Installation Operation & Maintenance Manual. Rotary Piston Vacuum Pumps

Size: px
Start display at page:

Download "Installation Operation & Maintenance Manual. Rotary Piston Vacuum Pumps"

Transcription

1 Installation Operation & Maintenance Manual Rotary Piston Vacuum Pumps Part No P02 Rev. A / January 2018

2 ROTARY PISTON VACUUM PUMPS TABLE OF CONTENTS CUSTOMER SERVICE 5 CONTACT INFORMATION 5 ORDER INFORMATION 5 INTRODUCTION 6 SAFETY 6 THEORY OF OPERATION 7 STORAGE 8 INITIAL FREIGHT RECEIPT AND INSPECTION 8 INSTALLATION 8 OVERVIEW 8 UNPACKING 8 LIFTING 8 LOCATION 9 MOUNTING 9 VENTILATION 9 ELECTRICAL PREPARATION 9 PIPE CONNECTION AND SIZING 10 INLET PIPING 10 DISCHARGE PIPING 10 COOLING WATER PIPING 11 COOLING CAPACITIES AND PORT SIZES 11 START-UP PROCEDURES 12 SHUT DOWN PROCEDURES 16 MAINTENANCE 17 PUMP BEARING LUBRICATION 17 MOTOR BEARING LUBRICATION (WHERE REQUIRED) 17 INLET FILTER (IF INSTALLED) 17 SEAL FLUID 17 OIL CHANGE PROCEDURE 18 STANDARD SYSTEM CAPACITIES 18 COMPLIMENTARY OIL ANALYSIS 19 GAS BALLAST VALVE(S) 19 OIL SOLENOID VALVE 19 DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 2

3 SHAFT SEALS 19 MAINTENANCE SCHEDULE 20 DURING FIRST MONTH OF OPERATION 20 DAILY 20 EVERY 3 MONTHS 20 EVERY YEAR / ANNUALLY 20 EVERY 5 YEARS 20 EVERY 10,000 HOURS OF OPERATION 20 ACCESSORIES (IF INCLUDED) 21 TROUBLESHOOTING 22 START-STOP PROBLEMS 22 UNIT WILL NOT START 22 VACUUM PROBLEMS 22 UNIT OPERATES, BUT DOES NOT ACHIEVE DESIRED VACUUM LEVEL 22 OVERHEATING PROBLEMS 22 UNIT OVERHEATS OR OPERATES ABOVE 180 F 22 UNIT OVERHEATS ON START-UP IN LOW AMBIENT TEMPERATURES 22 NOISE AND VIBRATION PROBLEMS 23 THE UNIT IS MAKING AN ABNORMAL NOISE OR SOUND 23 UNIT IS VIBRATING EXCESSIVELY 23 OIL PROBLEMS 23 UNIT USES EXCESSIVE OIL OR PRODUCES AN OIL-MIST 23 TROUBLESHOOTING QUICK REFERENCE GUIDE 24 DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 3

4 THIS INSTALLATION, OPERATION, AND MAINTENANCE MANUAL MUST STAY WITH EQUIPMENT. PLEASE REGISTER YOUR EQUIPMENT WARRANTY AND START-UP RECORD ONLINE AT DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 4

5 CUSTOMER SERVICE Contact information 935 SOUTH WOODLAND AVENUE, MICHIGAN CITY, IN TEL.: FAX: TOLL-FREE: Bus. Hours: 7:30 a.m. 4:30 p.m. CST Website: Order Information When calling for service, parts or system information always have the pump or system model number and serial number(s) ready. Refer to the bill of lading or the gold-colored system information plate attached to the system (see image below). Gold-colored system information plate Parts should be purchased from the nearest authorized DEKKER Vacuum Technologies, Inc. (hereafter referred to as DEKKER) representative (visit to find a distributor near you via the Distributor Locator) or from the vacuum pump system supplier. If, for any reason parts, cannot be obtained in this manner, contact the factory directly. DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 5

6 INTRODUCTION The DEKKER HullVac TM rotary piston vacuum pump has been designed for safe, reliable, trouble-free service, provided the maintenance guidelines as set out in this manual are followed. Compared to other vacuum pump systems, the HullVac rotary piston vacuum pump offers the advantages of low blank off pressures, high pumping speeds at low pressures, and durability. These pumps are low maintenance and easy to use. However, a vacuum pump is a rotating piece of equipment and operators must exercise good judgment and follow proper safety procedures to avoid damage to the equipment or personal injury. Please review and follow all instructions in this manual before attempting to install, start or operate the equipment. SAFETY All vacuum pumps, systems and/or compressors (hereafter referred to as the Product) offered by DEKKER have been designed and manufactured for safe operation. However, the responsibility for safe operation rests with those who use and maintain these products. The safety department where the product is installed should establish a safety program based on OSHA, federal, state, and local codes. It is important that due consideration be given to hazards which arise from the presence of electrical power, hot liquids, harmful gases, and rotating equipment. Proper installation and care of protective devices is essential to safe system operation. These safety procedures are to be used in conjunction with the instructions contained in this manual. WARNING: DO NOT PUMP OXYGEN or oxygen rich mixtures with these pumps - EXPLOSION HAZARDS! DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 6

7 THEORY OF OPERATION The DEKKER HullVac rotary piston vacuum pump is designed and manufactured to achieve a high level of performance. These pumps create a vacuum with a piston that moves in a circular path. As it rotates, pressure is decreased on the inlet side and increased on the discharge side. The two sides are separated by a film of oil between the piston and the cylinder. Once the piston makes a complete cycle, the clearance volume is completely filled with oil, increasing the compression ratios within the pump. This design is what gives rotary piston pumps their deep vacuum levels and durability. Depending on the application and desired vacuum level, HullVac pumps are offered in single-stage or two-stage configurations. The two-stage pump can obtain a deeper vacuum level because it utilizes two piston chambers in series. Intake Stroke Discharge Stroke Not suitable above 100 Torr Not suitable above 10 Torr DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 7

8 STORAGE Keep the system in a cool dry environment. Plug all open ports to keep out dirt and foreign objects. Every 2-3 months remove the belt guard and rotate the lower pulley 2 ¼ turns. If the pump is to be stored in a location where freezing temperatures may be encountered, drain the water jacket if applicable. The water jacket drain plugs are typically located on the exhaust side of the pump. Refill with antifreeze for storage. INITIAL FREIGHT RECEIPT AND INSPECTION Before a system ships from DEKKER, it is thoroughly tested, and will not be released unless it passes our Quality Control standards. All pumps are thoroughly inspected and are not released unless they pass our Quality Control standards. Once the product is received and signed for in Good Condition, DEKKER cannot be held accountable for undiscovered, unclaimed damage that is a result of freight transit. It is the responsibility of the receiver to thoroughly inspect and test the product for functionality upon delivery. The customer should take photos of the product as it arrives and send to DEKKER and the freight carrier if there are any issues. The party who selected the shipper is responsible for filing the freight claim. Failure to report these issues within the freight carriers undiscovered damage window can result in non-acceptance of freight claims. DEKKER does keep photos of all systems, as shipped, to assist in freight claims. Report any damage immediately to AfterSales_Support@DEKKERvacuum.com. Key items to inspect: Is the product received as requested? Are all parts, accessories, and components delivered? Was the skid or crating received in good condition? Check for cosmetic damage. Check wiring inside of control panel. Are all wires should be terminated and connections tight? (If applicable) Check control panel components. Are they tight on DIN rail and/or other mounts/fasteners? Are there any leaks or puddles around the pump? Specify hose, piping or housing leak. System must be given an initial startup test as soon as possible after delivery. This is to ensure that the motor has not shifted out of alignment during transit as well as to verify that electrical components are functioning without fault Variable Frequency Drive (VFD), Programmable Logic Controllers (PLC), panel cooling fans, transducers. INSTALLATION Overview The design of the piping system, foundation layout, and plant location are the responsibility of the purchaser. DEKKER Vacuum Technologies, Inc. and its representatives may offer advice, but cannot assume responsibility for operation and installation design. Please consult the factory or a specialist skilled in the design of plant layout, system piping design, and foundation design. The installer should carefully read this manual before installing the equipment. DEKKER or your authorized dealer can provide start up assistance in most instances for a fee. Contact DEKKER for hourly/daily service rates. Unpacking Upon receipt of pump or system, immediately inspect for signs of damage. Carefully remove packing or crating from around pump or system. Be sure to keep equipment in upright position. Lifting Lift the equipment carefully and with weight evenly distributed. DEKKER is not responsible for equipment that has been damaged through mishandling or dropping. DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 8

9 Location Install the unit in a well ventilated and dust free area. The pump or system should be a minimum distance of 3 feet from surrounding walls to allow for checking fluid level, temperatures, pressures and general servicing. Mounting The pump or system must be installed on a level surface in the horizontal position. The foundation must be designed to support the total unit weight, without any settlement or crushing, be rigid and substantial enough to absorb any equipment vibration, maintain true alignment with any drive mechanism, and must permanently support the system baseplate at all points. The vacuum system must be leveled and secured with anchor bolts. Anchor bolts must be of adequate size to withstand the mechanical stresses exerted on it. Systems 50 HP and larger should also be grouted into position per local codes. The foundation should be constructed to allow for ¾ to 1-½ inch of grout. The baseplate is set on shims and the grout is poured between the foundation and the baseplate. To have the required body to support the baseplate, grout should be at least ¾ inch thick. The number and location of shims will be determined by the design of the baseplate. Firm support should be provided at points where weight will be concentrated and at the anchor bolt locations. Use enough, and large enough, shims to provide rigid support. Baseplates are usually designed with openings to allow pouring grout. When the baseplate has been shimmed, leveled, and the anchor bolts have been snugly tightened, a dam is constructed around the foundation to contain the grout. The dam level should be at least ½ inch above the top surface of the shims. Grout should be poured inside and around the outside of the baseplate and leveled. Allow the grout to dry for a minimum of 48 hours before tightening the anchor bolts. Please note that the pump/motor coupling and V-belt units will need to be realigned prior to start-up, with the exception of monoblock units. Ventilation Locate the unit in an area with sufficient airflow and accessibility. To prevent excessive ambient temperature rise it, is imperative to provide adequate ventilation. Cooling is an important aspect of reliable equipment operation and it is therefore important to install the unit in a reasonably cool area where the temperature does not exceed 104 F (40 C). For higher ambient temperatures contact the factory. Typical system operating temperature is between F. Minimum oil temperature should not be below 45 F. Electrical Preparation All system wiring is performed at the factory if a control panel is supplied and installed on the skid. Check area classification to ensure all electrical enclosures comply with code. Required customer wiring is minimal, but should be done by a qualified electrician in compliance with OSHA, National Electric Code and any other applicable local electrical code concerning switches, fused disconnects, etc. DEKKER includes a wiring diagram in the control panel for use by the installer. DEKKER recommends a main disconnect switch be fitted between the vacuum system and the incoming power. All HullVac pumps are equipped with an oil flow solenoid valve that prevents oil from entering the pumping chamber when the pump is not in use. Oil flow solenoid coil voltage should match the motor voltage. The solenoid valve coil is energized whenever the motor is energized. During initial operation, confirm valve operation by holding a screwdriver, or other metal object, close to but not touching the valve stem top. If the coil is energized, a gentle tugging or vibration will be detected. An oil stream will also be present on the oil level site port whenever the pump is in operation. If an oil stream or splash is not present, check the solenoid valve for proper operation. After the electrical wiring connections are completed check the incoming voltage to make sure the incoming voltage is the same as the vacuum system voltage. Line voltage should be within the voltage tolerance as specified on the motor or to local code. Check the system for proper motor rotation. The direction of rotation is marked by an arrow on the motor or pump housing. Jog the motor by pressing the ON button and then the OFF button. If the rotation is incorrect switch any two of the three main power leads (three phase power) on the contactor inside the control panel. Failure to do so could result in serious equipment damage. DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 9

10 WARNING: Install, ground, and maintain equipment in accordance with the National Electrical Code and all applicable federal, state and local codes. Pipe Connection and Sizing Before installation, remove all protective inserts on the pump suction and discharge. Piping connected to the system must be installed without imposing any strain on the system components. Improperly installed piping can result in misalignment, general operating problems, and pump failure. Use flexible connectors and vibration isolators where necessary. Piping must be cleaned of debris before installation. Inlet Piping Note: Install a temporary screen at the pump inlet flange at first start-up to protect the unit against carryover of pipe debris and welding slag. The screen must be removed after the initial run in period. Inlet piping must be welded carbon steel that is vacuum rated and should be at least the size of the pump inlet. Install the system as close as possible to the process to minimize losses due to the length of the suction line. If the system has to be installed further away from the process, be sure the inlet piping is properly sized to minimize the overall line pressure drop. For more information consult your authorized dealer or the factory. If the inlet gas pumped contains dust or foreign particles, a suitable 5 micron (or finer) inlet filter should be installed at the inlet port. For more information consult your authorized dealer or the factory. A vacuum rated isolation valve should be installed for routine blank-off performance testing and servicing. Discharge Piping DEKKER recommends, as a minimum, CPVC discharge piping as discharge temps may exceed +170 F. CPVC is rated for 200 F max, and PVC is only rated for 140 F max. Discharge piping must be at least the size of the pump exhaust port. Discharge piping should be routed outside or to a properly sized coalescing filter. Install a drip leg with a tee on the discharge line to prevent condensables from draining back into the pump. See the Discharge Piping Diagram as shown below. The drip leg volume should be such that it is unlikely to fill with condensate between routine draining. No flow restriction should be present in the discharge piping. Discharge flow restrictions lead to excessive power consumption at high inlet pressure as well as overheating which may cause damage to the pump. Discharge Piping Diagram DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 10

11 Cooling Water Piping For water-cooled vacuum systems, it is necessary to check cooling water supply. A proper, consistent water flow must be maintained for adequate cooling. Refer to the Cooling Capacities and Port Sizes table below for recommended cooling water capacities at 60 F based on standard operation. Water jacket pressure must not exceed 30 psig. Normal system operating temperature is between F as measured on the oil solenoid valve body located below the exhaust port. Pump casing temperature should not exceed 180 F. If excessive temperature is measured, increase the cooling water flow. Maximum cooling water supply temperature should not exceed 85 F. Oil temperature should be maintained at 165 F. Minimum oil temperature should not be below 55 F. The increased sealing oil viscosity caused by low temperature can lead to internal galling and motor overload. Water-cooled systems require an adequate supply of cooling water at 60 F and a maximum supply pressure of 30 psig. If the cooling water temperature or available pressure is higher, consult your authorized dealer or the factory. The cooling water outlet connection of the heat exchanger may be fitted with an optional water miser valve, which regulates the cooling water flow rate depending on pump operating temperature. To raise the system operating temperature, turn the valve-adjusting screw counter-clockwise when viewed from the top. To lower operating temperature, turn clockwise. Cooling Capacities and Port Sizes Pump Pump CFM HP Cooling Water Capacities (gpm) Cooling Water Port Sizes (Inch NPT) HV55A HV140A HV /2 HV412XT 300/340 10/ /2 HV /4 HV /4 HV HVC35A HVC /2 HVC100A HVC /2 HVC /2 DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 11

12 START-UP PROCEDURES 1 Ensure all shipping plugs and/or paper covers are removed from system and tagging information is followed for successful startup. 2 Remove the belt guard and rotate the pump two complete revolutions by hand in the counterclockwise* direction. This will clear accumulated oil from the pump housing that can collect during long inactive periods. Reinstall the belt guard. *Rotation is clockwise on the HV412XT 3 For units utilizing V-belt drives, make sure the sheaves are properly installed and aligned before attempting to tension the drive. The V-belts should be placed over the sheaves and in the grooves without forcing them over the sides of the grooves. The tensioning steps below can be used for all types of V-belts, all cross sections and number of belts and all types of construction. Avoid excessive heat (140 F and higher); belt life will be shortened. Never switch or mix belts from one groove to another on the sheaves. Do not use belt dressing. Sheaves should remain free of oil and grease. When replacing belts install an identical set. For more specific V-belt tensioning guidelines consult factory. Sheave alignment should be checked by placing a straight edge or tight cord across the sheave faces so that it touches all four points of contact. Ordinarily, a misalignment of more than one-half of one degree (one eighth inch in one foot) will adversely affect belt life. Improper sheave alignment produces uneven wear on one side of the belt, causes the belt to roll over in the sheaves or throws the entire load on one side of the belt, stretching or breaking the cords on that side. Tensioning a Drive - General Rules of Tensioning 1. Ideal tension is the lowest tension at which the belt will not slip under peak load conditions. 2. Check tension frequently during the first hours of run-in operation. 3. Over tensioning shortens belt and bearing life. 4. Keep belts free from foreign material which may cause slip. 5. Make V-Drive inspection on a periodic basis. Tension belt when slipping. Never apply belt dressing as this will damage the belt and cause early failure. If the unit is idle for an extended period of time, the tension on the belts should be removed. Simple Tensioning Procedure 1. Measure the span length. 2. At the center of the span apply a force (perpendicular to the span) large enough to deflect the belt 1/64, for every inch of span length. For example, one deflection of a 100 inch span would be 100/64 or 1-9/16 inches. 3. Compare the force you have applied with the values given in Table 3.1 on the next page. If the force is between the values for normal tension, and 1-1/2 times normal tension, the drive tension should be satisfactory. A force below the value for normal tension indicates an under tensioned drive. If the force exceeds the value for 1-1/2 times normal tension, the drive is tighter than it needs to be. 4. After the proper operating tension has been applied to the belts, double check the following: A) Parallel position of the sheave shafts. B) Correct alignment of sheave grooves. Tensioning rules and procedure courtesy of Dodge PT Manual MN DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 12

13 3.1 Tensioning Table V-Belt Section A B AX BX Small Sheave Deflection Force (lbs) For Drive Speed Ratios of: Speed Range (RPM) Diameter (in) Tensioning Table and installation image courtesy of Dodge PT Manual MN-4002 Notes: 1. Use approximately 130% of above values to tension a new set of belts. 2. Use closest sheave diameter for sizes not shown. DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 13

14 4 Install a blank off flange to the inlet port or attach to a sealed vacuum chamber. Make certain the pump is attached to a closed system. The discharge must be open to atmosphere during startup. Excessive motor load characterized by low rotation speed can be experienced if the discharge is closed. Repeated efforts to start the pump when the discharge is not open to atmosphere may result in motor and/or control system damage. 5 Jog the motor briefly and check direction of rotation. The correct direction of rotation is marked by an arrow on the motor or pump housing. If direction is incorrect switch any two of the three leads at the power connection. The correct direction of rotation is counterclockwise facing the pump from the drive end and clockwise if viewed from the non-drive end. *Rotation is Clockwise on the HV412XT 6 Turn the cooling water on, if applicable. DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 14

15 7 Energize the motor a slight belt slipping noise may be heard as oil is pushed from the pumping chamber through the valve deck. If the belt slip noise does not stop within the first few seconds: 1. Stop the pump. 2. Disconnect the power. 3. Remove the belt guard. 4. Rotate the pump once by hand. 5. Tighten the belts if needed. 6. Reinstall the belt guard. 7. Reconnect power. 8. Restart. 8 Confirm the oil solenoid valve is open. The valve s solenoid coil is energized whenever the motor is energized. During initial operation, confirm valve operation by holding a screw driver or other metal object close to, but not touching the valve stem top. If the coil is energized, a gentle tugging or vibration will be detected. An oil stream will also be present on the oil level sight port whenever the pump is in operation. If an oil stream or splash is not present, check the solenoid valve for proper operation. 9 The oil level should be checked after the pump has been operating at an inlet pressure below 1 torr for 5 minutes. Proper oil fill is confirmed when the sight port oil level is at least ½ level. During initial evacuation, the oil level may rise but will fall as the pump operates below 1 torr. During operation, oil should always be visible in the sight port. Normal oil fill level is mid to two-thirds of the sight port, throughout all operating conditions. An oil fill level above the sight port should be avoided as it will be difficult to verify correct fill level and could damage the pump. 10 Check the voltage and motor current. They should be within the specifications for the motor. Amperage should be checked at the Overload. Note: This test should also be performed under normal system operating conditions. DANGER: HIGH VOLTAGE! Lethal shock hazard present. USE EXTREME CAUTION! DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 15

16 11 After minutes of operation, check pump operating temperature, which should be in the F range at the solenoid body. The casing temperature will rise faster and be warmer at higher suction pressures. During any operation, the casing should not rise above 180 F. SHUT DOWN PROCEDURES To stop the vacuum pump follow the procedure as outlined below. 1 Close the system inlet isolation valve 2 Push the STOP button or turn switch to the OFF position. 3 Open the gas ballast valves to vent the pump to atmosphere. If system is equipped with an automatic vent valve or an antisuckback valve, no action is needed. Failure to vent the pump to atmosphere may cause oil to fill into the pumping chamber and travel back through the inlet manifold into the vacuum process chamber. 4 If water cooled, turn off the cooling water supply. DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 16

17 MAINTENANCE WARNING: Before attempting any maintenance such as changing the fluid, disconnect all power from the system by switching off the main breaker, isolate all energy sources and allow system to cool. Pump Bearing Lubrication Internal pump components do not require preventative maintenance. Bearings are self-lubricating type. Motor Bearing Lubrication (where required) For information regarding motor bearing lubrication, refer to the motor maintenance and operation manual. Inlet Filter (If Installed) Check after first 8 hours of operation. Clean or replace inlet filter element every 1000 to 3000 hours depending on application or if excessive pressure drop is noticed. In some applications it may be necessary to clean inlet filter more often. Clean filters by gently knocking off into a dust bin. Brush filter free of debris and clean with a wet/dry vacuum cleaner. DO NOT USE COMPRESSED AIR TO CLEAN ANY FILTERS. CAUTION: Be careful not to allow foreign material to fall in the pump suction opening when removing the filter cartridge. Horizontal filter installation is recommended to prevent this. Filters must be disposed of properly as they might contain toxic substances carried over from the process. Seal Fluid The units are shipped with DEKKER s specially formulated HullVac seal fluid (hereafter referred to as oil). DEKKER recommends that this oil be used to obtain the optimal performance from the HullVac product and to maintain the 3-year warranty period. Oil should be changed whenever it appears white or yellow, foams consistently, or when dirty. Oil change frequency depends on the materials being pumped. For clean applications, oil should be changed every 3000 operating hours or every 9 months, whichever comes first. For other applications, oil change could range from once or twice a week or less dependent upon the type of process. The most common contamination is water in the oil and can be recognized by a milky appearance visible in the site port. Closing the pump inlet valve and operating the gas ballast valves for 2 to 4 hours can remove this water. If this does not clear the oil, change it. In applications with consistent water accumulation, draining the water from the reservoir prior to operation is recommended. HullVac Oil Container Size Standard Water Application 1 Gallon Container Gallon Container Gallon Drum Safety Data Sheets (SDS) available upon request. DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 17

18 Oil Change Procedure Run the pump until normal operating temperature is achieved. ( F as measured on the oil solenoid valve). Run the pump for at least 1 hour prior to draining the oil. This will warm the oil to facilitate faster and more complete draining. CAUTION: OIL WILL BE HOT! Follow these steps to drain the oil: Disconnect main power to pump. Vent the inlet to atmosphere for 10 to 15 seconds. This will force the oil from the lower pumping chambers into the upper reservoir. Open the oil drain valve and allow the oil to drain completely. Close the oil drain valve and rotate drive belts by hand with the inlet open to atmosphere for 5 10 rotations, then open the drain valve again to scavenge residual oil. This will force residual oil from the pumping chamber into the oil reservoir where it can be drained. Follow these steps to fill with new oil: Close the oil drain valve and fill the reservoir to two-thirds of the sight port by pouring oil through the oil fill port located on top of the pump. Reconnect main power to pump. Close the inlet isolation valve so that the pump is blanked-off. Run the pump for 2-3 minutes. Check the oil level. Add oil until the sight port level is between mid to two-thirds level in the sight port. If overfilled, open drain to drain off excess and re-run unit to confirm oil level. The approximate oil capacities are given in the Standard System Capacities table below. Standard System Capacities System Capacity (gal) HV55A 0.9 HV140A 3.3 HV160 4 HV412XT 12 HV HV HV HVC35A 0.9 HVC HVC100A 3.3 HVC HVC DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 18

19 Complimentary Oil Analysis DEKKER offers oil analysis to customers, regardless of the age of their system, at no charge. Collect approximately 4 fluid ounces from the machine, and secure it in any type of clean bottle. On the bottle or a packing list, please include the following: system serial number, the type of oil, the run hours on the oil and machine, and note any problems you are having with the system if applicable. Also make sure to include your contact information with address. After the analysis is complete, DEKKER will provide a report of the condition of the oil, along with recommendations. Send to: DEKKER Vacuum Technologies, Inc. 935 S. Woodland Ave. Michigan City, IN United States ATTN: After Sales Gas Ballast Valve(s) The gas ballast is a method of operating the pump to help prevent vapors from condensing into liquids in the pump oil. Properly applied, it works well with water vapor and reasonably well with some other condensable vapors. The drawback of using the gas ballast is that it will limit the ultimate vacuum the pump can attain. To engage, open one or both ball valves depending on the degree of ballasting required to clear the condensable contamination from the oil supply. There will be a slight change in the sound of the pump and the base pressure will rise slightly. Excessive heat will be generated when the valves are open and care must be given to ensure adequate cooling water flow. Be sure the pump body temperature does not exceed 180 F as measured on the casting surface below the sight port. Oil Solenoid Valve The oil solenoid valve is typically located under the exhaust port and prevents oil from filling into the pumping chamber when the pump is turned off or when there is a power failure. It is critical that this valve operates properly. If the valve malfunctions in an open position, oil will flow back into the pumping chamber when the pump is shut off. This will result in hard starting, excessive belt wear, and possible equipment damage. If the valve is stuck in the closed position, poor vacuum performance will result. If the pump is operated for longer than a minute without oil, internal damage may occur. The condition of the solenoid valve interior will mirror the condition of the oil reservoir housing. If there is a buildup of sludge, varnish, or particulate in the oil reservoir, the solenoid valve body may be likewise contaminated. Shaft Seals The pumps are equipped with lip seals and do not require preventative maintenance. DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 19

20 MAINTENANCE SCHEDULE To help ensure trouble free operation, a basic maintenance schedule consisting of the following system checks is recommended. During First Month of Operation Check belt tension weekly. Verify tightness of pump mounting bolts weekly. Torque the side cover bolts at the end of first month of operation. Side Cover Bolt Torque Value BOLT SIZE FT-LBS M5 3 M6 5 M7 8 M8 12 M10 24 M12 40 M14 65 M Daily Check oil level daily - oil level should be between mid to two-thirds level in the sight port while in operation. Check pump temperature daily - casing temperature should not exceed 180 F. Every 3 Months Check belt tension. Verify tightness of pump mounting bolts. Every Year / Annually Remove the oil reservoir access plate. Clean and inspect the sump for signs of metal filings that may be an indication of excessive internal wear. Strain the oil through a mesh bag to inspect for particulates. Remove the oil / air separator and the valve deck cover. Verify the valves are intact and free to move up and down. Examine for signs of excessive wear. If needed, replace the valve deck springs and wear plates. Examine the belts for signs of excessive wear and replace as needed. Verify if motor lubrication is required for pump motor. Every 5 Years Replace the bearings, shaft seals, shaft seal wear sleeves, and o-rings. Replace the oil flow solenoid valve wear components. Replace the gas ballast valves. Every 10,000 Hours of Operation Check coupling element for wear, if applicable. Replace if worn. Clean strainer in seal fluid line. Check belt tension, if applicable. DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 20

21 ACCESSORIES (IF INCLUDED) The following accessories are available for HullVac rotary piston vacuum pump systems: Automatic Inlet Vent Valve (optional): Includes a normally open solenoid valve and filter assembly mounted to the pump inlet port. When power is shut off, the pump inlet and manifold will be vented to atmosphere. This will prevent accidental oil backflow into the manifold and process chamber and will also vent the chamber up to atmosphere. Automatic Inlet Isolation Valve (optional): Consists of a pneumatically actuated ball valve mounted on the pump inlet that automatically closes whenever power is shut off. NOTE: This includes the automatic inlet vent valve. Temperature Control Valve (optional): Reduces cooling water flow by up to 90% while it controls pump operating temperature within the optimal range of F. This temperature optimizes water and solvent evaporation from the oil supply while preventing damage due to excessive heating. Inlet Filter (optional): Traps particulate larger than the internal clearances of the pump (5 micron). Must be installed horizontally. Oil Mist Eliminators (optional): Strips atomized oil droplets from the exhaust stream, reducing the appearance of smoke. Assembly comes complete with a ball valve on the canister drain and a 0 to 15 psig gauge to monitor filter element condition. DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 21

22 TROUBLESHOOTING The following is a basic troubleshooting guide and not all options may be included. Service should be done by a DEKKER authorized distributor or a properly trained service technician. Each unit is tested and checked at the factory. Always indicate model and serial number when calling. The model and serial number is viewable on the gold-colored information plate attached to the unit. WARNING: Before attempting any maintenance such as changing the fluid, disconnect all power from the unit by switching off the main breaker, isolate all energy sources and allow unit to cool. All electrical work should be done by a qualified electrician in compliance with OSHA, National Electric Code and any other applicable local electrical code. Start-Stop Problems Unit will not start 1. Check that the main AC power disconnect is ON and supplying power to the unit. 2. Check if the disconnect or circuit breaker is switched on. 3. Check the overload setting on the starter. 4. Ensure that the proper voltage is supplied and that the wire size is correct. 5. Check if the pump has seized by removing the belt guard and rotating the belts by hand (disconnect power first). If a rubbing noise or binding is observed, contact the factory. Vacuum Problems Unit operates, but does not achieve desired vacuum level 1. Stop unit and disconnect power. 2. Check if the inlet valve is open and inlet filter is clean. 3. Ensure that no lines are open to the atmosphere, causing loss of vacuum. 4. Check for leaks in piping systems, using conventional leak detection methods. 5. Ensure that the oil level is correct. 6. Check if the oil solenoid valve is working. 7. Check if the motor rotation is correct. Check if the motor rotation is correct. Rotation is marked by an arrow on the motor or pump housing. If incorrect, switch any two of the three main power leads on the contactor inside the control panel. Overheating Problems Unit overheats or operates above 180 F 1. Stop unit and disconnect power. 2. Check if the oil solenoid valve is working. 3. Ensure that the oil level is correct. 4. Verify cooling water flow, if applicable. 5. Verify ambient air temperature is 104 F or below. Unit overheats on start-up in low ambient temperatures 1. Stop system and disconnect power. 2. Verify oil temperature. Oil tends to thicken in temperatures of 55 F and below. DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 22

23 Noise and Vibration Problems The unit is making an abnormal noise or sound 1. Stop unit and disconnect power. 2. Check belt tension and alignment. 3. Ensure that the oil level is correct. 4. Check the inlet filter and clean if necessary. 5. Check if the inlet valve is closed. Unit is vibrating excessively 1. Stop unit and disconnect power. 2. Check belt tension and alignment. 3. Check if unit is properly supported. An uneven foundation can cause vibration problems. 4. Check that the mounting bolts of pump are not loose. Tighten as required. Oil Problems Unit uses excessive oil or produces an oil-mist 1. Ensure that the unit is pulling a deep vacuum level (deeper than 100 torr for single-stage and 10 torr for two-stage). 2. Stop unit and disconnect power. 3. Confirm oil level is not too high. 4. Confirm the unit is using factory recommended oil. 5. Ensure that discharge piping is arranged correctly. DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 23

24 Troubleshooting Quick Reference Guide DEKKER Vacuum Technologies, Inc. / Part No P02 Rev. A 24

Installation Operation & Maintenance Manual. Oil-Free (Dry) Rotary Vane Vacuum Pump Systems

Installation Operation & Maintenance Manual. Oil-Free (Dry) Rotary Vane Vacuum Pump Systems Installation Operation & Maintenance Manual Oil-Free (Dry) Rotary Vane Vacuum Pump Systems Part No. 9983-0000-S07 / November 2018 OIL-FREE (DRY) ROTARY VANE VACUUM PUMP SYSTEMS TABLE OF CONTENTS CUSTOMER

More information

Installation Operation & Maintenance Manual. High Vacuum Lubricated Rotary Vane Pumps

Installation Operation & Maintenance Manual. High Vacuum Lubricated Rotary Vane Pumps Installation Operation & Maintenance Manual High Vacuum Lubricated Rotary Vane Pumps Part No. 9983-0000-P07 / November 2018 HIGH VACUUM LUBRICATED ROTARY VANE PUMPS TABLE OF CONTENTS CUSTOMER SERVICE 5

More information

Installation Operation and Maintenance Manual

Installation Operation and Maintenance Manual Installation Operation and Maintenance Manual Lubricated high vacuum rotary vane pumps SERIAL NO.: June 2006/5 LUBRICATED HIGH VACUUM ROTARY VANE PUMPS TABLE OF CONTENTS INTRODUCTION 3 Safety 3 STORAGE

More information

Installation Operation & Maintenance Manual. Oil-Sealed Liquid Ring Vacuum Pump Systems

Installation Operation & Maintenance Manual. Oil-Sealed Liquid Ring Vacuum Pump Systems Installation Operation & Maintenance Manual Oil-Sealed Liquid Ring Vacuum Pump Systems Part No. 9983-0000-S01 Rev. A / January 2018 OIL-SEALED LIQUID RING VACUUM PUMP SYSTEMS TABLE OF CONTENTS CUSTOMER

More information

Installation Operation and Maintenance Manual

Installation Operation and Maintenance Manual Installation Operation and Maintenance Manual C Water-sealed liquid ring compressors and compressor systems SERIAL NO.: May 2013/3 C WATER-SEALED LIQUID RING COMPRESSORS AND COMPRESSOR SYSTEMS TABLE OF

More information

Series Base mounted pump. Installation and operating instructions

Series Base mounted pump. Installation and operating instructions Series 4030 Installation and File No: 40.80 Date: june 25, 2015 Supersedes: 40.80 Date: october 10, 2009 contents General 4 Inspection 4 Installation - Series 4030 base mounted Pump 4 1.0 Location 4 2.0

More information

Eurovacuum Installations and Operating manual EV Series Vacuum pumps Models

Eurovacuum Installations and Operating manual EV Series Vacuum pumps Models Eurovacuum Installations and Operating manual EV Series Vacuum pumps Models 0010-0630 Single Stage Oil Sealed Rotary Vane Pump Eurovacuum EV Series Single Stage Oil Sealed Rotary Vane Pumps Eurovacuum

More information

Installation and Operating Manual

Installation and Operating Manual Installation and Operating Manual L-Series Vacuum Pumps Models L/H400C - L/H630C INSTALLATION & OPERATING MANUAL L/H-SERIES SINGLE STAGE ROTARY VANE VACUUM PUMPS L/H400C-L/H630C Please read the manual

More information

SERIES PC INSTRUCTION AND OPERATION MANUAL

SERIES PC INSTRUCTION AND OPERATION MANUAL MEGGA SERIES PC INSTRUCTION AND OPERATION MANUAL Models PCT and PCF Close-coupled and frame-mounted single-stage horizontal end-suction pumps. WARNING: Read this manual before installing or operating this

More information

Installation Operation and Maintenance Manual

Installation Operation and Maintenance Manual Installation Operation and Maintenance Manual Lubricated and lubricated for saturated air (wet) service rotary vane vacuum pumps and systems SERIAL NO: Feb 2008/07 LUBRICATED ROTARY VANE VACUUM PUMPS AND

More information

Operating Manual. High Performance Vacuum Pump Models and 15600

Operating Manual. High Performance Vacuum Pump Models and 15600 Operating Manual High Performance Vacuum Pump Models 15400 and 15600 CoolTech High Performance Vacuum Pumps Congratulations on purchasing one of Robinair s top quality CoolTech vacuum pumps. Your pump

More information

Routine Compressor Maintenance

Routine Compressor Maintenance Establishing a regular, well-organized maintenance program and strictly following it is critical to maintaining the performance of a compressed air system. One person should be given the responsibility

More information

Installation Operation and Maintenance Manual

Installation Operation and Maintenance Manual Installation Operation and Maintenance Manual Oil-sealed liquid ring vacuum pump systems SERIAL NO.: June, 2006/13 OIL-SEALED LIQUID RING VACUUM PUMP SYSTEMS TABLE OF CONTENTS INTRODUCTION 3 Safety 3 STORAGE

More information

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST BELT TYPE IMPORTANT PLEASE MAKE CERTAIN THAT THE PERSON WHO IS TO USE THIS EQUIPMENT CAREFULLY READS AND UNDERSTANDS THESE INSTRUCTIONS BEFORE STARTING

More information

Series Base mounted pump. Installation and operating instructions

Series Base mounted pump. Installation and operating instructions Series 4030 Installation and File No: 40.80 Date: december 12, 2016 Supersedes: 40.80 Date: july 27, 2016 contents General 4 Inspection 4 Installation - Series 4030 base mounted Pump 4 1.0 Location 4

More information

INSTRUCTION MANUAL OIL SEALED ROTARY VACUUM PUMP MODEL PKS-016 PKS-030 PKS-070

INSTRUCTION MANUAL OIL SEALED ROTARY VACUUM PUMP MODEL PKS-016 PKS-030 PKS-070 INSTRUCTION MANUAL OIL SEALED ROTARY VACUUM PUMP MODEL PKS-016 PKS-030 PKS-070 Components division ULVAC, Inc. Table of Contents 1. Inspection 4 2. Mounting 5 3. Oil filling 5 4. Electrical connections

More information

READ AND SAVE THESE INSTRUCTIONS. High Velocity Restaurant-Duty Utility Set Belt Driven for Roof Mounting

READ AND SAVE THESE INSTRUCTIONS. High Velocity Restaurant-Duty Utility Set Belt Driven for Roof Mounting READ AND SAVE THESE INSTRUCTIONS INSTALLATION, OPERATING INSTRUCTIONS & PARTS MANUAL High Velocity Restaurant-Duty Utility Set Belt Driven for Roof Mounting Electrical wiring and connections should be

More information

Pneumatic High-Viscosity Filtration System Instruction Manual

Pneumatic High-Viscosity Filtration System Instruction Manual Pneumatic High-Viscosity Filtration System Instruction Manual P/N: 61512 05/17 1 2 Pneumatic High Viscosity Filtration Systems PN: 61512 14 April, 2009 rev A 36933 Pneumatic Hand Cart HV Filtration System

More information

Models

Models Models 15300 15301 15500 15501 SAFETY PRECAUTIONS WARNING! To prevent personal injury, Wear goggles when working with refrigerants. Contact with refrigerants may cause injury. Incorrect use or connections

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING dv Sentry TM 208V 600V INSTALLATION GUIDE FORM: DVS-IG-E REL. January 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-10 RX-21 RX-25

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-10 RX-21 RX-25 V acuum Pumps Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-10 RX-21 RX-25 www.republicsales.com Revised 10.14 2014 Republic Sales & Manufacturing Single Stage Rotary Vane Vacuum

More information

Two Stage Rotary Vane Vacuum Pumps Operation and Maintenance Manual

Two Stage Rotary Vane Vacuum Pumps Operation and Maintenance Manual Two Stage Rotary Vane Vacuum Pumps Operation and Maintenance Manual Model 100 3.5 100 l/min. 3.5 CFM 6 m 3 /hr. Model 200 7 200 l/min. 7 CFM 12 m 3 /hr. Model 400 14 400 l/min. 14 CFM 24 m 3 /hr. Model

More information

9/28/2018. Refrigeration compressor operation, maintenance and safety

9/28/2018. Refrigeration compressor operation, maintenance and safety Refrigeration compressor operation, maintenance and safety Presented By: Dhananjay S. Deshpande Company name: Technex HVAC&R Engg. Works 304, Shivshakti CHS, Sector 09, Plot no 15, Khanda colony, New Panvel

More information

High Performance Vacuum Pump Model 15120A/15121A Operating Manual...

High Performance Vacuum Pump Model 15120A/15121A Operating Manual... High Performance Vacuum Pump Model 15120A/15121A Operating Manual... Operating Manual Table of Contents Warnings...1 CoolTech high performance vacuum pumps...1 Pump components...2 Before using your vacuum

More information

Eclipse GEN 2.0 CAFSystem, Model 150-ECL CAFS PTO Kit Installation Instructions

Eclipse GEN 2.0 CAFSystem, Model 150-ECL CAFS PTO Kit Installation Instructions Eclipse GEN 2.0 CAFSystem, Model 150-ECL CAFS PTO Kit Installation Instructions Read Read through the the safety installation information instructions overhaul carefully instructions before carefully beginning

More information

Advantage-D. Operating Instructions and Maintenance Manual. Central Vacuum Systems (Expandable/Modular Models) (Ver.

Advantage-D. Operating Instructions and Maintenance Manual. Central Vacuum Systems (Expandable/Modular Models) (Ver. Advantage-D Series 3 Central Vacuum Systems (Expandable/Modular Models) (Ver. 8/05) Operating Instructions and Maintenance Manual DESCRIPTION The Becker Advantage-D and Advantage-L central vacuum systems

More information

SERIES G3DB/AG3DB ELEVATOR

SERIES G3DB/AG3DB ELEVATOR TM INSTRUCTIONS AND PARTS LIST SERIES G3DB/AG3DB ELEVATOR WARNING This manual, and GENERAL INSTRUCTIONS MANUAL, CA-1, should be read thoroughly prior to pump installation, operation or maintenance. SRM00059

More information

INSTRUCTION MANUAL: Industrial Series Piston Air Compressor. Model Number: V Part Number: L001128KNA

INSTRUCTION MANUAL: Industrial Series Piston Air Compressor. Model Number: V Part Number: L001128KNA INSTRUCTION MANUAL: Industrial Series Piston Air Compressor Model Number: V8051-335 Part Number: L001128KNA Pump Model: LP335 K335 Motor: 5 HP / 1 PH Air Tank: 80 Gal Vertical 1830 W. 15 th St. Houston,

More information

Medium and high pressure pumps

Medium and high pressure pumps Screw pumps Medium and high pressure pumps Installation and Start-up Instruction This instruction is valid for all standard high pressure pumps: E4, D4 and D6 Contents Page Pump identification 2 Installation

More information

OWNER S MANUAL EVOLUTION 3500, 4500, 5500, & 8500 SERIES PUMPS

OWNER S MANUAL EVOLUTION 3500, 4500, 5500, & 8500 SERIES PUMPS OWNER S MANUAL EVOLUTION 3500, 4500, 5500, & 8500 SERIES PUMPS IMPORTANT SAFETY INSTRUCTIONS When installing and using this electrical equipment, basic safety precautions should always be followed, including

More information

C T h e A d va n t a g e

C T h e A d va n t a g e C The Advantage TABLE OF CONTENTS Introduction...1 Product Numbering System...1 Safety...2 Receiving and Inspection...2 Installation...2 Electrical...3 Parts Identification...7 Lubrication...9 Start-up...10

More information

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-40 RX-63 RX-100

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-40 RX-63 RX-100 V acuum Pumps Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-40 RX-63 RX-100 www.republicsales.com Revised 02.15 2015 Republic Sales & Manufacturing Single Stage Rotary Vane

More information

NECO Pumping Systems

NECO Pumping Systems INSTALLATION OPERATION & MAINTENANCE INSTRUCTIONS For Your NECO Pumping Systems PACKAGED CIRCULATING SYSTEM THIS COMPLETELY ASSEMBLED, TESTED, PACKAGED CIRCULATING SYSTEM IS OF THE HIGHEST QUALITY AND

More information

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting READ AND SAVE THESE INSTRUCTIONS INSTALLATION, OPERATING INSTRUCTIONS & PARTS MANUAL Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting Electrical wiring and connections should be done

More information

Eclipse GEN 2.0 CAFSystem, Model 150-ESECL as used with TC20 Series PTO Installation Instructions

Eclipse GEN 2.0 CAFSystem, Model 150-ESECL as used with TC20 Series PTO Installation Instructions Eclipse GEN 2.0 CAFSystem, Model 150-ESECL as used with TC20 Series PTO Installation Instructions Read Read through the the safety installation information instructions overhaul carefully instructions

More information

WARCO CHEMAG SERIES GH FILTERS

WARCO CHEMAG SERIES GH FILTERS WARCO CHEMAG SERIES GH FILTERS High Performance Pleated & Bag Type Filtration Systems INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS Thank you for your purchase of a WARCO Series GH Filtration System.

More information

Emergency Smoke Control Centrifugal Roof Exhaust Fans

Emergency Smoke Control Centrifugal Roof Exhaust Fans IN THIS SECTION Emergency Smoke Control Centrifugal Roof Exhaust Fans HA~~ISAI~ SYSTEl\t1S, INC. Heat:ing &.-Air Condit:ioning Inst:allat:ion &,-Service -------- READ AND SAVE THESE INSTRUCTIONS [RGREENHECK

More information

UNPACKING SAFETY GUIDELINES GENERAL SAFETY INFORMATION. Operating Instructions & Maintenance Manual

UNPACKING SAFETY GUIDELINES GENERAL SAFETY INFORMATION. Operating Instructions & Maintenance Manual Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

READ AND SAVE THESE INSTRUCTIONS. Air Boss MP600M Vertical Air Flow Mist Precipitator Industrial Applications. TRION

READ AND SAVE THESE INSTRUCTIONS. Air Boss MP600M Vertical Air Flow Mist Precipitator Industrial Applications. TRION READ AND SAVE THESE INSTRUCTIONS Vertical Air Flow Mist Precipitator Industrial Applications TRION Vertical Air Flow Mist Precipitator for Industrial Applications Table of Contents Design...2 Installation...2

More information

Operating Instructions & Parts Manual

Operating Instructions & Parts Manual Operating Instructions & Parts Manual Grainger Model No. 36NE14 Bucher Hydraulics Model No. M-4509-0217 Please read the instructions carefully and always operate this equipment in a safe manner. Unit Description:

More information

Maintenance and Repair

Maintenance and Repair Maintenance and Repair WARNING ALWAYS shut off the engine, remove key from ignition, make sure the engine is cool, and disconnect the spark plug and positive battery terminal from the battery before cleaning,

More information

ROOTS Meters Series B3 Meter Models 8C175-56M175

ROOTS Meters Series B3 Meter Models 8C175-56M175 ROOTS Meters Series B3 Meter Models 8C175-56M175 Refer to IOM-B3 for Complete Instructions IS:B3 3.03 RECEIVING, HANDLING AND STORAGE ROOTS rotary positive displacement gas meters are precision measurement

More information

UNPACKING SAFETY GUIDELINES GENERAL SAFETY INFORMATION. Operating Instructions & Maintenance Manual

UNPACKING SAFETY GUIDELINES GENERAL SAFETY INFORMATION. Operating Instructions & Maintenance Manual Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

MODEL VBO-HV & VBO UPBLAST PROPELLER ROOF FANS

MODEL VBO-HV & VBO UPBLAST PROPELLER ROOF FANS READ AND SAVE THESE INSTRUCTIONS 9668-D Heinrich Hertz Drive, San Diego, CA 92154 PH: 619-946-1224 MODEL VBO-HV & VBO UPBLAST PROPELLER ROOF FANS SHIPPING INSPECTION Romlair Model VBO-HV & VBO fans are

More information

TM-1620 OPERATING INSTRUCTIONS AND OWNERS MANUAL

TM-1620 OPERATING INSTRUCTIONS AND OWNERS MANUAL TM-1620 OPERATING INSTRUCTIONS AND OWNERS MANUAL tracopackaging.com 800-284-WRAP 620 SOUTH 1325 WEST OREM, UT. PHONE 800-284-WRAP (9727) IMPORTANT: READ ALL INSTRUCTIONS BEFORE OPERATING EQUIPMENT Your

More information

Maximum operating temperature for standard motors = 110 C. Shut down temperature in case of a malfunction = 115 C.

Maximum operating temperature for standard motors = 110 C. Shut down temperature in case of a malfunction = 115 C. Section 3 Maintenance & Troubleshooting General Inspection Lubrication & Bearings Type of Grease WARNING: UL rated motors must only be serviced by authorized Baldor Service Centers if these motors are

More information

Installation Operation and Maintenance Manual

Installation Operation and Maintenance Manual Installation Operation and Maintenance Manual Water-sealed liquidring vacuum pump systems SERIAL NO.: October 2006/13 WATER-SEALED LIQUID RING VACUUM PUMP SYSTEMS TABLE OF CONTENTS INTRODUCTION 3 Safety

More information

OCTOPUS SELECTION & INSTALLATION GUIDE

OCTOPUS SELECTION & INSTALLATION GUIDE OCTOPUS SELECTION & INSTALLATION GUIDE CRB SERIES CONTINUOUS RUNNING PUMPSET A. GENERAL DESCRIPTION: Octopus CRB pumpsets are heavy duty, continuously running, electric motor driven pumps which are used

More information

TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: FAX:

TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: FAX: TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: +353 66 7121911 FAX: +353 66 7124503 e-mail: sales@tillotson.ie SERIES SERVICE MANUAL INTRODUCTION The gasoline engine industry

More information

PO Box 645, Stockton, Missouri, FAX superiorgearbox.com

PO Box 645, Stockton, Missouri, FAX superiorgearbox.com I000-7000-D0447-A 4/7/05 1 SAFETY PRECAUTIONS CAUTION Please read this entire document prior to operating the gear drive. Gear drive failure and / or injury to operators may be caused by improper installation,

More information

Installation Operation and Maintenance Manual

Installation Operation and Maintenance Manual Installation Operation and Maintenance Manual Oil-free (dry) rotary vane vacuum pumps and systems SERIAL NO.: May 2006/10 OIL-FREE (DRY) ROTARY VANE VACUUM PUMPS AND SYSTEMS TABLE OF CONTENTS INTRODUCTION

More information

OPERATIONS MANUAL LEVER CHAIN HOIST

OPERATIONS MANUAL LEVER CHAIN HOIST OPERATIONS MANUAL LEVER CHAIN HOIST IMPORTANT SAFETY INFORMATION Please read, understand and follow all safety information contained in these instructions prior to the use of this hoist. Retain these instructions

More information

Low Profile J Series Power Unit with Vane Pump

Low Profile J Series Power Unit with Vane Pump Low Profile J Series Power Unit with Vane Pump READ ALL INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT YOURSELF AND OTHERS BY OBSERVING

More information

Operating Instructions - Electric Pow'r-Riser Models

Operating Instructions - Electric Pow'r-Riser Models ADivisionOf Templeton, Kenly& Co., Inc. Operating Instructions - Electric Pow'r-Riser Models Table of Contents 1.0 Recieving Instructions 2.0 Safety 3.0 Specifications 4.0 Initial Installation Before Operating

More information

WELDING FUME EXHAUSTERS & ARMS

WELDING FUME EXHAUSTERS & ARMS WELDING FUME EXHAUSTERS & ARMS The Ace 75 Series is our flexible and effective line of welding fume exhausters and extraction arms for shops that elect to exhaust their weld fumes outdoors instead of through

More information

User s Manual D-Series Blowers and Exhausters

User s Manual D-Series Blowers and Exhausters User s Manual D-Series Blowers and Exhausters D05-1 ½ HP TEFC 115/230 VOLTS, 1 PH D05-3 ½ HP TEFC 208/230/460 VOLTS, 3 PH D10-1 1 HP TEFC 115/230 VOLTS, 1 PH D10-3 1 HP TEFC 208/230/460 VOLTS, 3 PH D15-1

More information

ISP-500B. Oil-free Scroll Vacuum Pump. Instruction Manual. View our inventory. Record of Pump Information. Serial Number: Purchase date:

ISP-500B. Oil-free Scroll Vacuum Pump. Instruction Manual. View our inventory. Record of Pump Information. Serial Number: Purchase date: ISP-500B Oil-free Scroll Vacuum Pump Instruction Manual View our inventory Serial Number: Record of Pump Information Purchase date: In Service date: Dealer information: IM-500B 1/3/07 Page 1 of 26 Important

More information

Installation, Operation & Maintenance Instructions for Liquid Ring. Compressor Systems. Liquid Ring & Rotary Vane Vacuum Pumps and Systems

Installation, Operation & Maintenance Instructions for Liquid Ring. Compressor Systems. Liquid Ring & Rotary Vane Vacuum Pumps and Systems Installation, Operation & Maintenance Instructions for Liquid Ring Compressor Systems Liquid Ring & Rotary Vane Vacuum Pumps and Systems INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS FOR COMPRESSOR

More information

S3 General Installation

S3 General Installation Wilfley Drylock Assembly General Installation Operating & General Servicing Clearance Settings Safety Precautions Spare Parts Ordering Assembly Instructions Model S3 General Installation Inspection upon

More information

Instruction Manual. 149-H/149-HS/212-J/412-J Microvac Pumps

Instruction Manual. 149-H/149-HS/212-J/412-J Microvac Pumps Instruction Manual S149-01-880 Issue F Original 149-H/149-HS/212-J/412-J Microvac Pumps Description Item Number 149H Microvac Rotary Piston Pump 230/460 V, 3 Ø, 60 Hz with 230/460 V Coil 900-149-011 149H

More information

Voltmaster Centrifugal Trash Pumps

Voltmaster Centrifugal Trash Pumps Voltmaster Centrifugal Trash Pumps Model TSP2, TSP3 and TSP4 Owner s Manual February 2011 Table of Contents 1 Introduction............................ 1 1.1 Read before using..................... 1 1.2

More information

PT, PTS & PTP Series Pump/Reservoirs

PT, PTS & PTP Series Pump/Reservoirs PT, PTS & PTP Series Pump/Reservoirs Installation, Operation and Maintenance Manual Table of Contents FOREWORD... 1 INSTALLATION... 1 RECEIVING INSPECTION... 1 RIGGING, HANDLING, AND LOCATING EQUIPMENT...

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, ADD, DDS, DDP

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, ADD, DDS, DDP INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, ADD, DDS, DDP The purpose of this manual is to aid in the proper installation and operation of the fans.

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL RBK FRP FAN

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL RBK FRP FAN Bulletin 62-January-20-09 ROOF UPBLAST & SIDEWALL CENTRIFUGAL FIBERGLASS EXHAUST FAN INSTALLATION, OPERATION, AND MAINTENANCE MANUAL RBK FRP FAN The M.K. Plastics catalog on the above corrosion resistant

More information

H.S. MACHINERY RING COMPRESSORS

H.S. MACHINERY RING COMPRESSORS OPERATION & PARTS MANUAL Thank you for purchasing an H.S Machinery Limited Regenerative Blower. This product is manufactured under strict ISO-9001-2000 quality control guidelines to ensure your satisfaction.

More information

DURAVAC RP SERIES MANUAL. Oil Lubricated, Rotary Piston Vacuum Pumps INSTALLATION OPERATION. Models RP-35 & RP-50 WARNING

DURAVAC RP SERIES MANUAL. Oil Lubricated, Rotary Piston Vacuum Pumps INSTALLATION OPERATION. Models RP-35 & RP-50 WARNING DURAVAC RP SERIES Oil Lubricated, Rotary Piston Vacuum Pumps Models RP-35 & RP-50 INSTALLATION OPERATION MANUAL WARNING DO NOT OPERATE BEFORE READING MANUAL US VACUUM PUMPS LLC P.O. BOX 909 CANTON, TX

More information

Fluid Coil Installation, Operation and Maintenance

Fluid Coil Installation, Operation and Maintenance Bulletin FCO&I 001 REV A Fluid Coil Installation, Operation and Maintenance Monika Hewlett Packard Company [Pick the date] FLUID COIL INSTALLATION, OPERATION & MAINTENANCE GUIDELINES Fluid Coil Installation,

More information

Swing Piston Compressors and Vacuum Pumps

Swing Piston Compressors and Vacuum Pumps Swing Piston Compressors and Vacuum Pumps NPK 018 AC Pressure NPK 018 DC Pressure NPK 018 AC Vacuum NPK 018 DC Vacuum Operating and Installation Instructions Read and observe these Operating and Installation

More information

LIQUIDYNAMICS Light Viscosity Bulk Transfer Cart

LIQUIDYNAMICS Light Viscosity Bulk Transfer Cart This manual contains important warnings and information. READ AND KEEP FOR REFERENCE. LIQUIDYNAMICS Light Viscosity Bulk Transfer Cart Instruction & Parts Manual This Manual Covers P/N 33271 P/N 33271

More information

SPECIFICATIONS: Tank Size: 80 gallons PUMP RPMs: 1050 CFM: 40PSI; 90 PSI Max Pressure: 150 PSI Thermal overload protection

SPECIFICATIONS: Tank Size: 80 gallons PUMP RPMs: 1050 CFM: 40PSI; 90 PSI Max Pressure: 150 PSI Thermal overload protection 5HP 80 GALLON TWO STAGE COMPRESSOR Models: 51866, 51870 CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or grind materials such as wood, paint, metal, concrete, cement,

More information

PRODUCT NUMBERING SYSTEM SERIES PHASE. HD: Heavy Duty (15,000+ hour life) SD: Standard Duty (5,000+ hour life) LD: Light Duty (2,000+ hour life)

PRODUCT NUMBERING SYSTEM SERIES PHASE. HD: Heavy Duty (15,000+ hour life) SD: Standard Duty (5,000+ hour life) LD: Light Duty (2,000+ hour life) TABLE OF CONTENTS Product Numbering System...1 Safety...2 Receiving and Inspection...2 Installation...2 Electrical...3 Parts Identification...7 Lubrication...9 INTRODUCTION The compressor you have purchased

More information

TriScroll TM 620 Series Dry Scroll Vacuum Pump

TriScroll TM 620 Series Dry Scroll Vacuum Pump vacuum technologies TriScroll TM 620 Series Dry Scroll Vacuum Pump INSTALLATION AND OPERATION MANUAL Manual No. 699904343 Revision E April 2007 TriScroll 620 Dry Scroll Vacuum Pump TriScroll is a trademark

More information

Farval. Dualine Installation System Start-Up. Bulletin DL300 BIJUR DELIMON INTERNATIONAL

Farval. Dualine Installation System Start-Up. Bulletin DL300 BIJUR DELIMON INTERNATIONAL Farval Dualine Installation System Start-Up Bulletin DL300 BIJUR DELIMON INTERNATIONAL 2685 Airport Road Kinston, NC 28504 Tel. 800-227-1063 Fax: 252-527-9232 website: www.bijurdelimon.com DC1-1 SECTION

More information

Operating Manual Includes Pumps: PG-9000 Part #R809606

Operating Manual Includes Pumps: PG-9000 Part #R809606 Operating Manual Includes Pumps: PG-9000 Part #R809606 Introduction Thank you for selecting the PG Series Pumps from Lifegard Aquatics. Before using this pump please take a moment to review this manual.

More information

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING SineWave Guardian TM 380V 600V INSTALLATION GUIDE FORM: SWG-IG-E REL. October 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of

More information

PRODUCT NUMBERING SYSTEM SERIES PHASE. 1: Single Phase 3: Three Phase

PRODUCT NUMBERING SYSTEM SERIES PHASE. 1: Single Phase 3: Three Phase TABLE OF CONTENTS Product Numbering System and Specifications... Safety... Receiving and Inspection... Installation... Electrical...6 Start-up...7 INTRODUCTION The compressor you have purchased is a combination

More information

1100W PORTABLE GENERATOR

1100W PORTABLE GENERATOR 1100W PORTABLE GENERATOR MODEL NO: G1200 PART NO: 8010110 OPERATION & MAINTENANCE INSTRUCTIONS LS0312 INTRODUCTION Thank you for purchasing this CLARKE 1100W Portable Generator. Before attempting to use

More information

D-Series Blowers and Exhausters

D-Series Blowers and Exhausters Operation and Maintenance Manual D-Series MONOXIVENT - SOURCE CAPTURE SYSTEMS - info@ Oct. - 2015 MONOXVENT BLOWERS AND EXHAUSTERS D05-1 D05-3 D10-1 D10-3 D15-1 D15-3 D20-1 D20-3 D30-1 D30-3 ½ HP TEFC

More information

36 HYPER MAX DIRECT DRIVE GALVANIZED BOX FAN

36 HYPER MAX DIRECT DRIVE GALVANIZED BOX FAN Assembly & Installation Manual Read carefully the information provided. Retain manual for future reference. 36 HYPER MAX DIRECT DRIVE GALVANIZED BOX FAN IS10063.DOC Step 1 Unpack and become familiar with

More information

M-3025CB-AV Fuel Pump

M-3025CB-AV Fuel Pump SAVE THESE INSTRUCTIONS M-3025CB-AV Fuel Pump Owner s Manual TABLE OF CONTENTS General Information... 2 Safety Instructions... 2 Installation... 3 Operation... 4 Maintenance... 4 Repair... 5 Troubleshooting...

More information

Hydraulic Immediate Need Power Pack

Hydraulic Immediate Need Power Pack Safety, Operation, and Maintenance Manual WARNING Improper use of this tool can result in serious bodily injury This manual contains important information about product function and safety. Please read

More information

Positive Displacement Pump

Positive Displacement Pump www.conairgroup.com U S E R G U I D E UGC028-1105 Positive Displacement Pump Models PD 3. 5, 7.5, 10, 15 and 25 Corporate Office: 724.584.5500 l Instant Access 24/7 (Parts and Service): 800.458.1960 l

More information

PHANTOM (PH10 and PH12) COMMERCIAL AND INDUSTRIAL SERIES

PHANTOM (PH10 and PH12) COMMERCIAL AND INDUSTRIAL SERIES Document No: ICM-IOM Date: 0411 PHANTOM (PH10 and PH12) COMMERCIAL AND INDUSTRIAL SERIES Installation, Operation and Maintenance Manual Please read and save these instructions. Read carefully before attempting

More information

Installation and Service Manual for RV33, RV332, RV75, RV752, RV100, RV1002

Installation and Service Manual for RV33, RV332, RV75, RV752, RV100, RV1002 Rotary Vane Compressors RV Series Installation and Service Manual for RV33, RV332, RV75, RV752, RV100, RV1002 Thank you for purchasing the Stratus RV series rotary vane compressor. This instruction manual

More information

Crispin Valves Operating Guide. Crispin

Crispin Valves Operating Guide. Crispin Crispin Valves Operating Guide Crispin Since 1905 Crispin Multiplex Manufacturing Co. 600 Fowler Avenue Berwick, PA 18603 1-800-AIR-VALV T: (570) 752-4524 F: (570) 752-4962 www.crispinvalve.com sales@crispinvalve.com

More information

Portable Electric/Gas Compressor Operating Instructions

Portable Electric/Gas Compressor Operating Instructions Portable Electric/Gas Compressor Operating Instructions NOTICE Carefully read this instruction manual before attempting to operate this compressor. MODEL # SERIAL # 1-800-551-2406 TABLE OF CONTENTS Safety

More information

H-2034, H-2035 SHRINK TUNNEL

H-2034, H-2035 SHRINK TUNNEL H-2034, H-2035 SHRINK TUNNEL SPECIFICATIONS IMPORTANT! Read this manual thoroughly and familiarize yourself with ALL controls and operating features. Keep this manual for future reference and maintenance.

More information

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Upblast Exhaust Fan (Standard & High Pressure Exhaust) Belt Driven for Roof & Wall Mounting

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Upblast Exhaust Fan (Standard & High Pressure Exhaust) Belt Driven for Roof & Wall Mounting READ AND SAVE THESE INSTRUCTIONS INSTALLATION, OPERATING INSTRUCTIONS & PARTS MANUAL Centrifugal Upblast Exhaust Fan (Standard & High Pressure Exhaust) Belt Driven for Roof & Wall Mounting Electrical wiring

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS Part #469003 Model Vektor -H Installation Operation and Maintenance Manual for Vektor-H Laboratory Exhaust System Receiving Greenheck model Vektor-H fans are thoroughly

More information

ATD-6810 SPRAY GUN W/CUP INSTRUCTION MANUAL

ATD-6810 SPRAY GUN W/CUP INSTRUCTION MANUAL ATD-6810 SPRAY GUN W/CUP INSTRUCTION MANUAL Read this Instruction Manual carefully and understand it completely, basic precaution should be strictly followed to prevent the damage to the tool and injury

More information

(SDU 50, SDU 90, and BKSDU) Shortening Disposal Unit * * Installation, Operation, Service, and Parts Manual

(SDU 50, SDU 90, and BKSDU) Shortening Disposal Unit * * Installation, Operation, Service, and Parts Manual Shortening Disposal Unit (SDU 50, SDU 90, and BKSDU) Installation, Operation, Service, and Parts Manual Frymaster, a member of the Commercial Food Equipment Service Association, recommends using CFESA

More information

Instruction Manual. 212-J/412-J Microvac Pumps

Instruction Manual. 212-J/412-J Microvac Pumps Instruction Manual S149-01-880 Issue G Original 212-J/412-J Microvac Pumps Description Item Number 212J Microvac Rotary Piston Pump 230/460 V, 3 Ø, 60 Hz with 230/460 V Coil 900-212-014 212J Microvac Rotary

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT DRIVE XBL FANS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT DRIVE XBL FANS INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT DRIVE XBL FANS The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

Water Treatment Plant Maintenance Considerations. Operation and Maintenance. Types of Maintenance 5/1/15

Water Treatment Plant Maintenance Considerations. Operation and Maintenance. Types of Maintenance 5/1/15 Water Treatment Plant Maintenance 1 Operation and Maintenance Purpose of O&M maintain design functionality (capacity) restore the system components to their original condition and thus functionality. Effective

More information

Installation and Operating Manual

Installation and Operating Manual Installation and Operating Manual L-Series Vacuum Pumps Models L/H400C-L/H630C INSTALLATION & OPERATING MANUAL L/H-SERIES SINGLE STAGE ROTARY VANE VACUUM PUMPS L/H400C-L/H630C Please read the manual before

More information

MARLEY ENGINEERED PRODUCTS OPERATING INSTRUCTIONS AND PARTS LIST

MARLEY ENGINEERED PRODUCTS OPERATING INSTRUCTIONS AND PARTS LIST MARLEY ENGINEERED PRODUCTS OPERATING INSTRUCTIONS AND PARTS LIST TUBE AXIAL DUCT FANS INDUSTRIAL PROPELLER FANS INDUSTRIAL ROOF EXHAUSTERS HEAVY DUTY MAN/PRODUCT COOLERS WARNING BY ACCEPTANCE OF THIS MERCHANDISE,

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

DISPLACEMENT PUMP INSTRUCTIONS-PARTS LIST Rev. K. Model , Series A Model , Series B Model , Series A

DISPLACEMENT PUMP INSTRUCTIONS-PARTS LIST Rev. K. Model , Series A Model , Series B Model , Series A INSTRUCTIONS-PARTS LIST INSTRUCTIONS This manual contains important warnings and information. READ AND KEEP FOR REFERENCE. DISPLACEMENT PUMP 308190 Rev. K 3000 psi (210 bar) MAXIMUM WORKING PRESSURE Model

More information

BOSS 107 SEPARATOR SYSTEM INSTALLATION & APPLICATION MANUAL

BOSS 107 SEPARATOR SYSTEM INSTALLATION & APPLICATION MANUAL Website: www.recoveredenergy.com Email: oilwatersales@recoveredenergy.com BOSS 107 SEPARATOR SYSTEM INSTALLATION & APPLICATION MANUAL BOSS 2.2T/107 BOSS 5T/107 BOSS 11T/107 BOSS 25T/107 BOSS 45T/107 Installation

More information