Displacer Type. Installation and Operating Manual. Liquid Level and Proof-er Switches

Size: px
Start display at page:

Download "Displacer Type. Installation and Operating Manual. Liquid Level and Proof-er Switches"

Transcription

1 isplacer Type Installation and Operating Manual Liquid Level and Proof-er es

2 UNPAKIN Top mounting displacer units are shipped from the factory with the displacer and cable assembly removed from the head assembly and packed separately in the same container. Unpack the instrument carefully. Make sure all components have been removed from the packing material. Inspect all components for damage. Report any concealed damage to the carrier withing 24 hours. heck the contents of the packing slip and report any discrepancies to the factory. heck the nameplate model number to be sure it agrees with the packing slip and purchase order. heck and record the serial number for future reference when ordering parts. Nameplate: - part number - serial n AUTION: If re-shipping to another location, displacer assembly must again be secured using same strap and wire assembly. After unpacking, inspect all components to see that no damage has occurred during shipment. These units are in conformity with the provisions of: 1. irective 2014/34/U for quipment or protective system for use in potentially explosive atmospheres. -type examination certificate number ISSeP01ATX027X (intrinsic safe units) or ISSeP09ATX024X (x d units). 2. The P directive 2014/68/U (pressure equipment directive). Safety accessories per category IV module 1. AUTION: The threaded connection link protruding from the head assembly is extremely fragile. O NOT handle or place in a position such that any amount of force is placed on the stem. Proper operation of the control requires that the stem is not damaged or bent. SPIAL ONITIONS OR ATX INTRINSIALLY SA US When the enclosure is made of aluminium, if it is mounted in an area where the use of category 1 apparatus is required, it must be installed such, that, even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded. INTROUTION isplacement type level switches offer the industrial user a wide choice of alarm and control configurations. These units utilize simple buoyancy principle and are well suited for simple or complex applications. PRINIPL O OPRATION Standard controls Operation is based upon simple buoyancy, whereby a spring is loaded with weighted displacers which are heavier than the liquid. Immersion of the displacers in the liquid results in buoyancy force change, which moves the spring upward. Since the spring moves only when the level moves on a displacer, spring movement (1) is always a small fraction of the level travel between displacers (2). A magnetic sleeve (3) is connected to the spring and operates within a non-magnetic barrier tube (4). Spring movement causes the magnetic sleeve to attract a pivoted magnet (5), actuating a switch mechanism (6) located outside the barrier tube. uilt-in limit stops, prevent over stroking of the spring under level surge conditions. Proof-er controls The purpose of the PROO-R is to check the operation of a displacer control without having to raise the level in the tank. This is accomplished by pulling downward on the PROO-R cable. A spring-loaded lever arm then lifts the switch actuator simulating a high or high-high level condition. When the cable is released, the PROO-R returns the actuator to its previous position to resume normal operation. loating roof controls The floating roof control is designed for installation on 'barrier' (floating roof) tanks. The control may be furnished with a brass displacer to prevent sparking. A hollow brass displacer is required if the control is to actuate in liquid as well as by the barrier. A stainless steel displacer is also available. 6 Rising level Pivot Return spring 5 alling level 2

3 MOUNTIN AUTION: isplacer spring and stem are fragile. o not drop displacers into tank. and feed cable into position to avoid bending stem. Adjust the displacers on the displacer cable for the desired switch actuating levels. (Instruction tag attached to cable.) Screw displacer cable fitting to threaded connection link protruding from the underside of control. e sure there are no tubes, rods, or other obstacles in the tank or vessel to interfere with the operation of the displacers. No guides into the tank are necessary unless liquid turbulence is excessive, in which case a "guided pipe" or tube should be at least 25 mm larger than the displacer diameter, open at the bottom end and with several vent holes located above the maximum high level of the liquid. heck installation of pipe or tube to be certain it is plumb. or floating roof top applications, the displacer switch may be mounted via flange or threaded mounting on a bracket, catwalk, etc. or through an opening in an outer dome roof. nsure that there are no obstacles to interfere with the operation of the displacers or weights and that there is a level surface on the roof beneath the displacer/weight. AUTION: Operation of all buoyancy type level devices should be done in such a way as to minimize the action of dynamic forces on the float or displacer sensing element. ood practice for reducing the likelihood of damage to the control is to equalize pressure across the device slowly. AUTION: efore attaching Magnetrol control to tank or vessel, using a level, check to see that tank mounting flange is within 3 of horizontal in all directions. Proper operation of the control depends on the switch housing being plumb. 3

4 WIRIN AUTION: All units are shipped from the factory with the enclosing tube tightened and the switch housing set screw locked to the enclosing tube. ailure to loosen the set screw prior to repositioning the supply and output connections may cause the enclosing tube to loosen, resulting in possible leakage of the process liquid or vapor. NOT: If control is equipped with pneumatic switch mechanism, disregard these instruction and refer to instruction bulletin and on mechanism furnished for air (or gas) connections. The units are shipped with the cable entry of the switch housing placed 90 opposite the tank connections to simplify installation in most cases. If the location of the cable entry on the level switch is appropriate to the installation, proceed to Step 4 to begin wiring the unit. If another configuration is desired, the switch housing can be easily rotated by first following Steps 1, 2, and 3. 1.Loosen set screw(s) at base of switch housing. Refer to igure housing may be rotated 360 to allow correct positioning of cable entry. 3. Tighten set screw(s) at base of switch housing. 4. Unscrew and remove switch housing cover. The threads have been lubricated to facilitate removal. AUTION: O NOT attempt to unscrew cover of ATX explosion proof housings before loosening locking screw in cover (igure 3 - ATX cast aluminium) or base (igure 4 - ATX cast iron) of housing. ALWAYS retighten locking screw after replacing cover. over locking screw (ATX explosion proof only) Screw Screw Set screw Locking screw igure 3 ast aluminium switch housing igure 4 ATX cast iron switch housing NOT: or supply connections use wire with a minimum rating of 75, as required by process conditions. Use a minimum of 14 AW wire for power and ground field wires. On high temperature applications (above 120 [250 ] at mounting flange or bushing), high temperature wire should be used between control and first junction box located in a cooler area. 5. The switch terminals are located next to the cable entry to facilitate wiring. ring supply wires through cable entry. Route extra wire around enclosing tube under the baffle plate, and connect them to the proper terminals. Refer to the wiring diagram. 6. ress wiring to ensure no interference or contact with the switch actuation arm, or replacement of switch housing cover. NOT: Observe all applicable electrical codes and proper wiring procedures. Prevent moisture seepage into the enclosure by installing approved cable glands. AUTION: or units with explosion proof housing, do not power the unit until the cable gland is sealed and the enclosure cover is screwed down securely. 7. Replace housing cover and retighten locking screw in case of ATX explosion proof housing. 8.Test switch action by varying liquid level in the tank or vessel. NOT: If switch mechanism fails to function properly, check vertical alignment of control housing and consult installation bulletin on switch mechanisms furnished. 9.heck cover to base fit to be certain gasketed joint is tight. A positive seal is necessary to prevent infiltration of moisture laden air or corrosive gasses into switch housing. or wiring diagrams, refer to the specific bulletin listed in the chart below: Series Letter escription ulletin No.,,,, O, Q, U, W, X, 8 ry ontact S ermetically Sealed Snap V Inductive Proximity J leed Type Pneumatic K Non-leed Type Pneumatic

5 PRVNTIV MAINTNAN Periodic inspections are a necessary means to keep your level control in good working order. This control is a safety device to protect the valuable equipment it serves. A systematic program of preventive maintenance must be implemented when the control is placed into service. If the following sections on What to do and What to avoid are observed, your control will provide reliable protection of your equipment for many years. What to do 1. Keep control clean e sure the switch housing cover is always in place on the control. This cover is designed to keep dust and dirt from interfering with switch mechanism operation. In addition, it protects against damaging moisture and acts as a safety feature by keeping bare wires and terminals from being exposed. Should the housing cover become damaged or misplaced, order a replacement immediately. 2. Inspect switch mechanisms, terminals and connections regularly ry contact switches should be inspected for excessive wear on actuating lever or misalignment of adjustment screw at point of contact between screw and lever. Such wear can cause false switch actuating levels ➀. O NOT operate your control with defective or maladjusted switch mechanisms ➀.. Level controls may sometimes be exposed to excessive heat or moisture. Under such conditions, insulation on electrical wiring may become brittle, eventually breaking or peeling away. The resulting bare wires can cause short circuits. NOT: heck wiring carefully and replace at the first sign of brittle insulation. What to avoid 1. NVR leave switch housing cover of the control longer than necessary to make routine inspections. 2. NVR use lubricants on pivots of switch mechanisms. A sufficient amount of lubricant has been applied at the factory to insure a lifetime of service. urther oiling is unnecessary and will only tend to attract dust and dirt which can interfere with mechanism operation. 3. NVR attempt to make adjustments or replace switches without reading instructions carefully. ertain adjustments provided for in Magnetrol controls should not be attempted in the field. When in doubt, consult the factory or your local Magnetrol representative. 4. NVR attempt to readjust magnetic attraction sleeves which are factory set. Tampering may cause failure of control while in service even though manual operation actuates switches. 5. NVR place a jumper wire across terminals to cut-out the control. If a jumper is necessary for test purposes, be certain it is removed before placing control into service. Vibration may sometimes cause terminal screws to loosen. heck all terminal connections to be certain that screws are tight. On units with pneumatic switches, air (or gas) lines subjected to vibration, may eventually crack or become loose at connections causing leakage. heck lines and connections carefully and repair or replace, if necessary. NOT: Spare switches should be kept on hand at all times. ➀ See switch mechanisms bulletin furnished should switch adjustment or replacement be necessary. 5

6 TROULSOOTIN Usually the first indication of improper operation is failure of the controlled equipment to function pump will not start (or stop), signal lamps fail to light, etc. When these symptoms occur, whether at time of installation or during routing service thereafter, check the following potential external causes first. uses may be blown. Reset button(s) may need resetting. Power switch may be open. ontrolled equipment may be faulty. Stem may be bent causing hang-up. Wiring (or medium lines) leading to control may be defective. If a thorough inspection of these possible conditions fails to locate the trouble, proceed next to a check of the control's switch mechanism. heck switch mechanism 1. Pull disconnect switch or otherwise assure that electrical circuit(s) through the control is deactivated. 2. Remove switch housing cover. 3. isconnect power wiring from switch assembly. 4. Swing magnet assembly in and out by hand, checking carefully for any sign of binding. Assembly should require minimal force, to move it through its full swing. 5. If binding exists, magnet may be rubbing enclosing tube. If magnet is rubbing, loosen magnet clamp screw and shift magnet position. Retighten magnet clamp screw. 6. If switch magnet assembly swings freely and mechanism still fails to actuate, check installation of control to be certain it is within the specified three (3 ) degrees of vertical (use spirit level on side of enclosing tube in two places, 90 apart). 7. heck switch continuity with ohm meter. Replace immediately if found defective. NOT: Spare switches should be kept on hand at all times. 8. If switch mechanism is operating satisfactorily, a test of the complete control's performance is the next likely step. Test control's performance 1. Reconnect power supply and carefully actuate switch mechanism manually (using a non-conductive tool on electrical switch mechanism) to dertermine whether controlled equipment will operate. AUTION: With electrical power "on" care should be taken to avoid contact with switch leads and connections at terminal block. 2. If controlled equipment responds to manual actuation test, trouble may be located in level sensing portion of the control (displacers, spring, stem and magnetic attracting sleeve. NOT: heck first to be certain liquid is entering tank or vessel. A valve may be closed or pipe line plugged. AUTION: e certain to pull disconnect switch or otherwise assure that electrical circuit(s) through control is deactivated. lose operating medium supply valve on controls equipped with pneumatic switch mechanisms. 3. With liquid in tank or vessel, proceed to check level sensing action by removing switch housing assembly. A. isconnect wiring from supply side of switch mechanism(s) and remove electrical conduit or operating medium line connections to switch housing.. Relieve pressure from tank or vessel and allow unit to cool.. Remove switch housing assembly by loosening set screw located immediately below housing base. 4. With switch housing assembly removed, inspect attracting sleeve(s) and inside of enclosing tube for excessive corrosion or solids build-up which could restrict movement, preventing sleeve(s) from reaching field of switch magnet(s). 5. Inspect displacer stem and spring assembly to assure it is not damaged. If stem or spring is bent or otherwise damaged, movement of the attraction sleeve inside the e-tube will be restricted, preventing proper function of the control. 6. If trouble is still not located, proceed to remove the entire sensing unit from the tank or vessel by unbolting head flange or unscrewing mounting bushing. Inspect displacer assembly and all internal parts for any signs of damage. heck assembly for binding by supporting head flange or mounting bushing over the edge of a bench and move displacer assembly by hand. NOT: When in doubt about the condition or performance of a Magnetrol control, contact the factory or consult your local representative. 6

7 TROULSOOTIN Proof-er If the Proof-er is not functioning properly, listed below are potential problems and corrective action. 1. Proof-er does not return to the down position after it is activated. efective return spring. AUS Replace Spring. RMY uildup between the shaft and housing restricting movement. lean Proof-er to remove buildup. andle stops are not adjusted properly. Adjust handle stop screws in or out to allow the handle to move to the proper position. 2. will not trip when Proof-er is activated. AUS The switch mechanism is defective and not the Proof-er. andle stops are not adjusted properly. RMY heck switch mechanism. Adjust handle stop screws in or out to allow the handle to move to the proper position. ANY APPROVALS ANY APPROV MOL ARA LASSIIATION ATX M Ix SA A (Russia, Kazakhstan, elarus) LRS All with electric switch mechanism and housing listed as ATX x d All with electric switch mechanism and housing listed as ATX x ia All with electric switch mechanism and housing listed as NMA 7/9 onsult factory for proper model numbers All with electric switch mechanism and housing listed as ATX x d onsult factory for proper model numbers onsult factory for proper model numbers All with electric switch mechanism and housing listed as ATX x d All with electric switch mechanism and housing listed as ATX x ia Lloyds Register of Shipping ATX II 2 x d II T6 b ATX II 1 x ia II T6 lass I, iv 1, groups & lass II, iv 1, roups, & lass I, iv 1, groups, & lass II, iv 1, roups, & x d II T6 b lass I, iv 1, groups & lass II, iv 1, roups, & lass I, iv 1, groups, & lass II, iv 1, roups, & 1x d II T6 b 0x ia II T4 a Marine approval 2014/68/U Other approvals are available, consult factory for more details The units are conform to the ATX directive 2014/34/U, The P directive 2014/68/U and the Low Voltage irective 2014/35/U 7

8 SPIIATIONS asic electrical ratings Series and Non-Inductive Ampere Rating Voltage S O Q U W X V A V A V V V Pressure temperature ratings Process temperature Process pressure (for higher ratings consult factory) Threaded models langed models Medium pressure Proof-er models Low pressure Proof-er models displacers: ➀ 55,1 40 ( ) for threaded tank connections 17,2 bar 250 psi) for threaded tank connections 96,5 40 ( ) for flanged 600" tank connections Stainless steel displacers: 49,6 40 ( ) 34,5 bar 500 psi) langed models are downrated to the design pressure of the selected flange ollow brass displacers: 6,9 40 ( ) 8,6 150 ( ) 1,7 90 ( ) ➀ o not use porcelain displacers on non-vented boiler water condensate systems over 90 (200 ). 8

9 V V SPIIATIONS Model A15 dimensional data and actuating levels in mm (inches) ➀ Threaded mounting X Y langed mounting X Y Z Z W W 80 (3.15) Outside Ø 73 (2,87) A min. A min. Rising Level alling Level Rising Level alling Level ousing type V W ø X Y mm (inches) mm (inches) mm (inches) mm (inches) Z Weatherproof - M (NMA 7/9) - ATX (ast Alu) with S-switch 257 (10.12) excl. S-switch 202 ( 7.94) 45 (1.77) 151 (5.93) 109 (4.29) ATX (ast Iron) 249 ( 9.80) 45 (1.77) 143 (5.63) 110 (4.33) Pneumatics Module J Pneumatics Module K 165 ( 6.50) 39 (1.54) 118 (4.65) M20 x 1,5 (*) or 1" NPT (2 entries - 1 plugged) (*) not for M (NMA 7/9) M20 x 1,5 or 3/4" NPT (single entry - 2 entries at request) 110 (4.33) 1/4" NPT (1 entry) 165 ( 6.50) 130 (5.12) 1/4" NPT (2 entries) Allow 200 mm (7.87") overhead clearance / All housings are 360 rotatable Outline imension A min isplacer Threaded langed Type Mounting Mounting Stainless Steel (5.62) (7.62) (5.62) (7.62) isplacer Type 65 (2.56) 184 (7.25) Stainless Steel 64 (2.50) 229 (9.00) Standard actuating levels and liquid specific gravity isplacer Type Liquid Temp. ( ) (100) 129 (5.10) 53 (2.10) 114 (4.50) 43 (1.70) 99 (3.90) 43 (1.70) 88 (3.50) 38 (1.50) 81 (3.20) 35 (1.40) +95 (200) 142 (5.60) 66 (2.60) 124 (4.90) 53 (2.10) 109 (4.30) 53 (2.10) 96 (3.80) 45 (1.80) 88 (3.50) 43 (1.70) +150 (300) 132 (5.20) 60 (2.40) 114 (4.50) 58 (2.30) 104 (4.10) 53 (2.10) 93 (3.70) 48 (1.90) +205 (400) 142 (5.60) 71 (2.80) 121 (4.80) 66 (2.60) 109 (4.30) 58 (2.30) 99 (3.90) 53 (2.10) +260 (500) 129 (5.10) 73 (2.90) 116 (4.60) 66 (2.60) 106 (4.20) 60 (2.40) +40 (100) 171 (6.70) 64 (2.50) 137 (5.40) 50 (2.00) 114 (4.50) 40 (1.60) 99 (3.90) 35 (1.40) 86 (3.40) 30 (1.20) 76 (3.00) 27 (1.10) 68 (2.70) 25 (1.00) +95 (200) 152 (6.00) 66 (2.60) 127 (5.00) 53 (2.10) 109 (4.30) 45 (1.80) 93 (3.70) 40 (1.60) 83 (3.30) 35 (1.40) 76 (3.00) 33 (1.30) Stainless Steel +150 (300) 162 (6.40) 76 (3.00) 134 (5.30) 60 (2.40) 116 (4.60) 53 (2.10) 101 (4.00) 45 (1.80) 91 (3.60) 43 (1.70) 81 (3.20) 38 (1.50) +205 (400) 175 (6.90) 88 (3.50) 144 (5.70) 71 (2.80) 124 (4.90) 60 (2.40) 109 (4.30) 53 (2.10) 96 (3.80) 48 (1.90) 86 (3.40) 43 (1.70) +260 (500) 154 (6.10) 81 (3.20) 132 (5.20) 71 (2.80) 116 (4.60) 60 (2.40) 104 (4.10) 55 (2.20) 93 (3.70) 50 (2.00) onsult factory for other specific gravities ➀ See page 24 for Proof-er and/or loating roof top switch dimensions 9

10 SPIIATIONS Model A10 dimensional data and actuating levels in mm (inches) ➀ Threaded mounting X Y langed mounting X Y W Z A min. V W Z 80 (3.15) Outside Ø 73 (2,87) A min. V Rising Level Rising Level alling Level alling Level ousing type V W ø X Y mm (inches) mm (inches) mm (inches) mm (inches) Z Weatherproof - M (NMA 7/9) - ATX (ast Alu) 257 (10.12) 45 (1.77) 151 (5.93) 109 (4.29) ATX (ast Iron) 249 ( 9.80) 45 (1.77) 143 (5.63) 110 (4.33) Pneumatics Module J Pneumatics Module K 216 ( 8.50) 39 (1.54) 118 (4.65) Allow 200 mm (7.87") overhead clearance / All housings are 360 rotatable M20 x 1,5 (*) or 1" NPT (2 entries - 1 plugged) (*) not for M (NMA 7/9) M20 x 1,5 or 3/4" NPT (single entry - 2 entries at request) 110 (4.33) 1/4" NPT (1 entry) 216 ( 8.50) 130 (5.12) 1/4" NPT (2 entries) Outline imension A min isplacer Threaded langed Type Mounting Mounting Stainless Steel (5.00) (7.00) (4.75) (6.75) isplacer Type 65 (2.56) 184 (7.25) 92 (3.62) Stainless Steel 64 (2.50) 229 (9.00) 114 (4.50) Standard actuating levels and liquid specific gravity isplacer Liquid Type Temp. ( ) +40 (100) 134 (5.30) 38 (1.50) 104 (4.10) 30 (1.20) 81 (3.20) 27 (1.10) 63 (2.50) 25 (1.00) 50 (2.00) 22 (0.90) +95 (200) 121 (4.80) 50 (2.00) 96 (3.80) 45 (1.80) 76 (3.00) 40 (1.60) 63 (2.50) 38 (1.50) +150 (300) 109 (4.30) 60 (2.40) 86 (3.40) 53 (2.10) 73 (2.90) 48 (1.90) +205 (400) 86 (3.40) 66 (2.60) 73 (2.90) 60 (2.40) Stainless +40 (100) 177 (7.00) 60 (2.40) 134 (5.30) 50 (2.00) 104 (4.10) 45 (1.80) 78 (3.10) 40 (1.60) 60 (2.40) 35 (1.40) Steel +95 (200) 149 (5.90) 71 (2.80) 119 (4.70) 63 (2.50) 91(3.60) 55 (2.20) 71 (2.80) 50 (2.00) +150 (300) 129 (5.10) 78 (3.10) 101(4.00) 68 (2.70) 81 (3.20) 60 (2.40) +205 (400) 111(4.40) 81 (3.20) 91 (3.60) 73 (2.90) +260 (500) 99 (3.90) 83 (3.30) onsult factory for other specific gravities ➀ See page 24 for Proof-er and/or loating roof top switch dimensions 10

11 SPIIATIONS Model 15 dimensional data and actuating levels in mm (inches) ➀ Threaded mounting X Y langed mounting X Y W Z A min. V W Z 80 (3.15) Outside Ø 73 (2,87) A min. V Rising Level alling Level Rising Level alling Level Rising Level alling Level Rising Level alling Level ousing type Weatherproof - M (NMA 7/9) - ATX (ast Alu) V W ø X Y mm (inches) mm (inches) mm (inches) mm (inches) 257 (10.12) 45 (1.77) 151 (5.93) 109 (4.29) ATX (ast Iron) 249 ( 9.80) 45 (1.77) 143 (5.63) 110 (4.33) Z M20 x 1,5 (*) or 1" NPT (2 entries - 1 plugged) (*) not for M (NMA 7/9) M20 x 1,5 or 3/4" NPT (single entry - 2 entries at request) Allow 200 mm (7.87") overhead clearance / All housings are 360 rotatable Outline imensions A min isplacer Threaded langed Type Mounting Mounting Stainless Steel (5.50) (7.50) (5.88) (7.88) isplacer Type 65 (2.56) 184 (7.25) 127 (5.00) Stainless Steel 64 (2.50) 267 (10.50) 152 (6.00) Standard actuating levels and liquid specific gravity isplacer Type Liquid Temp. ( ) Stainless +40 (100) 241 (9.50) 127 (5.00) 124 (4.90) 33 (1.30) 193 (7.60) 93 (3.70) 109 (4.30) 27 (1.10) Steel +95 (200) 208 (8.20) 109 (4.30) 127 (5.00) 45 (1.80) Liquid isplacer Temp. Type ( ) +40 (100) 139 (5.50) 50 (2.00) 93 (3.70) 25 (1.00) 127 (5.00) 43 (1.70) 88 (3.50) 20 (0.80) +40 (100) 139 (5.50) 50 (2.00) 93 (3.70) 25 (1.00) 124 (4.90) 43 (1.70) 86 (3.40) 22 (0.90) Stainless +95 (200) 152 (6.00) 68 (2.70) 106 (4.20) 38 (1.50) 137 (5.40) 55 (2.20) 101 (4.00) 38 (1.50) Steel +150 (300) 162 (6.40) 78 (3.10) 119 (4.70) 50 (2.00) 144 (5.70) 63 (2.50) 111 (4.40) 48 (1.90) +205 (400) 154 (6.10) 73 (2.90) 124 (4.90) 60 (2.40) onsult factory for other specific gravities ➀ See page 24 for Proof-er and/or loating roof top switch dimensions 11

12 SPIIATIONS Model 10 dimensional data and actuating levels in mm (inches) ➀ Threaded mounting and langed mounting and displacer arrangement 1 displacer arrangement 1 Outline imensions A min X X isplacer Threaded langed Y Y Type Mounting Mounting W Z A min. V W 80 (3.15) Outside Ø 73 (2,87) Z A min. V Stainless Steel (4.88) (6.88) (4.75) (6.75) ousing type V W ø X Y mm (inches) mm (inches) mm (inches) mm (inches) Z Weatherproof - M (NMA 7/9) - ATX (ast Alu) 257 (10.12) 45 (1.77) 151 (5.93) 109 (4.29) ATX (ast Iron) 249 ( 9.80) 45 (1.77) 143 (5.63) 110 (4.33) Allow 200 mm (7.87") overhead clearance / All housings are 360 rotatable M20 x 1,5 (*) or 1" NPT (2 entries - 1 plugged) (*) not for M (NMA 7/9) M20 x 1,5 or 3/4" NPT (single entry - 2 entries at request) Model 10 actuating levels arrangement 1 isplacer Type Upper 65 (2.56) 255 (10.04) 127 (5.00) Stainless Steel 64 (2.50) 305 (12.00) 152 (6.00) Lower Standard actuating levels and liquid specific gravity with displacer arrangement 1 porcelain isplacer Liquid Type Temp. ( ) Level ( ) ( ) ( ) ( ) ( ) ( ) ( ) (100) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (7.91) ( ) ( ) ( ) ( ) ( ) ( ) (200) (3.06) ( ) ( ) ( ) ( ) ( ) ( ) (2.76) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (300) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (400) ( ) onsult factory for other specific gravities ( ) ➀ See page 24 for Proof-er and/or loating roof top switch dimensions

13 SPIIATIONS Standard actuating levels and liquid specific gravity with displacer arrangement 1 porcelain isplacer Liquid Type Temp. ( ) Level ( ) ( ) ( ) ( ) ( ) ( ) (100) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (200) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (300) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (400) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (500) ( ) ( ) ( ) ( ) ( ) ( ) onsult factory for other specific gravities ( ) ( ) ( ) ( ) ( ) ( ) Standard actuating levels and liquid specific gravity with displacer arrangement 1 stainless steel isplacer Liquid Type Temp. ( ) Level ( ) ( ) ( ) ( ) ( ) ( ) (100) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) Stainless ( ) ( ) ( ) ( ) ( ) Steel (200) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (300) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (400) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (500) ( ) onsult factory for other specific gravities ( ) 13

14 SPIIATIONS Model 10 actuating levels arrangement 2 Upper isplacer Type 65 (2.56) 255 (10.04) 127 (5.00) Stainless Steel 64 (2.50) 305 (12.00) 152 (6.00) Lower Standard actuating levels and liquid specific gravity with displacer arrangement 2 stainless steel isplacer Liquid Type Temp. ( ) Level ( ) ( ) ( ) ( ) ( ) ( ) (100) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) () ( ) ( ) ( ) (200) () ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) Stainless Steel (300) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (400) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (500) ( ) ( ) onsult factory for other specific gravities 14

15 SPIIATIONS Standard actuating levels and liquid specific gravity with displacer arrangement 2 porcelain isplacer Type Liquid Temp. Level ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (100) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (3.15) ( ) ( ) ( ) ( ) ( ) ( ) (200) (7.71) ( ) ( ) ( ) ( ) ( ) ( ) (3.40) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (300) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (400) ( ) ( ) onsult factory for other specific gravities Standard actuating levels and liquid specific gravity with displacer arrangement 2 porcelain isplacer Type Liquid Temp. Level ( ) ( ) ( ) ( ) ( ) ( ) ( ) (100) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (200) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (55 39) ) ( ) ( ) (300) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (400) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (500) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) onsult factory for other specific gravities 15

16 SPIIATIONS Model 10 actuating levels arrangement 3, 4, 5 Arrangement 3 Arrangement 4 Arrangement 5 Upper Lower Lower Upper Upper Lower isplacer Type Stainless Steel (2.56) (5.00) (5.00) (5.00) (2.50) (6.00) (6.00) (6.00) Standard actuating levels and liquid specific gravity with displacer arrangements 3, 4 and 5 stainless steel isplacer Liquid Temp. Type ( ) Level ( ) ( ) ( ) ( ) ( ) ( ) (100) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (200) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) Stainless Steel (300) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (400) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (500) ( ) onsult factory for other specific gravities ( ) 16

17 SPIIATIONS Standard actuating levels and liquid specific gravity with displacer arrangements 3, 4 and 5 porcelain isplacer Liquid Type Temp. ( ) Level ( ) ( ) ( ) ( ) ( ) ( ) ( ) (100) ( ) ( ) ( ) ( ) ( ) ( ) () ( ) ( ) ( ) ( ) ( ) ( ) ( ) (3.15) ( ) ( ) ( ) ( ) ( ) ( ) (200) (2.69) ( ) () ( ) ( ) ( ) ( ) (2.76) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (300) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (400) ( ) ( ) onsult factory for other specific gravities Standard actuating levels and liquid specific gravity with displacer arrangements 3, 4 and 5 porcelain isplacer Liquid Temp. Level Type ( ) ( ) ( ) ( ) ( ) ( ) ( ) (100) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (200) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (300) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (400) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) (500) ( ) ( ) ( ) ( ) ( ) ( ) onsult factory for other specific gravities ( ) ( ) ( ) ( ) ( ) ( ) 17

18 SPIIATIONS Model 15 dimensional data Threaded mounting langed mounting X Y X Y Outline imension A min isplacer Threaded langed Type Mounting Mounting (7.75) (9.75) Z V Z V Stainless Steel (7.25) (9.25) W W 80 (3.15) Outside Ø 73 (2,87) A min. A min. Rising Level Rising Level Upper Upper alling Level alling Level Rising Level Middle Rising Level Middle J alling Level J alling Level K L Rising Level Lower alling Level K L Rising Level Lower alling Level isplacer Type Stainless Steel (2.56) (7.25) (6.42) (5.00) (2.50) (9.00) (7.50) (6.00) ousing type V W ø X Y mm (inches) mm (inches) mm (inches) mm (inches) Z Weatherproof 376 (14.81) 45 (1.77) 151 (5.93) 109 (4.29) M20 x 1,5 (*) or 1" NPT (2 entries - 1 plugged) (*) not for M (NMA 7/9) Allow 200 mm (7.87") overhead clearance / All housings are 360 rotatable 18

19 SPIIATIONS Model 15 actuating levels Standard actuating levels and liquid specific gravity isplacer Type Liquid Temp. ( ) J K L J K L J K L 0 to (30 to 130) (6.20) (1.40) (5.30) (1.00) (3.80) (0.90) Stainless 0 to Steel (30 to 130) (7.70) (2.20) (6.10) (2.00) (4.90) (1.40) (6.70) (1.60) (5.50) (1.60) (4.60) (1.30) (6.50) (2.00) (5.20) (1.60) (4.30) (1.10) onsult factory for other specific gravities isplacer Type Liquid Temp. ( ) J K L J K L J K L 0 to (30 to 130) (6.20) (1.90) (5.00) (1.40) (3.60) (1.00) (4.60) (0.70) (4.00) (0.80) (3.30) (0.90) (4.20) (1.10) (3.80) (1.00) (3.10) (0.90) Stainless 0 to Steel (30 to 130) (6.60) (2.60) (5.20) (1.80) (4.00) (1.20) (4.60) (1.00) (4.00) (1.00) (3.60) (1.10) onsult factory for other specific gravities isplacer Type Liquid Temp. ( ) J K L J K L 0 to (30 to 130) (114) (40) (93) (27) (73) (22) (99) (27) (83) (22) (71) (20) onsult factory for other specific gravities 19

20 SPIIATIONS Model 10 dimensional data Threaded mounting langed mounting X Y X Y Outline imensions A min isplacer Threaded langed Type Mounting Mounting (6.38) (8.38) Z V Z V Stainless Steel (5.75) (7.75) W W 80 (3.15) Outside Ø 73 (2,87) A min. A min. ousing type V W ø X Y mm (inches) mm (inches) mm (inches) mm (inches) Z Weatherproof 376 (14.81) 45 (1.77) 151 (5.93) 109 (4.29) Allow 200 mm (7.87") overhead clearance / All housings are 360 rotatable M20 x 1,5 (*) or 1" NPT (2 entries - 1 plugged) (*) not for M (NMA 7/9) 20

21 SPIIATIONS Model 10 actuating levels arrangement A,, Arrangement A Arrangement Arrangement Upper Upper J Middle Lower J Lower Middle Upper J Middle Lower K K K isplacer Type Stainless Steel (2.56) (6.42) (5.00) (5.00) (3.62) (2.50) (6.00) (6.00) (4.50) (4.50) Standard actuating levels and liquid specific gravity isplacer Liquid Type Temp. ( ) J K J K J K J K (100) (2.50) (2.20) (2.20) (2.00) (2.30) (2.00) (1.90) (1.70) Stainless (100) Steel (4.50) (3.70) (3.20) (2.30) (3.80) (3.20) (3.00) (2.20) (4.20) (3.80) (2.10) (1.90) (1.80) (2.20) (1.30) (1.70) (200) (3.20) (2.90) (2.50) (2.30) onsult factory for other specific gravities isplacer Liquid Type Temp. ( ) J K J K J K J K Stainless Steel +40 (100) (3.0) (2.4) (2.7) (1.5) (1.4) (1.4) (2.1) (1.4) (3.0) (2.6) (2.5) (1.2) (1.7) (1.7) (2.1) (1.1) +95 (200) +40 (100) +95 (200) +150 (300) onsult factory for other specific gravities (3.2) (2.7) (2.8) (1.7) (1.7) (1.7) (2.3) (1.6) (3.1) (3.2) (2.5) (1.5) (1.3) (1.9) (1.8) (1.3) (3.1) (3.2) (2.5) (1.3) (1.6) (2.2) (1.9) (1.2) (3.6) (3.6) (1.7) (2.0) (1.7) (2.3) (1.1) (1.8) (3.4) (3.0) (2.4) (2.7) (1.6) (1.8) (1.7) (2.4) 21

22 SPIIATIONS Model 10 actuating levels arrangement, Arrangement Arrangement Upper Upper Middle Lower Middle Lower J J isplacer Type Stainless Steel (2.56) (14.44) (5.00) (3.62) (2.50) (12.00) (4.50) (4.50) Standard actuating levels and liquid specific gravity isplacer Liquid Type Temp. ( ) J J J J (100) (7.50) (2.60) (2.20) (2.00) (6.90) (2.40) (1.90) (1.70) Stainless (100) Steel (9.90) (3.70) (3.20) (2.30) (9.20) (3.20) (3.00) (2.20) (8.90) (3.80) (2.10) (1.90) (6.70) (2.20) (1.30) (1.70) +95 (200) (7.40) (2.90) (2.50) (2.30) onsult factory for other specific gravities isplacer Liquid Type Temp. ( ) J J J J Stainless Steel +40 (100) (6.60) (2.80) (2.70) (1.50) (5.20) (1.80) (2.10) (1.40) (6.10) (3.00) (2.50) (1.20) (5.00) (2.10) (2.10) (1.10) +95 (200) (6.20) (3.10) (2.80) (1.70) (5.20) (2.10) (2.30) (1.60) +40 (100) +95 (200) +150 (300) onsult factory for other specific gravities (7.20) (3.20) (2.50) (1.50) (5.50) (1.90) (1.80) (1.30) (6.40) (3.20) (2.50) (1.30) (5.20) (2.20) (1.90) (1.20) (7.60) (3.60) (1.70) (2.00) (5.90) (2.30) (1.10) (1.80) (7.00) (3.00) (2.40) (2.70) (5.40) (1.80) (1.70) (2.40) 22

23 SPIIATIONS Model 10 actuating levels arrangement, Arrangement Arrangement Upper Upper Middle Middle Lower Lower J J isplacer Type Stainless Steel (2.56) (6.42) (5.00) (8.65) (2.50) (6.00) (6.00) (9.00) Standard actuating levels and liquid specific gravity isplacer Liquid Type Temp. ( ) J J J J (100) (2.50) (2.20) (5.80) (1.90) (2.30) (2.00) (5.50) (2.10) Stainless (100) Steel (4.50) (3.70) (7.70) (2.80) (3.80) (3.20) (7.50) (2.70) (4.20) (3.80) (6.60) (2.50) (1.80) (2.20) (5.80) (2.20) (200) (3.20) (2.90) (7.00) (3.40) onsult factory for other specific gravities isplacer Liquid Type Temp. ( ) J J J J (100) (3.00) (2.40) (6.30) (3.20) (1.40) (1.40) (5.70) (1.90) (3.00) (2.60) (6.10) (3.60 (1.70) (1.70) (5.70) (3.40) (200) (3.20) (2.70) (6.40) (3.60) (1.70) (1.70) (5.90) (3.40) (100) Stainless (3.10) (3.20) (7.00) (3.80) (1.30) (1.90) (6.30) (3.40) (3.10) (3.20) (7.00) (4.40) (1.60) (2.20) (6.40) (4.00) Steel (200) (3.60) (3.60) (6.20) (3.00) (1.70) (2.30) (5.60) (2.70) +150 (300) onsult factory for other specific gravities (3.40) (3.00) (6.90) (3.70) (1.60) (1.80) (6.20) (3.30) 23

24 SPIIATIONS Proof-er dimensional data 370 (14.62) min clearance required for actuation 370 (14.62) min clearance required for actuation 9 m (30') able assembly 9 m (30') able assembly Threaded: 126 (4.96) ➀ langed: 171 (6.74) ➀ loating roof of displacers dimensional data A min. min. OLLOW RASS ISPLAR A15 15 A min min Threaded 143 (5.62) langed 194 (7.62) n/a SS stainless steel 381 (.50) 76 (3.00) 21 (0.82) rass n/a 381 (.50) n/a 73 (2.88) n/a 21 (0.82) ollow rass 229 (9.00) 64 (2.50) 23 (0.92) Threaded 149 (5.88) langed 200 (7.88) n/a SS stainless steel n/a 38 (1.50) 19 (0.75) 76 (3.00) 102 (4.00) 21 (0.82) rass 28 (1.12) 19 (0.75) 73 (2.88) 21 (0.82) ➀ Threaded (126) and langed (171) to be added to V-dimension of housing. 24

25 RPLAMNT PARTS Partn : igit in partn : X Serial n : See nameplate, always provide complete partn and serial n when ordering spares. X = product with a specific customer requirement AUTION: Location of magnetic sleeve(s) must be maintained for proper switch actuation. o NOT attempt to alter differential of control by repositioning jam nuts Typical single switch model (threaded connection) Typical dual switch model (flanged connection) Typical model with Proof-er and floating roof displacer (threaded connection) Typical model with Proof-er and floating roof displacer (flanged connection) 25

26 RPLAMNT PARTS and housing reference type ulletin,,,, O, Q, U, W, X, S V J K ousing (1) nclosing tube kit (contains items 1 & 2) Replacement part ousing type Model (digits 1, 2 & 3) A10 A15 10 or or 15 ast aluminium housing for electric switch ast iron housing for electric switch not applicable Pneumatic switch housing not applicable Replacement part (2) nclosing tube gasket (4) Mounting bushing consult factory (5) Proof-er cable kit [cable length = 9 m (30 ft)] (3) Spring, stem and attraction sleeve kit igit 7 igit 4 Replacement part Model (digits 1, 2 & 3) A10 A A,, A,, K, L consult factory, A,, consult factory , consult factory, A,, consult factory , consult factory consult factory M, N, P, Q A not applicable consult factory R A not applicable T A not applicable igit 4 (6) able kit [cable length = 6 m (20 ft)] Replacement part Model (digits 1, 2 & 3) A10 A A,,, K or L (7) isplacer + cable kit [cable length = 6 m (20 ft)] (contains items 6 & 7) igit 4 igit 7 Replacement part Model (digits 1, 2 & 3) A10 A A, or , or A,,, K M or N consult factory consult factory or L P or Q not applicable not applicable not applicable R or T not applicable or all consult factory 26

Displacer Type. Installation and Operating Manual. Liquid Level and Proof-er Switches

Displacer Type. Installation and Operating Manual. Liquid Level and Proof-er Switches isplacer Type Installation and Operating Manual Liquid Level and Proof-er es Read this Manual Before Installing This manual provides information on the xternal Cage isplacer Liquid Level. It is important

More information

Series 3. Liquid Level Switches. ASME B31.1 Construction. Installation and Operating Manual

Series 3. Liquid Level Switches. ASME B31.1 Construction. Installation and Operating Manual Series 3 Liquid Level Switches Installation and Operating Manual Liquid Level Switches ASM B31.1 Construction Read this Manual Before Installing This manual provides information on Series 3 Liquid Level

More information

J52 Refrigerant Level Switches

J52 Refrigerant Level Switches J2 Refrigerant Level Switches Instruction Manual and Parts List OPERATING PRINCIPLE Figures 1 and 2 illustrate the simple and foolproof Magnetrol operating principle. Switching action is obtained through

More information

LIQUID LEVEL FLOAT SWITCH. F7 Series INSTALLATION AND OPERATIONS MANUAL. Single-Point, Vertically-Mounted Liquid Level Float Switch

LIQUID LEVEL FLOAT SWITCH. F7 Series INSTALLATION AND OPERATIONS MANUAL. Single-Point, Vertically-Mounted Liquid Level Float Switch F7 Series LIQUID LEVEL FLOAT SWITCH INSTALLATION AND OPERATIONS MANUAL Single-Point, Vertically-Mounted Liquid Level Float Switch F7 Series LIQUID LEVEL FLOAT SWITCH Single-Point, Vertical Mount 1.0 Installation

More information

Model B73 & Series 75

Model B73 & Series 75 Model B73 & Series 75 Installation and Operating Manual Sealed External Cage Liquid Level Switches Read this Manual Before Installing This manual provides information on the B73 and Series 75 Liquid Level

More information

Series V. Electric. switch mechanisms. and housings. Installation and Operating Manual

Series V. Electric. switch mechanisms. and housings. Installation and Operating Manual Series V Installation and Operating Manual Electric switch mechanisms and housings UNPACKING Unpack the instrument carefully. Make sure all components have been removed from the foam protection. Inspect

More information

L007 LIQUID LEVEL FLOAT SWITCH. Side-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

L007 LIQUID LEVEL FLOAT SWITCH. Side-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL L007 LIQUID LEVEL FLOAT SWITCH INSTALLATION AND OPERATIONS MANUAL Side-Mounted Liquid Level Float Switch READ THIS MANUAL PRIOR TO INSTALLATION This manual provides information on the L007 Side- Mounted

More information

L-Series: LIQUID LEVEL FLOAT SWITCH. Single-Point, Vertically-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

L-Series: LIQUID LEVEL FLOAT SWITCH. Single-Point, Vertically-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL L-Series: L001, L002, L003, L170, L175, L176, L177, L178, L180, L190 AND L195 LIQUID LEVEL FLOAT SWITCH INSTALLATION AND OPERATIONS MANUAL Single-Point, Vertically-Mounted Liquid Level Float Switch L001

More information

S003 LIQUID LEVEL FLOAT SWITCH. Single or Multi-Point, Vertically-Mounted, Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

S003 LIQUID LEVEL FLOAT SWITCH. Single or Multi-Point, Vertically-Mounted, Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL S003 LIQUID LEVEL FLOAT SWITCH INSTALLATION AND OPERATIONS MANUAL Single or Multi-Point, Vertically-Mounted, Liquid Level Float Switch READ THIS MANUAL PRIOR TO INSTALLATION This manual provides information

More information

L500 LIQUID LEVEL FLOAT SWITCH. Single or Multi-Point, Vertically-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

L500 LIQUID LEVEL FLOAT SWITCH. Single or Multi-Point, Vertically-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL L500 LIQUID LEVEL FLOAT SWITCH INSTALLATION AND OPERATIONS MANUAL Single or Multi-Point, Vertically-Mounted Liquid Level Float Switch READ THIS MANUAL PRIOR TO INSTALLATION This manual provides information

More information

L312 LIQUID LEVEL FLOAT SWITCH. Multi-Point, Vertically-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

L312 LIQUID LEVEL FLOAT SWITCH. Multi-Point, Vertically-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL LIQUID LEVEL FLOAT SWITCH INSTALLATION AND OPERATIONS MANUAL Multi-Point, Vertically-Mounted Liquid Level Float Switch READ THIS MANUAL PRIOR TO INSTALLATION This manual provides information on the Multi-

More information

Tuffy Liquid Level Controls with Pneumatic Switch

Tuffy Liquid Level Controls with Pneumatic Switch Tuffy Liquid Level Controls with Pneumatic Switch Installation and Operating Manual Side Mounted Float Level Switch Read this Manual Before Installing This manual provides information on the Tuffy Liquid

More information

Series K. Pneumatic. switch mechanism. and housings. Installation and Operating Manual

Series K. Pneumatic. switch mechanism. and housings. Installation and Operating Manual Series K Installation and Operating Manual Pneumatic switch mechanism and housings UNPACKING Unpack the instrument carefully. Make sure all components have been removed from the foam protection. Inspect

More information

Tuffy II Liquid Level Controls with Electric Switches Installation and Operating Manual

Tuffy II Liquid Level Controls with Electric Switches Installation and Operating Manual Tuffy II Liquid Level Controls with Electric Switches Installation and Operating Manual Side Mounted Float Level Switch Read this Manual Before Installing This manual provides information on the Tuffy

More information

For Hazardous Locations

For Hazardous Locations L500E LIQUID LEVEL FLOAT SWITCH INSTALLATION AND OPERATIONS MANUAL Single or Multi-Point, Vertically-Mounted Liquid Level Float Switch For Hazardous Locations READ THIS MANUAL PRIOR TO INSTALLATION This

More information

L070 LIQUID LEVEL FLOAT SWITCH. Side-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL. For Industrial Use

L070 LIQUID LEVEL FLOAT SWITCH. Side-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL. For Industrial Use L070 LIQUID LEVEL FLOAT SWITCH INSTALLATION AND OPERATIONS MANUAL Side-Mounted Liquid Level Float Switch For Industrial Use READ THIS MANUAL PRIOR TO INSTALLATION This manual provides information on the

More information

External Cage Displacer Actuated

External Cage Displacer Actuated xternal Cage Displacer Actuated Installation and Operating Manual Liquid Level Switches Read this Manual Before Installing This manual provides information on the xternal Cage Displacer Liquid Level Switch.

More information

Levalarm Gold. Installation, Operation, & Maintenance Instructions R500.E253A 03/16/2016

Levalarm Gold. Installation, Operation, & Maintenance Instructions R500.E253A 03/16/2016 Installation, Operation, & Maintenance Instructions R500.E253A 03/16/2016 Levalarm Gold STORAGE AND HANDLING The Reliance Levalarm Gold meets or exceeds all applicable specifications when shipped from

More information

Installation Instructions

Installation Instructions Page 6300-S-1 Installation Instructions 1. Read complete instructions before proceeding and do not discard packing materials until any/all loose items are located. Also, make sure that the installation

More information

I N S T R U C T I O N M A N U A L

I N S T R U C T I O N M A N U A L E L E C T R I C L E V E L C O N T R O L S LINC L471 L471SC LV471 L971 SERIES Recognized as a world-class leader in Electric & Pneumatic level control switches, flow indicators, chemical metering pumps,

More information

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004 U00X ULTRASONIC LEVEL SWITCH INSTALLATION AND OPERATIONS MANUAL Ultrasonic Liquid Level Switches For Non-Hazardous Locations For Models: U002, U003 & U004 READ THIS MANUAL PRIOR TO INSTALLATION This manual

More information

PROCESS DEVELOPMENT & CONTROL LLC 1075 MONTOUR WEST INDUSTRIAL PARK CORAOPOLIS, PENNSYLVANIA PHONE (724) FAX (724)

PROCESS DEVELOPMENT & CONTROL LLC 1075 MONTOUR WEST INDUSTRIAL PARK CORAOPOLIS, PENNSYLVANIA PHONE (724) FAX (724) 1075 MONTOUR WEST INDUSTRIAL PARK CORAOPOLIS, PENNSYLVANIA 15108 PHONE (724) 695-3440 FAX (724) 695-8635 INSTALLATION, OPERATION AND MAINTENANCE FOR 2 THRU 14, SERIES 09 ECON-O-TROL VALVE WITH LOCK LEVER

More information

Instructions for Installing and Operating Clark Reliance EA100 Series Levalarm

Instructions for Installing and Operating Clark Reliance EA100 Series Levalarm Section: R500.532F Bulletin: 532F Date: 7/1/2015 Supersedes: 532E Instructions for Installing and Operating Clark Reliance EA100 Series Levalarm This manual covers the following model numbers: EA100D,

More information

For CRN Installations

For CRN Installations L072 LIQUID LEVEL FLOAT SWITCH INSTALLATION AND OPERATIONS MANUAL Side-Mounted Liquid Level Float Switch With Manual Reset For CRN Installations READ THIS MANUAL PRIOR TO INSTALLATION This manual provides

More information

Fisher 657 Diaphragm Actuator Sizes and 87

Fisher 657 Diaphragm Actuator Sizes and 87 Instruction Manual 657 Actuator (30-70 and 87) Fisher 657 Diaphragm Actuator Sizes 30 70 and 87 Contents Introduction... 1 Scope of Manual... 1 Description... 2 Specifications... 2 Installation... 3 Mounting

More information

PROCESS DEVELOPMENT & CONTROL LLC 1075 MONTOUR WEST INDUSTRIAL PARK CORAOPOLIS, PENNSYLVANIA PHONE (724) FAX (724)

PROCESS DEVELOPMENT & CONTROL LLC 1075 MONTOUR WEST INDUSTRIAL PARK CORAOPOLIS, PENNSYLVANIA PHONE (724) FAX (724) 1075 MONTOUR WEST INDUSTRIAL PARK CORAOPOLIS, PENNSYLVANIA 15108 PHONE (724) 695-3440 FAX (724) 695-8635 INSTALLATION, OPERATION AND MAINTENANCE FOR (50mm-350mm) 2 THRU 14, EXCEL SERIES 40 WAFER STYLE

More information

Pneumatic Modulevel & APM Controllers

Pneumatic Modulevel & APM Controllers Pneumatic Modulevel & APM Controllers Installation and Operating Manual Liquid Level Control Read this Manual Before Installing This manual provides information on F10 and F50 Flow Switches. It is important

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM)

INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM) INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM) IOM-1088 03-16 Model 1088 Vacu-Gard Blanketing Valve ISO Registered Company SECTION I I. DESCRIPTION AND SCOPE The Model 1088 Vacu-Gard is a tank blanketing

More information

W91/W94 Series TEMPERATURE REGULATORS. Self-Operated Temperature Regulators. Design & Operation W91 Non-Indicating W94 Dial Thermometer

W91/W94 Series TEMPERATURE REGULATORS. Self-Operated Temperature Regulators. Design & Operation W91 Non-Indicating W94 Dial Thermometer Design & Operation W91 Non-Indicating W94 Dial Thermometer Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2010 Watson McDaniel Company CAPILLARY

More information

CVS Type 667 Diaphragm Actuator Sizes 30-70

CVS Type 667 Diaphragm Actuator Sizes 30-70 Instruction Manual CVS Type 667 Diaphragm Actuator Sizes 30-70 All CVS Controls actuators are to be installed and maintained in accordance with instructions supplied by CVS Controls. This manual includes

More information

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004 U00X ULTRASONIC LEVEL SWITCH INSTALLATION AND OPERATIONS MANUAL Ultrasonic Liquid Level Switches For Non-Hazardous Locations For Models: U002, U003 & U004 READ THIS MANUAL PRIOR TO INSTALLATION This manual

More information

Electromechanical Level Control

Electromechanical Level Control Electromechanical Level Control Catalog 9034CT9701R2/08 08 Class 9036, 9037, and 9038 and Class 9049 Accessories CONTENTS Description..............................................Page Selection Guide..............................................

More information

Type 2000 Transducer Product Instructions

Type 2000 Transducer Product Instructions Type 2000 Transducer Product Instructions The Type 2000 is an electro-pneumatic device that regulates an unregulated supply pressure down to an electronically-controlled output pressure. There are two

More information

DISPLACER SWITCH- DS INSTALLATION AND MAINTENANCE MANUAL

DISPLACER SWITCH- DS INSTALLATION AND MAINTENANCE MANUAL Pune Techtrol Private Limited DISPLACER SWITCH- DS INSTALLATION AND MAINTENANCE MANUAL Every Techtrol product should be installed properly, maintained regularly a used within its specified limits to ensure

More information

Fisher 249 Caged Displacer Sensors

Fisher 249 Caged Displacer Sensors Instruction Manual 249 Caged Sensors Fisher 249 Caged Displacer Sensors Contents Introduction... 1 Scope of Manual... 1... 2 Type Number... 3 Educational Services... 4 Maintenance... 4 Cleaning the Cage...

More information

Types 472, 473, 3572, 3573

Types 472, 473, 3572, 3573 Instruction Manual Form 1844 May 1998 Types 472, 473, 3572, 3573 Types 472, 473, 3572, 3573 Contents Introduction.............................. 2 Scope of Manual............................. 2 Type Number

More information

Level Measurement. Point level measurement Capacitance switches. Pointek CLS200 Standard. 5/16 Siemens FI Overview.

Level Measurement. Point level measurement Capacitance switches. Pointek CLS200 Standard. 5/16 Siemens FI Overview. Level Measurement Pointek LS200 Standard Siemens A 20 Overview onfiguration Installation Pointek LS200 (standard version) is a versatile inverse frequency shift capacitance level switch with optional rod/cable

More information

270A SERIES HIGH-SIDE FLOAT VALVES BULLETIN 270A-SB13-01 SERVICE BULLETIN

270A SERIES HIGH-SIDE FLOAT VALVES BULLETIN 270A-SB13-01 SERVICE BULLETIN VALVES VESSELS SYSTEMS CONTROLS 270A SERIES HIGH-SIDE FLOAT VALVES BULLETIN 270A-SB13-01 SERVICE BULLETIN System drawings shown in this bulletin are for illustration purposes only. Refrigeration systems

More information

SERIES 270A HIGH SIDE FLOAT VALVES BULLETIN 270A-SB11-02 SERVICE BULLETIN

SERIES 270A HIGH SIDE FLOAT VALVES BULLETIN 270A-SB11-02 SERVICE BULLETIN VALVES VESSELS SYSTEMS CONTROLS SERIES 270A HIGH SIDE FLOAT VALVES BULLETIN 270A-SB11-02 SERVICE BULLETIN System drawings shown in this bulletin are for illustration purposes only. Refrigeration systems

More information

Temperature Sensor Series

Temperature Sensor Series GENERAL DESCRIPTION The patented* No. 85026-Series Temperature Sensor contains a two-position valve operated by temperature variations around the integral sensing bulb. It is used to vent or block a pneumatic

More information

Fisher L2e Electric Level Controller

Fisher L2e Electric Level Controller Instruction Manual L2e Controller Fisher L2e Electric Level Controller Contents Introduction... 1 Scope of Manual... 1 Description... 2 Specifications... 2 Educational Services... 2 Installation... 4 Attaching

More information

Fisher 249 Cageless Displacer Sensors

Fisher 249 Cageless Displacer Sensors Instruction Manual 249 Cageless Sensors Fisher 249 Cageless Displacer Sensors Contents Introduction... 1 Scope of Manual... 1 Description... 1 Type Number Description... 2 Educational Services... 3 Maintenance...

More information

OPERATION AND MAINTENANCE INSTRUCTIONS

OPERATION AND MAINTENANCE INSTRUCTIONS OPERATION AND MAINTENANCE INSTRUCTIONS 334 SERIES THREE-PIECE BALL VALVES 1/4 to 2-1/2 Installation and Operation Always install your valve according to accepted industry standards and practices and operate

More information

Standard Valves Series Globe Valves Series Angle Valves Series Way-Valves

Standard Valves Series Globe Valves Series Angle Valves Series Way-Valves Installation, Operation, Maintenance Instructions Standard Valves Series 035 000 Globe Valves Series 031 000 Angle Valves Series 033 000 3-Way-Valves 1 GENERAL INFORMATION These instructions are designed

More information

Jerguson s Tri-Magnet Level Switches deliver failure-free performance.

Jerguson s Tri-Magnet Level Switches deliver failure-free performance. Top Mount Displacer Operated Magnetic Level Switch Section: Bulletin: Date: Supercedes: JS100 JS100.05 4/2017 10/2004 Jerguson s Tri-Magnet Level Switches deliver failure-free performance. The innovative

More information

Bray/ VAAS Slurry Series Knife Gate Valve 760/762/765/766/767/768 Series Operation and Maintenance Manual

Bray/ VAAS Slurry Series Knife Gate Valve 760/762/765/766/767/768 Series Operation and Maintenance Manual Bray/ VAAS Knife Gate Valve 760/762/765/766/767/768 Series Table of Contents Definition of Terms 1 Safety Instructions 1 Introduction 2 Unpacking 2 Storage 2 Installation 3 Commissioning 3 Cylinder-Operated

More information

Crispin Valves Operating Guide. Crispin

Crispin Valves Operating Guide. Crispin Crispin Valves Operating Guide Crispin Since 1905 Crispin Multiplex Manufacturing Co. 600 Fowler Avenue Berwick, PA 18603 1-800-AIR-VALV T: (570) 752-4524 F: (570) 752-4962 www.crispinvalve.com sales@crispinvalve.com

More information

Technical Data TYPE T124 & T134 TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4512A

Technical Data TYPE T124 & T134 TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4512A WATTS INDUSTRIES, INC. Technical Data SD 4512A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 PRINTED IN U.S.A. SD 4512A/9806 T124/T134 PILOT FRONT VIEW 2 1 /16 F 5 7 /8 2 3

More information

Installation Manual For ISL98, ISL03, ISL07, ISC07

Installation Manual For ISL98, ISL03, ISL07, ISC07 Installation Manual For ISL98, ISL03, ISL07, ISC07 Table of Contents Section 1: Introduction... 3 Housing Identification... 3 Engine Identification... 3 Special Tools... 3 Automatic Transmissions... 3

More information

Jo-Bell Products. DIVISION OF DALNOR SYSTEMS, INC Sierra Vista Drive Carlsbad NM, Phone: Fax:

Jo-Bell Products. DIVISION OF DALNOR SYSTEMS, INC Sierra Vista Drive Carlsbad NM, Phone: Fax: Jo-Bell Products DIVISION OF DALNOR SYSTEMS, INC. 5325 Sierra Vista Drive Carlsbad NM, 88220 Phone: 575-628-0675 Fax: 575-628-0679 Jo-Bell Products has been producing liquid level controls since 1947,

More information

OFFICINE OROBICHE S.p.A. 1/7 INSTRUCTION MANUAL FOR FLOW SWITCHES PL SERIES

OFFICINE OROBICHE S.p.A. 1/7 INSTRUCTION MANUAL FOR FLOW SWITCHES PL SERIES OFFICINE OROBICHE S.p.A. 1/7 INSTRUCTION MANUAL FOR FLOW SWITCHES PL SERIES 1.INSTRUMENT DESCRIPTION Flow switches PL series are designed to be mounted in an upright position along horizontal pipes. These

More information

Variable area meter F VA TUBUX M30

Variable area meter F VA TUBUX M30 VA TUUX M30 The variable area meter must be fitted vertically and without tension. ontrol elements or reductions/extensions in the pipe diameter upstream or downstream of the variable area meter have no

More information

VG2000 Series Cast Iron Flanged Globe Valves

VG2000 Series Cast Iron Flanged Globe Valves Installation Instructions VG2000 Issue ate November 15, 2002 VG2000 Series ast Iron Flanged Globe Valves pplication VG2000 Series ast Iron Flanged Globe Valves are primarily designed to regulate the flow

More information

X4 Installation and Operation Manual - POWER FLAME INCORPORATED

X4 Installation and Operation Manual - POWER FLAME INCORPORATED 7.13.2 Set the burner s combustion air inlet damper to the approximate setting as shown in this manual for the desired firing rate. Also, verify that the correct main orifice is installed in the main orifice

More information

Models F10 and F50. Installation and Operating Manual. Flow Switches

Models F10 and F50. Installation and Operating Manual. Flow Switches Models F10 and F50 Installation and Operating Manual Flow Switches Model F10 Model F50 Read this Manual Before Installing This manual provides information on Model F10 and F50 Flow Switches. It is important

More information

Type 657 Diaphragm Actuator Sizes and 87

Type 657 Diaphragm Actuator Sizes and 87 Instruction Manual Form 1900 January 2000 Type 657-70 & 87 Type 657 Diaphragm Actuator Sizes 30-70 and 87 Contents Introduction............................... 1 Scope of Manual.............................

More information

Type 3571 Pneumatic Actuator. Actuator areas: 27 in² 54 in² 116 in². Original instructions. Mounting and Operating Instructions EB 8820 EN

Type 3571 Pneumatic Actuator. Actuator areas: 27 in² 54 in² 116 in². Original instructions. Mounting and Operating Instructions EB 8820 EN Type 3571 Pneumatic Actuator Actuator areas: 27 in² 54 in² 116 in² Original instructions Mounting and Operating Instructions Edition April 2016 Note on these mounting and operating instructions These mounting

More information

M-100 Adjustable flow switch with right-angle flow

M-100 Adjustable flow switch with right-angle flow M-100 Adjustable flow switch with right-angle flow Operating Instructions and Quick Start Guide Table of Contents Introduction 03 Operation 03 Storage and Handling 03 Installation Instruction 03 Specification

More information

Cageless 249 Series Displacer Sensors

Cageless 249 Series Displacer Sensors Instruction Manual Form 1803 October 1993 Cageless 249 Series Cageless 249 Series Displacer Sensors Contents Introduction............................... 1 Scope of Manual............................. 1

More information

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators I & M Mark (/ ) 0 Wasson Road Cincinnati, OH 0 USA Phone --00 Fax -8-00 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark Pressure Regulators Warning: Jordan Valve

More information

CVS Type 657 Diaphragm Actuator Sizes 30-70

CVS Type 657 Diaphragm Actuator Sizes 30-70 Instruction Manual CVS Type 657 Diaphragm Actuator Sizes 30-70 All CVS Controls equipment, including actuators, are to be installed and maintained in accordance with instructions supplied by CVS Controls.

More information

Series K Pneumatic Switch Mechanism

Series K Pneumatic Switch Mechanism Series K Pneumatic Switch Mechanism Installation and Operating Manual Non-Bleed Switch For Liquid Level Switches Read this Manual Before Installing This manual provides information on the Series K Pneumatic

More information

VSI, LLC SERIES 2100 RESILIENT SEATED BUTTERFLY VALVES INSTALLATION, OPERATION AND MAINTENANCE MANUAL

VSI, LLC SERIES 2100 RESILIENT SEATED BUTTERFLY VALVES INSTALLATION, OPERATION AND MAINTENANCE MANUAL VSI SERIES 2100 RESILIENT SEATED BUTTERFLY VALVES VSI, LLC. 2-0 SERIES 2100 RESILIENT SEATED BUTTERFLY VALVES INSTALLATION, OPERATION AND MAINTENANCE MANUAL Publication: V2100- August 2016 TABLE OF CONTENTS

More information

END SUCTION CENTRIFUGAL PUMPS

END SUCTION CENTRIFUGAL PUMPS OWNERS GUIDE TO INSTALLATION AND OPERATION FW000 009 Supersedes 07 END SUCTION CENTRIFUGAL PUMPS READ THESE INSTRUCTIONS CAREFULLY Read these installation instructions in detail before installing your

More information

MODEL 40 TYPE W TANK OVERFILL ALARM

MODEL 40 TYPE W TANK OVERFILL ALARM MODEL 40 TYPE W TANK OVERFILL ALARM www.petro-meter.com PETRO-METER CORPORATION 300 WEST HOFFMAN AVE. LINDENHURST, NY 11757 www.petro-meter.com info@petro-meter.com Toll Free 1.800.935.8257 Tel. 1.631.225.2322

More information

APM Pneumatic Control for Boiler Feed System Applications

APM Pneumatic Control for Boiler Feed System Applications APM Pneumatic Control for Boiler Feed System Applications Installation and Operating Manual Pneumatic Control Read this Manual Before Installing This manual provides information on the APM Pneumatic Control

More information

Fisher 1061 Pneumatic Piston Rotary Actuator with Style H & J Mounting Adaptations

Fisher 1061 Pneumatic Piston Rotary Actuator with Style H & J Mounting Adaptations Instruction Manual 1061 H & J Actuator Fisher 1061 Pneumatic Piston Rotary Actuator with Style H & J Mounting Adaptations Contents Introduction... 1 Scope of Manual... 1 Description... 2 Specifications...

More information

Click Here for Printable PDF File. CHAPTER 3 - BASIC INFORMATION for PERFORMING HYDRAULIC SYSTEM MAINTENANCE

Click Here for Printable PDF File. CHAPTER 3 - BASIC INFORMATION for PERFORMING HYDRAULIC SYSTEM MAINTENANCE HWH Online Technical School Lesson 1: Introduction to Hydraulics Chapter 3 - "BASIC INFORMATION for PERFORMING HYDRAULIC SYSTEM MAINTENANCE" (Filename: ML57000-012-CH3.DOC Revised: 22APR16) Click Here

More information

Temperature Regulators

Temperature Regulators Temperature Regulators DESIGN & OPERATION DIAL THERMOMETER (Model 91400 only) BELLOWS OVERRANGE PROTECTION SPRING CAPILLARY TUBING CONNECTION SENSING BULB RANGE ADJUSTMENT SPRING CAP ADJUSTMENT SCREW BUSHING

More information

Installation Operation Maintenance. LSSN Butterfly Valve AGA Approved 50MM - 150MM. QAD#IM6055.REVA

Installation Operation Maintenance. LSSN Butterfly Valve AGA Approved 50MM - 150MM.  QAD#IM6055.REVA LSSN Butterfly Valve Installation Operation Maintenance Licence Number: 5326 www.challengervalves.com.au 1 Index 1. INTRODUCTION 1.1 Design Features 3 1.2 Flange and Pipe Compatibility 4 1.3 Operating

More information

ANDCO Eagle Actuator Instruction Manual

ANDCO Eagle Actuator Instruction Manual ANDCO Actuators ANDCO Eagle Actuator Instruction Manual The information contained in this manual is essential to safe, successful, long term operation of your Andco Eagle Linear Actuator. Read and follow

More information

Technical Instructions

Technical Instructions IS-P-595DB Double Seat - Balanced Valve - Bronze (Type DB) or Stainless Steel Trim (Type DS) Technical Instructions Description The Powers #11 Double Seat Balanced Valve Regulator (Bronze or Stainless

More information

Installation for L1100, L1200, L1200N Series Liquid Level Switches and DVU150, DVU175, and DVU2105/2115/2120 Series Dump Valves. GENERAL INFORMATION

Installation for L1100, L1200, L1200N Series Liquid Level Switches and DVU150, DVU175, and DVU2105/2115/2120 Series Dump Valves. GENERAL INFORMATION Installation for L1100, L1200, Series Liquid Level Switches and DVU150, DVU175, and DVU2105/2115/2120 Series Dump Valves. A =1-1/2 NPT B =2 NPT Meets NACE standard MR-01-75 for direct exposure to H2 S

More information

Mounting and Operating Instructions EB EN. Type 3372 Electropneumatic Actuator. Actuator area: 120 and 350 cm² With Type 3725 Positioner

Mounting and Operating Instructions EB EN. Type 3372 Electropneumatic Actuator. Actuator area: 120 and 350 cm² With Type 3725 Positioner Type 3372 Electropneumatic Actuator Actuator area: 120 and 350 cm² With Type 3725 Positioner Translation of original instructions Type 3372 with 120 cm² actuator area Type 3372 with 350 cm² actuator area

More information

2N1 TM PROXSENSOR ACCESSORIES VALVE STATUS MONITOR SERIES 52 2 INDUCTIVE PROXIMITY SENSORS AC, DC & INTRINSICALLY SAFE VERSIONS

2N1 TM PROXSENSOR ACCESSORIES VALVE STATUS MONITOR SERIES 52 2 INDUCTIVE PROXIMITY SENSORS AC, DC & INTRINSICALLY SAFE VERSIONS 2N1 TM PROXSENSOR VALVE STATUS MONITOR ACCESSORIES SERIES 52 2 INDUCTIVE PROXIMITY SENSORS AC, DC & INTRINSICALLY SAFE VERSIONS The High Performance Company PDF processed with CutePDF evaluation edition

More information

CAPSU-PHOTOHELIC PRESSURE SWITCH/GAGE*

CAPSU-PHOTOHELIC PRESSURE SWITCH/GAGE* CAPSU-PHOTOHELIC PRESSURE SWITCH/GAGE* Specifications - Installation and Operating Instructions Bulletin B-34 Series 43000 CAPSU-Photohelic Switch/Gage The CAPSU-Photohelic Switch/Gage is a most versatile,

More information

Established Leaders in Valve Actuation CP RANGE COMPACT PNEUMATIC ACTUATORS INSTALLATION AND MAINTENANCE MANUAL. Publication F230E Date of issue 03/08

Established Leaders in Valve Actuation CP RANGE COMPACT PNEUMATIC ACTUATORS INSTALLATION AND MAINTENANCE MANUAL. Publication F230E Date of issue 03/08 Established Leaders in Valve Actuation COMPACT PNEUMATIC ACTUATORS INSTALLATION AND MAINTENANCE MANUAL TABLE OF CONTENTS SECTION CONTENT PAGE Introduction Installation Maintenance 5 4 Grease Specification

More information

Mounting and Operating Instructions

Mounting and Operating Instructions Mounting and Operating Instructions EB 8310-6 EN Translation of original instructions Type 3271 Type 3277 Type 3271 and Type 3277 Pneumatic Actuators Actuator area: 240, 350, and 700 cm² Edition March

More information

Mounting and Operating Instructions EB EN. Type 3271 Pneumatic Actuator. Actuator area: 1000 cm². Translation of original instructions

Mounting and Operating Instructions EB EN. Type 3271 Pneumatic Actuator. Actuator area: 1000 cm². Translation of original instructions Type 3271 Pneumatic Actuator Actuator area: 1000 cm² Translation of original instructions Type 3271 Pneumatic Actuator Mounting and Operating Instructions Edition April 2018 Note on these mounting and

More information

Safe & Secure Series Electric Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual

Safe & Secure Series Electric Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual Safe & Secure Series Electric Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual For Use with: SNS4, SNS6, SNS10 & SNS15 Models Additional supplements may be needed for

More information

Installation, Operation and Maintenance Guide II NIBCO High Performance Butterfly Valves Series 6822 and 7822

Installation, Operation and Maintenance Guide II NIBCO High Performance Butterfly Valves Series 6822 and 7822 Installation, Operation and Maintenance Guide II NIBCO High Performance Butterfly Valves Series 6822 and 7822 Statements: NIBCO High Performance Butterfly Valves, Series 6822 and 7822, have been designed

More information

Westingh'ouse Steam Turbines-I. B (Rev. 3) GOVERNOR, GOVERNING VALVE

Westingh'ouse Steam Turbines-I. B (Rev. 3) GOVERNOR, GOVERNING VALVE Supersedes l. B. 697 (Rev. 2) Westingh'ouse Steam Turbines-I. B. 697 (Rev. 3) GOVERNOR, GOVERNING VALVE AND OIL PUMP This governor mechanism comprises a vertical shaft centrifugal weight governor a gear

More information

Mobrey MLT100. Displacer Level Transmitter. Product Data Sheet February 2015 IP119, Rev CA. Level, contents or interface measurement transmitter

Mobrey MLT100. Displacer Level Transmitter. Product Data Sheet February 2015 IP119, Rev CA. Level, contents or interface measurement transmitter Product Data Sheet February 2015 IP119, Rev CA Displacer Level Transmitter Level, contents or interface measurement transmitter Direct or external chamber mounting 4 20 ma HART output ATEX Intrinsically

More information

CR193 Vacuum Limitamp* Contactors

CR193 Vacuum Limitamp* Contactors GE Electrical Distribution GEH-5306C Maintenance Instructions CR193 Vacuum Limitamp* Contactors Contents Section 1 Introduction... 3 General... 3 Section 2 Description... 4 Principle of Operation... 4

More information

COOKSON OWNER'S MANUAL

COOKSON OWNER'S MANUAL COOKSON OWNER'S MANUAL FDO-A10 INDUSTRIAL DUTY FIRE DOOR OPERATOR R L I S T E D 3040233 US CONTROL PANEL SERIAL# OPERATOR SERIAL# 9001.DWG ECN 0959 REV 4 SPECIFICATIONS MOTOR TYPE:...INTERMITTENT HORSEPOWER:...1/8

More information

70 Series 8700 End Mount Three Phase Brake Instructions IP56 (NEMA 4) Housing

70 Series 8700 End Mount Three Phase Brake Instructions IP56 (NEMA 4) Housing Bulletin No. BK4773-3 (08/2016) 70 Series 8700 End Mount Three Phase Brake Instructions IP56 (NEMA 4) Housing Read carefully before attempting to assemble, install, operate or maintain the product described.

More information

APT10-2 Automatic Pump Trap

APT10-2 Automatic Pump Trap 6120050/3 IM-P612-18 ST Issue 3 APT10-2 Automatic Pump Trap Installation and Maintenance Instructions 1. General safety information 2. Product information 3. Installation Closed loop steam systems only

More information

Fisher 249VS Cageless Displacer Sensor

Fisher 249VS Cageless Displacer Sensor Instruction Manual 249VS Sensor Fisher 249VS Cageless Displacer Sensor Contents Introduction... 1 Scope of Manual... 1 Description... 1 Educational Services... 3 Installation... 3 Mounting the Sensor on

More information

Instalation, Operation and Maintenance Manual

Instalation, Operation and Maintenance Manual POWER BALL VALVE Instalation, Operation and Maintenance Manual Rev. 1 1 of 23 INDEX PAGE 1.0 INTRODUCTION-----------------------------------------------------------------------------4 2.0 RECEIVING & PREPARATION

More information

I & M MK96 & MK96C. Ideal Installation. Start-Up. Maintenance PROTECT VALVES WITH LINE STRAINERS

I & M MK96 & MK96C. Ideal Installation. Start-Up. Maintenance PROTECT VALVES WITH LINE STRAINERS **VIP** If you purchased your MK96 or MK96C Valve, or any stem repair component for this valve, after 9/7/08 - please see **VIP** assembly instruction change on page, middle-right, section. I & M MK96

More information

LNG Screw Down Non-Return Valve Installation, Operation and Maintenance Manual

LNG Screw Down Non-Return Valve Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual Date of Issue: 04 August 2010 Page 1 of 27 QF 80: Issue 2 WARNING! BEFORE ANY INSTALLATION AND MAINTENANCE WORK CAN COMMENCE ENSURE THE VALVE AND SURROUNDING

More information

The POWER. In PRESENTATION PRODUCTS. Instruction Book for BOARDROOM ELECTROL DA-LITE SCREEN COMPANY, INC.

The POWER. In PRESENTATION PRODUCTS. Instruction Book for BOARDROOM ELECTROL DA-LITE SCREEN COMPANY, INC. The POWER In PRESENTATION PRODUCTS Instruction Book for BOARDROOM ELECTROL DA-LITE SCREEN COMPANY, INC. 3100 North Detroit Street Post Office Box 137 Warsaw, Indiana 46581-0137 Phone: 574-267-8101 800-622-3737

More information

Ideal Installation. I & M Mark 80. Bulb Installation PROTECT VALVES WITH LINE STRAINERS

Ideal Installation. I & M Mark 80. Bulb Installation PROTECT VALVES WITH LINE STRAINERS I & M Mark 80 370 Wasson Road Cincinnati, OH 4509 USA Phone 53-533-5600 Fax 53-87-005 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark 80 Temperature Regulator

More information

60 Series End-Mount Brake Instructions Standard Housing

60 Series End-Mount Brake Instructions Standard Housing Bulletin No. BK4655 (04/18) 60 Series End-Mount Brake Instructions Standard Housing Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and

More information

70 Series 8700 End Mount Three Phase Brake Instructions IP43 (NEMA 2) Housing

70 Series 8700 End Mount Three Phase Brake Instructions IP43 (NEMA 2) Housing Bulletin No. BK4772S-3 (6/2017) 70 Series 8700 End Mount Three Phase Brake Instructions IP43 (NEMA 2) Housing Read carefully before attempting to assemble, install, operate or maintain the product described.

More information

Ideal Installation. I & M Mark 80. Bulb Installation PROTECT VALVES WITH LINE STRAINERS

Ideal Installation. I & M Mark 80. Bulb Installation PROTECT VALVES WITH LINE STRAINERS I & M Mark 80 370 Wasson Road Cincinnati, OH 4509 USA Phone 53-533-5600 Fax 53-87-005 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark 80 Temperature Regulator

More information

DWYER INSTRUMENTS, INC. Phone: 219/ P.O. BOX 373 MICHIGAN CITY, IN 46361, U.S.A. Fax: 219/

DWYER INSTRUMENTS, INC. Phone: 219/ P.O. BOX 373 MICHIGAN CITY, IN 46361, U.S.A. Fax: 219/ Series 43000 Capsu-Photohelic Pressure Switch/Gage Specifications - Installation and Operating Instructions Bulletin B-34 Ø4-3/4 [120.65] 3-7/8 SQ [98.43] 3/4 CONDUIT 4-3/8 [111.13] HOUSING REMOVAL 3-1/16

More information

Model MC-30D Impact Press. Operation & Maintenance Instructions

Model MC-30D Impact Press. Operation & Maintenance Instructions Model MC-30D Impact Press Operation & Maintenance Instructions Revised 12/05/2007 1 WARNINGS 1. Safety glasses must always be worn by the machine operator, as well as any co-workers, or any other persons

More information

Mounting and Operating Instructions EB EN. Type 3271 and Type 3277 Pneumatic Actuators. Actuator areas: 175v2, 350v2, and 750v2 cm²

Mounting and Operating Instructions EB EN. Type 3271 and Type 3277 Pneumatic Actuators. Actuator areas: 175v2, 350v2, and 750v2 cm² Type 3271 and Type 3277 Pneumatic Actuators Actuator areas: 175v2, 350v2, and 750v2 cm² Translation of original instructions Type 3271 (left) and Type 3277 (right) Pneumatic Actuators Mounting and Operating

More information

Valtek Auxiliary Handwheels and Limit Stops

Valtek Auxiliary Handwheels and Limit Stops Valtek Auxiliary s and Limit Stops Table of Contents Page 1 General information 2 Installation 2 Side-mounted handwheels, size 25 and 50 (linear actuators) 3 Side-mounted handwheels, size 100 and 200 (linear

More information