PROJ. NO SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

Size: px
Start display at page:

Download "PROJ. NO SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS"

Transcription

1 SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the following components and accessories: 1. Hot water heating coils. 2. Chilled water cooling coils. 3. Direct-Expansion cooling 4. Scroll Compressors 5. Variable frequency controllers 6. Economizer outdoor- and return-air damper section. 7. Roof curbs. 1.3 SUBMITTALS A. Product Data: Include manufacturer's technical data for each model indicated, including rated capacities of selected model clearly indicated; dimensions; required clearances; shipping, installed, and operating weights; furnished specialties; accessories; and installation and startup instructions. B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loadings, required clearances, method of field assembly, components, and location and size of each field connection. Detail mounting, securing, and flashing of roof curb to roof structure. Indicate coordinating requirements with roof membrane system. 1. Wiring Diagrams: Detail wiring for power, signal, and control systems and differentiate between manufacturer-installed and field-installed wiring. C. Commissioning Reports: Indicate results of startup and testing commissioning requirements. Submit copies of checklists. D. Maintenance Data: For equipment to include in the maintenance manuals. 1.4 QUALITY ASSURANCE / 1

2 PROJ. NO A. ARI Certification: Rooftop air-handling units and their components shall be factory tested according to the applicable portions of ARI 430, "Central-Station Air-Handling Units," and shall be listed and bear the label of the Air-Conditioning and Refrigeration Institute (ARI). B. UL and NEMA Compliance: Provide motors required as part of air-handling units that are listed and labeled by UL and comply with applicable NEMA standards. C. Listing and Labeling: Provide electrically operated components specified in this Section that are listed and labeled. 1. The Terms "Listed" and "Labeled": As defined in the National Electrical Code, Article 100. D. Comply with NFPA DELIVERY, STORAGE, AND HANDLING A. Deliver rooftop units as factory-assembled units with protective crating and covering. B. Handle rooftop units to comply with manufacturer's written rigging and installation instructions for unloading and moving to final location. 1.6 COORDINATION A. Coordinate installation of roof curbs, equipment supports, and roof penetrations. 1.7 EXTRA MATERIALS A. Furnish extra materials described below that match products installed, are packaged with protective covering for storage, and are identified with labels describing contents. 1. Fan Belts: One set for each belt-driven fan. 2. Filters: One set of filters for each unit. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. AAON. (RN and RQ Series) 2.2 ROOFTOP AIR HANDLING UNITS A. General: Provide rooftop air handling units of capacities and characteristics as scheduled on the drawings / 2

3 1. Each unit shall be completely factory assembled, piped, wired, tested and shipped in one piece. The unit shall have single point power connection. Units shall be specifically designed for outdoor rooftop application and include a weatherproof cabinet. Modified interior air handling units are not acceptable. 2. All units shall have decals and tags to indicate caution areas and aid unit service. Unit nameplates shall be fixed to the main control panel door. Electrical wiring diagrams shall be attached to the control panels. Installation and maintenance bulletins shall be supplied with each unit. B. Cabinet, Casing and Frame: 1. The frame and unit base shall be made of minimum 14 gauge galvanized steel; cabinet shall be constructed of minimum 22 gauge galvanized steel. The unit base shall overhang the roof curb for water runoff and shall have a formed recess that seats on roof curb gasket to provide a positive weathertight seal. Unit cabinet shall be designed to operate at total static pressures up to 6-inches wg. 2. Exterior surfaces shall be phosphatized and coated with baked-on enamel. Hinged doors shall be provided for access to each unit section and shall be constructed of galvanized steel with flush mounted single lever, staggered engagement latching mechanism. 3. Unit shall be completely insulated with 2" thick, R-13 closed-cell foam. All interior casing surface shall have solid minimum 24 gauge galvanized sheetmetal liners completely enclosing insulation. Lifting brackets shall be provided on the unit base with lifting holes to accept cable or chain hooks. C. Coil Section: 1. Chilled water (if applicable) and hot water coils shall be fabricated from seamless copper tubing mechanically bonded to rippled and corrugated aluminum fins. Coils shall be factory piped to a location within the unit to permit field connection to building piping distribution systems. Coils shall be factory leak tested under water. Coil capacities shall be ARI certified. 2. A double-sloped, insulated, stainless steel drain pan shall be provided with the cooling coil, and shall extend beyond the leaving side of the coil and under the cooling coil connections. The drain pan shall be connected to a threaded drain connection extending through the unit housing. 3. Drain piping shall be constructed of Schedule 40 PVC pipe with a deep seal p- trap and assembled with Type DWV solvent welded fittings. Terminate piping over a 4-inch thick solid concrete splash block on the roof. 4. Units shall be provided with a pipe chase section for field installation of piping, and accessories. D. Direct Expansion Coil Section (If Applicable): 1. Minimum Number of Refrigerant Circuits: Two (2) a. Exception: Units sized 15 tons total cooling and less may have a single refrigeration circuit. 2. Compressors: Provide direct-drive hermetic, scroll type, mounted on vibration isolators; with internal overcurrent and high-temperature protection, internal pressure relief, and crankcase heater. a. Minimum number of compressors and temperature control stages: Four (4) compressors and four (4) stages of capacity control (plus off) / 3

4 PROJ. NO ) Two (2) compressors will be acceptable if one of the compressors is modulation, variable speed or is a Copeland digital scroll. The minimum capacity step shall be no more than 10% of total unit capacity. 3. Refrigeration Specialties: a. Refrigerant: R-410A b. Expansion valve with replaceable thermostatic element. c. Refrigerant filter/dryer d. Manual-reset high-pressure safety switch. e. Automatic-reset low-pressure safety switch. f. Minimum off-time relay. g. Automatic-reset compressor motor thermal overload. h. Brass service valves installed in compressor suction and liquid lines. E. Direct Driven Supply-Air Fans: Unhoused, backward curved, plenum supply fan; with permanently lubricated, variable-speed motor installed on an adjustable fan base resiliently mounted in the casing. Bearings shall be selected for L50 life at 200,000 hrs. 1. Extended grease lines static deflection spring isolators. F. Condenser-Coil Fan: Vertical discharge, axial flow, direct drive fans. G. Variable Frequency Drives: Variable air volume fan control shall be provided via an adjustable frequency drive factory installed and wired. Variable frequency drives shall be housed in a conditioned unit section providing ambient temperatures compatible with the operating temperature range of the VFD. VFD shall be as manufactured by Eaton Corp.; Westinghouse & Cutler-Hammer Products; or Square D Co.. 1. Description: NEMA ICS 2, variable-frequency controller, listed and labeled as a complete unit and arranged to provide variable speed of a standard NEMA MG 1, Design B, 3-phase, induction motor by adjusting output voltage and frequency. 2. Design and Rating: Match load type such as fans; and type of connection used between motor and load such as direct or through a power-transmission connection. 3. Isolation Transformer: Match transformer voltage ratings and capacity to system and motor voltages; and controller, motor, drive, and load characteristics. 4. Output Rating: 3-phase, 6 to 66 Hz, with torque constant as speed changes. 5. Starting Torque: 100 percent of rated torque. 6. Speed Regulation: Plus or minus one percent. 7. Ambient Temperature: 0 to 40 deg C. 8. Efficiency: 95 percent minimum at full load and 60 Hz. 9. Internal Adjustability: Include the following internal adjustment capabilities: a. Minimum Speed: 5 to 25 percent of maximum rpm. b. Maximum Speed: 80 to 100 percent of maximum rpm. c. Acceleration: 2 to 22 seconds. d. Deceleration: 2 to 22 seconds. e. Current Limit: 50 to 110 percent of maximum rating / 4

5 10. Multiple-Motor Capability: Controller suitable for service to multiple motors and furnished with a separate overload relay and protection for each controlled motor. Shut off the controller and motors served by it when an overload relay is tripped. 11. Self-protection and reliability features include the following: a. Input transient protection by means of surge suppressors. b. Snubber networks to protect against malfunction due to system voltage transients. c. Motor Overload Relay: Adjustable and capable of NEMA 250, Class 10 performance. d. Notch filter to prevent operation of the controller-motor-load combination at a natural frequency of the combination. e. Instantaneous overcurrent trip. f. Loss of phase protection. g. Reverse phase protection. h. Under- and overvoltage trips. i. Overtemperature trip. j. Short-circuit protection. k. Harmonic Filters. 12. Automatic Reset/Restart: Attempt 3 restarts after controller fault or on return of power after an interruption and before shutting down for manual reset or fault correction. Restarting during deceleration will not damage controller, motor, or load. 13. Status Lights: Door-mounted LED indicators to indicate the following conditions: a. Power on. b. Run. c. Overvoltage. d. Line fault. e. Overcurrent. f. External fault. 14. Panel-Mounted Operator Station: Start-stop and auto-manual selector switches with manual speed control potentiometer and elapsed time meter. 15. Indicating Devices: Meters or digital readout devices and selector switch, mounted flush in controller door and connected to indicate controller output current, voltage, and frequency. 16. Manual Bypass: Magnetic contactor arranged to safely transfer motor between controller output and bypass controller circuit when motor is at zero speed. Controller-off-bypass selector switch indicator lights set and indicate mode selection. 17. An integral disconnect switch shall be provided. 18. Bypass Controller: NEMA ICS 2, full-voltage, nonreversing motor controller, provides across-the-line starting capability in manual-bypass mode. Provide motor overload protection under both modes of operation with control logic that allows common start-stop capability in either mode. 19. Isolating Switch: Non-load-break switch arranged to isolate variable-frequency controller and permit safe troubleshooting and testing, both energized and deenergized, while motor is operating in bypass mode / 5

6 PROJ. NO Remote Indicating Circuit Terminals: Mode selection, controller status, and controller fault. H. Filter Section: 1. The filter shall be supplied complete with filter rack as an integral part of the unit. Filters shall be accessible from both sides of the unit. 2. The filter section shall be provided with 2" thick, MERV-8 pleated filters designed to slide into the galvanized steel racks. I. Outside Air Section: 1. The outside and return air section shall be designed to form a plenum. Outside air arrangement shall be 0-100% outside air with economizer control. 2. Outside air shall be introduced through louvered intake panels complete with rain lip and bird screen. The units floor of the outside air section shall provide for water drainage. The outside and return air dampers shall be sized to handle 100% of the supply air volume. The dampers shall be arranged to converge the return and outside airstreams in mixing patterns. Low leak dampers shall be provided. Dampers shall be hollow core, air foil type and fully gasketed and side sealed. Leakage shall not exceed 0.3% at 3" S.P. 3. A relief type exhaust air damper shall be provided and shall be located in the return air section to exhaust air out of the back of the unit. Exhaust louvers and bird screen shall be provided to prevent infiltration. Exhaust dampers shall be lined with urethane gasketing on contact edges. Mechanical closure shall be provided on the dampers by means of a motor operator which shall shut the exhaust dampers when the unit is in unoccupied mode. J. Electrical: 1. Each unit shall be wired and tested at the factory before shipment. Wiring shall comply with NEC requirements and shall conform to all applicable UL standards. All electrical components shall be labeled according to the electrical diagram and shall be UL recognized where applicable. Each unit shall have a 115 volt circuit transformer, 115 volt receptacle, and control circuit fuse. 2. The supply air fan motor branch circuit shall be individually fused. The supply air fan motor shall have contactors and external overload protection. 3. Main control panel shall be of weatherproof construction with a dead front cover over main power circuit control. A terminal block shall be provided for the main power connection and a terminal board shall be provided for the low voltage control wiring. Knockouts shall be provided in the bottom of the main control panels for field wiring entrance. 4. A main unit non-fused disconnect switch in a NEMA 3R enclosure shall be provided. K. Roof Curbs: 1. Prefabricated 12-gauge galvanized steel mounting curbs furnished by the unit manufacturer shall be provided for field assembly on the roof decking prior to unit shipment. The roof curbs shall be perimeter type with complete perimeter support of the unit. Deliver curbs to the General Contractor for installation 2. The curb shall be a minimum of 16" high and include a nominal 2" x 4" wood nailer strip / 6

7 3. Gasketing shall be provided for field mounting between the unit base and the roof curb. L. Unit Control System: 1. All controls shall be provided by the Building DDC System Supplier (Controls Contractor) as specified in Division MOTORS A. Refer to Division 23 Section "Common Motor Requirements for HVAC Equipment" for general requirements for factory-installed motors. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine roof for compliance with requirements for conditions affecting installation and performance of rooftop units. Do not proceed with installation until unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. Install units according to manufacturer's written instructions. B. Install units level and plumb, maintaining manufacturer's recommended clearances. C. Curb Support: Install and secure rooftop units on curbs. 3.3 CONNECTIONS A. Piping installation requirements are specified in other Division 23 Sections. Drawings indicate the general arrangement of piping, fittings, and specialties. The following are specific connection requirements: 1. Install piping to allow service and maintenance. 2. Hot Water and Chilled-Water Piping: Conform to applicable requirements of Division 23 Section "Hydronic Piping." Connect with shutoff valve and union or flange. B. Duct installation requirements are specified in other Division 23 Sections. Drawings indicate the general arrangement of ducts. 3.4 FIELD QUALITY CONTROL A. Verify that installation is as indicated and specified / 7

8 PROJ. NO B. Complete manufacturer's installation and startup checks and perform the following: 1. Level unit on curb, and flash curbs to unit and to roof. 2. Inspect for visible damage to unit casing. 3. Verify that clearances have been provided for servicing. 4. Check that labels are clearly visible. 5. Verify that controls are connected and operable. 6. Remove shipping bolts, blocks, and tie-down straps. 7. Verify that filters are installed. 8. Adjust vibration isolators. 9. Check operation of dampers. C. Lubricate bearings on fan. D. Check fan-wheel rotation for correct direction without vibration and binding. E. Adjust fan belts to proper alignment and tension. F. Start unit according to manufacturer's written instructions. G. Check and record performance of interlocks and protection devices; verify sequences. H. Operate unit for an initial period as recommended or required by manufacturer. I. Check internal isolators. J. Check outside-air damper for proper stroke and interlock with return-air dampers. K. Check controls for correct sequencing of heating, mixing dampers, and normal and emergency shutdown. L. Measure and record the following: 1. Coil leaving-air, dry- and wet-bulb temperatures. 2. Coil entering-air, dry- and wet-bulb temperatures. 3. Outside-air, dry-bulb temperature. M. Measure and record the following minimum and maximum airflows. Plot fan volumes on fan curve. 1. Supply-air volume. 2. Return-air volume. 3. Relief-air volume. 4. Outside-air intake volume. N. After starting and performance testing, change filters, vacuum coils, lubricate bearings, adjust belt tension, and check operation of power vents. 3.5 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel as specified below: / 8

9 1. Train Owner's maintenance personnel on procedures and schedules related to startup and shutdown, troubleshooting, servicing, and preventive maintenance. 2. Review data in the maintenance manuals. 3. Schedule training with Owner, through the Architect, with at least 7 days' advance notice. END OF SECTION / 9

Ice Rink Renovation & New Clubhouse

Ice Rink Renovation & New Clubhouse SECTION 262913 - ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION AXIAL HVAC FANS

SECTION AXIAL HVAC FANS SECTION 233413 - AXIAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS SECTION 16420 ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

SECTION CENTRIFUGAL HVAC FANS

SECTION CENTRIFUGAL HVAC FANS SECTION 233416 - CENTRIFUGAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 22 1123.13 DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Related Sections: 1. Section 15050 - Basic Mechanical Requirements. 2. Section 15051 - Motors. 3. Section 15185 - Hydronic Pumps. 4. Section 15625 - Centrifugal

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Climas y Proyectos Leyco, S.A. de C.V.

Climas y Proyectos Leyco, S.A. de C.V. GENERAL DESCRIPTION : FURNISH AND INSTALL MULTI COMPONENT ROOF MOUNTED LEYCO, MODEL CAH CUSTOM AIR HANDLER MADE SELF-CONTAINED, WEATHER RESISTANT, AIR HANDLING UNITS PER MODEL NUMBER, AND PERFORMANCE DATA

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,

More information

SECTION GENERAL-SERVICE AIR COMPRESSOR PART 1 - GENERAL

SECTION GENERAL-SERVICE AIR COMPRESSOR PART 1 - GENERAL 13686.00 GENERAL SERVICE AIR COMPRESSOR 221519-1 SECTION 22 1519 - GENERAL-SERVICE AIR COMPRESSOR 1.1 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of the Contract, including General

More information

HS17. HS17 SERIES CONDENSING UNITS 17.6 to 65.2 kw ( to Btuh) Cooling Capacity. MATCHED REMOTE SYSTEMS 50hz ENGINEERING DATA

HS17. HS17 SERIES CONDENSING UNITS 17.6 to 65.2 kw ( to Btuh) Cooling Capacity. MATCHED REMOTE SYSTEMS 50hz ENGINEERING DATA ENGINEERING DATA ENGINEERING DATA MATCHED REMOTE SYSTEMS 50hz HS17 SERIES CONDENSING UNITS 17.6 to 65.2 kw (60 200 to 222 500 Btuh) HS17 Bulletin #490001 November 1995 Supersedes August 1994 HS17-1353

More information

Air Handling Unit Construction Checklist

Air Handling Unit Construction Checklist Air Handling Unit Construction Checklist Project: Date: AHU Tag: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards: SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

"SPOAU" DEDICATED 100% OUTSIDE AIR UNITS Self Contained Single Package or Split System Units

SPOAU DEDICATED 100% OUTSIDE AIR UNITS Self Contained Single Package or Split System Units "SPOAU" DEDICATED 100% OUTSIDE AIR UNITS Self Contained Single Package or Split System Units Spinnaker Industries Inc. Model Series SPOAU 100% Outdoor Air Systems shall be factory assembled, wired and

More information

CHP

CHP Packaged Unit Heat Pump CHP16-024-030-036-048-060 2-5 Ton Cooling 23,000-57,500 Btuh Heating 12,800-85,300 Btuh (5-25 kw) Optional Electric Heating FEATURES Designed for outdoor rooftop or ground level

More information

University of Delaware

University of Delaware SECTION 23 36 00 _ SUMMARY PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Constant/Variable volume supply terminal units. 2. Fan powered terminal units. 3. Exhaust valves B. Related Sections: Section

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 23 3600 - AIR TERMINAL DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fan-powered air terminal units/devices. 2. Shut off air terminal units/devices. 3. Dual duct terminal units/devices.

More information

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS 50FN-1SB 50FNX,FNY078,088,104 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE AIR VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE WITH INTEGRAL ECONOMIZER AND HIGH-CAPACITY MODULATING

More information

ERV ENERGY RECOVERY VENTILATOR 60 HZ. Indoor / Outdoor 500 to 10,000 cfm Capacity ERV I - D - D - P - 1 MODEL NUMBER IDENTIFICATION

ERV ENERGY RECOVERY VENTILATOR 60 HZ. Indoor / Outdoor 500 to 10,000 cfm Capacity ERV I - D - D - P - 1 MODEL NUMBER IDENTIFICATION P R O D U C T S P E C I F I C AT I O N S I N D O O R A I R Q U A L I T Y ERV ENERGY RECOVERY VENTILATOR 60 HZ Bulletin No. 20245 March 200 Supersedes April 2009 Indoor / Outdoor 500 to 0,000 cfm Capacity

More information

UNIVERSITY OF NORTH FLORIDA Arena HVAC Replacement SECTION MODULAR INDOOR CENTRAL-STATION AIR-HANDLING UNITS

UNIVERSITY OF NORTH FLORIDA Arena HVAC Replacement SECTION MODULAR INDOOR CENTRAL-STATION AIR-HANDLING UNITS SECTION 23 73 13 MODULAR INDOOR CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions.

More information

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499]

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499] BC--1.0 03-01-1 Belt Drive Blower Coil Unit, Basic Unit Discharge ARGT. 1 4. See page 1 for filter rack details. 5. Base rail is optional on he base unit. See page 13. Base rails must be used with mixing

More information

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL 13686.00 MECHANICAL AND ELECTRICAL COORDINATION 230002-1 SECTION 230002 MECHANICAL AND ELECTRICAL COORDINATION 1.1 WORK INCLUDED PART 1 - GENERAL A. Work Included in This Section: Materials, equipment,

More information

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS 550.13-TG1Y(98) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS HCA300, 360, 80 & 600 5 THRU 50 NOMINAL TONS HCA80 DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece

More information

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410. PART 1 - GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

XeteX, Inc. All Rights Reserved.

XeteX, Inc. All Rights Reserved. Model XC Indoor or outdoor mounted, simple, in-case aluminum flat plate exchanger with options for frost control. Ideal for inline installations: in duct-work systems, in built-up units, or in modular

More information

FS Fan-Coil Units Hi-Rise, Vertical

FS Fan-Coil Units Hi-Rise, Vertical FS Fan-Coil Units Hi-Rise, Vertical FSC Concealed Dimensional Data 4-PIPE 2-PIPE TOP VIEWS Page Trims Short (5/8") Here! SIDE VIEW FRONT VIEW Dimensions Unit Size A B Single/Double Supply C D E 03 & 04

More information

Issue 4 (Record Only) Job #: Innovent Submittal Date: October 30, 2012 Project: Location: Columbus, OH Innovent Job #: Submittal Issue: 4 (Record Only) Engineer: Contractor: Tag Innovent Model # AHU-BG-01

More information

PROJ. NO SECTION HYDRONIC PUMPS

PROJ. NO SECTION HYDRONIC PUMPS SECTION 23 21 23 HYDRONIC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System V-Series (rev. 08/17/10) Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System Note: Optional items and/or items requiring a choice, are shown between brackets and/or parentheses

More information

Complete HVAC Capability

Complete HVAC Capability Air Handling Units Brochure 1110 January 2006 Complete HVAC Capability MEA Horizontal Draw-Thru to Size 65 Vertical Draw-Thru to Size 50 1000 to 60,000 CFM Forward Curved or Airfoil Wheels Inlet Vane Option

More information

SECTION (15444) - DOMESTIC WATER PACKAGED BOOSTER PUMPS

SECTION (15444) - DOMESTIC WATER PACKAGED BOOSTER PUMPS SECTION 22 11 23.13 (15444) - DOMESTIC WATER PACKAGED BOOSTER PUMPS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Packaged Domestic Water Booster Pumps B. Related Sections: 1.02 REFERENCES 1. Section

More information

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators Version: Dec. 01, 2004 RERV & RERVX Rotary Energy Recovery Ventilators Indoor and Outdoor Installations 250 20,000 CFM Capacities RERVLP Low Profile Indoor Rotary Energy Recovery Ventilators Ideal for

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

RAV Sales Guide FAN COIL UNITS HI-RISE, VERTICAL

RAV Sales Guide FAN COIL UNITS HI-RISE, VERTICAL RAV Sales Guide FAN COIL UNITS HI-RISE, VERTICAL RAVS RARM RARS RAVE RAVM RAVL RARP RISER www.superiorrex.com RAV Series: VERTICAL HI-RISE CONCEALED SO TOUGH, WE GUARANTEE IT! www.superiorrex.com Model

More information

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL SO TOUGH, WE GUARANTEE IT. SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL SBH SBV www.superiorrex.com SO TOUGH, WE GUARANTEE IT! www.superiorrex.com SBH / SBV Series: CONSTRUCTION FEATURES

More information

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 90 71 PART 1 GENERAL 1.01 DESCRIPTION A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings

More information

2SA13 60HZ P A C K A G E D E L E C T R I C / E L E C T R I C

2SA13 60HZ P A C K A G E D E L E C T R I C / E L E C T R I C P A C K A G E D E L E C T R I C / E L E C T R I C 2SA13 60HZ E N G I N E E R I N G D A T A Bulletin No. 210454 August 06 Supersedes July 06 MODEL NUMBER IDENTIFICATION SEER 13.00 2 to 2.5 Tons Capacity

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 23 30 00 - HVAC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00, "Mechanical

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Liebert CSU3000 DISCONTINUED PRODUCT. CSI Mainframe Cooling Systems. CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller

Liebert CSU3000 DISCONTINUED PRODUCT. CSI Mainframe Cooling Systems. CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller DISCONTINUED PRODUCT CSI 15621 - Mainframe Cooling Systems 1.1 SUMMARY Liebert CSU3000 CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller GUIDE SPECIFICATIONS 1.0 GENERAL These specifications describe

More information

TVS/R FAN COIL UNITS HI-RISE, VERTICAL

TVS/R FAN COIL UNITS HI-RISE, VERTICAL TVS/R FAN COIL UNITS HI-RISE, VERTICAL TVRM TVRP Riser TVRS TVSE TVSM TVSR TVSS Redefine your comfort zone. www.titus-hvac.com Redefine your comfort zone www.titus-hvac.com Model TVS/R: CONCEALED, HI-RISE

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS 50Hz Single Package Rooftop, Cooling Only with Puronr (R---410A) Refrigerant One Stage Cooling Capacity Control: Size 07 Two Stage Cooling Capacity Control: Sizes 08, 09, 12 & 14 Submittal Data PERFORMANCE

More information

SECTION DUST COLLECTOR

SECTION DUST COLLECTOR PART1-GENERAL 1.1 DESCRI PTION A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract Drawings. 1.2 SUBMITTALS

More information

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS DIVISION 26 ELECTRICAL SECTION 26 28 19 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection

More information

AIR COOLED CHILLERS WATER COOLED CHILLERS

AIR COOLED CHILLERS WATER COOLED CHILLERS AIR COOLED CHILLERS WATER COOLED CHILLERS STANDARD UNIT SPECIFICATIONS OF COMMERCIAL AIR COOLED CHILLERS General Description & Assembly Air Cooled Chillers are commercial packaged systems complete with

More information

SECTION DUCTWORK ACCESSORIES

SECTION DUCTWORK ACCESSORIES SECTION 15910 DUCTWORK ACCESSORIES PART 1- GENERAL SCOPE This sections includes accessories used in the installation of duct systems. Included are the following topics: PART 1- GENERAL Related Work Reference

More information

50JZ 7 to 14 kw ( ) STANDARD EFFICIENCY. SINGLE-PACKAGE 50 Hz. ELECTRIC HEAT PUMP UNITS with optional ELECTRIC HEAT

50JZ 7 to 14 kw ( ) STANDARD EFFICIENCY. SINGLE-PACKAGE 50 Hz. ELECTRIC HEAT PUMP UNITS with optional ELECTRIC HEAT 50JZ (50Hz.)-C1SB 50JZ 7 to 14 kw (024-048) STANDARD EFFICIENCY SINGLE-PACKAGE 50 Hz. ELECTRIC HEAT PUMP UNITS with optional ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB

More information

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

1. Division 26 Section Elevator Shunt-Trip Fused Disconnect Switches. SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

Submittal 30 [762] 36 [914] 40 [1016] 50 [1270] 60 [1524] 70 [1778]

Submittal 30 [762] 36 [914] 40 [1016] 50 [1270] 60 [1524] 70 [1778] FCU-THBP-1.0 08-22-18 THBP Horizontal Low Profile Plenum Return Top View (Drain Pan Omitted) Bottom View Front View Left hand unit shown. All dimensions are inches [millimeters]. Side View Unit Size A

More information

Direct Gas-Fired Heating

Direct Gas-Fired Heating Direct Gas-Fired Heating Model DG 800 to 15,000 cfm Up to 1,600,000 BTU/hr Optional Evaporative Cooling January 2005 PRODUCT FEATURES Model DG Direct Gas-Fired Make-Up Air Unit The Greenheck model DG is

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

HS18 HS18 SERIES CONDENSING UNITS EXPANSION VALVE AIR CONDITIONING SYSTEM. 3.6 to 16.0 kw ( to Btuh) Cooling Capacity ENGINEERING DATA

HS18 HS18 SERIES CONDENSING UNITS EXPANSION VALVE AIR CONDITIONING SYSTEM. 3.6 to 16.0 kw ( to Btuh) Cooling Capacity ENGINEERING DATA ENGINEERING DATA ENGINEERING DATA MATCHED CONDENSING REMOTE SYSTEMS UNITS 50hz HS18 SERIES CONDENSING UNITS EXPANSION VALVE AIR CONDITIONING SYSTEM 3.6 to 16.0 kw (12 200 to 54 700 Btuh) HS18 Bulletin

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not

More information

Submittal. Front View Side View

Submittal. Front View Side View RBHO Horizontal Low Profile Concealed Free Return Submittal FCU-RBHO-1.0 07-25-18 Top View (Drain Pan Omitted) Bottom View Front View Side View Left hand unit shown. All dimensions are inches [millimeters].

More information

ELITE SERIES R-410A Ready - Multi-Position

ELITE SERIES R-410A Ready - Multi-Position PRODUCT SPECIFICATIONS AIR HANDLERS CBXM ELITE SERIES R-0A Ready - Multi-Position Bulletin No. 0 October 07 Supersedes June 0 Nominal Capacity -. to Tons Optional Electric Heat -. to 0 kw MODEL NUMBER

More information

D M S 760 C01 A A 1 1

D M S 760 C01 A A 1 1 CONTENTS Description Features Options Available Selection Method Product Data Cooling Performance Data (85 F Ambient Cooling Performance Data (95 F Ambient) Cooling Performance Data (105 F Ambient)..............................

More information

Typical Applications. Horizontal Installation

Typical Applications. Horizontal Installation ENGINEERING DATA COILS COIL UNITS CB19 AND CBH19 SERIES UP-FLOW, DOWN-FLOW AND HORIZONTAL COIL UNITS *12,600 to 65,500 Btuh (3.7 to 19.2 kw) Cooling Capacity 11,500 to 60,000 Btuh (3.4 to 17.6 kw) Heat

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE Single stage cooling capacity control on all 0 241 models Two stage cooling capacity control on

More information

A. This Section includes the following types of sectional overhead doors:

A. This Section includes the following types of sectional overhead doors: SECTION 08361 - SECTIONAL OVERHEAD DOORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

The Premium Quality Fan Coil Units for Horizontal Application Hydronic or Electric Heat

The Premium Quality Fan Coil Units for Horizontal Application Hydronic or Electric Heat Producing Quality Heating & Cooling Equipment For Over 50 Years CEA SERIES CEILING EPOSED HORIZONTAL FAN COIL UNITS The Premium Quality Fan Coil Units for Horizontal Application Hydronic or Electric Heat

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 263213 - ENGINE GENERATORS PART 1 - GENERAL 1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

CPC Commercial. 15- & 20-Ton, Three-Phase Packaged Air Conditioner. 20-Ton Cooling Capacity: 240,000 BTU/h

CPC Commercial. 15- & 20-Ton, Three-Phase Packaged Air Conditioner. 20-Ton Cooling Capacity: 240,000 BTU/h CPC Commercial 15- & 20-Ton, Three-Phase Packaged Air Conditioner 15-Ton Cooling Capacity: 180,000 BTU/h 20-Ton Cooling Capacity: 240,000 BTU/h Contents Nomenclature...2 Product Features...3 Product Specifications...4

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph

More information

SECTION HVAC POWER VENTILATORS

SECTION HVAC POWER VENTILATORS SECTION 233423 HVAC POWER VENTILATORS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION LIFT ARM PARKING GATES

SECTION LIFT ARM PARKING GATES St. Anthony of Padua Catholic Church Phase I The Woodlands, Texas JRA Proj. No. 15004 Issued for Bidding - 1/20/2016 SECTION 11 12 33.13 LIFT ARM PARKING GATES PART 1 - GENERAL 1.01 SUMMARY A. Section

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 MOTOR CONTROLLERS SPEC WRITER NOTE: Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

IN2 Enclosed Switches and Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

Factory Option Codes L M E S P R D V F F H E

Factory Option Codes L M E S P R D V F F H E I N D O O R A I R Q U A L I T Y P R O D U C T S P E C I F I C AT I O N S ENERGY RECOVERY SYSTEM FOR L-SERIES ROOFTOP UNITS - 60 HZ Bulletin No. 10533 January 011 Supersedes October 010 800 to 600 cfm Capacity

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Product Data. Features/Benefits 50JS SINGLE-PACKAGED HEAT PUMP 50 HZ UNITS 7 TO 18 KW (2 TO 5 NOMINAL TONS)

Product Data. Features/Benefits 50JS SINGLE-PACKAGED HEAT PUMP 50 HZ UNITS 7 TO 18 KW (2 TO 5 NOMINAL TONS) SINGLE-PACKAGED HEAT PUMP 50 HZ UNITS 7 TO 18 KW (2 TO 5 NOMINAL TONS) Product Data UNIT (50 Hz) Single-packaged Heat Pump for Residential and Light Commercial applications. Features/Benefits One-piece

More information

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: 036-21323-001-B-0202 GENERAL SPECIFICATIONS OUTDOOR UNIT: Two independent refrigerant circuits Inherently protected fan motors Two independent scroll compressors V-Coil Design Exterior service port connections

More information

R-22, 13 SEER 60 Hertz

R-22, 13 SEER 60 Hertz TECHNICAL GUIDE R-22, 13 SEER 60 Hertz Description These UPG packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point

More information

SECTION COMPRESSED-AIR PIPING FOR LABORATORY FACILITIES

SECTION COMPRESSED-AIR PIPING FOR LABORATORY FACILITIES Page 226113-1 SECTION 226113 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION FACILITY FUEL OIL PIPING

SECTION FACILITY FUEL OIL PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION VARIABLE FREQUENCY DRIVE UNITS

SECTION VARIABLE FREQUENCY DRIVE UNITS SECTION 26 29 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide variable frequency drive (VFD) units, complete and operable, in accordance with the Contract Documents. It

More information

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein. 16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional

More information

SECTION MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK

SECTION MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK PART 1 - GENERAL 1.1 GENERAL: SECTION 15150 MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK A. The Mechanical Contractor shall furnish to the Electrical Contractor for installation,

More information

A I R H A N D L E R S CB26UH-R. MERIT Series R-22 - Upflow / Horizontal P R O D U C T S P E C I F I C AT I O N S

A I R H A N D L E R S CB26UH-R. MERIT Series R-22 - Upflow / Horizontal P R O D U C T S P E C I F I C AT I O N S P R O D U C T S P E C I F I C AT I O N S A I R H A N D L E R S CB6UH-R MERIT Series R- - Upflow / Horizontal Bulletin No. 1067 April 01 Supersedes January 01 Nominal Capacity - 1.5 to 5 Tons Optional Electric

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS

Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS TABLE OF CONTENTS H & V Features and Benefits...4 Coil and Filter Data, Static Pressure Data...7 Electric Resistance Heat Section...8 Coil Information

More information

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS 50FP-1SB 50FP034, 038, 044, 048, 054, 064, 074 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE FACTORY-INSTALLED OPTIONAL ELECTRIC HEAT

More information

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes:

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes: SECTION 15970 HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Thermostats, temperature transmitters, controllers, automatic valves, dampers, damper operators, pneumatic/ electric

More information

SECTION HVAC AIR CLEANING DEVICES

SECTION HVAC AIR CLEANING DEVICES SECTION 23 40 00 HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes activated carbon filters, automatic renewable media filters, disposable, extended area panel filters, disposable

More information

DESCRIPTION FEATURES

DESCRIPTION FEATURES SPLIT-SYSTEM AIR COOLED CONDENSING UNIT H5CE150, H5CE180 AND H5CE240 12-1/2, 15 AND 20 NOMINAL TONS (World 50Hz) DESCRIPTION These outdoor condensing units are completely assembled, piped and wired at

More information

ZHA/ZHB SERIES WARNING

ZHA/ZHB SERIES WARNING Service Literature Corp. 09-L Revised 7-08 ZHA/ZHB SERIES, 4, 5 and 6 ton 0.6 to kw ZHA/ZHB06, 048, 060, 07 The ZHA/ZHB packaged electric heat pump units are available in standard cooling efficiency (06S,

More information

SECTION GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT

SECTION GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT SECTION 22 05 12 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable in the section

More information

RBV Sales Guide FAN COIL UNITS FLOOR-MOUNTED, VERTICAL

RBV Sales Guide FAN COIL UNITS FLOOR-MOUNTED, VERTICAL RBV Sales Guide FAN COIL UNITS FLOOR-MOUNTED, VERTICAL RBVS RBVR RBVC www.superiorrex.com RBV Series: LOW POWER CONSUMPTION, ACCESSIBLE AND FLEXIBLE Owners Owners can choose between a standard or elevated

More information

.3 Section Waste Management and Disposal.

.3 Section Waste Management and Disposal. Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

1. Wiring Diagrams: Power, signal, and control wiring.

1. Wiring Diagrams: Power, signal, and control wiring. Page 232123-1 SECTION 232123 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

EMIP60 ISO. EM Series, Inch Pounds - 60 Hz EM (iso) Spec Guides Drawings Spec Sheets Extended Range Ratings Low Temp Heating.

EMIP60 ISO. EM Series, Inch Pounds - 60 Hz EM (iso) Spec Guides Drawings Spec Sheets Extended Range Ratings Low Temp Heating. EMIP60 ISO EM Series, Inch Pounds 60 Hz EM007360 (iso) Spec Guides Drawings Spec Sheets Extended Range Ratings Low Temp Heating Rev 1003 Revisions: 81402 Changed EM170/240HZ dwg 31103 Changed HZ dwg to

More information

WARREN COUNTY, N.Y. M/E REFERENCE

WARREN COUNTY, N.Y. M/E REFERENCE SECTION 262000 - ELECTRIC DISTRIBUTION PART 1 - GENERAL 1.1 DESCRIPTION A. Provide a complete secondary distribution system as indicated on the Contract Documents and as specified herein. 1.2 QUALITY ASSURANCE

More information

Q6SE Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase

Q6SE Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase TECHNICAL SPECIFICATIONS Q6SE Series Single Packaged Heat Pump, Single Phase Q6SE-14 SEER, 8.0 HSPF 2-5 Ton Units Cooling: 23,000 to 58,000 Btuh Heating: 22,800 to 59,000 Btuh The Q6 Series single packaged

More information