N-1001 Economizer Logic Network

Size: px
Start display at page:

Download "N-1001 Economizer Logic Network"

Transcription

1 , Rev. A N-1001 Economizer Logic Network Product Bulletin N-1001 Issue Date 0316 Features Choice of O.A. Dry Bulb Economizer, Differential Temperature Economizer, or Enthalpy Economizer cycles Compatible with all pneumatic controllers and transmitters Hypodermic needle test points on all inputs and outputs English Language connection identification The N-1001 Economizer Logic Network is a versatile multipurpose pneumatic device which provides a sequence of logic functions to all types of mixed air handling units. Based on cooling demand, fan status, and seasonal input conditions, the N-1001 provides fan interlock and minimum position control features, as well as economizer control and other auxiliary switching strategies. Operation The N-1001 Economizer Logic Network is used in conjunction with a pneumatic controller to provide mixed air economizer and cooling control logic to an air handling unit. The N-1001 receives a controller signal and either repeats the signal or modifies it to provide optimal control of mixed air dampers and cooling apparatus. The choice of either standard dry bulb, differential temperature, or enthalpy economizer is used to determine the Summer or Winter mode of O.A. damper operation. The fan status determines whether the dampers and cooling apparatus are to be operational or closed. An integral adjustable minimum percent O.A. setting provides ventilation. Mounting The N-1001 should be mounted in an upright position using the integral bracket and two #8 sheet metal screws (field furnished). The unit may be duct or panel mounted; refer to Fig. 13 for space requirements and additional mounting details. All pneumatic tubing connections should be made with 1/4 in O.D. polytubing. Application and Drawing Identification N-1001 Control Strategies Economizer Cycles The N-1001 offers a choice of either O.A. Dry Bulb, Differential Temperature, or Enthalpy Economizer cycles. Each of these methods uses different input measurements to determine which air stream (outside or return air) will impose the lightest load on the system cooling apparatus. Regardless of the economizer method selected, the Summer mode of operation will cause the DPR output to go to minimum Fig. 1: N-1001 Economizer Logic Network position pressure, and the AUX output will be at 20 PSIG (140 kpa) in the Winter mode, the DPR output signal will be equal to the IN signal or the minimum position setting, whichever is greater. The AUX output will be less than 1 PSIG (7 kpa) in the Winter mode. When the O.A. Dry Bulb Economizer cycle is selected by positioning the economizer jumper from COM to DB (see Fig. 2), the N-1001 compares the O.A. temperature signal to the switchover point established on the switchover adjustment. When the O.A. temperature signal to the switchover point established on the switchover adjustment. When the O.A. temperature is above the switchover point, the N-1001 will operate the system in the Summer mode. When the O.A. temperature is at or below the switchover point, the N-1001 will operate the system in the Winter mode. When the Differential Temperature Economizer cycle is selected by positioning the economizer jumper from COM to DIFF (see Fig. 3), the N-1001 compares the temperatures of the 1989 Johnson Controls, Inc. 1 Part No , Rev. A Code No. LIT

2 O.A. and R.A. transmitters (both transmitters must have identical ranges). Energy studies have concluded that this type of economizer method yields energy savings that are nearly as attractive as the Enthalpy Economizer method. When the O.A. temperature is equal to or greater than the R.A. temperature, the N-1001 will operate the system in the Summer mode. When the O.A. temperature is less than the R.A. temperature, the system will be controlled in the Winter mode. In this application, the switchover adjustment may be used to establish a differential between O.A. and R.A. This feature effectively adds one or more Fahrenheit degrees to the actual O.A. temperature. This may be done to account for a higher latent heat content in the O.A. due to levels of relative humidity. For example: Differential Setting = 5F O.A. Temperature = 68 F R.A. Temperature = 72 F Resultant Mode = Summer Mode Specifications For recommendations on the exact differential setting for a specific type of system in a specific geographical area, please consult the nearest Johnson Controls branch office. When the Enthalpy Economizer cycle is selected by positioning the economizer jumper from COM to DB (see Fig. 2), the N-1001 works in conjunction with an N-9000 Enthalpy Logic Center to execute the economizer cycle. Refer to Product Data N-9000 for more details. Fan Interlock The N-1001 interlocks the DPR and CLG output signals with the FAN status input signal. When the fan is ON, the FAN signal is at 20 PSIG (140 kpa) and the DPR and CLG signals are passed along to their respective controlled devices. When the fan is OFF, the FAN signal is at 1 PSIG (7 kpa) or less, and the DPR and CLG signals are at 0 PSIG (0 kpa), allowing their respective controlled devices to fail to their normal (closed) positions. The FAN connection provides a restricted source of supply air; therefore, no external source of supply air is required if a low volume fan status sensor is used (see Fig. 4). Other Control Strategies The TLL connection may be used for mixed air low limit control of the O.A. dampers or morning warmup interlock of the O.A. dampers, or both. In any 2 N-1001 Product Bulletin

3 N-1001 Product Bulletin 3

4 case, the TLL connection provides a restricted source of supply air to the low volume device that may be connected to it. If neither mixed air low limit or morning warmup features are required, the TLL connection MUST BE CAPPED. When TLL is used for Mixed Air Low Limit control of O.A. dampers (see Fig. 5), a proportional mixed air low volume thermostat, such as a T-3610, should be connected to the TLL connection. When the mixed air temperature drops below the low limit set point, the N-1001 will override the IN signal and may reduce the minimum position pressure to allow the O.A. dampers to modulate completely closed. Note: This mixed air low limit feature DOES NOT achieve coil freeze-up protection. When TLL is used for Morning Warmup control purposes (see Fig. 6), a direct acting two position R.A. sensor should be connected to the TLL connection. In this application, the N-1001 will keep the O.A. dampers completely closed until the morning warmup temperature is reached in the return air. At this time, minimum O.A. damper position will be restored by the N Manual override of the economizer cycle can be achieved by adding a three position selector switch, such as an S-2300, to the economizer selection jumper (see Fig. 7). Application/Operation Tips 1. There is an inherent delay of about five seconds in switchover from Winter mode to Summer mode. 2. On fan shutdown, the dampers and cooling apparatus return to their normal position; however, the AUX switchline remains unchanged. 4 N-1001 Product Bulletin 3. Control of the cooling apparatus may be altered externally to provide sequencing and/or cooling lockout. 4. All inputs, with the exception of the supply input, are deadended. This means that all input signals may be high volume (relay) or low volume (non-relay) type signals. 5. The N-1001 provides a.007 in. restricted source of supply pressure to the FAN and TLL input devices. No external source of restricted supply air is necessary to those input devices. 6. All outputs from the N-1001 are low volume. The volume of these outputs may be increased if necessary using a pilot positioner or an R-2080 Booster Relay.

5 7. The N-1001 may be used as a unit replacement for the N-1000 Logic Network. Note: The N-1001 does not provide a restricted source of supply air to the O.A. transmitter or thermostat; therefore, when replacing an N-1000 with a N-1001, an external source of supply air must be added to the O.A. transmitter or thermostat. Fig. 7 N-1001 Product Bulletin 5

6 EXAMPLE #1 Single Path Mixed Air with DX Cooling Room Control Economizer Switchover By Two-Position Thermostat Features Single Zone control Proportional control for operation of dampers and heating coil Two stages of DX cooling Inoperative dampers and cooling when fan is OFF 57 F low limit mixed air protection Return of O.A. dampers to minimum value at predetermined O.A. economizer dry bulb temperature Description of Operation The typical application illustrated in Fig. 8 shows the proportional output signal of TC-1 entering the IN connection of the N-1001 and being repeated to the DPR and CLG output, causing proportional operation of the O.A., R.A., and EXH.A. dampers and two-position operation of the cooling apparatus respectively. This is in sequence with the N.O. heating coil valve which is externally connected directly to TC-1. The DPR and CLG outputs modulate when the FAN signal is activated, and return to their normal positions when the FAN signal is deactivated. The low limit thermostat TLL-1 overrides the controller IN signal via an internal low signal selector, causing the O.A. dampers to modulate toward their closed position (beyond the minimum position signal if required) as the temperature at the TLL-1 element goes below its set point value. TS-1, which is connected to the O.A. input, has its element located in the outside air and has an adjustable switchover point. With the outside air temperature below the adjustable switchover setting, the O.A., R.A., and EXH.A. dampers modulate with the signal from TC-1 (Winter mode). When the outside air temperature rises above the setting, the O.A. dampers will close to their minimum position as established by the minimum position adjustment (Summer mode). 6 N-1001 Product Bulletin

7 N-1001 Product Bulletin 7

8 EXAMPLE #2 Single Path Mixed Air and Chilled Water Air Handling Unit Room Control - Multiple Zones Economizer Switchover By Ideal Dry Bulb Features Room control of unit via warmest zone Proportional operation of dampers and cooling coil valve in sequence Inoperative dampers and cooling when fan is OFF Low limit mixed air protection Return of O.A. dampers to minimum value when O.A. temperature plus its differential is greater than R.A. temperature. O.A. dampers automatically remain closed during morning warmup cycle Description of Operation The typical application illustrated in Fig. 9 shows the proportional output signal of TC-1, as the highest selected signal through PHLS-1, entering the IN connection of the N The TC-1 signal is repeated to the DPR and CLG outputs, causing proportional operation of the O.A., R.A., and EXH.A. dampers and cooling apparatus. These outputs modulate when the FAN signal is activated (20 PSIG), and return to their normal positions when the FAN signal is deactivated (1 PSIG or less). The low limit thermostat TLL-1 overrides the controller IN signal via an internal low signal selector, causing the O.A. dampers to modulate toward their closed position (beyond the minimum position signal if required) as the temperature at the TLL-1 element goes below its set point value. Transmitters TT-1 and TT-2 are connected to inputs O.A. and R.A. respectively, and the differential temperature of these transmitters is adjusted at the N An adjustable differential can be set at the N When the sum of the O.A. temperature plus its differential is less than the R.A. temperature, the O.A., R.A., and EXH.A. dampers will modulate with the highest signal selected by PHLS-1 (Winter mode). When the sum of the O.A. temperature plus its differential is greater than the R.A. temperature, the O.A. dampers will close to their minimum position as established by the minimum position adjustment (Summer mode). During morning warmup, the temperature at TT-2 is below the setting of PQ-1 and PQ-1 exhausts input signal TLL-1 to the atmosphere, causing the O.A. dampers to remain closed. When morning warmup is accomplished and TT-2 temperature has increased to the setting on PQ-1, the O.A. dampers operate as required by TC-1. 8 N-1001 Product Bulletin

9 N-1001 Product Bulletin 9

10 EXAMPLE #3 Single Path Mixed Air and Chilled Water Air Handling Unit Room Discharge Control Economizer Switchover By Dry Bulb Temperature Transmitter in Outside Air Perimeter Heating and Cooling Units Features Discharge air reset via room discharge control Proportional operation of dampers and cooling coil valve in sequence Inoperative dampers and cooling when fan is OFF Return of O.A. dampers to minimum value at predetermined O.A. dry bulb temperature Manual override of Summer/Winter switchover No switchover to Summer mode if no cooling available Low limit mixed air protection Summer/Winter switchover of heating-cooling thermostats via auxiliary switchline Description of Operation The typical application illustrated in Fig. 10 shows the proportional output signal of TC-1 entering the IN connection of the N The TRC-1 signal is repeated to the DPR and CLG outputs, causing proportional operation of the O.A., R.A., and EXH.A. dampers and cooling apparatus. These outputs modulate when the FAN signal is activated (20 PSIG), and return to their normal positions when the FAN signal is deactivated (1 PSIG or less). The Low limit thermostat TLL-1 overrides the controller IN signal via an internal low signal selector, causing the outside air dampers to modulate toward their closed position (beyond the minimum position signal if required) as the temperature at the TLL-1 element goes below its set point value. The transmitter TT-1 is connected to input O.A. and the dry bulb switchover temperature is adjusted at the N With the outside air temperature below the switchover setting, the O.A., R.A., and EXH.A. dampers modulate with the signal from TC-1 (Winter mode). When the outside air temperature rises above the switchover setting, the O.A. dampers will close to their minimum position as established by the minimum position adjustment (Summer mode). Additional functions of the system: 1. Manual override of the economizer mode is accomplished by the panel mounted switch PSM The TS-1 sensing the chilled water prevents the switchover of the unit to the Summer mode if no chilled water is available. 3. The AUX output (1 PSIG Winter, 20 PSIG Summer) switches the ASV-1 to change the room thermostats from the Winter heating mode to the Summer cooling mode. 10 N-1001 Product Bulletin

11 N-1001 Product Bulletin 11

12 EXAMPLE #4 Single Path Mixed Air and Chilled Water Air Handling Unit Proportional Plus Integral Discharge Air Temperature Control Enthalpy Switchover Features Proportional plus integral operation of dampers in sequence with cooling coil valve Inoperative dampers and cooling when fan is OFF Return of O.A. dampers to minimum value at proper enthalpy via N-9000 Enthalpy switchover of other similar systems Description of Operation The typical application illustrated in Fig. 11 shows the proportional plus integral output signal of TRC- 1 entering the IN connection of the N The TRC-1 signal is repeated to the DPR and CLG outputs, causing proportional plus integral operation of the O.A., R.A., and EXH.A. dampers and cooling apparatus. These outputs modulate when the FAN signal is activated, and return to their normal positions when the FAN signal is deactivated. The N-9000 Enthalpy Logic Center output is connected to the O.A. input and when its output is at 0 PSIG (0 kpa), the O.A., R.A., and EXH.A. dampers modulate with the signal from the TRC-1 (Winter mode). When the output signal of the N-9000 is at maximum, the O.A. dampers will close to their minimum position, as established by the minimum position adjustment (Summer mode). 12 N-1001 Product Bulletin

13 N-1001 Product Bulletin 13

14 Fig. 12: N-1001 Adjustment Points and Hypodermic Needle Test Points Set Point Adjustments (See Fig. 12) Adjusting screws are provided for field adjustment of: (1) the economizer switchover point, which is factory set in the differential economizer switchover mode at approximately 0.1 PSI (0.7 kpa) differential, and (2) the minimum position O.A. damper setting, which is factory set at approximately 9 PSIG (63 kpa). Economizer Switchover Point Adjustment (See Fig. 12) Differential Adjustment (if other than the factory setting) Note: Contact the local Johnson Controls branch office to determine the required differential for any given system. Jumper Position: COM to DIFF. Apply input pressure values from matched O.A. and R.A. temperature transmitters (T-5210s) to their respective connections. (This may be simulated by using a JC 5383 Calibration Kit, ordered separately.) The outside transmitter must be the lowest of the two inputs, separated by the required differential pressure. See the Differential Temperature Economizer example on page 2. Insert a hypodermic needle test probe (JC 5361, ordered separately) with a 0 to 30 PSIG test gage into the test point fitting of the AUX connection. The AUX output will be less than 1 PSIG (7 kpa) when the economizer switchover adjustment screw is set at minimum differential. Rotate the adjustment screw clockwise by small increments (allowing for a five second delay) until the AUX output increases. Reverse the adjusting screw slightly to cause the AUX output to decrease back to zero again. Check the economizer switchover by varying the O.A. input to cause the AUX output to switch from 0 PSIG (0 kpa) to 20 PSIG (140 kpa) and back again at the required differential. O.A. Dry Bulb Adjustment Jumper Position: COM to DB. Disconnect the jumper from the DB side and install a tube from DB side and install a tube from DB to a T-5500 Temperature indicator or a multirange transmission gage. The range chosen must match that of the O.A. transmitter (T-5210) used in the application. With the O.A. input connection (as labeled for dry bulb application) vented to atmosphere, adjust the economizer switchover adjustment screw to cause the desired O.A. input connection (as labeled for dry bulb application) vented to atmosphere, adjust the economizer switchover adjustment screw to cause the desired O.A. switchover temperature to be read on the gage. Disconnect the tube and gage and reconnect the jumper from COM to DB. Insert a hypodermic needle test probe (JC 5361, ordered separately) 14 N-1001 Product Bulletin

15 with a 0 to 30 PSIG test gage into the test point fitting of the AUX connection. Check the economizer switchover by varying the O.A. input to cause the AUX output to switch from 0 PSIG (0 kpa) to 20 PSIG (140 kpa) and back again at the desired temperature. (This may be simulated by using a JC 5383 Calibration Kit, ordered separately.) Reconnect the proportional O.A. transmitter (T-5210) to the proper O.A. input connection. Two-Position Input (A40 or N-9000) Jumper Position: COM to DB. Disconnect the jumper from the DB side and install a tube from DB to a 0 to 30 PSIG gage. With the O.A. input connection (as labeled for dry bulb application) vented to the atmosphere, adjust the economizer switchover adjustment screw to produce 5 PSIG (35 kpa) on the 0 to 30 PSIG gage. Disconnect the tube and gage and reconnect the jumper from COM to DB. Reconnect the two-position device to the proper O.A. input connection. Any temperature switchover adjustment must be made on the two-position device where applicable. Minimum Position O.A. Adjustment To accomplish minimum position O.A. damper adjustment, the following conditions must exist: 1. The FAN input must be at its ON value (20 PSIG). 2. The TLL input must be at its maximum value or be capped. After reducing the controller signal to the IN connection to its lowest value, insert a hypodermic needle test probe (JC 5361, ordered separately) with a 0 to 30 PSIG gage into the test point fitting for the DPR connection. The gage will indicate the minimum position O.A. setting. This setting may be changed from its factory setting of 9 PSIG (63 kpa) by turning the minimum position O.A. adjustment screw to the desired minimum pressure value. Note: An accurate 0 to 30 PSIG gage must be used and time must be allowed for the reading to stabilize. Repair Information Field repairs must not be made. For a replacement N-1001, contact the nearest Johnson Controls branch office. Replacement oil indicating filters are available, order A Dimension Drawing on Next Page -- N-1001 Product Bulletin 15

16 European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact: JOHNSON CONTROLS WESTENDHOF ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI USA JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE CHINA Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI Printed in U.S.A. 16 N-1001 Product Bulletin

C-5230 Pneumatic Signal Limiter

C-5230 Pneumatic Signal Limiter 24-4221- 9, Rev. B Product Bulletin C-5230 Issue Date February 2016 C-5230 Pneumatic Signal Limiter Features Independently Adjustable High/Low Limits Integral Hypodermic Needle Test Points Field Chosen

More information

T PI Receiver-Controller

T PI Receiver-Controller T-5800 Pneumatic Receiver-Controller Pneumatic Control Manual 717.1 Receiver-Controllers Section Product Bulletin T-5800 Issue Date 0386 Features High Volume Output Field Programmable Action and Readjustment

More information

R-317 Air Flow Controller

R-317 Air Flow Controller 24-4660- 1, Rev. B Product Bulletin R-317 Issue Date February 2016 R-317 Air Flow Controller The R-317 Air Flow Controller is a proportional, direct acting, low volume output signal instrument designed

More information

V-9502 Series Pneumatic Valve Actuator Positioners

V-9502 Series Pneumatic Valve Actuator Positioners P O S 14-365- 6, Rev. F Installation Instructions V-9502 Issue Date February 2016 V-9502 Series Pneumatic Valve Actuator Positioners Application V-9502 Series Pneumatic Valve Actuator Positioners are precision

More information

D-3240 Series Pneumatic Piston Actuators

D-3240 Series Pneumatic Piston Actuators D-3240 Series Pneumatic Piston Actuators 24-4659- 9, Rev. B Product Bulletin D-3240 Issue Date 0316 The D-3240 Series Pneumatic Piston Actuators are multipurpose positioning devices designed for operating

More information

V-2410 Three-Way Multipurpose Solenoid Air Valve

V-2410 Three-Way Multipurpose Solenoid Air Valve 24-7040- 7, Rev. D V-2410 Three-Way Multipurpose Solenoid Air Valve Product Bulletin V-2410 Issue Date March 2016 Features Compact Size with Durable, Solid Brass Construction Can Be Mounted in Any Position

More information

A25 Series Warm Air Control with Manual Reset

A25 Series Warm Air Control with Manual Reset FANs 125, 121 Product/Technical Bulletin A25 Issue Date 0316 A25 Series Warm Air Control with Manual Reset The A25 Series Warm Air Control with Manual Reset is designed to shut down fans, burners, dampers,

More information

S-2300 Pneumatic Selector Switch

S-2300 Pneumatic Selector Switch S-2300 Pneumatic Selector Switch Pneumatic Control Manual 717.1 Selector Switches Section Product Bulletin S-2300 Issue Date 0290 The S-2300 Pneumatic Selector Switch is designed for manual switching of

More information

Installation Instructions

Installation Instructions 34-636- 2286, Rev. C (barcode for factory use only) M9000-400 Jackshaft Linkage Kit Installation Instructions M9000-400 Part No. 34-636-2286, Rev. C Issued June 2017 Applications Refer to the QuickLIT

More information

R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators

R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators Installation Sheets Manual 121 Relays and Contactors Section R Technical Bulletin R81EAA Application R81 plug-in electronic

More information

P70, P72, and P170 Series Controls for High Pressure Applications

P70, P72, and P170 Series Controls for High Pressure Applications Installation Instructions P70 Issue Date 0918 P70, P72, and P170 Series Controls for High Pressure Applications Application P70, P72, and P170 Series Controls for High Pressure Applications provide high-side

More information

POWERS CONTROL RC 195 Multiple Input Receiver- Controller

POWERS CONTROL RC 195 Multiple Input Receiver- Controller POWERS CONTROL RC 195 Multiple Input Receiver- Controller Document No. 155-036P25 RC 195-1 Description Features Application The RC 195 Multiple lnput Receiver-Controller is a pneumatic instrument which

More information

P70 Series MICRO-SET TM Pressure Controls for Refrigeration and Air Conditioning, 4-Wire, 2-Circuit Contact Block

P70 Series MICRO-SET TM Pressure Controls for Refrigeration and Air Conditioning, 4-Wire, 2-Circuit Contact Block P70 Series MICRO-SET TM Pressure Controls for Refrigeration and Air Conditioning, 4-Wire, 2-Circuit Contact Block Installation Sheets Manual 121 Pressure Controls Section Technical Bulletin P70 Issue Date

More information

D-4070 Two Stage Pneumatic Actuator

D-4070 Two Stage Pneumatic Actuator FANs 268.1, 1628.3 Product/Techncial Bulletin D4070 Issue Date 1095 D-4070 Two Stage Pneumatic Actuator The D-4070 Two Stage Pneumatic Actuator is a multipurpose positioning device used to accurately position

More information

Terms. Direct Acting (DA) The action of a controller that increases its branch line pressure as the controlled variable increases

Terms. Direct Acting (DA) The action of a controller that increases its branch line pressure as the controlled variable increases Pneumatic Control Terms Direct Acting (DA) The action of a controller that increases its branch line pressure as the controlled variable increases Terms Reverse Acting (RA) The action of a controller that

More information

Distributed By: M&M Control Service, Inc PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE #

Distributed By: M&M Control Service, Inc PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # Switches Selector Switches SW 786 155-118P25 G-3 Positioning Switch SW 141 155-117P25 G-5 Enthalpy Control Switch EE 141 155-054P25 G-7 Static Pressure

More information

Discharge Air Control

Discharge Air Control Issue Date June 17, 2002 APPLICATION NOTE Discharge Air Control Discharge Air Control...2 Introduction... 2 Key Concepts... 3 Discharge Air Control Overview... 3 Design Considerations... 6 2002 Johnson

More information

RA-2000 Airflow Measuring System

RA-2000 Airflow Measuring System RA-2000 Airflow Measuring System Product Bulletin Code No. LIT-1201677 Issued May 2016 Refer to the QuickLIT website for the most up-to-date version of this document. Since 1905, Johnson Controls has provided

More information

VA-7450 Series. Electric Valve Actuators

VA-7450 Series. Electric Valve Actuators 34-636- 771, Rev. D Installation Instructions VA-7450 Series Issue Date 0216 VA-7450 Series Electric Valve Actuators Applications VA-7450 Series Electric Valve Actuators provide on/off, floating, or proportional

More information

Distributed By: M&M Control Service, Inc PRODUCT PRODUCT CODE RESOURCE DOCUMENTS PAGE #

Distributed By: M&M Control Service, Inc PRODUCT PRODUCT CODE RESOURCE DOCUMENTS PAGE # PRODUCT PRODUCT CODE RESOURCE DOCUMENTS PAGE # Pneumatic Receiver-Controllers Single Input Receiver-Controller RC 195 155-119P25 C-3 Multiple Input Receiver-Controller RC 195 155-036P25 C-5 Pneumatic Transmitters

More information

BD-1600 Balancing/Zone Control Damper

BD-1600 Balancing/Zone Control Damper BD-1600 Balancing/Zone Control Damper Product Bulletin Code No. LIT-12012355 Issued September 2016 Refer to the QuickLIT website for the most up-to-date version of this document. The BD-1600 Balancing/Zone

More information

Damper Actuator Installation

Damper Actuator Installation FANs 268.1, 977, 1628.3 Installation Bulletin EPP-1000 Issue Date 0800 EPP-1000 Series Electro-Pneumatic Positioners A pplication The EPP-1000 is designed for applications where electronic control of pneumatic

More information

P445 Series Electronic Lube Oil Control

P445 Series Electronic Lube Oil Control FANs 125, 121 s Section P Product/Technical Bulletin P445 Issue Date 0100 P445 Series Electronic Lube Oil The P445 Series Electronic Lube Oil is designed for use on refrigeration compressors equipped with

More information

Pneumatic Controls. Pneumatic Controls Sections

Pneumatic Controls. Pneumatic Controls Sections Pneumatic Controls Pneumatic Controls Sections Controllers and Switches Thermostats Relays Sensors and Transmitters See the Contents Section at the front of the Product Catalog for the complete data sheet

More information

A11 Series Low Temperature Cutout Control

A11 Series Low Temperature Cutout Control A11 Series Low Temperature Cutout Control Installation Instructions Part No. 997-358, Rev. F Issued March 2016 Applications IMPORTANT: All Series A11 temperature controls are designed for use only as operating

More information

EP-8000 Series Electro-Pneumatic Transducers

EP-8000 Series Electro-Pneumatic Transducers FANs 216, 1628.3 Product/Technical Bulletin Issue Date 1196 eries Electro-Pneumatic Transducers eries Electro-Pneumatic Transducers convert a voltage or current signal from an electronic controller into

More information

R81EAA-2 Economizer Circuit Board

R81EAA-2 Economizer Circuit Board FAN 121, 628.1 Motor Actuators Section M Technical Bulletin R81E Issue Date 0993 R81EAA-2 Economizer Circuit Board Applications Setpoint Adjustment Temp T1 T2 S2 1O S 1 8 9 Changeover Relay Refrigeration

More information

Section Va: Valve Actuators

Section Va: Valve Actuators Valve and Actuator Manual 977 Actuator Basics and Sizing Information Section Engineering Data Book Va Issue Date 0592 Section Va: Valve Actuators Pneumatic Actuators Page 3 Electric Actuators 5 Maximum

More information

Metasys Zoning Package Installation

Metasys Zoning Package Installation Technical Bulletin Issue Date August 28, 2002 Metasys Zoning Package Installation Metasys Zoning Package Installation...2 Introduction... 2 Key Concepts... 3 Installation Overview... 3 Metasys Zoning Package

More information

AD-1250 Airflow Measuring Station

AD-1250 Airflow Measuring Station AD-1250 Airflow Measuring Station Product Bulletin Code No. LIT-12011472 Issued March 2016 Refer to the QuickLIT website for the most up-to-date version of this document. The AD-1250 Airflow Measuring

More information

P10 Series Low Range Pressure Controls

P10 Series Low Range Pressure Controls Master Catalog 125 Pressure Controls Section P Product Bulletin P10 Issue Date 1290 P10 Series Low Range Pressure Controls Application The P10 Series low pressure controls are for applications in which

More information

Appendix A: Inputs, Outputs, and Parameters

Appendix A: Inputs, Outputs, and Parameters Technical Bulletin Issue Date 11/01/01 TECHNICAL BULLETIN Appendix A: Inputs, Outputs, and Parameters Introduction This appendix describes the inputs, outputs, and parameters used with the Metasys Zoning

More information

G72x Series Direct Spark Ignition Controls

G72x Series Direct Spark Ignition Controls Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin G72x Issue Date 1299 G72x Series Direct Spark Ignition Controls Figure 1: G72x Direct Spark Ignition

More information

Q35 Series Automatic Vent Damper System

Q35 Series Automatic Vent Damper System Installation Sheets Manual 121 Energy Conservation and Miscellaneous Kits Section Q Technical Bulletin Q35 Issue Date 0999 Q35 Series Automatic Vent Damper System Figure 1: Q35 Automatic Vent Damper System

More information

Components of Hydronic Systems

Components of Hydronic Systems Valve and Actuator Manual 977 Hydronic System Basics Section Engineering Bulletin H111 Issue Date 0789 Components of Hydronic Systems The performance of a hydronic system depends upon many factors. Because

More information

M9000-3xx Series Weather Shield Enclosures

M9000-3xx Series Weather Shield Enclosures M9000-3xx Series Weather Shield Enclosures Product Bulletin Code No. LIT-1201704 Issued June 2016 Refer to the QuickLIT website for the most up-to-date version of this document. The M9000-3xx Weather Shield

More information

TK-6024, TK-6124, TK-8024, TK-8124

TK-6024, TK-6124, TK-8024, TK-8124 TK-6024, TK-6124, TK-8024, TK-8124 Pneumatic Bulb Thermostats General Instructions APPLICATION For proportional temperature control of pneumatic valves and actuators to maintain air or liquid temperatures

More information

M9220-xxx-3 Electric Spring Return Actuators

M9220-xxx-3 Electric Spring Return Actuators M9220-xxx-3 Electric Spring Return Actuators Product Bulletin Code No. LIT-12011057 Issued September 2017 The M9220-xxx-3 Actuators are direct mount, spring return electric actuators that operate on these

More information

M9116, M9124, and M9132 Series Electric Non-spring Return Actuators

M9116, M9124, and M9132 Series Electric Non-spring Return Actuators Product Bulletin M91xxx Issue Date September 2017 M9116, M9124, and M9132 Series Electric Non-spring Return Actuators The M91xx Series includes M9116, M9124, and M9132 models. All of these direct-mount

More information

VA-7150 Electric Valve Actuator. Features and Benefits. G 500N force output in a compact unit G Magnetic clutch. G Unique Yoke Design

VA-7150 Electric Valve Actuator. Features and Benefits. G 500N force output in a compact unit G Magnetic clutch. G Unique Yoke Design VA-7150 Electric Valve Actuator European Electronic Controls Catalogue Section E Product Bulletin VA-7150 Issue Date 03 2000 I ntroduction The VA-7150 series synchronous motor driven actuator provides

More information

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL Temperature Controller TC5+2V4SA Plus USER'S MANUAL NOTICE Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,

More information

RD-2000 Round Control Dampers

RD-2000 Round Control Dampers RD-000 Round Control Dampers Product Bulletin Code No. LIT-8105 Issued February 5, 010 Supersedes July, 009 Johnson Controls provides top-quality, low-leakage RD-000 Round Control Dampers for use in Heating,

More information

Flare Valves 1/2 inch 2-Way and 3-Way

Flare Valves 1/2 inch 2-Way and 3-Way Valve and Actuator Manual 977 Valve Product Information Section Product Bulletin VTF Series Issue Date 0596 Flare Valves 1/2 inch 2-Way and 3-Way The 1/2 inch flared valve line is designed to accurately

More information

CAPSU-PHOTOHELIC PRESSURE SWITCH/GAGE*

CAPSU-PHOTOHELIC PRESSURE SWITCH/GAGE* CAPSU-PHOTOHELIC PRESSURE SWITCH/GAGE* Specifications - Installation and Operating Instructions Bulletin B-34 Series 43000 CAPSU-Photohelic Switch/Gage The CAPSU-Photohelic Switch/Gage is a most versatile,

More information

DWYER INSTRUMENTS, INC. Phone: 219/ P.O. BOX 373 MICHIGAN CITY, IN 46361, U.S.A. Fax: 219/

DWYER INSTRUMENTS, INC. Phone: 219/ P.O. BOX 373 MICHIGAN CITY, IN 46361, U.S.A. Fax: 219/ Series 43000 Capsu-Photohelic Pressure Switch/Gage Specifications - Installation and Operating Instructions Bulletin B-34 Ø4-3/4 [120.65] 3-7/8 SQ [98.43] 3/4 CONDUIT 4-3/8 [111.13] HOUSING REMOVAL 3-1/16

More information

Introduction to Johnson Controls Dampers

Introduction to Johnson Controls Dampers Damper and Actuator Product Guide 268.1 Damper Engineering Section Product Bulletin Issue Date 1297 Introduction to Johnson Controls Dampers For over 100 years, Johnson Controls has been the industry leader

More information

System 350 P352AB Electronic Pressure Control Series

System 350 P352AB Electronic Pressure Control Series System 350 P352AB Electronic Pressure Control Series System 350 Product Guide 930 Basic Controls Section Product/Technical Bulletin P352AB Issue Date 0200 The P352AB controls are On/Off electronic pressure

More information

ECONOMIZERS. 5/2012 Supersedes

ECONOMIZERS. 5/2012 Supersedes Litho U.S.A. 2012 ECONOMIZERS 507031 01 5/2012 Supersedes 506747 01 K1ECON ECONOMIZERS INSTALLATION INSTRUCTIONS FOR ECONOMIZERS AND OUTDOOR AIR HOODS USED WITH KG/KC/KH 024, 030, 036, 048, 060, 072, 090

More information

M Valve Actuator Weather Shield Kit

M Valve Actuator Weather Shield Kit 34-636- 2235, Rev. C M9000-341 Valve Actuator Weather Shield Kit Installation Instructions Part No. 34-636-2235, Rev. C Issued March 2016 Applications The M9000-341 Weather Shield Kit is a cost-effective

More information

G600 Series Replacement Intermittent Pilot Ignition Controls

G600 Series Replacement Intermittent Pilot Ignition Controls Installation Instructions G600 Issue Date 0601 G600 Series ment Intermittent Pilot Ignition Controls Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing

More information

Powers TM Controls RL 243 SW Switching Relay

Powers TM Controls RL 243 SW Switching Relay Powers TM Controls RL 243 SW Switching Document No. 155-040P25 RL 243-4 Description The Powers 243 SW Switching is a two-position, pilot-operated auxiliary device used for switching a common part from

More information

Installation Instructions

Installation Instructions 024A02 025A02 SMALL ROOFTOP UNITS HORIZONTAL ECONOMI$ER IV ACCESSORY 2TO12-1/2TONS Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 PACKAGE USAGE... 1 SAFETY CONSIDERATIONS... 1 GENERAL...

More information

VAV Terminal Unit Control Package

VAV Terminal Unit Control Package VAV Terminal Unit Control Package Model CP-133-STK Pneumatic Pressure Independent, VAV Cooling, Constant Volume Heating at Min CFM set point. This actuator/controller will accommodate Direct or Reverse

More information

P70, P72, and P170 Controls for Low Pressure Applications

P70, P72, and P170 Controls for Low Pressure Applications Master Catalog 125 Pressure Controls Section P Product/Technical Bulletin Issue Date 0900 P70, P72, and P170 Controls for Low Pressure Applications The P70, P72, and P170 controls for low pressure applications

More information

Installation Instructions

Installation Instructions 020A02 021A03 008C00 SMALL ROOFTOP UNITS VERTICAL ECONOMI$ER IV ACCESSORY 2to12-1 / 2 TONS LARGE ROOFTOP UNITS VERTICAL AND HORIZONTAL ECONOMI$ER IV ACCESSORY 13 to 25 TONS Installation Instructions TABLE

More information

I ntroduction. VA-7450 Electronic Terminal Unit Valve Actuator. Features and Benefits

I ntroduction. VA-7450 Electronic Terminal Unit Valve Actuator. Features and Benefits European Electronic Controls Catalogue Catalogue Section E Product Bulletin VA-7450 Issue Date 199 VA-7450 Electronic Terminal Unit Valve I ntroduction The VA-7450 Series provides floating or proportional

More information

BAS Construction Checklist

BAS Construction Checklist BAS Construction Checklist Project: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing. The checklist items

More information

ECONOMIZERS. 1/2012 Supersedes

ECONOMIZERS. 1/2012 Supersedes ECONOMIZERS Litho U.S.A. 2012 506948 01 1/2012 Supersedes 506394 01 K1ECON20C 1 ECONOMIZERS INSTALLATION INSTRUCTIONS FOR ECONOMIZER AND OUTDOOR AIR (604592 03; 54W77) USED WITH KG/KC/KH 180 300S UNITS

More information

I ntroduction. N ote. Series P74 Differential Pressure Controls, without time delay. Feature and Benefits

I ntroduction. N ote. Series P74 Differential Pressure Controls, without time delay. Feature and Benefits PSC9626 European Refrigeration Controls Catalogue Catalog Section 6 Product Bulletin Series Differential Pressure Controls, without time delay I ntroduction These controls are designed to sense pressure

More information

P70, P72 and P170 Series Controls for High Pressure Applications

P70, P72 and P170 Series Controls for High Pressure Applications Installation Instructions P70 Issue Date October 16, 2002 P70, P72 and P170 Series Controls for High Pressure Applications Application P70, P72 and P170 Series Controls for High Pressure Applications provide

More information

P20, P21 Series Air Conditioning Limit Controls

P20, P21 Series Air Conditioning Limit Controls Master Catalog 125 Pressure Controls Section P Product Bulletin P20, P21 Issue Date 0318 P20, P21 Series Air Conditioning Limit Controls Application These air conditioning limit controls are specially

More information

Library Product Section Product Model Literature Type Sequence Date File No. Supersedes

Library Product Section Product Model Literature Type Sequence Date File No. Supersedes INSTALLER'S GUIDE ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. Library Product Section Product Model Literature Type Sequence Date File No. Supersedes ACC-SVN85B-EN

More information

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

ZIP Economizer Fault Detection and Diagnostics (FDD) Table Fault Detection and Diagnostics (FDD) Table Fault Detection Problem Diagnostic ction (in addition to alarm stored / transmitted) Potential Cause C Fault Code OT sensor predetermined range O damper returns

More information

G76x Direct Spark Ignition Controls

G76x Direct Spark Ignition Controls Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin G76x Issue Date 0400 G76x Direct Spark Ignition Controls Figure 1: G76x Direct Spark Ignition

More information

Temperature Controller TC5-2V8SA USER'S MANUAL. M rev. 03 K rev. 00

Temperature Controller TC5-2V8SA USER'S MANUAL. M rev. 03 K rev. 00 Temperature Controller USER'S MANUAL M 890-00174 rev. 03 K 895-00327 rev. 00 TABLE OF CONTENTS Page PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE CONTROLS... 6 Controller Status Leds... 7 Internal Switches...

More information

ATP-2040 Electric Damper Actuator/Transmitter

ATP-2040 Electric Damper Actuator/Transmitter ATP-2040 Electric Damper Actuator/Transmitter Kit Includes 1. Actuator/Transmitter package: factory assembled Actuator (EDA-2040) and Transmitter (DPT-2000). Product Code Number Coupler Size Differential

More information

M x Series Valve Linkage Kits

M x Series Valve Linkage Kits M9000-51x Series Valve Linkage Kits Installation Instructions M9000-51x 14-1201- 13, Rev. H Part No. 14-1201-13, Rev. H Issued May 2016 Applications Use the M9000-51x Series Valve Linkage Kits to field

More information

TE-6001 Hardware Assemblies for TE-6000 Temperature Elements

TE-6001 Hardware Assemblies for TE-6000 Temperature Elements *24403434E* 24-4034-34, Rev. E Product/Technical Bulletin TE-6001 Issue Date September 2017 TE-6001 Hardware Assemblies for TE-6000 Temperature Elements TE-6001-2 TE-6001 Hardware Assemblies are used with

More information

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas Installation Manual IOM-MBC-00 08-30-04 Mixing Box Control Systems Installation,, and Maintenance Manual Contents Page Introduction...1 General...1 Safety...1 Inspection...1 Mixing Box Control Systems...2

More information

TROUBLESHOOTING GUIDE FOR HEAT PUMP BOOSTERS MODELS: HPB11, HPB15, & HPB22

TROUBLESHOOTING GUIDE FOR HEAT PUMP BOOSTERS MODELS: HPB11, HPB15, & HPB22 V3 TROUBLESHOOTING GUIDE FOR HEAT PUMP BOOSTERS MODELS: HPB11, HPB15, & HPB22 PREFACE This guide contains instructions for troubleshooting the Steffes Corporation room heating units: Models HPB 11, HPB

More information

M9109 Series Electric Non-spring Return Actuators

M9109 Series Electric Non-spring Return Actuators 34-636- 1190, Rev. D Installation Instructions M9109 Issue Date 03/1/16 M9109 Series Electric Non-spring Return Actuators Installation IMPORTANT: Use this M9109 Series actuator only to control equipment

More information

M9109-GGx-4 Series Proportional Electric Non-Spring Return Actuators

M9109-GGx-4 Series Proportional Electric Non-Spring Return Actuators 34-636- 1484, Rev. B Installation Instructions M9109-GGx-4 Issue Date March 2016 M9109-GGx-4 Series Proportional Electric Non-Spring Return Actuators Installation IMPORTANT: The M9109-GGx-4 Series Electric

More information

M9106-GGx-4 Series Proportional Electric Non-Spring Return Actuators

M9106-GGx-4 Series Proportional Electric Non-Spring Return Actuators M9106-GGx-4 Series Proportional Electric Non-Spring Return Actuators 34-636- 1468, Rev. B Installation Instructions M9106-GGx-4 Issue Date March 2016 Installation IMPORTANT: The M9106-GGx-4 Electric Actuator

More information

M100F Incremental Motor Actuator R81F Interface Board

M100F Incremental Motor Actuator R81F Interface Board Installation Sheets Manual 121 Motor Actuators Section M Technical Bulletin M100F Issue Date 0493 M100F Incremental Motor Actuator R81F Interface Board Application Details Figure 1: M100 Motor Actuator

More information

A91 Series Thermistor Temperature Sensors For Duct, Immersion and Space Sensing

A91 Series Thermistor Temperature Sensors For Duct, Immersion and Space Sensing A91 Series Thermistor Temperature Sensors For Duct, Immersion and Space Sensing Installation Sheets Manual 121 Temperature Controls Section A Technical Bulletin A91 Issue Date 0179 Application These thermistor

More information

Product Data. Features/Benefits. 45J,M,K,N,Q,R Standard, Quiet, and Low Profile Fan Powered Variable Air Volume Terminals

Product Data. Features/Benefits. 45J,M,K,N,Q,R Standard, Quiet, and Low Profile Fan Powered Variable Air Volume Terminals Product Data 5J,M,K,N,Q,R Standard, Quiet, and Low Profile Fan Powered Variable Air Volume Terminals 90 to 3900 Cfm Series Fan Box 5J,K,Q Parallel Fan Box 5M,N,R 5J,M 5K,N 5Q,R The 5J,M,K,N,Q,R units were

More information

AV-8020 Series Floating Control Actuated Valve

AV-8020 Series Floating Control Actuated Valve FANs 977, 1628.3 Product/Technical Bulletin AV-8020 Issue Date 0300 AV-8020 Series Floating Control Actuated Valve The AV-8020 is an electric actuator/brass valve combination that furnishes floating control

More information

M9109-GGx-5 Series Proportional Electric Non-spring Return Actuators

M9109-GGx-5 Series Proportional Electric Non-spring Return Actuators 34-636- 1360, Rev. C Installation Instructions M9109-GGx-5 Issue Date March 2016 M9109-GGx-5 Series Proportional Electric Non-spring Return Actuators Installation IMPORTANT: Use this M9109-GGx-5 Series

More information

SRC. An Outdoor Reset Control for Sub-Atmosphere Steam Systems OUTDOOR TEMPERATURE

SRC. An Outdoor Reset Control for Sub-Atmosphere Steam Systems OUTDOOR TEMPERATURE SRC STEAM RESET CONTROL An Outdoor Reset Control for Sub-Atmosphere Steam Systems Heat-Timer s theory of steam reset heating is as follows: Pulse the valve open to a limited valve position, very slowly

More information

Series P28. Oil Protection Controls. Feature and Benefits. P28DP Oil Protection Control (P) Setpoint adjusting cam

Series P28. Oil Protection Controls. Feature and Benefits. P28DP Oil Protection Control (P) Setpoint adjusting cam PSC9705 European Refrigeration Controls Catalogue Catalog Section 6 Product Bulletin P8 Series P8 Oil Protection Controls Introduction These oil protection controls are designed to give protection against

More information

Honeywell MP516A UNIT VENTILATOR DAMPER OPERATOR GENERAL DESCRIPTION APPLICATION SPECIFICATIONS OPERATION

Honeywell MP516A UNIT VENTILATOR DAMPER OPERATOR GENERAL DESCRIPTION APPLICATION SPECIFICATIONS OPERATION Honeywell MP516A UNIT VENTILATOR DAMPER OPERATOR GENERAL DESCRIPTION The MP516A is a sturdy, compact, rolling diaphragm pneumatic damper operator. APPLICATION Primarily, the MP5 16A controls dampers in

More information

VIFB Coil Technical Guide

VIFB Coil Technical Guide TGVIFB-5 VIFB Coil Technical Guide VERTICAL TUBE INTEGRAL FACE AND BY-PASS HEATING COILS FOR AIR PREHEATING Since 1875, the L.J. Wing Company has been a leader in providing innovative solutions for difficult

More information

SERIES 14 INSTALLATION INSTRUCTIONS and field service check list

SERIES 14 INSTALLATION INSTRUCTIONS and field service check list BULLETIN MI2046-1/04 REPLACED MI1078 SERIES 14 INSTALLATION INSTRUCTIONS and field service check list A1014 Amplifier A1014L1 Amplifier / AD1014/AD1014L1 Amplifier-Selectors AD1214 Amplifier Mixing Tube

More information

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

Screw. (Note 4) Spacer for 1 filter ILL. 3. Screw ICP INSTALLATION INSTRUCTIONS for (NPECOMZR006A00) ICP's economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions completely and carefully

More information

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

Screw. (Note 4) Spacer for 1 filter ILL. 3. Screw MicroMetl INSTALLATION INSTRUCTIONS for 0637-0311 (CPECOMZR006A00) MicroMetl's 0637 economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions

More information

Blank-off. HVAC unit screws. Spacer for 1" filter ILL. 3. Screw

Blank-off. HVAC unit screws. Spacer for 1 filter ILL. 3. Screw ICP INSTALLATION INSTRUCTIONS for NPECOMZR00A00 ICP's economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions completely and carefully

More information

Engineering Bulletin. Recirculation Energy Recovery Unit Controls CLCH-PRB009-EN

Engineering Bulletin. Recirculation Energy Recovery Unit Controls CLCH-PRB009-EN Engineering Bulletin Recirculation Energy Recovery Unit Controls Introduction The following represents just one of many configurations that are possible with the Trane Climate Changer air handler with

More information

A-4000 Series Oil Removal and Pressure Reducing Stations & Air Compressor Accessories

A-4000 Series Oil Removal and Pressure Reducing Stations & Air Compressor Accessories Pneumatic Air Supply Manual 718 Filter Stations Section Product Bulletin Issue Date 0907 A-4000 Series Oil Removal and Pressure Reducing Stations & Air Compressor Accessories Oil Removal and Pressure Reducing

More information

Fisher 2506 and 2516 Receiver Controllers

Fisher 2506 and 2516 Receiver Controllers 2506/2516 Receiver Controllers Product Bulletin Fisher 2506 and 2516 Receiver Controllers The 2506 receiver controller takes the input from a pneumatic transmitter, matches it against the adjustable set

More information

Installation Instructions

Installation Instructions 05A00 053A00 VERTICAL AND HORIZONTAL ECONOMIZER IV ACCESSORY MEDIUM ROOFTOP UNITS 5 to 5 TONS TABLE OF CONTENTS PACKAGE USAGE... SAFETY CONSIDERATIONS... PACKAGE CONTENTS... GENERAL... ACCESSORIES LIST...

More information

VA-4233-GGx Series Electric Valve Actuators

VA-4233-GGx Series Electric Valve Actuators Installation Instructions Issue Date August 11, 2003 VA-4233-GGx Series Electric Valve Actuators Installation Refer to Figures 2 through 4 for proper actuator orientation before attempting to make the

More information

VT Series Terminal Unit Valves 1/2 inch, 2-Way and 3-Way ANSI Class 250 Body Rating

VT Series Terminal Unit Valves 1/2 inch, 2-Way and 3-Way ANSI Class 250 Body Rating FANs 977, 125, 1628. Product Bulletin VT Issue Date 0596 VT Series Terminal Unit Valves 1/2 inch, 2-Way and -Way ANSI Class 250 Body Rating The VT Series Terminal Unit Valves are designed to accurately

More information

System 350 S350P Proportional Plus Integral Temperature Stage Module

System 350 S350P Proportional Plus Integral Temperature Stage Module FANs 930, 930.5 Add-On Modules Section Product/Technical Bulletin S350P Issue Date 0997 System 350 S350P Proportional Plus Integral Temperature Stage Module The S350P is used in conjunction with the A350

More information

Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output

Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output TCAF Series Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output Issue Date March 1, 2018 Features Ultra slim wall-mount unit to match any décor Large easy-to-read Liquid Crystal Display (LCD), with

More information

Installation Instructions

Installation Instructions Part Number: CPECOMZR011A00 & CPECOMZR012A00 Installation Instructions Read these instructions completely before attempting to install the Horizontal Accessory. CONTENTS SAFETY CONSIDERATIONS...1 GENERAL...1,2

More information

EconoMi$er, Power Exhaust, and Sensor Installation Instructions

EconoMi$er, Power Exhaust, and Sensor Installation Instructions Small Rooftop Units Gas Heating/Electric Cooling, Electric Cooling, and Heat Pump Units 3 to.5 Tons (50/60 Hz) EconoMi$er Package for Vertical and Horizontal Duct Systems Issue Date /0/0 EconoMi$er, Power

More information

First Correlating Revision No. 1-NFPA [ Section No ]

First Correlating Revision No. 1-NFPA [ Section No ] First Correlating Revision No. 1-NFPA 85-2013 [ Section No. 3.3.52.1 ] 3.3.52.1 Booster Fan. A device fan used to assist in the supply of air to, or the removal of flue gas products from, the combustion

More information

Installation Instructions

Installation Instructions Part Number: CPECOMZR008A00 & CPECOMZR009A00 Installation Instructions Read these instructions completely before attempting to install the Vertical Accessory. CONTENTS SAFETY CONSIDERATIONS...1 GENERAL...1,2

More information

TM-11x1 Series Room Temperature Module

TM-11x1 Series Room Temperature Module 24-10225- 4, Rev. C TM-11x1 Series Installation Instructions Part No. 24-10225-4, Rev. C Issued March 16 Applications The TM-11x1 Series of s are designed for use with the TC-9102 Direct Digital Control

More information