Low voltage moulded case circuit breaker EB2

Size: px
Start display at page:

Download "Low voltage moulded case circuit breaker EB2"

Transcription

1 Low voltage moulded case circuit breaker EB2 Product series description unit condition Model-type Number of poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation voltage Rated impulse withstand voltage EB2 125 EB2 160 L S H S H 3, 4 3, 4 I n (A) 50 C 20,32,50, ,100,125 U e (V) AC 50/60 Hz DC U i (V) U imp (kv) Ultimate breaking capacity (IEC, JIS, AS/NZS) I cu (ka) 690V AC V AC V AC /415V AC /240V AC V DC Service breaking capacity (IEC, JIS, AS/NZS) I cs (ka) 690V AC V AC V AC /415V AC 19 36/30 36/ /240V AC V DC Rated breaking capacity (NEMA) Protection Adjustable thermal, adjustable magnetic Fixed thermal, fixed magnetic Microprocessor Utilisation category Installation Front connection Attached flat bar Solderless terminal (cable clamp) Rear connection Plug-in Draw- out DIN rail mounting Dimensions Weight Operation Direct Opening Action Toggle operation Variable depth / direct mount operating handle Motor operator (ka) 480V AC VAC A A A h (mm) w (mm) 3 pole pole d (mm) W (kg) 3 pole pole Endurance Electrical cycles Mechanical cycles Standards 415V AC IEC , EN Standard Optional - Not Available 273

2 Product series description unit condition Model-type Number of poles Nominal current ratings EB2 250 EB2 250 L S H E 3, 4 3, 4 I n (A) 50 C 200, , 125, 160, 250 Electrical characteristics Rated operational voltage Rated insulation voltage Rated impulse withstand voltage U e (V) AC 50/60 Hz DC U i (V) U imp (kv) Ultimate breaking capacity (IEC, JIS, AS/NZS) I cu (ka) 690V AC V AC V AC /415V AC /240V AC V DC Service breaking capacity (IEC, JIS, AS/NZS) Rated breaking capacity (NEMA) I cs (ka) 690V AC V AC V AC /415V AC /240V AC V DC (ka) 480V AC VAC Rated short-time withstand current Protection Adjustable thermal, adjustable magnetic Fixed thermal, fixed magnetic Microprocessor Utilisation category Installation Front connection Attached flat bar Solderless terminal (cable clamp) Rear connection Plug-in Draw- out DIN rail mounting Dimensions Weight Operation Direct Opening Action Toggle operation Variable depth / direct mount operating handle Motor operator Endurance Electrical cycles Mechanical cycles Standards Standard Optional - Not Available I cw (ka) 0.3 s A A A h (mm) w (mm) 3 pole (mm) 4 pole d (mm) W (kg) 3 pole pole V AC IEC , EN

3 Product series description unit condition Model-type Number of poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation voltage Rated impulse withstand voltage EB2 400 EB2 400 EB2 630 L S E LE E HE 3, 4 3, 4 3,4 3,4 3, 4 3, 4 I n (A) 50 C 250, 250, 250, U e (V) AC 50/60 Hz * 690* 690* DC U i (V) U imp (kv) Ultimate breaking capacity (IEC, JIS, AS/NZS) Service breaking capacity (IEC, JIS, AS/NZS) I cu (ka) 690V AC * 20* 20* 525V AC V AC /415V AC /240V AC V DC I cs (ka) 690V AC * 15* 15* 525V AC V AC /415V AC /240V AC V DC Rated breaking capacity (NEMA) (ka) 480V AC VAC Rated short-time withstand current Protection Adjustable thermal, adjustable magnetic Fixed thermal, fixed magnetic Microprocessor Utilisation category Installation Front connection Attached flat bar Solderless terminal (cable clamp) Rear connection Plug-in Draw- out DIN rail mounting Dimensions Weight Operation Direct Opening Action Toggle operation Variable depth / direct mount operating handle Motor operator Endurance Electrical cycles Mechanical cycles Standards Standard Optional - Not Available * MCCB can not be used in IT system at this voltage I cw (ka) 0.3 s A A B A A A h (mm) w (mm) 3 pole (mm) 4 pole d (mm) W (kg) 3 pole pole V AC IEC , EN

4 Product series description unit condition Model-type Number of poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation voltage Rated impulse withstand voltage Ultimate breaking capacity (IEC, JIS, AS/NZS) Service breaking capacity (IEC, JIS, AS/NZS) EB2 800 EB2 800 EB EB EB L S H LE E HE LE E LE E LE E 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 I n (A) 50 C 630, , , Ue (V) AC 50/60 Hz DC Ui (V) Uimp (kv) Icu (ka) 690V AC 10* 20* 25* 20* 25* 25* 20* 25* 20* 25* 20* 45* 525V AC 15* V AC /415V AC /85 220/240V AC V DC Ics (ka) 690V AC 10* 20* 20* 20* 20* 20* 15* 20* 15* 20* 15* 34* 525V AC 15* V AC /415V AC /65 220/240V AC V DC Rated breaking capacity (NEMA) (ka) 480V AC V AC Rated short-time withstand current Protection Adjustable thermal, adjustable magnetic Fixed thermal, fixed magnetic Microprocessor Utilisation category Installation Front connection Attached flat bar Solderless terminal (cable clamp) Rear connection Plug-in Draw- out DIN rail mounting Dimensions Weight Operation Direct Opening Action Toggle operation Variable depth / direct mount operating handle Motor operator Endurance Electrical cycles Mechanical cycles Standards Standard Optional - Not Available * MCCB can not be used in IT system at this voltage Icw (ka) 0,3 sec A A A B B B A A B B B B h (mm) w (mm) 3 pole (mm) 4 pole d (mm) W (kg) 3 pole 8,5 8,5 8,5 9,1 9,1 12, ,8 19, pole 11,5 11,5 11,5 12,3 12,3 14,8 14,8 14, IEC , EN

5 Product series description unit condition Model-type Number of Poles Nominal current ratings Electrical characteristics Rated operational voltage Rated impulse withstand voltage EB2R EB2R 125L 250L 3, 4 3, 4 I n (A) 50 C 20, 32, , , 100, 125 U e (V) AC 50/60 Hz U imp (kv) 8 8 Ultimate breaking capacity (IEC, JIS, AS/NZS) I cu (ka) 525V AC V AC /415V AC /240V AC Service breaking capacity (IEC, JIS, AS/NZS) I cs (ka) 525V AC V AC /415V AC /240V AC Protection Adjustable thermal, adjustable magnetic Residual current protection, Type A Utilization category Installation Front connection Attached flat bar Solderless terminal (cable clamp) Rear connection Plug-in DIN rail mounting Dimensions Weight Operation Direct Opening Action Toggle operation Variable depth / direct mount operating handle Mechanical interlocks Motor operator Endurance Electrical cycles Mechanical cycles Standards Standard Optional - Not Available h (mm) w (mm) 3 pole pole d (mm) W (kg) 3 pole pole V AC A IEC , EN A 277

6 Low voltage switch disconnector Product series description unit condition Model-type Number of Poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation voltage Rated impulse withstand voltage Rated short-circuit making capacity Rated short-time withstand current Installation Front connection Attached flat bar Solderless terminal Rear connection Plug-in Draw- out DIN rail mounting Dimensions Weight Operation Direct Opening Action Toggle operation Variable depth / direct mount operating handle Motor operator Endurance Electrical cycles Mechanical cycles Standards ED2 ED2 ED2 ED2 ED , 4 3, 4 3,4 3,4 3, 4 I n (A) U e (V) AC 50/60 Hz DC U i (V) U imp (kv) I cm (ka peak) 3, I cw (ka rms) 0.3s AC AC-23A AC-23A AC-23A AC-23A AC-23A DC DC-22A DC-22A DC-22A DC-22A DC-22A h (mm) w (mm) 3 pole (mm) 4 pole d (mm) W (kg) 3 pole pole V AC IEC , EN Product series description unit condition Model-type Number of Poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation voltage Rated impulse withstand voltage Rated short-circuit making capacity Rated short-time withstand current Installation Front connection Attached flat bar Solderless terminal Rear connection Plug-in Draw- out DIN rail mounting Dimensions Weight Standards ED2 ED2 ED , 4 3, 4 3,4 I n (A) U e (V) AC 50/60 Hz DC U i (V) U imp (kv) I cm (ka peak) 9, I cw (ka rms) 0.3sec AC AC-23A AC-23A AC-23A DC h (mm) w (mm) 3 pole (mm) 4 pole d (mm) W (kg) 3 pole pole IEC , EN

7 Thermal magnetic adjustments and characteristics Thermal adjustment Low voltage moulded case circuit breakers have a wide thermal adjustment range, one of the largest on the market. The rated current I r is continuously adjustable from 63% to 100% of this nominal current I n. There are three main points of calibration marked at 63%, 80% and 100%. Magnetic adjustment An adjustable magnetic characteristics allows short-circuit protection to be matched to the load and supply characteristics, for example motor inrush current or generator short-circuit current. Time, current characteristics curves EB2 125 Time, current characteristics curves EB2 160 and EB2 250 Ambient compensating curves Ambient compensating curves 279

8 Time, current characteristics curves EB2 400 Time, current characteristics curves EB2 630 and EB2 800 Magnetic trip current Magnetic trip current 630 Max. 630 Max. Min. Min. X5 X10 X5 X10 Ambient compensating curves Ambient compensating curves 800A (min) Percent current rating Calibrated temperature 800A (max) Calibrated at 40 C 45 C 50 C Ambient temperature ( C) Special applications of thermal magnetic MCCBs SOURCE All standard thermal magnetic MCCBs are suitable for DC application up to 250 V DC. LOAD 280

9 Microprocessor based characteristics and adjustments EB2 series Etibreak 2 MCCBs from 250A to 1600A frame sizes are available with electronic protection units. Current ratings, In, of 40A, 125A, 160A, 250A, 400A, 630A, 800A, 1000A, 1250A and 1600A are available. These offer great flexibility as their characteristics can be set to suit a wide range of application conditions. Overload protection can be set between 0.4 and 1.0 times In. Selecting a Preset Characteristic for a 400A Etibreak 2 MCCB with Electronic Protection Every Etibreak electronic protection unit includes overload protection (L), delayed short-circuit protection (S) and instantaneous protection (I) as standard. Electronic protection characteristic Adjustment dials The left adjustment dial sets the rated current to match the conductor rating. The right adjustment dials select one of six on 630A models preset characteristics. The effects of the left adjustment dial (labelled IR(A)), and the right adjustment dial (labelled Characteristics) are detailed in the tables shown underneath each time/current graph. Tolerances of Characteristics Characteristics Tolerance Long Time Delay (LTD) t R +/- 20% Short Time Delay (STD) I sd +/- 15% Total clearnig time +50ms, resettable time - 20ms Instantaneous (INST) I i +/- 20% t R I sd t sd I i 281

10 EB2 250 E I n = 40, 125, 160, 250 Standard I R (A) LTD Pick-up current I R xi n Characteristics No LTD Index t R Index (s) at 200 % x I R at 600 % x I R Index I STD sd Index xi R Index t sd Index (s) INST Index I i Index xi R 14 (Max: 13 x I n ) Note (1) Note: (1) I i max. = 12 x I n. 282

11 EB2 400 E I n = 250, 400 I R (A) LTD Pick-up current I R xi n Standard Characteristics No LTD Index t R Index (s) at 200 % x I R at 600 % x I R Index I STD sd Index xi R Index t sd Index (s) INST Index I i Index xi R 14 (Max: 13 x I n ) Note (1) Note: (1) Ii max. = 13 x I n. 283

12 EB2 630 E 3 Tripping Time second minute hour T I R I p t R t p I g I sd tsd t g I i I Percent rated current In Percent Rated Current I R I n = 630A I R (A) LTD Pick-up current I R xi n Standard Characteristics No LTD Index t R Index (s) at 200 % x I R at 600 % x I R Index I STD sd Index xi R Index t sd Index (s) INST Index I i Index xi R 14 (Max: 10 x I n ) Note (1) Note: (1) Ii max. = 10 x I n. 284

13 EB2 800 E Percen t R ated Current I n P ercent R ated C urrent I R I = 800A; 630A I n = 800 I R (A) LTD Pick-up current I R xi n Standard Characteristics No LTD Index t R Index (s) at 200 % x I R at 600 % x I R Index I STD sd Index xi R Index t sd Index (s) INST Index I i Index xi R 14 (Max: 12 x I n ) Note (1) Note: (1) Ii max. = 12 x I n. 285

14 EB E 3 Tripping Time second minute hour T I R I p t R t p I g I sd tsd t g I i I Percen t R ated Current I n P ercent R ated C urrent I R I n = 1000A I R (A) LTD Pick-up current I R xi n Standard Characteristics No LTD Index t R Index (s) at 200 % x I R at 600 % x I R Index I STD sd Index xi R Index t sd Index (s) INST Index I i Index xi R 14 (Max: 10 x I n ) Note (1) Note: (1) Ii max. = 10 x I n. 286

15 EB E Percen t R ated Current I n P ercent R ated C urrent I R I = 1250A I n = 1250 I R (A) LTD Pick-up current I R xi n Standard Characteristics No LTD Index t R Index (s) at 200 % x I R at 600 % x I R Index I STD sd Index xi R Index t sd Index (s) INST Index I i Index xi R 14 (Max: 12 x I n ) Note (1) Note: (1) Ii max. = 12 x I n. 287

16 EB E Percen t R ated Current I n P ercent R ated C urrent I R I = 1600A I n = 1600A I R (A) LTD Pick-up current I R xi n Standard Characteristics No LTD Index t R Index (s) at 200 % x I R at 600 % x I R Index I STD sd Index xi R Index t sd Index (s) INST Index I i Index xi R 14 (Max: 12 x I n ) Note (1) Note: (1) Ii max. = 12 x I n. 288

17 EB2R adjustments Residual current I D is the Diferenčni adjustable tok tripping I D je threshold nastavljivo for earth območje leakage preklapljanja protection. pri It can toku be set napake. between Nastavimo 30mA and ga 3A. lahko Available med 30mA settings 3A. are Možne 30mA, nastavitve 100mA, 300mA, so 30mA, 100mA, 500mA, 300mA, 1000mA 500mA, and 3000mA. 1000mA and Available 3000mA settings so prikazane are shown spodaj. below Časovna Time delay zakasnitev t is introduced t je vpeljana to the v zaščitno residual karakteristiko current (earth diferenčnega leakage) protection toka. Možne characteristic. nastavitve so; Available INST, 60ms, settings 200ms, are; INST, 400ms, 60ms, 0ms 200ms, in NT. INST pomeni 400ms, brez 0ms časovne and zakasnitve NT. INST (max. means čas EB2R preklopa set to je time 40ms), delay 0 (max. NT pomeni actual brez tripping preklapljanja time is 40ms) (čas NT preklopa means No je trip O). (tripping Maksimalni time čas is O) The izklopa maximum je prikazan breaking v oklepajih. time is shown Opomba: in brackets. I n je nastavljen Note that na I 30mA, n is set at 30mA, t pa t na defaults I R je nastavljivo I območje R is the adjustable preklapljanja tripping threshold for pri zaščiti pred overload protection. preobremenitvijo. It can be set between Nastavimo ga lahko 0,63 and 1,0 times I med 0,63 and 1,0 x n. n Available I Možne nastavitve n ratings are I n so shown below prikazane spodaj I i Iis i je the nastavljivo tripping threshold območje for pri short-circuit kratkostični protection. zaščiti. Nastavljen It is fixed at je the na values spodaj prikazanih shown vrednostih. below Model l n t (ms) In (A) I i EB2R , 0.1, 0.3, 0.5, 1, 3 0(40), 60(195), 200(365), 400(620), 20, 32, 50, 63, x In (+/- 20%) 0(950), NT ( ) EB2R , 0.1, 0.3, 0.5, 1, 3 0(40), 60(195), 200(365), 400(620), x In (+/- 20%) 0(950), NT ( ) EB2R , 0.1, 0.3, 0.5, 1, 3 0(40), 60(195), 200(365), 400(620), x In (+/- 20%) 0(950), NT ( ) EB2R , 0.1, 0.3, 0.5, 1, 3 0(40), 60(195), 200(365), 400(620), 0(950), NT ( ) x In (+/- 20%) 289

18 Internal accessories series EB2 Ampere Frame size (A): , General Purpose Auxiliary Switch General Purpose Auxiliary Switch General Purpose Auxiliary Switch General Purpose Auxiliary Switch General Purpose Auxiliary Switch General Purpose Auxiliary Switch General Purpose Alarm Switch Shunt Trip General Purpose Alarm Switch Shunt Trip General Purpose Auxiliary Switch General Purpose Alarm Switch Shunt Trip OR or or OR or or or or Heavy Duty Alarm Switch Heavy Duty Alarm Switch Undervoltage Heavy Duty Alarm Switch Undervoltage Heavy Duty Auxiliary Switch Undervoltage Heavy Duty Auxiliary Switch Heavy Duty Auxiliary Switch Heavy Duty Auxiliary Switch Heavy Duty Auxiliary Switch Status indication switches mount in the left side of the MCCB. General purpose and heavy duty status indication switches cannot be mixed in the same MCCB. Only one alarm switch can be fitted to an MCCB. Shunt trips and undervoltage trips mount in the right side of the MCCB. It is not possible to install a shunt trip and an undervoltage trip in an MCCB as they occupy the same location. Undervoltage trips can provide remote tripping if necessary by wiring a normally closed contact or pushbutton in series with the protected supply. Undervoltage trips with time delays require an external time delay controller which clips to the side of the MCCB. 290

19 Internal accessories series EB2 General Purpose Auxiliary Switch General Purpose Alarm Switch.1.1 OFF, Terminal Designations and Function of General Purpose Auxiliary Switch.2.4 Trip.2.4 Trip Terminal Designations and Function of General Purpose Alarm Switch General purpose auxiliaries and alarm switch ratings Volts (V) Resistive Load AC Amperes (A) Inductive Load Volts (V) Resistive Load DC Amperes (A) Inductive Load Minimum Load 100mA -> 15V DC. Amperes (A).3 Terminal Designations and Function of Heavy Duty Auxiliary Switch NO contact.3 Terminal Designations and Function of Heavy Duty Alarm Switch, NO contact Heavy Duty Auxiliary Switch OFF, Trip OFF, Trip Terminal Designations and Function of Heavy Duty Auxiliary Switch, NC contact Heavy Duty Alarm Switch.1.4 Trip Trip.2 Terminal Designations and Function of Heavy Duty Alarm Switch, NC contact Ratings of Heavy Duty Auxiliary and Alarm switches Volts (V) Resistive Load AC Amperes (A) Inductive Load Volts (V) Resistive Load DC Amperes (A) Inductive Load

20 Ratings of Shunt Trips Rated Voltage Voltage AC Voltage DC Excitation Current (A) Shunt Trips C1 Controller C2 ~ ~ ( ) (+) Terminal Designations of Shunt Trips Undervoltage Trips Ratings of Undervoltage Trips Power supply capacity (VA) Excitation current (ma) Rated Voltage Voltage AC Voltage DC Power Supply Capacity (A) Controller D1 D2 ~ ~ ( ) (+) Terminal Designations of Undervoltage Trips 292

21 External accessories IZ Interpole barrier. Installed between MCCB teminal, which increases the distance between poles to reduce the possibility of creepage. PRS Terminal cover. The terminal covers are applied to the MCCB to prevent accidental contact with live parts and thereby protection against direct contact. PRS-ZB Terminal cover for att. Busbar. The terminal covers are applied to the MCCB to prevent accidental contact with live parts and thereby protection against direct contact. The width is different because of attach busbar. SP Solderless terminal RO Operating handle, breaker mounted. It's used when MCCB is installed in control centre/ switchboard RO_P Operating handle, panel mounted, variable depth. This consists of an operating mechanism mounted on the breaker, an operating handle mounted on the panel door and a square shaft to connect the mechanism with the handle. MO Motor operator. Enabling to switch MCCB ON or OFF remotly. PR Door flange. Accessory for mounting on panel door. ZA Handle lock. Enables the MCCB to be padlocked in neither the ON or OFF position. ZB Attach busbar. Used for easier instalation on busbar systems (widen terminals). PRO Handle extension. Used for easier manipulation ON/OFF at bigger MCCB s. 293

22 8 Dimensions EB2 & EB2R 125 H L Interpole barrier (removable) H L Mounting hole Operating knob C L 154 Front panel t2 24 screw Preparation of conductor ø9 17(max.) max.t5 8.5(max.) Drilling plan Panel hinge position (hatching area) bottom view 154± Connector plug (max.) 8 M4x0.7 Mounting screw M4x0.7 Tapped hole Operating knob C L 154 Front panel t2 Mounting plate (max. t3.2) 5 15 Conductor overlap max C L Drilling plan C L Panel cutout (Front view) R1 155 Pad lock Connector plug (max.) ø Stud can be turned 45 or 90 M4X0.7 Mounting screw ø M4X0.7 Tapped hole Panel cutout dimensions shown give an allowance of 1.5mm around the handle escutcheon. 294

23 EB2 160, EB2 250 & EB2R 250 (optional) 295

24 EB2 250/_E (Microprocessor s MCCBs) With extension bars (optional) 296

25 EB

26 EB

27 EB2 800 Front connected with extension bars (optional) AS L 1 51 W Rear connected Toggle extension (removable) ø Trip button (red) Stud can be turned Mounting screw Interpole barrier (removable) 110 AS L Mounting hole 13 ø ø15 for accessory wiring when necessary Conductor overlap, max Conductor overlap, max t1 Toggle extension (removable) Drilling plan (front view) Tapped hole Note: Studs are factory installed in horizontal direction both on the line and load sides. AS L L Mounting screw ø48 Groove for dissipating heat generated by overcurrent Drilling plan (front view) t2 L Breaker Type SEB2 800-C Thermal J, S 800-NJ magnetic R ated Current 630A S 800-R J, S 800-NN S 800-NE EB2, Electronic S 800-R E 800A 630A 800A Panel cutout (front view) R t Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon. t L Tapped hole L W Front connected with Motor Operator ø13 13 Interpole barrier (removable) 110 Mounting hole Front Panel Manual operating handle (removable) (18) t1 L1 Drilling plan (front view) Tapped hole Panel cutout (front view) Pad lock AS L AS L AS L Mounting screw AS L (15.5) Connector plug (19.8) W C onductor overlap, max t L2 Panel cutout dimensions shown give an allowance of 1.5mm around motor operator. Rear connected with Motor Operator 12.5 Front Panel Manual operating handle (removable) (18) Pad lock (15.5) Connector plug ø15 for accessory wiring 140 when necessary Stud can be turned (19.8) 99.5 Mounting screw C onductor overlap, max Drilling plan (front view) ø ø48 Tapped hole Panel hinge position (hatching area) (bottom view) Note: Studs are factory installed in horizontal direction both on the line and load sides. 299

28 EB : Arrangement Standard Line : Handle Frame Centre Line Front connected AS L ø13 13 Trip button (red) Interpole ba rrier (rem ovable) 110 AS L Mounting hole Conductor overlap, max Toggle extension (rem ovable) AS L Mounting scr ew Drilling plan (f ront view) Tapped hole Rear connected Toggle extension (rem ovable) ø Conductor overlap, max Vertical direction only Mounting scr ew 12 ø15 for accessory wi ring when necessa ry Drilling plan (f ront view) ø48 Tapped hole Groov e for dissipating heat gene rated by overcurrent Panel cutout (front view) R Panel cutout dimensions shown gi ve an allow ance of 1.0mm around the handle escutcheon. Front connected with Motor Operator ø13 13 Interpole ba rrier (rem ovable) 110 Mounting hole Front Panel Manual operating handle (rem ovable) (18) Drilling plan (f ront view) Tapped hole Panel cutout (front view) Pad lo ck AS L AS L AS L Mounting scr ew AS L (15.5) Connector plug (19.8) C onductor overlap, max Insulator Panel cutout dimensions shown give an allow ance of 1.5mm around motor operato r. Rear connected with Motor Operator Vertical ø15 for accessory wi ring direction 140 when necessa ry Front Panel only 136 Manual operating handle (rem ovable) (18) Pad lo ck Conductor overlap, max (15.5) Connector plug ø (19.8) Mounting scr ew Drilling plan (f ront view) ø ø48 Tapped hole Panel hinge position (hatching area) (bottom view) Note: Studs are facto ry installed in ho rizontal direction both on the line and load sides. 300

29 EB : Arrangement Standard Line : Handle Frame Centre Line Front connected Interpole ba rrier (rem ovable) ø Mounting hole 80 Toggle extension (rem ovable) Drilling plan (f ront view) Trip button (red) ø Mounting scr ew Rear connected Toggle extension (rem ovable) Mounting plate Mounting scr ew Insulating plate Conductor overlap, max Drilling plan (f ront view) ø Panel cutout (front view) ø Soft plastic tubing ø50 to be provided on center pole and neutral pole of vertical terminal type for insulation Conductor overlap, max ø15 for accessory wi ring when necessa ry Note: Studs are facto ry installed in ho rizontal direction both on the line and load sides Panel cutout dimensions shown gi ve an all owance of 1.5mm around t he handle escutcheon. Front connected with Motor Operator ø Pad lo ck Drilling plan (f ront view) AS L 166 AS L Control circuit terminal Conductor overlap, max 11(max.) (max.) 29 Mounting scr ew ø9 Rear connected with Motor Operator Mounting plate Mounting scr ew Insulating plate Drilling plan (f ront view) ø9 Panel cutout (front view) R 3 11(max.) ø Soft plastic tubing ø50 to be provided on center pole and neut ral pole of vertical te rminal type for insulation. Conductor overlap, max ø15 for accessory wi ring when necessa ry Note: Studs are facto ry installed in ho rizontal direction both on the line and load sides Panel cutout dimensions shown gi ve an all owance of 1.0mm around motor operator. 301

30 EB : Arrangement Standard Line : Handle Frame Centre Line Front connected Interpole barrier (removable) Mounting hole Insulating plate Drilling plan (front view) Toggle extension (removable) Mounting angle Trip button (red) Mounting screw Rear connected Mounting angle Mounting screw Conductor overlap, max 17 Drilling plan (front view) Panel cutout (front view) Toggle extension (removable) Conductor overlap, max Insulation tube ON side Center pole and Neutral pole ( OFF side All poles ) Panel cutout dimensions shown give an allowance of 1.5mm around the handle Front connected with Motor Operator Drilling plan (front view) Control circuit terminal AS L 166 AS L Pad lock AS L 11(max.) Insulating plate Mounting angle L Mounting screw AS L ø ø Conductor overlap, max (max.) Rear connected with Motor Operator Drilling plan (front view) Panel cutout (front view) 11(max.) 4.5 Mounting angle Mounting screw ø Conductor overlap, max Insulation tube ON side Center pole and Neutral pole ( OFF side All poles ) ø9 139(min.) R 3 H L Panel cutout dimensions shown give an allowance of 1.0mm around motor operator. 302

31 Low breaking capacity moulded case circuit breakers EB2S Product series description unit condition Model-type Number of poles Nominal current ratings Electrical characteristics Rated insulation voltage Rated impulse withstand voltage Ultimate breaking capacity (IEC, JIS, AS/NZS) I n (A) 50 C 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160 *F - fixed, A - adjustable EB2S 160 F EB2S 160 A EB2S 250 F EB2S 250 A LF SF HF LA SA HA LF SF HF LA SA HA 25, 40, 63, 80, 100, 125, 160 3, 4 200, , 250 U i (V) U imp (kv) I cu (ka) 690V AC V AC 6 7, , , V AC /400/415V AC V AC V DC V DC Service breaking capacity (IEC, JIS, AS/NZS) Rated short-circuit making capacity Rated short-circuit withstand current Protection Fixed thermal, fixed magnetic Adjustable thermal, fixed magnetic Adjustable thermal, adjustable magnetic Utilization category I cs (ka) 690V AC V AC 3 4 7, ,5 3 7, ,5 440V AC 5 7, , /400/415V AC V AC V DC V DC I cm (ka) peak I cw (ka) rms A A A A Outline dimensions a d b c e height (b) width (a) width (a) depth ( c) depth (d) toggle cutout( e) (mm) (mm) 3 pole (mm) 4 pole (mm) (mm) (mm) Weight Operation Direct Opening Action Trip button Suitable for isolation Standards (kg) 3 pole pole IEC , EN

32 I-t EB2S 160 LF, EB2S 160 SF, EB2S 160 HF 304

33 EB2S 160 LA, EB2S 160 SA, EB2S 160 HA 305

34 EB2S 250 LF, EB2S 250 SF, EB2S 250 HF 306

35 EB2S 250 LA, EB2S 250 SA, EB2S 250 HA 200A 250A 307

36 Internal accessories EB2S 160 F&A EB2S 250 F&A Shunt Trip Unit Shunt Trip Unit Auxiliary Switch (1x) Auxiliary Switch (2x) Alarm Switch (1x) ORor Alarm Switch (1x) ORor Undervoltage Trip Unit Undervoltage Trip Unit Status indication switches mount in the left side of the MCCB. Only one alarm switch can be fitted to an MCCB. Ratings of Auxiliary switch Auxiliary Switch Volts (V) AC Amperes (A) Resistive Load Inductive Load DC Amperes (A) Resistive Load Inductive Load The inductive load means power factor of no smaller than 0.4 and time constant of no larger than 7 ms..2.4 OFF, Trip Terminal designations and function Alarm Switch Ratings of Alarm switch Volts (V) AC Amperes (A) Resistive Load Inductive Load DC Amperes (A) Resistive Load Inductive Load The inductive load means power factor of no smaller than 0.4 and time constant of no larger than 7 ms..2.4 OFF, Trip Terminal designations and function 308

37 Shunt Trip Unit Ratings of Shunt Trip Rated Voltage Voltage AC Voltage DC Excitation Current (A) C1 Controller C2 ~ ~ ( ) (+) Terminal Designations of Shunt Trips The permissible voltage is from 85% to 110% of the rated voltage for AC or 75% to 125% thereof for DC. Ensure that the voltage does not drop exceeding the permissible voltage range when SHT is actuated. Breaker contacts usually start opening within 30 ms after the rated voltage is applied to the breaker. Undervoltage Trips Ratings of Undervoltage Trips Power supply capacity (VA) Excitation current (ma) Rated Voltage Voltage AC Voltage DC Power Supply Capacity (A) Controller D1 D2 ~ ~ ( ) (+) Terminal Designations of Undervoltage Trips External accessories Key lock (optional) Features Voltage presence LED indication Operating handle Lock plate Installation and removal ease: Simply rotate two knobs allows the motor operator to be installed on or removed from the breaker. High-speed, stable actuation: The operating time as short as up to 0.1 second makes it possible to use the motor operators for synchronized closing of breakers. Silent operation: MO2S use a direct drive system, providing operational silence. Lock-in off capability: This capability allows the breaker to be padlocked in the OFF state. Up to thee padlocks with a 5 to 8 mm hasp diameter can be used. Padlocks are not supplied. 309

38 Ratings and specifications Rated operational voltage (1*) Peak steady-state/starting current, A (2*) Operation method Operating time, s at rated voltage V AC 24V DC V AC 3.5/7 24V DC 18/26 Motor driven (direct drive system) ON 0.1 OFF/RESET 0.1 (3*, 4*) Operating switch ratings 100V 0.1A (open voltage/current: 44V/4 ma) (*5) Power supply required 300VA or higher Dielectric withstand voltage (for one minute) Weight 1*: Permissible operating range is 85% to 110%. 2*: The currents shown are at the maximum rated operational voltage. 1500V AC( 1000V AC -> 24V DC) 1.4kg 3*: The operating time is the value when the rated operational voltage is supplied. Allow the longer time for the motor operator to complete the operation. 4*: The motor operator is of a short time duty. Do not subject it to more than 10 continuous ON-OFF operations. If this occurs, allow the motor operator to cool for at least 15 minutes. 5*: When the rated operational voltage is DC24V the open voltage will be DC22V. Motorized operation The motor operator has an input-signal self-hold circuit; closing the ON or OFF switch (see circuit diagrams shown bellow) momentarily allows activating the motor operator. To reset the tripped breaker to the OFF position, close the OFF (RESET) switch. The voltage presence LED indication is on when the power is supplied to the motor operator. Auto reset feature (optional) The auto reset feature allows the breaker to be automatically reset approx. 1.5 seconds after the breaker trips open. This option contains auto-reset switches and does not require to use auxiliary or alarm switches installed in the breaker. Note : that after the thermal OCR trips a thermal-magnetic breaker, the breaker cannot be immediately closed though it can be auto-reset. Wait for a few minutes after the tripping and provide a close signal to the breaker. This option resets the tripped breaker automatically, regardless of the cause of the tripping. Manual operation Pull the operating handle out. Rotating the handle counterclockwise turns ON the breaker and clockwise turns OFF or resets the breaker. Operation precautions 1. Ensure that the actual operation voltage ranges from 85% to 110% of the rated one. 2. Use operation switches whose ratings and power capacity is as specified in the Ratings and Specifications table on the previous page. 3. Use noise filters if the control power supply of the motor operator is shared by peripheral devices. Otherwise, power supply noise may cause malfunction of the peripheral devices. 4. When the motors are used in conjunction with the mechanical interlock the electrical interlock should be provided between the motors in order to avoid the simultaneous closing. The followings are the available electrical interlock cables. 310

39 Control circuit diagram of MO2S T2MC25L P1(+) DS OFF(RESET) ON + The + and symbols indicate the Uc polarities of DC-rated motor operators. OFF ON COM Control power circuit ON/OFF control circuit LED Motor drive circuit M P2( ) E Dimensions EB2S 160 F & A EB2S 250 F & A 311

40 312

Low voltage moulded case circuit breaker EB2

Low voltage moulded case circuit breaker EB2 Low voltage moulded case circuit breaker EB2 Product series description unit condition Model-type Number of poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation

More information

Low breaking capacity moulded case circuit breakers

Low breaking capacity moulded case circuit breakers New series EB2S of MCCBs has excellent performances with reduced dimensions and new modern design. Advantages of low breaking capacity MCCBs Unique accessory cover opens with only one screw. Practical

More information

15-I73E CAT REF.

15-I73E CAT REF. & www.terasaki.co.jp 5-I7E CAT REF. TABLE OF CONTENTS General - Introduction - General - Selection Chart - Ratings and Specifications - Air Circuit Breakers for DC50V-00V - Moulded Case Circuit Breakers

More information

14-I73E CAT REF.

14-I73E CAT REF. & www.terasaki.co.jp -I7E CAT REF. TABLE OF CONTENTS General - Introduction - General - Selection Chart - Ratings and Specifications - Air Circuit Breakers for DC50V-00V - Moulded Case Circuit Breakers

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

MOULDED CASE CIRCUIT BREAKERS 16A TO 630A

MOULDED CASE CIRCUIT BREAKERS 16A TO 630A TEMBREAK 2 MOULDED CASE CIRCUIT BREAKERS 16A TO 630A 1. Welcome to TemBreak 2 2. Ratings and Specifications 3. Operating Characteristics 4. Application Data 5. Accessories 6. Installation 7. Dimensions*

More information

01 Spectra Plus - Introduction

01 Spectra Plus - Introduction 01 Spectra Plus - Introduction Standard features Conforming to IS13947-2/EN60947 2 Compact dimensions Available in 3P & 4P High performance microprocessor protection release Wide overload setting from

More information

Memshield - ACB Ratings & Specifications

Memshield - ACB Ratings & Specifications Memshield Memshield - ACB Ratings & Specifications Rating and specifications Current rating, A List No Number of poles RATED CURRENT (A) [In] IEC, BS, VDE, AS Neutral pole ampere frame (A) RATED PRIMARY

More information

cor Long Run Experience

cor Long Run Experience Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30

More information

18-I73E CAT REF.

18-I73E CAT REF. & www.terasaki.co.jp 1-I73E CAT REF. TABLE OF CONTENTS General 1-1 Introduction 1- General 1-3 Selection Chart 1- Ratings and Specifications -1 Air Circuit Breakers for DC350V-00V - Moulded Case Circuit

More information

MCCB Accessories to suit AF

MCCB Accessories to suit AF MCCB s MCCB Accessories to suit 125-630AF Accessory fitting combinations INTERNAL General purpose types Micro-switch types Auxiliary Heavy duty types Bridge -contact types Auxiliary Shunt UVT Internal

More information

DPX earth leakage DPX 3 -I earth leakage

DPX earth leakage DPX 3 -I earth leakage 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 250 + earth leakage Reference(s) : 420 225/ 227/ 228/229/ 255/ 257/ 258/ 259/ 285/ 287/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3.

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

DPX moulded case circuit breakers

DPX moulded case circuit breakers BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.

More information

MOULDED CASE CIRCUIT BREAKERS BC160N

MOULDED CASE CIRCUIT BREAKERS BC160N D MOULDED CASE CIRCUIT BREAKERS BC160N D BC160N COMMERCIAL INFORMATION Circuit breakers...d4 Switch-disconnectors...D5 Connecting sets......d6 Mounting sets......d6 Switches...D7 Shunt trips...d7 Undervoltage

More information

3VU13, 3VU16 Circuit-Breakers

3VU13, 3VU16 Circuit-Breakers 3VU3, 3VU6 Circuit-Breakers Description The 3VU3, 3VU6 circuit-breakers are compact circuit-breakers for currents up to 80 A which operate according to the current limiting principle. The devices are used

More information

C 1. SPECTRONIC SP - Air circuit breakers. Summary. C2. General characteristics. C3. Fixed circuit breaker. C4. Withdrawable circuit breakers

C 1. SPECTRONIC SP - Air circuit breakers. Summary. C2. General characteristics. C3. Fixed circuit breaker. C4. Withdrawable circuit breakers SPETRONI SP - Air circuit breakers Summary 2. General characteristics 3. Fixed circuit breaker 4. Withdrawable circuit breakers 5. haracteristics 6. RV23: protection and control unit 6. RV+ : protection

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 250

DPX Thermal magnetic and trip-free switches DPX 3 -I 250 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 250 Reference(s) : 420 205/ 207/ 208/209/ 215/ 217/ 218/ 219/ 235/ 237/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3.

More information

Overview of Low voltage equipment - Moulded-case & Air circuit-breakers

Overview of Low voltage equipment - Moulded-case & Air circuit-breakers Overview of Low voltage equipment - Moulded-case & Air circuit-breakers Moulded-case circuit-breakers for distribution (1) R16 and R20 Icu = 16 ka @ 220/230 V (2) All the versions with Icu = 35 ka are

More information

DRX 250 B/N/H Circuit breaker (not adjustable)

DRX 250 B/N/H Circuit breaker (not adjustable) 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 References rences: /18/19/20/21/22/23/24/25/26/27/28/29/ 32/33 INDEX PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. MOUNTING 2 5.

More information

12-I73Eb CAT REF.

12-I73Eb CAT REF. & www.terasaki.co.jp -I7Eb CAT REF. TABLE OF CONTENTS General - Outline Dimensions 5- Introduction - DC Air Circuit Breakers Outline Dimensions General - Selection Chart - AR6S, AR0S 5- AR5S, ARS 5- Ratings

More information

Molded Case Circuit Breaker

Molded Case Circuit Breaker & The Ultimate Safety Breaker Molded Case Circuit Breaker www.terasaki.co.jp Catalogue No. 13!5E ! Safety Notice Carefully read instruction manual to ensure proper installation, connection, operation,

More information

DMX 3 -I 2500 switch disconnectors

DMX 3 -I 2500 switch disconnectors 8704 LIMOGES Cedex Telephone : 0 0 87 87 Fax : 0 0 88 88 DMX 3 200 circuit breakers DMX 3 -I 200 switch disconnectors References: 0 28 20 / 21 / 22 / 23 / 24 / 2 / 2 / 30 / 31/ 32/ 33/ 34 / 3 / 3 / 40

More information

UTS400 SELECTION GUIDE CATALOG NUMBERING [PRODUCT SELECTION] UTS400 NT ATU 400A 3P LL LSIS UL MCCB

UTS400 SELECTION GUIDE CATALOG NUMBERING [PRODUCT SELECTION] UTS400 NT ATU 400A 3P LL LSIS UL MCCB PRODUCT CATALOG SELECTION GUIDE UTS400 CATALOG NUMBERING [PRODUCT SELECTION] UTS400 NT ATU 400A 3P LL UL SERIES & FRAME: Susol 400AF PERFORMANCE Rating 80% 0% ka N NT 65 SUFFIX UL : UL 240Vac H HT 0 L

More information

DRX 125 Circuit breaker (not adjustable)

DRX 125 Circuit breaker (not adjustable) 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 272 20/21/22/23/24/25/26/27/55/56/57/58/59/60 INDEX PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (continuation) 2 4.

More information

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250

More information

Protection components

Protection components Presentation, characteristics Presentation 1 2 3 motor circuit-breakers are 3-pole thermal-magnetic circuit-breakers standards IEC 60947-2 and IEC 60947-4-1. Connection These circuit-breakers are designed

More information

Phase + Neutral, neutral on left side

Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 160

DPX Thermal magnetic and trip-free switches DPX 3 -I 160 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 160 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS 3 6. CONFORMITY

More information

DRX 100 B/N/H Circuit breaker (not adjustable)

DRX 100 B/N/H Circuit breaker (not adjustable) 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 INDEX PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (continuation) 2 4. MOUNTING 2 5. CABLING 3 6. ELECTRIC AND MECHANICAL

More information

Moulded case circuit breakers

Moulded case circuit breakers Moulded case circuit breakers CONTENT Range 4 Protection Releases 5 Salient Features 8 Accessories, 4 Technical data 2 Time Current Characteristics 5 Overall Dimensions 7 SN4 SN3 SN2 SN 3 RANGE Moulded

More information

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases Index Page Circuit-Breakers M4 166 for motor protection Auxiliary contacts 167 Signalling switch Auxiliary releases Insulated 3-pole busbar system 168 Terminal block DIN-rail adapters 169 Busbar adapters

More information

DX³ 4-pole RCBO 6000 A/10 ka

DX³ 4-pole RCBO 6000 A/10 ka 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ 4-pole RCBO CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

DPX Electronic + earth leakage

DPX Electronic + earth leakage 87045 LIMOGES Cedex Phone :+33 5 55 06 87 87 Fax :+33 5 55 06 88 88 DPX 3 250 Electronic + earth leakage CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. ELECTRICAL AND MECHANICAL

More information

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 Functions and characteristics Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 NT and NW selection criteria Masterpact NT Masterpact NW NT06, NT08, NT10, NT12, NT16 NT06, NT08, NT10

More information

Manual Motor Starters. Meta-MEC

Manual Motor Starters. Meta-MEC Manual Motor Starters Meta-MEC Manual Motor Starters LS Meta-MEC Manual Motor Starters provide completed ranges up to 100A 45 mm 55 mm 32AF 2 2 45 mm 70 mm 63AF 100AF 3 3 Manual LS Meta-MEC Motor Starters

More information

Industrial Contactors CTX 3 3P 185A - 800A

Industrial Contactors CTX 3 3P 185A - 800A 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 Industrial Contactors CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Installation - Connection...

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

DPX Magnetic only

DPX Magnetic only 87045 LIMOGES Cedex Phone :+33 5 55 06 87 87 Fax :+33 5 55 06 88 88 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. ELECTRICAL AND MECHANICAL CHARACTERISTICS 3 5. CONFORMITY

More information

Phase + Neutral, neutral on right side

Phase + Neutral, neutral on right side 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34

More information

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX 3 4500 A / 6 ka CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features Standard Features Table : Standard Features GV2ME GV2P GV3P GV7RE/GV7RS 0. to 32 A Up to 20 hp @ 460 V 0 SCCR @ 480 V Push Button Operator 0. to 30 A Up to 5 hp @ 460 V 50 SCCR @ 480 V Rotary Handle Operator

More information

6300A 15 Optibreak B1 & B2 Optibreak B1 & B2 50/60 Hz Ue Icu [v] [ka] 415 65 690 40 4h 4i 1. Open / close Indication 2. Charge and Discharge Indicator 3. Release the reset button 4. Laser Nameplate

More information

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when

More information

3VT Kompaktleistungsschalter bis 630A

3VT Kompaktleistungsschalter bis 630A Katalog LV 36 AT Österreich - Auszug 2012 3VT Kompaktleistungsschalter bis 630A SENTRON Schutz-, Schalt- und Messtechnik www.siemens.com/lowvoltage 3VT1 Molded Case Circuit Breakers up to 160 A 1 Technical

More information

Vistop TM isolating switches 63 to 160A

Vistop TM isolating switches 63 to 160A DX 3 - IS main switches 16 to 125A Vistop TM isolating switches 63 to 160A 225 15 225 18 4 064 00 4 064 59 Pack Cat. No. Main switches AC 22 A category as per EN607-3 Grey handle Accept 1 signalling auxiliary

More information

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1.

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1. 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 LEXIC MCB s DX-H 80A, 100A, 125A Curv urves B and C CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1

More information

Wall mounted switchgear

Wall mounted switchgear Contents Safepact 2... pages /2 to / Enclosed MCCBs 6 to 60A... page /2 Enclosed switch disconnectors 100 to 60A... page / Earth leakage.... page /4 Auxiliaries and accessories... page /5 Enclosed Interpact...page

More information

Overcurrent releases - description, specifications, characteristics specifications specifications description...

Overcurrent releases - description, specifications, characteristics specifications specifications description... BA5*37 COMMERCIAL INFORMATION Type designation specification for ordering...68 (design and circuit breaker and switch-disconnector accessories selection, circuit breaker rated current selection) Connecting

More information

COMMERCIAL INFORMATION TECHNICAL INFORMATION BA511*33

COMMERCIAL INFORMATION TECHNICAL INFORMATION BA511*33 BA511*33 COMMERCIAL INFORMATION Type designation specification for ordering...146 (design and circuit breaker and switch-disconnector accessories selection, circuit breaker rated current selection) Connecting

More information

RX 3 MCB 4500 A Phase + Neutral, neutral on left side

RX 3 MCB 4500 A Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 RX 3 MCB 4500 A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20EJ

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20EJ Innovators in Protection Technology TemBreak Total Protection, Complete Control Catalogue No. 0 - IEJ Mission Statement. Terasaki aims to be the best supplier of circuit breakers and associated equipment

More information

3VT1 Molded Case Circuit Breakers up to 160 A

3VT1 Molded Case Circuit Breakers up to 160 A Siemens AG 4 VT Molded Case Circuit Breakers up to 6 A Catalog Technical Information VT Molded Case Circuit Breakers up to 6 A / General data / Circuit breakers Switch disconnectors Accessories and Components

More information

Electronic circuit breaker EBU10-T

Electronic circuit breaker EBU10-T Description The electronic circuit protector type EBU10-T (Electronic Breaker Unit) provides selective overcurrent protection in AC 230 V UPS systems. It consists of an MCB approved for short circuit interruptions

More information

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2. Index Index Page Manual Motor Starters 1 Auxiliary Contact Blocks 1 Trip Alarm Auxiliary 1 Switch Shunt Release 1 Under-voltage Release 2 Accessories 2 Busbar Connectors 2 Enclosures 2 Leistung, kw C mv

More information

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A Fuse protection The solution for > Motor load break > Protection of industrial cabinet > Electrical distribution fusom_063_b_1_cat Strong points > Tripping upon overload > High breaking capacity > Improved

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications Student Resource Building University of California Santa Barbara Clement Fung Lighting Electrical Option APPENDIX E Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection

More information

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20E

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20E Innovators in Protection Technology TemBreak Total Protection, Complete Control Catalogue No. 05 - I0E Terasaki (Europe) Ltd Terasaki Europe Ltd was established in 97 and is located near Glasgow, Scotland

More information

Catalogue No. 10!64E.

Catalogue No. 10!64E. www.terasaki.co.jp Catalogue No. 10!6E TBLE OF CONTENTS 1. Ratings and Specifications 1-1 Molded Case Circuit Breakers zfixed thermal and fixed magnetic MCCBs 1-2 cswitch-disconnectors 1- xdjustable thermal

More information

Low Voltage. EasyPact CVS. Moulded-case circuit breakers from 16 to 100 A

Low Voltage. EasyPact CVS. Moulded-case circuit breakers from 16 to 100 A Low Voltage EasyPact CVS Moulded-case circuit breakers from 16 to 100 A Catalogue 2013 EasyPact CVS Contents Functions and characteristics A-1 Installation recommendations B-1 Dimensions and connection

More information

New DMX 3. Efficient protection up to A AIR CIRCUIT BREAKERS PRODUCT GUIDE

New DMX 3. Efficient protection up to A AIR CIRCUIT BREAKERS PRODUCT GUIDE New DMX 3 Efficient protection up to 4 000 A AIR CIRCUIT BREAKERS PRODUCT GUIDE NEW DMX 3 ACBs UP TO 4 000 A EFFICIENT PROTECTION AND CONTROL FOR ALL TYPE OF BUILDINGS 02 Electrical panel equipped with

More information

DX³ RCCBs - ID 4P up to 100 A

DX³ RCCBs - ID 4P up to 100 A 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ s - ID CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Prisma ipm Switchboard Air Circuit Breaker (ACB) Moulded-case Circuit Breaker (MCCB) Contactor Power meter

Prisma ipm Switchboard Air Circuit Breaker (ACB) Moulded-case Circuit Breaker (MCCB) Contactor Power meter 3 Prisma ipm Switchboard Air Circuit Breaker (ACB) Moulded-case Circuit Breaker (MCCB) Contactor Power meter The easy choice for quality, value, and peace of mind Schneider Electric makes it an easy choice

More information

SD Series Non-Fused Load Switches

SD Series Non-Fused Load Switches SD Series Non-Fused Load Switches The SD1 and SD2 series of non-fused load switches are listed as Manual Motor Controllers and are designed for use in local motor isolation. The SD series of modular load

More information

Fuse switch-disconnectors

Fuse switch-disconnectors Fuse switch-disconnector FH00 is intended fuse-links with blade contacts size 000 and 00. It enables safe disconnection not only of rated current, but also overcurrent up to octuple rated current. A version

More information

Magnetic Overcurrent Circuit Breaker

Magnetic Overcurrent Circuit Breaker Magnetic Overcurrent Circuit Breaker 808-... Description ngle pole miniaturised magnetic circuit breakers with unique highspeed operating mechanism and push/pull on/off manual actuation. Fitted with electrically

More information

Protection and Connection Motorized and automatic transfer switches IEC Technical guide

Protection and Connection Motorized and automatic transfer switches IEC Technical guide Protection and Connection Motorized and automatic transfer switches IEC 61439 Technical guide Motorized change-over switches Uninterrupted power supply with motorized functionality ABB offers a wide variety

More information

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors MOTOR STARTERS SM Basic function Switching and protection of motors up to A Protection against short-circuit and protection against overload The device responds to phase failure The device is provided

More information

1 Phase electronic contactor (SC 1)

1 Phase electronic contactor (SC 1) 1 Phase electronic contactor (SC 1) - Rated operational voltage up to 600VAC 50/60 Hz - Rated operational current up to 15/30A/50/63A AC-1 - Control voltage from or - Compact modular design 22.5, 45, or

More information

DPX 630 Electronic release

DPX 630 Electronic release 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND MECHANICAL CHARACTERISTICS

More information

Instantaneous tripping TYPE B, C, D TYPE B, C TYPE B, C, D TYPE B, C IEC RCCB TYPE C IEC61008 RCBO 25, 40, 63A. IEC61009 Isolating Switch

Instantaneous tripping TYPE B, C, D TYPE B, C TYPE B, C, D TYPE B, C IEC RCCB TYPE C IEC61008 RCBO 25, 40, 63A. IEC61009 Isolating Switch Features (1) All models fully comply with IEC regulations (2) Units can be mounted on a standard 35mm IEC rail (3) Residual current circuit breakers use an original Mitsubishi Electric IC securing reliable

More information

DPX 1600 Electronic release

DPX 1600 Electronic release 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 1600 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND

More information

DPX Electronic. Fiche technique : F01362EN/02 Mise à jour le : 15/12/2011 Créé le : 15/06/2011

DPX Electronic. Fiche technique : F01362EN/02 Mise à jour le : 15/12/2011 Créé le : 15/06/2011 87045 LIMOGES Cedex Phone :+33 5 55 06 87 87 Fax :+33 5 55 06 88 88 DPX 3 250 Electronic Reference(s): 420 302/305/307/309/312/315/317/319/332/335/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3.

More information

Protection Equipment

Protection Equipment Protection Equipment Price Groups 101, 102, 121, 131, 143 /2 Introduction Motor Starter Protectors/ Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors up to 40 A new /7 General data /13 For motor protection

More information

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series Selection 3-pole shockproof contactors FG d.c. supply Selection guide for utilisation categories DC-1 to DC-5 Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current

More information

DX³ RCBO 4500/6 ka Phase + Neutral, neutral on left

DX³ RCBO 4500/6 ka Phase + Neutral, neutral on left 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX³ RCBO 4500/6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...

More information

D509E. Manual Motor - Starters

D509E. Manual Motor - Starters D509E Manual Motor - Starters Index Page Manual Motors Starters 182 Auxilliary Contact Blocks 182 Trip Alarm Aux. Switch 182 Shunt Release 182 Under-voltage Release 183 Accessories 183 Busbar Connectors

More information

Low voltage. Masterpact NT and NW. LV power circuit breakers and switch-disconnectors Draw-out Type & Fixed Type. Catalogue

Low voltage. Masterpact NT and NW. LV power circuit breakers and switch-disconnectors Draw-out Type & Fixed Type. Catalogue Low voltage Masterpact NT and NW LV power circuit breakers and switch-disconnectors Draw-out Type & Fixed Type Catalogue 2015 Functions and characteristics Circuit breakers and switch-disconnectors NT06

More information

Product index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4.

Product index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4. Product index -....1.3 Features and benefits...1 General information Suitable applications...2 -.3 Motor ratings... Pilot duty ratings and overload trip classes...5 Ordering details Type MS116...6 Type

More information

OPERATING CHARACTERISTICS

OPERATING CHARACTERISTICS TEMBREAK 2 MOULDED CASE CIRCUIT BREAKERS 16A TO 630A 1. Welcome to TemBreak 2 2. Ratings and Specifications 3. Operating Characteristics Thermal Magnetic Protection 23 Thermal Magnetic Time / Current Characteristics

More information

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866)

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866) .4 Miniature Circuit Breakers and Supplementary Protectors SPHM Supplementary Protector SPHM Supplementary Protector Product Description The SPHM Supplementary Protector is a dual rated product for both

More information

Essential equipment for all your requirements

Essential equipment for all your requirements NEW CTX CONTACTORS Essential equipment for all your requirements 9 A TO 310 A THREE-POLE INDUSTRIAL CONTACTORS CTX three-pole industrial contactors, a sense of family The new range of CTX contactors provides

More information

BETA Switching Switches and Light Indicators

BETA Switching Switches and Light Indicators Siemens AG 2008 BETA Switching /2 Product overview /3 5TE8 control switches / 5TE4 pushbuttons /2 5TE5 light indicators /5 5TE8 ON/OFF switches /22 5TE9 busbars /24 5TE switch disconnectors Siemens ET

More information

ME 07 Air Circuit Breakers. ME 07 - Air Circuit Breakers. Low Voltage. Low Voltage. Low Voltage

ME 07 Air Circuit Breakers. ME 07 - Air Circuit Breakers. Low Voltage. Low Voltage. Low Voltage Low Voltage ME 07 - Air Circuit Breakers ME 07 Air Circuit Breakers Low Voltage AEG Niederspannungstechnik GmbH & Co KG Berliner Platz 2-6 D-24534 Neumünster (Germany) Tel. +49/43211-0 Fax +49/43211-144

More information

Product index. 4 - Manual motor protectors. Phone: Fax: Web: -

Product index. 4 - Manual motor protectors. Phone: Fax: Web:  - Product index -....1.3 Features and benefits...1 General information Suitable applications...2 -.3 Motor ratings... Pilot duty ratings and overload trip classes...5 Ordering details Type MS116...6 Type

More information

The Ultimate Safety Breaker

The Ultimate Safety Breaker The Ultimate Safety Breaker OUR CUSTOMER CARE COMMITMENTS Quality is Guaranteed All products supplied from this catalogue carry a guarantee against defects in materials and workmanship for a period of

More information

Section Contents. 1. Introduction 2-5. Salient features, internal & general appearance of Drawout ACB

Section Contents. 1. Introduction 2-5. Salient features, internal & general appearance of Drawout ACB 1 Section Contents PAGES 1. Introduction 2-5 Salient features, internal & general appearance of Drawout ACB 2. Ratings & Specifications 6-9 Free air & enclosed thermal current ratings for AC & DC applications

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 630

DPX Thermal magnetic and trip-free switches DPX 3 -I 630 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS 2 6. CONFORMITY

More information

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI . Technical Data and Specifications Ratings Frames EG, JG and LG EG JG LG Maximum rated current (amperes) 15, 160 1 50 400, 630 Breaker type 3 B B E S S H H C E S H C U X E S H C U X of poles 1, 3, 4,

More information

MOULDED CASE CIRCUIT BREAKERS BC160N

MOULDED CASE CIRCUIT BREAKERS BC160N D MOULDED CASE CIRCUIT BREAKERS BC6N Tento výrobek byl vyvinut za finanční podpory ze státních fondů prostřednictvím Ministerstva průmyslu a obchodu. D BC6N COMMERCIAL INFORMATION Circuit breakers...d4

More information

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24

More information

Modeion MOULDED CASE CIRCUIT BREAKERS BL1600S

Modeion MOULDED CASE CIRCUIT BREAKERS BL1600S H MOULDED CASE CIRCUIT BREAKERS BL6S H BL6S COMMERCIAL INFORMATION Switching units, withdrawable device...h4 Overcurrent releases...h5 Signalling units...h5 Residual current monitor...h6 Current transformers

More information

and other modular devices for low voltage installation

and other modular devices for low voltage installation Technical catalogue System and other modular devices for low voltage installation 2CSC400002D0204 SUMMARY Introduction Miniature Circuit-Breakers Residual Current Devices Auxiliary elements and accessories

More information

ATyS. 63 to 3200 A. Functions. Conformity to standards. General characteristics. Changeover switches. Functions

ATyS. 63 to 3200 A. Functions. Conformity to standards. General characteristics. Changeover switches. Functions to 00 A Accessories Enclosed Characteristics M e atysm_007_a cat M s atysm_0_a cat products are and 4pole switches remotely controlled by volt free contacts ( ) or automatic transfer switches ( ). They

More information

DSE201 Compact design with enhanced protection

DSE201 Compact design with enhanced protection DSE201 Compact design with enhanced protection The best of safety DSE201 6 ka: the highest level of reliability The 1P+N electronic residual current circuit-breakers with overcurrent protection (RCBOs)

More information

Series KTU7 UL489 Molded Case Circuit Breakers

Series KTU7 UL489 Molded Case Circuit Breakers Series UL489 Molded Case Circuit Breakers Versatile, convenient and space saving for a variety of applications Sprecher+Schuh s series of UL are UL489 and CE listed for global applications. The current

More information

The effective choice The benefits of a product with the highest quality standards

The effective choice The benefits of a product with the highest quality standards The effective choice The benefits of a product with the highest quality standards Compact size for easy installation in small spaces and retrofitting of already existing facilities. Terminals designed