PRESS P/N - P/N ECO SERIES

Similar documents
RL/M BLU SERIES. Low NOx Modulating Light Oil Burners FIRING RATES. LOW NOx T. M 190/ kw M 223/ kw

PRESS G SERIES. Two Stage Light Oil Burners FIRING RATES

RS/M SERIES. Modulating Gas Burners FIRING RATES

RS/E-EV MZ SERIES. Modulating Gas Burners FIRING RATES

RIELLO 40 F SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL. F kw F kw F kw

RS SERIES. Two Stage Progressive Gas Burners FIRING RATES

RES G MRBLU SERIES. Low NOx One Stage Light Oil Burners FIRING RATES. LOW NOx LIGHT OIL

RS/1 SERIES. One Stage Gas Burners RS 34/1 MZ RS 44/1 MZ kw kw GAS

RDB SERIES. One Stage Light Oil and Kerosene Burners FIRING RATES LIGHT OIL

GULLIVER BSD SERIES. Low NOx Two Stage Gas Burners FIRING RATES. BS1D 16/19 52 kw BS2D 35/40 91 kw BS3D 65/ kw BS4D 110/ kw.

RIELLO 40 GS SERIES. One Stage Gas Burners FIRING RATES. S kw S kw S kw S kw

GULLIVER BS SERIES. Low NOx One Stage Gas Burners FIRING RATES. BS kw BS kw BS kw BS kw.

TWO STAGE LIGHT OIL BURNERS PRESS G SERIES

DB Series. Technical Data Leaflet. Industrial Dual Block Oil, Gas and Dual Fuel Burners. Industrial TS0086UK00

TWO STAGE PROGRESSIVE AND MODULATING GAS BURNERS RIELLO 40 GS/M SERIES GS 10/M 22/ kw GS 20/M 43/ kw

RIELLO 40 FS SERIES. One Stage Gas Burners FIRING RATES. FS kw FS kw FS kw FS kw FS kw FS kw GAS

ONE STAGE GAS BURNERS RDBS SERIES

ONE STAGE GAS BURNERS RS/1 SERIES RS 28/ kw RS 34/1 MZ kw RS 38/ kw RS 44/1 MZ kw

RS Series Two Stage Progressive Gas Burners

TECHNICAL DATA LEAFLET GAS. RS/1 Series. One Stage Gas Burners. RS 34/1 MZ kw RS 44/1 MZ kw.

TWO STAGE GAS BURNER GULLIVER RSD SERIES RS5D 160/ kw

TWO STAGE PROGRESSIVE GAS BURNERS

LOW NOx TWO STAGE GAS BURNERS GULLIVER BSD SERIES BS1D 16/19 52 kw BS2D 35/40 91 kw BS3D 65/ kw BS4D 110/ kw

ONE STAGE GAS BURNER GULLIVER RSF SERIES RS5F kw

TWO STAGE GAS BURNERS

KOLHAPUR FOUNDRY & ENGINEERING CLUSTER

RS/E BLU Series. Technical Data Leaflet. Low NOx Modulating Gas Burners. Low NOx Gas TS0087UK00

CODE MODEL TYPE G3BF 490T G5BF 492T G5BF 489T53

CODE MODEL TYPE PRESS GW 605 T80

Installation- and maintenance instruction BENTOFLEX ST 108 PL

Light oil - kerosene burner

Installation- and maintenance instruction B20K-2

Kerosene - oil burner

Installation- and maintenance instruction ST120 S75/21

Oil - kerosene burner

Installation- and maintenance instruction B20KA/K

product Information on oil, gas and dual fuel burners Industrial burners 1,000 11,700 kw flexible and reliable

Weishaupt Monarch oil burners Sizes 5 to 11 1/2002 GB

Installation- and maintenance instruction BENTOFLEX ST120KAV

Installation- and maintenance instruction B80-2/3

Weishaupt Monarch oil burners Sizes 5 to 11 1/2002 CA

Oil, Gas and Dual Fuel Burners

Weishaupt oil burners Sizes 30 to 70 1/2003 CA

Installation- and maintenance instruction B20KAV/KV

Weishaupt Monarch oil burners Sizes 1 and 3 1/2002 GB

OIL BURNERS MAIOR P 45 AB. techniques for energy saving MODEL. HYDRAULIC SYSTEM 220/380 V 60 Hz LB

Installation- and maintenance instruction BENTOFLEX ST133KA/K

Installation- and maintenance instruction B20KA/K

Oil, gas and dual fuel burners. Burner series

Doing more for clean environment and energy saving

product Oil burners, 1-11 monarch burners, sizes 1-11 ( kw) simply reliable Information on oil burners

Installation- and maintenance instruction BENTOFLEX ST133K

Emprendimiento Fénix Product Catalogue

Mobile Diesel Heaters GRY-D / GRY-I Service Training Course

SPARE PARTS LIST. for. Infrared oil heater. Model. Type. EPX5 for 120V 60Hz. May, 2017

XL9 E-S Serial number N for XL9 E Edition 2005

MODEL B360 E ILLUSTRATED PARTS BREAKDOWN UNIT 1. From Serial Number: Untill Serial Number: Edizione 2010 Rev. A. Cod

MULTIFIRE. High temperature dual fuel burner

Gas oil/ Kerosene burners

PRODUCT RANGE A COMPLETE RANGE OF BURNERS FROM 17 TO kw

available in battery up to 4 units for a total of 560 kw

Gas oil/ Kerosene burners

MODEL INFORMATION CANNED MOTOR PUMP TYPE CAM HERMETIC

CREATIVE EQUIPMENT CC 18 Main Road, Fishers Hill, Germiston, 1401 Tel: Fax:

K30H001YP cam star-delta switch - 3-pole A - screw mounting

Piston Metering Pump REKOS KR

Design and Application Details

AMR. GB-Ganz Tüzeléstechnikai Kft. MODULATING DUOBLOCK BURNER FAMILY

Installation- and maintenance instruction B45A2.2

Engine model Basic engine Number cylinders Firing order (N 1 nearest to fan) Cylinder arrangement Valves per cylinder Type Induction System

GAS BURNERS BLU 3000 PR BLU 4000 PR

GREENOx BT LOW RETURN TEMPERATURE DUAL BT WITH TILED BOILERS. GREENOx BT COND LOW RETURN TEMPERATURE WITH CONDENSER

TEAMTEC INCINERATORS Market leaders since More than units sold worldwide

XL9E-S Edition2005. Serial numbern forxl9e

Infrared oil heater. Model. Type. KBE5S for 120V 60Hz KBE5L for 120V 60Hz KBE5L 2-step for 120V 60Hz KBE1S for 230V 50Hz

Chiller. AQL/AQH 40 to 75. Air Cooled Water Chillers Cooling Only and Heat Pump Engineering Data Manual to 77.2 kw to 75.

OIL BURNERS. MINOR 1 Snorkel 240 Volt 50 Hz

Design and Application Details

Oil, Gas and Dual Fuel Monoblock Burners

Gas oil/ Kerosene burners

Liebert Hipluse U UPS;80-400kVA; 380/400/415V Detailed Specification

Design and Application Details

Gas burner Dual fuel burner. Gas burner. Series RG GG MG. Dual fuel burner. Series MK

Inverter scroll compressors VZH single and manifold

motor driven metering pumps

TECHNICAL DOCUMENTATION WOLF AIR HEATERS LH-EC / LH. 30m 3 /h

NEXTRON MONOBLOCK BURNERS kw

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS

SPECIFICATION PUMP. DW - G 2 UNI ISO 228 Flange

Fig Blast tube 2.Asbestos gasket 3.Flange 4.Body gasket 5. Brake plate. 6. Oil n ozzle 7.Heater 8.Rubber block 9. Transformer 10.

motor driven metering pumps

AXICIAT VA. Axial fans. Smoke extraction F200/120 and F400/120. High available pressure

Horizontal And Vertical Centrifugal Pumps

SPARE PARTS MANUAL VAL HEATERS

LIBERTY APPROVED OIL BURNERS AND SPECIFICATIONS. Supplemental Installation and Operating Instructions OIL-FIRED WATER AND STEAM BOILERS / NO.

End Suction Range MARCH 2018

motor driven metering pumps

MANUFACTURERS PARTS LIST RIELLO

In-Line Dry Rotor Circulating Pumps. EIL R Series EIL- FK Series

ABS submersible sewage pump AFP

Transcription:

The PRESS P/N series of burners covers a firing range from 800 to 5130 kw. They have been designed in three versions for use in commercial and industrial installation, to burn different oil viscosity from 7 up to 60 E @ 50 C. Operation can be two stage progressive or, alternatively, modulating with the installation of a PID logic regulator and respective probes, which guarantees a turn down ratio of 3:1. The versatility of this range makes the burner well suited for use on steam boilers where the load factor is subject to wide variations, on thermal oil boilers and on boilers for particular heating plants, as hospitals or similar. Simplified maintenance is achieved by the Riello designed slide bar system, which allows easy access to all of the essential components of the combustion head. 1 0 400/800 1600 kw 200 570/1140 2280 kw 300 683/1710 3420 kw 0 1140/2615 5130 kw 1 0 C 400/800 1600 kw 200 C 570/1140 2280 kw 300 C 683/1710 3420 kw 0 C 1140/2615 5130 kw FIRING RATES Useful working field for choosing the burner Modulation range Test conditions conforming to EN267 Temperature: 20 C Pressure: 1013,5 mbar Altitude: 0 m a.s.l. 225

Overall dimensions (mm) PRESS P/N A E F - F(1) O - O(1) H I B C PRESS P/N ECO A E F - F(1) O - O(1) H I B C MODEL A B C E F - F(1) H I O - O(1) u 1 0 796 396 400 910 323-433 222 467 1390-1390 u 200 796 396 400 910 352-462 250 467 1390-1390 u 300 858 447 411 1020 376-506 295 496 1535-1685 u 0 950 508 442 1090 435-565 336 525 1665-1820 u 1 0 C 900 396 504 890 323-433 222 467 1370-1370 u 200 C 900 396 504 890 352-462 250 467 1370-1370 u 300 C 984 447 537 1000 376-506 295 496 1515-1665 u 0 C 1100 508 592 1090 435-565 336 525 1665-1820 (1) Length with extended combustion head - BOILER MOUNTING FLANGE MODEL L M N P u 1 0 C 260 230 M 14 225 u 200 C 260 - M 16 255 u 300 C 260 - M 18 300 u 0 C 310 - M 20 350 PACKAGING MODEL X Y Z kg Z u 1 0 C 1740 990 950 180 u 200 C 1740 990 950 220 X Y u 300 C 2040 1180 1125 238 u 0 C 2040 1180 1125 300 226

Specification DESIGNATION OF SERIES Series : PRESS Size Operation : N Two stage N/ECO Two stage with separated oil pump T/N Three stage T/N ECO Three stage with separate oil pump P/N Modulating P/N ECO Modulating with separate oil pump Emission :... Class 1 EN267 Head : TC Standard head TL Extended head Flame control system : FS1 Standard (1 stop every 24 h) FS2 Continuous working (1 stop every 72 h) Electrical supply to the system : 1/230/50 1/230V/50Hz 3/230/50 3/230V/50Hz 3/400/50 3N/400V/50Hz 3/230-400/50 3/230V/50Hz - 3N/400V/50Hz 3/220-380/60 3/220V/60Hz - 3N/380V/60Hz Auxiliary voltage : 230/50 230V/50Hz 220/60 220V/60Hz SS 1 0 TC S1 3 230 00 0 230 0 BASIC DESIGNATION EXTENDED DESIGNATION 227

Specification STATE OF SUPPLY Monoblock forced draught oil burner with two-stage progressive or modulating operation, with a specific kit, fully automatic, made up of: - Air suction circuit lined with sound-proofing material - Fan with forward curved blades high performance pressure levels - Air damper for air setting and automatic oil output regulator controlled by a servomotor with variable cam - Fan motor at 2850 rpm, three-phase 400V with neutral, 50Hz - Combustion head, that can be set on the basis of the combustion output, fitted with: - stainless steel end cone, resistant to corrosion and high temperatures - ignition electrodes - flame stability disk - Gears pump for high pressure fuel supply, fitted with: - filter - pressure regulator - connections for installing a pressure gauge and vacuometer - internal by-pass for single pipe installation - Heavy oil heating cartridges (P/N ECO version) - Pipes heating cable (P/N ECO version) - Oil pump motor at 1400 rpm (P/N ECO version) - Valve unit with a double oil safety valve on the output circuit - Electrical preheater for heavy oil - Safey oil pressure switch - Photocell for flame detection - Burner safety control box, fitted with control function for the correct positioning of the servomotor and possibility of post-ventilaton by just changing the electric wiring - Flame inspection window - Slide bars for easier installation and maintenance - Protection filter against radio interference - IP X0D (IP 40) electric protection level. Stan ar e ui ent - 2 flexible pipes for connection to the oil supply network - 2 nipples for the connection to the pump - Wiring looms fittings for electrcial connections - 4 screws for fixing the burner flange to the boiler - 2 slide bar extensions (for the extended head models of P 300 P/N and P 450 P/N) - Gasket for flange - Starter* - Instruction handbook for installation, use and maintenance - Spare parts catalogue. * for versions with star-delta starting 228

Available models CODE MODEL HEAT OUTPUT TOTAL ELECTRICAL POWER (kw) (kg/h) (kw) CERTIFICATION NOTE 3436876 P 140 P/N TC FS1 3/230-400/50 230/50 400/800 1600 35/70 140 19-3436877 P 140 P/N TL FS1 3/230-400/50 230/50 400/800 1600 35/70 140 19-3437776 P 200 P/N TC FS1 3/230-400/50 230/50 570/1140 2280 50/100 200 20-3437777 P 200 P/N TL FS1 3/230-400/50 230/50 570/1140 2280 50/100 200 20-3438989 P 300 P/N TC FS1 3/230/50 230/50 683/1710 3420 60/150 300 30 - (1) 3438987 P 300 P/N TC FS1 3/230-400/50 230/50 683/1710 3420 60/150 300 30-3438991 P 300 P/N TC FS1 3/400/50 230/50 683/1710 3420 60/150 300 30 - (1) 3438990 P 300 P/N TL FS1 3/230/50 230/50 683/1710 3420 60/150 300 30 - (1) 3438988 P 300 P/N TL FS1 3/230-400/50 230/50 683/1710 3420 60/150 300 30-3438992 P 300 P/N TL FS1 3/400/50 230/50 683/1710 3420 60/150 300 30 - (1) 3439385 P 450 P/N TC FS1 3/230/50 230/50 1140/2615 5130 100/225 450 34 - (1) 3439387 P 450 P/N TC FS1 3/400/50 230/50 1140/2615 5130 100/225 450 34 - (1) 3439386 P 450 P/N TL FS1 3/230/50 230/50 1140/2615 5130 100/225 450 34 - (1) 3439388 P 450 P/N TL FS1 3/400/50 230/50 1140/2615 5130 100/225 450 34 - (1) Net calorific value: 11,16 kwh/kg; 9600 kcal/kg The burners of PRESS series are in according to 2004/108-2006/95-2006/42 EC Directive and EN 267 Norm. (1) Star-delta starting For ECO models ask for specific code. Viscosity The modulating burner P/N series can burn different heavy oil types from 7 up to 60 E @ 50 C (50 up to 450 cst @ 50 C). For different viscosity levels Riello recommends 3 different configurations: 1) PRESS P/N version for viscosity up to 7 E (50 mm 2 /s, cst), Type MEDIUM HEAVY OIL / USA n 4: basic version with 2800 rmp oil pump installed directly on fan motor shaft (see available codes in the table above) 2) PRESS P/N version for viscosity up to 20 E (150 mm 2 /s, cst), Type BUNKER B / USA n 5: as basic version + heavy oil heating cartridges factory installed on nozzle, pump and valves group (please ask for specific code) 3) PRESS P/N ECO version for viscosity up to 20 E (150 mm 2 /s, cst), Type BUNKER B / USA n 5: with separate 1400 rpm low speed pump, heavy oil heating cartridges factory installed on nozzle, pump and valves group (please ask for specific code) 4) PRESS P/N and PRESS P/N ECO versions for viscosity up to 60 E (450 mm 2 /s, cst), Type BUNKER C / USA n 6: as versions 2) or 3) with pipes heating cable factory installed (please ask for specific code) Special configuration on demand: - Steam oil pre-heater on P/N ECO models. 229

Burner accessories Available for P/N and P/N ECO versions Nozzles The nozzles must be ordered separately. The following table shows the features and codes on the basis of the maximum required output. NOTE: each burner needs N 1 nozzle. RATED OUTPUT kg/h NOZZLES BERGONZO B5 45 - WITH AA NEEDLE CODE NOZZLES FLUIDICS W2 45 - WITH AA NEEDLE CODE u 1 0 70 3009203 3045426 u 1 0 80 3009205 3045427 u 1 0 90 3009207 3045428 u 1 0 200 100 3009209 3045430 u 1 0 200 125 3009211 3045432 u 200 300 150 3009213 3045434 u 200 300 175 3009215 3045436 u 200 300 200 3009800 3045438 u 200 300 225 3009801 3045440 u 300 00 250 3009802 3045442 u 300 00 275 3009803 3045444 u 300 00 300 3009804 3045446 u 0 325 3009805 3045448 u 0 350 3009806 3045450 u 0 375 3009807 3045452 u 0 400 3009808 3045454 u 0 425 3009809 3045455 u 0 450 3009810 3045456 Spacer kit If burner head penetration into the combustion chamber needs reducing, varying thickness spacers are available, as given in the list. SPACER THICKNESS S (mm) KIT CODE u 1 0 200 102 3000722 u 300 130 3000723 u 0 130 3000751 Sound proofing box C If noise emission needs reducing even further, sound-proofing boxes are available. In case of generator heights, where a lower dimension B is required, ask for the Box Support Kit code 20065135. BOX TYPE A (mm) B (mm) min-max C (mm) [db(a)] (*) BOX CODE u 1 0 200 C4/5 850 160-980 110 10 3010404 u 300 0 C7 1255 160-980 110 10 3010376 u 1 0 200 300 0 T C C7 1255 160-980 110 10 3010376 (*) Average noise reduction according to EN 15036-1 standard 230

Burner accessories Self-cleaning filter For cleaning heavy oil from dirty particles and impurities, it is equipped with a thermostatic heater for oil with 60 E viscosity at 50 C. FILTER TYPE FILTERING DEGREE (µm) FILTER CODE u 1 1 2 0 at 0 C 300 3010022 HEATER / THERMOSTAT TYPE HEATER / THERMOSTAT CODE u Ther ostatic heater ith 3010060 u eater 3010061 u Ther ostat t o stage regula le 3010062 Gas separator bottle Gas separator bottle connects the burner oil circuit to the main ring circuit. It allows to recover heat in excess and discharge return circuit gas. CODE u 1 0 200 3000748 u 300 0 3010012 Heavy oil kit Equipped with electrical heaters, it permits the employment of PRESS P/N burners with fuel oil of max. viscosity at 50 C: 20 E (150 mm 2 /s, cst), Type BUNKER B / USA n 5. KIT CODE u 1 0 200 300 0 3000721 Heavy oil precirculation kit This kit, used with oil with high viscosity, in maintains fuel circulation in the oil circuit for avoiding system stop at start up. KIT CODE u 1 0 200 3000749 u 300 0 3000750 Cartridge filter For cleaning heavy oil from dirty particles and impurities, it is equipped with a cartridge system for oil with 7 E viscosity at 50 C. FILTER CODE u 1 0 200 300 0 3005209 231

Burner accessories Burner support For easier maintenance, a mobile burner support has been designed, which means the burner can be dismantled without the need of forklift trucks. SUPPORT CODE u 300 0 3000731 Accessories for modulating operation To obtain modulating operation, the PRESS P/N series of burners requires a regulator. REGULATOR TYPE REGULATOR CODE u 1 0 200 300 0 RWF 40 3010211 The relative temperature or pressure probes fitted to the regulator, must be chosen on the basis of the application. PROBE TYPE RANGE ( C) (bar) PROBE CODE u 1 0 200 300 0 Temperature PT 100-100 500 C 3010110 u 1 0 200 300 0 Pressure 4 20 ma 0 2,5 bar 3010213 u 1 0 200 300 0 Pressure 4 20 ma 0 16 bar 3010214 u 1 0 200 300 0 Pressure 4 20 ma 0 25 bar 3090873 Depending on the servomotor fitted to the burner, a three-pole potentiometer (1000 W) can be installed to check the position of the servomotor. POTENTIOMETER KIT CODE u 1 0 200 300 0 3010021 232