1 Zero Energy Verification An Alternative Approach Timothy Snow CESCP Electrical Safety Officer
2 Hierarchy of Risk Control Methods In Order from Safest to Least Safe Elimination Substitution Minimizes Human Error Engineering Controls Awareness Administrative Controls Personal Protective Equipment NREL 2
3 Establishing An Electrically Safe Work Condition NFPA 70E 2018 Article ) Determine all possible sources of electrical supply to the specific equipment. 2) After properly interrupting the load current, open the disconnecting device(s) for each source. 3) Wherever possible, visually verify that all blades of the disconnecting devices are fully open or that drawout-type circuit breakers are withdrawn to the fully disconnected position. 4) Release stored electrical energy. 5) Release or block stored mechanical energy. 6) Apply lockout/tagout devices in accordance with a documented and established procedure. Steps 1 through 6 are Administrative NREL 3
4 Establishing An Electrically Safe Work Condition Zero Energy Verification 7) Use an adequately rated portable test instrument to test each phase conductor or circuit part to verify it is deenergized. Test each phase conductor or circuit part both phase-to-phase and phase-to-ground. Before and after each test, determine that the test instrument is operating satisfactorily through verification on any known voltage source. Step 7 is Energized Work exposing the worker to potential shock and arc-flash hazards. NFPA 70E 2018 Article NREL 4
5 Establishing An Electrically Safe Work Condition 120.5(7) Zero Energy Verification Exception No. 1: An adequately rated permanently mounted test device shall be permitted to be used to verify the absence of voltage of the conductors or circuit parts at the work location, provided it meets the all following requirements: (1) It is permanently mounted and installed in accordance with the manufacturer s instructions and tests the conductors and circuit parts at the point of work; (2) It is listed and labeled for the purpose of verifying the absence of voltage; (3) It tests each phase conductor or circuit part both phase-to-phase and phase-to-ground; (4) The test device is verified as operating satisfactorily on any known voltage source before and after verifying the absence of voltage. **If Exception 1 is implemented the Zero Energy Verification is not Energized Work. Risk is Minimized Chance of Human Error is Minimized NFPA 70E 2018 Article NREL 5
6 PANDUIT VeriSafe Absence of Voltage Tester (AVT) Panduit Corporation The first commercially available device that meets the criteria for 120.5(7) Exception 1. NREL 6
7 VeriSafe Highlights Can be used with circuits up to 600 Volts AC or DC Works with: 120 VAC Single Phase Three Phase Absence of Voltage Threshold 3V Capacitors DC Rated Category III at 600V, Category IV at 300V NREL 7
8 Sample One-Line of a VeriSafe Installation NREL 8
9 Operation Above Energized Circuit Upper Right De-Energized Circuit Lower Right Successfully Completed Absence of Energy NREL 9
10 Installation Example Installation using Piercing Taps on 600 MCM 480V-3PH-800A Incident Energy 3.3 Cal/cm 2 NREL 10
11 Cleanroom Installation Installation in NREL s Clean Room 480V-3PH-50A No Arc Flash NREL 11
12 Installation Using Crimp-Style Connectors 208V 110A Incident Energy 3.1 Cal/cm 2 NREL 12
13 Questions? NREL 13
14 Thank you This work was authored by the National Renewable Energy Laboratory, operated by Alliance for Sustainable Energy, LLC, for the U.S. Department of Energy (DOE) under Contract No. DE-AC36-08GO Funding provided by U.S. Department of Energy Office of Energy Efficiency and Renewable Energy. The views expressed in the article do not necessarily represent the views of the DOE or the U.S. Government. The U.S. Government retains and the publisher, by accepting the article for publication, acknowledges that the U.S. Government retains a nonexclusive, paid-up, irrevocable, worldwide license to publish or reproduce the published form of this work, or allow others to do so, for U.S. Government purposes.
15 NREL 15
Electrical Safety and Overcurrent Protection
Electrical Safety and Overcurrent Protection Dave Vallier DSE Bussmann division Contact info: Phone: 586-201-1348 Email: Davemvallier@eaton.com Agenda 1. Electrical hazards overview 2. The role of the
More informationBP OIL -- TOLEDO REFINERY
BP OIL -- TOLEDO REFINERY Document Type: Procedure Effective Date: August 31, 2017 Owner: Dane P. Clark Refinery Wide Electrical Distribution System Switching and Isolation Auth. By: Rick J. Chmelovski
More informationNon-Beam Hazard - Electricity
Non-Beam Hazard - Electricity 2013 DOE LSO Workshop - NIST Heath Garrison September 1, 2013 NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy,
More informationElectrical Safety CSA Z462 & NB Regulations
Electrical Safety CSA Z462 & NB Regulations WorkSafeNB s 2014 Health and Safety Conference Daniel Roberts Senior Manager, Electrical Safety Consulting at Schneider Electric Vice-chair CSA Z462 daniel.roberts@schneider-electric.com
More informationMarket Drivers for Battery Storage
Market Drivers for Battery Storage Emma Elgqvist, NREL Battery Energy Storage and Microgrid Applications Workshop Colorado Springs, CO August 9 th, 2018 Agenda 1 2 3 Background Batteries 101 Will storage
More informationSM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety
SM-1700 Secondary Shunt Trip Coil Assembly Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly SM-1700 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com
More informationECET 211 Electric Machines & Controls Lecture 1-3 (Part 2) Electrical Safety in the Workplace Electrical Safety in the Workplace
ECET 211 Electric Machines & Controls Lecture 1-3 (Part 2) Electrical Safety in the Workplace Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Other
More informationReducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer
Reducing Arc Energies with Current Limiting Fuses arc flash note 2 By mike lang, Principal field engineer Why Use Current Limiting Fuses Current limiting fuses can reduce both the magnitude and duration
More informationNFPA 70E Electrical Safety in the Work Place. R. Casey 2/1/05
NFPA 70E Electrical Safety in the Work Place R. Casey 2/1/05 The Other Electrical Hazard Arc flash: high-intensity intensity flash (eye damage) and superheated ball of gas (skin burns and melting)created
More informationAgenda / ESPS Electrical Safety Program Solutions INC.
PEM Partners in Training Asset Management & Reliability Risk Assessment in the new CSA Z462 Electrical Power Distribution Reliability & Safety, a Valuable Balance Terry Becker, P.Eng., NFPA CESCP Owner,
More informationELECTRICAL GROUNDING SAFETY PROGRAM
ELECTRICAL GROUNDING SAFETY PROGRAM PURPOSE / SCOPE The purpose of this program is to ensure the proper installation, maintenance, inspection, and testing of equipment grounding conductors on construction
More informationWhat is electricity? A form of energy that is carried through wires and is used to operate machines, lights, etc. PPT-SM-ES
Electrical Safety What is electricity? A form of energy that is carried through wires and is used to operate machines, lights, etc. PPT-SM-ES 2015 2 There are two forms of electricity Static electricity
More informationIB PowlVac ITE-HK Remote Racking Device
IB-51802 PowlVac ITE-HK Remote Racking Device for use with ITE-HK 5kV & 15kV Circuit Breakers and PowlVac ITE-HK 5kV & 15kV Replacement Circuit Breakers Powered by Safety PowlVac ITE-HK Remote Racking
More informationSolar Photovoltaic (PV) Installation - Updates
Solar Photovoltaic (PV) Installation - Updates Malcolm Brown CCEI Electrical Safety Authority Technical Advisor - Western Region Electrical Safety Authority 2013 1 For Your Safety Topics of discussion
More informationElectrical Hazards in Construction
Electrical Hazards in Construction WELCOME Tim Dawson Presentation developed by Dawson Safety Services - 2013 Dangers of Electrical Shock Currents above 10 ma* can paralyze or freeze muscles. Currents
More informationJanuary 30, Ms. Safety Director Sample Medical Corp. PO Box X Somewhere, CT. Re: NFPA 70E Hazard Assessment. Date of Visit.
3018 Eastpoint Parkway Louisville, KY 40223 (502) 716-7073 January 30, 2006 Ms. Safety Director Sample Medical Corp. PO Box X Somewhere, CT Re: NFPA 70E Hazard Assessment Date of Visit January 24, 2006
More informationWhat is electricity? A form of energy that is carried through wires and is used to operate machines, lights, etc. PPT-SM-ES
Electrical Safety What is electricity? A form of energy that is carried through wires and is used to operate machines, lights, etc. PPT-SM-ES 2015 2 There are two forms of electricity Static electricity
More informationSECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT
SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.
More informationAVOIDING ELECTROCUTION HAZARDS
Print AVOIDING ELECTROCUTION HAZARDS MODULE DESCRIPTION This module will provide information that helps you recognize and avoid common electrocution hazards in your work environment. OBJECTIVES After completing
More informationBackfeed, Safety, and Work Practices
Backfeed, Safety, and Work Practices Michael T. Sheehan, P.E. March, 2015 NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, operated by the
More informationUnrestricted. S.Mukhopadhyay
Unrestricted S.Mukhopadhyay 10.09.15 Electrical safety A report says that every year 5500 Indians die due to electric shock and 800 due to electric fire. 12% work place death due to electrocution ELECTRICAL
More informationEnsuring the Safety Of Medical Electronics
Chroma Systems Solutions, Inc. Ensuring the Safety Of Medical Electronics James Richards, Marketing Engineer Keywords: 19032 Safety Analyzer, Medical Products, Ground Bond/Continuity Testing, Hipot Testing,
More informationMark Lyvers LLC / Cooper Bussmann Arc Flash Script Script to accompany PowerPoint on New 2002 NEC Arc Flash Hazard Marking Requirement
Mark Lyvers LLC / Cooper Bussmann Arc Flash Script Script to accompany PowerPoint on 110.16 New 2002 NEC Arc Flash Hazard Marking Requirement Slide 1 Suggestion on How to Use Download both the Mark Lyvers
More informationBP-Husky Refinery Toledo, OH
BP-Husky Refinery Toledo, OH Document Type: Procedure Refinery Wide Procedure No.: SAF 095 Effective Date: 2/25/16 Owner: D. Clark Working on or near Energized Electrical Equipment Rev. No.: 6 Auth. By:
More informationHazards SAFETY CORNER. of Establishing an. Work Condition
Hazards of Establishing an Electrically Safe Work Condition Written By Tony Demaria & Dean Naylor, Tony Demaria Electric, Mose Ramieh, III, Power Generation & Testing When working around electrical equipment,
More informationREDUCE RISK WITH PESDS MAKING NFPA 70E COMPLIANCE SAFER
REDUCE RISK WITH PESDS MAKING NFPA 70E COMPLIANCE SAFER Philip B. Allen Grace Engineered Products, Inc. 5001 Tremont Avenue Davenport, Iowa 52807 USA Page 1 / www.graceport.com Outline I. INTRODUCTION
More informationWIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST
WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.
More informationCOOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN
Voltage Regulators MN225064EN Effective March 2017 Supersedes October 2011 (S225-60-12) Testing a motor capacitor on a voltage regulator procedure instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES
More information120-ELECTRICAL SAFETY PROGRAM
120.1 PURPOSE A. To set forth procedures for the safe use of electrical equipment, tools, and appliances at Central New Mexico Community College (CNM). 120.2 SCOPE A. This program applies to all CNM employees
More informationMASTERsine Inverter PXA Series Installation Guide
Backup Power System Expert TM MASTERsine Inverter PXA Series Installation Guide Important Safety Instructions IMPORTANT: Read and save this Installation Guide for future reference. This chapter contains
More informationEnergized Electrical Work
Manitoba STANDARD PROCEDURE INSTRUCTION Title Energized Electrical Work Department Supersedes SPI Dated N/A SPI 32-4 Effective Date MAR 30, 2012 Energized Electrical Work SPI 32-4 Page 1 of 9 STANDARD
More informationService Requirements
Service Requirements General Contact Idaho Power before beginning work on any new service. All meter installations must meet current electrical code requirements and display the proper electrical permit.
More informationDefinitions. Exposed part. Live or energized part. De-energized part
Electrical Safety Definitions Exposed part Live or energized part De-energized part 1a Definitions De-energized exposed parts that are not locked/tagged are considered to be energized exposed parts 1b
More informationS&C Vista Underground Distribution Switchgear
S&C Vista Underground Distribution Switchgear Pad-Mounted, Vault-Mounted, and UnderCover Styles Instructions For Installation and Operation of Portable Motor Operator TABLE OF CONTENTS Section Page Section
More informationInstruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.
Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V6-4A00 www.usa.siemens.com/sdv7 Hazardous voltages and stored
More informationINDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH LIGHTING SYSTEMS AND OTHER ELECTRICAL EQUIPMENT All electrical systems and electrically energized equipment
More informationArc flash solutions catalogue Australia. Safety solutions - Protecting employees and the enterprise
Arc flash solutions catalogue Australia Safety solutions - Protecting employees and the enterprise The risk of an arc flash event is real An arc flash hazard is a proven significant and dangerous threat
More informationElectrical Safety in the Workplace
Electrical Safety in the Workplace Increasing Electrical Safety in the Workplace through Purchasing and Procurement Robert Mitchell, Safety and Technical Safety Advisor Safety Risk, Policy and Innovation
More informationSafety Training Topic ELECTRICAL SAFETY
Safety Training Topic Purpose of Meeting To remind workers that electrical hazards can result in a serious injury. To reinforce electrical safety rules. To consider ways to protect yourself from electrical
More informationService Requirements
Service Requirements General Contact Idaho Power before beginning work on any new service. All meter installations must meet current electrical code requirements and display the proper electrical permit.
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationINSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL
Photovoltaic (PV) Residential Page 1 of 10 Revision Date: 07/18/2018 INSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL INSPECTION CODE: 703 SCOPE: RESIDENTIAL APPLICABLE CODES: 2016 CBC, CRC, CPC,
More informationSTATISTICS ELECTRICAL INCIDENTS IN ALBERTA. January 1 to December 31, 2013
Safety Services 16 th floor, Commerce Place Tel: 1-866-421-6929 10155 102 nd Street Fax: 780-427-8686 Edmonton, Alberta Canada T5J 4L4 STATISTICS ELECTRICAL INCIDENTS IN ALBERTA January 1 to December 31,
More informationDESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5
DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this
More informationElectrical Safety Program
Electrical Safety Program Medford Area Public School District 124 West State St School District: Medford, WI 54451 715 748 4620 Review Date(s): January 2018 Program Dave Makovsky Coordinator: Purpose and
More informationElectrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1
Webinar 1 Electrical 2 1 Webinar Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due to electrical shock)
More informationCalifornia State University Bakersfield Electrical Safety Program. Revised November 2017
California State University Bakersfield Electrical Safety Program Revised November 2017 THIS PAGE INTENTIONALLY LEFT BLANK Contents 1.0 PURPOSE... 3 2.0 SCOPE... 3 3.0 REFERENCES... 4 4.0 DEFINITIONS...
More informationCPS 3Phs String Inverters NEC 2014 Compliance
Application Note: NEC 2014 Compliance Revision: 062016 CPS 3Phs String Inverters NEC 2014 Compliance This application note describes the major changes within the NFPA 70, National Electric Code, specifically
More informationShort Circuit/Coordination & Arc Flash Study Specifications
Delphi Short Circuit/Coordination & Arc Flash Study Specifications April 28, 2005 Short Circuit/Coordination & Arc Flash Specification Table of Contents I. General Overview 3 II. Engineering Firm Requirements..
More informationWastewater Solutions
Wastewater Solutions Featuring Meltric s Switch-Rated Plugs, Receptacles and Electrical Connectors meltric.com A company of MARECHAL ELECTRIC GROUP Meltric DECONTACTOR TM Series Plugs & Receptacles Decontactors
More information6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton
Advances in technology to address safety Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton 1 Advances in technology could mean use existing technology & back to basics Advances in safety are
More informationTaxonomies, Classifications, and Categories CIRCUIT BREAKING, COMPRESSOR, CONVEYOR, MOTOR GENERATOR SET, POLARIZED, WELDER
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 AP20467S22 3W-4P 200A Plug Cooper Crouse-Hinds Catalog Number AP20467S22 Manufacturer Cooper Crouse-Hinds Description
More informationRENEWABLE ENERGY PROGRAM Step 1, Section 1 ENROLLMENT FORM FOR LEASED RESIDENTIAL AND SMALL COMMERCIAL PHOTOVOLTAIC AND WIND TURBINE SYSTEMS
RENEWABLE ENERGY PROGRAM Step 1, Section 1 ENROLLMENT FORM FOR LEASED RESIDENTIAL AND SMALL COMMERCIAL PHOTOVOLTAIC AND WIND TURBINE SYSTEMS For residential and commercial systems, the combined generation
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Universal Air Series!! NOTE!! Covers the following model: 6000 Series 85-0100B-AZ Rev 0 5/07 To ensure that the system is installed properly, provide your electrician with these
More informationECET 211 Electric Machines & Controls Lecture 1-4 (Part 1) Electrical Safety in the Workplace Electrical Safety in the Workplace
ECET 211 Electric Machines & Controls Lecture 1-4 (Part 1) Electrical Safety in the Workplace Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Other
More informationPerfectSpeed NEMA 48 Pump Motor. With User Interface
PerfectSpeed NEMA 48 Pump Motor With User Interface Table of Contents Section 1 - PerfectSpeed Motor... 1 Important Safety Information...1 Overview...3 PerfectSpeed User Interface Box...4 Minimum and Maximum
More informationPower Arc Testing on Insulator Sets
Power Arc Testing on Insulator Sets Abstract:Insulator sets are among the most common components in transmission networks and their quality and performance play a vital role in ensuring a reliable electricity
More informationIntegrating Roles Within Electric Utilities to Achieve Arc Flash Safety. MIPSYCON Presenters Neil Stiller & Bob Cooke
Integrating Roles Within Electric Utilities to Achieve Arc Flash Safety MIPSYCON - 2018 Presenters Neil Stiller & Bob Cooke Presenters Neil Stiller, Sr. Electrical Engineer, RPU 30 years utility experience,
More informationIllinois State University. Electrical Safety Procedure
Illinois State University Electrical Safety Procedure Illinois State University Facilities Management Revision Date: May 2014 Illinois State University Facilities Management Electrical Safety Procedure
More informationELECTRICAL HAZARD EXAMPLES
ELECTRICAL HAZARD EXAMPLES UNFORTUNATELY, THE EVENTS LISTED BELOW ARE MORE COMMON THAN YOU WOULD EXPECT Circuit breaker does not open the circuit when operated manually or remotely. The contacts within
More informationUser Guide. Model Insulation Tester / Megohmmeter
User Guide Model 380260 Insulation Tester / Megohmmeter Introduction Congratulations on your purchase of Extech s Insulation Tester/Megohmmeter. The Model 380260 provides three test ranges plus continuity
More informationQuick Connection Panel (QCP) Installation Guide
Quick Connection Panel (QCP) Installation Guide DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read this document first. The installer is responsible for compliance with National Electrical
More information8300 Series Installation Guidelines
1-800-443-4859 8300 Series Installation Guidelines WARNING: RISK OF ELECTRICAL SHOCK OR BURNS. THIS CONVERTER ASSEMBLY SHOULD BE INSTALLED BY A QUALIFIED ELECTRICIAN OR CERTIFIED RV TECHNICIAN. IMPROPER
More informationAn average of one worker is electrocuted on the job every day There are four main types of electrical injuries:
Electrical Safety Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due to electrical shock) Electrical shock
More informationElectrical Safety - Protecting Yourself Against Electrical Injuries. from NIOSH Electrical Safety Student Manual
Electrical Safety - Protecting Yourself Against Electrical Injuries from NIOSH Electrical Safety Student Manual Oct 9 11:26 AM 1 Electricity is Dangerous There is a risk of an electrical injury - 1. Whenever
More informationCOOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing
Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification
More informationCP-250E-60/72-208/240-MC4 Microinverter with Modular Trunk Cable
CP-250E-60/72-208/240-MC4 Microinverter with Modular Trunk Cable Chilicon Power Aug 2016 1 CONTENTS CP-250E Microinverter System... 3 The CP-100 Cortex Gateway... 3 Important Safety Information... 4 Inverter
More informationPATENT PENDING. Phone: (877) Operation and Service Manual
PATENT PENDING Phone: (877) 544-2291 Operation and Service Manual 2 IMPORTANT NOTICE This document contains information intended to aid in the proper installation, operation, and maintenance of the product
More informationRental Industry Safety Tester Safe Check 5s
Rental Industry Safety Tester Safe Check 5s Feb 2006 2006 Clare Instruments Inc. Issue 2.0 Firmware Version : 1.2a Limited Warranty & Limitation of Liability Clare Instruments Inc, guarantees this product
More informationibusway for Data Center
ibusway for Data Center PBPQOD Plug-In Units with 15 60 A Circuit Breakers for Use On Busway Straight Sections Class 5600 Installation S1B99523 06/2012 Hazard Categories and Special Symbols Read these
More informationInspector Training Workshops Module One Photovoltaic Labeling based on 2008 NEC
Inspector Training Workshops Module One Photovoltaic Labeling based on 2008 NEC NJCE Market Manager HW Construction Department Wayne, NJ Robert A. Menist Contents Site inspections with attention on Labeling
More informationETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy
ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy ETAP 17 Goodyear, Suite 100 Irvine, CA 92618 White Paper No.001.14-2016 Albert Marroquin, PE Member
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationINTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY
INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,
More informationEquipotential Bonding of Rail Vehicles to Running Rail Potential
Railway Group Standard Equipotential Bonding of Rail Vehicles to Running Rail Potential Synopsis This standard mandates the requirements for equipotenial bonding of rail vehicles to comply with the Electricity
More informationPAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons
Page 1 Qualified Persons... 1 Safety Information... 2 Procedures... 3 Maintenance... 3 Security Inspection (Exterior)... 3 Verify Securing Devices... 3 Maintaining the Exterior... 3 Replacing Labels...
More informationElectrical Safety Policy (EHS-0018)
PAGE 1 OF 20 001 COPY# Electrical Safety Policy OHS-0018 Dates Original: April 2, 2012 Revised: September 09, 2014 Electrical Safety Policy (EHS-0018) For Issued: April 2012 Revised: September 2014 PAGE
More informationNot all Low Voltage Switchgear is created equal
Not all Low Voltage Switchgear is created equal White Paper The must-have solution for power distribution systems Introduction Reliability and safety are the two most important criteria in the proper functioning
More informationBest Practice #71 Adoption of NFPA 70E 2009 In place of NFPA 70E 2004
Facility: DOE Complex Points of Contact: Michael D. Hicks, 208-526-3724, hicksmd@id.doe.gov John P. Schaleger, 509 373-2202, John_P_Schaleger@rl.gov Randy S. Spaniel, 509-373-1146, Randy_S_Spaniel@rl.gov
More informationNATURAL HIGH IMPACT STRENGTH COPPER FREE ALUMINUM Number of Wires VAC AT 50 TO 400 HZ/250 VDC
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 AllenWatson@elliottelectric.com AR331 30 Amp Pin & Sleeve Recpt 3-W 3-P 250VDC/600vac Cooper Crouse-Hinds Catalog Number
More informationPage 1 of 6 NO START - ENGINE CRANKS OKAY General Inspection 1. Ensure proper starting procedure is being used. 2. Visually check vacuum hoses for splits, kinks and improper connections. See underhood
More informationInstruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.
www.usa.siemens.com/sdv7 Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V2-4A00 Answers for infrastructure
More informationUser Guide. Model Insulation Tester / Megohmmeter
User Guide Model 380260 Insulation Tester / Megohmmeter Introduction Congratulations on your purchase of Extech s Insulation Tester/Megohmmeter. The Model 380260 provides three test ranges plus continuity
More informationFuture Proof Your Arc Flash Assessment
Future Proof Your Arc Flash Assessment 2017 ENERGY CONNECTIONS CONFERENCE TRADE SHOW Presented by: Keith Mullen, P.E. November 9, 2017 Agenda > Utility requirements > Study objectives > Applicable standards
More informationQ-Frame Main Circuit Breaker (225 A Maximum) and Adapter Kit Installation onto an NQ Panelboard Class 1640
Instruction Bulletin 4-722-2 /29 Peru, IN, USA Replaces 4-722-1 1/28 Q-Frame Main Circuit Breaker (225 A Maximum) and Adapter Kit Installation onto an NQ Panelboard Class 164 Retain for future use. Introduction
More informationMULTIVOLTAGE PORTABLE BATTERY CHARGER MVM
_ M MULTIVOLTAGE PORTABLE BATTERY CHARGER MVM User's MANUAL Code: MVM Version: 01-BF Date: OCT 2005 Page 1/10 _ 1. INTRODUCTION Before starting to use your Energic plus MVM battery charger, please take
More informationDielectric Withstand Tester
Dielectric Withstand Tester Model HT-20KVPac 0-20,000 Volts AC Output Instruction Manual i Dear Customer: Congratulations! Compliance West USA is proud to present you with your Dielectric Withstand Tester.
More informationDefinitions. Scope. Customer Generation Interconnection Requirements
Updated 02/1 Page 1 Scope The purpose of this document is to describe Idaho Power s requirements for the installation and testing of Customer Generation acilities that are interconnected with Idaho Power
More informationGE Arc Vault TM Protection System. By Mark Clapper GE Specification Engineer. Introduction. What Variables Contribute To An Arcing fault?
By Mark Clapper GE Specification Engineer Introduction To address the increasing concerns and standards around arcing faults, GE challenged our Global Research Center to develop a new, active method of
More informationAppendix E-2. Occupational Safety and Health Administration (OSHA)
Appendix E-2 *IMPORTANT USER NOTE: This document was created in 2014 and is based on Codes and Standards in force in 2014. To use this document properly, the user must refer to the code in force at the
More informationDesign Considerations to Enhance Safety and Reliability for Service Entrance Switchboards
Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards Robert P. Hansen, P.E., PhD GE Specification Engineer Introduction Switchboards are a widely used type of equipment
More informationApplication of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear
ENGINEERING SERVICES 809 Gleneagles Court, Suite 309; Towson, MD 21286 Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear Prepared by: Keith Robertson, PE Staff Power
More informationElectric Vehicle Charging Safety Guidelines Part 2: Selection and Installation Edition DRAFT
Date of publication: 1 November 2016Not yet published Issued by: Mark Wogan, Manager Energy Safety WorkSafe New ZealandNot yet issued Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation
More informationTECHNICAL TOPICS UNIVERSITY. General Electrical Safety BEST PRACTICES
UNIVERSITY TECHNICAL TOPICS BEST PRACTICES General Electrical Safety Abstract Electrical systems by nature are considered extremely dangerous to most human beings as these systems operate under conditions
More informationELECTRICAL SAFETY-RELATED WORK PRACTICES
ELECTRICAL SAFETY-RELATED WORK PRACTICES This checklist is provided to assist organizations in reviewing compliance with OSHA Standard 29 CFR 1910.331 through 1010.335. Refer to the complete Standard for
More informationNot all Low Voltage Switchgear is created equal
White Paper Not all Low Voltage Switchgear is created equal The must-have solution for power distribution systems Prepared by: Tom Hawkins, Consulting Product Engineer Rahul Rajvanshi, Senior Product Engineer
More informationOTEC Transfer switch open transition
Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator
More informationSOLAR PV INSTALLATIONS
Winnipeg Information Bulletin 2016-003-B/E/S/Z SOLAR PV INSTALLATIONS An Information Bulletin is currently being created for City of Winnipeg guidelines for Solar PV Installations and will be published
More informationwww. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE
r \ FIG. 1. Cutaway View of Typical Switch. I.L. 46-723-1 DESCRIPTION INSTALLATION MAINTENANCE INSTRUCTIONS THE INERTEEN AND OIL INSULATED FEEDER SWITCH provides complete switching facilities in a minimum
More information5300 Series Installation Guidelines
1-800-443-4859 5300 Series Installation Guidelines WARNING: RISK OF ELECTRICAL SHOCK OR BURNS. THIS CONVERTER ASSEMBLY SHOULD BE INSTALLED BY A QUALIFIED ELECTRICIAN OR CERTIFIED RV TECHNICIAN. IMPROPER
More information