Transformer bushings, type GOA 250. Installation and maintenance guide
|
|
- Dulcie Smith
- 5 years ago
- Views:
Transcription
1 Transformer bushings, type GOA 250 Installation and maintenance guide
2 This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. Contravention will be prosecuted.
3 Safety information Keep this instruction available to those responsible for the installation, maintenance, and operation of the bushing. The installation, operation, and maintenance of a bushing present numerous potential unsafe conditions, including, but not limited to, the following: High pressures Lethal voltages Moving machinery Heavy components Slip, stumble or fall Specialized procedures and instructions are required and must be adhered to when working on such apparatus. Failure to follow the instructions could result in severe personal injury, death, and/or product or property damage. Additionally, all applicable safety procedures such as regional or local safety rules and regulations, safe working practices, and good judgement must be used by the personnel when installing, operating, maintaining and/or disposing such equipment. Safety, as defined in this instruction, involves two conditions: 1. Personal injury or death. 2. Product or property damage (includes damage to the bushing or other property, and reduced bushing life). Safety notations are intended to alert personnel of possible personal injury, death or property damage. They have been inserted in the instructional text prior to the step in which the condition is cited. The safety conditions are headed by one of the three hazard intensity levels which are defined as follows: DANGER Immediate hazard which will result in severe personal injury, death, or property damage. WARNING Hazard or unsafe practice which could result in severe personal injury, death, or property damage. CAUTION: Hazard or unsafe practice which could result in minor personal injury, or property damage.
4 en
5 Contents 1 Description Design Ordering particulars Electrical and technical data 9 2 Installation Transport and handling Lifting from the box Mounting Inner terminal Outer terminal Mounting of draw rod Mounting of outer terminal 11 3 Maintenance 12 4 Disposal after end of service life en 5
6 1 Description 1 Description This information is valid for the revised and improved GOA 250 with catalogue number LF The new bushing is completely interchangeable with the old one, if the upper part of the draw rod will be changed togethter with the bushing. NOTE: The part above the flange is 45 mm longer than for the old design. The table below shows the old and the new catalogue numbers. The old bushing The new bushing Catalogue No. Insulator Catalogue No. Insulator Brown Grey Brown Grey LF A -C LF A -D LF A -C LF B -E LF A -C LF C -F 1.1 Design The design priciple is shown in Fig. 1. The GOA 250 bushing is built up around a centre conductor tube made of electrolytic copper. The capacitance graded body is wound on a separate thin-walled supporting tube. This tube is only connected to the inner current carrying tube at the bottom end. The space between the two tubes makes and efficient cooling duct for dissipation of the heat, thus improving the current carrying capacity of the bushing. The upper insulator, the lower insulator and the mounting flange are held between the end details by the centre tube. A set of springs in the top housing provides adequate pressure on all gaskets, independent of temperature and load conditions. Sealing is accomplished by oil resistant rubber gaskets in grooves. The bushing is filled with insulating oil. The top housing has expansion space for the oil. Variations in the length of the centre tube and the housing are compensated by a flexible top cover. The mounting flange, the top housing and the top cover are made of corrosion resistant aluminium and are protected by painting with two-component primer and a grey-blue finishing coat paint. The standard colour is Munsell 5.5B 55/1.25, environmental class C3. The bushing is intended for mounting up to 45 to the vertical. Due to the high current rating, only the draw rod connection system is available. The centre tube of the bushing is used as the current conductor. The transformer leads are fitted with cable lugs, which are bolted to the inner terminal plate. This plate is drawn against the lower end of the tube by a thin steel draw rod. The bushing is furnished with a test tap according to Fig. 2. The test voltage for the tap is max. 2 kv en
7 1 Description Fig. 1. Design principle. 1. Outer terminal stud 2. Top end nut 3. Flexible cover 4. Oil filling plug, A (Gasket 16 x 8 x 3 nitrile rubber) 5. Prism glass, A 6. Set of springs 7. Top housing 8. Oil 9. Porcelain insulator, air side 10. Test tap 11. Mounting flange 12. Condenser body 13. Flange extension 14. Porcelain insulator, oil side 15. Bottom end nut 16. Inner terminal plate goa_0001 Fig. 2. Test tap A (not self-earthing) 2 1. Bushing for test tap 2. Disc spring 3. Press nut 4. Cover 5. Contact pin, 4 mm 6. O-ring 7. O-ring 8. Cable gob_ en 7
8 1 Description 220 D 140 H goa_0001 Outer terminal assembly L1±2 L2 60 D Earthed layer goa_0004 Draw rod (included) H H1 18 D Inner terminal plate goa_0006 goa_0003 Bushing 1.2 Ordering particulars When ordering, please state: Type and catalogue number for the bushings. Catalogue number for the outer terminal assembly. Catalogue number for the inner terminal plate. Additional accessories or modifications. Test required in addition to the normal routine tests en
9 1 Description 1.3 Electrical and technical data Rated voltage U R Phase-to-earth voltage U Y Dry lightning impulse Wet power frequency Routine test 1 min. dry 50 Hz Design dry switching impulse Rated current IEC Rated current IEEE Creepage distance total Creepage distance protected Max. permitted cantilever load perpendicular to the terminal Corresponding 1 min. test 52 kv, RMS 52 kv, RMS 250 kv, peak 105 kv, RMS 105 kv, RMS 230 kv, peak 2500 A 2200 A 1500 ±50 mm 580 mm 1000 N 2000 N Dimensions and nominal capacitance Catalogue No. Porcelain L1 L2 D Mass C 1 C 2 Brown Grey mm mm mm kg pf pf LF A -D LF B -E LF C -F Outer terminal assembly Catalogue No. D, mm H, mm Material/Surface Mass, kg LF CA Cu 3.0 LF CB Al 2.0 LF CC 2"-12 UN 125 Cu/Sn 3.7 Inner terminal plate Catalogue No. H, mm H1, mm D, mm Mass, kg LF A LF K LF L en 9
10 2 Installation 2 Installation 2.1 Transport and handling CAUTION: The bushing may be transported and stored horizontally up to 6 months. For storing over 6 months it is recommended to raise the bushing to vertical position with the top end upwards. Keep the bushings dry and clean and protected against mechanical damage. Keep the bushings protected from penetrating water when stored outdoors. This means that the case must not be stored in areas where it can be foreseen that the ground will be wet and muddy during heavy rains. Shelter the case from rain and snow with a tarpaulin or roofing. Carefully inspect the bushing on receiving with regard to shipping damage. Please note that the bushing has been routine tested in oil and some oil may be left, especially in the narrow openings between porcelain and metal. Vaseline is used for lubrications of threads, and at some temperatures the vaseline may appear as oil The bushings are normally delivered from ABB Components in boxes with the bushing supported by blocks and fibre boards. The boxes are marked with "Top End". 2.2 Lifting from the box WARNING For lifting the bushing from the box, apply lifting slings or ropes around the the air side insulator under the top housing. 2.3 Mounting The oil end of the bushing and the inside of the centre tube shall be carefully cleaned and inspected Inner terminal The connection of the bushing to the transformer or reactor is made by means of a draw rod. The draw rod bottom plate is made of copper Outer terminal The outer terminal is made of copper or aluminium en
11 2 Installation 2.4 Mounting of draw rod At the upper end, the rod passes through a spring device. The rod is fixed by a nut on the cover of the spring device. At mounting the spring device shall be tightened until the cover is at the same level as the upper end of the conductor tube. See Fig Mounting of outer terminal CAUTION: Before connection of conductor clamps, the outer terminals of aluminium must be carefully wire brushed and greased with a contact compound or vaseline. The inner contact surface on aluminium outer terminals are tin-zink plated, and wire brushing must thus not be carried out. In order to obtain the correct pressure and a low contact resistance, the following must be carried out: 1. Clean the contact and gasket surfaces carefully. 2. Lubricate the O-ring with Mobilgrease Assemble the retainer ring, the O-ring, and the outer terminal stud and push them over the inner terminal. An extra O-ring intended for final installation is delivered with the bushing. 4. Grease all bolts on thread and underneath the head with Molykote 1000, or other suitable compound. 5. Insert and tighten the screws M10, with plane washer, which press the stud against the top end of the bushing. Tighten stepwise to a final torque of 40±4 Nm. 6. Insert the M8 screws, with conical spring washer and plane washer, which hold the tightening ring. Tighten the screws alternately to a final torque of 20 ±2 Nm to obtain the necessary gasket pressure. CAUTION: It is extremely important in both cases to tighten evenly. The bolts shall thus be tightened in steps, alternately on both sides en 11
12 3 Maintenance Hole for fastening of the pull-through cord The nut shall be tightened until the plate is at the same level as the upper end of the tube. Tightening torque approx. 40 Nm Tightening torque approx. 20 Nm. Fig. 3. Connection of bushing. 1. Hexagon screw M8 x Conical spring washer 8.4 x 18 x 1 3. Gasket (O-ring) 49.2 x Tightening ring for gasket 5. Top end of bushing 6. Hexagon screw M10 x Washer 10.5 x 20 x 2 8. Inner terminal plate 8 goa_ Maintenance The GOA bushings are maintenance-free. It is, however, recommended that the oil level is checked at normal routine inspection. Correct oil level for a vertical bushing is at the middle of the prism glass for 20 C. The change of the oil level is approx. 1.5 mm for 10 C change of the temperature. Adjustment of the oil level is carried out by opening the filling plug. Then drain or fill up with pure new dry transformer oil. For remounting of the sealing plug a new gasket may be used. Adjustment of the oil level is allowed only when the temperature of the bushing is between +5 C and +35 C en
13 4 Disposal after end of service life 4 Disposal after end of service life The bushing consists of the following material: - Centre tube of copper. - Terminals of copper, brass or low-alloy aluminium may be plated with for instance silver, tin, gold or nickel in layer thickness up to 20 µm. - Transformer oil as per IEC 296, class 2. - Transformer oil impregnated condenser body consists of paper and 1 % Al foils. - Supporting tube, on which the condenser body is wound, consists of brass. - Top cover, top housing, flange, top nut and flange extension consist of Al alloys. - Press ring for oil level glass consist of plated brass. Test tap consists of stainless steel. - Prism glass consists of glass. - Insulators consist of quartz or alumino silicated based porcelain en 13
14 ABB Power Technology Products AB Components Visiting address: Lyviksvägen 10 Postal address: SE Ludvika, SWEDEN Tel Fax en,
HVDC bushing without oil side porcelain Type GOF, for outdoor mounting. Installation and maintenance guide
HVDC bushing without oil side porcelain Type GOF, for outdoor mounting Installation and maintenance guide This document must not be copied without our written permission, and the contents thereof must
More informationen, Rev. 7. Transformer bushings, type GOM Installation and maintenance guide
2750 515-41 en, Rev. 7 Transformer bushings, type GOM Installation and maintenance guide Original instruction The information provided in this document is intended to be general and does not cover all
More information1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide
1ZSE 2750-102 en, Rev. 9 Transformer bushings, type GOB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More information1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide
1ZSE 2750-112 en, Rev. 3 Wall bushings, type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationTransformer bushings, type GOH. Technical guide
Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required
More information1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide
1ZSE 2750-102 en, Rev. 7 Transformer bushings, type GOB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical
More information1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide
1ZSE 2750-106 EN, REV. 7 Oil SF 6 bushings type GOEK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More information1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide
1ZSE 2750-112 EN, REV. 4 Wall bushings type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationen, Rev. 10. Transformer bushings, type GOH Installation and maintenance guide
2750 515-85 en, Rev. 10 Transformer bushings, type GOH Installation and maintenance guide Original instruction The information provided in this document is intended to be general and does not cover all
More informationResin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide
1ZSC000563-AAC en, Rev. 2 Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,
More information1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide
1ZSC563-AAA en, Rev. 6 Resin impregnated paper bushing, oil to SF 6, type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover
More information1ZSE en, Rev. 9. Transformer bushings, type GSA-OA Technical guide
1ZSE 2750-111 en, Rev. 9 Transformer bushings, type GSA-OA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationProduct Information. Neutral Wall Bushing GOFL
ABB Components Info-No. 2750 515-93en, Rev. 1 From / Date Product Information Neutral Wall Bushing GOFL Description Page Design 2 Voltage tap 2 Dimensions 2 Terminals 2 Mounting instruction Packing 4 Storing
More informationTransformer bushings, type GSA-OA Technical guide
Transformer bushings, type GSA-OA Technical guide ZSE 2750- en, Rev. 5, 2005-05-5 This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to
More informationResin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK
1ZSC563-AAA en, Rev. 2 Resin Impregnated Paper Bushing, Oil to SF 6, Type GSBK Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,
More informationBushings for High Voltage AC Applications
Bushings for High Voltage AC Applications Selection guide 1ZSE 2750-100 en, Rev. 3, 2006-03-15 During selection of for high voltage applications several important factors have to be considered to ensure
More information1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide
1ZSC563-AAA EN, REV. 7 Transformer bushings type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More information1ZSC ABE en, Rev. 1. HVDC bushing, type GSD Installation and maintenance guide
1ZSC000563-ABE en, Rev. 1 HVDC bushing, type GSD Installation and maintenance guide Original instruction The information provided in this document is intended to be general and does not cover all possible
More information1ZSC ABJ EN, REV. 1. Gas insulated wall bushings type GGFL Technical guide
1ZSC000563-ABJ EN, REV. 1 Gas insulated wall bushings type GGFL Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
More informationOn-load tap-changers, types UCG, UCL, UCC and UCD with motor-drive mechanisms, types BUE and BUL Spare Parts List
On-load tap-changers, types UCG, UCL, UCC and UCD with motor-drive mechanisms, types BUE and BUL Spare Parts List ZSE 5492-33 en, Rev. 3, 2004-04-5 This document must not be copied without our written
More informationen, Transformer bushing, type GSA-OA Installation and maintenance guide...
Transformer bushing, type GSA-OA Installation and maintenance guide... The information contained in this document may be subject to change without prior warning and should not be considered as binding
More information1ZSC AAX EN, Transformer bushing, type GSC Installation and maintenance guide
1ZSC000563-AAX EN, 2018-01-16 Transformer bushing, type GSC Installation and maintenance guide The information contained in this document may be subject to change without prior warning and should not be
More informationdfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide
dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide Table of contents 1 Introduction... 3 1.1 Style Number... 3 1.1.1 Style Number Examples... 3 2 Basic Characteristics... 4 2.1
More informationTransformer Bushing Type EKTO
Transformer Bushing Type EKTO Mounting Operating and Maintenance Instructions Operating Instructions BAL EKTO/04e Visum 01/14 T/gue Page 1 of 16 SAFETY INSTRUCTIONS These instructions are valid for mounting,
More information1ZSC ABH en, Rev. 1. Motor-drive mechanisms, types BUE and BUL2 Maintenance guide
1ZSC000498-ABH en, Rev. 1 Motor-drive mechanisms, types BUE and BUL2 Maintenance guide Original instruction The information provided in this document is intended to be general and does not cover all possible
More informationBUSHINGS: GENERAL INFORMATION
BUSHINGS: GENERAL INFORMATION 1.0 Electrical characteristics (Ir = rated current; Ur = rated voltage) 1.1Standard insulation levels Rated voltage Ur kv (r.m.s.) 1 3,6 12 24 36 52 One minute power frequency
More informationCondenser Bushings. OIL-TO-AIR - Oil-Impregnated Paper ANSI STANDARDS IEEE C AND IEEE C AN ALSTOM COMPANY
PAO Condenser Bushings - kv BUSHINGS OI-TO-AIR - Oil-Impregnated Paper ANSI STANDARDS IEEE C.9.0-000 AND IEEE C.9.0-99 AN ASTOM COMPANY PAO bushings are capacitance-graded bushings with an oil-impregnated
More informationOIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC
OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) 1800 24kV to 550kV up to 5000A IEC 60137-2008 Features If you need any transformer bushing proven in operation conditions around the world, Trench
More informationBushing Insulators according to DIN and UNEL Standards
Bushing Insulators according to DIN and UNEL Standards Description and general specifications Outdoor transformer bushing DIN 42532 and UNEL 38159/74 rated current 630A Bushing EN 50180 12-24-36/630-1250-2000-3150
More informationPNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper
GE Grid Solutions PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper PNO bushings are capacitance graded bushings with an oil impregnated paper core. PNO bushings are conform
More informationMotor-drive mechanism, type BUL. Technical guide
Motor-drive mechanism, type BUL Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required
More information1ZSE en, Rev. 4. On-load tap-changers, type UC User s manual
1ZSE 5492-155 en, Rev. 4 On-load tap-changers, type UC User s manual Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationTransformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC
Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC 60137-2008 High current bushings for transformer Features Bushing Type CFPT version Porcelain Insulator Trench RIG technology for
More informationPABS. AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS ANSI STANDARDS AN ALSTOM COMPANY
PABS Air-to-SF 6 Bushings 7.5-800 kv BUSHINGS AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS 7 - ANSI STANDARDS AN ALSTOM COMPANY PABS bushings are gas-insulated types that meet IEC 7, ANSI/IEEE or
More informationOIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC
OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) 1800 24kV to 550kV up to 5000A IEC 60137-2008 Features If you need any transformer bushing proven in operation conditions around the world, Trench
More informationProduct presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st New RIS transformer bushings The paper-free solution
Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 New RIS transformer bushings The paper-free solution Transformer condenser bushings Why a new technology? To preserve
More informationTransformer Bushing Type EKTG
Transformer Bushing Type EKTG Mounting Operating and Maintenance Instructions Operation Instructions BAL EKTG/05e Visum 01/14 T/gue Page 1 of 18 SAFETY INSTRUCTIONS These instructions are valid for mounting,
More informationDM Condenser bushings, kV DURESCA
DM Condenser bushings, 36 DURESCA Through wall bushings for indoor and outdoor applications, Resin Impregnated Paper IEC 601378 and IEEE C57.19.01.004 DURESCA Wall bushings Swiss quality combined with
More informationSERIES TAP-CHANGER
SERIES 090 - TAP-CHANGER Main characteristics This is an off-circuit tap changer. It means DO NOT OPERATE WHILE THE TRANSFORMER IS ENERGISED. Main characteristics of this tap-changer series are: dimensional
More informationCurrent transformers. Outdoor operation SF 6 -gas insulated. JGF ( ) kv
Current transformers Outdoor operation SF 6 -gas insulated JGF (245 550) kv General description Current transformers type JGF are used in high voltage switchgear within the 245 550 kv range. They transform
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation Oil-paper insulated EOF (24 245) kv General description Voltage transformers type EOF are used in high voltage networks within the 24 245 kv range. They
More informationINSTRUCTION MANUAL CRS Combined insulation bushing
INSTRUCTION MANUAL CRS Combined insulation bushing 5COH020200 CRS REV03 2 TABLE OF CONTENTS 1 SAFETY... 5 1.1 SAFETY INSTRUCTION... 5 1.2 SPECIFIED APPLICATION... 5 1.3 SAFETY NOTES ON THE EQUIPMENT OPERATION...
More informationHigh Voltage Surge Arresters Buyer s Guide Section PEXLIM R
High Voltage Surge Arresters Buyer s Guide Section PEXLIM R Zinc Oxide Surge Arrester PEXLIM R Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching
More informationINSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00
INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR469100 BR25AT REV00 I CONTENT: 1 SAFETY 1.1 Safety instructions 1 1.2 Specified applications 1 1.3 Safety notes on the equipment operation 1 2 BR 25
More informationMicafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB
Micafil transformer oil-sf 6 bushings GARIP / RTKG 72.5 55 kv Power and productivity for a better world TM ABB Design and accessories The design of the main RIP insulating body includes a solid, non-removable
More informationINSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03
INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR469000 OR25 REV03 I II CONTENT: 1 SAFETY 1.1 Safety instructions 2 1.2 Specified applications 2 1.3 Safety notes on the equipment
More informationMedium voltage products. KEVCD A combined current and voltage sensor Instructions for installation, use and maintenance
Medium voltage products KEVCD A combined current and voltage sensor Instructions for installation, use and maintenance Instructions for installation, use and maintenance for the KEVCD A combined current
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation Oil-paper insulated EOF (24 245) kv General description Voltage transformers type EOF are used in high voltage networks within the 24 245 kv range. They
More informationType DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003
Type DTU De-energized Tap Changer Application, Installation & Selection Guide IL 44-750-1A Page 1 September, 2003 Page 2 September, 2003 Scope This leaflet contains general information about ordering and
More informationTransformer Bushings Type. STARIP / STARIP -Si. Mounting Operating and Maintenance Instructions
Transformer Bushings Type STARIP / STARIP -Si Mounting Operating and Maintenance Instructions Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 1 of 17 SAFETY INSTRUCTIONS These instructions
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation SF 6 -gas insulated EGF (245 550) kv General description Voltage transformers type EGF are used in high voltage substations within the 245 550 kv range.
More informationINTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.
INTRODUCTION The Power Systems 44 kv MiniSub TM is the most compact system at this voltage available. Utilizing a deadfront termination and lightning arrestor setup, it eliminates the line top or side
More informationInstallation Manual Bushings, IEEE/ANSI Standard
Installation Manual Bushings, IEEE/ANSI Standard Type COTA 150.2050 for Transformers Type COBA for OCB Bushing Replacement E 8322.72 2007 Contents Page 1. Introduction 3 2. Scope 3 3. Construction 3-5
More informationCombined instrument transformers
Combined instrument transformers Outdoor operation Oil-paper insulated EJOF (24 170) kv General description Combined instrument transformers type EJOF are used in high voltage networks within the 24 170
More informationINTERFACE E - 5/8" MEDIUM VOLTAGE SEPARABLE CONNECTORS AND BUSHINGS CATALOGUE 2017
INTERFACE E - 5/8" MEDIUM VOLTAGE SEPARABLE CONNECTORS AND BUSHINGS CATALOGUE 2017 NEXANS NETWORK SOLUTIONS DIV. EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer,
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation Oil-paper insulated EOF (24 245) kv General description Voltage transformers type EOF are used in high voltage networks within the 24 245 kv range. They
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation Oil-paper insulated EOF (24 245) kv General description Voltage transformers type EOF are used in high voltage networks within the 24 245 kv range. They
More information1ZVN A. Application manual
1ZVN460100 A Application manual 1ZVN460100 A 2 / 3 Table of contents 1 Rating Plate... 2 Tapchanger... 3 Bushing... 4 Cooling Equiptment... 5 Current Transformer... 6 Other Acessories... 7 Drawings...
More informationOIL-TO-OIL BUSHINGS SERIES PCTO SINGLE FLANGE TYPE VOLTAGE FROM 72,5 kv TO 420 kv
Page 1 of 14 OIL-TO-OIL BUSHINGS SERIES PCTO SINGLE FLANGE TYPE VOLTAGE FROM 72,5 kv TO 420 kv STORAGE, OPERATING AND MAINTENANCE INSTRUCTIONS Page 2 of 14 INDEX 1. DESCRIPTION...3 1.1 GENERAL...3 1.2
More informationMICAFIL RIP Transformer Bushings AirRIP / RTKF kv
INSULATION AND COMPONENTS MICAFIL RIP Transformer Bushings AirRIP / RTKF kv MICAFIL AirRIP bushings offer an extended service life combined with enhanced reliability and safety to ensure the maximum availability
More informationCombined instrument transformers
Combined instrument transformers Outdoor operation SF 6 -gas insulated EJGF (245 550) kv General description Type EJGF combined transformers are used in high-voltage substations within the 245 550 kv range.
More information023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA
023 : 2006 CEB STANDARD 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA Specification for 12kV & 36kV LOAD BREAK SWITCHES CEB Standard 023 : 2006 CEYLON ELECTRICITY BOARD No. 50, Sir
More informationBus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:
4 (Four) Pole Monoblock: Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers: Designed and manufactured in accordance with EN 50336:2002 and BS 2562: 1979 1 Introduction:
More informationpower cable accessories
power cable accessories kv up to 4 kv Completing the picture based on experience is the future nkt cables GmbH NKT was established in 89 as cable manufacturer. In 999 NKT A/S Denmark merged with Felten
More informationTEKNISK RIKTLINJE TR05-10E
Notes Change notes Date 1 (A) Revision of standards and new template 09 / 07 2010 2 Template changed.clause. 10.5.1.4 support clamp inserted. Clause 10.5.4.2 creepage text revised. Clause 10.6.7 Dry inserted
More informationTypical Specification
Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,
More informationAustin Insulators Inc. Manufacturers of Austin Base & Guy Insulators and Isolation Transformers for Radio Antenna Towers.
Austin Insulators Inc. Manufacturers of Austin Base & Guy Insulators and Isolation Transformers for Radio Antenna Towers Product Catalogue e&oe 05.11.01.a Austin Insulators Inc. Austin Ring Type Isolation
More informationOTCF. Grid Solutions. Capacitor Voltage Transformers 72.5 kv to 800 kv. Quality Product Design. Seismic Withstand Capability.
GE Grid Solutions OTCF Capacitor Voltage Transformers 72.5 kv to 800 kv In high and extra high voltage transmission systems, capacitor voltage transformers (CVTs) are used to provide potential outputs
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation SF 6 -gas insulated EGF (245 550) kv General description Voltage transformers type EGF are used in high voltage substations within the 245 550 kv range.
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation SF 6 -gas insulated EGF (245 550) kv General description Voltage transformers type EGF are used in high voltage substations within the 245 550 kv range.
More informationInstruction Manual for POC Bushings
1. Scope This instruction contains general procedures to be followed during receiving, installation, storage and maintenance of all PCORE POC bushings. This instruction does not cover all contingencies
More information(K),(M)430TB/G Up to 36 kv
IS90722-ENG - 430TB/G-45 25 June 2009 - Revision 8A - Supersedes edition of 25 November 2008 Page 1 of 10 CAUTION : Read instructions thoroughly and completely prior to beginning installation. Installation
More informationB kv Gas-insulated Substations
72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.
More informationZinc-Oxide Surge Arrester TEXLIM Q-C
Zinc-Oxide Surge Arrester TEXLIM Q-C Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching overs. in areas with very high lightning intensity where
More informationACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE
ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE hvgrid-tech designs and manufactures high voltage cable accessories for all types of cable systems, ranging from 69 kv to
More informationGuide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break
Part 1-GENERAL 1.1 DESCRIPTION Guide Specification Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break The switchgear shall consist of magnetically actuated solid dielectric insulated
More informationElectrobar Elite. Instruction Manual. Conductor Bar System. ELITE-03A October 2011 Part Number: R3 Copyright 2011 Electromotive Systems
Electrobar Elite Conductor Bar System Instruction Manual ELITE-03A October 2011 Part Number: 005-1054-R3 Copyright 2011 Electromotive Systems 2011 MAGNETEK All rights reserved. This notice applies to
More informationType HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv
Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv HS PEXLIM-P Metal Oxide Surge Arrester HS PEXLIM-P Surge Arresters are used for the protection of switchgear, transformers and other
More information25 kv Apparatus Bushings
Page 1 2001 ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric strength, dielectric loss and power factor Choice of shapes allows design innovation
More informationA of 14. Edition : Date : Page : Document No. Amendments :
&RQWHQWV,QVWUXFWLRQVIRU(UHFWLRQ 2SHUDWLRQ 2XWGRRU7UDQVIRUPHU%XVKLQJ 57.)N9.6,7 6HULHV&25,3 +/$%( Document No. Edition : Date : Page : Amendments : A 29.11.02 1 of 14 *(1(5$/'(6,*1 3$&.,1* %XVKLQJ6XSSO\&RQGLWLRQV
More informationIL Instruction Leaflet Page 1 November,2001. Type DTW De-energized Tap Changer Application, Installation & Selection Guide
Page 1 November,2001 Type DTW De-energized Tap Changer Application, Installation & Selection Guide Page 2 November, 2001 Scope This guide contains general information for ordering and installing the type
More information43-SDMS-01 SPECIFICATIONS FOR
SPECIFICATIONS FOR MV SHUNT POWER CAPACITOR BANK UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Description Page 1.0 SCOPE 3
More informationPIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution
Medium Voltage Distribution PIX Withdrawable Voltage Transformer Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual Nr. Edition 11/2011 www.schneider-electric.com Schneider
More informationa Nexans company Catalogue 2007
a Nexans company Catalogue 2007 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium
More informationZinc Oxide Surge Arrester EXLIM R
Zinc Oxide Surge Arrester EXLIM R Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching overs. For use when requirements of lightning intensity, energy
More informationWESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO. GUARANTEED TECHNICAL PARTICULARS 1 of 2
Sl. No. WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO GUARANTEED TECHNICAL PARTICULARS 1 of 2 REQUIREMENTS 11 Kv, 200 Amps, A.B Switches. Particulars 1 Maker's name and Country of origin. 2 Type
More informationFIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z
PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install fixed power factor correction equipment as specified herein and as shown on the contract drawings. This specification
More informationLV Capacitor CLMD03 Power Module Instruction manual
LV Capacitor CLMD03 Power Module Instruction manual Table of Contents 1 Safety... 3 2 Upon reception... 3 2.1 Inspection on reception... 3 2.2 Storage- transportation handling... 3 3 Hardware Description...
More information25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp
Page 1 2018 Grounded Metal Equipment Plate Equipment Connection 15 kv or 25 kv Separable Insulated Connector (elbow) Grounded Metal Equipment Plate Equipment Connection Power Cable Power Cable ELRIM Cycloaliphatic
More information(K),(M),(P)489TB/G Up to 42 kv
IS91374-ENG - 489TB/G-45/S 22 October 2012 - Revision 1 - Supersedes edition of 4 May 2012 Page 1 of 9 CAUTION : Read instructions thoroughly and completely prior to beginning installation. Installation
More informationCOOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN
Deadbreak Apparatus Connectors MN650048EN Effective May 2017 Supersedes April 2008 (S600-12-3) 600 A 15/25 kv class T-OP II connector assembly installation instructions COOPER POWER SERIES DISCLAIMER OF
More informationCable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples.
Transportation and storage.. 3 General. 3 Unpacking at installation site....... 3 Transfer of cubicles at installation site... 3 Weight.. 4 Temporary storage. 4 Erection at site 5 General. 5 The switchgear
More informationB kv T&D GAS INSULATED SWITCHGEAR
GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission
More informationPORCELAIN BUSHINGS ED Series
PORCELAIN BUSHINGS ED Series An innovative design: the most popular and most reliable 1 kv bushing on the market www.cedaspe.com LV BUSHINGS ED by CEDASPE CEDASPE is happy to present a complete new family
More informationABB SpA COMEM Operating Unit Power Grids Division Strada Regionale 11, Signolo Montebello Vicentino (VI) - ITALY
ABB SpA COMEM Operating Unit Power Grids Division Strada Regionale 11, Signolo 22 36054 Montebello Vicentino (VI) - ITALY www.abb.com/transformercomponents The information contained in this document is
More informationELB ELB
ELB-35-600 ELB-35-610 600A T-Body Elbow Connectors for Copper Tape (CT), Jacketed Concentric Neutral (JCN), and Concentric Neutral (CN) cables up to 35kV class Safety Instructions When installing electrical
More information15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch
Page 1 2015 Kinked roof prevents standing moisture Glass reinforced barriers meet NEMA GPO-3 Standards 0.625" diameter copper ground bar Elliott air-insulated bushings accept IEEE Standard inserts and
More informationMODVAR Low voltage reactive power compensation modules Installation manual
MODVAR Low voltage reactive power compensation modules Installation manual MODVAR Low voltage reactive power compensation modules Before installation, read this manual carefully and keep at the disposal
More information43-SDMS-04 REV. 00 SPECIFICATIONS FOR
43-SDMS-04 REV. 00 SPECIFICATIONS FOR SHUNT CAPACITOR BANK 13.8 kv THROUGH 69 kv FOR PRIMARY DISTRIBUTION SUBSTATIONS This specification is property of SEC and subject to change or modification without
More information