BC HYDRO REAL TIME OPERATIONS DISTRIBUTION OPERATING ORDER 1D-23. PERMIT FOR ENTRY INTO CABLE MAN HOLES Supersedes 1D-23 issued 29 February 2016

Size: px
Start display at page:

Download "BC HYDRO REAL TIME OPERATIONS DISTRIBUTION OPERATING ORDER 1D-23. PERMIT FOR ENTRY INTO CABLE MAN HOLES Supersedes 1D-23 issued 29 February 2016"

Transcription

1 BC HYDRO REAL TIME OPERATIONS DISTRIBUTION OPERATING ORDER 1D-23 PERMIT FOR ENTRY INTO CABLE MAN HOLES Supersedes 1D-23 issued 29 February 2016 Review Year 2021 Original signed by APPROVED BY: Doug Pochailo System Control Manager, Real Time Operations Denotes Revision

2 1.0 GENERAL DOO 1D-23 Page 2 of 7 This purpose of this operating order is to define the procedures used by the BC Hydro control centre for the application of a Man Hole Permit (MHP). The application of an MHP is reserved exclusively to support entry into a BC Hydro cable manhole, where either: A BC Hydro owned Feeder Cable exists, as defined in 1T-02, or A BC Hydro owned main trunk cable circuit exists, which extends beyond the portion of circuit defined as The Feeder Cable but not beyond protective fusing. Example: On circuit DGR 88, UC 7F149 Application of an MHP is not intended to minimize hazards associated with underground cables which are normally protected by fusing. When a MHP is issued for work in a manhole where both Feeder and fused cable (typically URD) exist, the BC Hydro control centre Person-In-Charge (PIC) will take positive and documented steps to help minimize hazards associated with the Feeder Cable. It is not expected that the PIC will take any action to minimize hazards associated with the fused cables. Should any hazard exist where the issuance of a MHP is deemed by the field worker as inadequate to meet worker safety requirements, the field worker is responsible to then arrange additional equipment outages, Safety Protection Guarantees or Assurance of No Reclose Permits as required, by making their requirements know to the Fraser Valley Office (FVO) Outage Scheduling department. See Operating Order 1D-02 for BC Hydro outage scheduling requirements. It must be firmly recognized that the application of a MHP is intended to help minimize the hazards associated with an energized Feeder Cable which exists in a BC Hydro manhole. There is no expectation that the application of a MHP can eliminate all hazards associated with entry into a manhole.

3 Page 3 of 7 The BC Hydro control centre will not take any action to address hazards introduced by the existence of customer-owned cables in a BC Hydro manhole, unless a customer Operating Order exists with specific instruction and requirements. 2.0 MAN HOLE PERMITS Prior to issuance of a MHP, there are no requirements for feeders to be in their normal operating configuration. In manholes where Feeder Cable exists, establishing a MHP will assist in minimizing the effect of additional s being switched on to a cable and will restrict the re energization of a cable after a feeder protection operation. Application of a MHP guarantees that a de-energized feeder, or one that becomes de-energized by its own protection, will not be energized until the Permit holder has been contacted and has approved the energization. For the purposes of re energization, a MHP will be restricted in the same manner as a Live Line permit and will conform to Safety Practice Regulation A circuit with a MHP in effect, may not be paralleled with another circuit, without first notifying the MHP holder. Persons holding MHP must be in radio or telephone contact with the BC Hydro control centre at all times. If continuous communication is not possible to maintain, information may be relayed via a reliable third party. Should a circuit, where a MHP is to be issued, be connected to a BC Hydro owned high voltage automatic transfer scheme, this scheme will be blocked prior to issuance of the MHP. Customer owned auto transfer schemes will not be blocked as part of the MHP process. 3.0 IMPLEMENTATION 3.1 Circuit Identification Responsibility Qualified Worker Responsibility for identifying the circuits that are routed through a manhole resides with the qualified electrical journeyperson that will be performing the work. If the worker is unable to perform an accurate verification on his own, they must consult with the BC Hydro Cable Department. The worker requesting the MHP will identify the work location and the required circuits to the PIC. Example: I (name) am requesting a Manhole Permit for work in manhole MH1234. The feeder cables in this manhole are STN 12F51, STN 12F52 and main trunk circuit UC7F12 on STN 12F54. BC Hydro Control Centre The PIC at the BC Hydro control centre is responsible to identify all directly associated feeder reclosing equipment and those BC Hydro owned schemes capable of automatically transferring to that circuit. 3.2 BC Hydro Control Centre Implementation The BC Hydro control centre will accept verbal, faxed or requests for MHP in real time. permit.requests@bchydro.com Fax:

4 Page 4 of 7 Once the appropriate circuits have been identified by the qualified electrical journeyperson, the BC Hydro control centre will establish conditions for a MHP by: Blocking the source circuit breaker auto reclosing control and tagging the associated control point in the PSSP mimic with a Reclose off tag. Enabling, where Scada control facilities exist, feeder protection fast trip, or Live Line settings at the source circuit breaker. Once done, the PIC will tag the fast trip control with a Reclose Off tag. Placing Man Hole Permit tags on the appropriate supply feeder breakers or switches in the PSSP mimic. Blocking any BC Hydro automatic control scheme that might transfer to a circuit where a MHP is to be issued and tagging that point with a Man Hole Permit tag. Entering the Permit details in the appropriate BC Hydro control centre Desk Log. After the appropriate conditions have been established, a MHP may be issued to the requesting PSSP Category 5 worker. 3.3 Automatically Switched Devices Where BC Hydro owned automatic switch facilities could result in transfer to the circuit where MHP is to be applied, the automatic operation of these facilities must be blocked and tagged appropriately. BC Hydro-Owned Devices, SCADA-Controlled From the BC Hydro Control Centre The PIC will disable automatic control and tag the associated control point in the PSSP mimic with Reclose off tags. The related source switch or breaker electrically nearest to the workers location will be tagged in the PSSP mimic with a Man Hole Permit tag. BC Hydro-Owned Devices, NOT SCADA-Controlled From the BC Hydro Control Centre A BC Hydro worker will be directed by the BC Hydro control centre PIC to disable the appropriate automatic control scheme and apply Reclose Off tags. The BC Hydro control centre PIC will then tag the corresponding PSSP mimic point with a Reclose Off tag(s). The BC Hydro control centre PIC will tag the PSSP mimic for the related source switch or breaker electrically nearest to the workers location with a Man Hole Permit tag(s).

5 Page 5 of REVISION HISTORY This order should also be distributed as follows: Posted on BC Hydro s external website Revised by Revision Date Summary of Revision DSP 04 September 2012 Removed requirements for customer owned auto transfer. K. McCormick 05 December 2012 Section 3.2 corrected cable department, to qualified electrical journeyperson. D. Clayton 14 January 2013 Appendix 1 Added BSC. D. Pochailo 29 Feb 2016 Major revision to remove 1D-23 from the pilot phase. D. Pochailo 19 April 2017 Section 3.2 made the enabling of LL PN for MHP issuance mandatory.

6 APPENDIX 1 CIRCUITS WITH BC HYDRO AUTOMATIC TRANSFER SCHEMES DOO 1D-23 Page 6 of 7 Circuit Location Switch type Notes CSQ 12F615 QE Theatre and Post Office open loop Vista switch vista switch CSQ 12F616 QE Theatre and Post Vista switch Office open loop Vista switch RBW 25F64 Whistler sliding Vista switch centre FCN 25F62 Whistler sliding Vista switch centre RBW 25F66 Whistler Celebration Vista switch Plaza RBW 25F21 Whistler Celebration Vista switch Plaza SPG 12F111 Nat Bailey, Hillcrest Vista switch and Curling SPG 12F68 Nat Bailey, Hillcrest Vista switch and Curling RIM 12F64 Richmond Ice Oval Vista switch and SEA 12F56 Richmond Ice Oval Vista switch and HPN 12F325 Old VANOC Offices, Vista switch Gravely, Vancouver HPN 12F75P Old VANOC Offices, Vista switch Gravely, Vancouver CSQ 12F126 Vancouver Vista switch Convention Centre MUR 12F62P Vancouver Vista switch Convention Centre, Port Shore Power CSQ 12F526 Vancouver Vista switch Convention Centre MUR 12F52Q Vancouver Vista switch Convention Centre, Port Shore Power CSQ 12F211 Port Shore Power Permission to close CSQ 12F111 Port Shore Power Permission to close MUR 12F62P Port Shore Power Permission to close MUR 12F52Q Port Shore Power Permission to close SPG 12F422 Vancouver Athletes Vista switch and Village MUR 12F69 Vancouver Athletes Vista switch 41525, Village and SPG 12F413 Vancouver Athletes Vista switch 41530, Village and Auto switching remote, Normal OFF Auto switching remote, Normal OFF

7 Page 7 of 7 Circuit Location Switch type Notes CSQ 12F623 GM Place (Rogers Vista switch Arena) MUR 12F87 GM Place (Rogers Vista switch Arena) CSQ 12F314 Dual Radial Vista switch CSQ 12F611 Dual Radial Vista switch JLN 12F52Q Park Royal South (PRC) NOR 12F61 PKL 25F54 HRD 25F51 VNT 25F55 VNT 25F64 GLS 25F52 SAL 25F64 Park Royal South (PRC) Fraser Valley Operations (FVO) Southern Interior Operations (SIO) Galiano (GLS) and Saltspring Island (SAL) LTS2 CB 7569, CB 7570, CB 7568 normally closed LTS1 CB 7565, CB 7566, CB 7567 normally closed Auto change-over on LV CB s at customer s stations Auto change-over on LV CB s at customer s stations Auto transfer scheme Mayne, Saturna and Pender Islands Loss of NOR 12F61 automatically adds to JLN 12F52Q. Open a LTS1 or LTS CB to stabilize and maintain. 7D-PRC-01 Loss of JLN 12F52Q automatically adds to NOR 12F61. Open a LTS1 or LTS CB to stabilize and maintain. 7D-PRC-01 Auto switching to alternate circuit can add. Customer can turn off auto transfer (see FVO DOO) Auto switching to alternate circuit can add. Customer can turn off auto transfer (see SIO DOO) Auto switching to alternate circuit can add. To block scheme see DOO 7D-GIL-01

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,

More information

Smart Grid Automation and Centralized FISR

Smart Grid Automation and Centralized FISR Smart Grid Automation and Centralized FISR March 21, 2016 Mike Colby Senior Engineer Distribution Control Center Smart Grid Automation and Centralized FISR Remote Controlled Devices & Communication Distribution

More information

National Certificate in Electricity Supply (Line Mechanic Distribution) (Level 4)

National Certificate in Electricity Supply (Line Mechanic Distribution) (Level 4) NZQF NQ Ref 0874 Version 6 Page 1 of 6 National Certificate in Electricity Supply (Line Mechanic Distribution) (Level 4) Level 4 Credits 118 This qualification is expiring. The last date to meet the requirements

More information

Contact: Michael Parks, Manager, Traffic Engineering Services (905) Council has directed staff to report on implementing a site-specific

Contact: Michael Parks, Manager, Traffic Engineering Services (905) Council has directed staff to report on implementing a site-specific Flower City COMMITTEE DATE: OF COUNCIL Report Committee of Council Standing Committee of the Council of the Corporation of the City of Brampton Date: February 3, 2009 File: Subject: T00TRAF Resident Permit

More information

Requirements for Secondary Voltage Revenue Metering (750 V and less)

Requirements for Secondary Voltage Revenue Metering (750 V and less) Requirements for Secondary Voltage Revenue Metering (750 V and less) To view the latest revision of this document go to: http://www.bchydro.com/ext/metering/ January 28, 2010 Copyright 2008 by BC Hydro.

More information

3.1 Overview of ATCO Electric s URD System Design

3.1 Overview of ATCO Electric s URD System Design Page: 3-1 3.0 URD DESIGN GUIDELINES 3.1 Overview of ATCO Electric s URD System Design The power supply to all single lot underground residential services is through front lot service. Single phase transformers

More information

This specification describes the minimum requirements for a hoist maintenance safeguard (HMS) system for mine hoists.

This specification describes the minimum requirements for a hoist maintenance safeguard (HMS) system for mine hoists. /2.0 PURPOSE This specification describes the minimum requirements for a hoist maintenance safeguard (HMS) system for mine hoists. The HMS system is a means of preventing hoist operation or movement to

More information

Exelon Energy Delivery Interconnection Guidelines for Generators 2 MVA or less

Exelon Energy Delivery Interconnection Guidelines for Generators 2 MVA or less Exelon Energy Delivery Interconnection Guidelines for Generators 2 MVA or less Original: October 31, 2006 Table of Contents: INTRODUCTION and SCOPE... 3 DEFINITIONS... 3 QUALIFICATIONS FOR AN EXPEDITED

More information

Small Generator Interconnection Program Interconnection Technical Requirements

Small Generator Interconnection Program Interconnection Technical Requirements General Program Information What is the purpose of the PGE Small Generator Interconnection Program? How do I initiate a distribution interconnection request for my project? The purpose of our Small Generator

More information

EXCEPTIONS TO NYSRC RELIABILITY RULES

EXCEPTIONS TO NYSRC RELIABILITY RULES 1 NYPA Run Back of EXCEPTIONS RELIABILITY RULES REVISION 1 MAY 11, 2010 Post Contingency Flow on Marcy-New Scotland The post-contingency flow on the Marcy-New Scotland 18 line is allowed to exceed its

More information

SA Power Networks Commissioning Witnessing Checklist

SA Power Networks Commissioning Witnessing Checklist SA Power Networks Commissioning Witnessing Checklist CUSTOMER NAME: SOLAR PV APPROVED CAPACITY: BATTERY APPROVED CAPACITY: kw (AC) kw (AC) OPERATING PHILOSOPHY: MAXIMUM EXPORT: Non-Export/Export kw (AC)

More information

EXCEPTIONS TO RELIABILITY RULES REVISION 4 MAY 8, 2015

EXCEPTIONS TO RELIABILITY RULES REVISION 4 MAY 8, 2015 1 NYPA Run Back of EXCEPTIONS RELIABILITY RULES REVISION 4 MAY 8, 2015 Post Contingency Flow on Marcy-New Scotland The post-contingency flow on the Marcy-New Scotland 18 line is allowed to exceed its LTE

More information

Maharashtra Electricity Regulatory Commission (Renewable Purchase Obligation, Its. Regulations, 2016 STATEMENT OF REASONS

Maharashtra Electricity Regulatory Commission (Renewable Purchase Obligation, Its. Regulations, 2016 STATEMENT OF REASONS MAHARASHTRA ELECTRICITY REGULATORY COMMISSION World Trade Centre, Centre No.1, 13th Floor, Cuffe Parade, Mumbai 400 005 Tel. 022 22163964/65/69 Fax 22163976 Email: mercindia@mercindia.org.in Website: www.mercindia.org.in

More information

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...

More information

DESCRIPTION OF REQUIREMENTS FOR GENERATION SYSTEMS SEEKING TO PROVIDE SYSTEM RESTART SERVICES

DESCRIPTION OF REQUIREMENTS FOR GENERATION SYSTEMS SEEKING TO PROVIDE SYSTEM RESTART SERVICES SYSTEM RESTART SERVICES DESCRIPTION OF REQUIREMENTS FOR GENERATION SYSTEMS SEEKING TO PROVIDE SYSTEM RESTART SERVICES System Management January 2015 INTRODUCTION System Management acting as the segregated

More information

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System This document is intended to be a general overview of PG&E s current technical

More information

TRANSMISSION PLANNING CRITERIA

TRANSMISSION PLANNING CRITERIA CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing

More information

Company Directive STANDARD TECHNIQUE : TP4B/2. Relating to 11kV and 6.6kV Transformer Protection

Company Directive STANDARD TECHNIQUE : TP4B/2. Relating to 11kV and 6.6kV Transformer Protection Company Directive STANDARD TECHNIQUE : TP4B/2 Relating to 11kV and 6.6kV Protection Policy Summary This document describes the detailed requirements for 11kV/415V and 6.6kV/415V distribution transformer

More information

XXXXX. Kokish River Hydroelectric Project. Interconnection Facilities Study and Project Plan

XXXXX. Kokish River Hydroelectric Project. Interconnection Facilities Study and Project Plan XXXXX Kokish River Hydroelectric Project Interconnection Facilities Study and Project Plan March 16, 2011 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2010. All

More information

E/ECE/324/Rev.1/Add.53/Rev.3/Amend.3 E/ECE/TRANS/505/Rev.1/Add.53/Rev.3/Amend.3

E/ECE/324/Rev.1/Add.53/Rev.3/Amend.3 E/ECE/TRANS/505/Rev.1/Add.53/Rev.3/Amend.3 22 February 2017 Agreement Concerning the Adoption of Uniform Technical Prescriptions for Wheeled Vehicles, Equipment and Parts which can be Fitted and/or be Used on Wheeled Vehicles and the Conditions

More information

TECHNICAL ALERT No Rev.01

TECHNICAL ALERT No Rev.01 Technical Alert No. 16-12 Rev.01 Issue Date 20 September 2016 TECHNICAL ALERT No. 16-12 Rev.01 Sulphur Oxides Emission Regulations in China 1. Introduction 1.1. The People s Republic of China s Ministry

More information

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1. Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations

More information

FORTISBC INC. PRUDENCY REVIEW KETTLE VALLEY SUBSTATION EXHIBIT A2 5

FORTISBC INC. PRUDENCY REVIEW KETTLE VALLEY SUBSTATION EXHIBIT A2 5 ALANNA GILLIS ACTING COMMISSION SECRETARY Commission.Secretary@bcuc.com web site: http://www.bcuc.com SIXTH FLOOR, 900 HOWE STREET, BOX 250 VANCOUVER, BC CANADA V6Z 2N3 TELEPHONE: (604) 660 4700 BC TOLL

More information

GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM

GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM Page 1 of 19 Table of Contents 1.0 SCOPE...4 2.0 PURPOSE...4 3.0 LIMITATIONS...5 4.0 GENERAL INTERCONNECTION

More information

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent

More information

2012 Water Consumption Statistics Report. Water Services Department

2012 Water Consumption Statistics Report. Water Services Department 212 Water Consumption Statistics Report Water Services Department Issued: December 213 TABLE OF CONTENTS 212 Water Consumption Statistics Report December 213 212 GVWD Statistics Book - Notes...3 Annual

More information

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND

More information

2015 WDC Disturbance and Protection Standards Overview

2015 WDC Disturbance and Protection Standards Overview NERC Update 2015 WDC Disturbance and Protection Standards Overview Rich Bauer Senior Manager Reliability Risk Management / Event Analysis IEEE PSRC meeting Denver, Co May 12, 2016 2 System Protection and

More information

Water Consumption Statistics Report

Water Consumption Statistics Report Water Consumption Statistics Report Operations and Maintenance Department 29 Edition TABLE OF CONTENTS 29 Water Consumption Statistics Report October 21 SYSTEM AND MUNICIPAL CONSUMPTION 29 GVWD Statistics

More information

AS/NZS 3112:2004 AS/NZS

AS/NZS 3112:2004 AS/NZS AS/NZS 3112:2011 Incorporating Amendment No. 1, 2, and 3 Australian/New Zealand Standard Approval and test specification Plugs and socket-outlets Superseding AS/NZS 3112:2004 AS/NZS 3112:2011 AS/NZS 3112:2011

More information

BC Hydro System 2017 Annual Progress Report

BC Hydro System 2017 Annual Progress Report March 14, 2017 Philip Augustin, P.E. Chair, Technical Studies Subcommittee 503-464-7783 philip.augustin@pgn.com Mr. Enoch Davies WECC Technical Staff 155 North 400 West, Suite 200 Salt Lake City, UT 84103-1114

More information

Spadina Subway Extension Downsview Station to Steeles Avenue Environmental Assessment

Spadina Subway Extension Downsview Station to Steeles Avenue Environmental Assessment Spadina Subway Extension Downsview Station to Steeles Avenue Environmental Assessment APPENDIX Q SUBWAY OPERATIONS REPORT Spadina Subway Extension Downsview Station to Steeles Avenue Environmental Assessment

More information

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1 Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 01, 2017 1 Initial release Newfoundland

More information

OSHA Update. Electric Power Generation, Transmission and Distribution Standard (Part 1910 & 1926)

OSHA Update. Electric Power Generation, Transmission and Distribution Standard (Part 1910 & 1926) OSHA Update Electric Power Generation, Transmission and Distribution Standard (Part 1910 & 1926) 5/14/2014 Significant Changes to the Standards General Training Host Employer & Contractor Responsibilities

More information

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018 Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018 Outlined below are the engineering documents and their associated minimum detail requirements for a Distributed Energy Resource (DER)

More information

Switchgear and Distribution Systems for Engineers and Technicians

Switchgear and Distribution Systems for Engineers and Technicians Switchgear and Distribution Systems for Engineers and Technicians WHAT YOU WILL LEARN: How to identify typical characteristics of an industrial distribution system Become familiar with the main components

More information

MAIN ROTOR BLADE ABRASION STRIP DAILY INSPECTION REQUIREMENTS

MAIN ROTOR BLADE ABRASION STRIP DAILY INSPECTION REQUIREMENTS Service Bulletin PAGE: 1 of 6 SUMMARY: Some operators of Model 369/500/600 Helicopters have experienced delamination or dis-bonding of the on Main Rotor Blades which resulted in a departure of the in-flight.

More information

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.

More information

February 28 th, 2018 UPDATE: Important Product Safety Bulletin Immediate Action Required INSTRUCTIONS FOR FIELD RISK MITIGATION

February 28 th, 2018 UPDATE: Important Product Safety Bulletin Immediate Action Required INSTRUCTIONS FOR FIELD RISK MITIGATION February 28 th, 2018 UPDATE: Important Product Safety Bulletin Immediate Action Required INSTRUCTIONS FOR FIELD RISK MITIGATION Eaton Bussmann series CUBEFuse Indicating TCF DANGER: FAILURE TO WEAR APPROPRIATE

More information

Network Safeworking Rules and Procedures

Network Safeworking Rules and Procedures Network Safeworking Rules and Procedures Setting Back or Propelling on Running Lines Rule Number: 4015 Version 1.0, 31 March 2016 Setting Back or Propelling on Running Lines Rule Number: 4015 Document

More information

To announce the issuance of Piper Service Bulletin 1157A

To announce the issuance of Piper Service Bulletin 1157A TELEDYNE CONTINENTAL AIRCRAFT ENGINE SERVICE BULLETIN Compliance Will Enhance Safety SUBJECT: PIPER SERVICE BULLETIN 1157A Category 3 SB05-11 Technical Portions FAA Approved PURPOSE: COMPLIANCE: MODELS

More information

SERVICE FUEL WARNING PLACARD AND POH INSPECTION

SERVICE FUEL WARNING PLACARD AND POH INSPECTION Piper Aircraft, Inc. 2926 Piper Drive Vero Beach, Florida, U.S.A. 32960 SERVICE NO. 1266 BULLETIN PIPER CONSIDERS COMPLIANCE MANDATORY Date: December 16, 2014 (S) (M) Service Bulletin (SB) 1266 supersedes

More information

EXCEPTIONS TO RELIABILITY RULES Revision 10 August 11, 2017

EXCEPTIONS TO RELIABILITY RULES Revision 10 August 11, 2017 1 NYPA Run Back of EXCEPTIONS RELIABILITY RULES Revision 10 August 11, 2017 Post Contingency Flow on Marcy-New Scotland The post-contingency flow on the Marcy-New Scotland 18 line is allowed to exceed

More information

Bulletin Engineering Department 6911 No. 3 Road, Richmond, BC V6Y 2C1

Bulletin Engineering Department 6911 No. 3 Road, Richmond, BC V6Y 2C1 Bulletin Engineering Department 6911 No. 3 Road, Richmond, BC V6Y 2C1 www.richmond.ca Electric Vehicle Charging Infrastructure Requirements Zoning Bylaw 8500, Section 7.15 No.: ENGINEERING-05 Date: 2018-03-16

More information

PROPOSAL FOR A LIMOUSINE MINIMUM RATES PILOT PROJECT FEBRUARY 2011

PROPOSAL FOR A LIMOUSINE MINIMUM RATES PILOT PROJECT FEBRUARY 2011 PROPOSAL FOR A LIMOUSINE MINIMUM RATES PILOT PROJECT FEBRUARY 2011 NOTE: IN RESPONSE TO INITIAL COMMENTS RECEIVED SINCE FEBRUARY, UPDATES WERE MADE TO THIS PROPOSAL ON MARCH 8, 2011. 1. Context The Board

More information

DEPARTMENT OF MARINE SERVICES AND MERCHANT SHIPPING (ADOMS) REGULATORY AMENDMENTS ENTERING INTO FORCE DURING JANUARY 2017

DEPARTMENT OF MARINE SERVICES AND MERCHANT SHIPPING (ADOMS) REGULATORY AMENDMENTS ENTERING INTO FORCE DURING JANUARY 2017 Information Notice 2016-006 DEPARTMENT OF MARINE SERVICES AND MERCHANT SHIPPING (ADOMS) REGULATORY AMENDMENTS ENTERING INTO FORCE DURING JANUARY 2017 Information regarding the most significant regulatory

More information

MINIBUS SAFETY POLICY STANDARD & PROCEDURES

MINIBUS SAFETY POLICY STANDARD & PROCEDURES MINIBUS SAFETY POLICY STANDARD & PROCEDURES This Policy Standard details the requirements placed on Colleges and Departments to ensure owned, leased and hired minibuses that are driven by staff, students

More information

TERMS AND CONDITIONS OF PARKING AT PALMERSTON NORTH AIRPORT

TERMS AND CONDITIONS OF PARKING AT PALMERSTON NORTH AIRPORT TERMS AND CONDITIONS OF PARKING AT PALMERSTON NORTH AIRPORT 14 December 2017 Palmerston North Airport Limited ( PNAL ) provides travellers and other members of the public with multiple car parking options

More information

Alberta Electric System Operator Needs Identification Document Application. Mowat 2033S Substation

Alberta Electric System Operator Needs Identification Document Application. Mowat 2033S Substation Decision 21781-D01-2016 Alberta Electric System Operator Needs Identification Document Application Facility Applications September 7, 2016 Alberta Utilities Commission Decision 21781-D01-2016: Alberta

More information

ENGINEERING SPECIFICATION

ENGINEERING SPECIFICATION December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References

More information

Suicide Deaths in BC

Suicide Deaths in BC Suicide Deaths in BC 2006-2016 This report summarizes all deaths classified as suicide between January 1, 2006 and December 31, 2016. This includes cases that have been completed and those still under

More information

Wal-Mart Canada Corp.

Wal-Mart Canada Corp. Decision 2010-596 New 500-kW Emergency Back-up Generator for Wal-Mart Perishable Foods Distribution Centre Balzac, Alberta December 17, 2010 ALBERTA UTILITIES COMMISSION Decision 2010-596: Wal-Mart Canada

More information

Alberta Electric System Operator Saleski Transmission Project Needs Identification Document

Alberta Electric System Operator Saleski Transmission Project Needs Identification Document Decision 2013-127 Alberta Electric System Operator Saleski Transmission Project Needs Identification Document ATCO Electric Ltd. Saleski 901S Substation and 144-kV Transmission Line 7L142 Facility Application

More information

EXCEPTIONS TO RELIABILITY RULES Revision 11 February 9, 2018

EXCEPTIONS TO RELIABILITY RULES Revision 11 February 9, 2018 1 NYPA Run Back of EXCEPTIONS RELIABILITY RULES Revision 11 February 9, 2018 Post Contingency Flow on Marcy-New Scotland The post-contingency flow on the Marcy-New Scotland 18 line is allowed to exceed

More information

Guidelines for connection of generators:

Guidelines for connection of generators: Guidelines for connection of generators: Greater than 30 kva, and not greater than 10 MW, to the Western Power distribution network January, 2017. EDM 32419002 / DM 13529244 Page 1 of 14 Contents 1 INTRODUCTION...

More information

National technical rules for vehicles Related Control Command and Signalling Requirements

National technical rules for vehicles Related Control Command and Signalling Requirements National technical rules for vehicles Related Control Command and Signalling Requirements Note: Relevant TSI is Control, Command and Signalling (Commission Regulation (EU) 2016/919 of 27 May 2016 - which

More information

APPLICATION FOR INSTALLATION OF SMALL SCALE EMBEDDED ELECTRICITY GENERATION

APPLICATION FOR INSTALLATION OF SMALL SCALE EMBEDDED ELECTRICITY GENERATION APPLICATION FOR INSTALLATION OF SMALL SCALE EMBEDDED ELECTRICITY GENERATION Work Order No: File Reference: 16/2/1 This application form for the connection of small scale embedded generation is for small

More information

ROLLOVER RIGHTS OF LONG TERM FIRM TRANSMISSION SERVICE

ROLLOVER RIGHTS OF LONG TERM FIRM TRANSMISSION SERVICE ROLLOVER RIGHTS OF LONG TERM FIRM TRANSMISSION SERVICE In this Section: Overview Evaluation of Initial Requests Rollover Request Competing Request Competing Examples 1.0 OVERVIEW Pursuant to Section 2.2

More information

Selective Coordination Requirements

Selective Coordination Requirements Selective Coordination Requirements Background Selective coordination of all upstream overcurrent protective devices in the supplying circuit paths is required by the NEC for a limited number of specific

More information

THE BRANTFORD HOME EXHIBITION 2018 EXHIBITOR KIT

THE BRANTFORD HOME EXHIBITION 2018 EXHIBITOR KIT TO: All Exhibitors FROM: The Jenkins Agency Inc. THE BRANTFORD HOME EXHIBITION 2018 EXHIBITOR KIT DATE: January 2018 RE: The Brantford Home Exhibition, April 20-22, 2018. Brantford Civic Centre, Brantford,

More information

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it. RC SCOPE This test procedure covers the testing and maintenance of Westinghouse RC relays. The Westinghouse Protective Relay Division was purchased by ABB, and new relays carry the ABB label. Refer to

More information

MISSOURI SERVICE AREA

MISSOURI SERVICE AREA MO.P.S.C. SCHEDULE NO. 6 2nd Revised 170 6 1st Revised 170 FROM QUALIFYING FACILITIES 1. *STANDARD RATES FOR PURCHASE The standard rates for purchase from a customer with a design capacity of 100 kw or

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Welcome to the MOL Blitz webinar Locking & Tagging in Mine Hoisting Plants

Welcome to the MOL Blitz webinar Locking & Tagging in Mine Hoisting Plants Welcome to the MOL Blitz webinar Locking & Tagging in Mine Hoisting Plants Thank you for joining us! We will be getting started at 10:00 a.m. EST To access the audio portion of this webinar, please phone:

More information

Network Safeworking Rules and Procedures

Network Safeworking Rules and Procedures Network Safeworking Rules and Procedures s Rule Number: 3025 Version 1.0, 31 March 2016 Temporary Speed Restrictions Rule Number: 3025 Document Control Identification Document title Number Version Date

More information

Decision Blaze Energy Ltd. Application for an Exemption under Section 24 of the Hydro and Electric Energy Act.

Decision Blaze Energy Ltd. Application for an Exemption under Section 24 of the Hydro and Electric Energy Act. Decision 2014-108 Application for an Exemption under Section 24 of the Hydro and Electric Energy Act April 17, 2014 The Alberta Utilities Commission Decision 2014-108: Application for an Exemption under

More information

PAID PARKING INFORMATION LEAFLET

PAID PARKING INFORMATION LEAFLET PAID PARKING INFORMATION LEAFLET INFORMATION ON PAID PARKING CONTROL WITHIN THE DÚN LAOGHAIRE-RATHDOWN COUNTY COUNCIL (DLRCC) ADMINISTRATIVE AREA Q. Why implement Paid Parking Control? The Council s practice

More information

National Certificate in Electricity Supply (Sub Station Maintainer) (Level 4)

National Certificate in Electricity Supply (Sub Station Maintainer) (Level 4) NZQF NQ Ref 1118 Version 2 Page 1 of 7 (Sub Station Maintainer) (Level 4) Level 4 Credits 140 This qualification has been reviewed. The last date to meet the requirements is 31 December 2018. Transition

More information

INTERCONNECTION FACILITIES STUDY REPORT

INTERCONNECTION FACILITIES STUDY REPORT INTERCONNECTION FACILITIES STUDY REPORT Interconnection Request No. TI-12-0217 8 MW Hydropower Generating Facility POI on the Dallas Creek to South Canal 115kV Line in SW Colorado FINAL REPORT February

More information

Application Summary Additional Vehicles & Amendment to Licence

Application Summary Additional Vehicles & Amendment to Licence Application Summary Additional Vehicles & Amendment to Licence Application # 404-16 Applicant Ripe Holdings Inc. Trade Name (s) Ripe Rides, Ripe, Ripe TX, TX Principals PERRICK, Otis GORAYA, Gagan (Ricky)

More information

PETROLEUM PRODUCTS ACT REGULATIONS

PETROLEUM PRODUCTS ACT REGULATIONS c t PETROLEUM PRODUCTS ACT REGULATIONS PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to February 1, 2004. It is intended

More information

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No. September, 1990 Supersedes Descriptive Bulletin 41-100, pages 1-4, dated June, 1989 Mailed to: E, D, C/41-100A Hi-Lo co induction-disc type overcurrent relays are activated when the current in them exceeds

More information

STUDENT TRANSPORTATION

STUDENT TRANSPORTATION Page 1 of 6 Operational Procedure 380 Background STUDENT TRANSPORTATION Although the transportation of students is no longer a requirement of the School Act, School District 72 provides an efficient and

More information

Actsafe Safety Bulletin #23 WORKING WITH LIGHTING SYSTEMS AND OTHER ELECTRICAL EQUIPMENT

Actsafe Safety Bulletin #23 WORKING WITH LIGHTING SYSTEMS AND OTHER ELECTRICAL EQUIPMENT WORKING WITH LIGHTING SYSTEMS AND OTHER ELECTRICAL EQUIPMENT This Safety Bulletin is intended to assist all production personnel with understanding the Regulations and to warn of potential electrical and

More information

Functional Specification Revision History

Functional Specification Revision History Functional Specification Revision History Revision Description of Revision Author Date B0 For comments Yale Zhou January 26, 2016 B1 Updated as per comments Yale Zhou February 1, 2016 Final issuance Yale

More information

European Aviation Safety Agency

European Aviation Safety Agency TCDS EASA.BA.028 Page 1 / 7 European Aviation Safety Agency EASA TYPE-CERTIFICATE DATA SHEET Cameron R Series Rozière Balloons - Manned Free Rozière Balloons Type Certificate Holder: CAMERON BALLOONS LTD.

More information

A Guide to the medium General Service. BC Hydro Last Updated: February 24, 2012

A Guide to the medium General Service. BC Hydro Last Updated: February 24, 2012 A Guide to the medium General Service Conservation Rate BC Hydro Last Updated: February 24, 2012 Executive summary The way Medium General Service (MGS) accounts pay for electricity is changing. MGS is

More information

Licence Application Decision

Licence Application Decision Licence Application Decision Limousine Additional Vehicles Application # AV167-15 Applicant Luxury Life Limousine Inc. Trade Name (s) Luxury Life Limousine Principals JHOOTY, Vikrambir JHOOTY, Jasbir Singh

More information

On June 11, 2012, the Park Board approved the installation of three electric vehicle charging stations along Beach Avenue.

On June 11, 2012, the Park Board approved the installation of three electric vehicle charging stations along Beach Avenue. January 8, 2017 TO: Park Board Chair and Commissioners FROM: General Manager Vancouver Board of Parks and Recreation SUBJECT: Electric Vehicle Charging Stations New Park Board Locations RECOMMENDATION

More information

To: Owners, Technical Managers, Deputy Registrars, Fleet Managers, Surveyors, Recognised Organisations

To: Owners, Technical Managers, Deputy Registrars, Fleet Managers, Surveyors, Recognised Organisations Circular 169/ 2018 To: Owners, Technical Managers, Deputy Registrars, Fleet Managers, Surveyors, Recognised Organisations Subject: MARPOL Annex VI Fuel Oil Consumption Data Collection Date: 12th April

More information

2020 GLOBAL SULPHUR LIMIT HISTORY, CURRENT STATUS, AND THE INTERNATIONAL MARITIME ORGANIZATION S (IMO S) WORK PLAN FOR EFFECTIVE IMPLEMENTATION

2020 GLOBAL SULPHUR LIMIT HISTORY, CURRENT STATUS, AND THE INTERNATIONAL MARITIME ORGANIZATION S (IMO S) WORK PLAN FOR EFFECTIVE IMPLEMENTATION 2020 GLOBAL SULPHUR LIMIT HISTORY, CURRENT STATUS, AND THE INTERNATIONAL MARITIME ORGANIZATION S (IMO S) WORK PLAN FOR EFFECTIVE IMPLEMENTATION Marshall Islands Registry and Korean Industry Stakeholders

More information

201F Fuel Pump Valve Assembly Leakage

201F Fuel Pump Valve Assembly Leakage 2900 Selma Highway Montgomery, AL 36108 USA Tel: 334-386-5400 Fax: 334-386-5450 201F Fuel Pump Valve Assembly Leakage 1. Planning Information A. Effectivity (1) Hartzell Engine Technologies LLC (HET) 201F

More information

IN THE MATTER OF the Ontario Energy Board Act, 1998, S.O. 1998, c.15, Schedule B;

IN THE MATTER OF the Ontario Energy Board Act, 1998, S.O. 1998, c.15, Schedule B; Ontario Energy Board Commission de l énergie de l Ontario IN THE MATTER OF the Ontario Energy Board Act, 1998, S.O. 1998, c.15, Schedule B; AND IN THE MATTER OF an Application by Thunder Bay Hydro Electricity

More information

Regulatory update on implementation of the 0.50% sulphur limit for international shipping

Regulatory update on implementation of the 0.50% sulphur limit for international shipping Regulatory update on implementation of the 0.50% sulphur limit for international shipping Marshall Islands Quality Council (MIQC), 19 April 2018 Trinity House, London Dr Edmund Hughes Marine Environment

More information

RULES ENABLING THE NET- METERING PROGRAM FOR RENEWABLE ENERGY

RULES ENABLING THE NET- METERING PROGRAM FOR RENEWABLE ENERGY RULES ENABLING THE NET- METERING PROGRAM FOR RENEWABLE ENERGY Outline 1. Introduction 2. Legal Basis 3. Scope, Applicability & Qualification 4. Interconnection Set-Up 5. Pricing Methodology 6. Net-Metering

More information

IOWA MOLD TOOLING CO., INC. BOX 189, GARNER, IA TEL: IMT PART NUMBER

IOWA MOLD TOOLING CO., INC. BOX 189, GARNER, IA TEL: IMT PART NUMBER CRANE LOG CALENDAR YEAR CRANE MODEL Daily Inspections Weekly Inspections Monthly Inspections Lubrication Record Maintenance Record Damage & Repair Record Modification Record Reference Specifications CRANE

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION IEC TS 62257-9-2 First edition 2006-10 Recommendations for small renewable energy and hybrid systems for rural electrification Part 9-2: Microgrids IEC 2006 Copyright - all rights

More information

ELECTRICAL GROUNDING SAFETY PROGRAM

ELECTRICAL GROUNDING SAFETY PROGRAM ELECTRICAL GROUNDING SAFETY PROGRAM PURPOSE / SCOPE The purpose of this program is to ensure the proper installation, maintenance, inspection, and testing of equipment grounding conductors on construction

More information

This qualification has been reviewed. The last date to meet the requirements is 31 December 2020.

This qualification has been reviewed. The last date to meet the requirements is 31 December 2020. NZQF NQ Ref 1117 Version 5 Page 1 of 7 National Certificate in Electricity Supply (Field Switcher) (Level 4) with optional strands in Distribution Networks, Transmission Networks, and Operational and Co-ordination

More information

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Decision D ATCO Electric Ltd. Decommissioning of Transmission Line 6L79. October 18, 2016

Decision D ATCO Electric Ltd. Decommissioning of Transmission Line 6L79. October 18, 2016 Decision 21481-D01-2016 October 18, 2016 Alberta Utilities Commission Decision 21481-D01-2016 Proceeding 21481 Application 21481-A001 October 18, 2016 Published by the: Alberta Utilities Commission Fifth

More information

TORONTO TRANSIT COMMISSION REPORT NO.

TORONTO TRANSIT COMMISSION REPORT NO. Revised: March/13 TORONTO TRANSIT COMMISSION REPORT NO. MEETING DATE: March 26, 2014 SUBJECT: COMMUNITY BUS SERVICES ACTION ITEM RECOMMENDATION It is recommended that the Board not approve any routing

More information

Train Safety Systems. Railway Group Standard GM/RT2185 Issue Two Date December 2001

Train Safety Systems. Railway Group Standard GM/RT2185 Issue Two Date December 2001 Train Safety Systems Synopsis This document defines the requirements for train safety systems to enable safe operation of trains on Railtrack controlled infrastructure. Signatures removed from electronic

More information

HydroGenerations PROGRAM HANDBOOK

HydroGenerations PROGRAM HANDBOOK HydroGenerations PROGRAM HANDBOOK TABLE OF CONTENTS Please ensure you are reading the most recent version of this handbook by visiting the NV Energy website, www.nvenergy.com/hydro. Contents HydroGenerations

More information

SUBJECT: Kelly Aerospace Energy Systems Service Bulletin 038 A ES TCM P/N Inspection of Slip Ring End Housings for Cracks

SUBJECT: Kelly Aerospace Energy Systems Service Bulletin 038 A ES TCM P/N Inspection of Slip Ring End Housings for Cracks TELEDYNE CONTINENTAL AIRCRAFT ENGINE SERVICE BULLETIN Contains Important Information Pertaining to Your Aircraft Engine. Compliance Will Enhance Safety Category 3 Technical Portions FAA Approved SUBJECT:

More information

If you have any questions, please do not hesitate to contact the Board's Legal Counsel, Ms. Jacqui Glynn, via or (709)

If you have any questions, please do not hesitate to contact the Board's Legal Counsel, Ms. Jacqui Glynn, via or (709) NEWFOUNDLAND AND LABRADOR BOARD OF COIIIIISSIONERS OF PUBLIC UTILITIES 120 Torbay Road, P.O. Box 21040, St. John's, Newfoundland and Labrador, Canada, AlA 5B2 E-mail: gyoung@nlh.nl.ca 2014-0-12 Mr. Geoffiey

More information

Decision (Errata) Access Pipeline Inc. Errata to Decision Temporary Generation at Smoky Lake Pump Station.

Decision (Errata) Access Pipeline Inc. Errata to Decision Temporary Generation at Smoky Lake Pump Station. Decision 2011-424 (Errata) Access Pipeline Inc. Errata to Decision 2011-424 Temporary Generation at Smoky Lake Pump Station January 4, 2012 The Alberta Utilities Commission Decision 2011-424 (Errata):

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Network. ENMAX Power Corporation Network Planning & Design November 4, 2011

Network. ENMAX Power Corporation Network Planning & Design November 4, 2011 Network ENMAX Power Corporation Network Planning & Design November 4, 2011 ENMAX Fast Facts Service area of 1,044 square kilometers 1,738MVA Peak load (2009) Transmission System 266 km overhead 15km underground

More information

d. Note: LPG conversions are acceptable providing the relevant Vehicle Declaration is completed by the HSVOC Registrar.

d. Note: LPG conversions are acceptable providing the relevant Vehicle Declaration is completed by the HSVOC Registrar. Title: Historic & Classic Vehicles Registration Rules Number of Pages: 5 Reviewed By: Michael Benton Issue Date: 9 th November 2018 UNCONTROLLED IF PRINTED Replaces Issue: 12th February 2017 1. BACKGROUND

More information