I nstallation I nstruction Heatshrink Term ination For 3 Core Polym eric Cables 7.2 kv to 3 6 kv

Installation Instruction EPP /92

Installation Instruction EPP /02. Terminations for Screened Single Core Polymeric Insulated Cables up to 24 kv without Armour

INSTALLATION INSTRUCTION

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

QT-III Cold Shrink Silicone Rubber

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

(K),(M),(P)489TB/G Up to 42 kv

HVS S 15kV Class

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

(K),(M)430TB/G Up to 36 kv

INSTALLATION INSTRUCTION PEM1093ENG ENGLISH

Cold Shrink QS T Trifurcating Transition Splice Kit

3M Cold Shrink QT-III Silicone Rubber Termination

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

BBIT/BPTM 5-35kV Class. High Voltage, Heat-shrinkable Bus Insulation Tubing

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

INSTALLATION INSTRUCTION PEM1121ENG ENGLISH

H e a t s h r i n k P r o d u c t G u i d e

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

Heat-Shrink Indoor and Outdoor Termination SKSE

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

POWERHEAT TYPE AHT TERMINATION INSTRUCTIONS. Ref TK/AHT Issue C Date 16 August 1999

MV TERMINATIONS. INDOOR SINGLE CORE TERMINATION - ELTI-1C for polymeric cables - Slip-on termination - Modular type APPLICATION STANDARDS

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

Medium Voltage. Joints & Terminations

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

QTII (X) Series Silicone Rubber Cold Shrink Termination Kits

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

EMK-XP ElectroMelt Power Connection and End Seal Kit Installation Instructions

CS Fiber Optic Splice Case. Instruction

ELB ES. Product Installation Instructions

a Nexans company Catalogue 2008

WRSS Wraparound Repair Sleeve Installation Instructions

MEDIUM VOLTAGE TERMINATIONS

INSTALLATION INSTRUCTION PEM1367ENG ENGLISH

Heatshrink Terminations 7.2 to 36kV

Cold-shrinkable Silicone 12 kv - 24 kv - 36 kv

C Power Connection Kit

SRK02 Hard Wire Power Connection Kit. Installation, Operation and Maintenance Instructions

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

HTP PTP/ PTJ Power Connection Kit for Pipes

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

Nexans Network Solutions Div. Euromold

ELB ELB

WORLDWIDE GUARDWIRE ACCESSORIES INSTALLATION MANUAL PROVEN PERIMETER PROTECTION

Installation Instructions

3M Cold Shrink Splice Kits, QS T Series

QUICKTERM TERMINATION KIT

February Heat shrinkable tubing Insulate, identify and protect your cables

Installation instruction PEM1150ENG

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

Heat Shrinkable Tubing

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

Power & Control Cable IEC

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

Company Directive STANDARD TECHNIQUE: CA3V/3. Relating to Procedures for Making 33kV CableTerminations

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

Power & Control Cable IEC

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

BEST PRACTICE for the installation of medium voltage cable accessories

SLiC Aerial Terminal and Spiral End Seal for use with AMP* Quiet Front Terminal Blocks

High Voltage Joints and Terminations up to 72,5 kv 145 kv

WARNING. This product uses High Brightness LEDs. Direct viewing of the SMD LEDs at close range should be avoided. Keep product away from children.

22kV 425 AMP KA STYLE COUPLER 224BKA - Range

CORDAFLEX(SMK) (N)SHTÖU Tough Rubber-Sheathed Reeling Cables

Installation Instructions

Construction and Wiring Guidelines for Ergon Energy Substation Panels

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

ET-PWR-END-KIT Installation Instructions (part #JSR00)

3 TM Cold Applied Barrier Boot System

3 Reenterable Encapsulated PST Dome Closure

AutoMatrix Power Connection Kit. (1) This type 4X enclosure is intended for indoor or outdoor use primarily to. (2) May be required (see step 1).

HARNESS KIT 3-PORT ISOLATION MODULE LIGHT SYSTEM

Cable Accessories. Product Catalogue

Product Number

Branch Splice QS-2001B

OFFSHORE WIND FEASIBILITY STUDY APPENDICES Appendix C.2 Subsea Cable Data Sheets

a Nexans company Catalogue 2007

RG7H1R-1,8/3 26/45 kv RG7H1OR-1,8/3 18/30 kv

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

High Voltage Accessories up to 72.5 kv

HARNESS KIT 3 PORT ISOLATION MODULE LIGHT SYSTEM

type r remote drive for auxiliary

HARNESS KIT 3 PORT ISOLATION MODULE LIGHT SYSTEM

THORNE & DERRICK UK TEL FAX TEL FAX

Tapecoat. Application Guideline

Transcription:

Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV * PLEASE READ INSTRUCTIONS THOROUGHLY BEFORE PROCEEDING * INDOOR OUTDOOR Download free QR code scanning software on your smartphone and scan to see a jointer training video on a termination with earthing ISSUE DATE: 21.02.17 UNITS E3 CROWN WAY CROWN PARK INDUSTRIAL ESTATE RUSHDEN NORTHANTS NN10 6FD TEL: +44(0) 1933 356758 FAX: +44(0) 1933 413821 E-MAIL:info@shrinkpolymersystems.co.uk WEB: www.shrinkpolymersystems.co.uk

General Fitting Instructions * It is highly recommended that a tool suitable for the removal of the semi-conductive screen is used to provide a reliable discharge free termination screen point. See our website for training videos. * Use a propane gas torch with a soft flame * Avoid a pencil like blue flame which is caused by unregulated supply * Keep the flame on the move to ensure even shrinkage of all the materials and also helps to reduce scorching * Ensure that all components are kept clean and grease free during installation * Allow to cool before applying any mechanical strain Remove Outer Cable Sheath: VOLTAGE INDOOR L OUTDOOR L 7.2kV 650mm 700mm X 12kV 650mm 700mm LENGTH OF LUG 17.5kV 650mm 700mm BARREL + 5mm 24kV 700mm 800mm 36kV 800mm 900mm Table 1 Note:- Dimension L is a guide only. The actual length is determined by the overall geometry of the equipment. 3 Core Cable With Armour If the cable is armoured, bonding of the armours must be completed using the appropriate armour earthing kit. A) For indoor terminations (cable end box) - Order kits Ref: SPS 180, SPS 193 * B) For outdoor terminations (pole top) - Please advise conductor size and voltage. 2 * SPS 180-16-95mm at 7.2 to 17.5kV 2 SPS 193-120-300mm at 7.2 to 17.5kV (For other voltages see selection chart in general catalogue) IMPORTANT NOTICE TO PURCHASER:- Sellers and Manufacturere s only obligation shall be to replace such quantity of the product proved to be defective. Neither the Seller nor Manufacturer shall be liable for any injury, loss or damage, direct or consequential, arising out of the use or inability to use the product. Before using, User shall determine the suitability of the product for his or her intended use and User assumes all risk and liability whatsoever in connection therewith.

Bushing centre X L 100mm Bedding 100mm Armours 1. Installation Prepare the cable as shown. Note:- The L dimension should not be longer than the distance between bushing centres and base plate. De-grease and abrade the cable for a distance of 100mm below the outer sheath cut. Note:- User may wish to alter bedding and armour dimensions to suit the type of gland/earthing arrangement to be used. Fig 1 Fig 2 SEALANT TAPE 30mm 2. Screen Preparation Copper Wire Screen Apply one layer of sealant tape around the outer cable sheath 30mm below the sheath cut. Bend back each screen wires and press them into the sealant tape. Apply another layer of tape over the bent back wires. Twist together to form a conductor and bond to a suitable earth point. Note:- If cable has copper screen wires on each core, bend these back and press into the mastic tape. Just like the overall copper screen wires, twist together and bond to earth. Fig 3 ROLL SPRINGS SEALANT TAPE COPPER TAPE SCREEN 100mm COPPER BRAIDS Copper Tape Screen Secure the earth braids to the copper tape screens so that the solder block is positioned upon the cable bedding. A turn of mastic sealant tape should be applied beneath and on top of the solder block. If a constant force spring is used to connect the earth braids, the spring should preferably be positioned above the fingers of the breakout boot. These braids will either be bonded to the earth gland or other suitable earth point.

X A Remove the copper tape screen to length A+X as indicated in Table 2. Note:- If the cores are to be crossed the copper screen should be removed after the initial setting of the cores. It may be necessary to temporarily secure the copper tapes to prevent them from unwinding. Voltage 7.2kV 12kV 17.5kV 24kV 36kV A B X 130mm 185mm 240mm 310mm 500mm 110mm 165mm 220mm 290mm 480mm Lug Barrel Length + 5mm Fig 4 Table 2 B B 3. Conductive Layer Treatment Extruded Conductive Screen Layer Remove the semi-conductive screen layer using a suitable tool to dimension B+X as indicated in Table 2. Fig 5 YELLOW STRESS CONTROL TAPE Note:- It is very important that the screen is removed leaving a clean straight cut and that no scoring or damage is done to the primary insulation. We highly recommend the use of approved screen removal tools (see our website for tools and demonstration videos). It is good practice to flame brush the primary insulation and conductive screen cut, this has the effect of removing any minor surface irregularities or burrs that may be present. 10mm 5mm Fig 6 COPPER TAPE SCREEN Apply Stress Control Tape De-grease the insulation and screen using the solvent tissues provided. Remove the release paper from the yellow stress control tape. Stretch to approx. 50% width and apply the tape around the end of each core screen. Extend onto the primary insulation by 10mm and about 5mm onto the copper tape screens. Note: It may not be necessary to use all of the tape supplied.

4. Stress Control Tubes Position the stress control tubes onto each core so that the bottom of each tube extends past the yellow mastic by a maximum of 10mm. Starting at the end closest to the cable crutch, Shrink each tube one at a time keep the flame on the move to ensure an even wall thickness. Fig 7 Fig 8 Fig 9 X ROLL SPRINGS ANTI-TRACK TUBE RED SEALANT TAPE 5. Installing Cable Lugs Remove the insulation from each core to the X dimension in Table 1. Install cable lug and remove any burrs or sharp points that may be present. Preheat each Lug and wrap two layers of Red Sealant Tape over the Lug barrel and extend onto the Insulation by approx 10mm. Ensure the Tape is applied as shown. Important:- use more tape to build up the diameter to ensure tube recovers upon it and creates a moisture seal. 6. Installing The Breakout Boot Slide the three legged boot over the cores and push down into the crutch of the cable. Shrink from the shoulder of the breakout and down to the cable sheath, then from the shoulder to the cores. Apply a turn of red sealant tape around each breakout turret as shown. 7. Installing The Anti-Track Tube Position the anti-track tubes so that they cover the turrets of the breakout boot and the barrels of the lugs. Starting from the cable crutch area, Shrink the tubes in place. Keeping the flame moving to ensure an even wall thickness, ensure the tubes are fully recovered and wrinkle free. Allow the tubes to cool to hand hot and trim at the lug end with a sharp knife if necessary.

AIR CLEARANCE TO LOCAL SPEC Indoor Terminations d E d To ensure long term performance of medium voltage terminations, certain separation distances are required as indicated in Table 3. Distance (d) Phase/Phase & Phase/Ground Top of Stress Control Tube To Bottom of Lug Barrel Voltage d=(mm) E 7.2kV 12kV 17.5kV 24kV 36kV 15mm 20mm 20mm 40mm 50mm Table 3 30mm 50mm 75mm 95mm 250mm Fig 10 Note:- Bushing protection boots will be required for the majority of installations. If it is necessary to cross the cores, the cross MUST be in a screened area as shown. 8. Installation Of Rain Sheds On outdoor terminations the sheds should be fitted from the bottom up as indicated in the drawing opposite. Indoor 36kV terminations are supplied with one shed per phase and four sheds per phase for outdoor. Fig 11 d = SEE TABLE 4 80mm NUMBER OF SHEDS PER PHASE VOLTAGE INDOOR OUTDOOR 7.2kV - 1 12kV - 2 17.5kV - 2 24kV - 3 36kV 1 4 Table 4 Fig 12 200mm The first shed should be fitted at a distance 200mm from the lower edge of the anti-track tube to the edge of the shed. All subsequent sheds should be fitted at a distance of 80mm from edge to edge. Note:- It is advisable not to position rain sheds at the top of stress control tubes, re-position if necessary.

Inverted Connections If a termination is to mounted for connection from above the equipment i.e in the inverted position, sheds should be installed through 180 as shown Fig 13 MIN BENDING RADIUS r = 15xD Cable Bending Radius During installation care should be taken not to over bend the cable. In cold condition it may be necessary to gently heat the cable to prevent damage whilst bending. Fig 14 D