1 2007 L&T SWITCHGEAR SAFE & SURE Electrician Handbook
2 The assurance of a leader Larsen & Toubro Limited (L&T), India's largest manufacturer of low tension switchgear, now offers the most comprehensive range to suit applications for the Building Segment. L&T s switchgear conform to the latest international standards and is comparable with the best in the world. Electrical from L&T for the Building Segment are dependable, easily available and carry the assurance of L&T backed by a strong service capability that extends nationwide. The need for safe electrical for buildings is critical because it touches each and every individual directly - be it at a commercial mall, a cinema house, a residential complex, an educational institution, a place of worship, an airport lounge, a railway station, a bus station. Unsafe electrical in these buildings expose us to potential risks of electrical shock, fire, electrical failure. That is why buildings need electricals that are safe and sure. And if these electrical are aesthetically pleasing, that an added advantage! That is why, for your buildings, you should insist on L&T's electrical. Building Electrical from L&T provide you with: greater safety, higher reliability, assured performance and aesthetically appealing designs. Personal Details Name: Address (Office): Phone: Mobile: Fax: Address (Resi): Phone: Electrical Supervisor Licence No: Vehicle Registration No: Driving Licence No: Bank Pass Book No: Blood Group: In Emergency, Contact: Phone: General:
3 Contents Page No. Modular devices - Tripper Range Modular devices - Hager 6 Wire Range 7 MCBs & Necessity of Earthing 8 RCCBs 9 Sensitivity for RCCBs & its Selection 0 Surge Protection Devices -2 Control & Automation - Selection chart for Typical Domestic Loads 6 Details of Max. Short circuit current as per transformer kva 7 Selection chart for motor applications 8 Cable selection chart 9 Conduit sizes 20-2 System designing 22 First aid for electric shock 2-2 Modular Devices - Tripper Miniature Circuit Breaker Conforms to latest global standards like IS 8828, EN / IEC Carries CE and ISI marking and KEMA certification Breaking capacity of 6 ka throughout the range Available in B curve in SP & DP and C Curve in SP, DP, TP & FP versions from 6 A to 40 A ratings Unique - True Contact Indication shows actual status of contact Low power loss - almost 0% of the values prescribed by IEC Terminals are suitable up to sq.mm wire, with provided with of Dual Termination facility No line-load bias Isolator Conforms to global standards like IS 947, EN / IEC Carries CE marking and KEMA certification Available in range of 40 and 6 A in DP, TP and FP versions Suitable for AC22-A utilization category Finger-proof terminals IP20 degree of protection Ergonomically designed, profiled for superior cooling and manufactured with fire retardant material Earth Leakage + Miniature Circuit Breaker (EL+MCB) Provides in protection against Earth leakage, Short circuit and Overload. It also avoids excessive metering due to leakage Conforms to global standards like IS 2640, EN / IEC Carries CE and ISI marking Available in DP & FP versions in the range of 6 to 6 A with 0mA or 00mA or 00mA sensitivity Truly current operated operates even at nominal volt Featured with neutral advance mechanism Operation even in case of neutral failure Distribution Boards - Tripbox Available in aesthetically pleasing ivory colour to suit the interiors of buildings and can be supplied in different colour for bulk requirements Readily available in IP0 & IP42 degree of protection Distribution boards are suitable for flush and surface mounting Ready to use DBs - provided with 00 A phase busbar, wire sets, earth & neutral bars as standard Provided with removable top and bottom gland plates with adequate knockout for easy wiring For bottom entry, neutral bar can be shifted to bottom for comfortable wiring TPN DBs will have provision to accommodate 6 MOD incomer Easy installation and flexibility in usage
4 L AF SU L A FE & S U O H O L L Modular Devices-Hager Wires & Cables Miniature Circuit Breakers (MCBs) High breaking capacity of 0 ka Protects against overload and short circuits in domestic, commercial and industrial electrical distribution systems Available in SP, DP, TP & FP versions in B, C and D curve, widest rang from 0. to 2 A ratings Two position DIN rail clips allows faster installation Suitable for DC applications Conforms to latest standards IEC: 60898, IEC: 60947, IS: Accessories for MCBs and RCCBs Auxiliary contact ( NO+NC) Trip alarm contact Shunt release Under-voltage release Locking kit Flush-mounting kit Residual Current Circuit Breakers (RCCBs) Available in DP and FP versions in 2 A, 40 A, 6 A and 00 A ratings with 0 ma, 00mA and 00mA sensitivity No nuisance tripping Conforms to IEC 6008 RCBOs Offers in protection against earth leakage, short circuit and over load Rating: 6 A to 2 A in 2 pole with 0 ma and 00mA sensitivity Breaking capacity 4.kA Conforms to IEC 6009 FR House Wires Flat Cables Wires for industrial, commercial and domestic applications Voltage grade up to 00V Conforms to IS standards Complete safety ensured Insulation types available for all wires are Flame Retardant (FR) Flame Retardant Low Smoke (FRLS) Zero Halogen Flame Retardant (ZHFR) Heat Resistant (HR) House Wires Made of annealed copper conductor Conforms to IS standards The insulation used is FR PVC compound for additional safety Twin coating for superior insulation Range : 0.7 sq.mm to 2 sq.mm Flat Cables The cables are rigid and withstand all adverse conditions Made of bright plain multi-strand annealed copper conductors Available in 00 meter coils and drums of 00 and 000 meters Range :. sq.mm to 70 sq.mm Also available: earth-leakage relays and voltage surge devices Distribution Boards A comprehensive range of insulated and metal distribution boards for domestic, commercial and industrial applications All components comply with the latest standards Wide range of accessories for additional safety and flexibility Plug and socket DBs TPN and SPN DBs Vertical TPN DBs Phase changeover DBs Phase segregated DB Flexible Wires Telephone Cable The L&T Advantage Technology Raw Material Unmatched service Stringent quality Top ranking company Advanced know-how and state-of-the-art manufacturing processes High quality raw material Pre and post sales service backed by a nationwide network L& T ES AF & S U RE 2 P A I R L & T Comprehensive quality assurance that exceeds industry standards & T S E & R E 7 M R G6F & T &T S R E 7 H M RG F &T Automation & Control Devices Isolators, two-way / centre-off changeover switches Modular electro-mechanical / digital time switches Time lag and twilight switches Modular bells and buzzers Electronic thermostats Dimmers and dimming systems Analog voltmeter and ammeters Co-Axial Cable Flexible Wires Single and multi-core wires are available Suitable for industrial wiring applications Available in standard length of 00 meters coil Range : 0. sq.mm to 000 sq.mm The assurance of one of India's most reputed companies 2
5 Technical Specification Why use an MCB? MCBs are safety devices used to protect electrical installations from overload and short circuit. They switch off the circuit automatically, thus protecting from electrical fires. Advantage over conventional / rewireable fuse For MCBs, power supply can be restarted by just switching on the MCB, whereas replacing a blown fuse between live, current-carrying points is potentially dangerous, especially in the dark. Range Conforms to the latest version of the international Standards IEC / 200 & IS 8828 : to 2 A,, 2, & 4 pole with 0 ka breaking capacity. 6 to 40 A SPN MCB in one module size. Methods of providing earth leakage protection RCDs can be installed in two ways :-. Whole house protection 2. Selective protection Whole house protection is provided typically by a consumer unit where RCD device serves as the main incomer switch. Although very popular, this suffers from a disadvantage : all circuits are disconnected in the event of fault. Selective protection can be provided by associating the RCD with identified high risk circuits by adopting one of the following methods.. Split busbar consumer unit All circuits are fed via an isolator and selected circuits fed additionally via the RCD. Typical circuits fed direct are lighting, freezer and circuits fed via the RCD are socket outlets, garage circuits, geysers and kitchen outlets. This concept minimizes inconvenience in the event of fault. 2. Whole ring circuit A 0mA device adjacent to the consumer unit which provides protection for the downstairs ring circuit, provides an easy installation with protection for all associated socket outlets. This represents the best solution for upgrading existing installations. Nuisance tripping All Tripper / Hager, ELMCB / RCDs incorporate technology preventing the risk of nuisance tripping due to transient voltages (lightening, line disturbances on other equipment) and transient currents (from high capacitive circuit). Why use an RCCB? RCCBs are devices which protect the user from the harmful effects of electric shocks. These function by detecting the residual current, comparing the value with the rated residual operating value and opening the protected circuit when the residual current exceeds this value. 4
6 RCCBs / RCBOs Hi - version - Hager These can be used either individually or as an incomer to an MCB system. RCCBs with an inbuilt MCB called RCBO are devices which protect electrical installation from overload, short circuit and earth leakage faults. Connection diagram phase 4 wire system supply phase wire system supply phase system supply RCCBs / RCBOs - Hi version : The Hi-version RCCBs are designed to reduce unwanted tripping due to transient currents & voltages on account of lightening (8/20 current wave), flourescent lamps (400 Hz over voltage) operation of electronic products like computers / dimmers and industrial electronic products like drives. This has the capability to detect to sinusoidal and direct earth leakage currents. use use The human body's reaction to electric shock Control & Automation - Hager When electrical shock currents, pass through the human body, the nervous systemis thrown out of gear. This causes the body to react to the passage of current through it as follows : ma - a tingling sensation is felt Contactors Used for remote switching and control of power circuits. Available from 20 A to 6 A for AC Utilization Category. Sensitivity and Selectivity RCD 0mA 00mA 00mA 0-mA - muscle spasm and tightening occurs 20-0mA - the heart may fibrillate; severe shock is felt. >0mA - lethal. Fibrillation of the heart occurs Application personal protection domestic installation limited personal protection building / fire Twilight Switches Used for street, display lighting, illuminated signs, etc. Devices control by photo electric cell which measure light level, and in conjunction with relay are used to ON / OFF lighting circuit (in relation to natural light). Available in two sensitivities to 00 Lux and 0 to 2000 Lux. 6 7
7 Control & Automation - Hager Surge Protection Devices - Hager Time lag Switches Used for showrooms, multi storied buildings. Device controls lighting circuits with automatic switch - off after pre - set time (delay adjustable from 24 sec. to 2 min.) Rated for 6 A, 20 V AC and suitable with push buttons only. Dimmers & Dimming System Modular devices used for control of lighting levels in domestic premises, software offices, large corridors, conference halls and hotels. Control is localised. Remote is possible by associated Push Buttons. Separate dimmers are available for control of incandescent, halogen with standard or electronic ballast and flourescent lamps. Stand - alone dimmers for 600 W and 000 W, while control of 000 W can be possible by using master and slave combination. 2 - Way / centre-off changeover switches Used for changeover from one source of supply to another with centre - off position e.g. MSEB to DG supply changeover. AC 2 A utilisation category and suitable for use on 0 V DC. Available in 2 - Pole 2 & 40 A and 4 - Pole 40 A version. Voltage transients are mainly caused by switching events externally and internally Externally by :- Switching of transformers Switching of breaker and capacitor bank Large induction motors Speed controllers on motors Internally by :- Power Surges In low voltage AC power circuits, surges have two origins lightning or switching events. Voltage transients Lightening When lightening strikes on or near a primary circuit, it produces a transient voltage which is transmitted through a transformer to your secondary circuit. When lightening strikes on or near the secondary circuits, it results in an even higher surge to your equipment. Fluorescent, mercury / sodium discharge lighting Switching of compressors Air conditioners, commercial and domestic Washing machines In fact any inductive load will cause an increase in the line voltage at the time of switch off. As the fully excited magnetic field is collapsed due to switch off a very high voltage will be generated which may destroy sensitive electronic equipments. Surge is defined as voltage above 2 V (on a 20V Line) for a half cycle or longer. Power surges are bound to occur, but there is a way to offer protection for electrical and electronic equipment used in business. A surge protector is exactly the device that offers protection for the above equipment from transient over voltages. It can absorb and dissipate thousands of joules of energy. 8 9
8 Surge Protection Devices - Hager Surge Protection Devices - Hager SPD working :- The SPD responds to the transient over voltage by changing from its normal high resistance to low resistance and conducting surge current to ground. This current, and the resistance of the protector results in a discharge or residual voltage across the protector. This same voltage is seen by the protected equipment and defines the protective capacity of the surge protector. Damages caused by Transient over voltage - Disruption Degradation Damage Downtime SPD Standards :- Class I : 0/0 s impulse, lightning arrestors Spark gap technology, Up (residual voltage) - 4 kv / 7 kadiverting capacity to be used as main protection when there is a lighting rod near the installation. Our Products of class I are : SP7 Class II : 8/20 s impulse, over voltage protection, Varistors & GDT Up around <2. kv / 6 kadiverting capacity Our products of class II are : SP40D, SP440D. How to choose SPD :- Risk assessment What is the type of equipment? What costs the protected device? What is the risk of downtime? Is the protected material assured? Is the region exposed to lightening? Is there a lightening rod nearby the installation? What is the type of earthing system used TT, TN-S,TN-C, IT? Type of network (, 2 & phase)? What is Un (nominal working voltage) of the network? Any data network or telephone line? Caution: Use MCB or fuse as a backup protection for the SPD. * For further details on the product and installation guidelines, refer to our Technical Guide (on Hager Products). * In case of Electric Shock. Class III : Hybrid impulse, over voltage protection, Up < kv / 24 ka diverting capacity Our Products of class III are : SP208 The ability of a surge protector to handle a given amount of energy reflects its ability to survive. And to continue to protect the equipment, surge after surge it is most important to choose the proper surge protector. No protector can survive a direct lightening strike. 0
9 Selection chart for typical domestic loads S.No. Items Load/Wattage MCB rating Fan Lamp, Tubelight Room Heater Water Heater 8 ltrs ltrs 60 ltrs Immersion Heater Hot Plate-single Iron-Nonautomatic Automatic Mixer / Juicer TV / VCR / VCP Music system Refrigerator 6 ltrs 28 ltrs 0 ltrs Toaster Vacuum Cleaner Washing Machine without heater with heater Water Cooler Desert Cooler Oven Electric Kettle Air Conditioner ton. ton 2 ton Hair Dryer Microwave Formula for Calculations : Incomer Rating : Single Phase = 60W 40W 200W W W W 000W 000W 00W 000W 00W 200W 200W 400W 600W 70W 00W 400W 00-00W W 700W 00W 70W W 00W 2000W 000W 800W Total Load in Watts 20 volts Three Phase = Total Load in Watts x20 volts The given data is only for guidance and may vary for different manufacturers * * A 0 A 20 A 2 A 6A 6A A 6A 2A A A A 4A 6A A A 0 A 2 A 6A 2A 6A 7. A 0 A 6 A 6 A 7. A 6A Transformer Rating kva Max. Short Circuit current as per Transformer kva Full Load Current at 4 V Max. Short Circuit Current A (ka) 4% impedance % impedance
10 Motor Rating 4V, phase Selection table for motor application Full load current approx. Relay range Recommended back-up MCB 'C' Type 'D' Type hp kw amp. amp. amp. amp NC06N NC0N NC0N NC6N NC6N NC6N NC20N NC2N NC2N ND0N ND04N ND06N ND06N ND06N ND0N ND0N ND6N ND6N Cable selection chart Single core, twin insulated wires in voltage grade 00V, conforming to IS: with additional FR properties. Nominal area of conductor Sq. mm Current carrying capacity single phase In conduit Max. Resistance o per km. at 20 C Amp. Ohms Standard Colours : Red, Green, Blue, Yellow, Black. * As per IS: 96 (Part V) Above data is indicative. L&T will not be liable for damage arising from incorrect applications Chart for Star-Delta starting Colour identification of cables Motor Rating 4V, phase Full load current approx. Relay range Recommended back-up MCB 'C' Type 'D' Type hp kw amp. amp. amp. amp NC0N ND0N NC04N ND02N NC04N ND0N NC06N ND0N NC0N ND04N NC0N ND06N NC6N ND06N NC6N ND0N NC20N ND0N NC2N ND6N R phase of phase AC circuit Y phase of phase AC circuit B phase of phase AC circuit Neutral of single / phase AC circuit Earthing Derating of Wires Purpose Colour of cable 0 Ambient Temp. C 0 Rating factor red yellow blue black green
11 Cable Size Nominal Conductor Size mm² Capacities of PVC conduits Capacities of rigid steel conduits 6mm or /8" Conduit Size and Gauge 20mm or /4" 2mm or " 2mm or ¼" Number of Cables (maximum) Size of Copper Nominal cross sectional area mm² 6 Size of Conduit (mm) Number of Cables (maximum)
12 hager Board Type Enclosure Incomer Outgoing MCBs Busbar hager System designing System designing SPN Distribution Board TPN Distribution Board with SP Outgoing P N hager hager hager hager hager hager hager hager hager hager hager hager hager hager hager hager hager hager hager test regularly : push button to trip hager hager hager hager hager hager hager R Y B N 6-way 8-way 2-way Board Type 6-way 8-way 2-way CU8N CU0N/DU0N CU4N/DU4N Enclosure CU28N/DU28N CU6N/DU6N DU42N double pole - RCCB, RCBO, MCB or isolator Incomer four-pole - RCCB, RCD - Add-on Block + MCB 6 x SP 7 Mod of pole 8 x SP 9 Mod of pole 2 x SP Mod of pole Outgoing MCBs & blanking clips Busbar 8 x SP 2 x Mod 8 Mod of pole 24 x SP 4 x Mod 24 Mod of pole 6 x SP 2 x Mod 8 Mod of pole 8 9 0
13 System designing System designing TPN Distribution Board with TP/SP Outgoing SPN Spilt Load Distribution Board hager hager hager hager hager hager hager hager hager hager hager hager hager hager hager hager hager hager hager hager 6A AC22 BS 49 80/4 V ~ 0Hz 2 4 SB299 0N 0N test regularly : push button to trip R Y B N P N hager hager hager ION 0OFF Board Type 6-way 8-way 2-way Enclosure CU4N/DU4N - row 4 Mod Enclosure Incomer Outgoing MCBs & blanking clips CU28N/DU28N 4 pole - RCCB, RCD - Addon Block + MCB 6 x TP 6 x Mod CU6N/DU6N 8 x TP 8 x Mod DU42N 2 x SP 6 x Mod Incoming devices Outgoing devices Connection Main incomer - SF 29G - 2 pole change over switch Sub incomer - 2 pole RCCB (for high risk circuits) SP MCBs - 9 Nos. SP Busbar - 9 Mod. Busbar 2 Mod of pole 24 Mod of pole 9 Mod of pole End caps 4 x pole 4xpole 6xpole np
14 System designing - TPN DBs - PPI DBs TPN Distribution Board with per phase isolation having RCCBs in each Outgoing Phase hager hager hager hager hager hager hager hager hager hager hager test regularly : pushbuttontotrip hager hager hager hager hager hager hager hager hager hager hager test regularly : pushbuttontotrip hager hager hager hager hager hager hager hager hager hager hager test regularly : pushbuttontotrip hager 6A AC22 BS 49 80/4 V ~ 0Hz 7 SB N 0N 0N 0N N Y B R Enclosure DU6N - row 6 Mod * Incoming devices Main incomer - 4 pole Isolator Sub incomer - 2 pole RCCB in each phase Outgoing devices SP MCBs - 2 Nos. per phase Connection SP Busbar - Mod. per phase Neutral bar - per phase. * Above arrangement available with MCCB as incomer in a separate Distribution Board as standard. 22 First Aid in case of Electric Shock Which factors cause an electric shock? Contact with high-tension wires is often fatal. The upon intensity of a shock depends Voltage The Type of Current, Length of Exposure Time The Path it Takes Through the Body (the heart or head are the most dangerous routes) What can happen if you get an electric shock? Heart Failure ("cardiac arrest") Burns Nerve, Muscle, and Organ Damage What should you do if someone gets shock? To treat a person who has sustained electrical injury: Unplug the appliance and/or turn off the MCB (at the fuse box). (Merely turning the switch off will not necessarily stop the flow of current.) Call an ambulance. If the victim is not breathing, immediately begin mouth-to-mouth resuscitation. To prevent shock, Place the victim's feet higher than the head by about a foot. Cover person with a blanket or coat if available. 2 np 0 0 0
15 Check for indications of shock: Cold, Moist Skin Fast Heartbeat Paleness Feeling Faint Check for burns, which may not be visible from the outside. Sites to inspect in particular are: The fingers and toes Skin touching against metal accessories like jewelry or a belt buckle Take off any clothing over the burn - but only if it comes away without pulling skin along with it. As long as the skin is unbroken, you can rinse the burn in cool, running water to ease pain. Cover any surface burns with a sterile dressing or clean cloth. Separate burnt fingers or toes with the dressing. Take the victim to the emergency roomeven if the person is breathing, is conscious, and insists that s/he is all right. Things to avoid: Do not touch the person with your bare hands before you are certain there is no live electricity. WARNING: Never move the person if they are touching a power line or other source of high voltage. Under such circumstances keep a distance of at least 20 feet. The above precautions are for your own safety. 24 CAUTION: For the safety of the victim, do not move him/her if spinal injury is possible from an explosion or fall associated with the accident. Do not remove clothing that is stuck to the wound. Never put ice on a burn. Do not apply ointments or grease to burned skin (as with burns from flames). Do not bandage with a towel, blanket, or cotton dressing that will stick to the wound. (Instead, use a sheet for large area.) Take care not to break any blisters that have formed. Shield the burned area from chafing. What should you do if not sure if the power is off? If turning off the electricity is impossible or you can't tell whether it is off (unless it is high-voltage current), then to approach the victim: Stand on a mat (preferably rubber, but piled up newspapers/magazines could be used if necessary), and Extend a wooden or cloth object, such as a Broom handle, Chair, Piece of clothing, or Rope Sources: U.S. Centers for Disease Control and Prevention, U.S. National Library of Medicine 2
16 Important Telephone Nos.
About us. Switchgear Factory, Mumbai
Wires & Cables About us Larsen & Toubro is a technologydriven USD 9.8 billion company that infuses engineering with imagination. The Company offers a wide range of advanced solutions in the field of Engineering,
More informationRESIDUAL CURRENT CIRCUIT BREAKER
Quality Features Mid Trip - Different knob position to indicate whether the device is Switched OFF by a fault or Switched OFF manually Inscription Window - Ensures circuit identification and hence reduces
More informationDomae. The right solution for distribution boards
Domae The right solution for distribution boards Guaranteed quality and adapted solutions Domae : SIRIM approved The quality marks prove product conformity to their reference standard. They guarantee:
More informationRange 16A to 63A. Sensitivity 30mA, 100mA, 300mA, 500mA. Execution Double Pole, Four Pole. Specification IEC / IS : 2000
The flow of current through electrical facilities always involves risks. Poorly insulated equipment, faulty wires and incorrect use of an electrical devise cause currents to flow through the wrong path
More informationAmount (Rs) 1.5 sq. mm ISI marked, FR
BILL OF QUANTITY FOR ELECTRICAL WORK AT ESI REGIONAL OFFICE, STAFF QUARTERS, SEC-16 AND ASSOCIATED BRANCH OFFICE AND DISPENSARY. Part-II Sr. no SOR No. Details of Items Unit Quantity Rate (Rs) Amount (Rs)
More informationEquipment model: auxiliary control. Pack Cat.Nos 10/16 A V± P + T shuttered module module
transformers and buzzers and bells socket outlets and special supports 042 25 042 52 041 07 042 80 042 85 Pack Cat.Nos Bell transformers dconform to IEC / EN 61558-2-8 Protected against overloads and short
More informationMINIATURE CIRCUIT BREAKER
Technical Article MINIATURE CIRCUIT BREAKER T 146 PURCHASE he Spaceage MCB protects wires and cables automatically against overload and short-circuits in domestic, commercial and industrial installations.
More informationMiniature Circuit Breaker
Introduction - Miniature Circuit Breaker (MCB) SALIENT FEATURES SALIENT FEATURES Standards MCBs conform to the latest standard IS 8828: 1996/IEC: 898 1995 Mid-Trip Position The Mid trip position of the
More information20th Dec, aptis range
list effective 203Price 20th Dec, 203 aptis range aptis range value for money Hager unveils its "value for money" offer - aptis! A range with required features and functionality for safe electrical installations.
More informationDX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data
Specifications IS/IEC 60898-1 2002 Number of poles SP, SPN, DP, TP, TPN, FP Characteristics C & D Curve Breaking capacity 10 ka 0.5 A to 63 A as per IS/IEC 60898-1 2002 16 ka for 0.5 A to 25 A as per IEC
More informationTender Schedule for Electrical Works at Varagani Branch. Sl. No. Particulars Quantity Unit Rate Amount
Tender Schedule for Electrical Works at Varagani Branch Sl. No. 1 Particulars Quantity Unit Rate Amount SITC of following rated Indoor operated wall/floor mounted, cubicle type MV cum APFC Panel suitable
More informationThe young energy ensures more safety
The young energy ensures more safety Domestic Products Catalogue 2017 CORPORATE OFFICE ABOUT STANDARD STANDARD is a brand of India s leading FMEG company, Havells India Ltd., that offers a wide range of
More informationElectrical Workplace Safety
Electrical Workplace Safety Alan Kelly 23 rd September 2015 Objectives To provide an understanding of Electrical terms and the concepts of electricity To introduce Electrical Protective Devices and provide
More informationPerfection that Matters
Perfection that Matters Switchgear Range Catalogue 2017 Contents Power Series Distribution Boards Classique Distribution Boards Miniature Circuit Breaker Isolator Residual Current Circuit Breaker Residual
More informationic60h (6kA) single module combined RCD/MCB units ic60h (10kA) single module combined RCD/MCB units ild residual current circuit breakers idpn N Vigi
Contents Miniature circuit breakers ic60n miniature circuit breakers 6kA, C curve, 6-63A ic60h miniature circuit breakers 10kA, C curve, 6-63A ic60n miniature circuit breakers 6kA, B curve, 6-63A ic60h
More informationTENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID
TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID S.NO. HEAD DESCRIPTION AMOUNT (Rs.) 1 A DG SETS & ACCESSORIES
More informationNew DX 3 High rating & breaking capacity
New High rating & breaking capacity a new range OF MOduLar CirCuiT BrEakErs up TO 125 a T new dx³ MCBs AN ENHANCED range for HIgH-pErforMANCE INstALLAtIoNs DX³ : the new Legrand MCBs with dx³, Legrand
More informationUsing Electricity. Summary Notes. 1. From the Wall Socket Household appliances. Earth wire and safety.
Using Electricity Summary Notes Section Content 1. From the Wall Socket Household appliances. Earth wire and safety. 2. Alternating and Direct Battery and transformer. Current Circuit diagrams. Current
More informationUniversity of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab
University of Jordan School of Engineering Electrical Engineering Department EE 219 Electrical Circuits Lab EXPERIMENT 10 HOME WIRING BASICS Prepared by: Dr. Mohammed Hawa EXPERIMENT 10 HOME WIRING BASICS
More informationConsumer unit solutions to meet the requirements of the new 17th edition amendment 3 regulations
MEMT Memera full metal consumer units and protective devices Consumer unit solutions to meet the requirements of the new 17th edition amendment 3 regulations Memera full metal consumer units and protective
More informationGet detailed information on many digital or printed supports, or contact your Area Commercial Manager
The RX 3 and DX-E ranges provide essential functions for the protection requirements of people and property in residential and small commercial buildings Two breaking capacities, 4500 and 6000 (IEC 60898-1)
More informationTX³ RCCBs 2P up to 100 A
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 TX³ RCCBs CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More information(Miniature Circuit Breaker)
(Miniature Circuit Breaker) Features : l Uniform 10KA breaking capacity for B and C Curve l Low power consumption, thus cost effective & energy saving l Suitable for DC and for a wide frequency range of
More informationThe young energy ensures more safety
The young energy ensures more safety Domestic Products Catalogue 2017 CORPORATE OFFICE ABOUT STANDARD STANDARD is a brand of India s leading FMEG company, Havells India Ltd., that offers a wide range of
More informationWorking Principle of Earth Leakage Circuit Breaker (ELCB) and Residual Current Device (RCD)
Working Principle of Earth Leakage Circuit Breaker (ELCB) and Residual Current Device (RCD) Schneider Electric RCBO Earth Leakage Circuit Breaker (ELCB) An Earth Leakage Circuit Breaker (ELCB) is a device
More informationDX³ RCCBs - ID 4P up to 100 A
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ s - ID CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationCOMPLETE SOLUTIONS FOR POWER PROTECTION
COMPLETE SOLUTIONS FOR POWER PROTECTION GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES Modular protection P. 8 RX 3 MCBs 63 A 4500 & 6000 P. 18 DX 3 -IS isolating switches P. 9 RX
More informationRelax... you re in safe hands CONSUMER UNITS / PRODUCT GUIDE.
Relax... you re in safe hands CONSUMER UNITS / PRODUCT GUIDE Distributor : LEGRAND ELECTRIC LIMITED Great King Street North, Birmingham, B19 2LF Tel : 0870 608 9000 Fax : 0870 608 9004 CONSUMER UNIT BRO.10.05.??K
More informationBILL OF QUANTITY (BOQ) FOR ELECTRICAL WORKS BOGAPURAM BRANCH
BILL OF QUANTITY (BOQ) FOR ELECTRICAL WORKS BOGAPURAM BRANCH SL NO. DESCRIPTION OF ITEM / WORK UNIT QTY PART - A : ELECTRICAL WORKS 1 1 Energy Meter Cubicle : a Fabrication, Supply, Installation, testing
More informationINDIAN INSTITUTE OF TECHNOLOGY KANPUR
INDIAN INSTITUTE OF TECHNOLOGY KANPUR Tender tice. 21/Elect./2018 SCHEDULE OF QUANTITY Name of Work: Construction of second floor above central block at ACES building (SH: Electrical works). Name of the
More informationINDIAN INSTITUTE OF TECHNOLOGY KANPUR
INDIAN INSTITUTE OF TECHNOLOGY KANPUR Tender Notice No. 40/Elect./2018 SCHEDULE OF QUANTITY Name of Work: Electrical work for the Clean Room at NCFlexE IIT Kanpur. Name of the Contractor S. No Description
More informationTender Schedule. Sl. No. Particulars Quantity Unit Rate `
Tender Schedule Estimate for Electrical Works at Savalyapuram Branch(18901) Guntur(District). Sl. No. Particulars Quantity Unit Rate ` 1 Wiring for light point/ fan point/ exhaust fan point/ call bell
More informationPDL s DBF AND DBS SERIES DISTRIBUTION BOARDS
PDL s DBF AND DBS SERIES DISTRIBUTION BOARDS FEATURES Robust, durable construction Unique double doors open 180 with minimum projection Light grey colour standard, can be painted to suit décor re quirements
More informationxboard safety, reliability effectively combining and performance safety, reliability and performance in commercial and industrial applications
xboard commercial and industrial panelboards xboard effectively combining safety, reliability and performance safety, reliability and performance in commercial and industrial applications NEW xboard (xdb)
More informationELECTRICIAN S THEORY EXAMINATION 20 June 2015 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET54 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 20 June 2015 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three hours
More informationDX³ 4-pole RCBO 6000 A/10 ka
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ 4-pole RCBO CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationGreater protection UNDERSTANDING THE 17TH EDITION CONSUMER UNITS / PRODUCT GUIDE
Greater protection UNDERSTANDING THE 17TH EDITION CONSUMER UNITS / PRODUCT GUIDE Summary of changes Simplifying the 17 th Edition Understanding new regulations is never easy... that s why we ve tried to
More informationEstimate For The Electrical Works At Pittakayagulla Branch Sl.N Particulars Quantity Unit Rate Amount
Estimate For The Electrical Works At Pittakayagulla Branch Sl.N Particulars Quantity Unit Rate Amount 1 2 Writing for light point/ fan point/ exhaust fan point /call bell point with 1.5 sq.mm FR PVC insulated
More informationSCHEDULE OF QUANTITY
SCHEDULE OF QUANTITY ELECTRICAL WORKS PM PALEM BRANCH, VISAKHAPATNAM SL NO. DESCRIPTION OF ITEM / WORK UNIT Qty RATE AMOUNT PART - A : ELECTRICAL WORKS 1 Energy Meter Cubicle : 2 Emergency Off Box (Red
More informationCat. N (s) : /65/66/83/84, /94/95/96/99, /01/02/06/07/11/12/13/14. Pollution degree : C / + 40 C. .
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s 0090 00/01/02/06/07/11/12/13/14 0/01/02/06/07/11/12/13/14/18/19/23/24/25/26/ /18/19/23/24/25/26/45/46 45/46 0090
More informationName of work : Electrification of PG Block Second Floor in V.P.S.V Ayurveda college Kottakkal.
Name of work : Electrification of PG Block Second Floor in V.P.S.V Ayurveda college Kottakkal. TENDER SCHEDULE -1-1 2 3 4 5 6 7 1 208 Point Wiring for light point/ fan point/ exhaust fan point/ call bell
More informationBharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT
An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY NOTICE INVITING TENDER Phone:
More informationMAIN INCOMER -1 (500 KVA TRF.)
Sr.No. DESCRIPTION MAKE QTY 1 MAIN L.T.PANEL Design, fabrication assembling, supply, installation, testing and commissioning of cubicale type LT panels floor mounted free standing suitable for 415 V 3
More informationELECTRICAL INSTALLER EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET
Candidate Code No. EIN15 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSTALLER EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three
More informationDPX moulded case circuit breakers
BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.
More informationNPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations
Version:- 3.0 Date of Issue:- Dec 2013 Page 1 of 13 NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations 1. Purpose This document is the technical specification
More informationPhase + Neutral, neutral on right side
87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34
More informationBasic. Electrical Safety. January 2009
Basic Electrical Safety January 2009 Sunday, 10 January 2010 The complete circuit A complete Circuit or loop is necessary for current to flow Sunday, 10 January 2010 2 A complete circuit complete Circuit
More informationDSE201 Compact design with enhanced protection
DSE201 Compact design with enhanced protection The best of safety DSE201 6 ka: the highest level of reliability The 1P+N electronic residual current circuit-breakers with overcurrent protection (RCBOs)
More informationOrdinary Level Physics SOLUTIONS: EFFECTS OF AN ELECTRIC CURRENT
Ordinary Level Physics SOLUTIONS: EFFECTS OF AN ELECTRIC CURRENT Safety Features and kilowatt hours The unit of energy is called the kilowatt hour One kilowatt hour is the amount of energy used by a 1000
More informationR.C.B.O. SP / 1 module
87045 LIMOGES Cedex - France Telephone : (+33) 5 55 06 87 87 Fax : (+33) 5 55 06 88 88 R.C.B.O. SP / 1 module 6064 04 6064 64 05 6064 10 6064 11 6064 12 CONTENTS PAGES 1. Description, use... 1 2. Range...
More informationELECTRICIAN S THEORY EXAMINATION 19 June 2010 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET34 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 19 June 2010 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three hours
More informationVOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS
VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.
More informationDX³ RCBO 4500/6 ka Phase + Neutral, neutral on left
87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX³ RCBO 4500/6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...
More informationNS Feeder pillar up to 3200A
NS Feeder pillar up to 3200A Advanced technology for low voltage, outdoor distribution Merlin Gerin Modicon Telemecanique Outdoor electrical distribution with advanced technology Merlin Gerin low voltage,
More informationApproved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN
Motor Contactor Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN rail) up to 45 kw Range from 4 to 110 kw (AC 3, 380/415V) Finger proof ( VBG 4) Accessoires
More informationAN ISO 9001:2015 COMPANY
AN ISO 9001:2015 COMPANY Eco-Friendly Price List w.e.f. 01/03/2018 IS : 8828 ISO 9001:2008 CERTIFIED ORGANISATION IS : 13779 Introduction Welcome to the world of BillTech, One of the reputed name in the
More informationClass X Chapter 09 Electrical Power and Household circuits Physics
EXERCISE- 9 (A) Question 1: Write an expression for the electrical energy spent in flow of current through an electrical appliance in terms of current, resistance and time. Solution 1: Electrical energy,
More informationWall mounted switchgear
Contents Safepact 2... pages /2 to / Enclosed MCCBs 6 to 60A... page /2 Enclosed switch disconnectors 100 to 60A... page / Earth leakage.... page /4 Auxiliaries and accessories... page /5 Enclosed Interpact...page
More informationQUALITY ASSURANCE & DOCUMENTATION
QUALITY ASSURANCE & DOCUMENTATION RTECK IMPORTED PRODUCT STATEMENT Rteck has sourced most product from a large and reputable Chinese product manufacturer who specialise in the manufacture of modular electrical
More informationMINIATURE CIRCUIT BREAKERS RCBO s & DIN RAIL MOUNTED FUSE HOLDERS
MINIATURE CIRCUIT BREAKERS RCBO s & DIN RAIL MOUNTED FUSE HOLDERS MANUFACTURED IN THE EU EUROPEAN QUALITY 1, 2 & 3 POLE MCB s TRIPPING CURVES C & D CURRENT RATINGS 1AMP TO 63AMPS 10KA BREAKING CAPACITY
More informationELECTRICIAN S THEORY EXAMINATION 21 June 2014 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET49 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 21 June 2014 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three hours
More informationModular contactors and relays
pages /4 to / pages /8 and /9 pages /10 and /11 pages /12 and /13 Presentation and standards Presentation Designed for use in modular panels and enclosures, these contactors feature : i Easy installation
More informationPower System Solutions (PSS)
About Power System Solutions mission The Power System Solutions Mission Statement To achieve customer satisfaction by providing innovative solutions to improve upon power quality, energy efficiency, and
More informationA direct current (DC) circuit. L 26 Electricity and Magnetism [4] Alternating Current (AC) Direct Current DC. AC power
L 26 Electricity and Magnetism [4] A direct current (DC) circuit simple electrical circuits direct current DC Alternating current (AC) vs direct current (DC) electric power distribution household electricity
More informationELECTRICIAN S THEORY EXAMINATION 11 September 2010 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET36 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 11 September 2010 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three
More informationBtdin-RS RCBO 2p Phase + Neutral, neutral on right
Viale Borri 231, 21100 Varese - Italy RCBO 2p CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection... 1 5. General characteristics... 2 6. Compliance
More informationELECTRIC POWER AND HOUSEHOLD CIRCUITS
ELECTRIC POWER AND HOUSEHOLD CIRCUITS HEATING EFFECT OF CURRENT Heating effect of electricity is one of the widely-used effects in the world. When electric current is passed through a conductor, it generates
More informationBoardworks Ltd Mains Electricity
1 of 22 Boardworks Ltd 2016 Mains Electricity Mains Electricity 2 of 22 Boardworks Ltd 2016 Direct current 3 of 22 Boardworks Ltd 2016 There are two main types of electric current: direct current (DC)
More informationPhase + Neutral, neutral on left side
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1
More information1.4. Product overview Memera consumer units and devices
1.4 MEMT series Memera consumer units The Memera range of consumer units provide a broad scope of products to meet the requirements of the 17th edition of the wiring regulations. This well established
More informationUnrestricted. S.Mukhopadhyay
Unrestricted S.Mukhopadhyay 10.09.15 Electrical safety A report says that every year 5500 Indians die due to electric shock and 800 due to electric fire. 12% work place death due to electrocution ELECTRICAL
More informationPower systems Protection course
Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used
More information87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS
87045 LIMOGES Cedex Phone : + 33 5 55 06 87 87 Fax : + 33 5 55 06 88 88 R.C.B.O. DX 6000 A Phase + Neutral,, neutral on right side Cat. n (s) : 077 31 077 44-077 77 077 84 078 79 079 01-083 95 084 06 084
More informationElectrical Hazard Three factors determine the resistance of a substance to the flow of electricity: conductors insulators extreme caution
Electrical Safety Electrical Hazard Three factors determine the resistance of a substance to the flow of electricity: What it is made of. Its size. Its temperature. Substances with very little resistance
More information3 - Protection components Motor circuit-breakers
Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page
More informationTraining & Didactic Systems. Fundamentals of Electrical Engineering
Training & Didactic Systems Fundamentals of Electrical Engineering Catalog WA1E/01 Table of Contents Page Our Service, Our Customers and fields of technology 2 Introduction 4 Instruction modules measuring
More informationElectrical Safety in Die Casting
Electrical Safety in Die Casting April 2016 Beau Glim NADCA Project Manager NADCA Safety Series 4 parts Basic Safety Machine Maintenance Safety Electrical Safety Managing Safety General safety information
More informationCentral Battery Systems
Central battery system based emergency lighting is ideal for medium to large installations. For projects where central control and testing is desirable, a central battery system is a viable and cost effective
More informationTransforming Energy.. For Advanced Technology
Transforming Energy.. Manufacturers of CE approved Transformers & Reactors Five Decades of Manufacturing Experience Manufacturers of Quality Reliable Transformers. Auto C 201,4 th Cross Peenya Induatrial
More informationItem L.1 Voltages 1. The consumer voltage must be between +10% and -10% of the nominal national voltage (nnv.)
Village Hydro Specifications Line Distribution Description of Requirement Item L.1 Voltages 1. The consumer voltage must be between +10% and -10% of the nominal national voltage (nnv.) Recommendation 2.
More informationDNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation
More informationS H A D E S ELECTRICAL DB MANUFATURING
CORPORATE BROCHURE S H A D E S ELECTRICAL DB MANUFATURING S H D E S ELECTRICAL DB MANUFACTURING L.L.C. www.shadesdb.com I N T R O D U C T I O N Welcome to SHADES, this portfolio has been designed to give
More informationBattery Power Inverters
Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.4 Important Safety Instructions Please save these instructions.
More information(1,5 modules per pole)
87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 DX 3 MCB 36kA, 80A CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationINTERACTIVE SCIENCE 2A
INTERACTIVE SCIENCE 2A Workbook Solutions (Enrichment Edition) Chapter 8 MAKING USE OF ELECTRICITY Part A Sectional Exercise 8.1 & 8.2 Concept checking p.35 1. False 2. True 3. False 4. True 5. True Questions
More informationTechnical Journal September 2012
Technical Journal September 2012 Earth leakage protection in polluted low voltage network In present day irrespective of the application be it in process industry or in IT industry, Pollution of electrical
More informationELECTRICIANS REGULATIONS EXAMINATION 29 June 2013 QUESTION AND ANSWER BOOKLET
ER52 Candidate Code No. For Board Use Only Result Date Result Date Int ELECTRICIANS REGULATIONS EXAMINATION 29 June 2013 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY
More informationModular contactor for installation into distribution boards
Modular contactor for installation into distribution boards Description Modular contactors are used for installation in consumer units in dwellings, business premises, hotels, hospitals, shopping centres,
More informationParamount HRC Cartridge
Paramount HRC Cartridge Eaton MEM HRC fuselinks are manufactured to exacting standards using precision assembly methods and undergo rigorous quality checking before dispatch including resistance testing
More information5. High voltage warning labels should be placed on all cabinet doors and terminal covers enclosing equipment operating at above 50 volts.
Village hydro specifications Electrical components E1. Labels and notices Requirement 1. All electrical components must carry labels describing their function. This applies particularly to switches and
More informationInstallation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor
World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com
More informationCentral Battery Systems
Central battery system based emergency lighting is ideal for medium to large installations. For projects where central control and testing is desirable, a central battery system is a viable and cost effective
More informationDX³ RCBO 6000 A Phase + Neutral, neutral right side
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX³ RCBO 6000 A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection... 1
More informationDATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT
44LK-500/E.04/002A/A4 PROJECT NO 44LK-500 CHKD. BY VDV VDV A CLIMATIC CONDITIONS THIS DATA SHEET IS APPLICABLE FOR IN UTILITY BOILER PACKAGE DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.7
More informationl Suitable for most residential, commercial and light industrial applications
538 Consumer Units and Enclosures Standards and approvals All Sentry consumer units are designed to fully comply with the requirements of BS EN 60439-3. Weatherproof enclosures are designed to fully comply
More informationELECTRICAL SERVICE TECHNICIAN EXAMINATION 16 September 2017 QUESTION AND ANSWER BOOKLET
Candidate Code No. EST 2074 For Board Use Only Result Date Int Result Date Int ELECTRICAL SERVICE TECHNICIAN EXAMINATION 16 September 2017 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed:
More informationChapter 4 Utility Systems Electrical
Chapter 4 Utility Systems Electrical Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
More informationand other modular devices for low voltage installation
Technical catalogue System and other modular devices for low voltage installation 2CSC400002D0204 SUMMARY Introduction Miniature Circuit-Breakers Residual Current Devices Auxiliary elements and accessories
More information9. Effects of an electric current
Leaving Cert Physics Long Questions 2017-2002 9. Effects of an electric current Please remember to photocopy 4 pages onto one sheet by going A3 A4 and using back to back on the photocopier Contents Ordinary
More information