1 TECHNICAL INFORMATION / INSTALLATION MANUAL CIRCO5SolarCirculationUnit Wagner& Co CIRCO 5 Solar Circulation Unit the reliable pump station for efficient circulation of the heating fluid in combination with SUNGO controls Fast Installation through pre-mounted parts and compression fittings for the connection to the solar circuit Safe deaeration by integrated air venting pipe Variable Installation wall mounting or fitted directly to the storage cylinder Function Control through flow meter and thermometers Controlled heat flow by two temperature resistant non return ball valves High Energy Efficiency All around insulation and speed controlled circulation pump (in combination with all SUNGO solar controllers) Figure 1 CIRCO 5 solar circulation unit (SUNGO is an optional extra) Solar Thermal / Solar Circuit EN-CIRCO-5-MA

2 1. General Safety Guidelines The following safety advice is deemed to protect against dangers that can arise from improper handling of the device, whether knowingly or unknowingly. We distinguish between general advice which is given on this page and special advice which can be found in the texts of the instructions. Watch for the symbols! Qualification of the installer Setting up, installation and commissioning of the CIRCO 5 solar circulation unit must be carried out by a qualified installer. Please note that in case of a fault report the guarantee benefits can only be claimed if the correct commissioning has been certified by a qualified person in the commissioning protocol. Use and application Function The CIRCO 5 solar circulation unit is suitable for solar hot water systems and solar heating systems together with antifreeze solar as recommended. Limitations of use Use is limited to the hydraulic layout of the schematic drawings supplied by Wagner and Co. Some solar installations for space heating and the application of vacuum tube collectors do require special means of overheating protection, like the installation of an auxiliary vessel or alternative positioning of the safety components. The CIRCO 5 solar circulation unit can be mounted to a wall or directly to the storage cylinder. The CIRCO 5 solar circulation unit must not be mounted outside. Danger to Persons Live-threatening electrical shocks, burns, bruising and other health hazards are possible during installation. Please ensure that you pay attention to guidelines that are indicated with this symbol in the documentation. Caution Danger to Property This symbol indicates that damage may be done to components of the solar circuit or the function of the same may be impaired seriously. Please make sure that you follow the installation procedure step by step as instructed. Indicator for Additional Information This symbol points to practical advice, tricks of the trade which will make the installation and operation of the solar circuit easier. Norms and guidelines EC conformity declaration The CIRCO 5 solar circulation unit has been designed and constructed in accordance with EU regulations. Please regard national and EU regulations and guidelines for installation work. 2 EN-CIRCO-5-MA

3 2. Technical Information List of parts supplied The CIRCO 5 solar circulation unit is supplied pre-assembled. SUNGO control and CIRCO expansion kit are not part of the unit. You can find additional accessories on the last page. Maximum number of collectors to be installed Coll.- Type Serial-/Parallel connections * Serial connections 18 Ø 22 Ø 28 Ø 18 Ø 22 Ø 28 Ø EURO 2 x 3 3 x 3 x 3 Parallel connections LBM LBM * Number of fields each with 3 collectors connected in series Table 1 Maximum number of collectors that can be installed depending on the collector type, way of connection and size of piping. Single length of solar circuit up to 20m; heat carrier: frost protection/ water 0/ 60 % per. Volume, Volume flow = 35l/m²/hConnection and connection hoses at collectors are taken into account. Size of expansion vessel Fluid litre Coll. area m² Vessel volume in litres for system height in metres 2,5 5 7, , , CIRCO 5 solar circulation unit Order No Insulation Mounting plate Max. operating pressure EPP (λ = W/mK), in three parts with snap-lock Steel, galvanised 6 bar Max. operating temperature 120 C Circulation pump Wattage Max. pumping height Max. pumping volume Controller Non-return valves Temperature indicator Flow meter Safety unit Filler units Expansion vessel connection Security valve exhaust connection Solar circuit connections Centres distance of solar circuit connections ST 25/6 (230V, 50 Hz) 3 pump levels, /62/81 Watt 600 mbar 3.5 m³/h Suitable for SUNGO S/SL/SXL 2 x Heat-resistant metal 2 Integrated Thermometers Flow meter resistant to dirt clotting Safety valve 6 bar DN 15 in accordance with EN 12977, manometer 2 Filler and drain valves with caps ¾" male ¾" female Compression Fittings 18 and 22 mm 125 mm 2 12, Table 2 Size of expansion vessel depending on the fluid content of the entire system, collector area and height above vessel (distance vessel to upper edge of collectors). Dimensioning scenario: system exposed to full sun light but inactive. These values are only valid up to about 0.5 litres per m² collector volume. Installation options Dimensions (H xwxd) Weight Suitable for wall and cylinder installation (see accessories) 20x260x190mm 6.7 kg 7 v 0 0,5 1,0 1,5 2,0 [m/s] maximum H [m] economy ,0 2,0 3,0 [m /h] Figure 2 Pump characteristics curves Figure 3 Front and side view, measurements in mm 18 EN-CIRCO-5-MA

4 3. Installation compression fitting manometer safety valve ball valve with integrated thermometer and non-return valve compression fitting filler and drain valve air-release pipe circulation pump flow meter with filler and drain valve spring clips 15 D Figure The parts of the CIRCO 5 solar circulation unit (numbering fits to numbers in brackets at description of assembling steps), items with No. 7, 8, 9, 10, 12 and 1 are not part of the circulation unit. EN-CIRCO-5-MA

5 3.1 Installation Preparations The entire layout of flow and return pipes should be clear before mounting the CIRCO 5 solar circulation unit (125 mm centres)! In this context please also observe the operation instructions "Commissioning the System" If the solar system is installed for heating or if vacuum tubes are used you must pay attention to the technical documentation Heat Protection. These tools are required for the installation of the CIRCO 5 solar circulation unit: Power drill, masonry bits, pipe wrench, stilton etc. (figure 5). 3.2 Wall Mounting Use spirit level to place the wall mounting bracket (1), see figure, into the correct position, mark the three holes, drill and fix with plugs and screws supplied. Place the two pieces of assembly (2+6) into the correct holders of the wall mounting bracket and affix with the two spring clips (3). Place the two halves of the back insulation () with the recesses over the wall mounting bracket and push together. Connect the safety group (5) with the included ¾" gasket to the free exit of the return unit (6) using an open wrench SW30. Make sure of proper clamping during the tightening of the compression fittings to prevent damage or loosening of other parts of the assembly. Use the included wall anchors and screws to connect wall-mount (7) for the expansion vessel (8) to the right of the safety group. Observe length of the ¾" corrugated tube (9). There are special wall mounting kits for 35 litre and 50 litre vessels. Figure 5 Tools required for the installation of the CIRCO 5 solar circulation unit Rinse solar pump station and solar circuit and check for leaks. For this procedure a filler valve is fitted to the safety unit (5) and the flow meter below the pump. Install electrical wiring, switching and sensor circuits (12). Fix cables with cable ties to the prepared sections (notches and long holes) to the wall mounting bracket and ensure that there are no forces on the connectors of the control unit and that there is no contact with hot piping. If required feeding holes can be enlarged with a sharp knife. Always disconnect mains when working with electrical equipment! Remove frame (13) from the pump station in order to install the SUNGO control. Open SUNGO control (1) and affix with the four screws (15) supplied to the wall mounting bracket. You will find all required installation and operating instructions in the manuals for SUNGO S, SUNGO SL and SUNGO SXL. Put front insulation (16) into place. Connect the flexible hose with the expansion vessel and the pump station using supplied ¾ gaskets. It is recommended to fit in a special cap check valve between flexible hose and vessel. Connect exhaust pipe (10) to the safety unit and put empty container in place to collect any spills from the pipe. The connections to the solar circuit (11) (distance of pipes see figure 3) are made by compression fittings 18 or 22 mm (figure 6). Cut, burr pipes and push into fittings as far as possible, then tighten nuts. Using the 18 mm compression fitting a cracking sound will be heard, which is a sign of proper tightening. Continue until fully tight. Do not solder 18 mm compression fitting. Here too, special care must be taken to ensure proper clamping to prevent damage or loosening of other parts of the assembly. compression fitting for 22 mm snapping point compression fitting for 18 mm Figure 6 Compression fittings 18 and 22mm EN-CIRCO-5-MA

6 3.3 Mounting to Cylinder The adjustable mounting kits can be used with all Wagner solar cylinders with 1¼" flat tightening connections, if the vertical distance of these is between 00 and 60 mm. In order to prevent later obstructions of the pipe work in the area of the cylinder it is necessary to make proper layout plans before commencing. Connect pipes to cylinder using supplied gaskets. Adjust the height adjustment until both pipes are reaching the same level and have a distance of 125mm. Tighten adjustment nut. Trim off the insulation of the adjustable pipe and place pump station on top. Level the unit and affix to the cylinder. Connect remaining pipe work. 125 D=22mmfor compression fitting adjustable pipe fixing nut In order to prevent forces to the cylinder fixing because of pull from pipe work, pipe fixtures should be used at a near wall or at the ceiling. 50 mm The expansion vessel must not be hung from the pump station. Apply wall or floor mounting, depending on type of vessel. Always ensure proper clamping when tightening 32, 1 and 6 mm nuts in order to prevent loosening of other joints or damage to the unit. suitable for 50 mm to 69 mm 1¼ nut insulation filler and drain valve Figure 7 The adjustable cylinder mounting kit consisting of: Adjustable return pipe fitted with filler and drain valve, including insulation and fittings: 1¼" nut and 22 mm sleeve for compression joint. Flow pipe including insulation and fittings: 1¼" nut and 22 mm sleeve for compression joint. 6 EN-CIRCO-5-MA

7 +. Operating Advice The Flow Meter The flow meter indicates flow if the pump is switched on. The exact value can be read from the display. It is possible to adjust the flow by turning the adjustment screw with a mm Allen key during pump operation. If the screw is turned fully clockwise, flow will stop completely. Flow is cut off, when set screw is turned right to stop position. The Return-Flow Stoppers When the circulation pumps are turned of, unwanted heat distribution in the solar circuit is prevented by non-return ball valves. They only open into the flow direction and by pump pressure. The ball-valve handles can be used to turn them off. During operation litre/minute example 8 litre/minute mm + + Flow on Ball valve handle vertical Non-return valve in operation Flow off Ball valve handle vertical Non-return valve in operation Figure 9 Operational position Figure 8 Flow meter of the CIRCO 5 solar circulation unit with adjustment option Filling the system + Flow on Ball valve handle 5 Flow open, non-return valve off Flow off Ball valve handle horizontal Flow closed Figure 10 Filling the system Emptying the system + + Flow on Ball valve handle 5 flow open, non-return valve off Flow off Ball valve handle 5 Flow open, non-return valve off Figure 11 Emptying the System EN-CIRCO-5-MA

8 5. Accessories Accessories Description Order No. Kit for solar circuit Air release kit (not normally required because of included air vent pipe) Accessories for the solar circuit pipe work: 2 filler and drain valves and 2 earth connector clips Automatic air release kit Consisting of 2 automatic air release valves and heat resistant ball valves (up to 200 C), connection 3/8" Manual air release set Consisting of 2 Manual Air Release Valves 3/8" and Key CIRCO expansion vessel kit Expansion vessel for the CIRCO 5 solar circulation unit, operating pressure max. 10 bar, stainless steel connection hose, connection ¾" female with gasket 12 l-volume, incl. wall mounting bracket, pre-pressurised: 1.5 bar 18 l-volume, incl. wall mounting bracket, pre-pressurised: 1.5 bar 2 l-volume, incl. wall mounting bracket, pre-pressurised: 1.5 bar 35 l-volume, with brackets for wall and floor fixing, pre-pressurised: 2.5 bar Cap check valve for expansion vessel Check valve 3/" with filler and drain valve and with cap against maloperation Cylinder mounting kit for CIRCO 5 Non-adjustable pipe work 1¼" male flat tightening, insulated, adjustable return pipe for cylinder connections with 00 to 60 mm vertical distance, with 22 mm sleeves to connect to compression fittings of CIRCO Subject to modifications, errors excepted. Wagner & Co, WAGNER & CO Zimmermannstraße 12 D Cölbe/Marburg Fax

Solar Controller SUNGO S

Solar Controller SUNGO S OPERATING INSTRUCTIONS, Issue SW1201/ 2.01/ HW2.4 Solar Controller SUNGO S Wagner& Co Figure 1 Solar Controller SUNGO S. The benefits at a glance Large display to indicate temperature, balance values and

More information

Solar Controller SUNGO S

Solar Controller SUNGO S OPERATING INSTRUCTIONS, Issue 1201/2.4 Solar Controller SUNGO S Wagner& Co Figure 1 Solar Controller SUNGO S The benefits at a glance Large illuminated display to indicate temperature, balance values and

More information

TRIC A On-Roof Installation for EURO- Collectors*

TRIC A On-Roof Installation for EURO- Collectors* INSTALLATION INSTRUCTIONS TRIC A On-Roof Installation for EURO- Collectors* Fig. 1 Vertical and horizontal on-roof (roof parallel) installation examples Content 1 General Safety Notes. Horizontal Installation.

More information

Solar Thermal. Grant Solar Pump Station Installation & Servicing Instructions

Solar Thermal. Grant Solar Pump Station Installation & Servicing Instructions Solar Thermal Grant Solar Pump Station Installation & Servicing Instructions Part No. DOC 96. Rev 02. October 2012 Important Note Important Note for Installers The Pump Station supplied with your Grant

More information

OPERATION AND INSTALLATION

OPERATION AND INSTALLATION OPERATION AND INSTALLATION RESIDENTIAL SOLAR PUMP STATION» SE FLOWSTAR PUMP STATION Table of Contents 1 For your safety 1.1 About this manual 1.2 Designated use 1.3 Qualification of the installer 1.4 Hand-over

More information

SBS Manual for the specialised craftsman. Filling and flushing station. Connection Operation. en Manual

SBS Manual for the specialised craftsman. Filling and flushing station. Connection Operation. en Manual SBS 2000 Filling and flushing station Manual for the specialised craftsman Connection Operation Thank you for buying this RESOL product. Please read this manual carefully to get the best performance from

More information

Installation instruction

Installation instruction 1 Safety Before installing the device, please read this manual carefully. Please note that the installation must be executed according to relevant technical rules. The installation must also be adapted

More information

RESOL SBS 1000 * * Connection Operation

RESOL SBS 1000 * * Connection Operation RESOL SBS 1000 Connection Operation FlowCon SBS 1000 A www.resol.de *48003820* 48003820 Thank you for buying this RESOL product. Please read this manual carefully to get the best performance from this

More information

80 Litre Suction Oil Drainer With Inspection Chamber

80 Litre Suction Oil Drainer With Inspection Chamber Please dispose of packaging for the product in a responsible manner. It is suitable for recycling. Help to protect the environment, take the packaging to the local amenity tip and place into the appropriate

More information

KS Pump Stations. Engineering Submittal Sheet. Installation Sets for Collectors

KS Pump Stations. Engineering Submittal Sheet. Installation Sets for Collectors Engineering Submittal Sheet Installation Sets for Collectors Layout legend S Supply from collector to storage R Return from storage to collector 1 Ball valve with thermometer and integrated gravity break

More information

MANUAL. Collector FK7300. Mounting parallel roof bracket attachment system

MANUAL. Collector FK7300. Mounting parallel roof bracket attachment system MANUAL Mounting parallel roof bracket attachment system For horizontal positioning of the collectors, the assembly instructions apply accordingly! Collector FK7300 6 9 0 x x x x / version 2006.12 Contents

More information

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Product range. Technical specifications. Characteristic components

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Product range. Technical specifications. Characteristic components 7EN www.caleffi.com Circulation units for solar thermal systems Copyright Caleffi 7HE - 79HE series INSTALLATION AND COMMISSIONING MANUAL CONTENTS Function Product range Technical specifications Characteristic

More information

Installation and Operation Manual for a Solar System with KPC1-BP Collectors

Installation and Operation Manual for a Solar System with KPC1-BP Collectors Installation and Operation Manual for a Solar System with KPC1-BP Collectors EN v. 1.3 CONTENTS General Installation and Operation Instructions... 3 Collector Technical Data....... 4 1 Delivery of Mounting

More information

Valves, controls + systems Valves and controls for solar installations Regusol-180

Valves, controls + systems Valves and controls for solar installations Regusol-180 The Oventrop Quality Management System is certified to DIN-EN-ISO 9001 Application: The Oventrop programme for solar installations allows the connection of the collector to the storage cylinder within

More information

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Important Product range Technical specifications

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Important Product range Technical specifications 28237 www.caleffi.com Circulation units for solar thermal systems Copyright 204 Caleffi 278-279 series INSTALLATION AND COMMISSIONING MANUAL CONTENTS Function Important Product range Technical specifications

More information

SOLAR AEROLINE. fast simple reliable. The perfect connection technology for solar hot water

SOLAR AEROLINE. fast simple reliable. The perfect connection technology for solar hot water SOLAR The perfect connection technology for solar hot water Pipe systems for solar, heating, heat pumps and air-conditioning technology fast simple reliable Assembly options Applications: On-roof, in-roof

More information

Operating Instruction for Downlights

Operating Instruction for Downlights Operating Instruction for Downlights Type: ES_T4_1027_SILVER/ ES_T5_1027_WHITE/ ES_T6_1017_SILVER/ ES_T7_1017_WHITE/ ES_T8_1047_SILVER/ ES_T9_2019_WHITE/ ES_T10_1044_SILVER Index 1. General safety information...

More information

Product range Solex Technical data and dimensioning. 5 Years

Product range Solex Technical data and dimensioning. 5 Years Qualität made in Germany Product range Solex Technical data and dimensioning Quality made in Germany 5 Years Handwerkergarantie m anufacturer s warranty Product range Solex Dimensioning High-Flow system

More information

Installation and Operating Manual for Tank and Equipment Cleaning Nozzles Series 5TM

Installation and Operating Manual for Tank and Equipment Cleaning Nozzles Series 5TM Installation and Operating Manual for Tank and Equipment Cleaning Nozzles Series 5TM 150 150 150 This instruction manual contains proprietary information which is protected by copyright laws. No part of

More information

Industrial flue gas probes. Instruction manual

Industrial flue gas probes. Instruction manual Industrial flue gas probes Instruction manual 2 1 Contents 1 Contents 1 Contents... 3 2 Safety and the environment... 4 2.1. About this document... 4 2.2. Ensure safety... 4 2.3. Protecting the environment...

More information

For our present, For their future. Version 11.03

For our present, For their future. Version 11.03 For our present, For their future. SFB-AL (SF-B) series Installation Manual All-glass Evacuated Tubular Solar Collector with Heat Pipe Contents http://www.sunflower-solar.com/ 1. SOLAR COLLECTOR SIZE AND

More information

Part No: Genuine Mira Accessories

Part No: Genuine Mira Accessories Bar Valve Fixing Kit Part No: 1663.017 Genuine Mira Accessories 1 Introduction Please take time to read this guide thoroughly, having done so, keep it handy for future reference. This Fixing Kit has been

More information

Installation and Operation Manual for a Solar System with KPW Collectors

Installation and Operation Manual for a Solar System with KPW Collectors Installation and Operation Manual for a Solar System with KPW Collectors EN v. 1.0 CONTENTS General Installation and Operation Instructions... 3 Collector Technical Data....... 4 1 Delivery of Mounting

More information

These installation and maintenance instructions must be read in full and completely understood before the installation!

These installation and maintenance instructions must be read in full and completely understood before the installation! These installation and maintenance instructions must be read in full and completely understood before the installation! 1. General information on the installation and maintenance instructions These instructions

More information

SOLAR THERMAL EQUIPMENT

SOLAR THERMAL EQUIPMENT SOLAR THERMAL EQUIPMENT 6 DIRECT FLOW CPC COLLECTOR Rhico direct flow CPC collectors are acknowledged as the market s premium product. With an extremely low heat loss and optically efficient cylindrical

More information

DISTRIBUTION GROUP WITH THERMOSTATIC REGULATION. Upper connections G1 F Without fittings Fittings with running connection* Without pump

DISTRIBUTION GROUP WITH THERMOSTATIC REGULATION. Upper connections G1 F Without fittings Fittings with running connection* Without pump Description This preassembled pump group is part of the arberi trolli HEATING line. This distribution group allows the circulation of the thermal fluid, coming from the primary circuit and it maintains

More information

Product and installation manual. Underfloor Heating Composite Manifold

Product and installation manual. Underfloor Heating Composite Manifold Product and installation manual Composite Manifold Contents Introduction 2 Manifold Overview 3 Manifold Design 3 Manifold Dimensions 3 Manifold Installation 4-9 Pack Requirements 4 Required Tools 4 General

More information

GTFLOW EXTENSION MANIFOLD ASSEMBLY INSTRUCTIONS

GTFLOW EXTENSION MANIFOLD ASSEMBLY INSTRUCTIONS Page 1 of 5 Step 1: ASSEMBLE THE MAIN MANIFOLD AND MANIFOLD EXTENSION KIT First and very important step is to properly connect the main manifold and the manifold extension kit together by using the two

More information

VIESMANN. Installation instructions VITOSOL 200-T. for contractors. Vitosol 200-T Type SP2 Vacuum tube collector based on the heat pipe principle

VIESMANN. Installation instructions VITOSOL 200-T. for contractors. Vitosol 200-T Type SP2 Vacuum tube collector based on the heat pipe principle Installation instructions for contractors VIESMANN Vitosol 200-T Type SP2 Vacuum tube collector based on the heat pipe principle VITOSOL 200-T 6/2010 Dispose after installation. Safety instructions Please

More information

DeltaSol AX * *

DeltaSol AX * * DeltaSol X Differtial temperature controller Manual for the specialised craftsman Installation Operation Functions and options Troubleshooting *48000250* 48000250 Thank you for buying this RESOL product.

More information

A408 GB. Pneumatic oil and diesel pumps 1:1

A408 GB. Pneumatic oil and diesel pumps 1:1 03 594 A408 GB Pneumatic oil and diesel pumps 1:1 G Operating instructions for Pneumatic oil and diesel pump 1:1 Contents 1. General details 2 1.1 Intended use 2 1.2 Design and functional description 2

More information

Usage Instructions of Solar Control for 3Way-Ball Valve

Usage Instructions of Solar Control for 3Way-Ball Valve Table of Contents: Page: 2 Safety Instructions 3 Intended Use / General / Warranty / Installation: 4 Schematic Diagram: Mounting the sensor 5 Start-UP 6 Note: 7 Electrical connections: Technical Specifications

More information

LK Manifold RF. Design. Requirements

LK Manifold RF. Design. Requirements LK Manifold RF Design LK Manifold RF is made of stainless steel, the variants having 1 to 12 floor heating circuits. The manifold is delivered pre-mounted in brackets. The manifold has thermometers on

More information

Detailed Assembly Instructions. ATS Evacuated Tube - Solar Panel Units ATS10 / ATS20 / ATS30

Detailed Assembly Instructions. ATS Evacuated Tube - Solar Panel Units ATS10 / ATS20 / ATS30 Detailed Assembly Instructions ATS Evacuated Tube - Solar Panel Units ATS10 / ATS20 / ATS30 Release: 2/2012 1 ATS-10, ATS-20, and ATS-30 tube collectors are all setup using a similar method. Carefully

More information

Antifreeze Type SYC1025 (Long life coolant) Mixing ratio (water:antifreeze) Cooling fan module Type Electric Capacity

Antifreeze Type SYC1025 (Long life coolant) Mixing ratio (water:antifreeze) Cooling fan module Type Electric Capacity 152000 083 1. SPECIFICATION Unit Description Specification Cooling system Type Water cooling, forced circulation Coolant Capacity approx. 8.5 L Radiator Core size 555W x 582.4H x 27T (over 326,250mm2)

More information

TPH Series. MULTISTAGE CENTRIFUGAL PUMP Instruction Manual WALRUS PUMP CO., LTD. ISO 9001 Certified NSF/ANSI 372

TPH Series. MULTISTAGE CENTRIFUGAL PUMP Instruction Manual WALRUS PUMP CO., LTD. ISO 9001 Certified NSF/ANSI 372 TPH Series MULTISTAGE CENTRIFUGAL PUMP Instruction Manual NSF/ANSI 372 ISO 9001 Certified WALRUS PUMP CO., LTD. EC Declaration of Conformity Manufacturer: Walrus Pump Co., Ltd. Address: No.8314, Dapiantou,

More information

SOLAR-LUX 6/12 INSTALLATION AND MAINTENANCE INSTRUCTIONS EVACUATED TUBE COLLECTOR ROOF MOUNTING INSTALLATION UK/IE (2011/05) GB/IE

SOLAR-LUX 6/12 INSTALLATION AND MAINTENANCE INSTRUCTIONS EVACUATED TUBE COLLECTOR ROOF MOUNTING INSTALLATION UK/IE (2011/05) GB/IE INSTALLATION AND MAINTENANCE INSTRUCTIONS EVACUATED TUBE COLLECTOR SOLAR-LUX 6/ 6 70 646 03-00.0TL ROOF MOUNTING INSTALLATION UK/IE 6 70 647 040 (0/05) GB/IE TABLE OF CONTENTS TABLE OF CONTENTS Key to

More information

SENSOFIT RET 5000 Technical Datasheet

SENSOFIT RET 5000 Technical Datasheet SENSOFIT RET 5000 Technical Datasheet Manual retractable assembly Variable immersion length up to 700 mm With ball valve for easy sensor exchange without process interruptions Bayonet coupling for easy

More information

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION:

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION: DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION: These instructions are provided to familiarize the user with the seal and its use. The instructions must be read carefully

More information

Mira Mode Shower and Bath Fittings

Mira Mode Shower and Bath Fittings Mira Mode Shower and Bath Fittings Installation Guide Please leave these instructions with the user If you experience any difficulty with the installation or operation of your new shower, then please refer

More information

BEFORE BEGINNING INSTALLATION

BEFORE BEGINNING INSTALLATION COMPLETE CHASSIS FUEL LINE KITS For 1996-2000 Honda Civic Equipped with B-Series Engine INSTALLATION INSTRUCTIONS PLEASE study these instructions carefully before beginning this installation. Most installations

More information

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION:

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION: DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION: These instructions are provided to familiarize the user with the seal and its use. The instructions must be read carefully

More information

SOLAR-LIFESTYLE INSTALLATION AND MAINTENANCE INSTRUCTIONS FLAT-PLATE COLLECTOR FLAT ROOF AND WALL-MOUNTED INSTALLATION (2011/05) UK

SOLAR-LIFESTYLE INSTALLATION AND MAINTENANCE INSTRUCTIONS FLAT-PLATE COLLECTOR FLAT ROOF AND WALL-MOUNTED INSTALLATION (2011/05) UK INSTALLATION AND MAINTENANCE INSTRUCTIONS FLAT-PLATE COLLECTOR SOLAR-LIFESTYLE FLAT ROOF AND WALL-MOUNTED INSTALLATION 670647803-00.T 6 70 648 3 (0/05) UK TABLE OF CONTENTS TABLE OF CONTENTS Key to symbols

More information

Duo water control system

Duo water control system Duo water control system Installation and maintenance guide DUOINSTRUCT Contents Important and safety information Pack contents / Tools required Duo trim plate dimensions Flow performance Typical wall

More information

Declaration of Conformity as per Directive 97/23/EC

Declaration of Conformity as per Directive 97/23/EC Declaration of Conformity as per Directive 97/23/EC The manufacturer declares that:, 47906 Kempen, Germany PTFE-lined Rotary plug valves Series 23e, with packing with lever for 90 operation with worm gear

More information

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION:

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION: DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION: These instructions are provided to familiarize the user with the seal and its use. The instructions must be read carefully

More information

LK Manifold RF. Design. Requirements. Documentation

LK Manifold RF. Design. Requirements. Documentation LK Manifold RF Design LK Manifold RF is made of stainless steel, the variants having 2 to 12 floor heating circuits. The manifold is delivered pre-mounted in brackets. The manifold has thermometers on

More information

Make sure that no hazardous fumes can build up in the piping and in the meter during commissioning, decommissioning and dismantling.

Make sure that no hazardous fumes can build up in the piping and in the meter during commissioning, decommissioning and dismantling. The device and its accessories must only be used for their intended purpose and comply with safety regulations. Aquametro devices are manufactured according to valid standards and guidelines. Aquametro

More information

Instruction Manual. Q Series 2 Motor Control Modules - OEM

Instruction Manual. Q Series 2 Motor Control Modules - OEM A382-21-880 Issue B Instruction Manual Q Series 2 Motor Control Modules - OEM Pump/ Q Motor Control Module Item Number pumping system Electrical supply 24 V d.c. control 24 V a.c. control QDP40 200-230

More information

Type 3360, Service Manual. Serviceanleitung Service Manuel

Type 3360, Service Manual. Serviceanleitung Service Manuel Electromotive control valve Elektromotorisches Regelventil Vanne de régulation électromotorisée Service Manual Serviceanleitung Service Manuel We reserve the right to make technical changes without notice.

More information

for Solar Systems with KTU R Collectors

for Solar Systems with KTU R Collectors Installation and Operation Manual for Solar Systems with KTU R Collectors EN v. 1.7 CONTENTS General Installation and Operation Instructions... 3 Collector Technical Data... 4 1. Mounting System Delivery...

More information

COMPONENTS FOR SOLAR THERMAL SYSTEMS

COMPONENTS FOR SOLAR THERMAL SYSTEMS COMPONENTS FOR SOLAR THERMAL SYSTEMS 2012 2 The CALEFFI SOLAR product range has been specially developed for use in solar thermal systems, where high temperatures can normally be reached and where, depending

More information

Installation and Operating Instructions

Installation and Operating Instructions Original Installation and Operating Instructions Hawle E2 Valve with Flange Outlet, System 2000 or PE Spigot Ends Table of Contents A) General...... 2 A1 Symbols..... 2 A2 Intended use... 2 A3 Labeling...

More information

Operating Instructions

Operating Instructions Translation of the original instructions ONF 16 S / ONF 25 S Oil Mist Filter Operating Instructions PD 0057 BEN/C (1301) EN Table of contents Table of contents 1 About this manual...............................................

More information

Fuel Oil Deaerator with Integrated Filter Type GS 2000

Fuel Oil Deaerator with Integrated Filter Type GS 2000 Edition 11.02 Page 1 Fuel Oil Deaerator with Integrated Filter Type GS 2000 Fuel oil deaerator to DIN EN 12514-2 with filter and quick action stop valve General Design Operating materials Connections Designation

More information

Manual CPK 7210 N. Flate plate collector. Mounting parallel bench srew mountingsystem x x x x / version

Manual CPK 7210 N. Flate plate collector. Mounting parallel bench srew mountingsystem x x x x / version Manual Mounting parallel bench srew mountingsystem Flate plate collector CPK 7210 N 6 9 0 x x x x / version 2008.03 Contents Safety information...3 Transport note...4 Assembly instructions - Collector...5

More information

Type 3320, Service Manual. Serviceanleitung Service Manuel

Type 3320, Service Manual. Serviceanleitung Service Manuel Electromotive 2/2-way valve Elektromotorisches 2/2-Wege-Ventil Vanne électromotorisée à 2/2 voies Service Manual Serviceanleitung Service Manuel We reserve the right to make technical changes without notice.

More information

Type Operating Instructions. Bedienungsanleitung Manuel utilisateur

Type Operating Instructions. Bedienungsanleitung Manuel utilisateur Water flow rate transmitter Wasser-Durchfluss-Transmitter Transmetteur de débit d eau Operating Instructions Bedienungsanleitung Manuel utilisateur We reserve the right to make technical changes without

More information

LDG6000SA DIESEL GENERATOR OWNERS MANUAL

LDG6000SA DIESEL GENERATOR OWNERS MANUAL LDG6000SA DIESEL GENERATOR OWNERS MANUAL BEFORE OPERATING THIS EQUIPMENT PLEASE READ THESE INSTRUCTIONS CAREFULLY Preface Thank-you for purchasing this generator. This operation manual contains information

More information

INSTALLATION AND OPERATING INSTRUCTIONS SOLAR HEATING PROGRAMMER TDS SD UK/IE (2010/04)

INSTALLATION AND OPERATING INSTRUCTIONS SOLAR HEATING PROGRAMMER TDS SD UK/IE (2010/04) INSTALLATION AND OPERATING INSTRUCTIONS SOLAR HEATING PROGRAMMER TDS 300 6720613720-00.1 SD UK/IE CONTENTS Contents Contents 2 1 Safety instructions and explanation of symbols 5 1.1 General safety instructions

More information

INSTALLATION, SERVICE AND MAINTENANCE INSTRUCTIONS Y-FILTER 83700

INSTALLATION, SERVICE AND MAINTENANCE INSTRUCTIONS Y-FILTER 83700 INSTALLATION, SERVICE AND MAINTENANCE INSTRUCTIONS Y-FILTER 83700 11.106.32.0001 INOXPA, S.A. c/telers, 54 Aptdo. 174 E-17820 Banyoles Girona (Spain) Tel. : (34) 972-57 52 00 Fax. : (34) 972-57 55 02 email:

More information

INSTALLATION, SERVICE AND MAINTENANCE INSTRUCTIONS Y-FILTER 83700

INSTALLATION, SERVICE AND MAINTENANCE INSTRUCTIONS Y-FILTER 83700 INSTALLATION, SERVICE AND MAINTENANCE INSTRUCTIONS Y-FILTER 83700 11.106.32.0001 INOXPA, S.A. c/telers, 54 Aptdo. 174 E-17820 Banyoles Girona (Spain) Tel. : (34) 972-57 52 00 Fax. : (34) 972-57 55 02 email:

More information

Assembly instruction. Pendant Light Toccata GENERAL REMARKS ON SAFETY: Technical data: BOM

Assembly instruction. Pendant Light Toccata GENERAL REMARKS ON SAFETY: Technical data: BOM GENERAL REMARKS ON SAFETY: Read all of these instructions before installing fixtures. Keep all of the instructions for future reference. Turn off power before installing fixture. Installation is to be

More information

GATE VALVES. Type P (Standard: Plug) Type S (Soft Seal) Contents. (1) Be sure to read the following warranty clauses of our product 1

GATE VALVES. Type P (Standard: Plug) Type S (Soft Seal) Contents. (1) Be sure to read the following warranty clauses of our product 1 Serial No. H-V011-E-12 GATE VALVES Type P (Standard: Plug) Type S (Soft Seal) Contents (1) Be sure to read the following warranty clauses of our product 1 User s Manual (2) General operating instructions

More information

User manual Pipe notcher Type: AL 1-2E

User manual Pipe notcher Type: AL 1-2E User manual Pipe notcher Type: AL 1-2E Page 1 of 27 Table of contents 1. Foreword... 4 1.1. Name of machine... 4 1.2. Warning... 4 1.3. Target group for each chapter... 4 1.4. Symbols... 4 1.5. Re-ordering

More information

MEDIA LED. Pendant Standard Mount Installation ou de montage WARNING:

MEDIA LED. Pendant Standard Mount Installation ou de montage WARNING: MEDIA LED Pendant Standard Mount WARNING: Disconnect main power at the source prior to installation! Thread gripper base onto 1 /4 20 stud, or with #8 screw. Depress gripper nozzle to insert aircraft cable.

More information

NEOTECHA NTB-NTC BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

NEOTECHA NTB-NTC BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installation these instructions must be fully read and understood 2 SAFETY Please also read through these notes carefully. 2.1 General potential danger due to: a. Failure to observe the instructions

More information

Installation Instructions. Ultimate Screen. English Version 2.3

Installation Instructions. Ultimate Screen. English Version 2.3 Installation Instructions Ultimate Screen English Version 2.3 REMARKS. This manual simply describes the rules governing use and installing of the Ultimate Screen Blind. For different versions we would

More information

Reflex ex separator. Exvoid / Exvoid HC (HiCap) Exdirt / Exdirt HC (HiCap) Extwin /Extwin HC (HiCap) Operating manual

Reflex ex separator. Exvoid / Exvoid HC (HiCap) Exdirt / Exdirt HC (HiCap) Extwin /Extwin HC (HiCap) Operating manual Reflex ex separator Exvoid / Exvoid C (icap) Exdirt / Exdirt C (icap) Extwin /Extwin C (icap) 21.11.2016 GB Operating manual English Refle x ex sep ar ato r Contents 21.11.2016 Contents 1 Safety... 4

More information

Honeywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION

Honeywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION Honeywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION The VV Series class A vent valves are intended to be used in combination with the VQ400M series combination valve.

More information

HOT WASHER MODEL NO: KING 125 OPERATION & MAINTENANCE INSTRUCTIONS PART NO: LS1009

HOT WASHER MODEL NO: KING 125 OPERATION & MAINTENANCE INSTRUCTIONS PART NO: LS1009 HOT WASHER MODEL NO: KING 125 PART NO: 7320170 OPERATION & MAINTENANCE INSTRUCTIONS LS1009 INTRODUCTION Thank you for purchasing this Hot Washer. This machine is a portable, high pressure power washer,

More information

PolAIR High Pressure Fog Cooling System. Important Installation Notes Please read before starting installation

PolAIR High Pressure Fog Cooling System. Important Installation Notes Please read before starting installation PolAIR High Pressure Fog Cooling System Important Installation Notes Please read before starting installation Read operational manual for POlAIR Controller before starting. Familiarize yourself with the

More information

AUTOMATIC POOL COVER. Serial number: ENGLISH SOLAR CARLIT MODEL INSTALLATION MANUAL AND MAINTENANCE /18 Revision number

AUTOMATIC POOL COVER. Serial number: ENGLISH SOLAR CARLIT MODEL INSTALLATION MANUAL AND MAINTENANCE /18 Revision number AUTOMATIC POOL COVER SOLAR CARLIT MODEL INSTALLATION MANUAL AND MAINTENANCE Serial number: Revision number: 008-2008-01-31 - 1 -/18 Revision number 008-2008-01-31 TABLE OF CONTENTS - Personnel and material

More information

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve Type 3310/AT and Type 3310/3278 Pneumatic Control Valves Type 3310 Segmented Ball Valve Fig. 1 Type 3310/3278 with positioner Fig. 2 Type 3310/AT Mounting and Operating Instructions EB 8222 EN Edition

More information

Flue installation instructions. Air flue duct for use with ecomax and ecotec boilers. For the installer

Flue installation instructions. Air flue duct for use with ecomax and ecotec boilers. For the installer 834449_05GB_022005.qd 02.02.2005 17:12 Uhr Seite 1 For the installer Flue installation instructions Air flue duct for use with ecomax and ecotec boilers ecomax 613/2 E ecomax 618/2 E ecomax 622/2 E ecomax

More information

12v / 24v Diesel Transfer Pump Kit

12v / 24v Diesel Transfer Pump Kit Please dispose of packaging for the product in a responsible manner. It is suitable for recycling. Help to protect the environment, take the packaging to the local amenity tip and place into the appropriate

More information

Installation and service instruction

Installation and service instruction Original Installation and service instruction Table of contents A) General... 2 A1 Symbols... 2 A2 Valve destination... 2 A3 Related documents... 2 A4 Valve marking... 3 A5 Transport, storage and handling...

More information

Installation Instructions LamboStyleDoors (The instruction are to be used as a reference. Please repeat for both doors)

Installation Instructions LamboStyleDoors (The instruction are to be used as a reference. Please repeat for both doors) Installation Instructions LamboStyleDoors (The instruction are to be used as a reference. Please repeat for both doors) Pre installation check list: - Double check vehicles data with TUV certificate -

More information

King Dome. user manual

King Dome. user manual King Dome user manual INTRODUCTION The Martin King Dome is a light weight, inflatable transparent housing for protection of a luminaire from precipitation in temporary outdoor applications. It features

More information

Installation instructions for the TriVision Car Docking Station

Installation instructions for the TriVision Car Docking Station Contents 1. Symbols used in this installation guide......................................... 30 2. Prior to installation......................................................... 31 3. Safety instructions.........................................................

More information

DORMA INTERIOR. DORMA PURE FAMELESS SLIDING Glass Wall Systems

DORMA INTERIOR. DORMA PURE FAMELESS SLIDING Glass Wall Systems TABLE OF CONTENTS Overview Intended use Structure requirements and fittings Requirements for glass panel Safety instructions Symbols used - safety/ installation Maintenance, care, repair Disposal 3 Overall

More information

WARNING Carefully Read These Instructions Before Use

WARNING Carefully Read These Instructions Before Use DO NOT RETURN THIS SPRAYER TO STORE Call: 1-800-950-4458 Backpack Sprayer Use and Care Manual Manufactured for Northern Tool + Equipment Co., Inc. WARNING Carefully Read These Instructions Before Use Model

More information

Elektric actuator MC50/24-C

Elektric actuator MC50/24-C Issue 2014-04-29 Operating manual 3.10-TA.150-15-EN Elektric actuator for KTM512, KTH512 DN15-50 Application Elektric actuator for 3-point or modulating controllers in heating systems. Positive connection

More information

VIESMANN. Installation instructions VITOSOL-F. for contractors

VIESMANN. Installation instructions VITOSOL-F. for contractors Installation instructions for contractors VIESMANN Vitosol-F Type SV and SH Flat-plate collector for installation on supports and wall mounting VITOSOL-F 9/2010 Dispose after installation. Safety instructions

More information

LED GEL MOUNTED FRAME

LED GEL MOUNTED FRAME LED31-11onmp1.pdf INSTRUCTION MANUAL Model: LED-31-11-3200(5600) Lamps: 15 4 W LEDs driven at 2 W Driver: Electronic, high frequency Beam angle: 11 degrees Voltage: 120, 230, 277 50-60 Hz Manufacturer:

More information

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 1054-7 / 34405 www.onicon.com sales@onicon.com

More information

GREENOx BT LOW RETURN TEMPERATURE DUAL BT WITH TILED BOILERS. GREENOx BT COND LOW RETURN TEMPERATURE WITH CONDENSER

GREENOx BT LOW RETURN TEMPERATURE DUAL BT WITH TILED BOILERS. GREENOx BT COND LOW RETURN TEMPERATURE WITH CONDENSER TECHNICAL MANUAL GREENOx BT LOW RETURN TEMPERATURE DUAL BT WITH TILED BOILERS GREENOx BT COND LOW RETURN TEMPERATURE WITH CONDENSER GREENOx/GREENOx.e/K WITH THREE GAS PASSES DUAL GRX/DUAL GRX.e THREE GAS

More information

VADA - V75-S PRODUCT OVERVIEW CONSTRUCTION USAGE LIMITATIONS MOTOR WARRANTY

VADA - V75-S PRODUCT OVERVIEW CONSTRUCTION USAGE LIMITATIONS MOTOR WARRANTY PRODUCT OVERVIEW The VADA V75-S submersible pumps are suitable for installation in traditional wells, water deposits, collection tanks, clear watercourses, lakes etc. The V75-S provides a hydraulic system

More information

Installation and service instruction

Installation and service instruction Original Installation and service instruction Knife gate valves Original Installation and service instruction Knife gate valves Table of contents A) General... 3 A1 Symbols... 3 A2 Valve destination...

More information

INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL INSTALLATION AND OPERATION MANUAL Models S120U & S240U Read all instructions before assembling or using the SunHeater system. Retain this manual for future use. TABLE OF CONTENTS Important Safety Information...2

More information

Differential pressure gauge with output signal For the process industry, all-metal media chamber Models DPGT and DPGT43.160

Differential pressure gauge with output signal For the process industry, all-metal media chamber Models DPGT and DPGT43.160 Pressure Differential pressure gauge with output signal For the process industry, all-metal media chamber Models DPGT43.100 and DPGT43.160 k Applications Acquisition and display of process values Output

More information

Installation Instructions LamboStyleDoors (The instruction are to be used as a reference. Please repeat for both doors)

Installation Instructions LamboStyleDoors (The instruction are to be used as a reference. Please repeat for both doors) Installation Instructions LamboStyleDoors (The instruction are to be used as a reference. Please repeat for both doors) Mercedes C-Class Sport coupé type W203 Part number 500 25 009 Pre installation check

More information

MECHANICAL CYLINDERS Operating Instructions

MECHANICAL CYLINDERS Operating Instructions SW3001EN.1 MECHANICAL CYLINDERS Operating Instructions Sweden Int +46 372 265 00 info@swedrive.se Vat.no SE556145631901 138-4551 1 Table of Contents 1. Health and Safety... 3 1.1. Notice about safety...

More information

COMPONENTS FOR SOLAR THERMAL SYSTEMS

COMPONENTS FOR SOLAR THERMAL SYSTEMS COMPONENTS FOR SOLAR THERMAL SYSTEMS The Caleffi Solar product range has been specially developed for use in solar thermal systems, where high temperatures can normally be reached and where, depending

More information

SOLAR-LUX 6/12 INSTALLATION AND MAINTENANCE INSTRUCTIONS EVACUATED TUBE COLLECTOR FLAT ROOF INSTALLATION (30, 45 ) WALL INSTALLATION (45, 60, 90 )

SOLAR-LUX 6/12 INSTALLATION AND MAINTENANCE INSTRUCTIONS EVACUATED TUBE COLLECTOR FLAT ROOF INSTALLATION (30, 45 ) WALL INSTALLATION (45, 60, 90 ) INSTALLATION AND MAINTENANCE INSTRUCTIONS EVACUATED TUBE COLLECTOR SOLAR-LUX 6/ 6 70 646 0-00.0TL FLAT ROOF INSTALLATION (0, 45 ) WALL INSTALLATION (45, 60, 90 ) UK/IE 6 70 647 04 (0/0) GB/IE TABLE OF

More information

Technical Information Manual

Technical Information Manual Technical Information Manual Revision n. 4 18 June 2008 MOD. A3000NF 3-PHASE NOTCH FILTER MANUAL REV. 4 NPO: 00120/04:3000N.MUTx/04 CAEN will repair or replace any product within the guarantee period if

More information

Read this entire manual before operation begins.

Read this entire manual before operation begins. Read this entire manual before operation begins. Record below the following information which is located on the serial number data plate. Serial No. Model No. Date of Installation Contents Specifications.............

More information

www.greenelectricalsupply.com 1x4 2x2 & 2x4 Read all instructions and warnings before attempting installation. RISK OF FIRE OR ELECTRIC SHOCK. LED RETROFIT INSTALLATION REQUIRES KNOWLEDGE OF LUMINAIRES

More information

Operating Instructions

Operating Instructions Operating Instructions Pendant Light Fitting > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Notes Regarding Safety...3 4 Intended Area of Application...4 5 Technical Data...5

More information

Preventive maintenance 4

Preventive maintenance 4 00 Series Preventive maintenance Preventive maintenance periods Use the procedures in this chapter to maintain your engine in accordance with the preventive maintenance schedule. Check the periods given

More information