Lug or Connector Figure 26 Note: For Aluminum Conductors - Thoroughly wire brush conductor strands to remove aluminum oxide layer. Immediately insert conductor into lug or connector barrel as far as it will go. 7.1 Position lug or connector and crimp according to manufacturer s directions. Remove excess oxide inhibitor and sharp crimp flashing following crimping. Figure 27 illustrates the appearance following installation of the Skirted Insulator Assembly and Lug. Note extension of approximately 1" (25 mm) cable insulation beyond the end of the installed Skirted Insulator Assembly and 1/2" (13 mm) gap from the end of the lug the cable insulation. 1/2" (13 mm) Cable Insulation Skirted Insulator Assembly Figure 27 16 78-8141-5460-1 Rev B

7.2 Wrap Scotch Rubber Mastic Sealing Tape 2228 half-lapped over the lug or connector barrel and the 1/2" (13 mm) insulation/lug gap, building to a diameter equal to the cable insulation and tapered toward the required 2" (50 mm) coverage length onto the lug or connector barrel. Cover 2" (50 mm) of the lug or connector barrel. (Figure 28) NOTE: Do Not build tape O.D. larger than the end of the Skirted Insulator Assembly and Do Not tape over the end of the Skirted Insulator Assembly. 2" (51 mm) Scotch Rubber Mastic Sealing Tape 2228 Skirted Insulator Assembly 8.0 Install Sealing Tubes Figure 28 8.1 Slide the parked cold shrink silicone rubber ground seal assembly onto the termination. Start to shrink underneath the first skirt. Remove the core by pulling the loose core end while unwinding counter-clockwise. (Figure 29) Unwind counter-clockwise Ground Seal Assembly Figure 29 78-8141-5460-1 Rev B 17

8.2 Slide the cold shrink silicone rubber lug seal insulator assembly tube onto the lug, or connector, and termination, as shown in Figure 30. Start to shrink the tube near the top of the last skirt and onto the lug or connector barrel. If the tube overlaps the lug pad, or is not tight to the lug barrel, carefully trim the tube just past (1/4 (6 mm)) the Scotch Rubber Mastic Sealing Tape 2228. A roll of Scotch Silicone Rubber Tape 70 is provided to cover the edge of the trimmed tube (See paragraph 8.4 and Figure 32.) Apply with moderate tension, stretching only enough to conform to the lug barrel and tube. Unwind counter-clockwise Lug Sealing Tube Figure 30 8.3 Figure 31 illustrates the appearance following installation of the Cold Shrink Silicone Rubber Lug Seal Insulator Assembly tube. Figure 31 Silicone Rubber Lug Seal Insulator Assembly Tube 8.4 Figure 32 illustrates the appearance following installation of Scotch Silicone Rubber Tape 70 (if needed) partially over the the Cold Shrink Silicone Rubber Lug Seal Insulator Assembly tube and the lug barrel. Figure 32 Scotch Silicone Rubber Tape 70 (if needed) 18 78-8141-5460-1 Rev B

8.5 Connect the completed termination to equipment/system following standard practice. 8.6 Connect the neutral wires to the ground system following standard practice. 78-8141-5460-1 Rev B 19

3M, Scotch-Seal and Scotch are trademarks of 3M Company. All other trademarks are property of their respective owners. Important Notice All statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use. Any statements related to the product which are not contained in 3M's current publications, or any contrary statements contained on your purchase order shall have no force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M. Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture at the time of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M's option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of the legal theory asserted. 3 Electrical Markets Division 6801 River Place Blvd. Austin, TX 78726-9000 800.245.3573 Fax 800.245.0329 www.3m.com/electrical Please Recycle. Printed in USA. 3M 2013. All Rights Reserved. 78-8141-5460-1 Rev B