LIFT STATION 11 ONE-LINE DIAGRAM
|
|
- Roberta Cameron
- 5 years ago
- Views:
Transcription
1 LAC JOB : OSG-D-ELEC06.DWG LIFT STATION 11 ONE-LINE DIAGRAM DWG : SHEET : E
2 NEW NEW GENERATOR PAD BOLLARD BOLLARD WETWELL ACCESS HATCH WETWELL OUTLINE HANDHOLE SEWER MANHOLE LIFT STATION 11 ELECTRICAL PLAN LIFT STATION YARD HYDRANT D HOTBOX MAIN SERVICE DISCONNECT, TO BE REPLACED. SEE DWG E18 FOR DETAIL. FIELD FIT CONDUIT RISERS UNDER ENCLOSURE LIGHT POLE MAIN CONTROL ENCLOSURE POWER DISTRIBUTION AND SIGNAL PLAN CONCRETE PAD BOLLARD NEW AUTOMATIC TRANSFER SWITCH, FOR DETAIL SEE DWG E17 B ELECTRICAL NOTES EDGE OF PAVED AREA 1. SEE DWG E17 FOR CONDUIT AND WIRE SCHEDULE. 2. CONTRACTOR SHALL COORDINATE WITH ELECTRICAL UTILITY TO DE-ENERGIZE ELECTRICAL SERVICE DURING SERVICE DISCONNECT SWITCH REPLACEMENT. ALL UTILITY COORDINATION AND COSTS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. LAC JOB : OSG-D-ELEC06.DWG DWG : SHEET : E
3 REMOVE MANUAL TRANSFER SWITCH LOCATED ON INTERIOR OF MAIN CONTROL CABINET UTILITY METER, TO BE REPLACED, SEE DWG NO E18 FOR DETAIL. 36" MIN. SERVICE ENTRANCE DISCONNECT SWITCH TO BE REMOVED AND REPLACED WITH NEW SWITCH. MODIFY OR REPLACE CONDUITS AND CONDUCTORS TO ACCOMMODATE THE NEW SWITCH. SEE DWG E18 FOR DETAIL. REMOVE GENERATOR RECEPTACLE. AND WIRING. PATCH PENETRATIONS WITH BOLTED 1/8 INCH TYPE 304 SS PLATE AS NECESSARY. INSTALL NEW CONDUCTORS IN CONDUIT SS UNISTRUT, TYP. UNISTRUT FOOTING, TYP. B 6'-0" LIFT STATION 11 GENERATOR AND ATS DIAGRAM GENERATOR AND ATS DIAGRAM ATS FED BY THE UTILITY DISCONNECT AND STATION FED BY THE UTILITY DISCONNECT AND UTILITY DISCONNECT TO THE RIGHT OF ENCLOSURE GENERATOR EMERGENCY STOP INSIDE GENERATOR DISCONNECT BREAKER INSIDE LAC JOB : OSG-D-ELEC06.DWG DWG : SHEET : E
4 6' MAX LIFT STATION 11 METER AND S.E.D. MODIFICATIONS DISCONNECT AND METER BASE LAYOUT NEW DISCONNECT AND METER BASE LAYOUT REROUTE CONDUCTORS: - REMOVE FEEDERS CONNECTED TO THE DISCONNECT. - EXTEND CONDUIT "S" - INSTALL NEW METER BASE (LOWER THAN THE METER BASE) AND RECONNECT TO THE NEW METER BASE - PLUG AND SEAL THE OLD PENETRATIONS USING TYPE 304 SS PLATE. SECURE PLATE AND MAKE WEATHERPROOF. METER AND S.E.D. MODIFICATIONS NOT TO SCALE LAC JOB : OSG-D-ELEC06.DWG DWG : SHEET : E
5 LAC JOB : OSG-D-ELEC07.DWG LIFT STATION 17 ONE-LINE DIAGRAM DWG : SHEET : E
6 CONTINUES TO UTILITY TRANSFORMER SEE DWG C10 FOR DETAIL HOTBOX HANDHOLE SECONDARY SERVICE CONDUIT, TO BE ABANDONED IN PLACE WATER METER HANDHOLE UNISTRUT SUPPORTS TELEMETRY PANEL MAIN SERVICE DISCONNECT, TO BE REMOVED ENCLOSURE YARD HYDRANT UTILITY METER, TO BE REMOVED NEW AUTOMATIC TRANSFER SWITCH MANUAL TRANSFER SWITCH, TO BE REMOVED D DRY WELL OUTLINE JUNCTION VAULT FIELD FIT CONDUIT RISERS UNDER NEW AND ENCLOSURES NEW UTILITY METER NEW MAIN SERVICE DISCONNECT NEW CONCRETE PAD EXTENSION. NEW UNISTRUT SUPPORT, FOR DETAIL SEE DWG E21 B NEW GENERATOR PAD NEW STANDBY GENERATOR ELECTRICAL NOTES 1. INTERCEPT CONDUIT FEEDING THE PUMP CONTROL PANEL IN DRY WELL ABOVE GRADE WITH NEW CONDUIT. INSTALL JUNCTION BOX TO MAKE CONNECTION. INSTALL NEW CONDUCTORS IN NEW AND CONDUIT. 2. SUPPORT NEW CONDUIT ON AND NEW UNISTRUT SUPPORT. 3. ROUTE CONDUIT ABOVE GRADE AND PENETRATE DRYWELL WALL 2 ABOVE GRADE. SEAL CONDUIT PENETRATION WATER TIGHT. 4. SEE DWG E21 FOR CONDUIT AND WIRE SCHEDULE. 5. CONTRACTOR SHALL COORDINATE WITH ELECTRICAL UTILITY TO DE-ENERGIZE ELECTRICAL SERVICE DURING SECONDARY POWER AND SERVICE DISCONNECT SWITCH REPLACEMENT. SECONDARY POWER CONDUIT SIZE, TYPE AND MATERIALS SHALL BE PER UTILITY STANDARDS. ALL UTILITY COORDINATION AND COSTS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. LIFT STATION 17 ELECTRICAL PLAN CONCRETE APRON LAC JOB : OSG-D-ELEC07.DWG POWER DISTRIBUTION AND SIGNAL PLAN DWG : SHEET : E
7 UTILITY METER ON REAR OF UNISTRUIT TO BE REMOVED MAXIMUM HEIGHT OF METER BASE SHALL BE 6"-0" ABOVE GRADE REMOVE MANUAL TRANSFER SWITCH AND GENERATOR RECEPTACLE ON REAR OF UNISTRUIT ENCLOSURE, DO NOT DISTURB TELEMETRY PANEL SERVICE ENTRANCE DISCONNECT SWITCH ON REAR OF UNISTRUT TO BE REMOVED. 7'-0" APPROX. 1-1/2" LR 1-1/2" PULLING ELL SS UNISTRUT, TYP. 1-1/2" LL 6'-0" NEW 6"X6" JUNCTION BOX CONDUITS CONTINUE TO BREAKER PANEL LOCATED IN DRY WELL CL2 ANALYZER PANEL LIFT STATION 17 GENERATOR AND ATS DIAGRAM ATS FED BY THE UTILITY DISCONNECT AND STATION FED BY THE UTILITY DISCONNECT AND UTILITY DISCONNECT B CONDUIT CONTINUES TO UTILITY TRANSFORMER UNISTRUT FOOTING, TYP. 3/4" PREMOLDED JOINT FILLER GENERATOR AND ATS DIAGRAM 3/4" PREMOLDED JOINT FILLER 3/4" PREMOLDED JOINT FILLER CONDUIT CONTINUES TO 2-INCH PVC PUMP CONTROL PANEL CONDUIT LOCATED IN DRY WELL LAC JOB : OSG-D-ELEC07.DWG GENERATOR EMERGENCY STOP INSIDE GENERATOR DISCONNECT BREAKER INSIDE DWG : SHEET : E
8 ɸ LAC JOB : OSG-D-ELEC08.DWG LIFT STATION 24 ONE-LINE DIAGRAM DWG : SHEET : E
9 BOLLARDS PVC RISER, TYP. NEW NEW GENERATOR PAD OUTLINE OF BELOW GRADE HOLDING TANK WETWELL ACCESS HATCH NEW AUTOMATIC TRANSFER SWITCH, FOR DETAIL SEE DWG E24 B JUNCTION BOX WETWELL OUTLINE MAIN SERVICE DISCONNECT, TO BE REPLACED. SEE DWG E25 FOR DETAIL. CONCRETE PAD BOLLARD LIFT STATION 24 ELECTRICAL PLAN STUBOUT CONDUIT 2 FEET BEYOND CONCRETE PAD AND STAKE FOR FUTURE USE. BOLLARD BOLLARD FIELD FIT CONDUIT RISERS UNDER ENCLOSURE D LAC JOB : OSG-D-ELEC08.DWG ELECTRICAL NOTES 1. SEE DWG E24 FOR CONDUIT AND WIRE SCHEDULE. 2. CONTRACTOR SHALL COORDINATE WITH ELECTRICAL UTILITY TO DE-ENERGIZE ELECTRICAL SERVICE DURING SERVICE DISCONNECT SWITCH REPLACEMENT. ALL UTILITY COORDINATION AND COSTS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. MAIN CONTROL PANEL POWER DISTRIBUTION AND SIGNAL PLAN UTILITY METER YARD HYDRANT HOTBOX DWG : SHEET : E
10 REMOVE MANUAL TRANSFER SWITCH LOCATED ON INTERIOR OF MAIN CONTROL CABINET UTILITY METER REMOVE GENERATOR RECEPTACLE. AND WIRING. PATCH PENETRATIONS WITH BOLTED 1/8 INCH TYPE 304 SS PLATE AS NECESSARY. 36" MIN. SERVICE ENTRANCE DISCONNECT SWITCH TO BE REMOVED AND REPLACED WITH NEW SWITCH. MODIFY OR REPLACE CONDUITS AND CONDUCTORS TO ACCOMMODATE THE NEW SWITCH. SS UNISTRUT, TYP. UNISTRUT FOOTING, TYP. B 6'-0" LIFT STATION 24 GENERATOR AND ATS DIAGRAM GENERATOR AND ATS DIAGRAM ATS FED BY THE UTILITY DISCONNECT AND STATION FED BY THE UTILITY DISCONNECT AND UTILITY DISCONNECT TO THE RIGHT OF ENCLOSURE GENERATOR EMERGENCY STOP INSIDE GENERATOR DISCONNECT BREAKER INSIDE LAC JOB : OSG-D-ELEC08.DWG DWG : SHEET : E
11 LAC JOB : OSG-D-ELEC08.DWG LIFT STATION 24 METER AND S.E.D. MODIFICATIONS DISCONNECT AND CONDUIT "R" LAYOUT NEW DISCONNECT AND NEW CONDUIT "R" LAYOUT - RE-USE 240V FEEDERS AND METER BASE - INSTALL NEW THE CONDUIT ( R ) AND CONDUCTORS BETWEEN THE METER BASE AND DISCONNECT - INSTALL NEW DISCONNECT S.E.D. AND CONDUIT MODIFICATIONS NOT TO SCALE DWG : SHEET : E
12 LAC JOB : OSG-D-ELEC09.DWG LIFT STATION 27 ONE-LINE DIAGRAM DWG : SHEET : E
13 NEW BOLLARD, TYP. LIGHT POLE EDGE OF ROADWAY JUNCTION BOX SALVAGED STANDBY GENERATOR NEW GENERATOR PAD JUNCTION BOX GENERATOR NAMEPLATE SALVAGED GENERATOR, PROVIDED BY CITY. TO BE INSTALLED ON NEW GENERATOR PAD. GENERATOR IS 115" LONG, 29" WIDE, 65" TALL. CONTRACTOR SHALL MOVE THE GENERATOR FROM ITS CURRENT LOCATION TO THE SITE. WETWELL ACCESS HATCH FIELD FIT CONDUIT RISERS UNDER ENCLOSURE NEW UTILITY METER D DESCRIPTION PLOT DATE: REVIEWED: DATE SAVE DATE: 1. SEE DWG E28 FOR CONDUIT AND WIRE SCHEDULE. 2. CONTRACTOR SHALL COORDINATE WITH ELECTRICAL UTILITY TO DE-ENERGIZE ELECTRICAL SERVICE DURING SERVICE DISCONNECT SWITCH REPLACEMENT. ALL UTILITY COORDINATION AND COSTS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. GENERATOR POWER DISTRIBUTION AND SIGNAL PLAN ELECTRICAL NOTES ENGINEER: PVC RISER, TYP. Apr 17, 2019 NEW AUTOMATIC TRANSFER SWITCH LAC MAIN CONTROL PANEL CONCRETE PAD OSG-D-ELEC09.DWG JOB : YARD HYDRANT BY REVIEW NEW SERVICE DISCONNECT LIFT STATION 27 ELECTRICAL PLAN WETWELL OUTLINE CITY CITY OF OF LACEY LACEY ON-SITE ON-SITE LIFT LIFT STATION STATION GENERATORS GENERATORS SITE FENCE 0" 1" DWG : SHEET : E " 47
14 NEW AUTOMATIC TRANSFER SWITCH LOCATED ON THE BACK OF THE MAIN CONTROL CABINET ENCLOSURE SERVICE ENTRANCE DISCONNECT SWITCH TO BE REMOVED AND REPLACED WITH NEW SWITCH. MODIFY OR REPLACE CONDUITS AND CONDUCTORS TO ACCOMMODATE THE NEW SWITCH. UTILITY METER BASE, TO BE REMOVED AND REPLACED WITH NEW UTILITY METER BASE. LAC JOB : LIFT STATION 27 GENERATOR AND ATS DIAGRAM GENERATOR AND ATS DIAGRAM ATS FED BY THE UTILITY DISCONNECT AND STATION FED BY THE UTILITY DISCONNECT AND UTILITY DISCONNECT TO THE RIGHT OF ENCLOSURE GENERATOR EMERGENCY STOP INSIDE GENERATOR DISCONNECT BREAKER INSIDE OSG-D-ELEC09.DWG DWG : SHEET : E
15 1-1/2" PULLING ELL 1-1/2" LL LIFT STATION 27 CONTROL PANEL MODIFICATION 1-1/2" LR 2-INCH CONDUIT CONTINUES TO UTILITY TRANSFORMER 2-INCH CONDUIT CONTINUES TO UTILITY TRANSFORMER 1-1/2" PULLING ELL LAC JOB : OSG-D-ELEC09.DWG CONTROL PANEL MODIFICATIONS DWG : SHEET : E
UTILITY CROSSING DETAIL
6" OF CSBC COMPACTED TO A FIRM AND UNYIELDING CONDITION. NOTE: - SILT FENCE SHALL CONFORM TO 8-01.3(9)A - SILT FENCES SHALL BE INSTALLED ALONG CONTOUR WHENEVER POSSIBLE. - POST SPACING MAY BE INCREASED
More informationCOMMERCIAL QUICK REFERENCE
COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR
More informationSECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS
CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATION 100 KVA AND LARGER (CONCRETE PADS ONLY) 27.05-01 CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATION
More informationFor Conduit Inspections
Underground Conduit Standards - Table of Content 5/8/2017 Section S22 Underground Conduit Standard Index: Description: 00 Table of Content 01 General Notes 02 Definition of Terms 03 Primary Riser Conduit
More information10 Commercial, Industrial, Agricultural Services
10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three
More information7 Single Family Service
7 Single Family Service 7. General The location of the service entrance on the Customer s premises is an important consideration. For clearance and location information see section 5 (Clearances). Consult
More informationCommercial Electric Policy
Commercial Electric Policy 7/19/16 1 Table of Contents General Information..3 Construction.3 Ownership.4 Multi-Unit/Multi-Service Buildings....4 Secondary Termination Enclosures.4 Meter Bases.5 Temporary
More informationELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016
UTILITY/CATV SERVICES CHAPTER 9 900. GENERAL A. Alliant Energy receives many requests for electric service from other utilities; telephone, telecommunications companies, cable television, the Department
More informationD9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE
SOURCE 20V 240V STUD (PER NEC) A customer supplied and installed teaser wire is required from the neutral lug to a 5th terminal mounted on the left side of the meter block between the line and load terminals.
More informationCommercial Electric Service Handbook
Commercial Electric Service Handbook January 2011 CONTACTS Clark Public Utilities: Website........................................... www.clarkpublicutilities.com Construction Services department (To initiate
More informationCITY OF WEST PALM BEACH
REVISION: OCT. 2018 SUBMERSIBLE LIFT STATION - WET WELL SECTION VIEW SLS-2 WETWELL DATA PUMP/ELECTRICAL DATA REVISION: OCT. 2018 SUBMERSIBLE LIFT STATION - REQUIRED DATA SLS-3 PUMP TEST / START-UP FORM
More informationAGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS
Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This
More informationRESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS
SECTION VI SERVICE REQUIREMENTS This section discusses the requirements for establishing electric service to new residential subdivisions in Palo Alto. Subdivisions are normally constructed on dedicated
More informationLift Station Design Standards and Details. Summary of Revisions
Lift Station Design Standards and Details Summary of Revisions April 2017 Updates Standard Detail SLS 19 SUBMERSIBLE LIFT STATION GROUDING PLAN & S Removed Barbed Wire from FENCE GROUNDING. TYPICAL LIFT
More informationClark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally.
This page left blank intentionally. 38 Chapter 4: Commercial Metering / January 2011 APPENDIX Glossary Approval Acceptable to the authority having jurisdiction. Associated equipment As related to metering
More informationBID SPECIFICATIONS 2018 TERMINAL BUILDING STANDBY GENERATOR PROJECT
BID SPECIFICATIONS 2018 TERMINAL BUILDING STANDBY GENERATOR PROJECT The County of Hancock, Maine is seeking bids from qualified firms for the purchase and installation of at least a 20KW backup generator
More informationPERMANENT RESIDENTIAL UNDERGROUND SERVICE
CITY OF RICHLAND ENERGY SERVICES DEPARTMENT 505 Swift Boulevard, MS-21 Richland, WA 99352 Telephone (509) 942-7403 Fax (509) 942-7405 PERMANENT RESIDENTIAL UNDERGROUND SERVICE A. INTRODUCTION This guide
More informationAssociated equipment As related to metering equipment: such as the current transformers, CT wiring and test switches.
APPENDIX Glossary Approval Acceptable to the authority having jurisdiction. Assessor s Parcel Number (APN) Identifying number assigned by the county assessor s office to each taxable building lot in the
More informationENTRANCE EQUIPMENT ER D PAGE 1 OF 5
PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument
More informationApproved Contractor Construction e-guide Residential Commercial
Approved Contractor Construction e-guide Residential Commercial Clark Public Utilities PO Box 8900 Vancouver, WA 98668 (PAGE 2) TABLE OF CONTENTS PAGE Trenching 3 Wire 8 Single-Phase Transformer Set 13
More information320A Single Phase URD Meter Loop Installations
320A Single Phase URD Meter Loop Installations Location: The meter loop shall be mounted on the side of the pedestal facing the consumer's lot. (The side being one of the four flat surfaces of the pedestal
More information9. Non-Residential Services (Commercial, Industrial, and Agricultural)
Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect
More informationPretest Module 24 Three-phase Service Entrance
Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?
More informationSALEM CITY POWER ELECTRICAL REQUIREMENTS & STANDARDS MANUAL
SALEM CITY POWER DEPARTMENT TABLE OF CONTENTS Section 1 General Requirements Purpose...1.1 Codes and Ordinances...1.1 Changes or Conflicts in Requirements and Guidelines...1.1 Application for Service...1.2
More informationTABLE OF CONTENTS. Important Notices Underground Plant Protection Information. Commercial/Industrial Information Sheet
DRAWING NUMBER INTRODUCTORY INFORMATION Important Notices Underground Plant Protection Information Code Clearances Commercial/Industrial Information Sheet Work Management Customer Projects Engineering
More informationUNDERGROUND SERVICES - SECONDARY
UNDERGROUND SERVICES - SECONDARY Contents - Underground Services... U-1 General Requirements for Underground Service...U-2 Names of Parts for Underground Service... U-3 Service Termination in a Service
More informationELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016
DISTRIBUTED GENERATION CHAPTER 5 500. SCOPE This chapter includes distributed or customer-owned generation connected in parallel and operating with Alliant Energy s electric distribution system. For all
More informationBID ITEM ESTIMATED UNIT TOTAL UNIT TOTAL UNIT TOTAL NO. QUANTITY UNIT ITEM COST COST COST COST COST COST
PAGE 1 BID OPENING: AUGUST 11, 2011 ENGINEER'S ESTIMATE: $3,108,320.60 CONTRACT NO.110269 SABINO CANYON AND TANQUE VERDE INTERSECTION IMPROVEMENTS *FOR A MORE DETAILED ITEM DESCRIPTION* *REFER TO PROPOSAL
More informationMetering and Service Installation:
Table of Contents 1. Metering Installation Requirements, General... 1 2. Type of Service... 2 3. Definitions... 2 4. Who Provides Metering Equipment?... 2 5. Establishment of Service... 2 6. Meter Access...
More informationSPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION
Roseville Electric SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION REVISED 04/25/18 Specifications for Residential Construction Revision List REVISION Date Page No. Description 03/20/00 6.1-6.2 Added Armorcast
More information34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE
4. METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4.-4 4. SELF-CONTAINED METERING, SINGE-PHASE INSTALLATION DETAILS /4 VOLT SINGLE-PHASE UNDERGROUND RESIDENTIAL SERVICE AND METER
More informationUNDERGROUND CONDUIT SYSTEMS for Primary and Secondary Conductors (Rev. 7)
April 2018 UNDERGROUND CONDUIT SYSTEMS for Primary and Secondary Conductors (Rev. 7) Engineering & Asset Management Policy No. 242 Rocky Mountain Power Utah Wyoming Idaho This policy and related documents
More informationDiane Lindsey CenterPoint Energy SWEDE 2010
Diane Lindsey CenterPoint Energy SWEDE 2010 Agenda Background Pre Hurricane Ike Dredge Evaluation Aftermath of Hurricane Ike in 2008 Temporary West Galveston Mobile Substation Post Hurricane Ike Dredge
More informationExisting 400A Circuit Breaker For B Secondary Chill Water Pump. Existing Single 2.5 Conduit. Reuse As Much As Practical
New A Secondary Chill / 60V /36A Fused Disconnect For A Secondary Chill and Flex New B Secondary Chill / 60V / 36A B Secondary Chill Single 2.5 Conduit. Install New Additional 2.5 R.S.G. Conduit From 00A
More informationCustomer Requirements Downtown Secondary Network Service
Application This standard describes the limitations and requirements for receiving service from the Tacoma Power secondary network system within the City of Tacoma downtown core area. In This Standard
More informationEngineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes
Engineering Service Specifications Commercial Single-Phase Current Transformer Metering Schemes Specifications for Commercial Underground Current Transformer Metering Requirements for a Single-Phase Customer
More informationThe information found in this document are general guidelines that may be used to aid in the preparation of your service request proposal.
The information found in this document are general guidelines that may be used to aid in the preparation of your service request proposal. Please be advised that depending on the specific needs and actual
More informationPUBLIC UTILITY DISTRICT NO. 1 OF LEWIS COUNTY METERING SPECIFICATIONS
PUBLIC UTILITY DISTRICT NO. 1 OF LEWIS COUNTY METERING SPECIFICATIONS 1. General Metering Requirements a. Interpretation The District s metering requirements shall not be interpreted to conflict with the
More informationUNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service.
UNDERGROUND SERVCE tems to consider f your trenching route has to be dug by hand, or if a cable must be installed under a paved surface, additional charges apply. f your service cable has to be moved later
More informationSPECIFICATIONS FOR COMMERCIAL CONSTRUCTION
Roseville Electric SPECIFICATIONS FOR COMMERCIAL CONSTRUCTION REVISED 06/28/18 Commercial Construction Specifications Revision List REVISION Date Page No. Description 03/01/00 4.2-4.3 Changed leveling
More informationRESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS
SECTION II This section discusses the City of Palo Alto's requirements for establishing electric service to new or upgraded residential installations. The same requirements apply to both underground and
More informationADDENDUM #2 TO BID # BID NUMBER: ISSUE DATE: Friday, January 18, 2019
Georgetown County, South Carolina 129 Screven Street, Suite 239 Post Office Drawer 421270 Georgetown, SC 29442-4200 (843) 545-3083 Fax (843) 545-3500 E-Mail purch@gtcounty.org Website http://www.gtcounty.org
More informationSPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION
Roseville Electric SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION REVISED 10/03/17 Specifications for Residential Construction Revision List REVISION Date Page No. Description 8/18/09 T.O.C., 8.1-8.1.5 &
More informationCorrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections
Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of
More informationSERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING
SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary
More information2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code
2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of
More informationInstalling or Rebuilding Your Electric Service
Installing or Rebuilding Your Electric Service 2 3 Contents Policies for New and Rebuilt Electric Service 2-4 Paperwork and fees...2 Five-year policy...3 Proposed route location and conditions...3 Construction
More information5. Company's Installation
10 Electric Retail --Baltimore Gas and Electric Company 5. Company's Installation 5.1 Service Equipment Furnished by Company: For the purpose of determining the amount of electricity used, a meter will
More informationSECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT
SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.
More informationPublic Works & Utilities Department Memorandum
Public Works & Utilities Department Memorandum To: Land Development Owners, Engineers, and Contractors From: Public Works and Utilities Date: March 21, 2016 Subject: Solid Waste Facilities The information
More informationWater to Water Geothermal Heat Pump 3-Phase Models Both 208 & 480
Installer Water to Water Geothermal Heat Pump 3-Phase s Both 208 & 480 Installation Instructions : THA-***-2 (208, 3-Phase) THT-***-2 (208, 3-Phase) THA-***-3 (480, 3-Phase) THT-***-3 (480, 3-Phase) This
More informationANZI Transfer Switch and Generator Wiring Installation Addendum
ANZI Transfer Switch and Generator Wiring Installation Addendum Reference all appropriate documentation. NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS. THIS PRODUCT CAN BE INSTALLED BY THE
More informationBID FORM PART A. Total Quantity 1 LS $ - 2a Surveying, Layout, and Field Staking 1 LS $ - 2b Maintenance of Traffic 1 LS $ -
BID FORM PART A Name & Category Unit Unit Cost (B) Cost (AxB) GENERAL REQUIREMENTS 1 Mobilization (Maximum 3.0% of the total Contract Price) 1 LS $ - 2a Surveying, Layout, and Field Staking 1 LS $ - 2b
More informationSPRINGVILLE CITY ELECTRICAL REQUIREMENTS & STANDARDS MANUAL
1 POWER DEPARTMENT EFFECTIVE AS OF FEBRUARY 1, 2008, REVISED JULY 1, 2013 STANDARDS ARE SUBJECT TO REVIEW Table of Contents 2 TABLE OF CONTENTS Section 1 General Requirements Purpose...1.1 Codes and Ordinances...1.1
More informationZG 521 Padvault Three-Phase Transformer
E n g in e e r :R.An th o n Ap p r o v e r :Jo s h u a Jo n e s 2 0 De c 1 7 2 0 De c 1 7 ZG 521 Padvault Three-Phase Transformer ZG 521 Padvault Three-Phase Transformer 1. Scope This material specification
More informationSPRINGVILLE CITY ELECTRICAL REQUIREMENTS & STANDARDS MANUAL
POWER DEPARTMENT EFFECTIVE AS OF FEBRUARY 1, 2008, REVISED JULY 1, 2013 STANDARDS ARE SUBJECT TO REVIEW TABLE OF CONTENTS Section 1 General Requirements Purpose...1.1 Codes and Ordinances...1.1 Changes
More information9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.
Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution
More informationProject Book Worksheet for Cost Estimation
001.01 MOBILIZATION LS $34,716.18 007 3/17/2039 001.02 INCIDENTAL LS $23,929.43 019 3/17/2039 001.03 CONSTRUCTION STAKING LS $10,504.39 201 5/9/2013 001.04 REESTABLISH PROPERTY CORNERS EA $496.08 201 5/9/2013
More informationElectric Service Requirements & Guidelines
Electric Service Requirements & Guidelines Montana Service Area September 2011 NORTHWESTERN ENERGY Montana Service Area ELECTRIC SERVICE REQUIREMENTS AND GUIDELINES CONTENTS I. GENERAL INFORMATION 1.01
More informationNew Commercial Service Request-Job Process
New Commercial Service Request-Job Process HILCO Electric Cooperative, Inc. thanks you for the opportunity to be your electric provider. We are committed in providing you the best electric service promptly
More informationAREA OF WORK ENERGY
THIS DOCUMENT CONTAINS PROPRIETARY 408-859-545 AREA OF WORK THIS DOCUMENT CONTAINS PROPRIETARY Chlorking Chlor-25SM Controllers Chlorking & CO-2 controlled by chemical controller 3 x Chlorking Cells, 25
More information1 OF 8 LAD LAD PROJECT AREA KIMBERLY GERBER TITLE SHEET C.E.S. DWG. NO. NPN12045 SHEET INDEX
LAD05-9, CA 964 TITLE SHEET LAD05-9 SHEET INDEX 00 DEXTER AVE. SUITE 50 SEATTLE, WA 9809 PROJECT SUMMARY PROJECT DESCRIPTION COORDINATES LATITUDE: 33.678084 N LONGITUDE: -7.84858 W 0640 Sepulveda Blvd.
More information7. Residential Single-Family and Duplex Buildings (Dwellings)
Sin g le -F a mily a n d Du p le x Bu ild in g s 2016 Electric Service Requirements, 2 nd Edition Section 7 Section 7 Residential Single-Family and Duplex Buildings (Dwellings) Directory Page 7.1 General
More informationDocument Requirements for Engineering Review PV Systems v1.0 6/9/2017
Document Requirements for Engineering Review PV Systems v1.0 6/9/2017 Outlined below are the documents and associated minimum details required for Engineering Review of Distributed Energy Resources Interconnection
More informationSOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS
SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS November 17, 2016 Engineering Service Specifications Table of Contents Commercial Service Requirements SLEMCO Commercial
More informationGenerator Fire Safety: Generator assemblies should be located outside the building.
SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building
More informationStandards for Design and Construction
Standards for Design and Construction Of Water, Wastewater, Fiber optics and Reclaimed Water Facilities For Pasco County Utilities Department Revised: March 2018 Board of County Commissioners: Kathryn
More informationPentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION
PULL BOX F SECONDARY SYSTEM Typical grade Pentahead bolts See note 2 Conduit run as specified Plastic or fiberglass for grass areas or Polymer concrete for light duty areas (see notes 2, 3, & 4) Company
More informationFLORIDA DEPARTMENT OF TRANSPORTATION
FLORIDA DEPARTMENT OF TRANSPORTATION ADDENDUM NO. 1 DATE: 3/8/2011 RE: BID/RFP #: RFP-DOT-10/11-9031-LG BID/RFP TITLE: FURNISH AND INSTALL EMERGENCY GENERATOR POWER SYSTEM AT CARYVILLE OPENING DATE: March
More informationNew Panelboard for Lot H, EV Charger Energization, Las Positas College. Scope of Work and Technical Specifications
CHABOT-LAS POSITAS COMMUNITY COLLEGE DISTRICT New Panelboard for Lot H, EV Charger Energization, Las Positas College Scope of Work and Technical Specifications Chabot-Las Positas Community College District
More informationIndianapolis Power & Light Company
Indianapolis Power & Light Company Electric Service and Meter Manual The Electric Service & Meter Manual is not copyrighted and permission is hereby given to reproduce this document. However, the Indianapolis
More informationA. Submit manufacturer's literature and technical data before starting work.
SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop
More informationSee NT POWERCOS , Classification Based On Service Size.
Newmarket-Tay Power Distribution Ltd. Conditions of Service Number: NT POWER COS 310 01 Issue Date: July, 2007 Next Review Date: February, 2020 Residential 1. Preamble This section covers all items that
More informationApproved Meter Sockets and Cabinets
Single Unit Residential Guide 1 PHASE, 120/240 VOLT SERVICES SERVICE CAPACITY OWNED METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to
More informationGENERAL NOTES ELECTRICAL NOTES MATCH LINE SEE SHEET E1.11 KEY PLAN NTS MATCH LINE SEE SHEET E1.12 SPR-2" SPR-2" SPR-2" SPR-2" SPR-2" SPR-2" TYP DH-108
MATCH NE SEE SHEET E. N DH-6 DH-7 DH-9 DH-9 DH-8 DH-6 DH-8 MATCH NE SEE SHEET E. GENERAL NOTES KE PLAN NTS 407 North st Street, Suite 0 (5) 96-050 Fax (5) 96-06 N MATCH NE SEE SHEET E. DH- DH- DH- DH-7
More informationOutdoor Power Transmission & Distribution
Description: The purpose of the section is to highlight the current applicable UMCP Design Standards and requirements for Outdoor Power Transmission and Distribution, including but not limited to the following:
More informationElectric Service Rules
2017 Electric Service Rules GENERAL INFORMATION TEMPORARY SERVICES OVERHEAD SERVICES UNDERGROUND SERVICES DISTRIBUTED GENERATION METERING HUD MANUFACTURED HOMES FARM SERVICES UTILITY/CATV SERVICES PRIMARY
More informationMETERING REQUIREMENTS
METERING REQUIREMENTS KUA will not accept a non-securable service trough entrance. That is, all enclosed conductors prior to the meter (line side) will be securable by and accessible to KUA personnel only.
More informationRESIDENTIAL. Metering Guidelines for Electric Service. Meter Standards. October 25, 2017
Meter Standards RESIDENTIAL Metering Guidelines for Electric Service October 25, 2017 13315 Goodnough Drive NW Gig Harbor WA 98332-8640 Phone (253) 857-1547 Fax (253) 857-1557 www.penlight.org Residential
More informationInstallation Instructions
Installation Instructions MX3635-01 Rev. E Models HydraSwing 40s HydraSwing 40F 4,000 lb (1,814 kg) 10-15 seconds HydraSwing 40 4,000 lb (1,814 kg) 15-20 seconds HydraSwing 40 Twin 4,000 lb (1,814 kg)/leaf
More informationMINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS. Larry Vogt. Manager, Rates
MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS Larry Vogt Manager, Rates Minimum Distribution System What is MDS? MDS is an analysis module of the cost-of-service study in which distribution investment
More informationMETRO Magnolia Transit Center - Bid Tab
Section A - GENERAL ITEMS A-1 01505 Mobilization LS 1 $ 100,000.00 $ 100,000.00 A-2 -- Payment and Performance Bonds LS 1 A-3 01310 Document Control LS 1 A-4 01311 CPM Schedule LS 1 A-5 01590 Engineer's
More informationOptions: PART NUMBER MAIN BREAKER PHASE VOLTAGE
BC Hydro Metering Kiosk BCH Metering and distribution kiosk built to BC Hydro distribution standards. Used for applications where secondary services are installed in weatherproof kiosks outside of a main
More informationSERVICE REQUIREMENTS COMMERCIAL & INDUSTRIAL CUSTOMERS
ENERGY SERVICES ENGINEERING 840 Northgate Drive Telephone (509) 942-7403 Fax (509) 942-7405 P.O. Box 190 Richland, WA 99352 www.ci.richland.wa.us SERVICE REQUIREMENTS COMMERCIAL & INDUSTRIAL CUSTOMERS
More informationENGINEERING SPECIFICATION
December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References
More informationBIDDER'S PROPOSAL (continued) CITY OF BERKELEY BID PROPOSAL ITEM NO. A: BASE BID
SPECIFICATION 16-11031-C CITY OF BERKELEY BID PROPOSAL A: BASE BID 1 MOBILIZATION 1 LS 2 TRAFFIC CONTROL 1 LS 3 CONTRACTOR INFORMATION SIGN 2 EA 4 CONSTRUCTION AREA SIGN 18 EA 5 PROJECT IDENTIFICATION
More informationService Entrance Methods
Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility
More informationCustomer Substation Manual
Customer Substation Manual Table of Contents Section Page 2 of 81 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation
More informationElectric Vehicle Pricing Plan Contractor Set-Up Guide
Electric Vehicle Pricing Plan Contractor Set-Up Guide Contractor s Set-Up Guide: Overview Pricing Plan Summary Our special Pricing plan makes it easy for electric vehicle owners to save on charging costs.
More informationSAMPLE. Job Name: Anywhere Water District Construction of Reservoir Suggest'd Equipment Rent Total. Suggest'd Material.
Job Name: Anywhere Water District Construction of Reservoir 1500 Anywhere Water District Construction of Reservoir 1500 Electrical Contractor Sub Bid Qty #Elect Hours Unit Underground Conduit Work $60/hr
More informationCITY OF DAVIS PUBLIC WORKS DEPARTMENT STANDARD SPECIFICATIONS
CITY OF DAVIS PUBLIC WORKS DEPARTMENT STANDARD SPECIFICATIONS JANUARY 1996 EDITION ADDENDA THROUGH JULY 2017 DIANNA JENSEN City Engineer 1717 Fifth Street Davis, CA 95616 530-757-5686 2017 Edition STANDARD
More informationInstalling a Downstream Distribution Panelboard
Job Sheet 5 Installing a Downstream Distribution Panelboard OBJECTIVE To install a downstream distribution panelboard (DDP) on the Mobile Workstation. To mechanically and electrically connect the DDP to
More informationQ. Are you familiar with the matter which is the subject of this petition? A. Yes, I am.
October, 0 0 0 Q. Please state your full name and occupation. A. My name is Dean Benton. I am employed as the Plant Supervisor at the New Hampshire Electric Cooperative, Inc. ( NHEC ), Tenney Mountain
More informationWaste and Recycling Disposal Service Requirements for New Residential Developments
Waste and Recycling Disposal Service Requirements for New Residential Developments Introduction This document applies to all residential building/development applications and outlines the minimum design
More informationFertilizer Type B 2 CWT $ $ $60.00 $ $60.00 $ Sod Water 60 MGAL $60.60 $3, $30.00 $1, $30.00 $1,
BID TABS PROJECT 18-1029 22 nd AVENUE RECONSTRUCTION BID DATE: MAY 9, 2018 Stark Pavement Corp. Lalonde Contractors Cornerstone Pavers LLC Brookfield, WI Waukesha, WI Racine, WI Item Number Roadway Quantity
More informationNew Service. From... BARRON. Spooner Office: P.O. Box 261 Spooner, WI Barron Office: P.O. Box 40 Barron, WI
New Service Guidelines and Diagrams From... BARRON www.barronelectric.com email: janderson@barronelectric.com Barron Office: P.O. Box 40 Barron, WI 54812-0040 Spooner Office: P.O. Box 261 Spooner, WI 54801-0261
More informationTYPICAL MDF DESIGN REQUIREMENTS
A70000 MEP COORDINATION NOTES: TYPICAL MDF DESIGN REQUIREMENTS : ALL ROOM RECEPTACLES SHALL BE FED FROM DEDICATED IT PANEL, AND TIED INTO EMERGENCY SYSTEM. RECEPTACLES (CONVENIENCE): () 0 AMP DUPLEX RECEPTACLE
More informationFlorham Park, NJ USA Call (ASCO) for sales or service
Operator s Manual 7000 Series ATS Automatic Transfer Switches D design, 30 through 230 A DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious
More informationNEW SERVICE HANDBOOK
NEW SERVICE HANDBOOK LOCATING UNDERGROUND UTILITIES CHECK SHEET cut here Will you be working within ten feet of any overhead power lines? Yes No Type of work Work being done for County Nearest City Address
More information