Instructions for the BASIC BCVA Rotary heat exchanger, Sizes
|
|
- Leslie Long
- 5 years ago
- Views:
Transcription
1 Instructions for the BASIC BCVA Rotary heat exchanger, Sizes General The BCVA heat recovery unit is a rotary heat exchanger that offers high temperature efficiency. The heat exchanger operates with an efficiency of up to 82% on equal supply and exhaust flows. The efficiency is regulated by varying the rpm of the rotor. The BCVA can be supplied with a drive motor for constant speed, or a drive motor with speed control. The BCVA operates with horizontal flow. 1.1 Specification The version, size, etc. are specified in the delivery documents. 2. Installation 2.1 Mounting The BCVA heat exchangers are supplied with base beams as standard. It is important that the heat exchanger be positioned according to the labels on the side of its casing before it is connected to a duct or functional sections. The labels indicate the supply, exhaust, warm and cold sides. 2.2 Where to locate the filters The filters should preferably be located upstream of the rotor in the supply and the exhaust. If the exhaust fan is located at the pressure side of the rotor, a filter should be located upstream of the fan. 2.3 Inspection Always provide sufficient means for reaching the rotor for inspection and service from all four connections. If access cannot be gained from an adjacent functional section, a BCIA inspection section should be installed for this purpose. 2.4 Purging sector The BCVA heat exchanger is supplied with an adjustable purging sector as standard. On delivery, the sector is preset at max. and should be adjusted to the appropriate angle determined by the pressure differential across P 1 P 3 (see adjacent figure). The angle can be read from Table 1. If P 3 is greater than P 1, the purging sector should be omitted and a permanent cover plate should be fitted instead. This condition arises e.g. if the exhaust fan is upstream and the supply fan is downstream of the rotor. On placing an order with Swegon, specify if the purging sector is to be omitted The flow through a correctly adjusted purging sector is specified in Table 2. Exhaust Supplay Table 1 Pressure Angle differential, ( ) P 1 P 3 (Pa) Purging sector BCVA Table 2 BCVA Air flow through purging sector, (m 3 /s) Extract Outdoor Specifications are subject to alteration without notice. 1
2 2.5 Installation example - + Supply Exhaust 2.6 Commissioning Direction of rotation Before starting the heat exchanger, slip off its drive belt and run the motor briefly to check that it is rotating in the direction indicated by the arrow on the casing. If it is rotating in the wrong direction, move lead 2A to 2B or vice versa. Then check the operating current of the motor. All phases must be measured and checked against the data sheet Speed control With the rotor running at constant speed, the supply temperature cannot be kept constant at the preset value. On a rise in outdoor temperature, the indoor temperature can easily become too high. To restrict this undesirable temperature rise, the heat exchanger should be equipped with a speed controller. The efficiency of the heat exchanger varies with changes in the rotor speed. Varying the efficiency will keep the supply temperature constant at the preset value. If the indoor temperature is lower than the outdoor temperature, due to cooling for instance, running the rotor at full rpm will transfer cooling energy from the exhaust to the supply. The controller variably regulates the rotor speed between approx rpm to rpm depending on the size of heat exchanger. The cubicle containing logic equipment for speed control, purging operation, etc. is mounted on the drive motor Rotor in operation Make sure that the heat exchanger is running before the exhaust fan is started. Otherwise, dust is likely to collect in the passages of the rotor and clog them. 3. Maintenance 3.1 Cleaning Inspect the heat exchanger at least every six months and clean if necessary. Clean only by vacuum-cleaning with a soft nozzle or blowing with compressed. If more thorough cleaning is needed, get in touch with Swegon Service. The rotor bearings are maintenance-free. 3.2 Bristled seal While cleaning, check that there is no play between the rotor and the bristled seal. If the seal is worn, it should be replaced. If the bristled seal of the rotor has been removed and is to be reused, it is important that you refit it with the bristles leaning toward the direction of rotation. With use, the bristles namely bend toward the direction of rotation and later cannot be straightened. After you have replaced or adjusted the rotor seal, the heat exchanger should be run for 30 minutes to allow the seal to adapt to the rotor surface. Then measure the current consumed by the drive motor while it is operating and compare this figure with the rated current to make sure that the rotor is not running sluggishly. The max. permissible operating current is 80% of the rated current. An instrument that measures True RMS should be used. 4. Technical data 4.1 Operating principle The BCVA contains four rotors arranged diagonally in ps (as shown in the illustration below). EXTRACT AIR AVLUFT Viewed from above OUTDOOR UTELUFTAIR UTELUFT OUTDOOR AIR EXHAUST FRÅNLUFT AIR S U P P LY TILLUFT AIR Viewed from the side AVLUFT EXTRACT AIR UTELUFT OUTDOOR AIR FRÅNLUFT EXHAUST AIR TILLUFT S U P P LY AIR 2 Specifications are subject to alteration without notice.
3 4.2 Motor data Single phase, 220 V, 50 Hz Constant speed/variable speed control Number of Rated output Current A at Konden- BCVA motors per per motor rated output ser (W) 230 V unit µf Dimensions 75 A G 900 C E F O M L B BCVA A B C E F G L M O Wgt Baase beams: Standard Specifications are subject to alteration without notice. 3
4 Speed Control of the BCVA Rotary Heat Exchanger Motor. Variable Speed Control, Part No NB! There are 4. General The speed controller is mounted in a plastic enclosure with factoryfitted grommets for the various cables and a transparent cover. The controller is designed for installation inside the rotary heat exchanger casing and for operating a heat exchanger motor of Japan Servo manufacture, with tacho-generator. Output range: 25 70W. The controller variably regulates the speed of the heat exchanger motor between 70 and 1400 rpm. The standard transmission ratio will enable a rotor speed range from approx rpm to rpm depending on the size of heat exchanger. Performance is controlled by switching in and out of the "stand-by mode" and a control signal. The controller regulates the motor rpm in a capacity-linear manner in proportion to the input signal. Thus the speed change, per volt of signal change, will be slight for input signals less than 50% and great for those more than 50%. A rotation monitor and a purging operation function are incorporated into the controller. Alarms are indicated by a red LED and group alarms are initiated by means of alternating potential-free contact. Electrical installation (See the diagram below.) Power supply cable: 3 x 1.5, voltage: 230 V +/-10%, 50/60Hz. Control cable from the logic equipment cubicle for: Stand-by mode from potential-free contacts. Control signal: 0 10 V DC, 2 10 V DC, 0 20 ma or 4 20 ma for speed control. Group alarm function output, if specified. Separate alarm cable, if specified. The motor cable and rotation monitor sensor cable are factoryconnected if the controller is supplied with the heat exchanger. LON network cable, if specified. If the controller is to be connected to a master system across LONWorks, it must be ordered with the LON accessory. Setting The only setting that need be made is selecting the type of control signal. This can be set by means of the dip switch (see figure to the right) on the circuit board. 1 0 ON V DC V DC ma ma 1 1 Functions Stand-by mode: Closure between terminals 16 and 17 puts the controller on stand-by. The motor will start when the control signal exceeds 10%. Beyond that point, the speed will variably follow the control signal in a capacity-linear manner up to max. motor rpm. Start function: On closure of the stand-by mode contacts, the heat exchanger will operate at max. rpm for one minute and then adjust itself to the speed called for by the control signal. The start function will switch in regardless of whether or not a control signal is present. The purpose of this function is to counteract any shocking chill when the handling unit is started up. Control signal: The speed of the heat exchanger motor is controlled in a capacity-linear manner between min. and max speeds ( rpm). If the control signal is less than 10% of the max. input signal, the exchanger motor will not start. If the signal is at 10%, the motor will run at min. rpm. On a control signal of 100%, the motor will run at max. rpm. Purging operation: If the controller has been in the stand-by mode for 4 hours and during that time the control signal has not exceeded the 10% limit, the heat exchanger will start up and run at max. rpm for 1 minute to purge the rotor and rid its passages of contaminants. Rotation monitor: The rotation monitor sensor transmits an impulse to the controller every time the magnet on the heat exchanger rotor passes it. If the sensor has not sensed any impulse within 4 minutes while the control signal is above 10%, the heat exchanger motor will stop and the rotation monitor alarm will trip. Tacho-monitor: The controller senses the rpm of the heat exchanger rotor across the input from the tacho-generator mounted on the motor. If no impulses are obtained 10 seconds after the output voltage has reached max., the heat exchanger motor will stop and the tacho-monitor alarm will trip. To check the purging operation function: The purging operation function is similar to the start function; only the conditions required for start differ. The four-hour period cannot be overridden. Test the function by first switching of the stand-by mode and then switching it back on. 4 Specifications are subject to alteration without notice.
5 Alarms Rotation monitor: The alarm will trip after 4 minutes if no pulse has been received from the rotation monitor sensor during this period even though the control signal exceeds10%. The red LED (LD3) steadily shines and the yellow LED (LD4) flashes. The alarm relay is closed between terminals 9 and 11. Tacho-monitor: The alarm will trip if no pulse has been obtained from the tacho-generator 10 seconds after the output voltage has reached max. The red LED (LD3) steadily shines and the yellow LED (LD4) is off. The alarm relay is closed between terminals 9 and 11. LON-monitor: is active only if the LON-communication accessory is fitted. The red LED (LD3) steadily shines and the yellow LED (LD4) steadily shines. The alarm relay is closed between terminals 9 and 11. Power failure: None of the LEDs are lit. The alarm relay is closed between terminals 9 and 11. To reset the alarms The alarms can be reset by switching off the stand-by mode or power supply and then switching it back on. If the LON is connected, resetting can be done across the LON network. The LEDs Yellow LED: LD1. Is lit if the service pin for the LON has been activated. Used only if the LON-communication accessory is fitted. Green LED: LD2. Steadily shines while the controller is on standby. Closure between terminals 16 and 17. Red LED: LD3. Steadily shines if any alarm has tripped. Red LED in combination with yellow LED (LD4) indicates which alarm has tripped. Rotation monitor alarm: Red LED steadily shines yellow LED flashes. Tacho-monitor alarm: Red LED steadily shines yellow LED is off. LON alarm: Red LED steadily shines yellow LED steadily shines. Yellow LED: LD4. Steadily shines if the input signal is greater than 10% and the heat exchanger motor is to rotate. The LED will blink off 1 second and on, every time the magnet on the rotor passes the rotation monitor sensor. A yellow LED in combination with a red LED (LD3) indicates which alarm has tripped. Technical data Mains power supply V +/- 10%, 50/60 Hz Power supply fuse.... Min. 2AT, max. 10 AT Ambient temperature j C through +50 C Enclosure dimensions... W x H x D = 230 x 80 x 65 mm Degree of protection... IP 54 Alarm relay... Max. 250 V AC, 2 AT Fuse at motor output... Fine wire fuse 20 x 5 mm, 2 AT Rotation monitor sensor... Part. no Speed Control of the BCVA Rotary Heat Exchanger Motor Constant Speed, part no NB! There are 4. General The speed controller is located in a cubicle in the casing of the heat exchanger. The controller has a built-in thermostat that switches the rotary heat exchanger in and out. The temperature is registered in the outdoor intake section of the unit. The controller can be switched on standby and off by means of external, potential-free contact. It has a built-in rotation monitor and purging function. Group alarm output via alternating, potential-free contact. Electrical wiring (See the figure to right and below.) The terminal block is of spring-action type without any tightening screw. Connect to a 230 V AC ±10%, 50 Hz power supply. Connect the control cable from the logic equipment cubicle for: standby from potential-free contact, output group alarm function. Motor cable, sensor cable for the speed monitor and the temperature sensor cable are factory-wired. black red* brown t blue grey M grey yellow/green Supply 230V AC Setting Potentiometer P1 can be set for switching off the heat exchanger at the desired temperature. Factory setting:15 C. Potentiometer P2 can be set to the appropriate switch-on and switch-off differential. Factory setting: 0.25 C. Summary alarm *) By wrong rotation direction, shift red and blue wire brown blue Rotating guard sensor RR-G3 Start/Stopp temp. 0±30 0±90 C C P1 Drift Stopp Stop Temp.sensor P2 Service prep. Differential Differens 0,25±4,0 0.25±4.0 C C P2 P1 t C Specifications are subject to alteration without notice. 5
6 Functions Operational readiness: When the potential-free contacts are closed, the controller is ready for operation. If the contacts are opened, the motor will stop and the alarm and purging operation will be blocked. Control: The heat exchanger will be switched off if a rising outdoor temperature is registered by the temperature sensor in the outdoor intake section of the handling unit. The switch-off temperature can be reset on potentiometer P1. The difference between the switch-off and switch-on temperatures can be preset on potentio-meter P2. Rotation monitor: The controller receives a pulse every time the magnet on the rotor periphery passes the sensor. If the temperature is lower than the preset switch-off value (P1), and the pulses have ceased for more than 5 min., the controller will switch out the heat exchanger and an alarm will be initiated. Purging operation: If the controller has been ready for operation for 4 hours, and the outdoor temperature has been higher than the switch-off value that has been preset on P1, the heat exchanger will start up and run at full speed for one minute to purge the rotor surfaces clean of dust. To check the purging operation function: If the outdoor temperature is higher than the switch-off value preset on P1 at the time that the power supply is switched on, purging operation will start after 30 seconds. Alarms Rotation monitor: An alarm with flashing red LED (lit 75% of one second) will appear if pulses from the rotation monitor sensor cease for more than 5 minutes. The alarm relay will alternate. Sensor error: An alarm with flashing red LED (lit 25% of one second) if pulse transmission is interrupted or if the conductor from the sensor is short-circuited. Power failure: The alarm relay alternates. To reset alarms: Alarms can be reset by opening and closing the standby contacts or by briefly opening the mains power supply. LEDs Green LED: Steadily shines when the unit is ready for operation. Yellow LED: Steadily shines if the outdoor temperature is lower than the switch-off value preset on potentiometer P1. The LED is off for one second every time the rotation monitor sensor receives an impulse. Red LED: Flashes (lit 75% of one second) if the thermostat calls for rotor operation and pulses from the rotation monitor sensor cease for more than 5 minutes. Flashes (lit 25% of one second) if pulse transmission is interrupted or if the conductor from the sensor is shortcircuited. Technical data mains power supply V AC ±10%, 50 Hz Fuse - power supply...10a Operating temperature till +50 C Dimensions of the enclosure...b x H x D = 230 x 80 x 65 mm Degree of protection...ip54 Alarm relay...potential-free, alternating 250 V AC 10A Fuse motor output... Fine-wire fuse, 20 x 5 mm, 1.25 AT 6 Specifications are subject to alteration without notice.
Instructions for the BCEA Rotary heat exchanger
Instructions for the Rotary heat exchanger 1. General The heat recovery section is a rotary heat exchanger with high temperature and humidification efficiencies. The heat exchanger operates with an efficiency
More informationPUR (A, B, C, D) INSTRUCTION FOR VARIABLE SPEED WITH WIRING DIAGRAM FOR EMX P10 ROTOR SIZE
PUR (A, B, C, D) INSTRUCTI FOR VARIABLE SPEED WITH WIRING DIAGRAM FOR EMX P10 ROTOR SIZE 030 089 2 Installation and commissioning VARIABLE SPEED DESCRIPTI, CTROL CTENTS Safety instructions/scrapping...
More informationTechnical data. WARNING! Residual voltage is present for 1 minute after disconnecting mains voltage.
INSTALLATI Speed-controlled drive system manufacturer EMS Model Units included S for rotary heat exchanger EURA, size 20 60. Page Content 1 Technical data 1 Units included............motor, Control unit
More informationROTARY HEAT EXCHANGER EQRB
ROTARY HEAT EXCHANGER EQRB INSTALLATI AND MAINTENANCE INSTRUCTIS INSTALLATIS INSTRUCTI, DRIVE SYSTEM EMX-R, EQRB SIZE 020-090 SAFETY INSTRUCTIS IMPORTANT! During installation Read the instruction manual
More informationInstallation Instructions, TBLZ-1-23-aa Pressure Transducer GOLD/COMPACT/MIRUVENT
Installation Instructions, TBLZ-1-23-aa Pressure Transducer GOLD/COMPACT/MIRUVENT 1. General The pressure transducer is designed for use in ventilation systems intended for variable flow by keeping the
More informationECONOVENT PUM Installation and maintenance instructions for rotary heat exchangers
Plant: Heat exchanger designation: ECONOVENT PUM Installation and maintenance instructions for rotary heat exchangers Contents Design, Condition on delivery........................................3 Handling,
More informationRE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW
Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient
More informationInstallation Instructions, TBLZ-1-23-aa Pressure Transducer GOLD/COMPACT/MIRUVENT
Installation Instructions, TBLZ-1-23-aa Pressure Transducer GOLD/COMPACT/MIRUVENT 1. General The pressure transducer is designed for use in ventilation systems intended for variable flow by keeping the
More informationPURA INSTALLATION AND MAINTENANCE INSTRUCTION
PURA INSTALLATION AND MAINTENANCE INSTRUCTION 2 Installation and maintenance Content Page Delivery Version PURA... 3 Handling, Loads on the Unit, Inspection Facilities... 4 Connection, Checks, Rotor Seals...
More informationAdvantage-D. Operating Instructions and Maintenance Manual. Central Vacuum Systems (Expandable/Modular Models) (Ver.
Advantage-D Series 3 Central Vacuum Systems (Expandable/Modular Models) (Ver. 8/05) Operating Instructions and Maintenance Manual DESCRIPTION The Becker Advantage-D and Advantage-L central vacuum systems
More informationPUM(O,R,V) AND PUML INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR ROTARY HEAT EXCHANGERS ROTOR SIZE (460/500)
PUM(O,R,V) AND PUML INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR ROTARY HEAT EXCHANGERS ROTOR SIZE 060 420 (460/500) 2 Installation and maintenance Content Page 1. Description - Unit design... 3 2. Handling
More information& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL
72-6850 & 72-6852 HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL Table of Contents Introduction 2 Specification 2 Safety 4 EMC 5 Installation 6 Connections 6 Operation 7 Maintenance and Repair 8 www.tenma.com
More informationUser manual MTS-32. QUI-1013 Version 1.5 January
Version 1.5 January 2015 User manual MTS-32 Page 2 Contents 1. Introduction... 3 2. Principles of operation... 3 2.1 Principles of MTS-32 ventilation... 3 2.2 Principles of sorbent tube sample collection
More informationIndoor air quality sensor.
Indoor air quality sensor. Options and Accessories, Installation manual Ref.: N-40175_EN 1107 Index Index 1 Indoor air quality sensor... 1 1.1 General Information... 2 1.2 General measurements... 2 1.3
More informationIBC control. MicroMax MANUAL. With adjustable boost function and threshold value. Since Set of EMC-glands as an option
Made in Since 1983 S w e d e n MANUAL Set of EMC-glands as an option CONTROL UNIT FOR ROTARY HEAT EXCHANGER MicroMax Article no. F21009301 With adjustable boost function and threshold value IBC control
More informationElectronic Ballast EVG 2000-T
Electronic Ballast EVG 2000-T Operating Manual Table of contents 1 Description 1.1 Advantages of this ballast... 3 1.2 Functional principle... 3 1.3 Energization... 4 1.4 Visualization... 5 1.5 Indications
More informationUltrasonic heat meter
Ultrasonic heat meter Installation and user guide Flow sensor-vmc-p Energy integrator Compact heat meter Temperature senor CONTENTS Kapitel Please read this manual prior to installation Page 3 2! T! Important
More informationDUAL 60V 20A POWER FLEX POWER SUPPLY INSTRUCTION MANUAL
72-7570 DUAL 60V 20A POWER FLEX POWER SUPPLY INSTRUCTION MANUAL Table of Contents Specification 1 Safety 3 EMC 4 Installation 5 Connections 5 Operation 6 Maintenance 8 Specification General specifications
More informationHP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control
SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains
More informationTe 803 Electronic Controller. Service, Operation & Technical Information Manual
Te 803 Electronic Controller Service, Operation & Technical Information Manual WARNING! Technical descriptions and data given in this document are accurate, to the best of our knowledge, but can be subject
More informationSystem 6000 Electropneumatic Converters for DC ranges I/P Converter Type 6102 Type 5288
System 6000 Electropneumatic Converters for DC ranges I/P Converter Type 6102 Type 5288 Fig. 1 Type 6102-51 Rack-mounting Unit Fig. 2 Type 6102-52 Rack-mounting Unit Fig. 3 Type 6102-53 Field Unit Fig.
More informationC RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
C RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING INSTALLATION Thermoscreens Ltd St. Mary s Road Nuneaton Warwickshire England
More informationDifferential Pressure Transmitter
Specifications/Instructions Differential Pressure Transmitter General Model PY9000D is a differential pressure transmitter that uses a ceramic cantilever sensor. Deflection of the ceramic cantilever caused
More informationRE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW
Page 1 of 5 RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & Features: Benefits: 0-10Vdc or 0-5Vdc control input Over temperature protection with auto reset Din-rail mounting Efficient electronic switching No
More informationDC-Motor Controller. User Manual
Jægergårdsgade 152/05A DK-8000 Aarhus C DENMARK WWW.WAHLBERG.DK Forside DC-Motor Controller User Manual Firmware V4.00 Product content 1 Controller box - for controlling a DC-motor. 1 PowerCON TRUE1 female
More informationRVP-R- VAV controller. In explosion-proof version
VAV controller In explosion-proof version RVP-R- SMAY LLC / 29 Ciep³ownicza St. / 31-587 Cracow / Poland tel. +48 12 378 18 00 / fax. +48 12 378 18 88 / e-mail: info@smay.eu Intended use VAV control units
More informationVA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service
VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service Installation Instructions VA-908x Code No. LIT-12011566 Issued August 24, 2009 Applications The VA-908x Series Electric
More informationLQLR Fan. Installation instruction. Outlet: Installation. Inlet:
Installation : LQLZ-04 Protective screen LQLZ-03 counterflange LQLZ-01 flexible connection LQLZ-02 connection piece Inlet: Fig. 1 LQLZ-09 damper LQLZ-06 connection piece LQLZ-05 flexible connection LQLZ-07
More informationWALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models
SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASH9LSACW ASH12LSACW Outdoor unit AOH9LSAC AOH12LSAC CONTENTS SPECIFICATIONS...................... 1 DIMENSIONS..........................
More informationPULSE-8: MASTER PULSATION CONTROL
PULSE-8: CONTROL Version - February 2006 For Software Version V1.02 Part Number - 39-0020 CONTROL: INDEX GOOD PRACTICE: Mains Supply. A separate mains supply and earth running directly from the consumer
More informationPUR (A, B, C, D) INSTRUCTION FOR VARIABLE SPEED WITH WIRING DIAGRAM, EMX-R ROTOR SIZE TECHNICAL DATA
PUR (A, B, C, D) INSTRUCTI FOR VARIABLE SPEED WITH WIRING DIAGRAM, EMX-R ROTOR SIZE 125-250 TECHNICAL DATA 2 Installation and commissioning Content Page General description... 3 Control- and operation
More informationInstallation Instructions Spector compact Conductivity Transmitter System LRGT 16-1
Installation Instructions 810701-00 Spector compact Conductivity Transmitter System LRGT 16-1 IMPORTANT NOTES...4 SAFETY NOTES...4 Danger...4 EXPLANATORY NOTES...4 Scope of supply...4 System description...4
More informationMANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER. MicroMax. Article no. F IBC control Made in Sweden
MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER MicroMax Article no. F21009201 IBC control Made in Sweden TABLE OF CONTENTS Installation instructions 2 Mounting 2 Safety instructions 3 Manufacturer's
More informationStarting System DS-102 Series 200. Elmatik AS P.O.Box 309 NO-3471, Slemmestad T F
Starting System DS-102 Series 200 Elmatik AS P.O.Box 309 NO-3471, Slemmestad T - +47 31 28 37 83 F - +47 31 28 37 93 www.elmatik.no post@elmatik.no CONTENT 1. INTRODUCTION 3 2. TECHNICAL SPECIFICATIONS
More informationCCO kit. Compact Change Over - 6-way switch valve with motor QUICK FACTS
kit Compact Change Over - 6-way switch valve with motor QUICK FACTS Enables heating & cooling in products with only one heat exchanger circuit Precise flow regulation For 4-pipe cooling/heating system
More informationECONOVENT Rotary heat exchanger Instruction for variable speed EMX-R PUM with wiring diagram
ECOVENT Rotary heat exchanger Instruction for variable speed EMX-R PUM 060-340 with wiring diagram Contents Variable speed PUM 060 340 General information...............................................
More informationMANUAL. MiniMax V / VK
MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER MiniMax V / VK Revised 2014-10-07 Version 1.3.1 F21037901GB Declaration of Manufacturer The manufacturer s assurance of the agreement of the product with
More informationMODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM
MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM DSE 520 ISSUE 4 4/4/02 MR 1 TABLE OF CONTENTS Section Page INTRODUCTION... 4 CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION.... 4 1. OPERATION...
More informationMANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGERS. MicroStart. IBC control
MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGERS MicroStart IBC control PAGE REFERENCE Functional description 1 Technical data 2 Functions 2-3 - Push-button - DIP-switches - Operation indications - Alarm
More informationPREMIER POWER PACK INSTRUCTION MANUAL EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL. GLT.MAN-138 Issue: /05/2016 N.R.P.J.
EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL GLT.MAN-138 CONTENTS Introduction to the Premier Power Pack PSU... 2 Changes to EN54-4 (The Fire Alarm Equipment Power Supply Standard)... 3 Indications... 4
More informationTroubleshooting Bosch Proportional Valves
Troubleshooting Bosch Proportional Valves An Informative Webinar Developed by GPM Hydraulic Consulting, Inc. Instructed By Copyright, 2009 GPM Hydraulic Consulting, Inc. TABLE OF CONTENTS Bosch Valves
More informationMobile recleanable HEPA filter units for a flow of m 3 / h
Mobile recleanable HEPA filter units for a flow of 3.000 m 3 / h Page 1/11 consisting of Mobile online recleanable HEPA filter block, Type M-RHF hightec 1 x 2 and Mobile air conveyor block, Page 2/11 RHF
More informationSTEPPER-BLOCKplus. Manual. Version: 2.0 As of: 06/2002 Author: Edmund Burger &RPSDFW6WHSSHU'ULYHU IRU3KDVH6WHSSLQJ0RWRUV. Main. Status-LED.
Manual STEPPER-BLOCKplus &RPSDFW6WHSSHU'ULYHU IRU3KDVH6WHSSLQJ0RWRUV Main Status-LED Current Adjustment Controller Motor Version: 2.0 As of: 06/2002 Author: Edmund Burger All rights reserved: MOTRON Steuersysteme
More informationHarmony Installation, Operation and Maintenance
Harmony Installation, Operation and Maintenance IMI FLOW DESIGN / Installation - Maintenance / F402.0 Harmony IOM Harmony Technical Description Application: HVAC, Chilled and Hot Water Hydronic Systems
More informationSHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual
Electronic Motor Brake Type G Instructions and Setup Manual Table of Contents Table of Contents Electronic Motor Brake Type G... 1 1. INTRODUCTION... 2 2. DESCRIPTION AND APPLICATIONS... 2 3. SAFETY NOTES...
More informationENTRANCE EQUIPMENT ER D PAGE 1 OF 5
PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument
More informationORION PLUS three-phase kVA
ORION PLUS three-phase 30-1250kVA Orion Plus stabilizers are available for different ranges of input voltage fluctuation. In the ±15%/ ±20% and ±25%/ ±30% types, the change of input range is obtained through
More informationTecomotive - tinycwa - User Manual Intercooler Version
Tecomotive - tinycwa - User Manual Intercooler Version Operation Overview When activated the controller is measuring the coolant temperature and the rate of increase with the connected temperature sensor.
More informationAccessories for Stand-alone inverter SUNNY ISLAND GENMAN
Accessories for Stand-alone inverter SUNNY ISLAND GENMAN Technical Description GenMan-TEN082730 98-2001230 Version 3.0 EN SMA Solar Technology AG Table of Contents Table of Contents 1 Notes on this manual..............................
More informationSB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320
Inlet Controller SB 2000 USER'S MANUAL AUTO OPEN MANUAL PUSH TO SEARCH NEXT STAG E CLOSE Aerotech, Inc. FORM: QM 1320 4215 Legion Dr. Mason, MI 48854-1036 USA Rev. 3, Sept. 1997 Ph. (517) 676-7070 Fax
More informationMarine Exhaust Temperature Alarm. COMPONENTS
Marine Exhaust Temperature Alarm. Model: SM0012 INTRODUCTION COMPONENTS Marine water cooled exhaust systems are designed to withstand temperatures of up to about 120 C. However the exhaust gases from the
More informationMotor-drive mechanism, type BUL. Technical guide
Motor-drive mechanism, type BUL Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required
More informationSeries 430 Type 3430 Pneumatic Indicating Controller for Temperature with Capillary Sensor Type 3432 Controller Station Type 3436 Transmitter Module
Series 430 Type 3430 Pneumatic Indicating Controller for Temperature with Capillary Sensor Type 3432 Controller Station Type 3436 Transmitter Module Application Temperature controller for process engineering
More informationROTARY HEAT EXCHANGER
ROTARY HEAT EXCHANGER Energy Recovery Ventilation Specialist Beijing Holtop Artificial Environment Technology Co., Ltd ISO9001 CE EUROVENT COMPANY BRIEF INTRODUCTION TO COMPANY ENERGY RECOVERY VENTILATION
More informationOperations Manual. Zero Speed Switch Sensor Model ZS09P
Zero Speed Switch Sensor Model ZS09P The must be referred to for correct installation. Failure to comply with the shall void all warranties and liabilities. Overview The Phares Electronics Model ZS09P
More informationDCC-3000 Climate Control for Vintage Air GEN-IV systems
INSTALLATION AND OPERATOR S MANUAL FOR DCC-3000 Climate Control for Vintage Air GEN-IV systems PARTS INCLUDED WITH THIS SYSTEM Vent sensor housings: 2 1 / 2 housings (x2) 2 housings (x2) Installation/operator
More informationTecomotive - tinycwa User Manual
Tecomotive - tinycwa User Manual Overview Contents - tinycwa controller - Fuse holder - Fuses (15A/30A) - Connector 8 pin (controller) - Connector 4 pin (water pump) - Connector 2 pin (temperature sensor)
More informationSky Wing. Contents. Power Roof Ventilator
Power Roof Ventilator Contents Quick Guide... 14 General, Advantages of the... 15 Specification... 16 Technical Description of the... 17 LTSA Roof duct... 19 Electrical and Control Equipment, Control Functions...
More informationA system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.
General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail
More informationSteering column and sensor
Steering column and sensor Type LAB Series 1 x Nominal voltage 12 to 48 volt Output signal digital, analog and direction (option) HE 11874 / 09.2017 2 LAB HE 11874 / 09.2017 Page Content 4 4 5 6 7 7 8
More informationTherm-L-Tec Building Systems LLC. Therm-L-Tech. Power Operated Retrofit Kit 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual
Therm-L-Tec Building Systems LLC Therm-L-Tech Power Operated Retrofit Kit 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual Rev. A 01/2015 Index Index 1 Electrical Requirements for Therm-L-Tec
More informationAUTOMATIC 12 WAY HEAT TREATMENT CONSOLE
Maritime Stress PO Box 2898, 30 Estates Road Dartmouth, NS, B2W 4Y2, Canada Toll Free: 1-877-468-1781 Phone: (902) 468-7873 Fax: (902) 468-2304 Website: E-mail: info@maritimestress.com OPERATION MANUAL
More informationMAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -
MAKING MODERN LIVING POSSIBLE Quick Setup VLT FCM 300 Series Factory setting Motors type B14 & B34 mounting Reset (pushbutton) Start Jog Speed reference Fig. 1 - Reset to be closed short time for resetting
More informationPlanning and Commissioning Guideline for NORD IE4 Synchronous Motors with NORD Frequency Inverters
Getriebebau NORD GmbH & Co. KG Getriebebau-Nord-Straße 1 22941 Bargteheide, Germany www.nord.com Planning and Commissioning Guideline for NORD IE4 Synchronous Motors with NORD Frequency Inverters General
More informationBurden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM
Contents Section Page 1.0 Introduction 1 2.0 Specification 1-4 3.0 Installation 5-8 4.0 Programming 9-10 5.0 Menus 10-12 6.0 Fault Finding/Diagnostics 12-13 7.0 Communication 13 8.0 Setting Up 13-16 1.0
More informationP66 Series Electronic Fan Speed Controls
FANs 125, 121 Pressure Controls Section P Product/Technical Bulletin P66 Issue Date 0498 P66 Series Electronic Fan Speed Controls The P66 is a pressure actuated electronic motor speed controller. This
More informationDUST ALERT BinMaster Price Book binmaster.com Subject to change without notice 1
DUST ALERT - 3000 BinMaster Price Book 01-2019 binmaster.com Subject to change without notice 1 DUST ALERT - 3000 Dust Alert - 3000 The Dust Alert with integrated electronics and sensing probe utilizes
More informationSystem 6000 Electropneumatic Converter for Direct Current Signals i/p Converter Type 6126
System 6 Electropneumatic Converter for Direct Current Signals i/p Converter Type 66 Application Devices used to convert a direct current signal into a pneumatic signal for measurement and control. Especially
More informationFault Codes. J control
J control Timer Temp Fault Codes 12 11 10 9 8 7 6 5 4 3 2 1 30 29 28 27 26 25 24 23 22 21 20 Enter unit inspection mode by pushing the UP and DOWN buttons simultaneously for two seconds. Ensure that the
More informationOPERATING INSTRUCTIONS
Series II OPERATING INSTRUCTIONS and MAINTENANCE MANUAL TANK MOUNTED DUPLEX MODELS (Version 5/99) CENTRAL VACUUM SYSTEMS DESCRIPTION The Becker Advantage-D and Advantage-L central vacuum systems are available
More informationVALVE CONTROLLERS Controllers for Dust Extr 2010 / 2011 action Technology
VALVE CONTROLLERS Controllers for Dust Extraction 2010 Technology / 2011 Valve controllers for all cases HESCH has the skills and technology to tackle any control task for dedusting of filter and dust
More informationOperating Instructions Overcurrent Protection - Tester
Operating Instructions Overcurrent Protection - Tester WWW.LECOM.CN CONTENTS Table of contents 1. ORDER REFERENCE...2 1.1. Standard set...2 1.2. Options...3 2. INTRODUCTION...4 2.1. General description...4
More informationUser Instructions for WRC1021D. Doc
User Instructions for WRC1021D Doc. 0001-5989 CONTENTS 1.0 INTRODUCTION TO THE WRC1021D... 2 2.0 FUNCTIONAL DESCRIPTION... 3 3.0 POTENTIOMETERS, SWITCHES AND INDICATORS... 5 4.0 CALIBRATION AND START-UP
More informationInstallation manual. Cooling system. Industrial engines DC09, DC13, DC16 OC16. 01:05 Issue 12 en-gb. Scania CV AB 2018, Sweden
Installation manual Cooling system Industrial engines DC0, DC13, DC OC 333 3 01:05 Issue en-gb Changes from the previous issue...3 Design and dimensioning...3 Expansion tank...4 and earlier emission levels...
More informationDEVICE STATE/BYPASSED FAILURE OVERLOAD
Technical specifications Type 5. 7. Control electronics Rated values Terminal Rated control supply voltage A1A2 V AC 115 230 115 230 Tolerance % -15+10-15+10 Rated control supply STANDBY ma 15 15 Rated
More informationOwners Manual. Features
Owners Manual Pumptec is a microcomputer based pump protection device that continuously monitors motor load and power line conditions to provide protection against dry well conditions, waterlogged tanks,
More informationKerosene - oil burner
Installation, use and maintenance instructions Kerosene - oil burner Two stage operation CODE MODEL TYPE 3746686 G0D 76T8 90 (0) TECHNICAL FEATURES Thermal power output 44 / 54 0 kw 3.7 / 4.5 0 kg/h Fuel
More informationEGQ 212: Duct transducer, CO 2 and temperature
Product data sheet 7.0 EGQ : Duct transducer, CO and temperature How energy efficiency is improved Measuring the CO concentration and temperature for energy-efficient, demand-controlled regulation of the
More informationDifferent oils are used in automotive A/C systems, based on the type of refrigerant. Polyalkylene Glycol (PAG) oil is used for R-134a refrigerant.
Lubricants Automotive air conditioning lubricants are specially formulated because of how and where they operate. Air conditioning oils must be dry (having little or no water content) and mix with the
More informationHYGRODYNAMICS DIGITAL DEW POINT MONITOR PC BOARD MODEL 6392N & 6392N2 TABLE OF CONTENTS
HYGRODYNAMICS DIGITAL DEW POINT MONITOR PC BOARD MODEL 6392N & 6392N2 TABLE OF CONTENTS INTRODUCTION... 2 SPECIFICATIONS... 2 INSTALLATION... 3 PC Board Mounting...3 Sensor Installation...3 Manifold Assembly...4
More informationNON MAINTAINED TWIN SPOTLIGHT WALL MOUNT LED EMERGENCY LIGHT
Model No. PEL00581 NON MAINTAINED TWIN SPOTLIGHT WALL MOUNT LED EMERGENCY LIGHT 1 Please read these instructions carefully before starting installation and retain for future reference. The centre page
More informationCALTRAP INSTALLATION AND OPERATIONS MANUAL
INSTALLATION AND OPERATIONS MANUAL NOTE Please read this entire installation and operations manual before energizing the. Safety Considerations: Installing and servicing capacitor equipment can be hazardous.
More informationRotary heat exchanger EURA, 20 53
Rotary heat exchanger EURA, 0 5 Fig. Adjustment At a constant speed, check that the rotor is rotating in the right direction. The direction of rotation is indicated on the casing. If the purging sector
More informationRVS-AX Instruction Manual
RVS-AX Analog Soft Starter 8-170A, 220-600V Instruction Manual Ver. 10/11/2009 2 Table of Content RVS-AX Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3
More informationMODEL 422 Submersible Pump Controller
MODEL 422 Submersible Pump Controller Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or 240VAC, Single-phase or 3-phase Built-in Trip and
More informationECONOVENT PUR (C) Installation and Maintenance Instruction
ECONOVENT PUR (C) Installation and Maintenance Instruction Installation and Maintenance Instruction PUR (C) Contents Delivery Version of PUR (C)...3 Lifting PUR (C)...5 Assembling PUR (C)...6 Handling,
More informationOil-free piston compressors KK and piston vacuum pumps KV
Oil-free piston compressors KK and piston vacuum pumps KV Installation and Operating Instructions 0678106030L02 1707V003 Contents Important information 1 About this document 2 1.1 Warnings and symbols
More informationElectronic Water Meters in measuring cell design
5 343 SIEMECA Electronic Water Meters in measuring cell design WMC... WMH... Electronic, mains-independent meters to acquire water consumption in autonomous domestic water plants. Storage and display of
More informationPhoenix Inverter
Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Appendix Phoenix Inverter 12 250 12 375 12 500 12 800 24 250 24 375 24 500 24 800 48 250 48 375 48 500 48 800 1. Safety instructions WARNING: ELECTRIC
More informationEnergy Supply Systems
Energy Supply Systems SINGLE POLE INSULATED CONDUCTOR RAIL 815 100 amps KAT0815-0001b-E Conductor rail system in a high bay storage Slip ring with conductor rail system in a stretch-foil packing machine
More informationXM1 - Motor protection relay
XM1 - Motor protection relay Contents 1 Applications and features 1 Applications and features 2 Design 3 Working principle 3.1 Overload protection 3.2 Stalling protection 3.3 Earth fault protection 3.4
More informationGRUNDFOS PRODUCT GUIDE. Redi-Flo3 and CU 300. Environmental Pumps 60Hz
GRUNDFOS PRODUCT GUIDE Redi-Flo3 and CU 300 Environmental Pumps 60Hz Table of Contents Features and Benefits..................................... pages 4-5 Applications.............................................
More informationTECHNICAL BROCHURE BSPDDRIVE. Aquavar SPD (Single Pump Drive) SIMPLEX VARIABLE SPEED PUMP CONTROLLER FOR SUBMERSIBLE AND CENTRIFUGAL PUMPS
TECHNICAL BROCHURE BSPDDRIVE C U L US Aquavar SPD (Single Pump Drive) SIMPLEX VARIABLE SPEED PUMP CONTROLLER FOR SUBMERSIBLE AND CENTRIFUGAL PUMPS Aquavar SPD variable speed, constant pressure pump controller
More informationmodel ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION
MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.
More informationBI-DIRECTIONAL INSERTION FLOW TRANSDUCER
DUALPULSE BI-DIRECTIONAL INSERTION FLOW TRANSDUCER INSTRUCTION MANUAL DUALPULSE LOCK 1.1 General arrangement Thank you for purchasing a Dualpulse Flowmeter. It is important that you read this manual to
More informationTemperature Controllers
Controllers SCR Power Controllers Introduction to Silicon Controlled Rectifier (SCR) Power Controllers Features and Benefits of SCRs High reliability Because the SCR power controller is a solid-state device,
More informationModel DS1000/DT20 System
Model DS1000/DT20 System Installation, Commissioning and Operation Manual Alpha Moisture Systems Alpha House 96 City Road Bradford BD8 8ES England Tel: +44 1274 733100 Fax: +44 1274 733200 Email: mail@amsytems.co.uk
More informationINSTRUCTION MANUAL FOR THE THERMOCOUPLE ATTACHMENT UNIT (TAU)
INSTRUCTION MANUAL FOR THE THERMOCOUPLE ATTACHMENT UNIT (TAU) Model Number: 41756 (100 125Vac) 41757 (220 240Vac) Manufactured in the United Kingdom CONTENTS Chapter Page Specification 3 What the TAU does
More informationSDS Enclosed Star-Delta Starter User Guide
SDS Enclosed Star-Delta Starter User Guide (7.5kW~90kW) V2.0.0 PLEASE NOTE: AS STANDARD AND UNLESS OTHERWISE SPECIFIED, THIS PRODUCT IS EQUIPPED WITH A BASIC LOW INTEGRITY EMERGENCY STOP CIRCUIT STOPPING
More informationCh 4 Motor Control Devices
Ch 4 Motor Control Devices Part 1 Manually Operated Switches 1. List three examples of primary motor control devices. (P 66) Answer: Motor contactor, starter, and controller or anything that control the
More information