1 Greater Cincinnati Water Works The Great Tennyson Pump Station Mystery Imagine the result
2 OTCO Workshop August 12, 2009 Authors: Gary L. Hoffman, P.E. ARCADIS Mark Ginty, P.E. Greater Cincinnati Water Works William Barhorst, P.E. ARCADIS John Anspach, P.E. John Anspach Consulting Special Thanks: Carel Vandermeyden, P.E. Chief Engineer Greater Cincinnati Water Works Imagine the result
3 Greater Cincinnati Water Works Regional water utility serving over 1,200,000 customers over 800 square miles Supplies over 50 billion gallons of water per year Two water treatment plants (220 mgd and 40 mgd) Over 3,100 miles of water mains 24 pumping stations 32 storage tanks
4 Tennyson Pump Station Components Flow from clearwell 10 feet diameter shaft, ~170 feet deep 8 feet diameter tunnel miles long, concrete lined, built in 1951 Stand pipe for surge protection at the end of the tunnel Tennyson pump station 160 to 185 mgd capacity 6 25 mgd, expandable to 8 pumps
5 Why Can t We Pump at Least 100 MGD Consistently? Vacuum priming problem? Pump packing problem? Pump impeller problem? Partially closed valve? Standpipe problem? Access shaft problem? Tunnel blockage? Is there a hydraulic issue?
6 Why Can t We Pump at Least 100 MGD Consistently? Tunnel Hydraulics Modeled TENNYSON TUNNEL HYDRAULICS CW#1 TO PUMP STATION SHAFT HEADLOSS VS. FLOW HEADLOSS (FT) Tunnel Calibration C = 125 (based on 2005 data) FLOW TO TENNYSON (MGD) 2004 data appears to have incorrect gage calibration or incorrect reference elevation.
7 Why Can t We Pump at Least 100 MGD Consistently? Tennyson Pump Station Layout?
8 Why Can t We Pump at Least 100 MGD Consistently? NPSH Checked Out OK TENNYSON P.S. - OPTIMAL CAPACITY ALL PUMPS NPSH VS. FLOW NPSH (available) Note: Existing pump curves indicate 16 feet NPSH required at 25 MGD duty point. NPSH (FT) NPSH required with 1.3 Factor of Safety NPSH (required) POTENTIAL CAVITATION ZONE FLOW TO TENNYSON PS (MGD) CALCULATED LIMIT OF PUMPING
9 Why Can t We Pump at Least 100 MGD Consistently? What About Surge? Measured on gauge 16.5 ft below pump centerline
10 Why Can t We Pump at Least 100 MGD Consistently? Hydraulic Transient Analysis Performed Candidates for Surge Problems Due to: 2.3 mile tunnel with no branches to absorb pressure waves One source Clear Well at Richard Miller WTP One Surge tank at the Pump Station open to atmosphere Observations of the Surge Well level dramatically changing during Pump on/off operation added to the hypothesis that surge may be the problem
11 Why Can t We Pump at Least 100 MGD Consistently? Start-up Modeled with Fourth Pump Pump CS-2 Start-up Flow Suction (mgd) (MSL ft.) steady 520 Pump CL Atm. Pressure 33.25
12 Why Can t We Pump at Least 100 MGD Consistently? NPSHA Still OK Under Surge Pump Tests Sept 2007 NPSH Available for Pump Starting Table 5 Tennyson Pump Station NPSH Available During Pump Starting Pump Clearwell HGL Suction HGL NPSHA Before Total Starting Before Start (ft) Before Start (ft) Start (ft) Surge (ft) Minimum NPSHA During Start (ft) 4th Pump (CS-2) 5th Pump (CS-3) 6th Pump* (CS-1) * -3.8* 28.9* -9* 23.7* - *projected from model
13 Narrowed Down to Three Pump Tests May 16 and 17 Purpose of the Pump Test on May 16 and 17, 2008 Was to Evaluate the Remaining Three Identified Possibilities for the Limited Capacity: - Starting Procedure? - Pump Wear? - Air Intrusion?
14 Narrowed Down to Three Pump Tests May 16 Shut-off Head Test Design Actual Pump PSI PSI KW EH EH EH-3 * CS CS CS *est. Shut-off Head Testing Performed to: Determine if adequate pressure available Gauge pump wear Manual Prime and Air Relief, Results showed: Adequate Pressure Minimal Wear
15 Narrowed Down to Three Pump Tests May 17 Attempt to Bring All 6 Pumps Online under Two Scenarios Scenario 1 Start EH Pumps under normal conditions and bring CS pumps online by manually isolating all the prime to the pump and bleed air from casing; keep cone check closed until adequate pressure is developed and then open valve. Scenario Two Have EH Pumps running; bring CS pumps on during normal operation (i.e., normal priming condition and no air relief from casing) except cone check valve held closed until adequate pressure reached.
16 Narrowed Down to Three Pump Tests May 17 Scenario 1 Scenario 1 Controlled Valves, manual prime and air relief, started CS-1, CS-2 and CS-3 in that order. Success! MGD OBSERVATIONS EH MGD EH MGD EH MGD CS MGD CS MGD CS MGD -Starting Pumps CS-2 and CS-3 was noisy and pressures on suction side oscillated before steady-state -CS-3 was the last pump turned on and discharge pressure gauge dropped as low as 20 psi before stabilizing at 84 psi and opening valve
17 Narrowed Down to Three Pump Tests May 17 Scenario 1 Shut-off Head Test May 16 May 17 May 17 Pump KW KW Suction below CL CS ft. CS ft. KW directly correlates to specific gravity of liquid pumped. CS-2 and CS-3 pumping something other than water actually a water and air mixture. Air is getting into the casing. CS ft.
18 Narrowed Down to Three Pump Tests May 17 Scenario 2 Scenario 2 Controlled Valves, but normal priming, no air relief, started CS-3, attempted CS-1 and CS-2 in that order. With CS-3 running, CS-1 was started against a closed valve and after 4 minutes of pumping, did not develop enough pressure to overcome the discharge pressure and was then shutdown. The test was halted with the three EH Pumps running and CS-3 running. Result: only four of six pumps were able to be started under this scenario.
19 Narrowed Down to Three Pump Tests May 17 Why is air in the pump casing? Priming system? Packing? Coming out of solution?
20 Narrowed Down to Three Pump Tests May 17 How do the hydraulic conditions affect air volume in pump? Pump Starting Clearwell HGL Before Start (ft) Suction HGL Before Start (ft) 4th Pump (CS-2) 5th Pump (CS-3) 6th Pump* (CS-1) 7th Pump* (Prop. EHS-4) * -3.8* 6.0* -5.0*
21 Narrowed Down to Three Pump Casing Full of Water Ideal conditions usually when no more than three pumps running and air relieved.
22 Narrowed Down to Three Pump Casing Half Water and Half Air Even with priming system, not likely to be better than this with 4 pumps running.
23 Narrowed Down to Three Pump Casing Full of Air With 4 or more pumps running, suction HGL below pump centerline, is priming system able to pull water into casing or is it a straw in the ocean?
24 Narrowed Down to Three Air is the Problem What s next? Review priming set-up and capacity Evaluate packing Recommend automatic air relief on top of casing Evaluate pump start-up sequence and valve opening timing
25 Improvements In Progress Original Prime Location New Prime Location
26 Thank You
Pump Analysis 1) Capacity - volume of liquid pumped per unit of time 2) Head
Pump Analysis 1) Capacity - volume of liquid pumped per unit of time 2) Head - several terms are used as shown in the attached Figures Static Suction Head, h s The difference in elevation between the suction
More informationLACT MEASUREMENT. Total Head = Or PSI = S.G. 2.31
LACT MEASUREMENT Prepared By: Ken A. Steward. P.E. Linco-Electromatic, Inc. 4580 West Wall Street Midland, Texas 79703 The Operation of L.A.C.T. Units The simplest approach to the understanding of the
More informationPumping Station. Marisa Handajani
Pumping Station Marisa Handajani Function To lift or to elevate the liquid from a lower elevation to an adequate height at which it can flow by gravity or overcome the hydrostatic head Applications: 1.
More informationDESIGN, OPERATION & MAINTENANCE OF L.A.C.T. UNITS
DESIGN, OPERATION & MAINTENANCE OF L.A.C.T. UNITS INTRODUCTION The two most common methods of measuring the volume of petroleum liquids are tank gauging and liquid metering. The problems associated with
More informationAPPENDIX C. City of Santa Rosa Pump Replacement Evaluation at Stations S14 and S13 TM July 9, 2013
APPENDIX C City of Santa Rosa Pump Replacement Evaluation at Stations S14 and S13 TM July 9, 2013 TECHNICAL MEMORANDUM DATE: July 9, 2013 Project No.: 405-02-11-31 TO: Norman Amidon, City of Santa Rosa
More informationUnderground Tank Applications Installation Guide
IF Underground Tank Applications Installation Guide Coro-Flo Pumps Background: Because of the environmental problems caused by traditional fuels such as gasoline and diesel, the use of alternative fuels,
More informationPump Control Ball Valve for Energy Savings
VM PCBVES/WP White Paper Pump Control Ball Valve for Energy Savings Table of Contents Introduction............................... Pump Control Valves........................ Headloss..................................
More informationSERVICE THE GORMAN-RUPP COMPANY P.O. Box 1217 MANSFIELD, OH FX
GORMAN-RUPP AT YOUR SERVICE THE GORMAN-RUPP COMPANY P.O. Box MANSFIELD, OH. 90 9..0 FX 9.. EMAIL GRSALES@GORMANRUPP.COM How To Read Pump Performance Curves The subject of this bulletin covers the reading
More informationFuel System Diagnosis
Page 1 of 6 2001 Chevrolet Express Express, Savana (VIN G) Service Manual Engine Engine Controls - 5.0L and 5.7L Diagnostic Information and Procedures Document ID: 720867 Fuel System Diagnosis Circuit
More informationInstallation, Operation, and Maintenance Manual Outdoor Glycol Feed System JWOP /055/100
Installation, Operation, and Maintenance Manual Outdoor Glycol Feed System JWOP-53-030/055/100 Rev. 1 3/21/11 K.G. Type - John Wood #JWOP-53-030/055/100, Outdoor Glycol Feed System Capacity 30/55/100 Gallons
More informationPositive Displacement Rotary Lobe Pumps
Positive Displacement Rotary Lobe Pumps Three Great Lines G Series: General Use R Series: Sludge, Mud & Slurries C Series: Chemicals & Corrosives Is a LobeStar rotary pump right for you? 1). Are you pumping
More informationMinuteman Vertical Pumps
Description: Condensate Pumps Type: Vertical Centrifugal Pumps Horsepower: /3 to /2 HP GPM: 0 to 37 PSIG: 0-35 Overview: vertical pumps are the workhorse of the NES pumps product offering. All minuteman
More informationVariable Speed Pumping
Variable Speed Pumping Jim Vukich Application Engineer ITT Corp. Malvern, PA Why Do It? Why Do It? Flow-Matching Minimize Starting & Stopping Flexibility Different Discharge Points, Flows Changing Conditions
More informationPumps and Maintenance
Pumps and Maintenance Questions 1) Where would you find information on when to lubricate a pump? 2) What problems can develop if too much grease is used in lubricating an electric motor? 3) Why should
More informationCA-NV AWWA 2013 Fall Conference. Chemical Metering Pump, Accessories and Systems. By Richard Hopkins Hopkins Technical Products, Inc
CA-NV AWWA 2013 Fall Conference Chemical Metering Pump, Accessories and Systems. By Richard Hopkins Hopkins Technical Products, Inc Mathematics Equation #: 1 for Chlorine Flow(MGD) x Dosage(mg/l) x 3.785/gal
More informationAUTOGAS 150 SERIES PUMPS INSTALLATION GUIDELINES FOR UNDERGROUND TANK APPLICATIONS
Application Bulletin A Unit of IDEX Corporation No. 13 June 21 AUTOGAS 1 SERIES PUMPS INSTALLATION GUIDELINES FOR UNDERGROUND TANK APPLICATIONS CORKEN, INC. A Unit of IDEX Corporation P.O. Box 12338, Oklahoma
More informationWater Treatment Plant Maintenance Considerations. Operation and Maintenance. Types of Maintenance 5/1/15
Water Treatment Plant Maintenance 1 Operation and Maintenance Purpose of O&M maintain design functionality (capacity) restore the system components to their original condition and thus functionality. Effective
More informationFLUID FLOW Introduction General Description
FLUID FLOW Introduction Fluid flow is an important part of many processes, including transporting materials from one point to another, mixing of materials, and chemical reactions. In this experiment, you
More informationOperations Manual. Automated Fuel Maintenance System FUEL TECHNOLOGIES INTERNATIONAL
Operations Manual Automated Fuel Maintenance System FTI-10A & 20A FUEL TECHNOLOGIES INTERNATIONAL Replacement Manuals Available on Website: www.fueltechnologiesinternational.com 07/15/2015 Rev E Fuel Technologies
More informationPV Series E, J, & L Piston Pump Installation Tips and Procedures
Sept. 9, 2005 PV Series E, J, & L Piston Pump Installation Tips and Procedures Oil recommendations Do not use automatic transmission fluid (ATF), bio-degradable oil, or fire resistant fluids due to the
More informationCHAPTER 7 PUMPING SYSTEM DESIGN
CHAPTER 7 PUMPING SYSTEM DESIGN 7-1. FORCE MAIN HYDRAULICS. a. General. The pipeline which receives waste-water from a pumping station, and conveys it to the point of discharge, is called a force main.
More informationWater Hammer. Tackling Transient Events at San Jose Water Company. Jake Walsh, P.E. Andy Yang, P.E. October 21, 2014
Water Hammer Tackling Transient Events at San Jose Water Company Jake Walsh, P.E. Andy Yang, P.E. October 21, 2014 Introduction [map of SJWC] Map data 2014 Google Introduction What is Water Hammer? Water
More informationInstallation, Operating, Maintenance and Safety Instructions for CW332 Pressurised water system for boats 24 volt d.c.
24V DC-CW332 DOC531/11 Installation, Operating, Maintenance and Safety Instructions for CW332 Pressurised water system for boats 24 volt d.c. To obtain the best performance from your Pressurised water
More informationEJseries. Self-Priming Centrifugal Pumps
EJseries Self-Priming Centrifugal Pumps T w w w. e u r o f l o p u m ps. c o m EJseries - Coding System Eg. EJS -11 XX XX XX EJT - XXX XX-XXX XX XXXX XXXX Series EJS = Shaft (bare) pumps EJT = Large Flow
More informationS200-P Series Centrifugal Fire Pumps Operation and Maintenance Instructions
S200-P Series Centrifugal Fire Pumps Operation and Maintenance Instructions Table of Contents Read through the safety information and operating instructions carefully before using your S200-P Series Fire
More informationscfm (6.5 psi) Max HP
Direct Drive, Energy Efficient, High- Speed Turbo Blowers Alvin C. Firmin, PE, BCEE Presented at: PNCWA 2009 Annual Conference Boise, Idaho September 16, 2009 Introduction of Blower Technologies PD Blowers
More informationAquaBoost Packaged Systems
Constant Pressure. Plain and Simple. AquaBoost Packaged Systems BUILT WITH THE QUALITY YOU VE COME TO EXPECT FROM GOULDS WATER TECHNOLOGY BRAQBST AQUABOOST P U M P S T A T I O N S AquaBoost Pump Stations
More informationWater Residuals Management Presented by Michael F. Graves, PE CP&Y Co-Authors Larry L. Hare, PE Oklahoma City J. Dustin Segraves Oklahoma City
Water Residuals Management Presented by Michael F. Graves, PE CP&Y Co-Authors Larry L. Hare, PE Oklahoma City J. Dustin Segraves Oklahoma City October 2014 Discussion Topics Project Background Thickening
More informationNECO Pumping Systems
INSTALLATION OPERATION & MAINTENANCE INSTRUCTIONS For Your NECO Pumping Systems Fuel Oil Transfer System THIS COMPLETELY ASSEMBLED, TESTED, PACKAGED SYSTEM IS OF THE HIGHEST QUALITY AND DESIGN. TO OBTAIN
More informationKEY FEATURES. Product Overview. Product Line Drawing
Main Valves Options Model 106-C 106-PG-C Globe KEY FETURES Solves high pressure drop problems Controls variable flows & vibration Significantly reduces noise Self-contained actuators not required Customizable
More informationValve and Piping Replacements Various Facilities Deer Island Treatment Plant
Massachusetts Water Resources Authority Presentation to MWRA Board of Directors Valve and Piping Replacements Various Facilities Deer Island Treatment Plant Richard Adams Manager, Engineering Services
More informationINSTALLATION AND OPERATING INSTRUCTIONS MANUAL Owner s manual FIXED SPEED BOOSTER SETS SERIES:
INSTALLATION AND OPERATING INSTRUCTIONS MANUAL Owner s manual FIXED SPEED BOOSTER SETS SERIES: CPD: Two pumps CPT: Three pumps CPC: Four pumps Page 1 of 15 INSTRUCTIONS FOR INSTALLATION AND USE 2009 CAREFULLY
More informationFIRE PUMPS F AI LISTED R LISTED N K S MOR S E P U IT Y S Y S T E M CE R T IF IE D
IS O 9 0 0 1 IT Y S Y S T E M R LISTED RBA N K S MOR S E P U MP C F AI LISTED UAL T IF IE D R CE R Q FIRE PUMPS HORIZONTAL SPLIT CASE FIRE PUMP SYSTEM DIESEL ENGINE DRIVEN 1 4 5 2 3 6 7 8 1. Fuel Tank,
More informationTo ensure proper installation, digital pictures with contact information to before startup.
Check List for Optimal Filter Performance? There should be no back-pressure on the flush line. A 1 valve should have a 2 waste line, and 2 valve should have a 3 waste line. Do not use rubber hosing or
More informationTECHNICAL INFORMATION Bulletin
Peerless Pump Company 2005 Dr. M.L. King Jr. Street, P.O. Box 7026, Indianapolis, IN 46207-7026, USA Telephone: (317) 925-9661 Fax: (317) 924-7338 www.peerlesspump.com www.epumpdoctor.com TECHNICAL INFORMATION
More informationColumbus Collection and Treatment System Real Time Wet Weather Operational Implementation
Columbus Collection and Treatment System Real Time Wet Weather Operational Implementation Presenters Ed Heyob, CDM Smith Automation Engineer Kim Brown, JPWWTP Supervisor II Existing Collection System Rhodes
More informationPressure Distribution. Western Canada Onsite Wastewater Management Association
Pressure Distribution EFFLUENT DISTRIBUTION Get even distribution Space the doses Layout the distribution system Make choices for: piping, orifices, volumes Use worksheets for calculations Dose or flush
More informationBA100K Diesel Driven Dewatering and Sewage Pump Max. 836 US GPM, Max. 73 ft. / 31 PSI
Pump specifications: Type... BA100K D193 Max. flow... 836 US GPM (190 m 3 /hour) Max. pressure... 73 ft. / 31 PSI (22 mwc) Solids handling... 3,23 (82 mm) Impeller type... Channel impeller Priming system...
More informationRS Multi-Stage, Ring Section Pumps
RS Multi-Stage, Ring Section Pumps Technical Specification Pages This page left intentionally blank. 1.0 Overview. The RS Series is Carver s multi-stage pump for fluids at moderate to high pressures. The
More informationCase Study. Metropolitan Water Board. Siewert Equipment. Centrifugal Water Pump Repair MWB Eastern Pump Station. David D Angelo Water System Manager
Case Study Metropolitan Water Board & Siewert Equipment Centrifugal Water Pump Repair MWB Eastern Pump Station Bruce Collins NY Service Manager Siewert Equipment Barry Erickson, Ph.D Pump Improvement Engineer
More informationFuel System Diagnosis
Page 1 of 9 1999 Chevrolet Express Express, Savana (VIN G) Service Manual Engine Engine Controls - 5.0L and 5.7L Diagnostic Information and Procedures Document ID: 412957 Fuel System Diagnosis Circuit
More informationRAIN BIRD - AQUAGATOR AQUAGATOR INSTALLATION & TROUBLESHOOTING MANUAL
AQUAGATOR INSTALLATION & TROUBLESHOOTING MANUAL Cozz GT27069-A Revised July 2002 P/N 632360 AQUAGATOR TABLE of CONTENTS DESCRIPTION PAGE INTRODUCTION....... 1 SECTION 1 - PRE-INSTALLATION REQUIREMENTS.
More informationNMSU FIRE DEPARTMENT FIRE PUMP ACCEPTANCE TEST
Date Documents Submitted: Log No.: File No.: Plan Examiner: Permit No.: Property Information Building Name: Building Address: Building Manager's Name: Building Manager's Phone: Fax: System Designer/Contractor
More informationQuality Value Assurance
Pump Selection Guide Quality Value Assurance In the beginning From it s inception in 1990 with one man in a service van, to the industry leader in innovative dairy solutions that DariTech is today, we
More informationEND SUCTION CENTRIFUGAL PUMPS
OWNERS GUIDE TO INSTALLATION AND OPERATION FW000 009 Supersedes 07 END SUCTION CENTRIFUGAL PUMPS READ THESE INSTRUCTIONS CAREFULLY Read these installation instructions in detail before installing your
More informationSuccess Case Water and Wastewater
Influent Pump Station Solves Surge Issue with Custom Engineered Motors Authors: James M. Scott, Senior Project Coordinator - Large Machines, WEG Electric Corp.; Gerardo Elias Rodriguez, North and Central
More informationPenn Valley Pump Company Design Information for Double Disc Pumps
Penn Valley Pump Company Design Information for Double Disc Pumps INTRODUCTION The Penn Valley Double Disc Pump utilizes a unique principle of operation whereby the discs perform the duties of pumping
More informationEVALUATION OF THE AQUA-DUK PUMP
Roscommon Equipment Center Program Project No. 50 EVALUATION OF THE AQUA-DUK PUMP Published March 1986 Reviewed and Reprinted March 1987 Reformatted for Web Page November 1998 Northeast Forest Fire Supervisors
More informationITT. Goulds Pumps. AquaForce PRESSURE BOOSTING SIZING GUIDE. Engineered for life. Building and Municipal Applications.
Goulds Pumps AquaForce PRESSURE BOOSTING SIZING GUIDE Building and Municipal Applications Goulds Pumps is a brand of ITT Corporation. www.goulds.com Engineered for life AquaForce GENERAL INFORMATION The
More informationPeerless Pump FULL PRODUCT LINE. Brochure B Sterling Fluid Systems (USA), Inc.
Peerless Pump FULL PRODUCT LINE Sterling Fluid Systems (USA), Inc. Brochure B-1270 Vertical Industrial and Process Axial and Mixed Flow for Large Volume Pumping Encased (Can ) Water and Process Liquid
More informationSP SERIES SELF-PRIMING MAG DRIVE
SP SERIES SELF-PRIMING MAG DRIVE spend less time waiting. and more time pumping. year Big on power yet short on energy consumption, the SP Series from Finish Thompson is one of the most versatile and economical
More informationPUMP PERFORMANCE TEST
Performance by Weis Fire & Safety as Per NFPA 1911-2012 and ISO Standards Recommended On Rated and n-rated Fire Service Performed With A Draft Commander 3000 Using Clean Clear Water 1911-86 INSPECTION,
More informationTroubleshooting Pumps in a System
Troubleshooting Pumps in a System First of Two Parts by Ray Hardee In the last three columns ("Troubleshooting Piping Systems" in the September, October and November 2015 issues of Pumps & Systems, read
More informationInstallation & Operating Manual
Installation & Operating Manual 25INV-M 1/17 Edition NV Series Vertical Booster Stainless Steel Multistage Centrifugal Pump Congratulations On Your Choice In Purchasing This Webtrol Pump Its Quality is
More informationBLOWERS EXHAUSTERS. Positive Displacement blowers (PD), as the name implies, compress CONTINENTAL INDUSTRIE
COMPARISON Blowers Exhausters Page 1 of 6 Technical comparison... P 4 Positive Displacement blowers (PD), as the name implies, compress an incremental volume of gas between the inlet and outlet of the
More informationModel 133 Models 134 & 135 AURORA 130 SERIES SINGLE STAGE TURBINE TYPE PUMPS
Model Models 4 & AURORA 0 SERIES SINGLE STAGE TURBINE TYPE PUMPS WWW.AURORAPUMP.COM AURORA 0 SERIES Single Stage Turbine Type Pumps Capacities to 0 G.P.M. Heads to 700 Ft. Temperatures to F A Pioneer in
More informationHALLMARK INDUSTRIES INC.
4 Deep Well Submersible Pump Part # Power Flow M 3 /H 0 1 2 2.6 3.2 3.6 4.2 4.5 Weight HP Volt Amp Flow (GPM) 0 4.6 9.1 11.5 14 16 18.4 20 (lbs) MA0343X-4 1/2 115 6.5 Head (ft) 154 142 120 103 80 56 27
More informationSD Series. SD, SDA, SDL Series Heavy Duty Submersible Dewatering and Drainage Pumps 415V. Dewatering Pumps. 3 Year Warranty!
SD Series SD, SDA, SDL Series Heavy Duty Submersible Dewatering and Drainage Pumps 41V Dewatering Pumps 3 Year Warranty! SD Series Heavy Duty Submersible Dewatering Drainage Pump 41V Aquaplus SD Series
More informationabcdef EJseries Self-Priming Centrifugal Pumps where innovation flows SNG
abcdef SNG 9 where innovation flows Self-Priming Centrifugal Pumps EJseries www.euroflopumps.com Coding System EJseries Series EJS = Shaft Sewage Bare Pumps EJT = Large Flow Trash Pumps EJU = High Head
More informationElectronic Control Valves
131 Series (Full Internal Port) 631 Series (Reduced Internal Port) MODEL Electronic Control Valves Model 131-01/631-01 Simple Proven Design Quality Solenoid Pilot Controls Ideal For SCADA Systems Multi-Function
More informationS200-G Series Centrifugal Fire Pumps Operation and Maintenance Instructions
by Waterous S200-G Series Centrifugal Fire Pumps Operation and Maintenance Instructions Table of Contents IL3771 Read through the safety information and operating instructions carefully before using your
More informationFuel System Diagnosis
Page 1 of 6 2001 Chevrolet Malibu Malibu (VIN N) Service Manual Engine Engine Controls - 3.1L (LG8) Diagnostic Information and Procedures Document ID: 704675 Fuel System Diagnosis System Description When
More informationAuditing Water System Pumps for Efficient Operation. Tyler Clary, P.E. City of Vancouver
Auditing Water System Pumps for Efficient Operation Tyler Clary, P.E. City of Vancouver tyler.clary@ci.vancouver.wa.us City of Vancouver System Fourth largest water utility in Washington State Service
More informationANALYSIS OF BREST-OD-300 SAFETY DURING ANTICIPATED OPERATIONAL OCCURRENCES
ANALYSIS OF BREST-OD-300 SAFETY DURING ANTICIPATED OPERATIONAL OCCURRENCES D.V. Didorin, V.A. Kogut, A.G. Muratov, V.V. Tyukov, A.V. Moiseev (NIKIET, Moscow, Russia) 1. Brief description of the aim and
More informationHydraulic System (i.e. Brakes & Cowl Flaps)
Hydraulic System (i.e. Brakes & Cowl Flaps) B-17 Technical Session for Flight Engineers 7/8/2017 (with post meeting revisions 7/9/2017) The B-17G (specifically our Texas Raiders, TR) has a hydraulic system
More informationUsing an SMC-50 Solid-State Smart Motor Controller for Pump Protection
Using an SMC-50 Solid-State Smart Motor Controller for Pump Protection William Bernhardt and Richard Anderson, Rockwell Automation Pump system protection comes in many methods, from preventing water hammer
More informationBASIC FOAM FIREFIGHTING OPERATIONS Red and Green Systems
BASIC FOAM FIREFIGHTING OPERATIONS Red and Green Systems Page 730.60 Each of the Red and Green Foam Systems consists of one 3000 gallon foam concentrate storage tank, two foam concentrate pumps, a balanced
More informationGT-Suite European User Conference
GT-Suite European User Conference E-Charging on a High Performance Diesel engine D. Peci, C. Venezia EMEA Region - Powertrain Engineering Powertrain Research&Technology Frankfurt, Germany October 26th,
More information50-01 (Full Internal Port) (Reduced Internal Port) Pressure Relief. & Pressure Sustaining Valve MODEL
50-01 650-01 & 1 Hytrol (Main ) 2 X42N-2 Strainer & Needle 3 CRL Control Accurate Pressure Control Optional Check Feature Fast Opening to Maintain Line Pressure Slow Closing to Prevents s Completely Automatic
More informationApplication & Reference Data Typical Specifications. Section 914 Vertical Turbine Fire Pump
Section 914 Page 101 Supersedes Section 913 Page 101 Dated November 1, 199p Application & Reference Data Typical Specifications Section 914 Section 914 Page 102 Supersedes Section 913 Page 102 Dated November
More informationCity of St. Pete Beach Model Capacity Report Addendum
Model Capacity Report - Addendum City of St. Pete Beach Model Capacity Report Addendum Prepared for: City of St. Pete Beach 155 Corey Avenue St. Pete Beach, FL 33706 Prepared By: Kimley-Horn and Associates,
More informationAUTOMATIC CONTROL VALVES. TIS asia
AUTOMATIC CONTROL VALVES VALVES DEDICATED TO THE WATER DISTRIBUTION NETWORK AND HYDROPOWER SECTOR WE DO NOT SELL JUST VALVES, WE SELL A SOLUTION FOR THE EFFICIENCY OF THE WATER NETWORK TIS asia MADE IN
More informationWater Treatment Plant Historical Timeline
Water Treatment Plant Historical Timeline 1874 The citizens of the the Village of Evanston, with a population of 3500, started to build a communal water system. The system consisted of a 16 inch intake
More informationExcellence In Fluid Control Since 1975
Excellence In Fluid Control Since 1975 Company Profile HVC Engineering & Technologies, is engaged in the manufacturing of Hydraulic Valves and Systems since 1975; the Industrial Hydraulic Valves & Systems
More informationSMX. Self-priming magnetic drive pumps Magnetic drive pumps with an excellent balance of features and performance GFRPP
SMX s e r i e s Self-priming magnetic drive pumps Magnetic drive pumps with an excellent balance of features and performance Self-priming magnetic drive pumps Main material GFRPP The SMX is a horizontal
More informationBB-4 DIESEL BB-4-D902 VEHICLE MOUNT HIGH PRESSURE 4-STAGE FIRE PUMP. Applications. Features and Benefits DATA SHEET
DATA SHEET BB-4 DIESEL BB-4-D902 VEHICLE MOUNT HIGH PRESSURE 4-STAGE FIRE PUMP The WATERAX BB-4-D902 pump pairs a reliable high performance 4-stage pump end with a powerful Kubota D902-E4B 3-Cylinder Fuel
More informationOceanic. 4 Deep Well Submersible Pump Performance chart. Features & Technical Specifications: Part # MA0343X-4. Head (ft) MA0343X-4A.
Oceanic Power Flow M3/H 0 1 2 2.6 3.2 3.6 4.2 4.5 Weight Volt mp Flow (GPM) 0 4.6 9.1 11.5 14 16 18.4 20 (lbs) M0343X-4 1/2 115 6.5 Head (ft) 154 142 120 103 80 56 27 5 26 M0343X-4 1/2 230 3.3 Head (ft)
More informationBA150E Diesel Driven Dewatering and Sewage Pump Max US GPM, Max. 115 ft. / 50 PSI
Pump specifications: Type... BA150E D285 Max. flow... 2091 US GPM (475 m 3 /hour) Max. pressure... 115 ft. / 50 PSI (35 mwc) Connections... 6 (DN 150) Solids handling... 3,15 (80 mm) Impeller type... Open
More informationSeries
MTH PUMPS 15 25 26 17 27 Series Flexible Coupled Capacities to 15 GPM Heads to 115 Feet Low NPSH Requirements Page 1-19 15 17 25 26 27 LIMITATIONS Discharge Pressure Seal Pressure* Suction Pressure (Min.)
More informationHot-Tap Machines. Specification Sheet TBL Bulletin nº: SPECIFICATION FOR TBL-0322 TAPPING MACHINE Tapping Range 1 through 6
Bulletin nº: 2009.602.00 Specification Sheet TBL-0322 SPECIFICATION FOR TBL-0322 TAPPING MACHINE Tapping Range 1 through 6 Boring Bar Travel 32 (813 mm) Standard Auto Feed 0.006 per rev. (0.15 mm per rev.)
More informationECH 4224L Unit Operations Lab I Fluid Flow FLUID FLOW. Introduction. General Description
FLUID FLOW Introduction Fluid flow is an important part of many processes, including transporting materials from one point to another, mixing of materials, and chemical reactions. In this experiment, you
More informationMemorandum October 5, 2017
614 Magnolia Avenue Ocean Springs, Mississippi 39564 228.818.9626 Memorandum October 5, 2017 To: Gary Miller, U.S. Environmental Protection Agency From: David Keith, John Laplante, Matt Henderson, and
More informationMark Howell Florida Crystals September 26, 2013
Flat Land, Low Level Farm Drainage Mark Howell Florida Crystals September 26, 2013 Pumping Head Pump Size Power Discharge Arrangement Problems To Avoid Pump Stations Head From The Field To The Pump Start
More informationPUB-PMPFL rev. 4/2007
Subaru Robin is a division of Fuji Heavy Industries Ltd., headquartered in Tokyo, Japan. Fuji is a global manufacturing company of diversified premium brand products. Total annual sales exceed $13 billion.
More informationSelection Chart. SC Series 6 inch (150mm) Submersible Borehole Pumps PERFORMANCE DATA SC65 SC50 SC30 SC18 TOTAL HEAD FEET Q (LITRES PER MINUTE)
PERFORMANCE DATA Selection Chart TOTAL HEAD FEET 450 400 350 300 250 200 150 100 50 0 GALLONS PER MINUTE 0 50 100 150 200 250 300 SC18 SC30 SC50 SC65 0 200 400 600 800 1000 1200 1400 Q (LITRES PER MINUTE)
More informationTransportation Highway Engineering Conference February 24, 2015
Transportation Highway Engineering Conference February 24, 2015 Today s Agenda Move Illinois status Jane Addams Memorial (I-90) Rebuilding and Widening Project Building a 21 st century corridor Incorporating
More informationDTC P0174 Fuel Trim System Lean Bank 2
2000 Chevrolet/Geo S10 Pickup - 4WD DTC P0174 Fuel Trim System Lean Bank 2 Circuit Description In order to provide the best possible combination of driveability, fuel economy, and emission control, the
More informationSTRUCTURE 5A PURPOSE
STRUCTURE 5A This structure is a six unit pumping plant located on the south side of U.S. Highway 441 and Canal 51 (West Palm Beach Canal) between the canal and the borrow canals of Levees 7 and 40 about
More informationZD 600/900 COMPACT COMBI SILENT
Pump specifications Type ZD 900 ZD 600 Design with gear casing with gear casing Max Capacity 95 m³/h 65 m³/h Max Discharge head 20 mwc 20 mwc Max Suction head 9.6 mwc 9.6 mwc Noise level (Diesel) 47 db(a)
More informationMark 5108 Series. Back Pressure Regulating Valves Mark 5108 Series. Back Pressure Regulating Valves. Valve Features. Operation
Mark 5108 Series Back Pressure Regulating Valves In many liquid piping systems, it is vital that line pressure is maintained within relatively narrow limits. The Mark 5108 is designed to do just that.
More informationSERIES PC INSTRUCTION AND OPERATION MANUAL
MEGGA SERIES PC INSTRUCTION AND OPERATION MANUAL Models PCT and PCF Close-coupled and frame-mounted single-stage horizontal end-suction pumps. WARNING: Read this manual before installing or operating this
More informationSIHI prime - Side Channel Pumps Self-priming, segmental type
SIHI prime - Side Channel Pumps Self-priming, segmental type AKH-X 1201 3606 TECHICAL DATA Capacity: Delivery head: Speed: from 0.4 up to 7.5 m³/h from 10 up to 242 m 1450 rpm (max. 1800 rpm) Temperature:
More informationFire Water Utility 2002 Training Manual Raw Water Storage Area
Effective: 10/21/11 Page 1 of 17 Rev. by J. Shively Fire Water Utility 2002 Training Manual Raw Water Storage Area Document Revision Change Table Revision Number Revision Description Revised By Revision
More informationPDF-A Self-priming magnetic drive pumps. SMX series
PDF-A 0067-02 SMX series Versatile self-priming magnetic drive pump with enhanced durability under abnormal operation The SMX is a horizontal self-priming magnetic drive pump made from reinforced plastic.
More information6X6 3-Stage Jet Pump. Safe Operating Procedures
6X6 3-Stage Jet Pump Safe Operating Procedures Suction Hose Fuel Tank Siphon Valve Control Panel Starting Lever Suction Fitting Jet Pump Major Components Daily Maintenance Operations Visually inspect to
More informationInstallation, Operation & Maintenance Instructions for MF Series Solution Feeders
INDUSTRIES LIMITED Installation, Operation & Maintenance Instructions for MF Series Solution Feeders Startup Procedure ) Close isolation valve between feeder and system connection point 2) Fill reservoir,
More informationFuel System Diagnosis
Page 1 of 8 Document ID# 104786 1997 Chevrolet Corvette Feedback Print Fuel Diagnosis (1) Fuel Pressure Gauge Bleed Hose (2) J 37287 Fuel Line Shut-off Adapters (3) Return Pipe (4) Feed
More informationTanker Off-Load Test: 5,000 gallon Tanker with a 500 gpm Pump
Tanker Off-Load Test: 5,000 gallon Tanker with a 500 gpm Pump Granby Fire Department Granby, Massachusetts The Tanker Granby FD s Tanker 1 is a 5,000-gallon tanker that is outfitted with an 8-inch rear
More informationWater Storage Systems
Water Storage Systems Water Storage Tanks Types: Gravity or Elevated Ground Storage Hydropneumatic Water Storage Tanks Ground Storage Hydropneumatic Elevated Storage 1 Diurnal Flow Pattern Peak Demand
More informationA ZURN Company Rotovalve Cone Valve 20 Questions
Rodney Hunt A ZURN Company Rotovalve Cone Valve 20 Questions Rodney Hunt Rotovalve Cone Valve 20 Questions 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. What is a cone valve? How
More information