IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations
|
|
- Martina Griffin
- 5 years ago
- Views:
Transcription
1 1 IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations Sponsored by the IEEE Substations Committee Presented By Joe Gravelle
2 Organization of the Guide 1. Scope / Purpose 2. Normative References 3. Definitions 4. AC System Design 5. DC System Design Annex A Bibliography Annex B - Conductor Sizing examples Annex C Battery Sizing Examples 2
3 Organization of the Guide 1. Scope / Purpose 2. Normative References 3. Definitions 4. AC System Design 5. DC System Design Annex A Bibliography Annex B - Conductor Sizing examples Annex C Battery Sizing Examples 3
4 1.1 Scope This guide provides guidelines for the design of the ac and dc systems. This guide covers the low voltage auxiliary systems from the source(s) to the distribution point(s). Reliability requirements and load characteristics 4
5 1.2 Purpose The low-voltage ac and dc auxiliary systems comprise very important parts of the substation equipment. Design of the ac and dc auxiliary systems reliability, load requirements, system configuration, personnel safety, safe and reliable operation protection 5
6 6 2.0 Normative References IEEE 485, IEEE Definitions Definitions are provided for technical terms used in the guide.
7 Organization of the Guide 1. Scope / Purpose 2. Normative References 3. Definitions 4. AC System Design 5. DC System Design Annex A Bibliography Annex B - AC examples Annex C DC Examples 7
8 4.0 AC System Design Design Criteria Source Requirements Load Analysis Conductor Selection Transformer(s) Transfer Switch Bus Layout Panels Protection Equipment Specifications Operations and Maintenance 8
9 9 4.1 Introduction Design Criteria Source Requirements Number of sources 1 phase or 3 phase Load Requirements These sections define the AC system for the substation Application.
10 Design Criteria AC system loads 1 or 3 phase System stability Protection Voltage This section defines the AC system design.
11 AC sources Transformer tertiary Substation bus Distribution line Generators
12 AC Load Analysis Identification Amps/Volts/kW Equipment rating Demand factors Load calculations
13 Conductor Selection Conductor Type Insulation Temperature Rating Size Ampacity Voltage Drop
14 Station Auxiliary Transformer Transformer Type
15 Station Auxiliary Transformer Number of transformers Single/Three phase Transformer Ratings Transformer Connections
16 Station Auxiliary Transformer Transformer Ratings KVA Voltage Short Circuit Impedance BIL
17 4.6 AC System Design Transformer Connections Single Phase 17
18 AC System Design Transformer Connections Three Phase
19 Transfer Switch Manual / Automatic Considerations: Break before Make Switching Neutrals
20 Bus Layout - Distribution Configuration Essential / Non-Essential Loads Simple Radial System Expanded Radial System Primary / Secondary Selective systems
21 Bus Layout and Distribution Circuit Configuration
22 AC Distribution Panelboards Application Ratings Short Circuit ratings Standards
23 AC Auxiliary System Protection Panelboard or Switchboard Circuit Breaker Selection Fuse Selection
24 Equipment Specifications General considerations Standards
25 Operation - Maintenance Consideration Accessible Disconnects Indoor/Outdoor Design Adequate Working Space Standby or Backup AC System
26 26
27 Organization of the Guide 1. Scope / Purpose 2. Normative References 3. Definitions 4. AC System Design 5. DC System Design Annex A Bibliography Annex B - AC examples Annex C DC Examples 27
28 DC System Design Design Criteria DC Equipment One Line Diagram Batteries Chargers Panels Design Considerations Maintenance Provisions 28
29 Battery System 29
30 30 Battery System Single cell battery with acid containment on a two step rack
31 DC System Design Criteria Reliability Redundancy Environment
32 5.2 Equipment Served by the DC System System Protection Equipment Motor Operators Breakers SCADA Fire Protection Security 32
33 5.3 One Line Diagram Power System One Line System protection DC System One Line DC Load Calculations DC Connections Number of Batteries Load Transfer 33
34 34 Substation One Line Operating sequence: 12D3 is normally closed, no generation on feeder circuits Operating time for MOS 10 seconds Transformer T1 differential: Trip 69CB1, 69CB3, 12CB1 Open 69DT1 Breaker Failure on 12CB1: Open 12CB2, Open 12D3, Reclose 12CB2
35 35 DC System Battery To DC Cab. Panel Maint Charger & Battery Battery Charger
36 DC System distribution cabinet(s) 36
37 DC Batteries Battery System Battery Charger(s) Battery Disconnect(s) DC Panel(s) Maintenance Connections DC Loads
38 5.4 DC Batteries 38
39 DC Battery Types Vented Lead Acid (VLA) Valve Regulated Lead Acid (VRLA) Nickel Cadmium (NiCad) For substation use, vented lead-acid cells are the most common
40 5.4 DC Battery 40
41 5.4 DC Battery 41
42 5.4 DC Battery 42
43 43 Battery Sizing Sizing the battery using IEEE 485 (Vented Lead Acid Batteries) Defining the Duty Cycle (loading on battery based on time duration) Continuous Load Momentary Load Worst Case Tripping
44 44 Continuous Loads Indicating lamps, Microprocessor Relays, Electronic Meters, SCADA Systems, Annunciators, Communication Equipment o For loads that are non-linear such as power supplies, the current increases as voltage declines. o The watt rating is typically used to determine current at end of battery cycle discharge voltage
45 45 Momentary Loads Lock Out Relay (LOR) Breaker tripping Motor Operators Breaker Fail operation Considerations: o Worst Case Tripping Scenarios o MOD use Locked Rotor rating o Breaker Fail use SOE not sum of all currents select highest
46 46 Worst Case Tripping Operating sequence: 12D3 is normally closed, no generation on feeder circuits Operating time for MOS 10 seconds Transformer T1 differential: Trip 69CB1, 69CB3, 12CB1 Open 69DT1 Breaker Failure on 12CB1: Open 12CB2, Open 12D3, Reclose 12CB2 Timing: T=0cy (0 sec) Trip 69CB1, 69CB3, 12CB1, open 69DT1 Current= =92A T=12cy (0.2sec) (12CB1 breaker failure timer) Trip 12CB2, Re-Trip 12CB1 open 12D3 Current= =96A T=600cy (10sec) Reclose 12CB2 Current=6A From the above, the worst case tripping load is 96A for the 12CB1 breaker failure.
47 47 Duty Cycle Duration 1. Charger fails Initiates Alarm to SCADA 2. Dispatcher notices Alarm 3. Dispatch contacts Substation Personal 4. Substation Personal Drive to Substation 5. Investigate Alarm 6. Determines Charger Failed contacts dispatch requesting maintenance 7. Dispatch contacts Maintenance 8. Maintenance Technician Drives to Substation 9. Maintenance attempts to repair charger (unsuccessful) 10. Maintenance Supervisor locates spare charger 11. Maintenance Supervisor contacts additional resources 12. Resources drive to service center PU spare charger and drive to substation 13. Replace failed Charger
48 Duty Cycle Example 48
49 49 Battery Chargers Sizing battery Chargers Charger Connections Charger Circuit Protection
50 Battery Chargers 50
51 Battery Charger size 51
52 52 DC Panels Considerations Critical Loads vs non-critical Loads Circuit size Number of circuits
53 DC Panels 53
54 DC Panels 54
55 55 Design Considerations Battery location Maintenance considerations Working clearances Method for removing battery cells An eyewash station Spill containment systems Terminal Covers
56 Battery Terminal Covers 56
57 57 Design Considerations Battery area temperature Specifications published for sizing Heat and Cold impact battery performance Reference IEEE485 for effect on Battery Size
58 Design Considerations Acid spill containment Spill Pans Acid-resistant paint on the floor 58
59 59 Design Considerations Battery racks Three types step, tier, or stepped tier Height variations between cells can cause cell temperature differences within the same battery system acid-resistant coating applied to the structural frame seismic zone
60 60 Design Considerations Battery rack
61 61 Design Considerations Circuit considerations Grounded and ungrounded systems Ungrounded Substation Control - SCADA Grounded ((+) grounded) Communications
62 Design Considerations - Circuit considerations Isolation of Main DC cables Recommendations - IEEE 1375 Battery fuse Battery circuit breaker Battery disconnect switch Mid-point battery fuse 62
63 63 Circuit considerations Isolation of main dc cables - Separate the pos and neg cables
64 64 Design Considerations Circuit considerations Coordination of overcurrent protection Short-circuit levels Fuses Breakers Equipment voltage ratings
65 65 Maintenance Provisions Isolation switches Equipment accessibility Back-up supplies
66 66 Maintenance Provisions Testing Provisions
67 67 DC System Battery To DC Cab. Panel Maint Charger & Battery Battery Charger
68 68 Annex Annex A Bibliography Annex B - Conductor Sizing Example Annex C Battery Sizing Example
69 Questions? 69
IEEE IAS Atlanta Chapter
Stationary Battery Sizing IEEE IAS Atlanta Chapter Presented by: Lesley Varga, P.E. Quality Standby Services, LLC 1649 Sands Place, SE, Suite C Marietta, GA 30067 (770) 916-1747 lesley@qualitystandbyservices.com
More information9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.
Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution
More informationBurns & McDonnell ISU Senior Design Project 2010/2011
Burns & McDonnell ISU Senior Design Project 2010/2011 STATION DATA BY BTJ DATE 02/04/2013 SHEET 1 OF 10 PROTECTION AND MEASUREMENTS EQUIPMENT SPECIFICATIONS PROJECT SCOPE New substation installaton. Add
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements
Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner
More informationAppendix C. Interval Every 2 Year. Functional Test Weekly Monthly Quarterly. Semi. Every 3. Engineering Studies
Engineering Studies Coordination Study Every 5 years and in conjunction with electrical system modifications. Short Circuit Study NETA MTS 6.2 Every 5 years and in conjunction with electrical system modifications.
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More informationStandards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.
FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared
More informationReference Number PDS 18 - (RIC Standard: EP SP)
Discipline Engineering Standard - NSW Category Electrical Title Reference Number PDS 18 - (RIC Standard: EP 06 00 00 01 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Jan 05 Standards
More informationAppendix T: BATTERY REQUIREMENTS FOR INTERCONNECTION TO PG&E SYSTEM
Appendix T: BATTERY REQUIREMENTS FOR INTERCONNECTION TO PG&E SYSTEM The purpose of this document is to ensure safety and reliability of Pacific Gas and Electric Company and its customers who will or plan
More informationTECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III
TECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III 1. SCOPE A. The Central Lighting Inverter shall be a solid-state three phase system designed to provide
More informationPower Systems Trainer
Electrical Power Systems PSS A self-contained unit that simulates all parts of electrical power systems and their protection, from generation to utilisation Key Features Simulates generation, transmission,
More informationTEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES
INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR
More informationSECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT
SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.
More informationEE 741 Over-voltage and Overcurrent. Spring 2014
EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with
More informationA comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear
Robert J. Gustin Eaton Fellow Application Engineer, P. E. Southfield, Michigan Definitions Metal-enclosed load interrupter switchgear type ME Metal-enclosed switchgear is defined in ANSI C37.20.3-1987,
More informationSECTION DC POWER SUPPLY/BATTERY CHARGER
SECTION 26 33 05 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide the single-phase heavy-duty industrial battery charger and all accessories required, complete and operable, in accordance
More informationBattery Storage Systems
Battery Storage Systems Agenda System Components Applications How to Size Batteries System Components Basic battery theory Electro-chemical reaction Two dissimilar metals Positive electrodes Negative electrodes
More informationSUBSTATION EQUIPMENT - Page 1 of 8
BATTERY BANKS 1. GENERAL: JEA utilizes a 125 volt DC system for the control and operation of its transmission and distribution substations. JEA has standardized on lead acid type battery banks to supply
More informationStation dc supply voltage. Electrolyte level. Inspect: Verify:
Table 1-4(a) Component Type Protection System Station dc Supply Using Vented Lead-Acid (VLA) Batteries Protection System Station dc supply used only for non-bes interrupting devices for SPS, non-distributed
More informationUBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit
More information3.0 Radial Distribution Systems
3.0 Radial Distribution Systems Radial distribution systems (RDS) are the most common design used by electric utilities, and are the least expensive to plan, construct, and maintain. They generally consist
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationTRANSMISSION SYSTEMS
TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric
More informationE-15 Uninterruptible Power Systems (UPS)
Guideline No.E-15 (201705) E-15 Uninterruptible Power Systems (UPS) Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6
The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 6 PROTECTIONS 1 FUNCTION OF ELECTRICAL PROTECTION SYSTEMS Problems:
More informationGENERAL SPECIFICATION ELECTRICAL
GENERAL SPECIFICATION ELECTRICAL GS ELE 152 AC Uninterruptible Power Systems (UPS) 02 09/03 Change of Group name and logo 01 10/02 Updated 00 03/01 First issue Rev. Date Notes GS ELE 152.doc Contents 1.
More informationDesign Considerations to Enhance Safety and Reliability for Service Entrance Switchboards
Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards Robert P. Hansen, P.E., PhD GE Specification Engineer Introduction Switchboards are a widely used type of equipment
More informationRecommended Procedures
Selective Coordination Study Recommended Procedures The following steps are recommended when conducting a selective coordination study.. One-Line Diagram Obtain the electrical system one-line diagram that
More informationMar H: SUPPLEMENTAL PARALLELING GEAR (16315-H)
2101 Commonwealth Blvd, Suite B Ann Arbor, MI 48105-5759 www.med.umich.edu/facilities/plan/ 263010-H: SUPPLEMENTAL PARALLELING GEAR (16315-H) Related Sections Basis Guideline: N/A For an explanation of
More informationBREAKER FAILURE PROTECTION
29 th Annual HANDS-ON RELAY SCHOOL March 12-16, 2012 BREAKER FAILURE PROTECTION Brent Carper, PE Protection & Integration Engineer brent.c@relayapplication.com OUTLINE Protection System Failures and Breaker
More informationDual Power. Protection. Protection
54 Fault Clearing Systems by Damien Tholomier., AREVA T&D Automation, Canada Dual Power Single Battery What if it? Short circuits and other abnormal power system conditions are very rear, but may result
More informationE-12 Low-voltage Switchboard
Guideline No.E-12 (201510) E-12 Low-voltage Switchboard Issued date: 20 October 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements, inspection
More informationLow Voltage Automatic Transfer Switch Systems
Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in
More informationPretest Module 29 High Voltage Unit 1
Pretest Module 29 High Voltage Unit 1 1. Is a person qualified to work on high-voltage installations when this module is completed? 2. What is the code definition of high-voltage? 3. What is the IEEE definition
More informationChapter 6 Generator-Voltage System
Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals
More informationHydro Plant Risk Assessment Guide
September 2006 Hydro Plant Risk Assessment Guide Appendix E8: Battery Condition Assessment E8.1 GENERAL Plant or station batteries are key components in hydroelectric powerplants and are appropriate for
More informationDESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5
DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this
More informationChapter 6. Batteries. Types and Characteristics Functions and Features Specifications and Ratings Jim Dunlop Solar
Chapter 6 Batteries Types and Characteristics Functions and Features Specifications and Ratings 2012 Jim Dunlop Solar Overview Describing why batteries are used in PV systems. Identifying the basic components
More informationSECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed,
More informationTransformer Protection
Transformer Protection Course No: E01-006 Credit: 1 PDH Andre LeBleu, P.E. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 info@cedengineering.com
More informationProtective Device Coordination ETAP Star
Protective Device Coordination ETAP Star Agenda Concepts & Applications Star Overview Features & Capabilities Protective Device Type TCC Curves STAR Short-circuit PD Sequence of Operation Normalized TCC
More informationOptimizing Emergency Power Systems for Health Care Applications
2018 Annual Conference Optimizing Emergency Power Systems for Health Care Applications aka: Using the latest code changes to improve system reliability and maybe even save some $$$... Overview Michigan
More informationPID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation
PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date
More informationCost Benefit Analysis of Faster Transmission System Protection Systems
Cost Benefit Analysis of Faster Transmission System Protection Systems Presented at the 71st Annual Conference for Protective Engineers Brian Ehsani, Black & Veatch Jason Hulme, Black & Veatch Abstract
More informationENGINEERING SPECIFICATION
December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References
More informationSPECIFICATION FOR BATTERY & BATTERY CHARGER (D.C. SYSTEM)
Doc No: 256324-500-SP-ELE-006 Rev: A Page 1 of 11 SPECIFICATION FOR BATTERY & BATTERY CHARGER (D.C. SYSTEM) Doc No: 256324-500-SP-ELE-006 Rev: A Page 2 of 11 List of Contents Pages 1.0 Scope...3 2.0 Technical
More informationA Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design
A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design Presented at the 2018 Transmission and Substation Design and Operation Symposium Revision presented at the
More information90.2 Scope. The installation of electrical conductors, equipment and raceways for:
NEC Generator Primer Rules on the installation of generators and transfer switches 1 90.2 Scope The installation of electrical conductors, equipment and raceways for: public and private premises Conductors
More informationSwitchgear Utility specific gravity nominal sulfuric acid. 10 years, full float service at 77 F (25 C)
12-373 UL Recognized Component RETURN LEAD RECYCLE LIBERTY SERIES 1000 VALVE REGULATED LEAD-CALCIUM BATTERY FOR STANDBY APPLICATIONS Capacities from 100 to 600 Ampere-hours (8 hours to 1.75 VPC) 343 to
More informationA system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.
General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail
More informationWIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST
WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.
More informationWhite Paper. Ground Fault Application Guide. WL Low Voltage Power Circuit Breakers
White Paper Ground Fault Application Guide WL Low Voltage Power Circuit Breakers Table of Contents Introduction 3 Need for ground fault tripping 3 Requirements from industry standards 3 National Electrical
More informationSUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More informationMedium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION
Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium
More informationCopyright 2003 Advanced Power Technologies, Inc.
Overview of the Standard for Interconnecting Distributed Resources with Electric Power Systems, IEEE 1547 and it s potential impact on operation of the Distributed Generation (DG) systems and on the design
More informationData Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931
Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC
More informationMedium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1
Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear ABB Group February 25, 2015 Slide 1 SafeGear HD arc resistant switchgear 63 ka arc resistant metal-clad air insulated switchgear
More informationSPECIFICATIONS UPS Triple Output 13.6VDC/213W, 48VDC/153W, 48VDC/39W
Page 1 / 7 Full operation without need of battery Two independent 48Vdc outputs for switching and control Local monitoring with 8 LEDs Remote monitoring with 4 alarm relays Monitoring and configuration
More information.3 Section Waste Management and Disposal.
Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section
More information2013 Grid of the Future Symposium. Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited Plant
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited
More informationSwitchgear and Distribution Systems for Engineers and Technicians
Switchgear and Distribution Systems for Engineers and Technicians WHAT YOU WILL LEARN: How to identify typical characteristics of an industrial distribution system Become familiar with the main components
More informationStationary Battery Testing
Stationary Battery Testing STATIONARY BATTERY TESTING The stationary backup batteries are the life line in any safety system, a life line that simply cannot fail. In order to ensure safe operation it is
More informationPowerware Master Modbus
Powerware Master Modbus Map 164201391 Rev D This document describes the format of the data contained in the Modbus messages. Not all registers apply to all UPS modules. Please consult the individual UPS
More informationNPS/003/016 Technical Specification for 48V and 110V Battery and Charger Systems
Version:- 2.1 Date of Issue:- August 2016 Page 1 of 28 NPS/003/016 Technical Specification for 48V and 110V Battery and Charger Systems 1. Purpose The purpose of this document is to detail the technical
More informationAP1000 European 8. Electric Power Design Control Document
8.3 Onsite Power Systems 8.3.1 AC Power Systems 8.3.1.1 Description The onsite ac power system is a non-class 1E system comprised of a normal, preferred, maintenance and standby power supplies. The normal,
More informationNPS/003/002 Technical Specification for 30V Distribution Tripping Battery and Charger Systems
Version:- 2.1 Date of Issue:- July 2016 Page 1 of 29 NPS/003/002 Technical Specification for 30V Distribution Tripping Battery and Charger Systems 1. Purpose This document is to detail the technical requirements
More informationE-15 Uninterruptible Power Systems (UPS)
Guideline No.E-15 (201510) E-15 Uninterruptible Power Systems (UPS) Issued date:20 October, 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements,
More information4-Day Power System Analysis, Coordination, System Studies
4-Day Power System Analysis, Coordination, System Studies Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Our
More informationSchedules 1 to 4, Lot B: Extension of the Lessos Substation
1.0 LIGHTNING ARRESTORS 1.1 ZNO lightning arrester, 192 kv rated voltage, 10 ka nominal discharge current 2.0 CAPACITIVE VOLTAGE TRANSFORMER ea. 45 2.1 220 kv capacitive voltage transformer 220/ 3 / 0.11/
More informationSummary of Revision, IEEE C , Guide for Breaker Failure Protection of Power Circuit Breakers
Summary of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection of Power Circuit Breakers Kevin Donahoe GE Grid Solutions 2018 Texas A&M Protective Relaying Conference Agenda Introduction
More informationwww. ElectricalPartManuals. com Section 13 Switchgear Low Voltage
Switchgear Low Voltage Introduction...13-1 AKD-10 Low-Voltage Switchgear...13-3 AKD-20 Low-Voltage Switchgear...13-3 Low Voltage Switchgear GE low-voltage switchgear is heavy-duty equipment built to ANSI
More informationMEDIUM-VOLTAGE SWITCHGEAR
REVISION RECORD SECTION 16341 Medium-Voltage Switchgear REV DATE PAGE PARA NO. DESCRIPTION APPROVED BY 28SEP01 ALL Initial issue. 1 29SEP03 ALL General update with miscellaneous changes in entire document.
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements
More information16.13 Unit Substation to 15kV Construction Standards Page 1 of 7
Construction Standards Page 1 of 7.1 General.1 New buildings are to be provided with an indoor unit substation designed to accept 15kV and 25kV primary voltages, however, the primary voltage connected
More informationAT30 SERIES BATTERY CHARGER
STANDARD FEATURES 5 YEAR WARRANTY 5 Year Product Warranty Universal main control board operates in any AT Series charger Alarm assembly with local LEDs and summary relay contact for AC Failure, DC Failure,
More informationNEC REQUIREMENTS FOR GENERATORS
PROFESSIONAL DEVELOPMENT SEMINAR SERIES NEC REQUIREMENTS FOR GENERATORS (Based on NEC 2005 with limited 2008 commentary) AIA certified Continuing Education Units (CEU) Available GPS-140 National Electric
More informationICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements. Guideline Number 3 Electrical
ICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements 1. PURPOSE sponsored by ABYC, BMF, ICOMIA, IMCI, and NMMA Author: Wieger de Wit Guideline Number 3 Electrical
More informationTRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES
TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC
More informationELECTRICAL POWER, DIRECT CURRENT, SPACE VEHICLE DESIGN REQUIREMENTS
MIL-STD-1539 (USAF) 1 AUGUST 1973 MILITARY STANDARD ELECTRICAL POWER, DIRECT CURRENT, SPACE VEHICLE DESIGN REQUIREMENTS FSC 1810 Electrical Power, Direct Current, Space Vehicle Design Requirements MIL-STD-1539
More information6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton
Advances in technology to address safety Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton 1 Advances in technology could mean use existing technology & back to basics Advances in safety are
More informationSubstation LV AC Supplies. Document Number: 1-11-FR-04
Substation LV AC Supplies Document Number: 1-11-FR-04 VERSION 1.0 June 2018 This functional requirements document is in line with the organisation's 1-11-ACS-04 LV AC Supplies Asset Class Strategy Intellectual
More informationStandby Power Systems
Source: Power Quality in Electrical Systems Chapter 13 Standby Power Systems The term standby power systems describes the equipment interposed between the utility power source and the electrical load to
More informationGenerator Fire Safety: Generator assemblies should be located outside the building.
SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building
More informationIII. Substation Bus Configurations & Substation Design Recommendations
III. Substation Bus Configurations & Substation Design Recommendations 1.0 Introduction Pre-existing conditions, electrical arrangements or the criticality of the existing facility may limit this flexibility,
More information1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.
RC SCOPE This test procedure covers the testing and maintenance of Westinghouse RC relays. The Westinghouse Protective Relay Division was purchased by ABB, and new relays carry the ABB label. Refer to
More informationSmall Generator Interconnection Program Interconnection Technical Requirements
General Program Information What is the purpose of the PGE Small Generator Interconnection Program? How do I initiate a distribution interconnection request for my project? The purpose of our Small Generator
More informationINTELEPOWER CXS SWITCHING SYSTEMS
INTELEPOWER CXS SWITCHING SYSTEMS INTELEPOWER CXS SWITCHING SYSTEMS Intelepower DC UPS - CXS Range Designed For Switching The demands for quality power in switching applications are placing new demands
More informationThis is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More informationSECTION MOTOR CONTROL
SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters
More informationInstallation Instructions Central Battery Units
Phone: 605.542.4444 concealite.com! Installation Instructions s Please Save These Instructions Important Safeguards Read and Follow All Safety Instructions When using electrical equipment, basic safety
More informationTD-2306B-001, Interconnecting Large 2-20MW Generation Systems. Employees involved with generation interconnection on electric distribution circuits.
SUMMARY The protection requirements for connecting new Distributed Generation (DG) have been modified to reduce the need for Direct Transfer Trip (DTT) schemes which are costly to employ and difficult
More informationService Entrance Methods
Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility
More information2015 WDC Disturbance and Protection Standards Overview
NERC Update 2015 WDC Disturbance and Protection Standards Overview Rich Bauer Senior Manager Reliability Risk Management / Event Analysis IEEE PSRC meeting Denver, Co May 12, 2016 2 System Protection and
More informationE-12 Low-voltage Switchboard
Guideline No.E-12 (201705) E-12 Low-voltage Switchboard Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements, inspection
More informationWheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation
Wheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation 1. Description In the 2013-2014 Transmission Planning Cycle, the ISO approved the construction
More informationAdvanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR
Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR Assembly Short-Circuit Current Ratings What Is A Short-Circuit
More informationSmall wonder. Station service voltage transformers for small power requirements
Small wonder Station service voltage transformers for small power requirements MATHEW PAUL An estimated 1.3 billion people worldwide have no access to electricity. In small communities, this is often due
More informationPower Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers
Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Main Service s INTRODUCTION by Robert E. Fuhr, P.E. The use of electronic equipment has dramatically increased
More informationSection S7 - DC and AC auxiliary services installations
S7/2 Section S7 - DC and AC auxiliary services installations Contents S7. Generalities...3 S7. Generalities...4 S7..1 Scope of work...4 S7..2 Dimensioning the auxiliary services equipment...4 S7.1 General
More informationIlluminator Series CR NEMA 3R
Illuminator Series CR NEMA 3R GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION For 3.0, 4.0, 5.0, 6.5, 8.0kVA / kw Series CR - Single Phase Uninterruptible Power System This description contains all the
More information