Dynamic Reactive Power Control for Wind Power Plants

Size: px
Start display at page:

Download "Dynamic Reactive Power Control for Wind Power Plants"

Transcription

1 Dynamic Reactive Power Control for Wind Power Plants Ernst Camm, Charles Edwards, Ken Mattern, Stephen Williams S&C Electric Company, 6601 N. Ridge Blvd, Chicago IL USA Abstract Hybrid reactive power compensation systems consisting of inverter-based dynamic compensators and mechanically-switched shunt capacitor and reactor banks provide an economical means of meeting typical grid code requirements for power factor and voltage control. Furthermore, the inverter-based dynamic component of the hybrid compensation system has short-time capabilities on the order of 264 percent of its steady-state rating for up to 3 seconds. These capabilities could reduce the overall reactive power system requirements in wind power plants where all wind turbine generators (WTGs) respond fast enough to allow dynamic power factor capabilities of the WTGs to be utilized to meet the grid code requirements for power factor control. The same short-time capabilities can also assist WTGs in meeting fault ride-through requirements. This paper provides an overview of the capabilities of the hybrid reactive power compensation system, typical configurations and ratings, and application examples. Index Terms grid code, hybrid reactive compensation system, power factor, wind power plant, wind turbine generators. I. INTRODUCTION Modern wind turbine generators (WTGs) have capabilities to dynamically control the power factor or voltage at the terminals of the generators. Grid codes typically require wind power plants to be able to vary their power factor to meet system operating conditions. In Spain the Royal Decrees 436/2004 [1] and 661/2007 [2] determines bonus payments for reactive power between 0.90 inductive and unity, based on an hourly assessment. Payments for the power factor at the point of connection (POC) can be positive or negative, depending on the actual power factor and the time of day as defined in Royal Decree 436/2004 [3] and summarized in Table I. The payment is defined as a percentage of the reference or average tariff and varies from -4% for a power factor of less than 0.95 inductive at peak and flat rate periods to +8% for a power factor of less than 0.95 inductive in valley periods or less than 0.95 capacitive in peak rate periods. In many cases the power factor at the wind power plant s POC is controlled using the dynamic power factor capabilities of the WTGs and a central wind plant management system. In cases where WTGs do not have the capability, switched power factor correction capacitors in the WTGs or medium-voltage mechanically switched capacitor banks in the substation are used to maintain the desired power factor at the POC. TABLE I. BONUS/PENALTY BY DEMAND PERIOD FOR SPANISH WIND POWER PLANTS. 1 Inductive Capacitive Power Factor Bonus/Penalty by demand period [% of reference tariff] Peak (Punta) Flat (Llano) Valley (Valle) < to < to < to < to < to < to < to < to < < II. INVERTER-BASED DYNAMIC COMPENSATORS Voltage source inverter technologies using pulse width modulation techniques to synthesize a voltage either greater than or less than the bus where the inverters are connected are now widely used in wind power plants for power factor or voltage control. See Figure 1. Commercial inverterbased dynamic compensators are available in modules of ±1.25 MVAR at 480 V and having short-term capabilities of 3.3 MVAR per module (i.e. 264% of the continuous rating) for up to 3 seconds. These units have the capability to swing from full inductive to full capacitive output, or vice versa, in about 2 milliseconds based upon the response time of the current control loop. Two modules can be connected to a single 2.5 MVA, 0.48/33 kv step-up transformer for connection to a 33 kv (or other medium voltage) collector substation. See Figure 2. Figure 3 shows two inverter modules for connection to a single step-up transformer. 1 The peak periods last from 11 to 21h in the winter, and from 12 to 22h in the summer. Valley periods last from 0 to 11h and 21 to 24h in the winter, and 0 to 12h and 22 to 24h in the summer. Other times fall in the flat period.

2 Larger dynamic compensators are comprised of multiple ±2.5 MVAR units with step-up transformers. Sometimes a single ±1.25 MVAR module is connected via its own stepup transformer if the total MVAR rating requires an odd number of inverters. Figure 1. Single-line diagram of ±1.25 MVAR, 480 V voltage source inverter module. Figure 2. Single-line diagram of two ±1.25 MVAR inverter modules and step-up transformer. III. HYBRID REACTIVE POWER COMPENSATORS Hybrid reactive power compensators consist of an inverter-based dynamic compensator and one or more medium-voltage mechanically-switched shunt capacitor banks and reactors, which are normally connecting to the collector bus of the wind power plant. The dynamic compensator can control up to six switched shunt devices (SSDs) and can be configured to control either voltage, reactive power, or power factor at the collector bus or at the POC. The dynamic compensator is typically sized such that the largest capacitor or reactor bank does not exceed about 70 to 75% of the rated total dynamic range (i.e. full inductive to full capacitive MVAR) of the dynamic compensator. The dynamic compensator will typically be configured to switch on a capacitor when it reaches a specified capacitive MVAR output level. Similarly, it will switch off a capacitor or switch on a reactor when it reaches a specified inductive MVAR output level. Figures 4 and 5 show the configuration of a typical hybrid reactive power compensation system and the actual physical arrangement of the same system. In this case the system consists of a ±6.25 MVAR dynamic compensator, two 8 MVAR, 33 kv shunt capacitor banks, and one 8 MVAR shunt reactor. This system provides reactive power in the range of 0.95 leading (inductive) to 0.95 lagging (capacitive) power factor at the 33 kv POC for a 48 MW wind power plant. Figure 3. Two ±1.25 MVAR inverter modules. Figure 4. Typical single-line diagram of a hybrid reactive power compensator.

3 Figure 5. Actual installation of the hybrid reactive power compensator shown in Figure 4. Collector and utility switchgear are located at the back. The inverters associated with the dynamic reactive power compensator are located in the container on the right. IV. POWER FACTOR CONTROL USING HYBRID REACTIVE POWER COMPENSATORS Hybrid reactive power compensators can be used to dynamically control the power factor at the POC with response times dictated by intentional delays associated with the switching of SSDs in the compensator. Through local collector bus voltage and current sensing and slow feedback of voltage and current at the POC through SCADA, the compensator can dynamically control the power factor at a remote POC using a line drop compensation algorithm. Figure 6 shows actual measurements associated with a hybrid reactive power compensator for a 90 MW wind power plant where the POC is at 345 kv, 37 km away from the collector substation. In this case the compensator is controlling the power factor at the POC at unity (i.e., zero net MVAR at the POC). MW, MVAR WPP MW INVERTER MVAR WPP NET MVAR Hours Figure 6. Actual hybrid reactive power compensator power factor control performance for a 90 MW wind power plant. Vertical changes in inverter MVAR output indicate where switching of capacitor banks occur. A hybrid reactive power compensator offers several advantages relative to additional switched power factor correction capacitors applied at the WTG low voltage terminals: The power factor of the wind power plant can be dynamically controlled without changing the power factor setpoints of individual WTGs, increasing the overall speed of response. The power factor at the WTG terminals can be independently controlled at or near unity power factor, thereby minimizing reactive current flow through the WTG step-up transformers and the collector system. This effectively reduces active and reactive power losses in the wind power plant. A wind farm management system is not required to control reactive power in the wind power plant. The available reactive power from the compensator can be utilized at all power output levels of the wind power plant, compensating for collector cable charging (capacitive) reactive power at zero and low power output levels or providing reactive power in accordance with a defined daily schedule based on power factor requirements such as those in [3]. Compared to using only mechanically-switched capacitor banks in the collector substation, the hybrid reactive power compensator offers the following advantages: The power factor at the POC can be controlled more precisely over the entire output range of the wind power plant. The number of switching events of capacitor banks is reduced due to the dynamic reactive power range of the inverters, thereby increasing the life of the capacitor bank switching devices. In addition, the number of occurrences of off delays due to capacitor banks discharging is reduced. The dynamic compensator control algorithm distributes the number of switching operations of any single capacitor bank based on historical number of switching operations, resulting in more even wear on capacitor switching devices and prolonged life in multiple capacitor bank applications. The severity of the capacitor-switching transients associated with the energization of the capacitor banks can be reduced slightly by the inverter control action. The same advantages listed in the last two items of the list above apply as well.

4 V. HARMONIC RESONANCE AND HARMONIC CURRENT INJECTION BY WTGS As in any situation where shunt capacitor banks are applied, the application review of the hybrid reactive power compensator must include a review of potential harmonic resonance conditions. The review will typically include detailed harmonic resonance analysis, including impedance frequency scans for various operating conditions of the wind power plant and harmonic distortion analysis based on representative ambient harmonic levels (i.e. harmonics present in the system without the wind power plant) or harmonic currents injected by WTGs. In cases where WTGs with power factor correction capacitors are involved, careful attention must also be paid to any potential resonance conditions caused by the WTG capacitors. In cases where resonance conditions with high local impedances at characteristic harmonic frequencies (i.e. 5 th, 7 th, 11 th, 13 th, etc. harmonics) are identified, capacitor banks in the hybrid reactive compensation system can be converted to harmonic filter banks. In wind power plants using WTGs with power factor correction capacitors where resonance conditions are caused by the WTG capacitors, a damped C-type filter is commonly used to lower the local impedance of the wind power plant over a wide range of frequencies. See Figures 7 and 8. In wind power plants utilizing WTGs with doubly-fed induction generators (DFIG) or full-converter WTGs with appreciable levels of harmonic current injection, it is sometimes necessary to apply a high-pass filter to prevent some of the harmonic currents from flowing into the system and causing high levels of harmonic voltage and current distortion. See Figure 9. If a hybrid compensator is applied in this situation, one or more of the capacitor banks can be converted to high-pass filters to address this issue. Z Harmonic number (n) Low Output High Output Damped Figure 8. Wind power plant impedance frequency scan with and without a damped C-type harmonic filter. Figure 9. Single-line diagram of a typical high-pass harmonic filter. VI. SUMMARY Hybrid reactive power compensation systems consisting of inverter-based dynamic compensators and mechanicallyswitched shunt capacitor and reactor banks provide an economical means of meeting typical grid code requirements for power factor and voltage control. The application and associated wind power plant and power system parameters must be carefully reviewed to optimize the design of the hybrid reactive power compensator and to identify any potential resonance conditions that may be caused by WTG power factor correction capacitors or collector substation capacitors applied in the hybrid compensator. REFERENCES Figure 7. Single-line diagram of a typical damped C-type harmonic filter. [1] Secretary of State for Energy, Industrial Development and Small Businesses, Spanish Ministry of Economy, Real Decreto 2818/1998 sobre producción de energía eléctrica por instalaciones abastecidas por recursos o fuentes de energía renovables, residuos ycogeneración, December ,

5 [2] Ministry of Industry, Tourism and Commerce, BOE 126, Royal Decree 661/2007, por el que se regula la actividad de produccion de energia electrica en regimen especial, 25 May [3] Ministry of Economy, Real Decreto 436/2004, de 12 de marzo, por el que se establece la metodología para la actualización y sistematización del régimen jurídico y económico de la actividad de producción de energía eléctrica en régimen especial

Grid code Compliance and Renewable Energy Projects. Mick Barlow, Business Development Director, S&C Electric, United Kingdom

Grid code Compliance and Renewable Energy Projects. Mick Barlow, Business Development Director, S&C Electric, United Kingdom Grid code Compliance and Renewable Energy Projects Mick Barlow, Business Development Director, S&C Electric, United Kingdom Why Grid Codes? Permit the development of and operation of an efficient and economical

More information

Experience on Technical Solutions for Grid Integration of Offshore Windfarms

Experience on Technical Solutions for Grid Integration of Offshore Windfarms Experience on Technical Solutions for Grid Integration of Offshore Windfarms Liangzhong Yao Programme Manager AREVA T&D Technology Centre 18 June 2007, DTI Conference Centre, London Agenda The 90MW Barrow

More information

Research RES LEGAL Access to the grid Country: Spain

Research RES LEGAL Access to the grid Country: Spain Research RES LEGAL Access to the grid Country: Spain 1. Overview of access to the grid Overview of access to the grid Statutory provisions Connection to the grid Usage of the grid Expansion of the grid

More information

Targeted Application of STATCOM Technology in the Distribution Zone

Targeted Application of STATCOM Technology in the Distribution Zone Targeted Application of STATCOM Technology in the Distribution Zone Christopher J. Lee Senior Power Controls Design Engineer Electrical Distribution Division Mitsubishi Electric Power Products Electric

More information

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008 PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral

More information

Reactive Power Compensation for Solar Power Plants. Andy Leon IEEE PES Chicago Chapter December 12 th, 2018

Reactive Power Compensation for Solar Power Plants. Andy Leon IEEE PES Chicago Chapter December 12 th, 2018 1 Reactive Power Compensation for Solar Power Plants Andy Leon IEEE PES Chicago Chapter December 12 th, 2018 2 Objectives Refresh the basics of reactive power from a generator s perspective Regulatory

More information

ABB POWER SYSTEMS CONSULTING

ABB POWER SYSTEMS CONSULTING ABB POWER SYSTEMS CONSULTING DOMINION VIRGINIA POWER Offshore Wind Interconnection Study 2011-E7406-1 R1 Summary Report Prepared for: DOMINION VIRGINIA POWER Report No.: 2011-E7406-1 R1 Date: 29 February

More information

PQC - STATCON The ultra fast Power Quality Compensator

PQC - STATCON The ultra fast Power Quality Compensator PQC - STATCON The ultra fast Power Quality Compensator PQC - STATCON The ultra fast power quality compensator PQC - STATCON is based on IGBT voltage source inverter technology. It is a shunt connected

More information

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM 106 CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM 5.1 INTRODUCTION Inherent characteristics of renewable energy resources cause technical issues not encountered with conventional thermal,

More information

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents

More information

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description Final Draft Report Assessment Summary Hydro One Networks Inc. : Refurbish 115/44 kv, 25/33/42 MVA DESN Station CAA ID Number: 2007-EX360 1.0 General Description Hydro One is proposing to replace the existing

More information

ELG4125: Flexible AC Transmission Systems (FACTS)

ELG4125: Flexible AC Transmission Systems (FACTS) ELG4125: Flexible AC Transmission Systems (FACTS) The philosophy of FACTS is to use power electronics for controlling power flow in a transmission network, thus allowing the transmission line to be loaded

More information

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 12, Issue 3 Ver. II (May June 2017), PP 124-129 www.iosrjournals.org Comparative Analysis

More information

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System Raju Pandey, A. K. Kori Abstract FACTS devices can be added to power transmission and distribution systems at appropriate

More information

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz Fall 2011

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz Fall 2011 EE 742 Chap. 7: Wind Power Generation Y. Baghzouz Fall 2011 Overview Environmental pressures have led many countries to set ambitious goals of renewable energy generation. Wind energy is the dominant renewable

More information

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment 2012 2nd International Conference on Power and Energy Systems (ICPES 2012) IPCSIT vol. 56 (2012) (2012) IACSIT Press, Singapore DOI: 10.7763/IPCSIT.2012.V56.2 Wind Power Plants with VSC Based STATCOM in

More information

Experiences with Wind Power Plants with Low SCR

Experiences with Wind Power Plants with Low SCR 1 Experiences with Wind Power Plants with Low SCR Lessons learned from the analysis, design and connection of wind power plants to weak electrical grids IEEE PES General Meeting Denver CO, 26 March 2015

More information

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT Prof. Chandrashekhar Sakode 1, Vicky R. Khode 2, Harshal R. Malokar 3, Sanket S. Hate 4, Vinay H. Nasre 5, Ashish

More information

S C ELECTRIC EUROPE LTD. Excellence Through Innovation. Harnessing the Wind. November 2011 Descriptive Bulletin E

S C ELECTRIC EUROPE LTD. Excellence Through Innovation. Harnessing the Wind. November 2011 Descriptive Bulletin E S C ELECTRIC EUROPE LTD. Excellence Through Innovation Harnessing the Wind November 2011 Descriptive Bulletin 2000-42E Introduction Founded in 1911, S&C Electric Company is a global provider of equipment

More information

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE Yunqi WANG, B.T. PHUNG, Jayashri RAVISHANKAR School of Electrical Engineering and Telecommunications The

More information

ABB FACTS Grid connection of Wind Farms

ABB FACTS Grid connection of Wind Farms Christian PAYERL ABB FACTS Grid connection of Wind Farms May 28, 2010 Slide 1 ABB Power of Wind May 28, 2010 Slide 2 ABB FACTS 300 engineers, highly skilled in the following disciplines: Development Marketing

More information

Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection

Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection B. Bagen, D. Jacobson, G. Lane and H. M. Turanli Manitoba

More information

Wind Generators Evolving Technology

Wind Generators Evolving Technology Wind Generators Evolving Technology Transmission Advisory Group Ray Brown Transmission Manager - Meridian Energy April 2008 Overview of Presentation 3 Different Wind Farms 3 Different Technologies Te Apiti

More information

Interconnection Feasibility Study Report GIP-226-FEAS-R3

Interconnection Feasibility Study Report GIP-226-FEAS-R3 Interconnection Feasibility Study Report GIP-226-FEAS-R3 System Interconnection Request #226 70 MW Wind Generating Facility Kings County (L-6013) 2010 07 21 Control Centre Operations Nova Scotia Power

More information

ABB Wind Power Solution

ABB Wind Power Solution Feng Li, Wind ISI, CNABB, November, 2016 ABB Wind Power Solution November 13, 2016 Slide 1 ABB deliveries from A to Z into the wind industry Wind power generation, transmission and integration, control

More information

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 61 CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 3.1 INTRODUCTION The modeling of the real time system with STATCOM using MiPower simulation software is presented in this

More information

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1 Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1 CONTENTS Introduction Types of WECS PQ problems in grid connected WECS Battery

More information

Grid Integration Issues for Large Scale Wind Power Plants (WPPs)

Grid Integration Issues for Large Scale Wind Power Plants (WPPs) Downloaded from orbit.dtu.dk on: Sep 28, 2018 Grid Integration Issues for Large Scale Wind Power Plants (WPPs) Wu, Qiuwei; Xu, Zhao; Østergaard, Jacob Published in: IEEE Power and Energy Society General

More information

Integration of Large Wind Farms into Electric Grids

Integration of Large Wind Farms into Electric Grids Integration of Large Wind Farms into Electric Grids Dr Mohammad AlZoubi Introduction Development WHAT IS NEXT!! Over the next 12 years, Europe must build new power capacity equal to half the current total.

More information

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems Ben Huckaba, P.E. President & Principal Engineer 317-273-9841 benh@alphaeng.us Indiana University Bloomington,

More information

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 01 July 2015 ISSN (online): 2349-784X Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC Ravindra Mohana

More information

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC Rong Cai, Mats Andersson, Hailian Xie Corporate Research, Power and Control ABB (China) Ltd. Beijing, China rong.cai@cn.abb.com,

More information

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

Journal of American Science 2015;11(11)   Integration of wind Power Plant on Electrical grid based on PSS/E Integration of wind Power Plant on Electrical grid based on PSS/E S. Othman ; H. M. Mahmud 2 S. A. Kotb 3 and S. Sallam 2 Faculty of Engineering, Al-Azhar University, Cairo, Egypt. 2 Egyptian Electricity

More information

Essential Reliability Services From PV Plants

Essential Reliability Services From PV Plants Essential Reliability Services From PV Plants Mahesh Morjaria, Ph. D. VP, PV Systems Enabling a world powered by reliable, affordable solar electricity. Utility-Scale PV Plants Support Grid Stability &

More information

Implementation of FC-TCR for Reactive Power Control

Implementation of FC-TCR for Reactive Power Control IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 5, Issue 5 (May. - Jun. 2013), PP 01-05 Implementation of FC-TCR for Reactive Power Control

More information

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Day 2 - Session V-B 299 Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Murali Kandakatla, B. Kondala Rao, Gopal Gajjar ABB Ltd., Maneja, Vadodara, India Thane Introduction

More information

ELECTRICAL POWER SYSTEMS 2016 PROJECTS

ELECTRICAL POWER SYSTEMS 2016 PROJECTS ELECTRICAL POWER SYSTEMS 2016 PROJECTS DRIVES 1 A dual inverter for an open end winding induction motor drive without an isolation transformer 2 A Robust V/f Based Sensorless MTPA Control Strategy for

More information

Voltage Control Strategies for Distributed Generation

Voltage Control Strategies for Distributed Generation Voltage Control Strategies for Distributed Generation Andrew Keane, Paul Cuffe, Paul Smith, Eknath Vittal Electricity Research Centre, University College Dublin Cigré Seminar 6 th October 2010 Penetrations

More information

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best. Medium Voltage Power Factor Correction Reactive Compensation Harmonic Filters POWER QUALITY Electrical Power Quality Management at its best. From electricity generation, transmission, thru its distribution

More information

Variable frequency transformer for asynchronous power transfer

Variable frequency transformer for asynchronous power transfer Variable frequency transformer for asynchronous power transfer by Einar Larsen, Richard Piwko and Donald McLaren, GE Energy A new power transmission technology has been developed. The variable frequency

More information

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Grid Interconnection & Contract Development Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Submittal Instructions Prior to submitting your application and

More information

PQC-STATCON. PPHVC-Power Quality Solutions. Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads

PQC-STATCON. PPHVC-Power Quality Solutions. Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads PQC-STATCON PPHVC-Power Quality Solutions Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads Contents What is poor power quality? Reasons for investing

More information

Modelling and Simulation of DFIG based wind energy system

Modelling and Simulation of DFIG based wind energy system International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 11, Issue 10 (October 2015), PP.69-75 Modelling and Simulation of DFIG based wind

More information

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian Shunt Capacitor Bank Protection in UHV Pilot Project Qing Tian 2012-5 INTRODUCTION State Grid Corp. of China, the largest electric power provider in the country, has first build a 1000 kv transmission

More information

IJRASET 2013: All Rights are Reserved

IJRASET 2013: All Rights are Reserved Power Factor Correction by Implementation of Reactive Power Compensation Methods of 220 KV Substation MPPTCL Narsinghpur Ria Banerjee 1, Prof. Ashish Kumar Couksey 2 1 Department of Energy Technology,

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

Emerald Reactive Support Alternative Solution Expressions of interest

Emerald Reactive Support Alternative Solution Expressions of interest Emerald Reactive Support Alternative Solution Expressions of interest Publishing Date 21/02/2017 Closing Date 21/03/2017 1. Executive Summary Ergon Energy Corporation Limited (EECL) is seeking expressions

More information

SIEMENS POWER SYSTEM SIMULATION FOR ENGINEERS (PSS/E) LAB1 INTRODUCTION TO SAVE CASE (*.sav) FILES

SIEMENS POWER SYSTEM SIMULATION FOR ENGINEERS (PSS/E) LAB1 INTRODUCTION TO SAVE CASE (*.sav) FILES SIEMENS POWER SYSTEM SIMULATION FOR ENGINEERS (PSS/E) LAB1 INTRODUCTION TO SAVE CASE (*.sav) FILES Power Systems Simulations Colorado State University The purpose of ECE Power labs is to introduce students

More information

Relative Power Factor Correction costs

Relative Power Factor Correction costs SSG REF: S026 Friday 19 th October 2007 TO: John Gleadow Senior Adviser Transmission Electricity Commission FROM: David Hume Ranil de Silva System Studies Group NZ Ltd Relative Power Factor Correction

More information

DRAFT. Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY

DRAFT. Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY DRAFT Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY 2018 1. INTRODUCTION Solar energy has become the most popular renewable energy source

More information

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application Issue #WP102: Technical Information from Cummins Generator Technologies Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application White Paper Ram Pillai

More information

Interconnection Feasibility Study Report GIP-157-FEAS-R2

Interconnection Feasibility Study Report GIP-157-FEAS-R2 Interconnection Feasibility Study Report GIP-157-FEAS-R2 System Interconnection Request #157 100.5 MW Wind Generating Facility Guysborough County (L-6515) 2009 09 14 Control Centre Operations Nova Scotia

More information

A Review on Reactive Power Compensation Technologies

A Review on Reactive Power Compensation Technologies IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 11, 2017 ISSN (online): 2321-0613 A Review on Reactive Power Compensation Technologies Minal Dilip Sathe 1 Gopal Chaudhari

More information

Electric Power Delivery To Big Cities

Electric Power Delivery To Big Cities Problem Definition Electric Power Delivery To Big Cities a) Socio-economic incentives are a major factor in the movement of population to big cities b) Increasing demand of electric power has strained

More information

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz EE 742 Chap. 7: Wind Power Generation Y. Baghzouz Wind Energy 101: See Video Link Below http://energy.gov/eere/videos/energy-101- wind-turbines-2014-update Wind Power Inland and Offshore Growth in Wind

More information

Request for Payment Instructions Rule 21 Export Submittal Instructions

Request for Payment Instructions Rule 21 Export Submittal Instructions Grid Interconnection & Contract Development Request for Payment Instructions Rule 21 Export Submittal Instructions Prior to submitting your application and fee or deposit, please complete and submit this

More information

Generator Interconnection System Impact Study For

Generator Interconnection System Impact Study For Generator Interconnection System Impact Study For Prepared for: January 15, 2015 Prepared by: SCE&G Transmission Planning Table of Contents General Discussion... Page 3 I. Generator Interconnection Specifications...

More information

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators Abstract: G. Thrisandhya M.Tech Student, (Electrical Power systems), Electrical and Electronics Department,

More information

Ukujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances

Ukujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances Ukujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances 29 Juli 2014 Page 1 Characteristics of the Project Parameter Detail

More information

Jemena Electricity Networks (Vic) Ltd

Jemena Electricity Networks (Vic) Ltd Jemena Electricity Networks (Vic) Ltd Embedded Generation - Technical Access Standards Embedded Generation - 5 MW or Greater ELE SP 0003 Public 1 October 2014 TABLE OF CONTENTS TABLE OF CONTENTS Abbreviations...

More information

Review paper on Fault analysis and its Limiting Techniques.

Review paper on Fault analysis and its Limiting Techniques. Review paper on Fault analysis and its Limiting Techniques. Milap Akbari 1, Hemal Chavda 2, Jay Chitroda 3, Neha Kothadiya 4 Guided by: - Mr.Gaurang Patel 5 ( 1234 Parul Institute of Engineering &Technology,

More information

Dynamic Reactive Power Control. By V. R. Kanetkar Full Time Consultant Technical Services at Veretiv Energy Private Limited Thane (West)

Dynamic Reactive Power Control. By V. R. Kanetkar Full Time Consultant Technical Services at Veretiv Energy Private Limited Thane (West) Dynamic Reactive Power Control By V. R. Kanetkar Full Time Consultant Technical Services at Veretiv Energy Private Limited Thane (West) Acknowledgement The author acknowledges with deep gratitude the experience

More information

Simulated Switching Transients in the External Grid of Walney Offshore Wind Farm

Simulated Switching Transients in the External Grid of Walney Offshore Wind Farm Downloaded from orbit.dtu.dk on: Apr 07, 2019 Simulated Switching Transients in the External Grid of Walney Offshore Wind Farm Arana Aristi, Iván; Johnsen, D. T.; Soerensen, T.; Holbøll, Joachim Published

More information

Performance Analysis of Transient Stability on a Power System Network

Performance Analysis of Transient Stability on a Power System Network Performance Analysis of Transient Stability on a Power System Network Ramesh B Epili 1, Dr.K.Vadirajacharya 2 Department of Electrical Engineering Dr. Babasaheb Ambedkar Technological University, Lonere

More information

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 2 August 2015 ISSN (online): 2349-784X Power System Stability Analysis on System Connected to Wind Power Generation with

More information

Grid Code Testing of Wind Turbines by VSC-based Test Equipment

Grid Code Testing of Wind Turbines by VSC-based Test Equipment Grid Code Testing of Wind Turbines by VSC-based Test Equipment Nicolás Espinoza, PhD Student nicolas.espinoza@chalmers.se CHALMERS VÄRLDENS UNIVERSITY SKILLNAD OF TECHNOLOGY Gothenburg, Sweden. 1 of 32

More information

(by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka Matsinen, Reijo Virtanen, and Antti Vilhunen)

(by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka Matsinen, Reijo Virtanen, and Antti Vilhunen) Technical Paper: Low voltage ride-through testing of wind turbine converters at ABB helps wind turbines meet the requirements of IEC 61400-21 more quickly (by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka

More information

Chapter 08 Dynamic power factor correction systems (real time PFC) Dynamic power factor correction systems (real time PFC) Optimised, thermal design

Chapter 08 Dynamic power factor correction systems (real time PFC) Dynamic power factor correction systems (real time PFC) Optimised, thermal design Dynamic power factor correction systems (real time PFC) Optimised, thermal design Long service life De-tuned version Minimised grid distortion Dynamic power factor correction systems (real time PFC) Hardly

More information

Power Factor Correction

Power Factor Correction Power Factor Correction Power Factor Correction and Voltage Optimisation have been around since the turn of the 20 th century and although in many cases their individual benefits and attributes make them

More information

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent

More information

CONTROL AND PERFORMANCE OF A DOUBLY-FED INDUCTION MACHINE FOR WIND TURBINE SYSTEMS

CONTROL AND PERFORMANCE OF A DOUBLY-FED INDUCTION MACHINE FOR WIND TURBINE SYSTEMS CONTROL AND PERFORMANCE OF A DOUBLY-FED INDUCTION MACHINE FOR WIND TURBINE SYSTEMS Lucian Mihet-Popa "POLITEHNICA" University of Timisoara Blvd. V. Parvan nr.2, RO-300223Timisoara mihetz@yahoo.com Abstract.

More information

APPENDIX E: Project Need and Description

APPENDIX E: Project Need and Description APPENDIX E: Project Need and California ISO/MID E-1 Intentionally left blank California ISO/MID E-2 Lakeville 115 kv Bus Upgrade Installation of a sectionalizing breaker to be installed on 115 kv bus section

More information

2013 Grid of the Future Symposium. Modeling, Simulation, and Applications of Distributed Battery Energy Storage Systems in Power Systems

2013 Grid of the Future Symposium. Modeling, Simulation, and Applications of Distributed Battery Energy Storage Systems in Power Systems 21, rue d Artois, F-75008 PARI CIGRE U National Committee http : //www.cigre.org 2013 Grid of the Future ymposium Modeling, imulation, and Applications of Distributed Battery Energy torage ystems in Power

More information

Operational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks

Operational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks Operational Planning Study Report RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks Report No. T&S Planning 2013-062 British Columbia Hydro and Power Authority British Columbia Hydro and

More information

The Application of Power Electronics to the Alberta Grid

The Application of Power Electronics to the Alberta Grid The Application of Power Electronics to the Alberta Grid Peter Kuffel, Michael Paradis ATCO Electric APIC May 5, 2016 Power Electronics Semiconductor devices used in power transmission systems Types: Thyristor

More information

Overview of Flexible AC Transmission Systems

Overview of Flexible AC Transmission Systems Overview of Flexible AC Transmission Systems What is FACTS? Flexible AC Transmission System (FACTS): Alternating current transmission systems incorporating power electronic-based and other static controllers

More information

1. RENEWABLE ENERGY I.SOLAR ENERGY PROJECT TITLES WE CAN ALSO IMPLEMENT YOUR OWN CONCEPT/IDEA

1. RENEWABLE ENERGY I.SOLAR ENERGY PROJECT TITLES WE CAN ALSO IMPLEMENT YOUR OWN CONCEPT/IDEA 1. RENEWABLE ENERGY I.SOLAR ENERGY S.NO PROJECT CODE PROJECT TITLES YEAR 1 ITPW01 Highly efficient asymmetrical pwm full-bridge renewable energy sources converter for 2 ITPW02 A Three Phase Hybrid Cascaded

More information

Full-Scale Medium-Voltage Converters for Wind Power Generators up to 7 MVA

Full-Scale Medium-Voltage Converters for Wind Power Generators up to 7 MVA Full-Scale Medium-Voltage Converters for Wind Power Generators up to 7 MVA Philippe Maibach, Alexander Faulstich, Markus Eichler, Stephen Dewar ABB Switzerland Ltd CH-5300 Turgi, Switzerland Phone: +41

More information

Power Electronics Projects

Power Electronics Projects Power Electronics Projects I. POWER ELECTRONICS based MULTI-PORT SYSTEMS 1. Analysis, Design, Modeling, and Control of an Interleaved- Boost Full-ridge Three-Port Converter for Hybrid Renewable Energy

More information

Interconnection Feasibility Study Report GIP-222-FEAS-R3

Interconnection Feasibility Study Report GIP-222-FEAS-R3 Interconnection Feasibility Study Report GIP-222-FEAS-R3 System Interconnection Request #222 48 MW Steam Generating Facility Pictou County (53N) 2010 07 30 Control Centre Operations Nova Scotia Power Inc.

More information

Interconnection Feasibility Study Report GIP-369-FEAS-R1

Interconnection Feasibility Study Report GIP-369-FEAS-R1 Interconnection Feasibility Study Report GIP-369-FEAS-R1 System Interconnection Request #369 50 MW Wind Generating Facility Cumberland County (L-6513) 2012-02-09 Control Centre Operations Nova Scotia Power

More information

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

Power Transmission Solutions Grid Access

Power Transmission Solutions Grid Access Power Transmission Solutions Grid Access Connecting the 500 MW Greater Gabbard Offshore Wind Farm to the Grid Dietmar Retzmann Alberto Schultze Siemens AG 2009 Energy Sector 1 04-2009 E T PS SL/Re Global

More information

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line Nitin goel 1, Shilpa 2, Shashi yadav 3 Assistant Professor, Dept. of E.E, YMCA University

More information

APPENDIX E: Project Need and Description

APPENDIX E: Project Need and Description APPENDIX E: Project Need and California ISO/MID E-1 Intentionally left blank California ISO/MID E-2 Tyler 60 kv Shunt Capacitor Installation of a 2x10 MVAR capacitor bank at Tyler 60 kv bus Objectives

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks

Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks Product Selection & Application Guide Product Description GE's Thyristor Switched Harmonic Filter Banks (TSC), are custom designed

More information

First Applications on AltaLink s Network. Roggero Ciofani, P. Eng. Colin Clark, P. Eng.

First Applications on AltaLink s Network. Roggero Ciofani, P. Eng. Colin Clark, P. Eng. First Applications on AltaLink s Network Roggero Ciofani, P. Eng. Colin Clark, P. Eng. Overview Technology Overview Applications and Alternatives Advantages Alberta Special Considerations Operational Implications

More information

PJM Generator Interconnection R81 Emilie (Fords Mill) MW Impact Study Re-Study

PJM Generator Interconnection R81 Emilie (Fords Mill) MW Impact Study Re-Study PJM Generator Interconnection R81 Emilie (Fords Mill) 100.9 MW Impact Study Re-Study August 2008 DMS # 498781 General Queue R81 Emilie (Fords Mills) is a Fairless Energy, LLC request to obtain an additional

More information

A Variable Speed Wind Generation System Based on Doubly Fed Induction Generator

A Variable Speed Wind Generation System Based on Doubly Fed Induction Generator Buletin Teknik Elektro dan Informatika (Bulletin of Electrical Engineering and Informatics) Vol. 2, No. 4, December 2013, pp. 272~277 ISSN: 2089-3191 272 A Variable Speed Wind Generation System Based on

More information

Interconnection Feasibility Study Report GIP-084-FEAS-R2

Interconnection Feasibility Study Report GIP-084-FEAS-R2 Interconnection Feasibility Study Report GIP-084-FEAS-R2 System Interconnection Request #84 50 MW Wind Generating Facility Pictou County (L-7004) August 17, 2007 Control Centre Operations Nova Scotia Power

More information

Workshop on Grid Integration of Variable Renewable Energy: Part 1

Workshop on Grid Integration of Variable Renewable Energy: Part 1 Workshop on Grid Integration of Variable Renewable Energy: Part 1 System Impact Studies March 13, 2018 Agenda Introduction Methodology Introduction to Generators 2 Introduction All new generators have

More information

Novel Control of PV Solar and Wind Farm Inverters as STATCOM for Increasing Connectivity of Distributed Generators

Novel Control of PV Solar and Wind Farm Inverters as STATCOM for Increasing Connectivity of Distributed Generators Western University Scholarship@Western Electronic Thesis and Dissertation Repository May 2013 Novel Control of PV Solar and Wind Farm Inverters as STATCOM for Increasing Connectivity of Distributed Generators

More information

Georgia Transmission Corporation Georgia Systems Operations Corporation

Georgia Transmission Corporation Georgia Systems Operations Corporation Georgia Transmission Corporation Georgia Systems Operations Corporation Reactive Power Requirements for Generating Facilities Interconnecting to the Georgia Integrated Transmission System with Georgia

More information

CHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK

CHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK 91 CHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK CHAPTER CONTENTS: 5.1 INTRODUCTION 5.2 CONDUCTION OF VARIOUS POWER FLOW STUDIES ON THE MODEL 5.3 EXPERIMENTS CONDUCTED FOR VARIOUS POWER FLOW

More information

Modeling and Simulation of Battery Energy Storage Systems for Grid Frequency Regulation. X. XU, M. BISHOP, D. OIKARINEN S&C Electric Company USA

Modeling and Simulation of Battery Energy Storage Systems for Grid Frequency Regulation. X. XU, M. BISHOP, D. OIKARINEN S&C Electric Company USA , rue d Artois, F-8 PARIS CIGRE US National Committee http : //www.cigre.org Grid of the Future Symposium Modeling and Simulation of Battery Energy Storage Systems for Grid Frequency Regulation X. XU,

More information

Chapter 3.1: Electrical System

Chapter 3.1: Electrical System Part-I: Objective type Questions and Answers Chapter 3.1: Electrical System 1. The heat input required for generating one kilo watt-hour of electrical output is called as. a) Efficiency b) Heat Rate c)

More information

SPIRO SOLUTIONS PVT LTD POWER ELECTRONICS 1. RENEWABLE ENERGY PROJECT TITLES I. SOLAR ENERGY

SPIRO SOLUTIONS PVT LTD POWER ELECTRONICS 1. RENEWABLE ENERGY PROJECT TITLES I. SOLAR ENERGY POWER ELECTRONICS 1. RENEWABLE ENERGY S.NO PROJECT CODE PROJECT TITLES I. SOLAR ENERGY YEAR 1 ITPW01 Photovoltaic Module Integrated Standalone Single Stage Switched Capacitor Inverter with Maximum Power

More information

Interconnection System Impact Study Final Report February 19, 2018

Interconnection System Impact Study Final Report February 19, 2018 Interconnection System Impact Study Final Report February 19, 2018 Generator Interconnection Request No. TI-17-0225 248.4 MW (Alternate Project Output of 217.35 MW) Wind Energy Generating Facility In Goshen

More information