INSTALLATION MANUAL FOR
|
|
- Kristopher Hood
- 5 years ago
- Views:
Transcription
1 MOUNTING LOCATION Reader RD- FOR RF CONTROLLER VIZIT-KTM60 R, EXIT 00M BUTTON This manual is intended as an addition to operating instructions on your access control system (ACS) units to guide through installation process. Before you start, please study thoroughly operating instructions on ACS units. RF controller VIZIT-KTM60R contains the reader RD- and control unit KTM60M, and may be used as the part of ACS as well as a stand-alone system. Please note, only VIZIT-RF keys ( KHz ) are supported. 7 mm The reader is mounted on a wall near the entrance door, outside the entrance doorway. EXIT 00M button 7 mm EXIT 00M button is intended for use with electromagnetic lock to ensure lock release from inside of the building. The button is mounted on a wall near the entrance door, inside the entrance doorway. Control unit KTM60M 6 mm The unit is located in any convenient place indoors. WARNING. Do not mount the unit near heating equipment. 00 mm 7 mm 00 ± 00 mm 00 ± 00 mm 7 mm 90 mm VCS-60R /8
2 SELECTION OF LOCK FOR VIZIT-KTM60R RF controller VIZIT-KTM60R allows operation with different types of locks, such as electromagnetic locks, various electric strikes, electromechanical solenoid locks. Electromagnetic lock The lock is blocked as long as the power is switched on. Once the current is switched off or interrupted due to a power failure, the lock is released and the door can be opened. Recommended: electromagnetic locks VIZIT with a built-in degaussing module, in combination with door closers. IMPORTANT. DO NOT use electromagnetic locks with resistance less than 0 Ohms and not provided with a built-in degaussing module. Basic types of electric strikes, solenoid locks - Fail-locked (Fail-secure) The strike / lock is blocked as long as the power is switched off. Once the voltage is switched on, the strike / lock is released and the door can be opened. Recommended: fail-locked strikes / solenoid locks with supply voltage VDC and current consumption up to A, or VDC and current consumption up to 0. A. - Fail-locked with hold-open function The strike / lock is unblocked after a short power impulse, and remains unblocked, even when the power is off. Once the door is opened and then closed again, the strike / lock will resume its normal operation, and will be blocked again. Recommended: fail-locked strikes / solenoid locks with supply voltage VDC or VDC and current consumption up to A. - Fail-unlocked (Fail-safe) The strike / lock is blocked as long as the power is switched on. Once the voltage is switched off or interrupted due to a power failure, the strike / lock is released and the door can be opened. Recommended: fail-unlocked strikes / solenoid locks with supply voltage VDC and current consumption up to 0.6 A, or VDC and current consumption up to 0. A. Note. The VIZIT-KTM60R does not support use of motor locks. VCS-60R /8
3 SELECTION OF LOCK FOR VIZIT-KTM60R Settings with regard to the lock type In order to correctly set the lock control logic, unlocked time, and lock supply voltage, the KTM60M PCB has corresponding jumpers installed: LOCK jumper defines the door lock control mode: - position ML strike / lock is released when voltage is switched off. - position EL strike / lock is released when voltage is switched on. TIME jumper defines the unlocked state duration ( or 7 seconds): - position S - unlocked state duration is second. - position 7S - unlocked state duration are 7 seconds. VOLT jumper defines the lock voltage across +DL & -DL terminals: - position voltage range within 7 VDC to VDC with current range from 0 A to A. - position 8 - voltage range within 7 VDC to 0 VDC with current range from 0 A to A. Note. The voltage ranges given are applicable for the mains voltage 0 VAC. IMPORTANT. Some models of electric strikes and solenoid locks are provided with an integrated damper diode to eliminate pulse noise after current off. If this is the case, the strike / lock has polar wiring. If an electric strike or solenoid lock does not contain a damper diode, then connect a damper diode supplied to the strike / lock's terminals observing polarity, as shown in the picture below. Diode N007 Control unit KTM60M -DL +DL - + A white stripe on the case indicates the diode s cathode Do not connect a damper diode to electromagnetic locks VIZIT for they contain a built-in degaussing module to eliminate pulse noise. VCS-60R /8
4 WIRING CABLES AND DISTANCES Wiring is recommended to be done using a cable with copper conductors () with PVC insulation () and PVC jacket (). Control unit KTM60M Electromagnetic lock VIZIT EXIT 00M button Reader RD- Note. EXIT 00M button is intended for lock release from inside of the building. Control unit KTM60M Electromechanical lock / strike Reader RD- Wires cross-sections and maximal distances are given in the table below: Circuit Maximum length, m Control Unit Reader Control Unit Button for exit Electromagnetic lock VIZIT Fail-unlocked strike / lock ( VDC / 0.6 A) 0* 0* 0 Control Unit Fail-unlocked strike / lock ( VDC / 0. A) 0 Control Unit Fail-locked strike / lock ( VDC / A or VDC / 0. A) 0 Control Unit Fail-locked strike / lock with hold-open function ( VDC / A or VDC / A) 0 Wire Diameter, mm Cross-section, mm * Capacity of the cable connecting the reader to control unit should not exceed 000 pf (approx. 0 meters for a -wire cable). VCS-60R /8
5 INSTALLATION Reader RD- 60 mm - Make measurements on a wall with center to center distance 60 mm. Drill holes () with diameter 6 mm and depth 0 mm. - Drive anchors () in the holes. - Strip the ends of connecting wires that will go to the control unit KTM60M, and solder the ends to the reader s wires following the diagrams given in the section WIRING DIAGRAMS. - Put tightly over each soldered connection a PVC tube or a heat-shrink tube around 0 mm long (). PVC tubes and heat shrink tubes are not supplied - Attach the Reader RD- to the wall and fasten two screws () in the anchors. - Drive in gags (). Anchors, screws and gags are supplied with VIZIT-KTM60R. EXIT 00M button 60 mm - Make measurements on a wall with center to center distance 60 mm. Drill holes () with diameter 6 mm and depth 0 mm. - Drive anchors () in the holes. Lock - Strip the ends of connecting wires that will go to the control unit KTM60M and to the lock and solder the ends to the button s wires following the diagrams given in the section WIRING DIAGRAMS. - Put tightly over each soldered connection a PVC tube or a heat-shrink tube around 0 mm long (). PVC tubes and heat shrink tubes are not supplied - Attach the EXIT 00M button to the wall and fasten two screws () in the anchors. - Drive in gags (). Anchors, screws and gags are supplied with EXIT 00M button. Follow directions given in the manufacturer s installation manual. VCS-60R /8
6 INSTALLATION Control unit KTM60M The control unit may be mounted on a wall or DIN-rail. - Drill in a wall holes () with diameter 6 mm and depth 0 mm. - Drive anchors () in the holes. - Attach the control unit to the wall and fasten screws () in the anchors. Anchors and screws are supplied with VIZIT-KTM60R. KTM60M mounting on a wall - Bosses on the control unit s base - DIN-rail with width mm and thickness - mm - Holder for fixing KTM60M mounting on a DIN-rail EL 6 V V 8V 8V FU FU VOLT 8 LOCK TIME PROGRAM IC S 7S ML LC ELC E -DL +DL ELC BIP RD GND 0P PRG -Unfasten two screws () and r emove the control unit s lid (). - Strip the ends of connecting wires () coming from the Reader RD-, EXIT-00M button and lock. - Connect the ends to the control unit s terminals () following the diagrams given in the section WIRING DIAGRAMS. - S et the jumpers( ) on the control unit s PCB ( 6) according to the table (default settings are given in bold font ): Lock Type Jumper LOCK TIME VOLT ELC Electromagnetic lock VIZIT Fail-unlocked strike / lock ( VDC / 0.6 A max.) ML 7s E Fail-unlocked strike / lock ( VDC / 0. A max.) ML 7s 8 E Fail-locked strike / lock ( VDC / A max.) EL 7s E Fail-locked strike / lock ( VDC / 0. A max.) EL 7s 8 E Fail-locked strike / lock with hold-open function ( VDC / A max.) Fail-locked strike / lock with hold-open function ( VDC / A max.) EL s E EL s 8 E VCS-60R 6/8
7 QUICK START OF THE CONTROL UNIT Make sure that the control unit is disconnected from the mains. Remove the PRG jumper from the control unit s PCB. Place the control unit s lid back, but do not tighten the screws. Connect the control unit to the mains. A long beep is sound ing. Perform the MASTER-key memorizing: approach a blank VIZIT-RF key close to the reader s antenna. One short and two long beeps are sounding: the MASTER-key has been recorded. Disconnect the control unit from the mains, take off the lid and restore the PRG jumper to its place. Put the lid to its place and tighten the screws. Connect the control unit to the mains. Perform ACCESS and GUARD keys memorizing as described in the VIZIT-KTM60R operating instruction. VCS-60R 7/8
8 WIRING DIAGRAMS KTM60M terminals layout: Control unit KTM60M Electromagnetic lock VIZIT -DL +DL ELC BIP RD GND OP - lock control - supply voltage for the lock - supply voltage for the reader - supply voltage for the reader s buzzer - RF key data input - ground - control signal from the EXIT 00M button White EXIT 00М button Green -DL +DL ELC BIP RD GND OP Red Black Blue Reader RD- Red Blue White Black Antenna Electromechanical lock / strike Diode N007 A white stripe on the case indicates the diode s cathode -DL +DL ELC BIP RD GND OP Reader RD- Red Blue White Black Antenna VCS-60R 8/8
MOTORIZED ROLLER SHADES PROGRAMMING GUIDE OTTO 30 OTTO DC2
MOTORIZED ROLLER SHADES PROGRAMMING GUIDE OTTO 30 OTTO DC2 REMOTE CONTROL BASICS Wall Mount Holder Remove cover from base by prying with flat head screwdriver. Use supplied fasteners and anchors to attach
More informationMOTORIZED ROLLER SHADES PROGRAMMING GUIDE OTTO RECHARGE OTTO RECHARGE PLUS OTTO RECHARGE MAX
MOTORIZED ROLLER SHADES PROGRAMMING GUIDE OTTO RECHARGE OTTO RECHARGE PLUS OTTO RECHARGE MAX REMOTE CONTROL BASICS Wall Mount Holder Remove cover from base by prying with flat head screwdriver. Use supplied
More informationDeluxe High Amp Switch Kit - 12 Volt Wiring Instructions
1404 N. Marshall Ave. El Cajon C 92020 WLH 09/01/16 514-0139 OUT IN 16 ga. Black wire 16 ga. Green wire Yellow Black Blue 50 AMP BREAKER MOTOR 16 ga. White wire ROCKER SWITCH (IN CAB) BATTERY 607-0139
More informationSWING GATE OPENERS 24V DC GEAR MOTOR
SWING GATE OPENERS 24V DC GEAR MOTOR FOR RESIDENTIAL USER MANUAL Flashing Light Push Button Control box Gate 2 Gate 1 Index Warnings 2 5. Technical Characteristics 21 1. Product Description and Applications
More informationSmart Switch Basic Kit - 24 volt ( ) Wiring Instructions
Smart Switch Basic Kit - 4 volt (54-08) Wiring Instructions NB 8/0/ 6 ga. wire 6 ga. wire 6 ga. wire OUT IN 6 ga. wire Yellow Black Blue 50 AMP BREAKER MOTOR 6 ga. wire 6 ga. wire 6 ga. wire ROCKER SWITCH
More informationACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS
II 1400-10 ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS Features: Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short Circuit Protection Standby Battery
More information2904 Power Supply Installation Instructions I-EA00041
FEATURES Controls an opening with electrified locking device and automatic door operator Separate inputs for activation switch on entry and exit sides of opening Separate 24 VDC outputs for fail safe and
More informationARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI
II 1400-6 ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI ACSI 1426-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1092, REV. C INSTALLATION For C-UL Listed applications,
More informationSwitch Machines Installation & Wiring
Switch Machines Installation & Wiring Conventional Twin Coil Switch Machines Electrically: In use since developed by Walthers in early 1930 s Long time standard for remote operation Currently: Rix, Atlas,
More informationINSTALLATION MANUAL. Model: PLUS For Technical Assistance, please call (800) , or visit
R Vehicle Security INSTALLATION MANUAL Model: PLUS-4700 This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference;
More informationREC-11+ REMOTE RECEIVER UNIT
Resetting The Programmable Features The installer may quickly and easily return all 17 programmable features back to the factory settings. Changing individual features were explained in detail in the previous
More informationINSTALLATION MANUAL. Remote Mobile Security System. Model: PL30
Remote Mobile Security System INSTALLATION MANUAL Model: PL30 Copyright 1998 Magnadyne Corporation For Technical Assistance (800) 638-3600 For Fax on Demand Technical Assistance (800) 994-9977 (Must be
More informationSSV2BR INSTRUCTIONS INSTALLATION INSTRUCTIONS
SSV2BR INSTRUCTIONS INSTALLATION INSTRUCTIONS CONTROLLER MOUNTING: Find a suitable location to mount the control box. Ideally, as with all pool equipment it should be installed out of direct weather and
More informationCM5100 COMPUTER MANAGED CYLINDRICAL LOCK HARD-WIRED (FSE/FSA) INSTALLATION MANUAL
The 5100 series lock is a stand-alone, microprocessor controlled, electromechanical locking system. The 5100 employs a heavy-duty mechanical design which is easy to install and highly reliable. The FSE
More informationRailing System BH-02
Railing System BH-02 ASSEMBLY AND OPERATION MANUAL Railing System BH-02 Assembly & Operation Manual CONTENTS 1 APPLICATION...3 2 OPERATION CONDITIONS...3 3 TECHNICAL SPECIFICATIONS...4 4 DELIVERY SET...4
More informationINSTALLATION MANUAL. Model: PLUS Vehicle Security
R Vehicle Security INSTALLATION MANUAL Model: PLUS-5000 Copyright 1999 Magnadyne Corporation For Technical Assistance (800) 638-3600 For Fax on Demand Technical Assistance (800) 994-9977 (Must be a Registered
More informationExplanation 1 Input External Switch 2 Input Hipot Safety Switch
on the 1100H+ The 1100H+ has capability, which allows you to set up the tester to control external devices with tester functions. You can also use an input on the tester to start a test. For example, the
More informationDycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD
Dycon D1532SM EN50131/PD6662 Grade 3, 12V 2A Power Supply Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Tel: +44 (0)1443 471 900 Unit A Cwm Cynon Business Park Mountain
More informationElectric strikes. An electric strike is an electromechanical device installed on the door frame allowing an electrical opening. Installation modes
Electric strikes An electric strike is an electromechanical device installed on the door frame allowing an electrical opening. Installation modes Flush mounted electric Rim electric strike installation
More informationIRREVERSIBLE OPERATOR FOR SWING GATES AND DOORS
VH IRREVERSIBLE OPERATOR FOR SWING GATES AND DOORS WARNING!! Before installing, thoroughly read this manual that is an integral part of the pack Our products if installed by qualified personnel capable
More informationSWING GATE OPENERS 24V DC GEAR MOTOR
SWING GATE OPENERS 24V DC GEAR MOTOR FOR RESIDENTIAL USER MANUAL Flashing Light Push Button Control box Gate 2 Gate 1 Index 1. Warnings 2 4. Technical Characteristics 16 2. Product Description 2.1 Applications
More informationTECHNICAL DATASHEET#TD1516AX 3 AMP SOLENOID DRIVER
TECHNICAL DATASHEET#TD1516AX 3 AMP SOLENOID DRIVER User Selectable V or ma Input Bipolar or Unipolar 0-3A Output Adjustable Dither and PWM Frequency PCB Board or Packaged in Metal Housing P/N: RSD-x-3A-y
More informationFM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017
FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017 Maxi-Tronic, Inc. 417 Wards Corner Road Loveland, OH 45140 513.398.2500 800.659.8250 FAX: 513.398.2536 info@maxitronic.com
More informationField Commander Lite Wiring Manual
2014-17 Field Commander Lite Wiring Manual (New Large Style Board board label Comm6 FC V4.1 or V4.2 only 1 relay ) Section 1 Pages 2-6 Irrigation Pivot wiring. Section 2 Page 6 Simple on/off monitor only
More informationModel PRO 9246CH Installation Manual
Model PRO 9246CH Installation Manual PRE-INSTALLATION NOTES: RF Programmable Features : Feature Selection 1 Flash 2 Flash 3 Flash Default 1st Do L/UL 1 Sec. 3.5 Sec. 1 Sec L, Dbl. U/L 1 Sec. 2nd Accy Lock
More information10 MM MINIATURE VALVES
1 MM MINIATURE VALVES LATCHING 1 MM MINIATURE VALVES Clippard s Latching series features a careful balance of forces through the precise placement of a permanent magnet in the valve core produces a bi-stable
More informationModel APS-101N Installation Manual
Programmable Features Model APS-101N Installation Manual Select By Operating Transmitter Press Lock Button Press Unlock Button Siren Indications 1 Chirp 2 Chirps Factory Default 1) Arming Method Passive
More informationASSA ABLOY Series Power Operator Installation and Instruction ASSA Manual ABLOY ASSA ABLOY
00 Series Power Operator Installation and Instruction ASSA Manual ABLOY Item No. Description Motor (00M) Cover (00COV) Control Inverter (00IN) Power Supply VDC (00PS) Track Assembly (0-) / Replacement
More informationVOC Duct and Rough Service Sensor
Overview and Identification Humans respirate Volatile Organic Compounds (VOCs) as well as CO 2. The BAPI sensor measures these VOCs and indicates space occupancy just as well as a CO 2 sensor. The advantage
More informationASSA ABLOY Series Power Operator Installation and Instruction ASSA Manual ABLOY ASSA ABLOY
0 Series Power Operator Installation and Instruction ASSA Manual ABLOY Item No. Description Motor (00M) Cover (00COV) Control Inverter (00IN) Power Supply VDC (00PS) / Replacement Motor Key (00KEY) Rod
More informationDESIGNED FOR RESIDENTIAL APPLICATION KIT PL600/PL1000 SLIDING GATE OPENERS
SLIDING GATE OPENER DESIGNED FOR RESIDENTIAL APPLICATION KIT PL600/PL1000 SLIDING GATE OPENERS The strongest solution for sliding gates PL600/PL1000 electro-mechanical sliding gate openers are designed
More informationDycon D2430 EN54-4 Fire Alarm Power Supply Series
Dycon D2430 EN54-4 Fire Alarm Power Supply Series Technical Description Installation and Operating Manual Construction Product Regulation 0359-CPR-00434 Page 1 of 14 Contents 1. General... 3 1.1 Product
More informationREMOTE MOUNT SOLENOID DRIVER (0-5 VDC/0-20 ma/10k Potentiometer Input)
REMOTE MOUNT SOLENOID DRIVER (0-5 VDC/0-20 ma/10k Potentiometer Input) Part No.: PCB Board - RSD-PCB-5V-x DIN Rail Mount RSD-DR-5V-x Packaged Driver (board installed in metal box) Available with no cable
More informationSivoia QS Wireless Drapery Lite System
Sivoia QS Wireless Drapery Lite System English Installation Guide Please Read Before Installing Important Notes - Please Read Before Installing A. Lutron systems are intended for use with only Lutron hardware
More informationINSTALLATION MANUAL. Remote Mobile Security System. Model: PL50
Remote Mobile Security System INSTALLATION MANUAL Model: PL50 Copyright 2000 Magnadyne Corporation For Technical Assistance (800) 638-3600 For Fax on Demand Technical Assistance (800) 994-9977 (Must be
More informationACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS
II 1400-8 Features: ACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS Filtered/Regulated 24 Volts DC Up to Full 2 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short Circuit
More information5700 Series Power Operator Hinge (Pull) Side Mount Installation and Instruction ASSA Manual ABLOY
5700 Series Power Operator Hinge (Pull) Side Mount Installation and Instruction ASSA Manual ABLOY 80-957-000-00 (06-5) Patents 5,88,97; 7,6,096; 7,8, 6 5 0 8 7 9 Item No. Description Back plate Door Closer
More informationPULSE-8: MASTER PULSATION CONTROL
PULSE-8: CONTROL Version - February 2006 For Software Version V1.02 Part Number - 39-0020 CONTROL: INDEX GOOD PRACTICE: Mains Supply. A separate mains supply and earth running directly from the consumer
More informationPivot Point Lite Wiring Manual
2009-10 Pivot Point Lite Wiring Manual (small square single circuit board design) Section 1 Pages 2-3 Pivot wiring to monitor and/or stop the irrigation system. Section 2 Page 4 Section 3 Page 4 Simple
More informationModel K20 installation guide. ProSecurity
Model K20 installation guide ProSecurity NOTE: This product is intended for installation by a professional installer only! Any attempt to install this product by any person other than a trained professional
More informationRequirements LEO Power Operator Installation Instructions Patents: 5,881,497; 7,316,096; 7,484,333 CAUTION CAUTION WARNING
CAUTION 80-957-00-00 (08-0) Series 570 Openings 85 to 0 or to 70 Double Lever Arm Application for Frame Reveals (76) to 7 (78mm)* Stop (Push) Side of Installation 5700 LEO Operator Installation Instructions
More informationRequirements LEO Power Operator Installation Instructions Patents: 5,881,497; 7,316,096; 7,484,333 CAUTION CAUTION WARNING
CAUTION 80-957-00-00 (08-0) Series 570 Door Openings 85 to 0 or to 80 Adjustable Arm and Slide Track Application Maximum Hinge Side Frame Reveal to /8 (mm) Hinge (Pull) Side of Door Installation 5700 LEO
More informationALVARADO (1029 mm) 25 (635 mm) 36.5 (927.1 mm)
ALVARADO EDCX Bullnose Waist High Turnstile Technical Specifications Dimensions Unit Height: Unit Width: Unit Depth: 40.5 (1029 mm) 25 (635 mm) 36.5 (927.1 mm) Materials Cabinet: Formed and welded 14 gauge
More informationSEN and SEN Outdoor Air Temperature Sensors
FANs 216, 1628.3 Product/Technical Bulletin SEN-500-2, SEN-500-3 Issue Date 0996 SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors The SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors offer
More informationFUEL MANAGEMENT SYSTEM SentryGOLD INSTALLATION MANUAL
FUEL MANAGEMENT SYSTEM SentryGOLD INSTALLATION MANUAL TRAK SentryGOLD Installation Manual rev.03 4-18-2014 IMPORTANT The SentryGOLD and associated equipment will be installed in close proximity to combustible
More informationIDC-136II-KIT 136kHz DC RX Assembly Guide
IDC-136II-KIT 136kHz DC RX Assembly Guide ICAS Enterprises May 2 nd,2016 The IDC-136II-KIT is a 136kHz direct conversion receiver. Most of the SDR software can be used with this receiver. It is quite easy
More informationASSEMBLING THE 15 INCH FLUSH MOUNT TOUCH SCREEN DIMENSIONS OF THE 15 INCH FLUSH MOUNT TOUCH SCREEN
DIMENSIONS OF THE 15 INCH FLUSH MOUNT TOUCH SCREEN 18 (457 mm) 12 39/64 (320 mm) 3 1/2 (89 mm) 1 13/32 (36 mm) 19 (483 mm) 3 5/8 (92 mm) 7/64 3 mm) 1 13/32 (36 mm) 23 53/64 (605 mm) 20 3/4 (527 mm) 12
More informationTravelPilot RNS 149 US
Radio/Navigation TravelPilot RNS 149 US Installation instructions Safety information Faulty installation or servicing of this equipment may result in malfunctions in the vehicle s electronic systems. To
More informationOperating Instructions Type MPT 53
Operating Instructions www.turnstiles.us Type MPT 53 Contents 1. Delivery... 2 2. Safety...3-4 3 Description and operation... 5 4. Technical Data 6 5. oundation...6-9 6. Assembly and installation...10-13
More informationSentinel Field Satellite Controller
WARNING HIGH VOLTAGE 115V M AP Sentinel Field Satellite Controller Installation Instructions Important: For your protection and the safety of the product user, please comply with all Caution and Warning
More informationIV-11 VFD tube clock Assembly instructions v1.2.2
IV-11 VFD tube clock Assembly instructions v1.2.2 Designer: Website: E-mail: Yan Zeyuan. China http://www.nixieclock.org yanzeyuan@qq.com 2017-01-26 NCH Attention Attention: Warning: Warning: Warning:
More informationIdle Timer Controller - A-ITC620-A Chevrolet Express/GMC Savana
Introduction An ISO 9001:2015 Registered Company Idle Timer Controller - A-ITC620-A1 2009-2019 Chevrolet Express/GMC Savana Contact InterMotive for additional vehicle applications The A-ITC620-A1 is an
More informatione-ask electronic Access Security Keyless-entry
e-ask electronic Access Security Keyless-entry Multiplex System Multiplex System Installation & Instructions (UM15 ~ 22272-03) Table of Contents Introduction... 1 Standard e-fob Operation and Features...
More informationV200 USER MANUAL SWING GATE OPENER. 100kg 1.5m. 100kg 1.5m
V200 USER MANUAL SWING GATE OPENER 100kg 1.m 100kg 1.m Content Important Safety Advice... Content of the Kit... Connection Diagram... Installation Guide... Actuator... Control box... AC cable wiring...
More informationRA2 Installation Manual Rev. B
Important Information Required Installation Tools Voltmeter Wire Strippers Electric Drill & Bits Phillips Screwdriver Convoluted Tubing * Solder Gun * Wire Crimpers Shrink Tube or Electrical Tape * Optional
More information(1032 mm) 30.5 (775 mm) 44 ( mm)
ALVARADO EDCX-EK Waist High Turnstile Technical Specifications Dimensions Unit Height: Unit Width: Unit Depth: 40.625 (1032 mm) 30.5 (775 mm) 44 (1117.6 mm) Materials Cabinet: Formed and welded 14 gauge
More informationPW320/PW330 USER MANUAL SWING GATE OPENERS 24V DC GEAR MOTOR FOR RESIDENTIAL. Flashing Light. Push Button. Control box. Gate 2.
PW320/PW330 USER MANUAL SWING GATE OPENERS 24V DC GEAR MOTOR FOR RESIDENTIAL Flashing Light Push Button Control box Gate 2 Gate 1 Declaration of Conformity Applicant: Powertech Electronics Inc. Manufacturer:
More informationD4BL. Protective Doors Are Locked Until Machines Completely Stop Operating. Guard Lock Safety-door Switch. Model Number Structure.
Guard Lock Safety-door Switch Protective Doors Are Locked Until Machines Completely Stop Operating A mechanical lock is applied automatically when the Operation Key is inserted. A high level of safety
More informationPW150/PW200 USER MANUAL SWING GATE OPENERS 24V DC GEAR MOTOR
PW150/PW200 USER MANUAL SWING GATE OPENERS 24V DC GEAR MOTOR FOR RESIDENTIAL Flashing Light Push Button Control box Declaration of Conformity Applicant: Powertech Electronics Inc. Manufacturer: Timotion
More informationElectro-Mechanical Swing Operator. Table of Contents
*640072* 640072 Electro-Mechanical Swing Operator Models 8230 & 8240 Installation Instructions Table of Contents General...1 Replacement Parts & System Components...1 1 Pre-Installation Site & Product
More informationSpeed Gate ST-01. Double-Sided Section STD-01 ASSEMBLY AND OPERATION MANUAL
Speed Gate ST-01 Double-Sided Section STD-01 ASSEMBLY AND OPERATION MANUAL Speed Gate ST-01 Double-Sided Section STD-01 Assembly and Operation Manual CONTENTS 1 APPLICATION...4 2 OPERATION CONDITIONS...4
More informationModel APS-25CH Installation Manual
Model APS-25CH Installation Manual Note : When both Passive Arming and Voltage Sensing are selected, you must hardwire the driver s do pin switch in der to begin the passive arming sequence. RF Programmable
More information91 (2311 mm) (1581mm) (1375 mm)
ALVARADO MSTX Maximum Security Turnstile Technical Specifications Dimensions Unit Height: Unit Width: Unit Depth: 91 (2311 mm) 62.25 (1581mm) 54.125 (1375 mm) Materials Yoke: (Curved Section) Yoke Guard
More informationAuto Gate System. General Description. Features EL-888A. elock EL-888A is an electro-mechanical complete system for. EL-888A (Auto gate)
General Description (Auto gate) elock is an electro-mechanical complete system for automatic swing gate. It is composed primarily of an electronic panel unit that control actuator motor to open or close
More informationTABLE of contents. Metal Oxide Varistor (MOV) Varistors-5D Series Varistors-7D Series Varistors-10D Series... 5
TABLE of contents Subject Page Metal Oxide Varistor (MOV)..................................................... 1 Varistors-5D Series............................................................ 3 Varistors-7D
More informationHA PRO INSTALLERʼS MANUAL. HA-008 v3. User s/installer s Manual
HA-008 v3 HA - 280 PRO User s/installer s Manual INSTALLERʼS MANUAL Manufacturer: COMMERCIAL ELECTRONICS 264 HAYDONS ROAD, WIMBLEDON, LONDON SW19 8TT. UK TEL: +44 020 8404 7105 FAX: +44 020 8404 7104 http://www.hawkcaralarm.com
More informationMINOTOUR SERVICE MANUAL
MINOTOUR SERVICE MANUAL The following areas are covered in this manual: Interlock Feature Vandalock Feature AC System Heaters Passenger Advisory System MINOTOUR SERVICE MANUAL ELECTRICAL TROUBLESHOOTING
More informationIdle Timer Controller - A-ITC520-A Ford E Series Ford F250 - F Ford F250 - F550 (*B-ITC520-A) F650/F750
An ISO 9001:2008 Registered Company Idle Timer Controller - A-ITC520-A 2009-2018 Ford E Series 2008-2016 Ford F250 - F550 2017-2018 Ford F250 - F550 (*B-ITC520-A) 2016-2018 F650/F750 *Uses the Ford 24-Pin
More informationMOTORIZED ROLLER SHADES OTTO WIRED 6 PROGRAMMING GUIDE
MOTORIZED ROLLER SHADES OTTO WIRED 6 PROGRAMMING GUIDE REMOTE CONTROL BASICS Wall Mount Holder Remove cover from base by prying with flat head screwdriver. Use supplied fasteners and anchors to attach
More informationRU BMS Power Supply and Battery Management System Owners Guide
RU2-4012- BMS Power Supply and Battery Management System Owners Guide (These instructions are intended for use by a technician familiar with electronic products) RU2-4012- BMS is a continuous duty power
More informationQRPGuys Digital RF Probe
QRPGuys Digital RF Probe First, familiarize yourself with the parts and check for all the components. If a part is missing, please contact us and we will send one. This kit contains seventeen 1206 size
More informationD4DL. Guard Lock Safety-door Switch. Model Number Structure
Guard Lock Safety-door Switch Two new types added to series: Mechanical-lock models that lock automatically when the Operation Key is inserted, and solenoid-lock models that lock when voltage is applied
More informationMLD-44S/g V AC/50-60Hz. MLD-28S/g. MLD-34S/g
MAINTAINED/NON-MAINTAINED (OPTIONAL) ILLUMINATION SIGNS WITH GREEN LEDs TECHNICAL CHARACTERISTICS Mains voltage Maximum power consumption Batteries (Ni-Cd) Battery protection Recharging time Minimum emergency
More informationBETA Switching Switches and Light Indicators
Siemens AG 2008 BETA Switching /2 Product overview /3 5TE8 control switches / 5TE4 pushbuttons /2 5TE5 light indicators /5 5TE8 ON/OFF switches /22 5TE9 busbars /24 5TE switch disconnectors Siemens ET
More informationModel APS-25N Installation Manual
Model APS-25N Installation Manual Note : When both Passive Arming and Voltage Sensing are selected, you must hardwire the driver s do pin switch in der to begin the passive arming sequence. RF Programmable
More informationChapter 2. Battery Charger and Base Assembly
Chapter 2 Battery Charger and Base Assembly 11 CHAPTER 2. BATTERY CHARGER AND BASE ASSEMBLY 2.1 Section Overview This Lab teaches students how to assemble a Tekbot, in the following steps: Describe the
More informationchannel damage the internal components and the weight may break the internal wiring or flexible strip.
YOU MAY NEED End cap Power adaptor Connector pin Splicing pin Connector Silicone glue Pliers Power converter Converter + surge protector Heat shrink Aluminium channel Heat gun NT cutter IMPORTANT NOTES
More informationUSERS GUIDE LO-21U LOCKOUT RELAY
USERS GUIDE LO-21U LOCKOUT RELAY PRODUCT DESCRIPTION The LO-21U (PN: 10LO21U) is a micro-processed lock out module designed to operate on swing door applications with BEA s Bodyguard or DK-12 overhead
More information24P Installation and Operations Manual
24P Installation and Operations Manual P/N 24P01A1A P/N 24P02A1A ler with integral potentiometer ler with cable for remote potentiometer 24P00M1H 5/15/2015 This instruction manual covers the 24P01A1A Proportional
More informationGLM SERIES CONTROL Users Manual Rev:
GLM SERIES CONTROL Users Manual Rev: 808062 Connecting Power Page 2 Motor Terminal Wiring Diagrams Page 3 Getting Started / Setup Page 4 1. Obstruction Detection Devices Page 4 2. Checking Power and Direction
More informationINSTALLATION INSTRUCTIONS AND OPERATION MANUAL
INSTALLATION INSTRUCTIONS AND OPERATION MANUAL UL325-2010 Compliant Commercial and Industrial Door Operator Logic Control Continuous Duty IMPORTANT INSTALLATION INSTRUCTIONS WARNING To reduce the risk
More informationAquiTron. AT-PIR-SOV Water Shut-Off System INSTALLATION INSTRUCTIONS
AquiTron Water Shut-Off System INSTALLATION INSTRUCTIONS System Please read these instructions carefully and keep them in a safe place (preferably close to the module) for future reference. These instructions
More informationUNDERGROUND OPERATOR FOR SWINGING GATES. WARNING!! Before installing, thoroughly read this manual that is an integral part of the pack
UNDERGROUND OPERATOR FOR SWINGING GATES COMPAS 2 WARNING!! Before installing, thoroughly read this manual that is an integral part of the pack Our products if installed by qualified personnel capable to
More information5700 Series Power Operator Stop (Push) Side Mount Installation and Instruction
5700 Series Power Operator Stop (Push) Side Mount ASSAManual ABLOY Installation and Instruction 80-957-0005-00 (06-5) Patents 5,88,97; 7,6,096; 7,8, 5 6 0 8 7 9 -/8 () Item No. Description Back plate Door
More informationINSTRUCTION MANUAL H WELDER INTERLOCK
INSTRUCTION MANUAL 700200H WELDER INTERLOCK MICROPROCESSOR BASED Welder Interlock Control Wiring Diagram 420721 NEMA 1 Cabinet ENTRON Controls, LLC. 1402 S. Batesville Road Greer, South Carolina 29650
More informationMST. Full Height Turnstiles. alvaradomfg.com
Full Height Turnstiles alvaradomfg.com The is the most trusted, secure and reliable full height turnstile available. It is installed in thousands of locations around the world and offers key product features
More informationAutoranging Multimeter
Owner's Manual Autoranging Multimeter Model No. 82334 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation Maintenance
More informationInstruction Manual for the. E-SL 450 Series
Instruction Manual for the E-SL 450 Series Estate Slide Summary of Functions The Estate Slide is only to be used for vehicular Slide gates in a Class I setting. Class I: A vehicular gate opener (or system)
More informationVC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL
1. INTRODUCTION VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL This MCU controlled Step Down DC-DC Converter has a digitally adjustable output in 0.2V increments. This
More informationALEX-TRONIX SMART CLOCK TM. BATTERY POWERED TEMPERATURE BUDGETING CONTROLLER MANUAL Patent Pending A DIVISION OF GNA INDUSTRIES, INC.
ALEX-TRONIX A DIVISION OF GNA INDUSTRIES, INC. SMART CLOCK TM BATTERY POWERED TEMPERATURE BUDGETING CONTROLLER MANUAL Patent Pending M A N U A L INTRODUCTION The Smart Clock is a non-solar battery powered
More informationE-SL 450BD Series INSTRUCTION MANUAL WARNING USER DRIVEN MANUAL*
USER DRIVEN MANUAL* Any feedback, changes, or advice we are glad to hear it. Please contact us at support@estateswing.com WARNING Read all instructions before beginning installation or use of this gate
More information/ S. Warhawk Road, Conifer, CO /
www.turnstiles.us www.turnstiles.us / www.entrapass.com 8641 S. Warhawk Road, Conifer, CO 80421 / 303-670-1099 TABLE OF CONTENTS 1 DIRECTIONS... 3 2 INTRODUCTION... 3 3 CATRAX CLIP CHARACTERISTICS... 4
More informationLjunggren Audio Roll Your Own Penta
Ljunggren Audio Roll Your Own Penta Version: Penta 1.0 Bills Of Material Bold = PCB1, The rest = PCB2 Type Parts Des cription Pow er header Qty Value 1 2x5pin POWER Euro pow er connector Jack 1 3.5mm J1,
More informationSIGNETMARINE. Livewell Bait Pump Alarm. No Dead Bait.
B A I T WAT C H SIGNETMARINE Livewell Bait Pump Alarm No Dead Bait. The SIGNETMARINE BaitWatch System alerts you to a livewell pump problem before your fishing trip turns into one. The loud alarm and dual-color
More informationQuiz Buzzer. Build Instructions. Issue 1.2
Build Instructions Issue 1.2 Build Instructions Before you put any components in the board or pick up the soldering iron, just take a look at the Printed Circuit Board (PCB). The components go in the side
More informationContents. DX Ignition Page 2
Contents 1.0 Intent 2.0 Specifications 3.0 Installation 4.0 Operation Precautions 5.0 Repair 6.0 Parts List 7.0 Glossary of Terms 8.0 Contact Information DX Ignition Page 2 1.0 Intent The purpose of this
More information94 Series - Socket overview for 55 series relays
94 Series - Socket overview for 55 series relays 94.04 See page 7 Module Socket Relay Description Mounting 99.02 94.02 55.32 Screw terminal (Box clamp) socket Panel or 35 mm rail - Coil indication and
More informationAPPENDIX B SPECIFICATION FOR GENERATOR OVERHAUL EMD MODEL AR10 D18... B-1
Table of Contents APPENDIX B SPECIFICATION FOR GENERATOR OVERHAUL EMD MODEL AR10 D18... B-1 B.01 SCOPE... B-1 B.02 GENERAL... B-1 B.03 ELECTRICAL QUALIFICATION... B-1 B.04 EQUIPMENT RECONDITIONING... B-2
More informationACSI MODEL POWER SUPPLY INSTALLATION INSTRUCTIONS
II 1400-9 ACSI MODEL 1400-6100 POWER SUPPLY INSTALLATION INSTRUCTIONS Features: Used exclusively with the ACSI Series 6100 Communicating Bath Door (Common Bath) System Two separate and identical rows of
More informationEDC-E. Waist HIGH Turnstiles. alvaradomfg.com
Waist HIGH Turnstiles alvaradomfg.com Descriptive SPECIFICATIONS The is an extended length cabinet turnstile with extended length turnstile arms. It is a rugged, multi-purpose turnstile used to provide
More information