Electrical Switchgear Replacement Montgomery County Community College
|
|
- Corey George
- 6 years ago
- Views:
Transcription
1 Electrical Switchgear Replacement Montgomery County Community College ADDENDUM NO.1 # SB01 November 12, 2014 The following clarifications, changes, additions or deletions for this project shall be made to the Contract Documents; all other conditions and work shall remain unchanged. The Addendum supersedes current conditions shown in the Contract Documents. Acknowledge the receipt of this Addendum by inserting the number and date in your bid. This Addendum forms a part of the Contract Documents and modifies the documents as follows: 1. Is there a spec for the new fence being provided or is the Electrical Contractor to match the existing? Match existing. 2. Refer to Page 54: Item #13-Arc Terminator states to "See specification Integrated Arc Extinguishing System." This item/spec section is not found in the specs. Please provide this spec section. Attached is Square D specification for Integrated Arc Extinguishing System. Comparable systems by other approved manufacturers are acceptable. Specification Number: Product Name: ARC EXTINGUISHING SYSTEM FOR MCLD SWITCHGEAR SECTION Integrated Arc Extinguishing System Medium Voltage Metal-clad Switchgear PART 1 GENERAL 1.01 SECTION INCLUDES A. This section describes the materials and installation requirements for integrated arc extinguishing system in metal-clad switchgear REFERENCES A. UL 508 Industrial Control Equipment, Sixteenth Edition, February 1993, and any identified subsidiary standards. B. CSA-C22.2, No. 14-M91 Industrial Control Equipment, September 1991 C. IEC Electromagnetic Compatibility for Industrial-Process Measurement and Control Equipment, Sections 2, 3, 4, and 5, Level 4. D. C IEEE Standard for Relays and Relay Systems Associated with Electrical Power Apparatus. E. C IEEE Standard Surge Withstand Capability (SWC) Tests for Protective Relays and Relay Systems. F. C IEEE Standard for Withstand Capability of Relay Systems to Radiated Electromagnetic Interference from Transceivers.
2 G. IEC68.2 Basic Environmental Testing Procedures, Sections 6, 27, 29, and SUBMITTALS A. The power equipment shop drawings shall clearly identify the system components, internal connections, and all contractor connections. B. Product Data: Provide catalog sheets and technical data sheets to indicate physical data and electrical performance, electrical characteristics, and connection requirements RELATED SECTIONS A. Section Metal-clad Circuit Breaker Switchgear. PART 2 PRODUCT 2.01 ARC EXTINGUISHING SYSTEM - GENERAL A. Provide integral arc extinguishing system within the metal-clad switchgear. The system shall respond to an internal arcing fault condition within the switchgear by actively controlling and directing the flow of current to extinguish the open burning arc. B. Extinguishing of the open arc fault condition shall be achieved by creating a low impedance conducting path for the fault current in parallel with the arc via a high speed closing switch. C. Sensing of the open arc fault condition within the switchgear shall be achieved by monitoring both current and optical sensors installed within the switchgear lineup. In order to prevent nuisance operations, the system shall incorporate a logical 'AND' function that requires both optical sensing of an open arc condition and the sensing of a discontinuity in the current waveform prior to activation of the high speed switch. D. The control unit for the system shall include a self-test module that continuously monitors the system and energizes an alarm relay in the event that a system component is not functioning properly. E. The system shall limit the duration of an arcing fault condition and associated pressure buildup within the switchgear by sensing the arc and closing the switch in less than 4 milliseconds.
3 2.02 ARC EXTINGUISHING SYSTEM - RATINGS A. The Arc Extinguishing System shall have the following ratings: Table 1: Arc Extinguishing System Ratings and Specifications Type Rating Currents Nominal Fault 25, 36 and 40 ka rms symmetrical Currents (I) Continuous Current Not Applicable Rating Making Current 2.6 x I ka peak Short Time Current 48 ka for 1 second Interrupting Current Not Applicable Voltages Maximum Operating 15 kv rms. Voltage 60 Hz. One minute 36 kv rms. withstand BIL 95 kv Mechanical Contact closing time 3.5 ms max Arcing fault detection time 0.5 ms Total operating time 4.0 ms Mechanism Reset Manual Only Closing Mechanism Spring operated with electrodynamic assist Mechanical operating life 100 operations Environmental Normal operating -30 C to + 40 C ambient temperature Humidity up to 95% RH Fault Detection Instantaneous analog detection from CT on main bus entrance Arc Detection Optical detectors installed on each individual compartment Closing Signal Provided by the output of AND gate for simultaneous fault current and optical signals Initial Power Up Time Max 1 Minute Power Supply Requirements 120 or 240 VAC or 48 to 250 VDC Auxiliary Contacts 2 a and 2 b type contacts (Form C) 2.03 ARC EXTINGUISHING SYSTEM - SWITCHGEAR REQUIREMENTS A. The high-speed switch and controller shall require the same physical mounting space as a metal-clad circuit breaker. It shall be possible to provide the high-speed switch and controller in the same vertical section with a feeder circuit breaker. B. The high-speed switch and controller cubicle shall be designed as an integral part of the structure and shall include fixed primary contacts located within insulating bushings. Designs that require cable connection of the high-speed switch to the main bus are not acceptable for new applications. C. One high-speed switch and controller shall be provided for each group of up to 10 vertical sections for each main bus segment in the switchgear lineup. D. An optical sensor shall be located in each isolated compartment of the switchgear lineup. E. Each vertical section of the switchgear lineup shall include a junction box in the low voltage compartment with operation indicators for each optical sensor in the section. The operation indicators shall indicate which specific sensor /compartment within the vertical section detected an arc. In addition a single operation indicator shall be mounted on the exterior of each vertical section to provide an indication of which section of the switchgear lineup the arc was detected without opening any compartment doors or removing panels. F. The arc extinguishing system shall be installed and completely wired at the factory.
4 2.03 MANUFACTURERS A. Approved Vendors: Square D Company Arc Terminator System. END OF SECTION 3. Refer to dwg E-2: Note #15 states "to see specification for requirements.. " These specs are not separated by spec sections. Please clarify. Attached is specification section See paragraph D.3. MCCC Breaker Replacement October 9, 2014 NEF No.: 5528 SECTION ELECTRICAL MEDIUM VOLTAGE METALCLAD SWITCHGEAR 1.1 GENERAL A. All applicable requirements of SECTION ELECTRICAL GENERAL shall apply to this entire section and shall have the same force and effect as fully included herein. B. Equipment supplied for the switchgear, such as transformers, receptacles, panelboards, etc., shall meet the requirements of SECTION ELECTRICAL INTERIOR ELECTRICAL WORK. C. Provide complete and wholly operating medium voltage 15KV freestanding metal-clad switchgear with fused disconnect switches and vacuum circuit breakers, PECO metering enclosures and fuses. D. Provide manufacturer's technical service as required for job site consultations on the installations of the equipment, testing and placing the equipment in satisfactory operation including final inspections and for engineering consultations for determining fuse sizes and relay settings. E. Provide written letter stating that the switchgear is ready to be energized. F. Applicable Drawings: The drawing shall be used to supplement these specifications but is furnished for information only. Installation shall be based on approved shop drawings. Drawing No. Title E-1 Single Line Diagram G. Delivery, Storage and Handling 1. Accept equipment on site and inspect for shipping damage. 2. Protect equipment from weather and moisture by covering with heavy plastic or canvas and by maintaining heat within enclosure in accordance with manufacturer's instructions. H. Extra Materials/Accessories 1. Submit one racking handle(s) with equipment. Charging handle to be furnished on each breaker mechanism. 2. Provide one sets of spare control fuses for each set installed. 3. For all switchgear with circuit breakers in upper compartments, provide one circuit breaker lifting device - portable, floor-supported with a roller base. I. Submittals 1. Shop Drawing Submittals - Vendor shall submit three (3) sets of shop drawings to Owner within two (2) weeks of receipt of purchase order. Fabrication to be completed within ten (10) weeks of receipt of Owner approved shop drawings. Vendor shall contact Owner upon receipt of Owner approved drawings. Deliver within one (1) week of fabrication completion. Provide Owner with two (2) weeks minimum notice of delivery date.
5 2. Operating and Maintenance Manuals Vendor shall supply three (3) complete sets of operating and maintenance manuals inclusive of fabrication drawings, complete parts and material listing, recommended spare parts listing and recommended service and service interval listing. 1.2 PRODUCTS A. The metalclad switchgear shall be manufactured by Eaton Corporation, General Electric, Siemens, Square D or an approved equal.
6 B. The metal-clad switchgear shall consist of an outdoor common aisle double row] enclosure containing circuit breakers and the necessary accessory components all factory assembled (except for necessary shipping splits) and operationally checked. The assembly shall be a self-supporting and floor mounted on a level concrete pad. The integrated switchgear assembly shall withstand the effects of closing, carrying and interrupting currents up to the assigned maximum short circuit rating. 1. System Voltage: 13.2KV nominal, three-phase solidly grounded 60 Hz. 2. Maximum Design Voltage:15.0KV. 3. Impulse Withstand (Basic Impulse Level): 95KV. 4. Power Frequency Withstand: 36KV, 1 minute test. 5. Main Bus Ampacity: 1200 amps, continuous. 6. Momentary Current Ratings: Equal to the circuit breaker close and latch rating. C. Components 1. Stationary Structure a. The switchgear shall consist of 10 sections including 3 breaker compartments, 2 PECO metering compartments and 5 auxiliary compartments assembled to form a rigid self-supporting completely enclosed structure providing steel barriers between sections. b. The sections are divided by metal barriers into the following separate compartments: 1) Circuit breaker, instrument, main bus, auxiliary device and cable. Each feeder section may have up to two circuit breaker compartments. c. Provide one set of MOV lighting arresters for each main breaker. d. A strip heater with ambient thermostat shall be provided in all compartments and wired to the control power panelboard. 2. Fused Switches a. The fused switches shall consist of deadfront, completely metal enclosed outdoor freestanding structures containing interrupter switches and fuses of the number, rating, and type noted on the drawings or specified herein. b. The load interrupter switches shall be quick make, quick-break three pole, gang operated, with stored energy operation. Each switch shall have the following minimum ratings: System Voltage 13.2 KV three phase, three wire Maximum Design Voltage 15.0 KV Basic Impulse Level 95 KV Amperes Continuous 600 Amperes Amperes Interrupting 25 K Amperes Sym. Momentary (Switch Closed, 10 cycle) 61 K Amps. Asym. Fault Close 40 K Amps. Asym c. A manual over toggle type mechanism shall be supplied which utilized a heavy duty coil spring to provide opening and closing action of the switch. The speed of opening and closing the switch shall be independent of the operator, and it shall be impossible to tease the switch into any intermediate position.
7 d. The interrupter switch shall have separate main and make/break contacts to provide maximum endurance for fault close and load interrupting duty. The switch assembly shall have insulating barriers between phases and between outer phases and the enclosure. e. The switch assembly shall be integrally designed and produced by the manufacturer of the interrupter switches, fuses and enclosures to assure a completely coordinated design and establish one source of responsibility for the equipment's performance. f. The switchgear shall be rated for outdoor weatherproof use. A strip heater with ambient thermostat shall be provided and wired to the control power panelboard for each switch. g. Dual lugs shall be provided for loop connection of the feeder circuit for the Chiller Plant Switch and the switch shall have provision for a key interlock which interfaces with an existing key lock such that the switch cannot be closed unless the Chiller Plant circuit breaker is open. h. All bus shall be insulated silver plated copper and be mounted on NEMA rated glass polyester insulators. All bussing shall be braced for the maximum available fault current. Bus shall have provisions for future extension. i. Provide a 500W, 240 volt, single phase strip heater with thermostat in each fused switch section. Wire all heaters to the control power panelboard in the switchgear section. 3. Circuit Breaker Compartment a. Each circuit breaker compartment shall be designed to house a horizontal drawout metal-clad vacuum circuit breaker. The stationary primary disconnecting contacts are to be silver-plated copper and mounted within glass polyester support bushings. The movable contacts and springs shall be mounted on the circuit breaker element for ease of inspection/maintenance. b. Entrance to the stationary primary disconnecting contacts shall be automatically covered by metal shutters when the circuit breaker is withdrawn from the connected position to the test or disconnected position or removed from the circuit breaker compartment. Extend a ground bus into the circuit breaker compartment to automatically ground the breaker frame with high-current spring type grounding contacts located on the breaker chassis when in the test and connected positions. Guide rails for positioning the circuit breaker and all other necessary hardware are to be an integral part of the circuit breaker compartment. Blocking devices shall interlock breaker frame sizes to prevent installation of a lower ampere rating or interrupting capacity element into a compartment designed for one of a higher rating. It shall be possible with indoor or outdoor walk-in switchgear to install a circuit breaker into a bottom compartment without use of a transport truck or lift device. 4. Cable Compartment/Ground Bus a. Clamp type cable lugs shall be furnished as shown on plans. The ground bus shall extend through this compartment for the full length of the switchgear including the fused switches. Auxiliary bus, if needed, and load bus support NEMA Class A-20 standoff insulators shall be epoxy. 5. Main Bus Compartment a. The main bus is to be rated 1200 amps and be fully insulated for its entire length including the fused switches and transition sections with an epoxy coating by the fluidized bed process. The conductors are to be silver-plated copper and be of a bolted design. Access to this compartment is gained from the front or rear of the structure by removing a steel barrier. Provide standard provisions for future extension.
8 6. Doors and Panels a. Relays, meters, control switches, etc., shall be mounted on a formed front-hinged panel for each circuit breaker compartment. 7. Circuit Breakers: a. The circuit breakers shall be rated 13,200 nominal volts,15000 maximum volts, 60 Hz, with a continuous current rating of 1200 amps and a maximum symmetrical interrupting rating of 25kA/500MVA - 15 kv system. Furnish Type VR circuit breakers with one vacuum interrupter per phase. Breakers of same type and rating shall be completely interchangeable. The circuit breaker shall be operated by means of a stored energy mechanism which is normally charged by a universal motor but can also be charged by the manual handle supplied on each VR breaker for manual emergency closing or testing. The closing speed of the moving contacts is to be independent of both the control voltage and the operator. Provide a full front shield on the breaker. Secondary control circuits shall be connected automatically with a self-aligning, self-engaging plug and receptacle arrangement when the circuit breaker is racked into the connected position. Provision shall be made for secondary control plug to be manually connected in test position. A minimum of 4 auxiliary contacts (2a 2b), shall be provided for external use. Provisions shall be made for 6 additional cell-mounted auxiliary contacts for external use. The racking mechanism to move the breaker between positions shall be operable with the front door closed and position indication shall be visible with door closed. b. An interlocking system shall be provided to prevent racking a closed circuit breaker to or from any position. An additional interlock shall automatically discharge the stored-energy operating mechanism springs upon removal of the breaker out of the compartment. c. The circuit breaker control voltage shall be: 120, volts ac - provide one capacitor trip unit for each circuit breaker. 8. Instrument Transformers a. Current transformers: Each breaker compartment shall have provision for front-accessible mounting of up to four current transformers per phase (ANSI standard relay accuracy), two on bus side and two on cable side of circuit breaker. The current transformer assembly shall be insulated for the full voltage rating of the switchgear. The current transformers wiring shall be Type SIS #12 AWG. Relaying and metering accuracy shall conform to ANSI Standards. b. Voltage transformers are drawout mounted with primary current-limiting fuses and shall have ratio as indicated. The transformers shall have mechanical rating equal to the momentary rating of the circuit breakers and shall have metering accuracy per ANSI Standards. 9. Control Wiring a. The switchgear shall be wired with type SIS #14 AWG, except where larger size wire is specified. The switchgear shall be provided with terminal blocks for outgoing control connections. Wire markers shall be provided for each end of all control wires. 10. Protective Relays: a. Provide relays as indicated on drawings for each circuit breaker. b. The overcurrent relays shall have time-current coordination curves which match exactly the CO8 and CO9 relays presently used and shall be set to the same settings as the existing relays so as to have exactly the same coordination as the present system.
9 c. The most recent relay test reports with existing relay settings are attached at the end of this specification. 11. With each main circuit breaker, provide a PowerLogic ION7650 manufactured by Schneider Electric or equal with the following characteristics: a. Current/Voltage Inputs 1) The PMS Instrument shall have no less then 4 voltage inputs and 5 current inputs. 2) The PMS Instrument in its standard configuration shall be able to accept 600VAC without using potential transformers. 3) The PMS Instrument shall be able to withstand 1500 VAC RMS continuously. 4) The PMS Instrument shall support nominal current ratings of 1A, 2A, 5A, 10A, and/or 20A. b. PMS Instrument shall provide at minimum the following voltage & current values: 1) Voltage L L Per- Phase, L-L 3-Phase Avg, L N Per-Phase, 3-Phase Avg, Voltage % unbalanced 2) The PMS Instrument shall provide at minimum the following current values: a) Current Per-Phase, Current, Neutral (measured), Current 3-Phase Avg, Current % Unbalanced 3) The PMS Instrument shall provide at minimum the following power & energy values: Real Power (Per-Phase, 3-Phase Total) Reactive Power (Per-Phase, 3-Phase Total) Apparent Power (Per-Phase, 3-Phase Total) Power Factor True (Per-Phase, 3-Phase Total) Power Factor Displacement (Per-Phase, 3-Phase Total Accumulated Energy (Real kwh, Reactive kvarh, Apparent kvah) (Signed/Absolute) Incremental Energy (Real kwh, Reactive kvarh, Apparent kvah) (Signed/Absolute) Conditional Energy (Real kwh, Reactive kvarh, Apparent kvah) (Signed/Absolute) Reactive Energy by Quadrant 12. Provide an automatic transfer system which will open the proper main breaker and close the tie breaker on loss of voltage at either of the two sources. The system shall be approved by PECO. Each main shall have a "push-to-test" pushbutton to allow periodic testing. 13. Arc Terminator: Integrated Arc Extinguishing System up to 50 KA. The system shall respond to an internal arcing fault condition within the switchgear by actively controlling and directing the flow of current to extinguish the open burning arc. See specification Integrated Arc Extinguishing System. 14. Control Power System a. Two control power transformers, each sized for the switchgear support loads (strip heaters, controls, lighting fixtures, receptacles, etc.) plus allowing 5KVA for other existing site loads, shall be provided and connected to the two sources with automatic transfer between the sources.
10 b. A control power panelboard shall be provided with circuit breakers as needed for the above support loads, plus ten 20A, 1 pole breakers for the existing Site Loads. D. Fabrication 1. Construction: Each equipment bay shall be a separately constructed cubicle assembled to form a rigid freestanding unit. Minimum sheet metal thickness shall be 11 gauge steel on all exterior surfaces. Adjacent bays shall be securely bolted together to form an integrated rigid structure. The rear covers shall be removable to assist installation and maintenance of bus and cables. Each individual unit shall be braced to prevent distortion. 2. Dimensions: Outdoor equipment dimensions will vary with enclosure style and circuit breaker selection. Maximum height shall be 115 in for walk-in style enclosure, measured to peak of the sloped roof. 3. Miscellaneous support equipment shall be provided for the walk-in enclosure as follows: a. Provide four two lamp T8 strip lighting fixtures and circuit to illuminate the aisleway with a local switch at each entrance. b. Provide three GFCI receptacles and circuit. Two shall be in weatherproof enclosures on two ends of the switchgear and one shall be in the aisleway. c. Provide two 50 watt metal halide exterior lighting fixtures and circuit with photocell control located over the switchgear doors. 4. The metal-clad switchgear shall be fully assembled, inspected and tested at the factory prior to shipment. Large line-ups shall be split to permit normal shipping and handling as well as for ease of rejoining at the job site. E. Factory Finishing 1. All steel parts, except galvanized (if used), shall be cleaned and a zinc-phosphate (outdoor equipment) or iron phosphate (indoor equipment) pre-treatment applied prior to paint application. 2. Paint color shall be ANSI-61 light grey; TGIC polyester powder, applied electrostatically through air. Following paint application, parts shall be baked to produce a hard durable finish. The average thickness of the paint film shall be 2.0 mils. Paint film shall be uniform in color and free from blisters, sags, flaking and peeling. 3. Adequacy of paint finish to inhibit the buildup of rust on ferrous metal materials shall be tested and evaluated per paragraphs of ANSI C Salt spray withstand tests in accordance with ASTM #D-1654 and #B-117 shall be performed on a periodic basis to provide conformance with the corrosion resistance standard of at least 2500 hours minimum (outdoor equipment) or 600 hours minimum (indoor equipment). 1.3 EXECUTION A. Examination 1. Visually inspect switchgear for evidence of damage and verify that surfaces are ready to receive work. 2. Visually inspect to confirm that all items and accessories are in accordance with specifications and drawings. 3. Verify field measurements are as shown on shop drawings. 4. Verify that required utilities (e.g., control voltage for heater circuits on outdoor switchgear) are available, in proper location, and ready for use.
11 5. Beginning of installation means installer accepts existing surface conditions. B. Installation 1. Install in accordance with manufacturer's instructions, applicable requirements of the NEC and in accordance with recognized industry practices. 2. Install cables, as provided by the switchgear manufacturer, to connect the primary surge arresters. 3. Bending of high-voltage cables should be avoided or minimized. All necessary bends should meet at least the minimum radii specified by the cable manufacturer. 4. Install PECO metering per their standards. 5. Install key interlock system between the fused switch and the existing chiller 13.2KV circuit breaker. C. Field Quality Control 1. Field inspection and testing shall be performed by a qualified Manufacturer's Representative. 2. Visually inspect for physical damage. 3. Perform start-up tests in accordance with manufacturer's instruction manual. 4. Touch-up paint all chips and scratches with manufacturer-supplied paint and leave remaining paint with owner. 5. Verify key interlock operation. 6. Perform low frequency withstand (Hi-Pot) tests according to ANSI/IEEE C , paragraph Perform relay testing by a certified Electrical Testing Agency. 8. Coordinate inspections by PECO's Representative. END OF SECTION
12
13
14
15 THERE ARE NO FURTHER CHANGES TO THIS ADDENDUM END OF ADDENDUM NO.1
SUBSTATION VACUUM CIRCUIT BREAKER (38KV)
SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)
SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products
More informationSUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)
SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationMedium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION
Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 26 24 14 600 VOLT DRAWOUT SWITCHGEAR PART 1 - GENERAL 1.01 SECTION INCLUDES: A. Individually mounted rear-accessible low voltage switchgear ANSI rated switchgear and low voltage power circuit breakers
More informationDetail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order
Amphitheater High School Medium Voltage Switchgear Replacement Basis of Design 8/21/17 1of3 Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationDESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5
DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this
More informationA system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.
General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail
More informationCITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008
CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationA. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.
SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position
LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble
More informationMedium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General
13 SWITCHGEAR Medium Voltage Equipment -1 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General Overview Features Siemens, 7, 1 and 38kV class medium voltage, one- or two-high vacuum circuit breaker switchgear
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................
More informationLow Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear
13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of
More informationMetal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents
January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed
More informationA. Submit manufacturer's literature and technical data before starting work.
SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop
More informationA. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.
16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to
More informationMEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES
MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES Description JRS arc-resistant fused/non-fused load break and fused/non-fused disconnect switches are available for applications
More informationThree-Phase Pole Mounted Recloser
Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE
More informationBGE STRATEGIC CUSTOMER ENGINEERING
TABLE OF CONTENTS 1. GENERAL.. 2 2. BGE SUPPLY FEEDER.. 4 3. SWITCHGEAR ENCLOSURE AND ASSEMBLY... 5 4. SWITCHGEAR MANUFACTURERS.. 8 5. CIRCUIT BREAKER.. 8 6. SWITCHGEAR EQUIPMENT.... 10 7. MAIN AND GROUND
More informationDescriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications
Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter
More information5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application
The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1
More informationContents. Page INTRODUCTION Power/Vac GUIDE FORM SPECIFICATION thru
Contents Page INTRODUCTION... 10-2 Power/Vac GUIDE FORM SPECIFICATION... 10-2 thru 10-12 10-1 Power/Vac Guide Form Specifications Guide Form Specifications INTRODUCTION Upon completion of the one-line
More informationUnderground Distribution Switchgear
Underground Distribution Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear 1. Scope 1.1. This specification applies to three-phase,
More informationTypical Specification
Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,
More informationUnderground Distribution Switchgear
Underground Distribution Switchgear Type VFI, Vacuum Fault Interrupter Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear
More informationUnderground Distribution Switchgear
Underground Distribution Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear 1. Scope 1.1. This specification applies to three-phase,
More informationSpecification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION
Specification Number: 26 24 13.20 Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION 26 24 13.20 SWITCHBOARDS (Long) Main Disconnect Group Mounted Fusible
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not
More informationDIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS
DIVISION 26 ELECTRICAL SECTION 26 28 19 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection
More information7. SERVICES OVER 600 VOLTS
7. SERVICES OVER 600 VOLTS 7.1 GENERAL The Company shall always be consulted to obtain required design criteria where service is contemplated.preliminary plans of the Customer shall be submitted for review
More informationPOWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers
POWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers Class 6037 CONTENTS Schneider Electric Brands Description Page Product Description..................................................
More information2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards
1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases
More informationType SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.
Type SDV6 distribution circuit breaker Top performance - proven reliability Answers for energy. Table of contents Introduction 2-4 Type 3AH3 stored-energy operating mechanism 6 Vacuum interrupters 7 Ratings
More informationSafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure
2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear
More informationSafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin
2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin SafeGear Motor Control Center Arc resistant Metal-Clad construction Descriptive Bulletin Table of Contents
More informationHorizontal Circuit Switchers
> Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving
More informationDesign Standard. Purpose: Design Standard:
Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard
More informationSECTION MOTOR CONTROL
SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters
More informationCapital Projects Group Metal-Clad Switchgears Specification
Capital Projects Group Specification Specification 26 13 26 Revision 0 Date: August 2018 Specification Specification 26 13 26 Publication Date: August 2018 COPYRIGHT 2018 Metrolinx, an Agency of the Government
More informationWARREN COUNTY, N.Y. M/E REFERENCE
SECTION 262000 - ELECTRIC DISTRIBUTION PART 1 - GENERAL 1.1 DESCRIPTION A. Provide a complete secondary distribution system as indicated on the Contract Documents and as specified herein. 1.2 QUALITY ASSURANCE
More informationBUSWAY Low Voltage (Pow-R-Flex)
BUSWAY LOW VOLTAGE (POW-R-FLEX) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein and
More informationSafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin
SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin Contents 1. Introduction 2 2. Product highlights 2 3. Available configuration/competitive
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL
SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationA. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.
1. APPLICATION A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 2. REFERENCE STANDARDS A. The transformers supplied shall
More informationQuik-Spec Coordination Panelboard Specifications
Quik-Spec Coordination Panelboard Specifications 30A - 400A Fusible Panelboards SECTION 26 24 XX (This Specification references CSI MasterFormat 2004) FUSIBLE BRANCH CIRCUIT PANELBOARDS PART 1 1.01 SUMMARY
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More informationPower Break II Switchboard
Power Break II Switchboard Now available with PowerBreak II Circuit Breakers through 4000A GE s Power Break II Switchboard is now available with the new Power Break II Insulated Case Circuit Breaker (800A
More informationGuide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break
Part 1-GENERAL 1.1 DESCRIPTION Guide Specification Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break The switchgear shall consist of magnetically actuated solid dielectric insulated
More informationSolar Power Switchgear & Energy Storage Renewable Energy Systems
7 Solar Power Switchgear & Energy Storage Renewable Energy Systems - Solution Brochure www.apt-power.com 433 N. 36 th Street PROVIDING A COMPREHENSIVE Lafayette, IN 47905 www.apt-power.com 433 APPROACH
More informationHorizontal Circuit Switchers
> Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving
More informationSubmersible Vacuum Fault Interrupters
Submersible Vacuum Fault Interrupters UG Distribution Medium Voltage Vacuum Fault Interrupters Functional Specification Guide PS024002EN Functional Specification for 2.4kV to 17.5kV UG Distribution Medium
More informationATLV MaxSG. Low Voltage Metal Enclosed Switchgear
ATLV MaxSG Low Voltage Metal Enclosed Switchgear ABB, INC. Product General Description MaxSG Switchgear ABB MaxSG switchgear is a further continuation in the development of innovative products from ABB,
More informationSIMOVAC and SIMOVAC-AR. Medium-voltage controllers 2.3 kv kv. usa.siemens.com/simovac
0000 00000 0000 000 0000 000000 00000 0000 00000 0000 000 0000 000000 00000 SIMOVAC and SIMOVAC-AR Medium-voltage controllers 2.3 kv - 6.9 kv usa.siemens.com/simovac 2 SIMOVAC and SIMOVAC-AR - the latest
More informationSECTION PANELBOARDS
SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.
More informationMedium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1
Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear ABB Group February 25, 2015 Slide 1 SafeGear HD arc resistant switchgear 63 ka arc resistant metal-clad air insulated switchgear
More informationC1000 Series Automatic Cap Bank
C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution
More informationSECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed,
More information16.13 Unit Substation to 15kV Construction Standards Page 1 of 7
Construction Standards Page 1 of 7.1 General.1 New buildings are to be provided with an indoor unit substation designed to accept 15kV and 25kV primary voltages, however, the primary voltage connected
More informationSpecification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RMVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope... 3 2.0 Standards... 3 3.0 Supplier Qualifications... 4 4.0 Circuit Breaker
More informationSolid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER
Solid Dielectric Load Break Switch SPECIFICATION 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED VACUUM LOAD INTERRUPTING
More informationOTEC Transfer switch open transition
Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator
More informationSolid Dielectric, Three Phase Reclosers CATALOG VS11
Solid Dielectric, Three Phase Reclosers Providing electronic, three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance
More informationSolid Dielectric, Triple Option Reclosers Catalog O-vlt14
Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical
More informationSERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES
SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT SUBMERSIBLE AND VAULT MOUNTED
More informationDesign Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak
Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak Powergrid Solution s Metal Enclosed Switchgear has many different customizable options and configurations. Customers
More informationSWITCHGEAR DIVISION PRODUCT PROFILES
SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,
More informationSECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT
SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.
More information16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12
16kA Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A continuous current, 16kA symmetrical interrupting
More informationSolid Dielectric, Triple Option Reclosers Catalog O-vlt14
Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical
More informationA. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:
SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification
More informationSafeGear TM Motor Control Center Arc resistant metal-clad construction
SafeGear TM Motor Control Center Arc resistant metal-clad construction Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor
More informationA. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.
16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional
More informationMedium Voltage. ANSI C37.20 and NEMA SG-5
Medium Voltage ANSI C37.20 and NEMA SG-5 ANSI C37.20 and NEMA SG-5 Medium Voltage Metal-Clad Switchgear Medium Voltage ANSI C37.20 and NEMA SG-5 04 General 06 Application Data 08 Features 10 Circuit Compartment
More informationCONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS
LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low
More informationA. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:
SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationMEDIUM-VOLTAGE SWITCHGEAR
REVISION RECORD SECTION 16341 Medium-Voltage Switchgear REV DATE PAGE PARA NO. DESCRIPTION APPROVED BY 28SEP01 ALL Initial issue. 1 29SEP03 ALL General update with miscellaneous changes in entire document.
More informationSpecification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers
Specification Guide for RMAX Direct Replacement AC Low Voltage Power Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards... 3 3.0 Supplier Qualifications... 3 4.0 Mechanical and
More informationMEDIUM VOLTAGE SWITCHGEAR SECTION
PART 1 GENERAL 1.01 Summary A. This specification covers the design and functional requirements for 5 kv medium voltage outdoor sheltered aisle metal-clad switchgear with vacuum circuit breakers. The switchgear
More informationPublication No.: PSG
TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06
More informationGE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc
GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4
More informationSwitchgear. Low Voltage
January 2001 Vol. 1, Ref. No. [0923] -1 Low Voltage Switchgear Contents Description Page Magnum DS Metal-Enclosed Product Description........................................... -2 Application Description........................................
More informationVersaRupter 5-38 kv Load Interrupter Switch. Technical Guide
VersaRupter 5-38 kv Load Interrupter Switch Technical Guide NOTICE Components in this catalog are intended for use by switchgear assemblers engaged in original equipment manufacturing. All sales are subject
More informationCITY OF MARYVILLE ELECRIC DEPARTMENT Maryville, Tennessee SPECIFICATIONS FOR 15KV POWER CIRCUIT BREAKERS. September 2018
CITY OF MARYVILLE ELECRIC DEPARTMENT Maryville, Tennessee SPECIFICATIONS FOR 15KV POWER CIRCUIT BREAKERS September 2018 Myrick Clinton Cannon TN P.E. #112337 Patterson & Dewar Engineers, Inc. P. O. Box
More information.1 Low Voltage Switchgear Magnum DS Switchgear with Molded Case Circuit Breaker Feeder Section Cross-Reference Eaton s Electrical Sector has an organi
Low Voltage Switchgear Magnum DS Switchgear.1 Cross-Reference................................................ 102 Product Description............................................. 102 Application Description...........................................
More information33KV INDOOR SWITCHGEAR
33KV INDOOR SWITCHGEAR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:
More informationwww. ElectricalPartManuals. com Section 13 Switchgear Low Voltage
Switchgear Low Voltage Introduction...13-1 AKD-10 Low-Voltage Switchgear...13-3 AKD-20 Low-Voltage Switchgear...13-3 Low Voltage Switchgear GE low-voltage switchgear is heavy-duty equipment built to ANSI
More informationA. Submittals shall be made in accordance with Division 1, Section
PART 1 - GENERAL 1.01 SCOPE A. The work of this section includes providing a fully enclosed metal-clad 12.47kV switchgear and auxiliary equipment as specified herein and as shown on the contract drawings.
More informationTransfer switch OTEC open or delayed transition
Transfer switch OTEC open or delayed transition 40-1000 Amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and standby generator sets.
More informationSERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES
SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED SWITCHGEAR WITH VACUUM LOAD
More informationFIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z
PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install fixed power factor correction equipment as specified herein and as shown on the contract drawings. This specification
More informationSECTION WIRING DEVICES
SECTION 16140 - WIRING DEVICES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION 16426B. RELATED SECTIONS Section 16671A Transient Voltage Surge Suppression Section Microprocessor-Based Metering Equipment
METAL-ENCLOSED DRAWOUT SWITCHGEAR (DSLII) LOW VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install, where indicated on the drawings, a deadfront type, low voltage metal-enclosed
More information100 / 110 DRYWELL FUSE SPECIFICATION
100 / 110 DRYWELL FUSE SPECIFICATION 15KV & 25KV SUBMERSIBLE VACUUM LOAD INTERRUPTERS AND DRYWELL FUSE ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED SUBMERSIBLE SWITCHGEAR WITH LOAD INTERRUPTING SWITCHES
More informationUBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit
More information