SPECIFICATION FOR EXTRUDED DIELECTRIC, SHIELDED POWER CABLES RATED 5 THROUGH 46 kv
|
|
- Oliver Lester
- 5 years ago
- Views:
Transcription
1 AEIC CS8-13 SPECIFICATION FOR EXTRUDED DIELECTRIC, SHIELDED POWER CABLES RATED 5 THROUGH 46 kv (4 th Edition) Association of Edison Illuminating Companies
2 AEIC CS8-13 SPECIFICATION FOR EXTRUDED DIELECTRIC, SHIELDED POWER CABLES RATED 5 THROUGH 46 kv (4 th Edition) Association of Edison Illuminating Companies 600 N. 18th St., P.O. Box 2641 Birmingham, Alabama September, 2013
3 Copyright 2013 by the Association of Edison Illuminating Companies No part of this specification may be reproduced in any form without the prior written permission of the Association of Edison Illuminating Companies. All rights reserved.
4 TABLE OF CONTENTS Paragraph Title Page LIST OF TABLES... V FOREWORD... VI DISCLAIMER... 1 PREFACE... 1 SCOPE INTRODUCTION Supporting AEIC Documents Test Reports Water Treeing Design Variables Summary Resampling Information Supplied by Purchaser Inquiries Guarantee Fault Current Requirements Alternative Proposals Operating Limits Maximum Conductor Temperatures Emergency Operating Temperatures Metallic Shield Short-Circuit Capability Ampacity Limits Industry Standards General Specification Requirements Cable Component Compatibility CONDUCTOR REQUIREMENTS CONDUCTOR SHIELD REQUIREMENTS Extruded Conductor Shield Thickness INSULATION REQUIREMENTS Temperature Requirements Thickness Requirements Diameter Requirements BIL Values INSULATION SHIELD REQUIREMENTS Thickness Requirements Diameter Requirements Removability Requirements METALLIC SHIELDING REQUIREMENTS MOISTURE BARRIER REQUIREMENTS JACKET REQUIREMENTS CABLE IDENTIFICATION Jacketed Cable Unjacketed Cable Options PRODUCTION TEST PROCEDURES Insulation Shield Field Strippability Test Field Strippability Test Procedure Partial Discharge Measurement GENERAL General Procedures Compliance Witnessing of Tests CS8-13 Page iii
5 Engineering Information Certified Test Reports Production Test Reports Production Test Record Retention Qualification Test Reports Shipping Length Location Testing Frequency Sampling Frequency Multiple Orders Per Lot Repairs SHIPMENT AND REELS Packing, Sealing, and Shipping Reels Marking on Reels GUARANTEE TESTS DURING AND AFTER INSTALLATION QUALIFICATION TESTS General Core Qualification Tests Tree Count Test Dissipation Factor Characterization Qualification Test Report Thermomechanical Qualification Test Optional Purpose Scope Electrical Measurements Physical Measurements Before and After the Thermomechanical Qualification Test Radial Resistivity after the Thermomechanical Qualification Test APPENDIX A INDUSTRY SPECIFICATIONS, STANDARDS, AND REFERENCES APPENDIX B CABLE DIAMETERS APPENDIX C PROCEDURE FOR DETERMINING DIAMETERS OF CABLE 5 THROUGH 46 KV APPENDIX D ANSI/ICEA TABLES INDEX Page iv CS8-13
6 LIST OF TABLES Table Title Page C-1 Insulation Shield Adders for Minimum Diameters Over Insulation 22 C-2 Adders for Maximum Insulation Diameter Calculation 23 C-3 Insulation Shield Adders for Maximum Diameters Over Insulation 23 C-4 Calculated Diameters Solid and Reverse-Lay Compressed Stranded Conductors Concentric Neutral Cables 25 C-5 Calculated Diameters Compact Stranded Conductors Concentric Neutral Cables 26 C-6 Calculated Diameters Solid and Reverse-Lay Compressed Stranded Conductors Flat Strap and Non-Concentric Neutral Cables 27 C-7 Calculated Diameters Compact Stranded Conductors Flat Strap and Non-Concentric Neutral Cables 28 D-1 Extruded Conductor Shield Thickness 29 D-2 Conductor Maximum Rated Temperatures 29 D-3 Conductor Size and Insulation Thickness 30 D-3(M) Conductor Size and Insulation Thickness (Metric) 30 D-4 BIL Values 30 D-5 Concentric Neutral Cable Insulation Shield Thickness and Concentric Neutral Indent 31 D-6 Flat Strap and Non-Concentric Neutral Cable Insulation Shield Thickness 31 D-7 Concentric Neutral Cable Extruded-to-Fill Jacket Thickness 31 D-8 Helical Tape, LC Tape, or Wire Shield Cable Jacket Thickness 32 D-9 Lead Sheath Cable Jacket Thickness 32 D-10 Nominal Insulation Thickness 32 CS8-13 Page v
LCT Shielded Primary UD TRXLP LCT Shielded Primary UD TRXLP Cable
ed Primary UD TRXLP ed Primary UD TRXLP Cable Aluminum or Copper Conductor. TRXLP Insulation. Copper Longitudinal Corrugated Tape (). Low Density Polyethylene Jacket. APPLICATIONS Predominantly used for
More informationLCT Shielded Primary UD EPR LCT Shielded Primary UD EPR Cable
ed Primary UD EPR ed Primary UD EPR Cable Aluminum or Copper Conductor. EPR Insulation. Copper Longitudinal Corrugated Tape (). Low Density Polyethylene Jacket. APPLICATIONS Predominantly used for primary
More informationHigh Voltage Aluminum, Smooth Aluminum Shield/Sheath
High Voltage Aluminum, Smooth Aluminum Shield/Sheath XLPE Insulation, HDPE Jacket, 69 kv - 138 kv Features True triple vertical extrusion system for optimum insulation concentricity, and excellent electric
More informationHigh Voltage Copper, Smooth Aluminum Shield/Sheath
High Voltage Copper, Smooth Aluminum Shield/Sheath XLPE Insulation, HDPE Jacket, 69 kv - 138 kv Features True triple vertical extrusion system for optimum insulation concentricity, and excellent electric
More informationANSI/NEMA WC ICEA No. S Portable and Power Feeder Cables for Use in Mines and Similar Applications
Approved as an American National Standard ANSI Approval Date: August 15, 2017 ANSI/NEMA WC 58-2017 ICEA No. S-75-381-2017 Portable and Power Feeder Cables for Use in Mines and Similar Applications Published
More informationMedium Voltage Power Cables
Medium Voltage Power s Distribution s (CN s) are suitable for use above ground in open air, in conduit in air, directly buried, in underground duct, or aerially when suspended on a messenger wire. CN cables
More informationC-L-X Aluminum Sheath Type IEC
COMPACT STRAND CONSTRUCTION C-L-X Aluminum Sheath A B C D E F G H J Conductor - Compact Stranded Copper Strand Screen - Extruded Semiconducting EPR Insulation - Okoguard EPR Insulation Screen - Extruded
More information4. SHIELDS. 4.1 Power Cable. 4.2 Electronic Cable Conductor Shield (Strand Shield) Outer Shield (Insulation Shield) 60
4. SHIELDS 4.1 Power Cable 4.1.1 Conductor Shield (Strand Shield) 60 4.1.2 Outer Shield (Insulation Shield) 60 4.2 Electronic Cable 4.2.1 Foil Shield 62 4.2.2 Copper Braid Shield 63 4.2.3 Spiral (Serve)
More informationRG7H1R-1,8/3 26/45 kv RG7H1OR-1,8/3 18/30 kv
Medium voltage - Energy RG7H1R-1,8/3 26/45 kv RG7H1OR-1,8/3 18/30 kv Structure and electrical, physical, mechanical requirements: CEI 20-13 IEC 60502 Flame propagation: EN 60332-1-2 Measurement of partial
More informationS.No. Tender Queries BRPL Reply 1 For 11KV(E) 3Cx300sqmm A2XWY High Ampacity cable conductor details specification not
S.No. Tender Queries BRPL Reply 1 For 11KV(E) 3Cx300sqmm A2XWY High Ampacity cable conductor details specification not clear.please provide Specification for High ampacity HT Cable with Trapezoidal wire
More informationEvolution of MV Cable Designs in the US from 1993 to 2014
Oct 2018 Sub A Evolution of MV Cable Designs in the US from 1993 to 2014 Evolution of MV Cable Designs in the US from 1993 to 2014 Essay Wen Shu & Nigel Hampton Several surveys were performed by Joe Dudas,
More informationOkoguard -Okoseal Type IEC
COMPACT STRAND CONSTRUCTION A B C D E F G H Conductor - Compact Stranded Copper Strand Screen - Extruded Semiconducting EPR Insulation - Okoguard EPR Insulation Screen - Extruded Semiconducting EPR Phase
More informationMedium Voltage Cable. marmonutility.com
Medium Voltage marmonutility.com Table Contents Introduction... 2 Hendrix Product Information... 4 Distribution s (URD) 15kV...6 25kV... 10 35kV...12 28kV...14 Electrical Data...16 Kerite Product Information...
More informationQuick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications
Quick Splice II 5451R (CN) Cable (JCN) Cable Accessory Splice Jacket 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet 1. Product Description The 3M 5451R Quick Splice II is a 25/28 kv class
More informationEasy-On II Terminations
Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables, concentric neutral, metal tape shielded or wire shielded cables without need for additional
More informationRaychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions
Raychem CSJA 1521 Cold-Shrinkable Splice for single core polymeric insulated (XLPE-EPR) cables up to 15kV for tape, wire, Unishield, LC shield, JCN, and flat strap neutral cable UniShield is a trademark
More informationOn-Site Guide (BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011)
(BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011) Author: IET Publications (edited by Mark Coles) Book details Author: IET Publications (edited by Mark Coles) Year: 2011 Format: Paperback,
More informationQuick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description
Quick Splice II 5461 (CN) Cable (JCN) Cable 35 kv Molded Rubber Inline Splicing Kit Data Sheet Accessory Splice Jacket 1. Product Description The 3M 5461 Quick Splice II is a 35 kv class inline splice
More information3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series
3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series Data Sheet 1. Product Description 3M Cold Shrink Termination Kit QT-III 7672-S-8 Series contains one silicone rubber termination
More informationMedium Voltage Cables for PermaLife Nuclear Utility Applications
Medium Voltage Cables for PermaLife Nuclear Utility Applications The science behind our medium voltage cables. Fig. 1 Fig. 2 non-conducting stress control layer 100% production tested in accordance with
More informationINSTALLATION PRODUCTION TESTS
Deadbreak Apparatus Connectors 600 A 15/25 kv Class Bol-T Deadbreak Connector Electrical Apparatus 600-10 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class Bol-T Deadbreak Connector is used to terminate
More informationQS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.
QS-III 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits Data Sheet Tape Shield Wire Shield UniShield Kit Contents: 1 Cold Shrink Silicone Rubber Splice Body 1 Cold Shrink Adapter Tube
More informationMetallic Gaskets for Pipe Flanges
ASME B16.20-2012 (Revision of ASME B16.20-2007) Metallic Gaskets for Pipe Flanges Ring-Joint, Spiral-Wound, and Jacketed AN AMERICAN NATIONAL STANDARD ASME B16.20-2012 (Revision of ASME B16.20-2007) Metallic
More information3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series
3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series Data Sheet March 2011 Description 3M Cold Shrink 1/C Transition Splice Kits QS-III, 5510A-1T-PILC Series (which includes 5513A-1T-PILC,
More information600 A 35 kv class BT-TAP deadbreak connector
Supersedes 600-55 July 2014 600 A 35 kv class BT-TAP deadbreak connector General Eaton's Cooper Power Systems 600 A 35 kv Class BT-TAP deadbreak connector is used to terminate high-voltage underground
More informationDeadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL
Deadbreak Apparatus Connectors 600 A 15/25 kv Class BOL-T Deadbreak Connector Electrical Apparatus 600-30 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class BOL-T Deadbreak Connector is used to terminate
More informationLoadbreak Apparatus Connectors
Loadbreak Apparatus Connectors 200 A 25 kv Class POSI-BREAK Loadbreak Elbow Connector with Optional Integral Jacket Seal* Electrical Apparatus 500-29-7 general The POSI-BREAK Loadbreak Elbow Connector
More informationFIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z
PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install fixed power factor correction equipment as specified herein and as shown on the contract drawings. This specification
More informationFTG10OM1-0,6/1KV. 50 N/mm 2 of copper section max for fixed layings
HEPR insulated flexible with braided shield of red copper wires and plastic sheath of halogen-free flame retardant and without emission of corrosive gases. The keeps the electrical characteristics for
More information3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A
3M Cold Shrink QS-III Inline Splice Kits 15 kv Data Sheet June 2014! CAUTION Working around energized high-voltage systems may cause serious injury or death. Installation should be performed by personnel
More informationSPECIFICATION S VR 1(4) HALOGEN FREE POWER AND CONTROL CABLE FOR MARINE APPLICATIONS LM-HF 0,6/1 kv and TEMAR PHFX-U 0,6/1 kv APPLICATI
1(4) HALOGEN FREE POWER AND CONTROL CABLE FOR MARINE APPLICATIONS LM-HF 0,6/1 kv and TEMAR PHFX-U 0,6/1 kv APPLICATION Power and control cable for fixed installations. Designed to fulfill requirements
More informationTechnical Specification For Outdoor Substation Harmonic Filter Banks
Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field
More informationN2XSEFGbY 3 x (25-300) mm² 3.6/6 kv
N2XSEFGbY 3 x (25-300) mm² 3.6/6 kv N2XSEFGbY 3 x (25-300) mm² 3.6/6 kv (Copper, XLPE Insulated, Copper Tape,, PVC Sheathed) 25 38.5 2,603 35 41.5 3,074 50 44.5 3,641 70 48.5 4,536 95 52.0 5,542 120 56.0
More informationTests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50
Deadbreak Apparatus Connectors 600 A 35 kv Class Bol-T Deadbreak Connector Electrical Apparatus 600-50 General The Cooper Power Systems 600 A, 35 kv Class Bol-T Deadbreak Connector is used to terminate
More informationMC or MV-105 Copper, TR-XLPE Insulated
MC MV-105 Copper, TR-XLPE Insulated 5 kv 35 kv, Shielded Features UL listed as MC MV-105. Cable jacket rated f Sun Resistant and Oil resistant. s 1/0 and larger are UL Listed as CT USE in accdance with
More information200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition
Loadbreak Connectors CA650101EN Supersedes 500-29-7C November 2011 COOPER POWER SERIES 200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition
More informationMEDIUM VOLTAGE
WWW.GENERGYCABLE.COM 800-308-1330 TM MEDIUM VOLTAGE MEDIUM VOLTAGE ASSEMBLIES Type SH Medium Voltage Power Cable Assemblies are designed for heavy-duty MV applications that require temporary or permanent
More informationNEC 2014 Code Changes
NEC 2014 Code Changes Articles 310 310.120 CHANGES FROM 2011 TO 2014 CODE ARE IN RED ARTICLE 310 Conductors for General Wiring I. General 310.2 Definitions Electrical Ducts Electrical conduits, or other
More informationHigh Voltage and Extra High Voltage Cables
High Voltage and Extra High Voltage Cables GUIDE TO THE SELECTION OF EHV AND HV CABLES EHV and HV cables are specially designed on the basis of the project data. To determine appropriate design of a high
More informationGas Turbine Aircraft Engines
ASME PTC 55-2013 Gas Turbine Aircraft Engines Performance Test Codes AN AMERICAN NATIONAL STANDARD ASME PTC 55-2013 Gas Turbine Aircraft Engines Performance Test Codes AN AMERICAN NATIONAL STANDARD Two
More informationTABLE OF CONTENTS Page
TABLE OF CONTENTS Page Objective 3 Summary 3 Conclusion 3 Sample Preparation 4 Testing 4 Test Results 5 Summary of Test Results (Table 1) 6 Appendix I 7 Addendum 1 8 2 I. OBJECTIVE To evaluate the performance
More informationBioprocessing Equipment
ASME BPE-2007 (Revision of ASME BPE-2005) Bioprocessing Equipment A N I N T E R N A T I O N A L S T A N D A R D ASME BPE-2007 (Revision of ASME BPE-2005) Bioprocessing Equipment AN AMERICAN NATIONAL STANDARD
More information200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition
Loadbreak Connectors Catalog Data CA650063EN Supersedes 500-10-7C November 2011 COOPER POWER SERIES 200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition General
More informationCorflex. Continuous Corrugated Aluminum Sheathed PL, MC and MV Industrial Cables. Introduction Applications... 3
Corflex Continuous Corrugated Aluminum Sheathed PL, MC and MV Industrial Cables Introduction................................. 2 Applications................................. 3 Corflex PL 300V Instrumentation
More informationLarge Diameter Steel Flanges
ASME B16.47-2011 (Revision of ASME B16.47-2006) Large Diameter Steel Flanges NPS 26 Through NPS 60 Metric/Inch Standard AN AMERICAN NATIONAL STANDARD ASME B16.47-2011 (Revision of ASME B16.47-2006) Large
More informationOFFSHORE WIND FEASIBILITY STUDY APPENDICES Appendix C.2 Subsea Cable Data Sheets
OFFSHORE WIND FEASIBILITY STUDY APPENDICES 10-7 10.3.2 Appendix C.2 Subsea Cable Data Sheets Design data for TFVA 36 kv 3x1x240 mm 2 KQ Metallic Laying up Inner sheath Bedding Armor Diameter of conductor
More informationDURAREEL TRAILING REELING CABLE
Supplementary Technical Information Reeling and trailing material characteristics: A. Power core conductor Flexible strands tinned annealed copper complies with AS/NZS 1802, AS/NZS 2802, AS/NZS 1125, and
More informationLIST OF PUBLISHED STANDARDS
Report : 08-0-6 Page o : Of 5 LST OF PUBLSHED STDRDS Total Count: 78 umber SS umber pproved mendment SBS/TC 066 SS 97:07 7.0 Electric cables - mpregnated paper-insulated 07-0-7 metal-sheathed cables for
More informationCables for Space Applications
Cables for Space Applications Summary Company profile... Page 2 Cross Reference Table... Page 3 ESA ISO9001/EN9100 Certificates... Page 4 SCC 3901 001 Series... Page 7 SCC 3901 002 Series... Page 11 SCC
More informationSubmarine Power Cables
Submarine Power Cables Submarine Power Cables Since decades Nexans plant in Hannover is specialised in the design, production and installation of low and medium voltage submarine power cables required
More informationN2XSEBY 3 x (25-300) mm² 3.6/6 kv
N2XSEBY 3 x (25-300) mm² 3.6/6 kv N2XSEBY 3 x (25-300) mm² 3.6/6 kv (Copper, XLPE Insulated, Copper Tape,, PVC Sheathed) 25 38.5 2,417 35 41.0 2,865 50 44.0 3,391 70 48.0 4,272 95 51.5 5,266 120 55.5 6,232
More information600 A 15 kv class T-OP II deadbreak connector
Deadbreak Apparatus Connectors CA650017EN Supersedes 600-12 February 2010 COOPER POWER SERIES 600 A 15 kv class T-OP II deadbreak connector General Eaton terminates high-voltage underground cable to transformers,
More informationCaledonian Medium Voltage Cables
Three Core Cables to VDE 0276 APPLICATIONS: The three core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 3.6/6.6KV to 19/33KV and frequency 50Hz. They
More informationType MMV-WP Medium Voltage Wind Power Cable
WP Type MMVWP Medium Voltage Wind Power Cable ThreeConductor: 5kV & 5kV, % Rated 05 C Renewable Energy Cables Conductors Soft annealed flexible stranded tinned copper per IEEE 580 Table and UL 07 Insulation
More information3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv
3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv Data Sheet September 2014 Description 3M Cold Shrink QT-III Silicone Rubber Termination Kits, 7640-T
More informationMEDIUM VOLTAGE TERMINATIONS
CAT010509- Rev 1. 2009 INERTIA- REPL INC. All rights reserved Printed January 2009 MEDIUM VOLTAGE TERMINATIONS General Information about Heat-shrinkable Terminations 3.00 T50NS Terminations for 5-8 kv,
More information200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition
Loadbreak Connector CA650099EN Supersedes 500-28-7C November 2011 COOPER POWER SERIES 200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition General Eaton
More informationCaledonian Medium Voltage Cables
Three Core Cables to VDE 0276 APPLICATIONS: The three core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 3.6/6.6KV to 19/33KV and frequency 50Hz. They
More informationQuintas & Quintas Group
Electric Conductors Quintas & Quintas Group Index Quintas & Quintas and Solidal 2 Bare Conductors l uminium Conductors for overhead lines 3 l uminium loy Conductors for overhead lines 4 uminium Conductors
More informationCaledonian Medium Voltage Cables Three Core Cables to VDE 0276-
Three Core Cables to VDE 0276 APPLICATIONS The three core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 3.6/6.6KV to 19/33KV and frequency 50Hz. They are
More informationCABLED TWISTED PAIRS CONDUCTORS
CABLED TWISTED PAIRS CONDUCTORS NQP SERIES Twisted Pair uctors Mil Spec, U.L. AWM Recognized Style 2464 and CSA Certified AWM II A/B GRAY PVC JACKET National Wire & Cable Corporation manufactures a complete
More informationCABLED SINGLE CONDUCTORS
CABLED SINGLE CONDUCTORS NQ SERIES Single uctors Mil Spec, U.L. AWM Recognized Style 2464 and CSA Certified AWM II A/B GRAY PVC JACKET National Wire & Cable Corporation manufactures a complete line of
More information3M Cold Shrink Splice Kits, QS T Series
3M Cold Shrink Splice Kits, QS-2000-3T Series For 15 kv Trifurcating Transition Splice Kits Data Sheet October 2011 Description 3M Cold Shrink Splice Kits, QS-2000-3T Series for 15 kv Trifurcating Transition
More information1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide
1ZSC563-AAA EN, REV. 7 Transformer bushings type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationLoadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL
Loadbreak Apparatus Connectors 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal Electrical Apparatus 500-10-7 GENERAL The Cooper Power Systems Loadbreak Elbow Connector is
More information1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide
1ZSC563-AAA en, Rev. 6 Resin impregnated paper bushing, oil to SF 6, type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover
More information600A Deadbreak Elbow. K656LR Elbow Connector (with Test Point) Features:
Issue Date: 07/17/2017 Page: 1 of 5 PSS- K656LR Elbow Connector (with Test ) Applications: The Elastimold K656LR (with test point) is designed to provide fully shielded, dead-front submersible cable connections
More informationMedium Voltage Catalog
Medium Voltage Catalog Insulate. Seal. Protect. Welcome to the DSG-Canusa Product Catalog The DSG-Canusa catalog includes information on all major products that we carry to service Electrical/ Utility,
More informationAustralian Standard. Uninterruptible power systems (UPS) Part 1.1: General and safety requirements for UPS used in operator access areas
AS 62040.1.1 2003 IEC 62040-1-1:2002 IEC 62040-1-1:2002/Corr.1:2002 Reconfirmed 2013 AS 62040.1.1 Australian Standard Uninterruptible power systems (UPS) Part 1.1: General and safety requirements for UPS
More informationThis document is a preview generated by EVS
INTERNATIONAL STANDARD ISO 10924-2 First edition 2014-02-15 Road vehicles Circuit breakers Part 2: User s guide Véhicules routiers Coupe-circuits Partie 2: Guide de l utilisateur Reference number ISO 10924-2:2014(E)
More informationPROTOLON(FL)-LWL (N)TSFLCGEWOEU 3,6/6 kv: medium voltage flat reeling cable with fibre-optics
PROTOLON(FL)-LWL (N)TSFLCGEWOEU 3,6/6 kv: medium voltage flat reeling cable with Application Flexible medium voltage reeling cable for high mechanical stresses (e.g. dynamic tensile loads, multiple changes
More informationAFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
PART B-07 TITLE: SERVICE CONNECTIONS SPECIFICTION NO: B-07 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) AMENDMENTS / REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
More informationProduct Number
Sealing and Grounding Cold Shrink cable accessory sealing kits are designed to seal the end of JCN cable. Use these kits when installing elbows or other cable accessories that do not include a jacket seal.
More informationNA2XSEKRY 3 x (25-300) mm² 3.6/6 kv
NA2XSEKRY 3 x (25-300) mm² 3.6/6 kv NA2XSEKRY 3 x (25-300) mm² 3.6/6 kv (Aluminium, XLPE Insulated, Copper Tape, Lead Sheathed,, PVC Sheathed) 25 47.5 5,292 35 50.5 5,960 50 53.5 6,694 70 58.5 7,816 95
More informationTerminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M
Terminations Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M Cold Shrink QT-III Silicone Rubber Terminations 265 3M Cold Shrink Termination QT-III 69 kv/72,5 kv 270 3M Cold Shrink
More informationSafety Code for Existing Elevators and Escalators
ASME A17.3-2011 (Revision of ASME A17.3-2008) Safety Code for Existing Elevators and Escalators Includes Requirements for Electric and Hydraulic Elevators and Escalators A N A M E R I C A N N A T I O N
More informationN2XSERY 3 x (25-300) mm² 3.6/6 kv
N2XSERY 3 x (25-300) mm² 3.6/6 kv N2XSERY 3 x (25-300) mm² 3.6/6 kv (Copper, XLPE Insulated, Copper Tape,, PVC Sheathed) 25 41.0 3,102 35 43.5 3,587 50 48.0 4,576 70 52.0 5,579 95 55.5 6,642 120 59.5 7,711
More informationLISTED. Applications. Features CORDAFLEX (SM) CORDAFLEX (SM)
CORDAFLEX (SM) Portable reel cable EP insulation, dual neoprene jacket with braid reinforcement, 90 C, 600 volts Rack and pinion elevators using sheave guided cables Container crane spreader reels Timber
More information56-SDMS-07 REV. 01 SPECIFICATIONS FOR
56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice
More informationMobile and Locomotive Cranes
ASME B30.5-2014 (Revision of ASME B30.5-2011) Mobile and Locomotive Cranes Safety Standard for Cableways, Cranes, Derricks, Hoists, Hooks, Jacks, and Slings AN AMERICAN NATIONAL STANDARD ASME B30.5-2014
More informationNA2XSEKY 3 x (25-300) mm² 3.6/6 kv
NA2XSEKY 3 x (25-300) mm² 3.6/6 kv NA2XSEKY 3 x (25-300) mm² 3.6/6 kv (Aluminium, XLPE Insulated, Copper Tape, Lead Sheathed, PVC Sheathed) 25 39.5 3,292 35 43.0 3,824 50 46.0 4,419 70 50.5 5,264 95 54.5
More information11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE
11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE 11.1 GENERAL Only single conductor cables as described in this section are acceptable for connection to PECO Energy Company
More informationUNDERGROUND TRANSMISSION SOLUTIONS PRODUCT CATALOG
UNDERGROUND TRANSMISSION SOLUTIONS PRODUCT CATALOG SOUTHWIRE SOLUTIONS FOR UNDERGROUND TRANSMISSION CABLES SERVICES XLPE Cables 69 through 400 kv with Copper and Aluminum conductors through 6,800 kcmil
More informationTechnical Specification for Pole Mounted Capacitor Rack
Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to
More information600 A 25 kv class BT-TAP deadbreak connector
Deadbreak Connectors Catalog Data CA650001EN Supersedes January 2015 600 A 25 kv class BT-TAP deadbreak connector COOPER POWER SERIES General Eaton terminates high-voltage underground cable to transformers,
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More informationMedium Voltage. Joints & Terminations
57 - Cold Shrink Joints Supporting Core Radially shrinkable elastomeric splice Semi-conductive layer High permitivity insulation layer 6.6/11/(12) kv 3M QS1000 is a one-piece cold shrink joint body manufactured
More informationHigh Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide
1ZUA2761-500 rev. 5, 6 April 2010 High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide 1ZUA2761-500 rev. 5, 6 April 2010 2 / 9 Table of contents 1 Description... 3 2 Ratings...
More informationProduct Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526
Product HVS Series Cable Splice Shim Kit for 1/C Extruded Dielectric (Poly/EPR) Power Cables: Metallic Tape, Wire Shield, UniShield, LC Shield, Lead Sheath or Concentric Neutral URD Cables UniShield is
More informationList of Malaysian Standard (MS) for Cables. Prepared by MCMA SWO. Cable - Armoured. Cable - Armoured
List of Malaysian Standard (MS) for Cables Prepared by MCMA SWO NO. PUBLICATIONS 1. MS 2100 : 2007 2. MS 2101 : 2007 3. MS 2102 : 2007 4. MS 2103 : 2007 5. MS 2104 : 2007 6. MS 2105 : 2007 7. MS 2106 :
More informationCold Shrink QS T Trifurcating Transition Splice Kit
Cold Shrink QS2012-13-3T Trifurcating Transition Splice Kit Instructions IEEE Std. 404-1993 15 kv Class 110 kv BIL Completed Splice Cable Size Range Requirements PILC 500 kcmil Conductor Size (240 mm 2
More informationAS AS Australian Standard. Starter batteries Lead acid. This is a free 6 page sample. Access the full version online.
AS 2149 2003 AS 2149 Australian Standard Starter batteries Lead acid This Australian Standard was prepared by Committee EL-005, Secondary Batteries. It was approved on behalf of the Council of Standards
More information200 A 15 kv class loadbreak elbow connector with optional integral jacket seal
Loadbreak Connectors Catalog Data CA650062EN Supersedes June 2015 COOPER POWER SERIES 200 A 15 kv class loadbreak elbow connector with optional integral jacket seal General Eaton s Cooper Power series
More informationThis document is a preview generated by EVS
INTERNATIONAL STANDARD ISO 10924-1 Second edition 2016-04-01 Road vehicles Circuit breakers Part 1: Definitions and general test requirements Véhicules routiers Coupe-circuits Partie 1: Définitions et
More informationYour Partner in Safe Power Solutions. About RESCAB
Your Partner in Safe Power Solutions About RESCAB Red Sea Cables Company (RESCAB) was established as a closed joint stock company in 2008 in the Kingdom of Saudi Arabia with a capital of 370 million SAR.
More informationSouthwire Company. Current Rating 70 AMPERE (60 DEG C), 85 AMPERE (75 DEG C), 95 AMPERE (90 DEG C) Ground Conductor Size
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 SEU43500 4-4-4 Seu Cable-500' Southwire Company Catalog Number SEU43500 Manufacturer Southwire Company Description Copper
More informationINTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.
INTRODUCTION The Power Systems 44 kv MiniSub TM is the most compact system at this voltage available. Utilizing a deadfront termination and lightning arrestor setup, it eliminates the line top or side
More informationACCELERATED CABLE AGING TESTS for DISTRIBUTION and TRANSMISSION CABLES PART 1 HV AC PAPER CABLES
ACCELERATED CABLE AGING TESTS for DISTRIBUTION and TRANSMISSION CABLES PART 1 HV AC PAPER CABLES Joseph T. Zimnoch Consultant ICC Educational Program October 26, 2011 Denver, Colorado ACKNOWLEDGMENT The
More informationJDR PRODUCT APPLICATIONS. MCE Deepwater Development 2017
Innovative 72 kv Wet-Design Cables for Dynamic Deepwater Power Umbilicals James Young, Chief Technology Officer JDR Cable Systems Ltd NH GRAND HOTEL KRASNAPOLSKY AMSTERDAM 3-5 APRIL 2017 JDR PRODUCT APPLICATIONS
More informationPower & Control Cables. U o. /U 0.6/1 kv - IEC
Power & Control Cables U o /U 0.6/1 kv - IEC 60502-1 2 KERPEN GmbH & Co. KG 07.2005 Printing errors excepted. Subject to alteration List of Contents Introduction Page B1 Construction Page B3 Use Page B4
More information