1 Future Proof Your Arc Flash Assessment 2017 ENERGY CONNECTIONS CONFERENCE TRADE SHOW Presented by: Keith Mullen, P.E. November 9, 2017
2 Agenda > Utility requirements > Study objectives > Applicable standards & methods > Example: Impact of system configuration > Conclusions 2
3 Definition of Arc-Flash Electric Arc-Flashover is defined as the passage of current between two electrodes through ionized gasses and vapors 3
4 Utility Requirements the employer shall ensure that an assessment is performed to determine potential exposure to an electric arc for employees who work near energized parts or equipment. Source: National Electrical Safety Code (NESC) 410A 4
5 Utility Requirements > Prepare arc flash assessment to provide a basis for: > Operating procedures > Equipment needs > Inform employees and contractors of potential exposure Priority #1 SAFETY > Train employees on equipment and operating procedures 5
6 Applicable Standards & Methods > NESC 410.A.3 > NFPA 70E > OSHA 29 CFR, > IEEE Standard 1584 > ARCPRO 6
7 Applicable Methods IEEE 1584 > Voltages in the range of 208 V V, three-phase > Frequencies of 50 Hz or 60 Hz > Bolted fault current in the range of 700 A A > Grounding of all types and ungrounded > Equipment enclosures of commonly available sizes > Gaps between conducts of 13 mm-152 mm > Faults involving three phases Note: A theoretically derived model, based upon Lee s paper [B19], is applicable for three-phase systems in open air substations, and open air transmission and distribution systems. This model is intended for applications where faults will escalate to three-phase faults. Where this is not possible or likely, this model will give a conservative result. Where single-phase systems are encountered, this model will provide conservative results. 7
8 Applicable Methods ARCPRO 8
9 Applicable Standards NFPA 70E Arc Flash Hazard PPE Category (HC) NFPA 70E PPE Categories Calculated Arc Energy (Cal/cm 2 ) (J/cm 2 ) >4 >40 >167.4 > 1.2 Cal/cm 2 is the threshold for a 2 nd degree burn > PPE limits injury to no more than a recoverable 2 nd degree burn 9
10 Applicable Standards OSHA 29 CFR Table 12 Selecting a Reasonable Incident-Energy Calculation Method 1 Incident-Energy Calculation Method 600 V and Less V to 15 kv 2 More than 15 kv 1Φ 3Φa 3Φb 1Φ 3Φa 3Φb 1Φ 3Φa 3Φb NFPA 70E-2004 Annex D (Lee Equation) 3 Y-C Y N Y-C Y-C N N 4 N 4 N 4 Doughty, Neal, and Floyd Y-C Y Y N N N N N N IEEE Std. 1584a Y Y Y Y Y Y N N N ARCPRO Y N N Y N N Y Y 6 Y 6 Key: 1Φ: Single-phase arc in open air 3Φa: Three-phase arc in open air 3Φb: Three-phase arc in an enclosure (box) Y: Acceptable; produces a reasonable estimate of incident heat energy from this type of electric arc N: Not acceptable; does not produce a reasonable estimate of incident heat energy from this type of electric arc Y-C: Acceptable; produces a reasonable, but conservative, estimate of incident heat energy from this type of electric arc 10
11 Revised Standards OSHA 29 CFR Table 14 Selecting a Reasonable Distance from the Employee to the Arc Class of Equipment Single-Phase Arc mm (inches) Three-Phase Arc mm (inches) Cable NA* 455 (18) Low voltage MCCs and panel boards NA 455 (18) Low voltage switchgear NA 610 (24) 5 kv switchgear NA 910 (36) 15 kv switchgear NA 910 (36) Single conductors in air (up to 46 kv), work with rubber insulating gloves 380 (15) NA Single conductors in air, work with live-line tools and live-line bare hand work MAD (2 x kv x 2.54) (MAD (2 x kv /10) ) NA * NA = Not applicable The terms in this equation are: MAD = The applicable minimum approach distance kv = The system voltage in kilovolts 11
12 Revised Standards OSHA 29 CFR Table 13 Selecting a Reasonable Arc Gap Class of Equipment Single-Phase Arc mm (inches) Three-Phase Arc mm 1 (inches) Cable NA 2 13 (0.5) Low voltage MCCs and panel boards NA 25 (1.0) Low voltage switchgear NA 32 (1.25) 5 kv switchgear NA 104 (4.0) 15 kv switchgear NA 152 (6.0) Single conductors in air, 15 kv and less 51 3 (2.0) Phase conductor spacing Single conductor in air, more than 15 kv Voltage in kv times 2.54 (0.1), but no less than 51 mm (2 inches) 3 Phase conductor spacing 1Source: IEEE Std. 1584a NA : Not applicable 3Table 6 of Appendix E of final Subpart V uses a more conservative arc gap that equals the electrical component of the minimum approach distance rather than a value corresponding to the dielectric strength of air for the system voltage which forms the basis for the values in this table. 12
13 Applicable Standards OSHA 29 CFR Exposure Minimum Head and Face Protection None 1 Minimum Head and Face Protection 1 Arc Rated Faceshield with a Minimum Rating of 8 Cals/cm 2 Arc-Rated Hood or Faceshield with Balaclava Single-phase, open air 2 8 Cal/cm Cal/cm 2 13 Cal/cm 2 or higher 2 Three-phase 2 4 Cal/cm Cal/cm 2 9 Cal/cm 2 or higher 3 1. These ranges assume that employees are wearing hardhats meeting the specifications in or (b)(2), as possible. 2. The arc rating must be a minimum of 4 Cal/cm 2 less than the estimated incident energy. Note that (g)(5)(v) permits this type of head and face protection, with a minimum arc rating of 4 Cal/cm 2 less than the estimated incident energy, at any incident energy level. 3. Note that (g)(5) permits this type of head and face protection at any incident energy level. 13
14 The Curve Method Relays > Prepare curves for specific incident energy levels > Compare with device responses for available fault range 14
15 Other Operating Scenarios 15
16 Study Findings Secondary Voltages (2012 NESC) NESC Table Equipment Type Nominal Voltage Range & Cal/cm 2 50V-250V 251V 600V 601V-1000V Self-contained meters / cabinets 4 (2) 20 (4) 30 (8) Pad-mounted transformers 4 (9) 4 (9) 6 (8) CT meters and control wiring 4 (2) 4 (5) 6 (8) Metal-clad switchgear / motor control centers 8 (3) 40 (6) 6 (8) Pedestals / pull boxes / hand holes 4 (2) 8 (7) 12 (8) Open air (includes lines) 4 (2) 4 (7) 6 (8) Network protectors 4 (10) (11) (11) Panel boards single phase (all) / three phase (< 100 A) 4 (2) 8 (12) 12 (8) Panel boards three phase (> 100 A) 4 (2) (13) (13) 16
17 Study Findings Secondary Voltages (2012 NESC) NESC Table Notes 1. This table was developed from fault testing based on equipment type and is independent of fault current unless otherwise noted. Calculations and test data are based on a 46 cm (18 in) separation distance from the arc to the employee. See IEEE Std Other methods are available to estimate arc exposure values and may yield slightly different but equally acceptable results. The use of the table in the selection of clothing is intended to reduce the amount or degree of injury but may not prevent all burns. 2. Industry testing on this equipment by two separate major utilities and a research institute has demonstrated that voltages 50 V to 250 V will not sustain arcs for more than 2 cycles, thereby limiting exposure to less than 4 Cal/cm 2. (See 208-V Arc Flash Testing [B1].) 3. Value based on IEEE 1584 formula for Motor Control Centers. [Gap = 2.54 cm (1 in)] (Xd = 1.641) [46 cm (18 in) distance] 51 ka (Based on a 208 V, 1000 kva, 5.3% Z, served from a 500 MVA system). Maximum duration without circuit protective device operation from industry testing (see 208-V Arc Flash Testing [B1]) is 10 cycles: 46.5 Cal/s/cm 2 x s = 7.8 Cal/cm Industry testing on 480 V equipment indicates exposures for self-contained meters do not exceed 20 Cal/cm Industry testing on 480 V equipment indicates exposures for CT meters and control wiring does not exceed 4 Cal/cm Value based on IEEE 1584 formula for Motor Control Centers. [Gap = 2.54 cm (1 in)] (Xd = 1.641) [46 cm (18 in) distance] 12.7 ka at 480 V (worst-case energy value from testing). (See Eblen and Short [B31].) Maximum duration without circuit protective device operation from tests is 85 cycles: 26.2 Cal/s/cm 2 x 1.42 s = 37 Cal/cm Incident analysis on this equipment indicates exposures do not exceed the values in the table. 8. Engineering analysis indicates that applying a 150% multiplier to the 480 V exposure values provides a conservative value for equipment and open air lines operating at 601 V to 1000 V. 9. Industry testing on 480 V equipment indicates exposures on pad-mounted transformers do not exceed 4 Cal/cm 2. (See Eblen and Short [B31].) 10. Industry testing on 208 V network protectors indicates exposures do not exceed 4 Cal/cm 2. (See 208-V Arc Flash Testing [B1].) 11. Industry testing on 480 V network protectors indicates arcs will not self-extinguish and heat flux rates will exceed 60 Cal/cm 2 /s at 24 in working distance. Perform arc hazard analysis. (See Eblen and Short [B31].) 12. Industry testing on 480 V panels with non-edge mounted bus bars indicates exposures do not exceed 8 Cal/cm 2. (See Eblen and Short [B31].) 13. Industry testing on panelboards with edge-mounted, parallel bus bars indicate arcs will not self-extinguish and heat flux rates will exceed 60 Cal/cm 2 /s at 46 cm (18 in) working distance. Perform arc hazard analysis. (See Eblen and Short [B31].) 14. IEEE 1584 original test data indicates there is no significant difference between heat flux rates for 400 V class equipment verses 600 V class equipment. 17
18 Sample Model System Normal Minimum 3ph fault on Feeder A: 3,200 A 18
19 Arc Flash Results for System Normal > Max Incident Energy: 7.36 Cal/cm 2 19
20 Sample Model Contingency Minimum 3ph fault 1,500 A 20
21 Arc Flash Results for Contingency > Max Incident Energy: Cal/cm 2 21
22 Field Condition Alerts Standard Standard w/ Faceshield Standard Standard w/ Faceshield Standard Standard 22
23 Conclusions > Utility compliance can be maintained by incorporating arc flash assessments into: > System planning and standards > Equipment purchasing > Operations and procedures > The Arc Flash Assessment needs to be a living document > Establish process to manage critical information > Adopt methods to share requirements with field staff and contractors > Stay current on industry regulations and standards 23
24 Thank you! Keith Mullen MANAGING DIRECTOR, SYSTEM PLANNING 131 Saundersville Road Suite 300 Hendersonville, TN Office: Mobile: Visit us at energy.leidos.com 24
Illinois State University. Electrical Safety Procedure
Illinois State University Electrical Safety Procedure Illinois State University Facilities Management Revision Date: May 2014 Illinois State University Facilities Management Electrical Safety Procedure
More informationJanuary 30, Ms. Safety Director Sample Medical Corp. PO Box X Somewhere, CT. Re: NFPA 70E Hazard Assessment. Date of Visit.
3018 Eastpoint Parkway Louisville, KY 40223 (502) 716-7073 January 30, 2006 Ms. Safety Director Sample Medical Corp. PO Box X Somewhere, CT Re: NFPA 70E Hazard Assessment Date of Visit January 24, 2006
More informationNFPA 70E Standard for Electrical Safety Requirements for Employee Workplaces. Table Hazard Risk Category Classification
Table 3-3.9.1 Hazard Risk Classification Table 3-3.9.1 Hazard Risk Classification Panelboards rated 240 V and below Notes 1 and 3 - - - Circuit breaker (CB) or fused switch operation with covers on 0 N
More informationIntegrating Roles Within Electric Utilities to Achieve Arc Flash Safety. MIPSYCON Presenters Neil Stiller & Bob Cooke
Integrating Roles Within Electric Utilities to Achieve Arc Flash Safety MIPSYCON - 2018 Presenters Neil Stiller & Bob Cooke Presenters Neil Stiller, Sr. Electrical Engineer, RPU 30 years utility experience,
More informationBP-Husky Refinery Toledo, OH
BP-Husky Refinery Toledo, OH Document Type: Procedure Refinery Wide Procedure No.: SAF 095 Effective Date: 2/25/16 Owner: D. Clark Working on or near Energized Electrical Equipment Rev. No.: 6 Auth. By:
More informationElectrical Safety and Overcurrent Protection
Electrical Safety and Overcurrent Protection Dave Vallier DSE Bussmann division Contact info: Phone: 586-201-1348 Email: Davemvallier@eaton.com Agenda 1. Electrical hazards overview 2. The role of the
More informationReducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer
Reducing Arc Energies with Current Limiting Fuses arc flash note 2 By mike lang, Principal field engineer Why Use Current Limiting Fuses Current limiting fuses can reduce both the magnitude and duration
More informationDesign Considerations to Enhance Safety and Reliability for Service Entrance Switchboards
Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards Robert P. Hansen, P.E., PhD GE Specification Engineer Introduction Switchboards are a widely used type of equipment
More informationApplication of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear
ENGINEERING SERVICES 809 Gleneagles Court, Suite 309; Towson, MD 21286 Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear Prepared by: Keith Robertson, PE Staff Power
More informationArc flash hazard mitigation
Low Voltage Products Arc flash hazard mitigation Each year more than 2,000 people are treated in burn centers with severe arc flash injuries. ABB designs and manufactures products and solutions to provide
More informationTwo Recent Case Studies in the Mining Industry
Two Recent Case Studies in the Mining Industry Remote Isolation Arc Flash Remediation David B. Durocher Senior Member, IEEE Global Industry Manager, Mining Eaton Corporation 26850 SW Kinsman Rd Wilsonville,
More informationUnderstanding Arc Flash Hazards. White Paper
White Paper By: Kevin J. Lippert Eaton Electrical 170 Industry Drive Pittsburgh, PA 15275 Donald M. Colaberardino Eaton Electrical 170 Industry Drive Pittsburgh, PA 15275 Clive W. Kimblin Eaton Electrical
More informationThe New 2017 National Electric Safety Code Overview and Significant Changes. Presented by. Mickey Gunter October 28, 2016
The New 2017 National Electric Safety Code Overview and Significant Changes Presented by Mickey Gunter October 28, 2016 NESC Technical Subcommittees Subcommittee 1 Coordination, Definitions Subcommittee
More informationOSHA Update. Electric Power Generation, Transmission and Distribution Standard (Part 1910 & 1926)
OSHA Update Electric Power Generation, Transmission and Distribution Standard (Part 1910 & 1926) 5/14/2014 Significant Changes to the Standards General Training Host Employer & Contractor Responsibilities
More informationtake to complete our safety compliance
This presentation is one of three steps you will take to complete our safety compliance requirements ECR Energizer Contractor Representative Primaryliaison between Energizer and the contractor for matters
More informationNESC 2007 FLAME RESISTANT CLOTHING
NESC 2007 FLAME RESISTANT CLOTHING Written by: Hugh Hoagland Published: Friday, February 1, 2008 by Incident Prevention, Inc. The NESC 2007 standard sets forth quite a challenge to electric and communication
More informationNew 2002 NEC. Arc Flash Hazard Marking Requirement Cooper Bussmann, Inc.
110.16 New 2002 NEC Arc Flash Hazard Marking Requirement 2001 Cooper Bussmann, Inc. 110.16 Flash Protection. Switchboards, panelboards, industrial control panels, and motor control centers in other than
More information6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton
Advances in technology to address safety Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton 1 Advances in technology could mean use existing technology & back to basics Advances in safety are
More informationNot all Low Voltage Switchgear is created equal
Not all Low Voltage Switchgear is created equal White Paper The must-have solution for power distribution systems Introduction Reliability and safety are the two most important criteria in the proper functioning
More information3.2. Current Limiting Fuses. Contents
.2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse
More informationElectrical Safety CSA Z462 & NB Regulations
Electrical Safety CSA Z462 & NB Regulations WorkSafeNB s 2014 Health and Safety Conference Daniel Roberts Senior Manager, Electrical Safety Consulting at Schneider Electric Vice-chair CSA Z462 daniel.roberts@schneider-electric.com
More informationGE Arc Vault TM Protection System. By Mark Clapper GE Specification Engineer. Introduction. What Variables Contribute To An Arcing fault?
By Mark Clapper GE Specification Engineer Introduction To address the increasing concerns and standards around arcing faults, GE challenged our Global Research Center to develop a new, active method of
More informationEnergized Electrical Work
Manitoba STANDARD PROCEDURE INSTRUCTION Title Energized Electrical Work Department Supersedes SPI Dated N/A SPI 32-4 Effective Date MAR 30, 2012 Energized Electrical Work SPI 32-4 Page 1 of 9 STANDARD
More informationOutside Link Box PRODUCT CATALOG 2018 EDITION
Outside Link Box PRODUCT CATALOG 2018 EDITION 2' Without an OFB 5' With an OFB EPRI Tested Reduces Arc Flash Hazard to 4 cal/square cm. Crews no longer need to reach into an energized Network Protector.
More informationSecondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor
Reducing Arc Flash Energies on Transformer Secondaries arc flash note 6 By Mike Lang, principal field engineer and Dave Komm, Technical Services Supervisor 1. Introduction Arc flash incident energy calculations
More informationNot all Low Voltage Switchgear is created equal
White Paper Not all Low Voltage Switchgear is created equal The must-have solution for power distribution systems Prepared by: Tom Hawkins, Consulting Product Engineer Rahul Rajvanshi, Senior Product Engineer
More informationBP OIL -- TOLEDO REFINERY
BP OIL -- TOLEDO REFINERY Document Type: Procedure Effective Date: August 31, 2017 Owner: Dane P. Clark Refinery Wide Electrical Distribution System Switching and Isolation Auth. By: Rick J. Chmelovski
More informationPretest Module 29 High Voltage Unit 1
Pretest Module 29 High Voltage Unit 1 1. Is a person qualified to work on high-voltage installations when this module is completed? 2. What is the code definition of high-voltage? 3. What is the IEEE definition
More informationETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy
ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy ETAP 17 Goodyear, Suite 100 Irvine, CA 92618 White Paper No.001.14-2016 Albert Marroquin, PE Member
More informationARC FLASH MANAGEMENT REVIEW. October 2017
ARC FLASH MANAGEMENT REVIEW October 2017 PURPOSE: The issue of Arc Flash Exposure has been knocking around for the past couple of months but unsure if we all understand the issue with this item and how
More informationMark Lyvers LLC / Cooper Bussmann Arc Flash Script Script to accompany PowerPoint on New 2002 NEC Arc Flash Hazard Marking Requirement
Mark Lyvers LLC / Cooper Bussmann Arc Flash Script Script to accompany PowerPoint on 110.16 New 2002 NEC Arc Flash Hazard Marking Requirement Slide 1 Suggestion on How to Use Download both the Mark Lyvers
More informationOntario Operations MAINTENANCE STANDARD PROCEDURE. Table of Contents. Electrical Electrical Department Energized Electrical Work Procedure
MAINTENANCE STANDARD PROCEDURE Ontario Operations TITLE Department Energized Work Procedure VALE # MPROC-50007 DATED 2018-05-04 PAGE Page 1 of 17 REV. 4 Table of Contents 1.0 PURPOSE... 2 2.0 APPLICATION...
More informationElectrical Safe Work Practices
Electrical Safe Work Practices Responsible Official: Matthew Early, VP for Campus Services Administering Division/Department: Facilities Management Effective Date: April, 22 Policy Sections: I. Purpose
More informationSafety Working with LV Drives
US1008e_LV Drive Safety_C, April 2009 Safety Working with LV Drives Intended Audience Only qualified electricians and engineers are allowed to install and maintain a LV Drive Students of this training
More informationUnrestricted. S.Mukhopadhyay
Unrestricted S.Mukhopadhyay 10.09.15 Electrical safety A report says that every year 5500 Indians die due to electric shock and 800 due to electric fire. 12% work place death due to electrocution ELECTRICAL
More informationArc Hazard Analysis Report For Lake Worth Generation Plant
Arc Hazard Analysis Report For Lake Worth Generation lant February, 2011 repared by: UC ynergetic, Inc. (Formerly ynergetic Design, Inc.) 4505 Fair Meadow Lane uite 215 Raleigh, NC 27607 Florida COA 9447
More informationTERMS AND DEFINITIONS
Application Guide Adjustable Alarm Level A setting on a protection relay at which an LED or an output contact operates to activate a visual or audible alarm. Adjustable Delay A setting on a protection
More informationElectrical Safety in Die Casting
Electrical Safety in Die Casting April 2016 Beau Glim NADCA Project Manager NADCA Safety Series 4 parts Basic Safety Machine Maintenance Safety Electrical Safety Managing Safety General safety information
More informationWhy arc-resistant drives need to be considered
White Paper WP020003EN Why arc-resistant drives need to be considered Aaron H. Vandereulen Application Engineer Stan R. Simms Design Engineer Reports have shown fatal injuries related to electrical incidents
More informationAppalachian Power Company Policy No. 2 Cover Up Procedures. Policy Summary:
Appalachian Power Company Policy No. 2 Cover Up Procedures Policy Summary: A. When a worker is in a position where the worker or a conductive object in the worker s hand can go or reach within the minimum
More informationZone Selective Interlocking
Application Paper AP02602002EN Supersedes 08/2003 Zone Selective Interlocking Contents Description.... Page What is Zone Selective Interlocking?... 3 What is the purpose of Zone Selective Interlocking?....3
More informationDescriptive bulletin. ReliaGear ND ANSI narrow frame metal-clad switchgear
Descriptive bulletin ReliaGear ND ANSI narrow frame metal-clad switchgear Table of contents Introduction...3 Vmax/A breaker...4 Instrument transformers...5 Potential transformers...6 15 kv potential transformers...6
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationMedium Voltage Controllable Fuse
Medium Voltage Controllable Fuse SOLUTIONS GUIDE SOLUTIONS GUIDE Intelligent Fuse Technology Introducing the Next Generation of Medium Voltage Arc-Flash Protection Mersen s new Medium Voltage Controllable
More informationWIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST
WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.
More informationTexas A&M Microgrid and Electrical System Study. Cushing Memorial Library & Archives
Texas A&M Microgrid and Electrical System Study Cushing Memorial Library & Archives Introduction of Texas A&M Microgrid Study Purpose Why are we studying the TAMU electrical system? Process How do we want
More informationCopyright 2003 Advanced Power Technologies, Inc.
Overview of the Standard for Interconnecting Distributed Resources with Electric Power Systems, IEEE 1547 and it s potential impact on operation of the Distributed Generation (DG) systems and on the design
More informationUPS Battery Maintenance Training
UPS Battery Maintenance Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq This UPS Battery Maintenance
More informationTECHNICAL TOPICS UNIVERSITY. General Electrical Safety BEST PRACTICES
UNIVERSITY TECHNICAL TOPICS BEST PRACTICES General Electrical Safety Abstract Electrical systems by nature are considered extremely dangerous to most human beings as these systems operate under conditions
More informationStudy of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank
Day 2 - Session V-B 299 Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Murali Kandakatla, B. Kondala Rao, Gopal Gajjar ABB Ltd., Maneja, Vadodara, India Thane Introduction
More informationThe Use of Low-Voltage Current-Limiting Fuses to Reduce Arc-Flash Energy
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 36, NO. 6, NOVEMBER/DECEMBER 2000 1741 The Use of Low-Voltage Current-Limiting Fuses to Reduce Arc-Flash Energy Richard L. Doughty, Fellow, IEEE, Thomas
More informationAgenda / ESPS Electrical Safety Program Solutions INC.
PEM Partners in Training Asset Management & Reliability Risk Assessment in the new CSA Z462 Electrical Power Distribution Reliability & Safety, a Valuable Balance Terry Becker, P.Eng., NFPA CESCP Owner,
More information2. Panelboards shall have new or updated paper directories printed from the master Excel spreadsheet inserted in the door
2013 Edition, Published February 28, 2013; Division Revision Date: February 28, 2013 Please add a section for identification. Incorporate the following requirements in your standards. These requirements
More informationCharacteristics of LV circuit breakers Releases, tripping curves, and limitation
Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationELECTRICAL UTILITY COST REDUCTION THROUGH PREDICTIVE CONTROL BACKGROUND
ELECTRICAL UTILITY COST REDUCTION THROUGH PREDICTIVE CONTROL Project Manager: Chris Hayes BACKGROUND Kraft Foods 35 Reduction of Energy Costs Over The Next 5 Yrs. (5 Benchmark) Kraft Foods Financial Model
More informationChapter 6 Generator-Voltage System
Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2
The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 2 SWITCHBOARDS Overview Also called Switchgear and Controlgear Assembly
More informationBackfeed, Safety, and Work Practices
Backfeed, Safety, and Work Practices Michael T. Sheehan, P.E. March, 2015 NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, operated by the
More information9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.
Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution
More informationAdvanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR
Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR Assembly Short-Circuit Current Ratings What Is A Short-Circuit
More informationPowerLogic High Density Metering System 4-Meter Enclosure Installation Guide
PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide 7002-0289-00 Instruction Bulletin HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment
More informationPower/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers
Section Contents 9 Section 9 Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers Page INTRODUCTION... 9- APPLICATION... 9- TESTING... 9- LONGER LIFE... 9- QUALITY... 9- INSTALLATION...
More informationIEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations
1 IEEE1818-2017 Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations Sponsored by the IEEE Substations Committee Presented By Joe Gravelle Organization of the Guide 1. Scope
More informationTechnical Specification for Pole Mounted Capacitor Rack
Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to
More informationUniversity of Vermont Physical Plant Department Burlington, Vermont
University of Vermont Physical Plant Department Burlington, Vermont ELECTRICAL SAFETY PROGRAM in accordance with VOSHA 29 CFR 1910 Subparts S VOSHA 29 CFR 1926 Subpart K NFPA 70E 2012 REVISED AND DISTRIBUTED
More informationThe safest, most reliable Switchgear in the market today
February 2008 MV Metal-Clad Switchgear The safest, most reliable Switchgear in the market today January 4, 2015 Slide 1 Arc-Resistant Standards Introduction Today s Topics What is Arc Flash and the risks
More informationCONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation
CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent
More informationCurrent Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer
Achieving Higher Short Circuit Current Ratings for Industrial Control Panels Standards & codes note 1 By Steve Hansen Sr. Field Engineer Introduction Articles 9.1 and. in the National Electrical Code require
More informationDER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.
Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations
More informationSECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT
SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.
More information7. SERVICES OVER 600 VOLTS
7. SERVICES OVER 600 VOLTS 7.1 GENERAL The Company shall always be consulted to obtain required design criteria where service is contemplated.preliminary plans of the Customer shall be submitted for review
More informationArc flash solutions catalogue Australia. Safety solutions - Protecting employees and the enterprise
Arc flash solutions catalogue Australia Safety solutions - Protecting employees and the enterprise The risk of an arc flash event is real An arc flash hazard is a proven significant and dangerous threat
More informationIEEE Northern Canada & Southern Alberta Sections, PES/IAS Joint Chapter Technical Seminar Series
IEEE Northern Canada & Southern Alberta Sections, PES/IAS Joint Chapter Technical Seminar Series Designing Electrical Systems for On-Site Power Generation Apr 04 th /05 th, 2016, Calgary/Edmonton, Alberta,
More informationwww. ElectricalPartManuals. com Section 13 Switchgear Low Voltage
Switchgear Low Voltage Introduction...13-1 AKD-10 Low-Voltage Switchgear...13-3 AKD-20 Low-Voltage Switchgear...13-3 Low Voltage Switchgear GE low-voltage switchgear is heavy-duty equipment built to ANSI
More informationIEEE IAS Atlanta Chapter
Stationary Battery Sizing IEEE IAS Atlanta Chapter Presented by: Lesley Varga, P.E. Quality Standby Services, LLC 1649 Sands Place, SE, Suite C Marietta, GA 30067 (770) 916-1747 lesley@qualitystandbyservices.com
More informationCONSIDERATIONS FOR THE APPLICATION OF A MV HIGH SPEED GROUNDING SWITCH FOR ARC FLASH MITIGATION OF LV EQUIPMENT
CONSIDERATIONS FOR THE APPLICATION OF A MV HIGH SPEED GROUNDING SWITCH FOR ARC FLASH MITIGATION OF LV EQUIPMENT Raymond Catlett, P.E. Senior Member, IEEE ABB Inc. 8 Driftwood Collinsville, IL 62234 USA
More informationENERGIZER BATTERY MANUFACTURING ST. ALBANS, VERMONT
ENERGIZER BATTERY MANUFACTURING ST. ALBANS, VERMONT HOUSE RULES FOR OUTSIDE CONTRACTORS Safety Equipment Safety equipment required for all Contractor's employees, including also all subcontractor's employees,
More information24kV Medium Voltage Switchgear Metal-Enclosed (LSC2A)
M6 24kV Medium Voltage Switchgear MetalEnclosed (LSC2A) GENERAL FEATURES GENERAL DESCRIPTION The structure of the cubicles, of considerable strength, has selfsupporting structure and is made of steel sheet
More informationTABLE OF CONTENTS Page
TABLE OF CONTENTS Page Objective 3 Summary 3 Conclusion 3 Sample Preparation 4 Testing 4 Test Results 5 Summary of Test Results (Table 1) 6 Appendix I 7 Addendum 1 8 2 I. OBJECTIVE To evaluate the performance
More informationSERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES
SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED SWITCHGEAR WITH VACUUM LOAD
More information25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:
25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report Report Number: Date: RN-R7604 9/16/2013 Table of Contents I. OBJECTIVE... 2 II. SUMMARY... 2 III. CONCLUSION... 2 IV. CABLE DATA... 2 V.
More informationCompany Directive STANDARD TECHNIQUE: SD4O/1. Standard HV Connection Arrangements
Company Directive STANDARD TECHNIQUE: SD4O/1 Standard HV Connection Arrangements Policy Summary This document specifies the standard arrangements for HV metered connections. NOTE: The current version of
More informationStatic frequency converter couples US paper mill s 25-Hz and 60-Hz electricity grids
Static frequency converter couples US paper mill s 2-Hz and 0-Hz electricity grids Before 0 Hz was adopted as the standard frequency for electricity distribution in the USA, power companies across the
More informationACHIEVING MAXIMUM BENEFITS WITH A FUSE PROTECTED MOTOR CONTROL CENTER
ACHIEVING MAXIMUM BENEFITS WITH A FUSE PROTECTED MOTOR CONTROL CENTER SYSTEM PROTECTION NOTE 2 BY MIKE LANG, PRINCIPAL FIELD ENGINEER INTRODUCTION Increasing concern for arc flash safety has grown to include
More informationS Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES
Fault Indicators S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions Service Information S320-40-1 Contents Product Information...........................1 Safety Information............................2
More informationELECTRICAL UTILITY COST REDUCTION THROUGH PREDICTIVE CONTROL December 2008 BACKGROUND
ELECTRICAL UTILITY COST REDUCTION THROUGH PREDICTIVE CONTROL December 2008 Project Manager: Chris Hayes Advisor: Paul I-Hai Lin 1 BACKGROUND Kraft Foods 35 uction of Energy Costs Over The Next 5 Yrs. (2005
More informationHazards SAFETY CORNER. of Establishing an. Work Condition
Hazards of Establishing an Electrically Safe Work Condition Written By Tony Demaria & Dean Naylor, Tony Demaria Electric, Mose Ramieh, III, Power Generation & Testing When working around electrical equipment,
More informationELECTRICAL PERSONAL PROTECTIVE EQUIPMENT STANDARD
Suncor-Wide Standard ELECTRICAL PERSONAL PROTECTIVE EQUIPMENT STANDARD Effective: On Date Approved Owned by Director of Maintenance and Reliability Services Reviewed every 5 years Livelink ID: 251254973
More information4-Day Power System Analysis, Coordination, System Studies
4-Day Power System Analysis, Coordination, System Studies Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Our
More informationLearning Module 6: Medium Voltage Power Circuit Breakers. 101 Basic Series
Learning Module 6: Medium Voltage Power Circuit Breakers 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Components 4 Frame 5 Operating Mechanism
More informationWisconsin Public Utility Institute. June 28, Minimum Distribution Charges. Larry Vogt. Director, Rates Mississippi Power
Wisconsin Public Utility Institute June 28, 2017 Minimum Distribution Charges Larry Vogt Director, Rates Mississippi Power 1 Costs of Service vs. Cost Recovery Residential Service Example Assuming that
More informationESSENTIAL SAFETY RESOURCES
ESSENTIAL SAFETY RESOURCES GS-3029 Originator: Safety Advisor s Signature: Type Name Approval: HSE Manager s Signature: Type Name Approval: Operations Manager s Signature: Type Name Table of Contents PURPOSE...
More informationLouisville Gas and Electric Company
P.S.C. Electric No. 11, Original Sheet No. 57 APPLICABLE In all territory served. AVAILABILITY OF SERVICE Available to any customer-generator who owns and operates a generating facility located on Customer
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................
More informationSelection Guide S&C ELECTRIC COMPANY. For Transformer-Primary Fuses in Medium- and High-Voltage
S&C Power FusesTypes SMD-1A, SMD-2B, SMD-2C, SMD-3, and SMD-50 Selection Guide For Transformer-Primary Fuses in Medium- and High-Voltage monsterfuses.com Utility and Industrial Substations Factory Authorized
More informationNFPA 70E Electrical Safety in the Work Place. R. Casey 2/1/05
NFPA 70E Electrical Safety in the Work Place R. Casey 2/1/05 The Other Electrical Hazard Arc flash: high-intensity intensity flash (eye damage) and superheated ball of gas (skin burns and melting)created
More informationFinal Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description
Final Draft Report Assessment Summary Hydro One Networks Inc. : Refurbish 115/44 kv, 25/33/42 MVA DESN Station CAA ID Number: 2007-EX360 1.0 General Description Hydro One is proposing to replace the existing
More informationSF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv 06B1-E-0002 Small Space Requirement, High Reliability and Safety ー 72.5 to 145 kv GIS, SDH314/SDHa314
More informationA comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear
Robert J. Gustin Eaton Fellow Application Engineer, P. E. Southfield, Michigan Definitions Metal-enclosed load interrupter switchgear type ME Metal-enclosed switchgear is defined in ANSI C37.20.3-1987,
More information