Approved Equipment Register BATTERIES
|
|
- Delilah Wood
- 5 years ago
- Views:
Transcription
1 1. SCOPE This document lists the categories of equipment shown below, which are approved and accepted for use in ScottishPower's transmission and distribution network. Substation Batteries. Battery Chargers. Battery Alarm and Monitoring Systems 2. ISSUE RECORD This is a document. The current version is held on the Energy Networks Document Library. It is your responsibility to ensure you work to the current version. Issue Date Issue No. Author Amendment Details February Fraser Ainslie Initial Issue: 7 pages September David Neilson Review of specification and equipment manufacturers December Patrick Dolan Approval of Eltek Chargers (all variants) revoked Approval of Haze Batteries (all variants) revoked Hoppecke GroE Battery Series Approved April Patrick Dolan Updated Specification Document s Dale Power Chargers and Alarm Module Approved PE Systems Alarm Module Approved Telecoms Battery Approvals Added December Patrick Dolan General Update on Approvals 3. ISSUE AUTHORITY Author Owner Issue Authority Name: Patrick Dolan Title: Lead Engineer 4. REVIEW Name: Alastair Ferguson Title: Substation Standards Manager Name: Martin Hill Title: Head of Engineering Design and Standards... Date:... This is a document which has a 3 year retention period after which a reminder will be issued to review and extend retention or archive. 5. DISTRIBUTION This document is not part of a Manual maintained by Document Control and does not have a maintained distribution list but is published to the Internet. SP Power Systems Limited Page 1 of 9
2 CONTENTS 1. SCOPE ISSUE RECORD ISSUE AUTHORITY REVIEW DISTRIBUTION... 1 CONTENTS REFERENCE AND RELATED DOCUMENTS ScottishPower Technical Specifications STANDARD REQUIREMENTS APPROVED SUPPLIERS AND EQUIPMENT Batteries Chargers Battery Alarm Systems APPENDIX Value Regulated Lead Acid (VRLA) Type High Reliability Planté Flooded Nickel Cadmium APPENDIX 2 CHARGERS V & 110V/36V Chargers V, 48V/30V & 48V/36V Chargers V Chargers Portable Chargers Pre-packaged Portable Battery Units Battery Control / Alarm Units Distribution Boards... 9 SP Power Systems Limited Page 2 of 9
3 6. REFERENCE AND RELATED DOCUMENTS 6.1 ScottishPower Technical Specifications BATT Issue 8: Auxiliary D.C. Power Supplies for Primary & Secondary Substations 48V Battery Chargers for 33 kv Substations. 30V and 48/30V Sealed Lead/Acid Batteries and Chargers for 11/6.6 kv Substations. 110V Battery and Charging Equipment for 33 kv Substations and 11/6.6 kv Substations. BATT Issue 1: 48 V and 110 V D.C. power supply systems in SP 400kV / 275k /220kV and 132kV substations 7. STANDARD REQUIREMENTS Distribution substations batteries and chargers are required to comply with BATT (In addition lead acid batteries to comply with IEC and BS6290 Part 2, SLA/VRLA to comply with BS6290 Part 4 and BS EN and BS EN ). Transmission substations and Grid Supply Point sites, chargers and batteries are required to comply with BATT Installation testing specifications BS 6290 Part 2 and BS EN Where Batteries offered are manufactured to an alternative standard (e.g. DIN standard), the battery can still be considered for use but its performance in relation to clauses in the BS6290 when go beyond the alternative standard must be considered prior to approval. 8. APPROVED SUPPLIERS AND EQUIPMENT 8.1 Batteries The only batteries technologies approved for use within SP-EN are; Valve Regulated Lead Acid (V.R.L.A.) AGN and Gel types Flooded Lead Acid (High Reliability Planté) Flooded Nickel Cadmium (NiCd) Batteries approvals relate to series types. Only batteries in the specific ranges listed for manufacturers approved can be used. All alternative batteries offered are subject to separate approval prior to use. All Batteries Series Approved are listed in the Appendix Chargers All Charger s who have demonstrated that they are capable of manufacturing chargers to SP requirements are listed in Appendix 2. Specific Chargers Models created and approved for recent applications are listed. Some aspects of Battery and Chargers solutions (e.g. distribution requirements) are bespoke manufactured for specific applications requirements however core equipment and principles of operation may not deviate from SP Power Systems Limited Page 3 of 9
4 previously approved equipment. Where specific charger offered is not listed, it shall be subject to individual approval prior to use and addition to register for all aspects of the design which have not previously been assessed. 8.3 Battery Alarm Systems All Battery Alarm systems approved for use are listed in Appendix 3.Where specific Battery Alarm Unit is not listed is shall be subject to approval prior to use. SP Power Systems Limited Page 4 of 9
5 9. APPENDIX 1 - Battery from ranges outside of those listed below shall be reviewed prior to consideration 9.1 Value Regulated Lead Acid (VRLA) Type Review Date Review Updates Manufacturer Series Acceptable Remarks / Application In use prior to document issue In use prior to document issue Series reviewed July 2010 Series reviewed July 2010 Enersys (Hawker) Enersys (Hawker) Powersafe V Series Powersafe SBS N/A Fiamm SLA Series In use prior to document issue N/A Yuasa Endurance Series (EN & ENL) Series reviewed historically N/A Marathon Proton AGM In use prior to document issue Series reviewed July 2010 DMS Technologies - (Enersys Cells made into 30V or 48V Blocks) CYCLON X Series Approved for all Substation VRLA within nominal temperature range (15 o C - 25 o C) - Model of Adequate Capacity to be selected for the associated Application Series Approved for all Substation VRLA within nominal temperature range (15 o C - 25 o C), series performs better than other V.R.L.A. Types approved in applications where temperature likely to exceed 25 o C Threshold (See Datasheet) - Model of Adequate Capacity to be selected for the associated Application Series Approved for all Substation within nominal temperature range (15 o C - 25 o C) - Model of Adequate Capacity to be selected for the associated Application Current approved applications are limited to Cell replacement on Telecoms VRLA within nominal temperature range (15 o C - 25 o C) Model of Adequate Capacity to be selected for the associated Current approved applications are limited to Cell replacement only on Telecoms VRLA within nominal temperature range (15 o C - 25 o C) Model of Adequate Capacity to be selected for the associated Series Approved for VRLA Secondary Substation Tripping Only (no standing load) within nominal temperature range (15 o C - 25 o C) 9.2 High Reliability Planté Review Date Review Updates Manufacturer Type Remarks / Application In use prior to document issue N/A Enersys / PowerSafe (Hawker) YAP/YCP/YHP In use prior to document issue N/A FIAMM SGL GroE 2012 N/A HOPPECKE GroE Series Series Approved used for Planté Substation within nominal temperature range (15 o C - 25 o C) - Model of Adequate Capacity to be selected for the associated application. As with other Planté Cells, tolerant of temperature variations (impact on level of gassing). Series Approved for Planté Substation within nominal temperature range (15 o C - 25 o C) - Model of Adequate Capacity to be selected for the associated application. As with other Planté Cells, tolerant of temperature variations (impact on level of gassing). Series Approved for Planté Substation within nominal temperature range (15 o C - 25 o C) - Model of Adequate Capacity to be selected for the associated application. As with other Planté Cells, tolerant of temperature variations (impact on level of gassing). 9.3 Flooded Nickel Cadmium Review Date Review Updates Manufacturer Type Remarks / Application In use prior to document issue N/A SAFT / ALCAD LCP Series Aug 2013 N/A SAFT / ALCAD LCE P Series Aug 2013 N/A SAFT / ALCAD Vantex Series Series Approved for NiCd Substation within nominal temperature range (15 o C - 25 o C) - Model of Adequate Capacity to be selected for the associated application. Tolerant of temperature variations (impact on level of gassing). Series Approved for NiCd Substation within nominal temperature range (15 o C - 25 o C) - Model of Adequate Capacity to be selected for the associated application. Tolerant of temperature variations (impact on level of gassing). Series Approved for NiCd Substation within nominal temperature range (15 o C - 25 o C) - Model of Adequate Capacity to be selected for the associated application. Tolerant of temperature variations (impact on level of gassing). SP Power Systems Limited Page 5 of 9
6 10. APPENDIX 2 CHARGERS The following Manufacturers have demonstrated that they can manufacture chargers compliant with SP-EN Requirements Manufacturer PB Design P.E. Systems Dale Power Master Power Switch-tripping & load supporting applications Load supporting applications Portable Chargers Switch-tripping & load supporting applications Load supporting applications Switch Tripping Only Switch-tripping & load supporting applications Load supporting applications Portable Chargers Portable Chargers Where specific charger types are not noted below, they shall be subject to specific design approvals. Alternative s subject to review and full approval via SP. Where Chargers s are followed with (X) Notation, the (X) should be replaced with (Battery Type ) of the choice of battery selected from listed compatible types V & 110V/36V Chargers Switch Tripping and Load Supporting Systems Date Reviewed Review Update Manufacturer Description Application SP Design Amendments Nov 2016 Design Amendments Nov 2016 PB Design PB Design 20A Charger 25A Charger Nov 2016 PB Design 40A Charger Dec 2016 Dale Power 10A Charger Primary Substations (Tripping and Load Supporting ) Primary Substations (Tripping and Load Supporting ) Primary Substations (Tripping and Load Supporting ) Secondary Substations (Tripping and Load Supporting ) P-STL (X) P-STL (X) P-STL (X) P-STL (X) & SD P-STL-110/L P-STL-110/M P-STL-110/H Powersafe V 12V125F, Powersafe V 12V92F, Others T.B.C. Powersafe V 12V170F, Powersafe V 12V190F, Others T.B.C. Powersafe V 12V125F (2 Strings) S-STL (X) DCV110/10 Powersafe V 12V62F Charger includes an unpopulated tier and a disconnection link such that a load disconnection device may be fitted or retrofitted as required Where separate distribution board is provided, board must be installed or configured in line with BATT requirements. For use in Secondary Substations for 110V Load Supporting and Tripping SP Power Systems Limited Page 6 of 9
7 V, 48V/30V & 48V/36V Chargers Switch Tripping and Load Supporting Systems Date Reviewed Review Update Manufacturer Description Application N/A PE Systems 4A Charger Nov 2016 Dale Power 10A Charger Dec 2016 PB Design 20A Charger Secondary Substations Switch Tripping and Load Supporting Secondary Substations Switch Tripping and Load Supporting Primary Substations Switch Tripping and Load Supporting S-STL-48-4(X) WCVF48V PowerSafe SBS 40 S-STL (X) DCV110/10 PowerSafe 12V62F P-STL (X) P-STL-48 PowerSafe SBS 170F Intended for use in secondary substations for use for tripping applications with low standing load (<1A) Intended for use in secondary substations for use for tripping applications with standing load (<2A) Intended for use in primary substations for use for tripping applications with medium/high standing load Switch Tripping Only Systems Date Reviewed Review Update Manufacturer Description Application N/A PE Systems 0.5A Charger Secondary Substations - Switch Tripping Only ST (Cyclon X) Cyclon X Sets (48V Sets Packaged to SP requirement DMS or Ritelite) Only to be used on secondary substations with no standing load Telecoms / Load Supporting Systems Date Reviewed Review Update Manufacturer Description Application Dec 2016 PB Design 20A Charger Primary Substations Telecoms P-TEL-48-20(X) Type C PowerSafe 12V170 FS Can be used to supply Telecoms and SCADA loads at Primary Substations SP Power Systems Limited Page 7 of 9
8 V Chargers Switch Tripping and Load Supporting Systems Date Reviewed Review Update Manufacturer Description 2013 N/A Dale Power 0.5A Charger Primary Substations - Switch Tripping Only S-STL (X) DC50/32P PowerSafe 6V105 Intended for use in primary substations for use for tripping applications with medium/high standing load Switch Tripping Only Systems Date Reviewed Review Update Manufacturer Description N/A PE Systems 0.5A Charger Secondary Substations - Switch Tripping Only S-ST (Cyclon X) Cyclon X Sets (30V Sets Packed by DMS or Ritelite) only Only to be used on secondary substations with no standing load 10.4 Portable Chargers Date Added Review Update Manufacturer Description Details In use prior to document issue N/A Masterpower Charger Unit 110/48/30 Aug N/A Dale Power DCV110/25 charger Aug N/A Dale Power DCV50/25 charger Aug N/A Dale Power DCV30/25 charger Nov 2016 N/A PB Design PSP Nov 2016 N/A PB Design PSP V Switch mode charger with 25A Output (typically paired with 17AHr battery) 110V Switch mode charger with 10A Output (typically paired with 17AHr battery) 10.5 Pre-packaged Portable Battery Units Date Added Review Update Manufacturer Description Details Nov 2016 N/A PB Design 17Ahr 48V & 108V Strings Use as temporary battery set for Battery/Cell replacement or for a short time in an emergency if there is a battery failure. Not for use on Grid Sites Pre-packaged Strings of 17AHr batteries 48V unit and 60V unit which can combined to form a 108V string, equipped with Anderson socket for connection and MCBs for protection SP Power Systems Limited Page 8 of 9
9 10.6 Battery Control / Alarm Units The following Manufacturers have demonstrated that they can provide Battery Alarm Units compliant with SP-EN Requirements. PB Design P.E. Systems Dale Power Where specific alarm/control modules are not noted below, they shall be subject to individual approval where offered. Date Reviewed Review Update Manufacturer Model/Description Application Jul-11 Factory Review Jan 12 PB Design 200 Series Controller Monitored V.R.L.A. And L.A Battery/Charger Systems Sept 13 Factory Review Aug 13 Dale Power DAU Controller Monitored V.R.L.A. And L.A Battery/Charger Systems Sept 13 Documentation Review Sept 13 PE Systems BM1 Module Monitored V.R.L.A. And L.A Battery/Charger Systems Supersedes 135 Series Controller, Firmware Version to be updated for single string asymmetry monitoring Where deployed - Test discharge should be via dedicated Push button and not via the controller module options buttons Control / Alarm Modules are approved on the basis of the functions they provide only. Where equipment specifications include additional requirements to those which can be provided by the modules listed above, supplementary modules will be required as to meet the overall system requirements. All Modules required will be subject to approval Distribution Boards The following Distribution boards have been approved. Date Reviewed Review Update Manufacturer Model/Description Application Nov-16 P&B Design PB 12 WAY SP DISTRIBUTION BOARD For use with 110V Battery Charger Systems with a separate distribution board requirement. Board fuseways are segregated into essential and non-essential ways with a bolted link in the positive D.C bar and multi-pole isolator for isolation of charger and battery supplies. SP Power Systems Limited Page 9 of 9
Appendix T: BATTERY REQUIREMENTS FOR INTERCONNECTION TO PG&E SYSTEM
Appendix T: BATTERY REQUIREMENTS FOR INTERCONNECTION TO PG&E SYSTEM The purpose of this document is to ensure safety and reliability of Pacific Gas and Electric Company and its customers who will or plan
More informationNPS/003/002 Technical Specification for 30V Distribution Tripping Battery and Charger Systems
Version:- 2.1 Date of Issue:- July 2016 Page 1 of 29 NPS/003/002 Technical Specification for 30V Distribution Tripping Battery and Charger Systems 1. Purpose This document is to detail the technical requirements
More informationNPS/003/016 Technical Specification for 48V and 110V Battery and Charger Systems
Version:- 2.1 Date of Issue:- August 2016 Page 1 of 28 NPS/003/016 Technical Specification for 48V and 110V Battery and Charger Systems 1. Purpose The purpose of this document is to detail the technical
More informationAsset Category Batteries LPN
Asset Category Batteries LPN Asset Stewardship Report 2013 Brian Matthews Approved by Richard Wakelen / Barry Hatton Approved date 03.06.2013 / 04.06.2013 Document Management and Governance by Victoria
More informationReference Number PDS 18 - (RIC Standard: EP SP)
Discipline Engineering Standard - NSW Category Electrical Title Reference Number PDS 18 - (RIC Standard: EP 06 00 00 01 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Jan 05 Standards
More informationIEC APPROVAL TESTS
IEC61427-1 APPROVAL TESTS Edition 1.0 : 2013-04 Secondary cells and batteries for renewable energy storage General requirements and methods of test Part 1 : Photovoltaic off-grid application Flooded lead-acid
More informationIEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations
1 IEEE1818-2017 Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations Sponsored by the IEEE Substations Committee Presented By Joe Gravelle Organization of the Guide 1. Scope
More informationIEEE IAS Atlanta Chapter
Stationary Battery Sizing IEEE IAS Atlanta Chapter Presented by: Lesley Varga, P.E. Quality Standby Services, LLC 1649 Sands Place, SE, Suite C Marietta, GA 30067 (770) 916-1747 lesley@qualitystandbyservices.com
More informationNPS/001/017 Technical Specification for Low Voltage and High Voltage Current Limiting Fuse Links
Version:- 7.0 Date of Issue:- July 2017 Page 1 of 19 NPS/001/017 Technical Specification for Low Voltage and High Voltage Current Limiting Fuse Links 1. Purpose The purpose of this document is to detail
More informationNPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations
Version:- 3.0 Date of Issue:- Dec 2013 Page 1 of 13 NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations 1. Purpose This document is the technical specification
More informationThis is a Reference document. The current version is held on the EN Document Library.
1. SCOPE This section of the Live Working Manual details the procedures to be followed when working on alkaline or acid substation batteries of any type or voltage. It also covers work on or near to battery
More informationDocument 21 Asset Category Batteries LPN
Document 21 Asset Category Batteries LPN Asset Stewardship Report 2014 Brian Matthews UK Power Networks (Operations) Limited. Registered in England and Wales. Registered No. 3870728. Registered Office:
More informationIndustrial Batteries / Network Power. Classic OCSM.»Exceptional combination of high power, long life and excellent cycling capability«
Industrial Batteries / Network Power»Exceptional combination of high power, long life and excellent cycling capability« Network Power > Product overview Industrial Batteries The powerful range of Network
More informationReserve Power Systems
Product Overview Motive Power Systems Reserve Power Systems Special Power Systems Service Your benefits with HOPPECKE standby batteries Highest safety - more than 80 years experience in manufacturing first-class
More information12468/10 SJC/fp 1 DG I 1A
COUNCIL OF THE EUROPEAN UNION Brussels, 20 July 2010 12468/10 ENV 504 ENT 91 COVER NOTE from: European Commission date of receipt: 16 July 2010 to: General Secretariat of the Council Subject: Commission
More informationConductance Reference Values Jan 2003
PO Box 11033 Banchory Aberdeenshire AB31 5WS Tel: +44 (0) 1330 823950 Fax: +44 (0) 1330 823966 Email: Info@ skylark.co.uk Conductance Reference Values Jan 2003 All REFERENCE VALUES are derived through
More informationINTRODUCTION MARKET SECTORS CUSTOMER SERVICE CCL OFFERS YOU. Switchmode Technology A highly efficient, lightweight
CCL OFFERS YOU Switchmode Technology A highly efficient, lightweight and compact charging technology. Providing less than 1% ripple output, this technology is especially suitable for VRLA batteries. CCL
More informationIndustrial Batteries / Network Power. Classic Energy Bloc.»High performance, long-life energy storage«
Industrial Batteries / Network Power»High performance, long-life energy storage« Network Power > Product overview Industrial Batteries The powerful range of Network Power Energy storage solutions for critical
More informationIndustrial Batteries / Network Power. Classic OGi.»Superior performance for
Industrial Batteries / Network Power»Superior performance for high current discharge« Network Power > Product Overview Industrial Batteries The strong range of Network Power Energy storage solutions for
More informationReserve Power Systems
Product Overview Motive Power Systems Reserve Power Systems Special Power Systems Service Your benefits with HOPPECKE standby batteries Highest safety - more than 80 years experience in manufacturing first-class
More informationCompany Directive ENGINEERING EQUIPMENT SPECIFICATION 104/1
Company Directive ENGINEERING EQUIPMENT SPECIFICATION 104/1 Substation 24V & 48V Batteries, Chargers, Distribution Boards & Associated Auxiliary Cabling NOTE: The current version of this document is stored
More informationPowerStor Standby Battery Systems
PowerStor Standby Battery Systems PowerStor Standby Battery Systems PowerStor Standby Battery Systems In today s environment battery systems must perform in the most challenging applications. The versatile
More informationLow breaking capacity moulded case circuit breakers
New series EB2S of MCCBs has excellent performances with reduced dimensions and new modern design. Advantages of low breaking capacity MCCBs Unique accessory cover opens with only one screw. Practical
More informationChristopher LaForge. IREC Certified Master Trainer. NABCEP Certified Photovoltaic Installation Professional - Emeritus
Energy Storage 201 Christopher LaForge IREC Certified Master Trainer NABCEP Certified Photovoltaic Installation Professional - Emeritus 30 years Operating Great Northern Solar 26 years Training with MREA
More informationNCC Leisure Battery Verification Scheme. Leisure Accommodation Vehicles
The UK trade body for the caravan, motorhome, caravan holiday and park home industry. NCC Leisure Battery Verification Scheme Leisure Accommodation Vehicles Page 1 of 11 1 Scope The NCC Battery Verification
More informationStation dc supply voltage. Electrolyte level. Inspect: Verify:
Table 1-4(a) Component Type Protection System Station dc Supply Using Vented Lead-Acid (VLA) Batteries Protection System Station dc supply used only for non-bes interrupting devices for SPS, non-distributed
More information4Electrically propelled vessels
4Electrically propelled vessels The Boat Safety Scheme Essential Guide For more technical information The requirements in this chapter have been informed by, and may refer to, the following technical references,
More informationPURE LEAD PLUS UPS APPLICATIONS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell
-11 PURE LEAD PLUS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications 305-545 Watts per Cell FEATURES & benefits APPLICATIONS Data Centers Network Operations Centers Industrial
More informationRange. Alcad Single Cell Range. Powerful assurance for maximum operating reliability
inglecell Range Alcad Single Cell Range Powerful assurance for maximum operating reliability Alcad Single Cell Range the reliability you need at the heart of your power backup system. Versatility for industry
More informationAINO MICRO RANGE VRLA. Compact energy for increased security BATTERY SOLUTIONS. EverExceed power your applications
EverExceed power your applications Maintenance free VRLA design Leak proof / Spill proof Gas recombination Absorbed electrolyte Float / Cycle use Low self-discharge rate Reliable one-way safety valve Lead
More informationIndustrial Batteries / Network Power. Classic OPzS.»Proven high reliability energy storage for critical applications«
Industrial Batteries / Network Power»Proven high reliability energy storage for critical applications« Network Power > Product overview Industrial Batteries The powerful range of Network Power Energy storage
More informationSegenSolar (Pty) battery storage training
OUR ENERGY FOR YOUR SUCCESS SegenSolar (Pty) battery storage training Accumulatorenwerke HOPPECKE Carl Zoellner & Sohn GmbH Bontkirchener Straße 1 D-59929 Brilon-Hoppecke www.hoppecke.com COMPANY FACTS
More informationBulk Storage Containers
UCSB AST SPCC SELF-INSPECTION CHECKLIST Year: Responsible Department: Tank Location: Tank ID: Bulk Storage Containers Total tank capacity: Petroleum type and amount: Secondary containment type: (diesel,
More informationBattery Storage Systems
Battery Storage Systems Agenda System Components Applications How to Size Batteries System Components Basic battery theory Electro-chemical reaction Two dissimilar metals Positive electrodes Negative electrodes
More information24V 3A EN54 Ancillary Power Supply
24V 3A EN54 Ancillary Power Supply Normal supply - green light on Fault condition - call Engineer Control relay - activated 3A Power Supply C-TEC Manufactured in England by C-Tec EN 54-4 : 1997 INSTALLATION
More informationYEARS. Alcad Stationary. Ni-Cd batteries ADVANCED SOLUTIONS ENGINEERING EXCELLENCE
YEARS Alcad Stationary Ni-Cd batteries ADVANCED SOLUTIONS ENGINEERING EXCELLENCE Alcad LTD is one of the world's major suppliers of nickel-cadmium batteries for industrial and commercial applications.
More informationPURE LEAD PLUS UPS APPLICATIONS. Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell
UPS 12-1121 PURE LEAD PLUS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications 305-545 Watts per APPLICATIONS Data Centers Network Operations Centers Industrial Process Control
More informationValve Regulated Lead Acid (VRLA) Battery Series Designed for UPS Standby Power Applications FEATURES & BENEFITS
12-1079 HIGH RATE MAX UPS 12-355MRF APPLICATIONS Data Centers Network Operations Centers Industrial Process Control Facilities Internet Housing Sites Semiconductor Manufacturing Banks & Financial Markets
More informationNovember 2018 Customer Switching Report for the Electricity and Gas Retail Markets
An Coimisiún um Rialáil Fóntas Commission for Regulation of Utilities November 2018 Customer Switching Report for the Electricity and Gas Retail Markets Information Paper Reference: CRU18266 Date Published:
More informationC-CODE TABLES FOR CADEX BATTERY ANALYZERS
Battery Maintenance Solutions Cadex Electronics Inc. 22000 Fraserwood Way, Richmond, BC Canada V6W 1J6 Tel: 604 231-7777 Fax: 604 231-7755 Toll-Free: 1 800 565-5228 (USA & Canada) E-mail: service@cadex.com
More informationIndustrial Chargers and
Industrial Chargers and DC Systems SPR - Single Phase Rectifier TPR - Three Phase Rectifier 12V 250V 5A 1000A Designed for all Industrial applications Oil & Gas, Petrochemicals Offshore, Onshore, Pipelines
More informationIndustrial Batteries / Network Power. Marathon L / XL.»More energy for safer storage«
Industrial Batteries / Network Power»More energy for safer storage«« Network Power > Product overview Industrial Batteries The powerful range of Network Power Energy storage solutions for critical systems
More informationIndustrial Batteries - Classic GroE The proven, reliable energy storage
Industrial Batteries - Classic GroE The proven, reliable energy storage Specifications GNB Industrial Power www.gnb.com Specifications Classic GroE batteries bridge short and long discharge times, reliably
More informationBattery Solutions. Presented by Wouter Vink Business Development Manager Enersys Powertech Reserve Power / DC Power Solutions
& Battery Solutions Presented by Wouter Vink Business Development Manager Enersys Powertech Reserve Power / DC Power Solutions Role /Activity EnerSys Group:Primary Markets RESERVE POWER : used to supply
More informationConnecting other lithium systems to Multis and Quattros
Connecting other lithium systems to Multis and Quattros Manual www.victronenergy.com Introduction Besides connecting one of the Victron Energy Lithium battery systems to a Multi or Quattro, it is also
More informationSECTION DC POWER SUPPLY/BATTERY CHARGER
SECTION 26 33 05 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide the single-phase heavy-duty industrial battery charger and all accessories required, complete and operable, in accordance
More informationHillstone PowerBank HPB54 Series ( 400A 700A )
Technical data Sheet Hillstone PowerBank HPB54 Series ( 400A 700A ) Ref. HPB54-400-700 Page 1 of 6 Features Electronic variable control Manual constant current Full current control range Digital ammeter
More informationReliability. Safety. Efficiency.
Reliability. Safety. Efficiency. Over a century of stored energy solutions for the rail industry. NATIONAL RAILWAY SUPPLY Supporting Rail Industry Reliability for 125 Years Standing outside the EnerSys
More informationAME. Rectifier - Battery charger. Industrial applications: Key features:
Rectifier - Battery charger AME VRLA batteries, flooded battery or Ni/Cd with output voltage from 24, 48, 110, 220 Vdc up to 150A Industrial applications: Oil&Gas (Petrochemicals Offshore, Onshore, Pipelines);
More informationNovember 2017 Customer Switching Report for the Electricity and Gas Retail Markets
An Coimisiún um Rialáil Fóntas Commission for Regulation of Utilities November 2017 Customer Switching Report for the Electricity and Gas Retail Markets Information Paper Reference: CRU18011 Date Published:
More information[Amounts in millions of dollars] Nondurable. Total. goods. equipment 34,415 30,717 24,506 8,868 9,566 8,981
1970 TABLE C-44. Manufacturers 1 new and unfilled orders, 1947-69 Unfilled orders2 Unfilled orders-shipments Machinery and equipment 1947.. 1948.. 1949.. 23,53.3 3 3 4 3 1961 * 31,085 15,698 17,026 18,522
More informationIndustrial Batteries / Network Power Classic Solar»Powerful energy storage for renewable energy systems« Network Power > Product overview Industrial Batteries The powerful range of Network Power Energy
More informationIndustrial Batteries Europe Middle East Africa ENGLISH
Secure Power Solutions Industrial Batteries Europe Middle East Africa ENGLISH AGM VRLA FG FGL FGC FGH FGHL AGM VRLA AGM VRLA AGM VRLA AGM VRLA AGM VRLA FIAMM AGM batteries have optimized internal gas recombination
More informationCONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation
CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent
More informationIndustrial Batteries / Network Power. Sonnenschein A400 FT.»The dryfit range for modular performance adaption«
Industrial Batteries / Network Power»The dryfit range for modular performance adaption« Network Power > Product overview Industrial Batteries The powerful range of Network Power Energy storage solutions
More informationMESP TECHNICAL SPECIFICATION FOR A STATIONARY CONTROL BATTERY AND CHARGER SET FOR USE IN A SUBSTATION
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A STATIONARY CONTROL BATTERY AND CHARGER SET FOR USE IN A SUBSTATION Version: 2 Issued: August 2016 Owner: Head of Engineering
More informationIndustrial Batteries / Network Power. Classic Solar.»Powerful energy storage for renewable energy systems«
Industrial Batteries / Network Power Classic Solar»Powerful energy storage for renewable energy systems« Network Power > Product overview Industrial Batteries The powerful range of Network Power GNB Industrial
More informationIndustrial Batteries / Network Power. Sonnenschein SOLAR.»Premium quality for renewable energy«
Industrial Batteries / Network Power Sonnenschein SOLAR»Premium quality for renewable energy« Network Power > Product overview Industrial Batteries The powerful range of Network Power Energy storage solutions
More informationInvestigation into UK socket-outlets incorporating USB charging points
Investigation into UK socket-outlets incorporating USB charging points Electrical Safety First investigated a number of commercially available UK socket-outlets incorporating USB ports, as a repeat of
More informationBuffer Charging Systems
Buffer Charging Systems for lead or NiCd-accumulators step down switched with I-U-I characteristic regulation series PLG Performance data... charging currents 2,5; 5; 10; 20 A nominal output voltage 24
More informationWestern Power s list of exemptions from compliance from Technical Rules granted after 1 July 2007.
Western Power s list of exemptions from compliance from Technical Rules granted after 1 July 2007. No Date of Exemption To whom Exemption was granted Clause to which Exemption has been granted Concise
More informationWhite Paper. Direct Current Load Banks for Battery Capacity Testing
White Paper Direct Current Load Banks for Battery Capacity Testing Direct Current Load Banks for Battery Capacity Testing Reliable Direct Current (DC) power requires battery systems to be maintained according
More informationCentral Battery Systems Loadstar AC/DC Systems
The Loadstar range of AC/DC central battery units comply with the latest relevant European and British standards. High quality, cost effective units provide secure sources of emergency power for escape
More informationIndustrial Batteries / Network Power. Sonnenschein A600.»Premium quality for uninterrupted communication«
Industrial Batteries / Network Power»Premium quality for uninterrupted communication« Network Power > Product overview Industrial Batteries The powerful range of Network Power Energy storage solutions
More informationHOPPECKE sun powerpack premium
HOPPECKE Product Information Accumulatorenwerke HOPPECKE Carl Zoellner & Sohn GmbH Bontkirchener Straße 1 D-59929 Brilon-Hoppecke www.hoppecke.com 1 sun powerpack classic Li-Ion (LiFePO prismatic cells)
More informationBATTERIES BATTERIES VRLA / SLA / GEL 2V/6V/12V. DP Electronics e.k (Deutsche Power Co., Limited)
BATTERIES BATTERIES VRLA / SLA / GEL 2V/6V/12V VRA / SLA BATTERIES AGM (2V, 12V Cell) Durable and Power Full Batteries A VRLA battery (valve-regulated lead-acid battery) more commonly known as a sealed
More informationGuidance for Low Voltage Electrical Installations
Guidance for Low Voltage Electrical Synopsis This document provides information in support of GI/RT7007 Low Voltage Electrical. Signatures removed from electronic version Submitted by Anne E Blakeney Standards
More informationBATTERIES MAXIMUM POWER AND PERFORMANCE FOR INDUSTRIAL EQUIPMENT
DOUGLAS LEGACY BATTERIES MAXIMUM POWER AND PERFORMANCE FOR INDUSTRIAL EQUIPMENT Legacy High Performance Battery Built with premium quality materials and advanced engineering technology, the Legacy High
More informationBatteries may be hazardous to human health and the environment if not properly handled.
Environmental Standard Operating Procedure (Approved by Jonathan Aunger) Document Owner: Environmental Division File Name: BM-ESOP 02H003v3 Effective Date: 9 December 2010 Revised: 13 April 2015 Title:
More informationIndustrial Batteries / Network Power. Sonnenschein A700.»The durable high energy and reliable battery system«
Industrial Batteries / Network Power»The durable high energy and reliable battery system« Network Power > Product Overview Industrial Batteries The strong range of Network Power Energy storage solutions
More informationEVO SERIES BATTERY CHARGER SERIES BATTERY CHARGER
EVO SERIES BATTERY CHARGER SERIES BATTERY CHARGER Evo Series battery charger designed with YOU in mind. Evo Series battery charger is a next generation SCR-based utility battery charger. This evolutionary
More informationSECTION A Division of Exide Technologies
SECTION 22.61 2016-09 A Division of Exide Technologies From the World Leader in VRLA Battery Technology Designed for durability in Telecommunications and Electric Utility applications, the GNB Industrial
More informationIndustrial Batteries / Network Power. Classic Solar.»Powerful energy storage for renewable energy systems«
Industrial Batteries / Network Power Classic Solar»Powerful energy storage for renewable energy systems« Network Power > Product overview Industrial Batteries The powerful range of Network Power Energy
More informationRX 3 MCB 4500 A Phase + Neutral, neutral on left side
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 RX 3 MCB 4500 A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationCOMMISSION REGULATION (EU)
30.11.2010 Official Journal of the European Union L 313/3 REGULATIONS COMMISSION REGULATION (EU) No 1103/2010 of 29 November 2010 establishing, pursuant to Directive 2006/66/EC of the European Parliament
More informationUPS FEATURES & BENEFITS TECHNICAL DATA Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications.
41-9027 Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications. TECHNICAL DATA FEATURES & BENEFITS 10 year design life @ 25 C Absorbent Glass Mat (AGM) technology for efficient gas
More informationList of exemptions from compliance with the Technical Rules granted by Western Power after 1 July 2007
to: details Version: 2007 Technical Rules 1 16-Jan-08 2 16-Jan-08 3 29-Jan-08 Neerabup (two generating units - Units G11 and G12) Neerabup (two generating units - Units G11 and G12) Bluewaters Power Station
More informationINVITATION TO TENDER MR 84/2016. SUPPLY and Install 110V DC BATTERY BANKS and CHARGERS for Rarawai, Sabeto and Lautoka Switching Station
INVITATION TO TENDER MR 84/2016 SUPPLY and Install 110V DC BATTERY BANKS and CHARGERS for Rarawai, Sabeto and Lautoka Switching Station Fiji Electricity Authority seeks reputable Manufacturer/Supplier
More informationIndustrial Batteries / Network Power. Classic Solar.»Powerful energy storage for renewable energy systems«
Industrial Batteries / Network Power Classic Solar»Powerful energy storage for renewable energy systems« Network Power > Product overview Industrial Batteries The powerful range of Network Power Energy
More informationSolar Storage Technologies Part of the BRE Trust
Solar Storage Technologies Steve Pester Part of the BRE Trust Smart Solar NSC 2015 Overview of next few minutes Challenges Some solutions Types of storage Main battery technologies How batteries behave
More informationVaultFlex Battery Enclosures. from EnerSys and Purcell Systems. Two industry leaders team up to provide new synergy, efficiency and flexibility
VaultFlex Battery Enclosures from EnerSys and Purcell Systems Two industry leaders team up to provide new synergy, efficiency and flexibility Visit us at www.enersys.com A one-stop resource for precision-matched
More informationFlexCharger Battery Chargers
FlexCharger Battery Chargers Operating Instructions Definitions (as used in these instructions) Flooded Battery Lead-acid battery with liquid electrolyte that requires open-venting and regular water replacement.
More informationModular Max Range BATTERY SOLUTIONS. NEBS qualified. Reliable capacities. EverExceed power your applications
EverExceed power your applications Modular Max Range BATTERY SOLUTIONS NEBS qualified Reliable capacities CADMIUM FREE FULLY RECYCLABLE LEAD ACID BATTERIES CONFORMS TO THE EUROPEANE.C.1992 DIRECTIVE ON
More informationThe IAEA does not normally maintain stocks of reports in this series.
IAEA-TECDOC- The IAEA does not normally maintain stocks of reports in this series. However, microfiche copies SAFETY ASPECTS OF STATION BLACKOUT AT NUCLEAR POWER PLANTS IAEA, VIENNA, 1985 IAEA-TECDOC-332
More informationTECHNICAL SERVICE BULLETIN
TECHNICAL SERVICE BULLETIN To: Minuteman Dealers and Customers From: Minuteman Technical Support Date: 1/12/2011 Subject: TSB for the KIT # K-FRSPEEDSWT. For the FR17115, FR17220, FR20115 and FR20220 models.
More informationDNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation
More informationSPECIFICATION FOR VT D 70 CONTENTS
CONTENTS 1/ SCOPE 2/ GENERAL ELECTRICAL CHARACTERISTICS 3/ GENERAL MECHANICAL CELL SPECIFICATION 4/ CAPACITY 5/ CHARGE RECOMMENDATIONS 6/ CYCLE LIFE 7/ CELL AND BATTERY MANAGEMENT 8/ SPECIFICATION APPROVALS
More informationGV-10 Manual 10.5A / 140W IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. Solar Charge Controllers with Maximum Power Point Tracking
GV-10 Manual Solar Charge Controllers with Maximum Power Point Tracking For models: GV-10-Pb-12V: GV-10-Pb-CV: 12V Lead-Acid/AGM/Gel/Sealed/Flooded 12V Custom Multi-Stage Lead-Acid/AGM/Gel/ Sealed/Flooded
More informationIndustrial Batteries / Network Power. Sonnenschein A400 FT.»The dryfit range for modular performance adaption«
Industrial Batteries / Network Power»The dryfit range for modular performance adaption« Network Power > Product overview Industrial Batteries The powerful range of Network Power Energy storage solutions
More informationANCR CRU Statistics February 2007 to December 2007
ANCR CRU Statistics February 2007 to December 2007 o Jan/07 Feb/07* Mar/07 Apr/07 May/07 Jun/07 Jul/07 Aug/07 Sep/07 Oct/07 Nov/07 Dec/07 Total notes data from Perimeter phone system unavailable prior
More informationPowerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A)
A Complete solution for small battery-backed dc instrument power systems. DATASHEET Supply 12Vdc 8A or 24Vdc 6A loads Ideal for RTU s, dataloggers, remote field instrumentation, alarm systems, etc. where
More informationIEC Low Voltage Products Module 4
IEC Low Voltage Products Module 4 IEC Low Voltage Products NH DIN o All variations o Features benefits o Dual indication IEC Cylindrical Fuse System o Wide range of sizes and ratings o CCP NEW Product!
More informationRenewable Energy Storage Solutions
Renewable Energy Storage Solutions Expertise in off-grid solutions for the most demanding applications Battery Enclosures Featuring advanced thermal management and technology, these enclosures keep batteries
More informationUptimax New Generation Ni-Cd battery. Maintenance-free solution for backup power applications
NiCd battery Maintenancefree solution for backup power applications The ideal choice for total security and availability Saft your trusted battery partner for stationary applications Saft has over 100
More informationINTELEPOWER CXS SWITCHING SYSTEMS
INTELEPOWER CXS SWITCHING SYSTEMS INTELEPOWER CXS SWITCHING SYSTEMS Intelepower DC UPS - CXS Range Designed For Switching The demands for quality power in switching applications are placing new demands
More informationand other -48VDC Power Systems. 19 or 23 Wide (Nominal) Relay Rack (part of system).
SYSTEM OVERVIEW Description: Application: Spec. Nos.: 588820100 (19 ). 588820200 (23 ). Models: 48BA1200-19 (19 ). 48BA1200-23 (23 ). Output Voltage: Capacity: Spec No. 588820100 (Model 48BA1200-19) Spec
More informationTrain Safety Systems. Railway Group Standard GM/RT2185 Issue Two Date December 2001
Train Safety Systems Synopsis This document defines the requirements for train safety systems to enable safe operation of trains on Railtrack controlled infrastructure. Signatures removed from electronic
More informationSUBSTATION EQUIPMENT - Page 1 of 8
BATTERY BANKS 1. GENERAL: JEA utilizes a 125 volt DC system for the control and operation of its transmission and distribution substations. JEA has standardized on lead acid type battery banks to supply
More informationHYPERION EOS 5i. User s Manual. Power, with Ease
HYPERION EOS 5i User s Manual Power, with Ease HYPERION EOS 5i - User s Manual Please read the following instructions carefully, to insure safety and convenience EOS 5i Special Features *Powerful, yet
More informationCOOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN
Reclosers MN280074EN Effective May 2017 Supersedes September 2009 (S280-90-6) Electronic control battery testing, charging, and replacement instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND
More information