EX510 Series Serial System Technical Specifications

Size: px
Start display at page:

Download "EX510 Series Serial System Technical Specifications"

Transcription

1 No.EX##-OMI000-A EX50 Series Serial System Technical Specifications GW Unit Applicable to DeviceNet : EX50-GDN Input Unit connector inputs type ( wire) : EX50-DXB connector inputs type (NPN) : EX50-DXN connector inputs type (PNP) : EX50-DXP connector input type (NPN) : EX50-DXN connector input type (PNP) : EX50-DXP SI Unit NPN output : EX50-S00( ) PNP output : EX50-S0( ) A B A B

2 Contents. Safety. Product Summary - Features - System structure. Specifications / How to Order - EX50 series general specifications - GW unit - Input unit - SI unit -5 Option. Valve Manifold 5. Name of parts / Accessory 5- GW unit (EX50-GDN) 5- Input unit (EX50-DX ) 5- SI unit (EX50-S 0 ) P P 7 P 7 P 7 P 8 P 8 P 8 P 0 P P P P 5 P 5 P 6 P 7 6. Wiring 6- GW unit 6-- Internal circuit 6-- Branch wiring 6-- Communication wiring 6-- Power supply wiring 6- Input unit 6-- Typical internal circuit and wiring 6-- Wiring of branch cables and e-con 6-- Sensor connection 6- SI unit 6-- Typical internal circuit and wiring 6-- Wiring of branch cables and load mounting connector 6-- How to use extra output P 8 P 8 P 8 P 8 P 0.. P 0.. P P P P P 5 P 5 P 5 P 6 7. Display / Switch Setting (GW unit) 7- LED display 7- Switch setting 7-- Setting of MAC ID. Baud rate HOLD/CLR. HW/SW mode(sw) 7-- Flexible setting of I/O point (SW) 7- Memory map 8. Dimension 8- GW unit 8- Input unit 8- SI unit 8- Valve manifold 9. Troubleshooting P 7 P 7 P 7 P 7 P 9 P 0 P P P P P P - - EX##-OMI000-A

3 . Safety This manual contains essential information to prevent possible injury and damage to (users and other people, and property) and to ensure correct handling. Please confirm understanding the definition of the following messages (signs) before going on to read the text, and always follow the instructions. Also read carefully the instruction manual of relevant equipment or apparatus before use. Indications IMPORTANT MESSAGES Read this manual and follow its instructions. Signal words such as WARNING, CAUTION and NOTE, will be followed by important safety information that must be carefully reviewed. Indicates a potentially hazardous situation which could result in death or serious injury if you do not follow instructions. Indicates a potentially hazardous situation which if not avoided, may result in minor injury or moderate injury. NOTE Gives you helpful information. Operator This operation manual has been written for those who have knowledge of machinery and apparatus that use pneumatic equipment and have full knowledge of assembly, operation and maintenance of such equipment. Please read this operation manual carefully and understand it before assembling, operating or providing maintenance to the SI Unit. Usage Restrictions This product is designed for use in general equipment for factory automation. Never use this product with equipment or apparatus that directly concerns human lives*, or which malfunction or failure can cause a huge loss. *: Equipment or apparatus that directly matters human lives means the following: Medical equipment such as life support systems or equipment used in operating rooms Compulsory equipment required by law such as the Fire Prevention Law, Construction Law and etc. Equipment or apparatus that conforms with those mentioned above. Contact our sales department when plans are made for the product to be used for the system* including equipment that concerns itself with the safety of persons or that seriously affects the public. This usage needs special consideration*. *: The system including equipment that concerns itself with the safety of persons or that seriously affects the public means the following: Nuclear reactor control systems in nuclear power plants, safety protection systems or other systems important for safety in nuclear power facilities Driving control systems of mass transportation systems, and flight control systems Equipment or apparatus that comes into contact with foods or beverages *: Special consideration means discussing usage with our engineers to establish a safe system designed as fool-proof, fail-safe, redundant and etc. Special consideration of safety or maintainability should be taken to prevent hazard or loss caused by a failure or malfunction that is likely to occur in certain probability due to environmental stress (deterioration). The special consideration means to fully review the equipment or apparatus in design stage and to establish a backup system in advance such as a redundant system or fail-safe system. - - EX##-OMI000-A

4 The compatibility of pneumatic equipment is the responsibility of the person who designs the pneumatic system or decides its specifications. Since the products specified here are used in various operating conditions, their compatibility with the specific pneumatic system must be based on specifications or after analysis and / or tests to meet your specific requirements. Only trained personnel should operate pneumatically operated machinery and equipment. Compressed air can be dangerous if an operator is unfamiliar with it. Assembly, handling or repair of pneumatic systems should be performed by trained and experienced operators. Do not service machinery / equipment or attempt to remove components until safety is confirmed..inspection and maintenance of machinery /equipment should only be performed after confirmation of safe locked-out control positions..when equipment is to be removed, confirm the safety process as mentioned above. Cut the supply pressure for the equipment and exhaust all residual compressed air in the system..before machinery / equipment is re-started, take measures to prevent quick extensions of the cylinder piston rod etc. (Bleed air info the system gradually to create back-pressure.) Contact SMC if the product is to be used in any of the following conditions:.conditions and environments beyond the given specifications, or if product is used outdoors..installation on equipment in conjunction with atomic energy, railway, air navigation, vehicles, medical equipment, food and beverage, recreation equipment, emergency stop circuits, press applications, or safety equipment..an application which has the possibility of having negative effects on people, property, or animals, requiring special safety analysis. - - EX##-OMI000-A

5 Do not disassemble, modify (including change of printed circuit board) or repair. An injury or failure can result. Do not operate the product beyond specification range. Operation at a range that exceeds the specifications can cause a fire, malfunction, or damage to the unit. Verify the specifications before use. Do not use the product in an atmosphere containing combustible, explosive or corrosive gas. It can cause a fire, explosion or corrosion. The unit is not designed to be explosion-proof. The following instructions must be kept when using the product in an interlocking circuit: Provide double interlocking by another system such as mechanical protection Check the product regularly to ensure proper operation Otherwise malfunction can cause an accident. The following instructions must be kept while in maintenance: Turn off the power supply Stop the supplied air, exhaust the residual pressure and verify the release to atmosphere before performing maintenance Otherwise the injury could be caused. Perform proper functional checks after maintenance. Stop operation when an abnormality is observed such that the unit does not work properly. Safety is not be assured due to unexpected malfunction. Provide grounding for securing safety and noise resistance of reduced-wiring system. Individual grounding is provided to the unit closely with short distance. - - EX##-OMI000-A

6 NOTE Follow the instructions given below when handling reduced-wiring system : Or it will have a risk of being damaged and operating failure. The instructions on selection (installation, wiring, environment of use, adjustment, operation and maintenance) described below must also be followed. Product specifications Use the following UL recognized direct-current power supply to combine. () Limited voltage current circuit in accordance with UL508 A circuit whose power is supplied by secondary coil of a insulating transformer that meets the following conditions Maximum voltage (with no load) : less than rms (.V peak) Maximum current : () less than 8A(including when short circuited) () limited by circuit protector (such as fuse) with the following ratings No load voltage (V peak) Max. current rating (A) 0 0 [V] 5.0 Above 0 to 0 [V] 00 / peak voltage () A circuit using max. rms or less (Class- circuit), whose power is supplied by Class- power supply unit in accordance with UL0 or Class- power supply unit in accordance with UL585 The reference of power supply for GW unit is for both powers for output and control of GW unit. +V +V Power for output Power for output Input and Power for Input and Power for control of GW unit control of GW unit +V -V Operate reduced-wiring system with the specified voltage. Operation with a voltage beyond specifications could cause malfunction or damage of the unit. Reserve a space for maintenance Be sure to keep a space for maintenance when designing layout of the unit. Do not remove nameplate. Otherwise maintenance error and misreading of an operation manual could cause damage or malfunction. It may also result in nonconformity to safety standards. Precautions on handling Installation Do not drop, hit or apply excessive shock to the unit. Otherwise the unit could be damaged so much as to result in. Follow the specified tightening torque. Excessive tightening torque can break screws. Wiring (including plugging in/out of connector) Do not bend the cables or apply excessive force to them by pulling or placing heavy load. Wiring subject to bending or tensile stress could cause the cables to break. Connect wires and cables correctly. Incorrect could wiring break the reduced-wiring system to its extent. Do not connect wires while the power is supplied. Otherwise it can break the reduced-wiring system or I/O devices could be damaged or malfunction. Do not connect power cable or high-voltage cable in the same wiring route as the unit. Otherwise the wires to the reduced-wiring system can be interrupted with noise or induced surge voltage from power lines or high-voltage lines and malfunction could be caused. Separate wiring of the unit and each I/O device from that of power line and high voltage line EX##-OMI000-A

7 Verify the insulation of wiring. Insulation failure (interference with other circuit, poor insulation between terminals and etc.) could introduce excessive voltage or current to the reduced-wiring system or each I/O device and damage them. Separate power line for solenoid valves from power line for input and control unit. Otherwise wires can be interrupted with noise or induced surge voltage causing malfunction. Take proper measurements such as noise filter against noise when the reduced-wiring system is incorporated in equipment or devices. Otherwise contamination with noise can cause malfunction. Environment Consider operating environment suitable for protection class. In case of IP0 protection class, avoid use in the place where water and oil scatter. Take sufficient shielding measures when the unit is installed. Insufficient measures could cause malfunction or failure. Verify the effect of the measures after incorporation of the unit in equipment or devices: () A place where noise due to static electricity is generated () A place where electric field strength is high () A place where there is radioactive irradiation () A place near power line Do not use the unit near by a place where electric surge is generated. Internal circuit elements of the reduced-wiring system can deteriorate or break when equipment generating a large surge (electromagnetic lifter, high frequency induction furnace, motor, etc.) is located near the reduced-wiring system. Provide surge preventives, and avoid interference with line for the equipment. Use the reduced-wiring system equipped with surge absorber when a surge-generating load such as solenoid valve is driven directly. Direct drive of a load generating surge voltage can damage reduced wiring system. Prevent foreign matter such as remnant of wires from entering the unit. Take proper measures for the remnant not to enter the reduced-wiring system in order to prevent failure or malfunction. Do not expose the reduced-wiring system to vibration and impact. Otherwise failure or malfunction could be caused. Keep the specified ambient temperature range. Otherwise malfunction could be caused. Do not use reduced-wiring system in a place where temperature suddenly changes even within the specified range. Do not expose the reduced-wiring system to heat radiation from a heat source located nearby. Malfunction could be caused. Adjustment and Operation Use precision screwdriver with for small flat blade for setting DIP switch. Maintenance Perform maintenance and check regularly. Otherwise an unexpected malfunction of components could of the unit occur due to a malfunction of the whole unit. Perform a proper functional check. Stop operation when an abnormality is observed such that the device doesn't work properly. Otherwise an unexpected malfunction of the unit component can occur. Do not use solvents such as benzene, thinner or other to clean the reduced-wiring system. They could damage the surface of the body and erase the indication on the body. Use a soft cloth to remove stains. For heavy stains, use a cloth soaked with diluted neutral detergent and fully squeezed, then wipe up the stains again with a dry cloth EX##-OMI000-A

8 . Product Summary - Features () Capable of decentralized control of input points of 6 / output points of 6 Decentralized control of input branches (max. points of 6 branches) and output branches 6 branches) per one GW unit is possible. () Easy setting and wiring Slave side doesn't need switch settings, but GW unit needs them such as address setting. It is possible to adjust length of branch cable and crimp branch cable without dedicated tool. Each slave doesn't need individual power supply because the branch cable is -core flat cable including a power supply line. () Small and compact Small and compact design is applied for all of GW unit which realizes decentralized control, Input unit which connects input equipments such as sensor, and SI unit which connects output equipment such as solenoid valve. () Flexible setting of number of occupied station Utilize I/O point effectively by setting number of occupied station of GW unit. (5) Applicable to each type of solenoid valves SMC s solenoid valves can be easily wired for serial communication. (See. Manifold Valve for applicable valve.) The extra output of SI unit can be used to actuate -port valve etc, with a cable assembly for output. - System structure Power supply for output Power supply for input and controlling GW VDC Connecting to bus at upper level (DeviceNet) Valve manifold with SI unit (connecting to sets maximum) VDC GW unit Input unit ( connector inputs type) Input unit ( connector input type) (connecting to sets maximum) Branch connector (EX50-LC) Branch cable (EX50-FC ) Cable assembly for output (EX50-V ) EX##-OMI000-A

9 . Specifiations/How to Order - EX50 series general specifications Item Specification Rated voltage Allowable instantaneous electrical stop Protection class VDC msec. or less IP0 Applicable standard UL / CSA, CE Marking * Withstand voltage Insulation resistance Ambient temperature Ambient humidity Vibration resistance Impact resistance Operating environment 50AC min. (between PE and external terminal block) 0MΩ or more (50DC Mega is given between PE and external terminal block) Operation : -0~50 C Storage : -0~60 C 5~85%RH (No dew condensation) 0~57Hz (constant amplitude) 0.05mm 57~50Hz (constant acceleration).9m/s hours for each direction, X, Y and Z (comply with JIS B 50 and IEC6-) 7m/s is given times for each direction, X, Y and Z (comply with JIS B 50 and IEC6-) No corrosive gas *Note : EMC directive (89/6/EEC) EN5008-/99, EN550/998+A, EN5008-/995, EN /999 - GW unit How to order EX50-G Basic specifications D N Applicable DN DeviceNet Item Rated voltage Power supply voltage Rated current Input / Output point Weight VDC Specification Power supply for input and control : VDC±0% Power supply for output : VDC+0% / -5% (Warning for voltage drop is given at approx. ) Communication power supply for DeviceNet : to 5VDC Power supply for input and control :.A Inside GW unit : 0.A Input unit : A Current for output : 6A Power supply for DeviceNet : 50mA Input point : Max.6 / Output point : Max.6 (Changeable by switch settings) 60g (including accessories) EX##-OMI000-A

10 Bus at upper level (Specifications of bus at upper level) Compatible system DeviceNet Release.0 Number of station occupied MAC ID setting 0 to 6 Device information Group Only Server Vender code : 7 (SMC Corp.) Product type : Product code : 00 Applicable message I/O message size Duplicate MAC ID Check Message Group Only Unconnected Explicit Message Explicit Message Poll / I/O Message Input : Maximum 8byte, Output : Maximum 8byte (Changeable by switch settings) Communication speed 5kbps 50kbps 500kbps Maximum length Thick cable 500m or less 50m or less 00m or less of Network Thin cable 00m or less Total extended cable length 56m or less 78m or less 9m or less Note : Maximum extended cable length is 6m. Bus at lower level (Specifications of bus at lower level) Number of branches for input / output Communication type Current for input branch Current for output branch Branch cable length branches for input branches for output Communication protocol : dedicated for SMC Communication speed : 750kbps Maximum [A] per branch Maximum.5 [A] per branch Within 0m (See diagram below for details.) Branch current [A] Output branch Input branch Cable length [m] Derating by cable length EX##-OMI000-A

11 - Input unit How to order EX50-DX N Applicable sensor N P B NPN output PNP output wire type Unit type Note) B ( wire type) is available only with unit type. connector inputs type connector input type (EX50-DX ) (EX50-DX ) Input unit specification Item EX50-DXN EX50-DXP EX50-DXB Applicable sensor NPN output PNP output wire type Number of input points 6 points (See diagram below for details.) Supply voltage for sensor VDC Max. supply current for sensor 0.A / point, 0.9A / unit Current consumption 00mA or less (inside of input unit) Input resistance 5.6kΩ Rated input current Approx. ma ON voltage / ON current 7V or more /.5mA or more (Between input terminal and +V for sensor) 7V or more /.5mA or more (Between input terminal and for sensor) OFF voltage / OFF current LED display Weight 7V or less / ma or less (Between input terminal and +V for sensor) 7V or less / ma or less (Between input terminal and for sensor) Green LED (lights up during ON time) EX50-DX : 90g (including accessories) EX50-DX : 0g Max.simultaneous input points Derating by input points Voltage for input and controlling part [V] EX##-OMI000-A

12 -. SI unit How to order EX50-S 0 0 Output unit specification Mounting specification 0 NPN output (+ COM.) PNP output (- COM.) Nil A B Thread mounting DIN rail vertical mounting DIN rail horizontal mounting (EX50-S 0) (EX50-S 0A) (EX50-S 0B) SI unit specification Item Specification Model EX50-S00 EX50-S0 Output type NPN output (sink type) PNP output (source type) Number of output points 6 points Rated load current VDC Maximum load current Protection Current consumption Weight Meet the three following conditions,. 0.5A / point..a / unit. Total current of OUT0 to OUT7 : A or less Total current of OUT8 to OUT5 : A or less Built-in protection circuit for short circuit 50mA or less (inside of SI unit) EX50-S 0 0g EX50-S 0A,B 80g (including accessories) - - EX##-OMI000-A

13 -5. Option () Branch cable It is a -core flat cable used for connecting each unit. How to order EX50-FC 0 Cable length [L] 0 [m] 0 [m] 05 5[m] 0 0[m] 0 0[m] 60 60[m] () Branch connector (packaged individually) It is a connector used for connecting a branch cable to each unit. Two branch connectors are attached to each of SI unit and Input unit. How to order EX50-LC Rated voltage Electrical specifications 6AC / DC or less Rated current Max. 5.0A Contact resistance Withstand voltage 0mΩ or less 00AC min. (Current leakage ma or less) () Cable assembly for output It is a cable assembly to transmit the extra output of SI unit to outside. How to order EX50-V S 0 S Output point S W Cable length [L] Valve connector Nil For SY/ SYJ S For SY/ SYJ Q For VQ/ VQZ 0.0[m] 0.0[m] - - EX##-OMI000-A

14 () e-con It is a connector used for connecting a sensor to the Input unit (EX50-DX ). See 6-- Sensor connection for connector model no. and applicable electric wire size. How to order ZS-8-C - (5) Fuse for replacement It is a fuse for replacement used for Input unit (EX50-DX ). How to order EX9-FU0 Electrical specifications Rated current Rated breaking capacity A AC / DC 8V 50A Fuse resistance 0.5Ω - - EX##-OMI000-A

15 . Valve Manifold EX50 series can use the following manifold valve. Contact SMC salesperson for its compatibility with other valves. Applicable manifold SY000 / 5000 / 7000 / 9000 series SYJ000 / 5000 / 7000 series VQZ000 / 000 / 000 series See catalog of each valve series and technical operation manual for details of solenoid valves, manifolds, etc. - - EX##-OMI000-A

16 5.Name of Parts / Accessory 5- GW unit (EX50-GDN) Communication connector for DeviceNet ( piece) Accessory Power supply connector ( pieces) No. Parts Purpose 5 Communication socket (BUS) Power supply socket (PWR(V)) Power supply socket (PWR) GW unit side branch connector (for input) GW unit side branch connector (for output) Connect to DeviceNet line with an accessory connector for DeviceNet ( ).* Supplying power for output instruments such as a solenoid valve with an accessory connector ( ).* Supplying power for controlling GW and for input instruments such as a sensor with an accessory connector ( ).* Connecting an input unit etc. by using branch cables (EX50-FC ). Connecting SI unit (manifold valve) etc. by using branch cables (EX50-FC ). 6 PE terminal Used for grounding. 7 Mounting hole Used when an unit is mounted with two M screws. 8 DIN rail mounting slot Used when an unit is mounted to DIN rail. 9 Display / switch setting part Switch setting such as LED display in unit state, MAC ID, Baud rate and I/O point. *Note : For wiring method, see "6. Wiring" in this "technical specifications" EX##-OMI000-A

17 5- Input unit (EX50-DX ) 8 6 (EX50-DX ) CN0 CN CN CN CN CN5 CN6 CN PWR Cover removed (EX50-DX ) 8 CN CN CN5 CN7 CN9 CN CN CN PWR 5 Cover removed CN0 CN CN CN6 CN8 CN0 CN CN 5 Accessory 9 0 EX50 Branch connector ( pieces) (EX50-LC) Bracket * Attached to EX50-DX only Marker plate No. Parts Purpose Branch Used to crimp branch connector ( ) into branch cable connector at (EX50-FC ) and connected them to GW unit. Input unit e-con socket The sensor is connected. Power supply Lights up : Power ON (normal) LED Goes off : Power OFF Display LED Lights up : Sensor signal input ON Goes off : Sensor signal input OFF 5 Fuse Fuse is replaceable. 6 Mounting slot Used for mounting the unit on DIN rail and with attached bracket ( ) (thread mounting). 7 Mounting hole Used to mount the unit with two M screws. 8 Cover Used to protect sensor cable and provided with marker plate ( ) on the top EX##-OMI000-A

18 5- SI unit (EX50-S 0 ) 6 5 CNCN CN CN PWR COM (EX50-S 0) CN7 CN CN6CN5 7 7 (EX50-S 0A) (EX50-S 0B) Accessory 8 9 EX50 Branch connector ( pieces) (EX50-LC) Connector lock pin ( piece) No. Parts Purpose SI unit side, Branch Crimping branch cable (EX50-FC ) to branch connector connector ( ) and connecting them to GW unit. Load mounting connector Connecting output equipment such as solenoid valve. Power supply LED Lights up : Power ON (normal) Goes off : Power OFF Communication LED Lights up : Data received Goes off : No data received 5 Mounting hole Used to mount the unit with two M screws. 6 Connector locking pin inserted hole Receiving connector locking pin ( ). 7 Mounting bracket Possible to mount on DIN rail EX##-OMI000-A

19 6.Wiring Note Be sure to turn off the power before wiring. 6- GW unit Wiring for GW unit is as follows. 6-- Internal circuit Internal circuit is shown below. V- CAN_L Drain CAN_H V+ PE Power supply for output Power supply for input and controlling GW +V +V CAN tranceiver DC-DC converter (uninsulation) Communication part insulated circuit (Photo-coupler) DC-DC converter (insulation) GW unit internal circuit Internal circuit (Brown) +V TD+ TD- +V RD+ RD- +V TD+ TD- +V RD+ RD- OUTPUT INPUT OUTPUT INPUT COM A COM D 6-- Branch wiring Each unit is wired with a branch cable, and connected with a branch connector. Two branch connectors are attached to each of SI unit and Input init. () Pressure welding for branch connector The method of pressure welding for branch connector is explained. Components Pin no. diplay Insulating cap Brown Black White Blue Cover Body Branch connector Branch cable(ex50-fc ) - 8- EX##-OMI000-A

20 Working procedure.set a branch cable to the cover. ) Set the brown wire of the branch cable so that it comes to the pin #. ) Meet the cable end to the insulating cap at the cover. Hole for fixing latch Latch )Fold the cover so that the branch cable can be put between the cover. )Fix the latch tip by inserting to a hole for fixing latch. Pin # : Brown wire Note) Check the color of wire written on a branch connector and the color of branch cable are same..fix to a body tentatively Fit latches on a body to ditches on the cover, and press them until the latch engages to the level..press fitting Press the cover to the body with plier etc..confirmation It is completed with a check on latches engaging. () Wiring of branch cables How to connect branch cable is shown below. branches for input branches for output COM D COM C COM B COM A Branch cable Branch connector at GW unit side Branch connector at cable side To SI unit To Input unit Connect the branch connectors for GW unit in order from the bottom one (COM A, B, C, and D) EX##-OMI000-A

21 6-- Communication wiring How to connect the DeviceNet dedicated cable and the DeviceNet communication connector for GW unit is as follows. ) Make sure to connect the signal cables to designated pins (Refer to Fig.). And tighten the connector surely to 0.5 to 0.6Nm tightening torque. ) Make sure to connect terminal resistor between "CAN_H"-"CAN_L" to the units at the both ends of the system. Terminating resistor is Ω, /W. (Refer to Fig.). ) Refer to Fig. about how to connect to the unit. Black Blue Drain White Red Terminal resistor Communication connector for DeviceNet V- CAN_L Drain CAN_H V+ V- CAN_L Drain CAN_H V+ Black Blue Drain White Red Fig. Black Blue Drain White Red Fig. 6-- Power supply wiring Connect power supply wiring to the two power supply pin connectors. Power supply consists of systems, but they it can be used with both of single power supply and separate power supply. Also, other units don't need individual power supply. Make sure of connection with the designated pin. Tighten the connector securely to 0.5 to 0.6 N. m tightening torque. Refer to Fig. about how to connecting. A. When separate power supply is used B. When separate power supply is used Fig. C. When used as power supply for DeviceNet (Power supply for output is another one.) VDC VDC VDC a a a VDC Fig. Power supply connector Power supply connector V Power supply PWR for output (V) Power supply for input and controlling GW PWR V Detail for part a When Input unit is used It is necessary to make power supply for DeviceNet VDC± 0%. When Input unit is not used Power supply for DeviceNet can be operated by to 5VDC EX##-OMI000-A

22 6- Input unit The wiring of Input unit is explained. 6-- Typical internal circuit and wiring Example of internal circuit and wiring are shown below. EX50-DXB:Input unit for -wire type ( connector inputs type) connector (e-con socket) ( Branch at Input unit) Fuse CN0 to CN7 For input+v RD(+) IN IN IN5 IN7 IN9 IN IN IN5 RD(-) For input IN0 IN IN IN6 IN8 IN0 IN IN Internal circuit CN0 CN CN CN CN CN5 CN6 CN7 Example of wiring: D-M9B (-wire type auto switch) : DC(+) : Input : DC(+) : Input (Brown) (Blue) (Brown) (Blue) For sensor +V Input For sensor +V Input EX50-DXN:Input unit for NPN ( connector inputs type) connector (e-con socket) ( Branch at Input unit) Fuse CN0 to CN7 For input+v RD(+) IN IN IN5 IN7 IN9 IN IN IN5 RD(-) For input +V IN0 IN IN IN6 IN8 IN0 IN IN CN0 CN CN CN CN CN5 CN6 CN7 Internal circuit +V Example of wiring: ZSE0(Pressure switch, NPN, outputs) For sensor +V Input For sensor Input : DC(+) : Input : DC(-) : Input (Brown) (White) (Blue) (Black) EX50-DXP:Input unit for PNP ( connector inputs type) connector (e-con socket) ( Branch at Input unit) Fuse CN0 to CN7 For input+v RD(+) IN IN IN5 IN7 IN9 IN IN IN5 RD(-) For input IN0 IN IN IN6 IN8 IN0 IN IN CN0 CN CN CN CN CN5 CN6 CN7 DC-DC converter noninsulation ( ) DC-DC converter noninsulation ( ) DC-DC converter noninsulation ( ) Internal circuit Example of wiring: ZSE0(Pressure switch, PNP, outputs) For sensor +V Input For sensor Input : DC(+) : Input : DC(-) : Input (Brown) (White) (Blue) (Black) - - EX##-OMI000-A

23 EX50-DXN:Input unit for NPN ( connector input type) (e-con socket) ( connector Branch at Input unit) Fuse CN0,,..., For input+v RD(+) IN IN IN5 IN7 IN9 IN IN IN5 RD(-) For input +V IN0 IN IN IN6 IN8 IN0 IN IN Internal circuit +V CN0 CN CN CN6 CN8 CN0 CN CN CN,,5..., NC NC NC NC NC NC NC NC IN IN IN5 IN7 IN9 IN IN IN5 CN CN CN5 CN7 CN9 CN CN CN5 For sensor +V Input For sensor Input For sensor +V NC For sensor Input Example of wiring: D-M9N (-wire type auto switch NPN output) : DC(+) : NC : DC(-) : Input (Brown) (Blue) (Black) EX50-DXP:Input unit for PNP ( connector input type) (e-con socket) ( connector Branch at Input unit) Fuse CN0,,..., For input+v RD(+) IN IN IN5 IN7 IN9 IN IN IN5 RD(-) For input IN0 IN IN IN6 IN8 IN0 IN IN DC-DC converter noninsulation ( ) DC-DC converter noninsulation ( ) Internal circuit CN0 CN CN CN6 CN8 CN0 CN CN CN,,5..., NC NC NC NC NC NC NC NC IN IN IN5 IN7 IN9 IN IN IN5 CN CN CN5 CN7 CN9 CN CN CN5 For sensor +V Input For sensor Input For sensor +V NC For sensor Input Example of wiring: D-M9P (-wire type auto switch PNP output) : DC(+) : NC : DC(-) : Input (Brown) (Blue) (Black) - - EX##-OMI000-A

24 6-- Wiring of branch cables and e-con Insert the branch connector at cable side into mating connector at Input unit side. Connect e-con after removal of cover. e-con Branch connector Branch connector at Input unit side 6-- Sensor connection Branch connector at cable side Utilize e-con to connect the sensor to the Input unit. To GW unit Cover 0mm or more Attaching the e-con to the lead wire for sensor Strip the sensor wire as shown in the right figure. (Refer to the table below for correspondence between connector and electrical wire gauge.) Lead Wire Table SMC Product No. ( piece) Color of cover Applicable gauge of cable ( φ ) Nominal sectional area (mm ) AMP Product No. ZS-8-CA- Orange 0.6 to ZS-8-CA- Red 0.9 to ZS-8-CA- Yellow.0 to.5 0. to 0.5 (AWG6 to 0) 756- ZS-8-CA- Blue.5 to ZS-8-CA-5 Green.5 to SMC Product No. ( piece) Color of cover Applicable gauge of cable ( φ ) Nominal sectional area (mm ) Insulator Sumitomo M Product No. ZS-8-C Red 0.8 to.0 0. to FL ZS-8-C- Yellow.0 to. (AWG6 to ) FL SMC Product No. ( piece) Color of cover Applicable gauge of cable ( φ ) Nominal sectional area (mm ) OMRON Product No. Transparency to to 0.5 (AWG8 to 0) XNA-0 * *Note: If given tensile force more than N, cable may separate from connector. - - EX##-OMI000-A

25 Insert the cable to the end with checking correspondence between color of cable and number stamped on e-con. (Refer to 6-- Typical internal circuit and wiring ) A It checks that the above-mentioned preparation work has been performed correctly, and A part shown in right figure is pushed by hand and makes temporary connection. A part center is straightly pushed in by tools, such as pliers. e-con is not allowable to be reused once crimped for connection. For the connection failure such as incorrect order of wire and incomplete insertion, please use the new e-con for sensor. - - EX##-OMI000-A

26 6- SI unit The wiring of SI unit is explained. 6-- Typical internal circuit and wiring Example of internal circuit and wiring are shown below. EX50-S00 For output +V TD(+) TD(-) For output ( ) Branch connector at SI unit side DC-DC converter Internal circuit NPN output NPN output (Load mounting connector) For load +V + OUT0 Load OUT For load +V + Load... For load +V OUT OUT5 For load +V... + Load + Load CN0 CN7 EX50-S0 For output +V TD(+) TD(-) For output ( ) Branch connector at SI unit side DC-DC converter Internal circuit +V PNP output +V PNP output (Load mounting connector) OUT0 + For load Load For load CN0 OUT + Load... OUT For load For load OUT Load Load CN7 NPN and PNP outputs use the transistor with built - in protective function for short circuit. 6-- Wiring of branch cables and load mounting connector Wiring of branch cables and load mounting connector are shown below. Insert load mounting connector with pinsette. After insertion at all load mounting connectors is completed, insert connector locking pin. The output no. of each load mounting connector can be found on the next page. Branch cable To GW unit Branch connector at cable side Branch connector at SI unit side Load mounting connector Connector locking pin EX##-OMI000-A

27 CN CN CN CN PWR COM EX50-S00 No. EX50-S0 Name Function CN0 CN CN CN CN CN5 CN6 CN7 COM Load actuating common (+) Output (n) OUT0 OUT OUT OUT6 OUT8 OUT0 OUT OUT Output (n+) OUT OUT OUT5 OUT7 OUT9 OUT OUT OUT5 COM Load actuating common (+) No. Name CN7 CN6 CN5 CN Function CN0 CN CN CN CN CN5 CN6 CN7 Output (n) OUT0 OUT OUT OUT6 OUT8 OUT0 OUT OUT COM Load actuating common (-) COM Load actuating common (-) Output (n+) OUT OUT OUT5 OUT7 OUT9 OUT OUT OUT5 6-- How to use extra output The extra output of SI unit can be used through cable assembly for output (EX50-V ). (Refer below.) For load current limit of SI unit, refer to - Specifications of SI unit. The current consumption of each valve series can be checked on table below. For further information, refer to catalog of the valve. Valve series SY000 / 5000 / 7000 / 9000 SYJ000 / 5000 / 7000 VQZ000 / 000 / 000 Current consumption Standard : 0.W (Approx.7mA) Power saving circuit : 0.W (Approx.mA) Standard : 0.W (Approx.7mA) Power saving circuit : 0.W (Approx.mA) Standard :.0W (Approx.mA) Low wattage : 0.5W (Approx.mA) SI unit For how to connect cable assembly for output, refer to 6-- Wiring of branch cables and load mounting connector. Caution : Do not apply strong tensile force on the cable assembly for output. The cable could have contact failure and breakage. Cable assembly for output (EX50-V ) EX##-OMI000-A

28 7. Display/ Switch Setting (GW unit) 7- LED display SW SW OFF ON OFF ON COM A COM B COM C COM D PWR(V) PWR MNS Display PWR(V) PWR MNS COM A COM B COM C COM D Meaning The power for output is supplied at specified voltage : Lights up The power for output is not supplied at specified voltage : Goes off The power for DeviceNet is supplied : Lights up The power for DeviceNet is not supplied : Goes off Power off, off line, or duplicate check MAC ID : Lights off Waiting for I/O connection (online) : Green flashing I/O connection completed (online) : Green lights up I/O connection time out (Light degree of communication error) : Red flashing MAC ID duplicate error, or BUS OFF error : Red lights up (Heavy degree of communication error) COM A is receiving data : Lights up * COM A is having no data to receive : Goes off COM B is receiving data : Lights up * COM B is having no data to receive : Goes off COM C is receiving data : Lights up * COM C is having no data to receive : Goes off COM D is receiving data : Lights up * COM D is having no data to receive : Goes off *Note: Only when Input unit (equipment) is connected and communicated normally. 7- Switch setting Make sure that switch setting is performed with power supply turned off. Open the cover, and set DIP switch with a flat blade driver, etc. 7-- Setting of MAC ID Baud rate HOLD / CLR HW / SW mode (SW) Setting of station number and transmission speed is performed with SW. MAC ID Baud rate HOLD / CLR HW / SW SW 8 6 OFF ON ON EX##-OMI000-A

29 ) MAC ID setting (switch No. to 6) All setting are turned ON at shipment and the station number is set 6. Make sure to set the station number in the range of 0 to 6. MAC ID (No.) (No.) (No.) 8(No.) 6(No.5) (No.6) 0 OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF ON ON OFF OFF OFF OFF : : : : : : : 0 OFF ON OFF ON OFF OFF ON ON OFF ON OFF OFF : : : : : : : 6 OFF ON ON ON ON ON 6 ON ON ON ON ON ON ) Baud rate setting (switch No.7 to 8) Make sure to set the baud rate in the range as follows. All setting are turned OFF at shipment, set to 5kbps. Baud rate No.7 No.8 5kbps OFF OFF 50kbps ON OFF 500kbps OFF ON - ON ON ) HOLD / CLR setting (switch No.9) The setting is as follows. The setting at shipment is turned OFF, set to CLR. HOLD / CLR No.9 Function CLR OFF Output is cleared when an error occurs. HOLD ON Output is held when an error occurs. ) HW / SW mode setting (switch No.0) The setting is as follows. The setting at shipment is turned OFF, set to HW mode. Mode No.0 Function HW OFF Set MAC ID and baud rate with SW to 8. SW ON MAC ID and baud rate are set by network. Note : SW to 8 are ignored EX##-OMI000-A

30 7-- Flexible setting of I/O point (SW) In GW unit, the number of controlled I/O point can be changed with SW. According to the setting of I/O point, as shown in the following figure, it branches. Number of Input setting Number of Output setting SW OFF ON ON 5 6 Input port Output port INPUT OUTPUT COM D Input data COM C Input data COM B Input data COM A Input data COM D COM C COM B COM A COM D Output data COM C Output data COM B Output data COM A Output data ) Input setting (switch No. to ) The setting at shipment is turned OFF, set to 6. No. No. No. Input point COM A COM B COM C COM D OFF OFF OFF OFF OFF ON OFF ON OFF OFF ON ON ON OFF OFF ON OFF ON ON ON OFF ON ON ON ) Output setting (switch No. to 6) The setting at shipment is turned OFF, set to 6. Reserve No. No.5 No.6 Output point COM A COM B COM C COM D OFF OFF OFF OFF OFF ON OFF ON OFF OFF ON ON ON OFF OFF ON OFF ON ON ON OFF ON ON ON Reserve EX##-OMI000-A

31 7- Memory map GW unit occupies memory area as follows according to the number of I/O point set up on the front page. Ex.) Input point : 6, Output point : 6 (Setting at shipment) In case of the input data, the sensor signal data of the Input unit which was connected with the COM A port, occupies "Word (a)" of the input area. If a sensor signal is stored in the "0 bit" of the Input unit, it becomes like the figure below. In the same way, in the case of the output data, the contents displayed in "Word (c)" of the output area. Memory map of input data Input area Branch connector (INPUT) Data ( byte ) MSB LSB MSB LSB Word (a) COM A byte (b+) byte (b) Word (a+) COM B byte (b+) byte (b+) Word (a+) COM C byte (b+5) byte (b+) Word (a+) COM D byte (b+7) byte (b+6) : : Memory map of output data Output area Branch connector (OUTPUT) (a, b : from 0) Data ( byte ) MSB LSB MSB LSB Word (c) COM A byte (d+) byte (d) Word (c+) COM B byte (d+) byte (d+) Word (c+) COM C byte (d+5) byte (d+) Word (c+) COM D byte (d+7) byte (d+6) : : (c, b : from 0) Note : Read carefully the user manual of PLC which is used as a master. The method of PLC setup, reading from or writing to memory differ from one PLC manufacturer to another EX##-OMI000-A

32 8. Dimension 8- GW unit EX50-GDN PWR (V) BUS PWR INPUT COM D COM C OUTPUT COM B COM A 8- Input unit EX50-DX 80 SMC EX##-OMI000-A

33 EX50-DX SI unit EX50-S 0 EX50-S 0A PWR PWR COM COM EX50-S 0B PWR COM 8- Valve manifold For valve manifold, refer to technical material including catalog and operation manual of each valve series. - - EX##-OMI000-A

34 9. Troubleshooting Overall system No. Item Remedy / Disposal Solenoid valve is not operated Check the power for output (V DC) is supplied. Check the branch cable is connected to SI unit. Check the LED for power supply (PWR) and the LED for communication (COM) at SI unit light up. Ensure output branch current doesn't exceed the specification range. Valve is not operated as programmed Re - program it after checking the wiring specification of manifold block assembly. Signals cannot be received even with a sensor COM A-D doesn't light up Check the power for input and controlling GW (V DC) is supplied. Check the LED for indication lights up. Ensure input branch current doesn't exceed the specification range. Check the connection of branch of COM port, which doesn't light up, to Input unit. DeviceNet compatible communication No. Item Remedy / Disposal PWR LED goes off Check the power supply for DeviceNet is supplied. PWR(V) LED goes off Check the power for output (V DC) is supplied. Check the power supply voltage for output doesn't decrease under. Check the power for input and controlling GW (V DC) is supplied. The status of MNS LED Off-line : goes off On-line, not allocated : Green flashing On-line, allocated : Green lights Light degree of communication error : Red flashing Heavy degree of communication error : Red lights Check the signal line from PLC is correctly connected. Check the wiring and pin numbers. Check the baud rate and MAC ID setting is correct. - - EX##-OMI000-A

No.EX -OME0016-A PRODUCT NAME. SI unit. MODEL / Series / Product Number EX140-SDN1

No.EX -OME0016-A PRODUCT NAME. SI unit. MODEL / Series / Product Number EX140-SDN1 No.EX -OME0016-A PRODUCT NAME SI unit MODEL / Series / Product Number EX140-SDN1 Table of Contents 1. Safety instructions 2 2. Specifications 7 2-1. General specifications 7 2-2. Electrical ant network

More information

Technical Specifications

Technical Specifications No.:EX##-OMG0007 Technical Specifications Product name : SI unit Model : EX250-SAS7 EX250-SAS9 Contents 1. Safety 2. Specifications 2-1 General specification 2-2 Communication specification 2-3 Electrical

More information

Technical Specifications

Technical Specifications No.EX##-OMG0008 Technical Specifications Product name : SI Model : EX240-SIB (EX240-IE) Contents. SAFETY... P2 2. Specification 2-. Network specification (EX240-SIB)... P5 2-2. General specification...

More information

SI unit for AS-Interface EX250-SAS#

SI unit for AS-Interface EX250-SAS# PRODUCT NAME SI unitfor AS-Interface MODEL / Series / Product Number EX250-SAS# Table of Contents Safety Instructions 2 Product Outline 8 Model Indication and How to Order 9 Summary of Product elements

More information

SI unit for EtherCAT. EX260 Series

SI unit for EtherCAT. EX260 Series PRODUCT NAME SI unit for EtherCAT MODEL / Series / Product Number EX260 Series Contents Safety Instructions 2 How to Order 7 Summary of Product elements 8 Installation and Cabling 9 Installation 9 Connecting

More information

SI unit for Ethernet POWERLINK

SI unit for Ethernet POWERLINK PRODUCT NAME SI unit for Ethernet POWERLINK MODEL / Series / Product Number EX260 Series Table of Contents Safety Instructions 2 Model Indication and How to Order 8 Summary of Product elements 9 Installation

More information

EX##-OMN0011-A. SI unit for EtherCAT PRODUCT NAME. EX260 Series MODEL/ Series

EX##-OMN0011-A. SI unit for EtherCAT PRODUCT NAME. EX260 Series MODEL/ Series EX##-OMN0011-A SI unit for EtherCAT PRODUCT NAME EX260 Series MODEL/ Series Contents Safety Instructions 2 How to Order 7 Summary of Product elements 8 Installation and Cabling 9 General instructions on

More information

Pressure Sensor for General Fluids PSE570/573/574

Pressure Sensor for General Fluids PSE570/573/574 PRODUCT NAME Pressure Sensor for General Fluids MODEL / Series / Product Number PSE570/573/574 Table of Contents Safety Instructions 2 Model Identification and How to Order 8 Names of Parts of Product

More information

SI unit for DeviceNet TM PRODUCT NAME. SI unit EX250-SDN1 EX250-SDN1-X102

SI unit for DeviceNet TM PRODUCT NAME. SI unit EX250-SDN1 EX250-SDN1-X102 SI unit for DeviceNet TM PRODUCT NAME SI unit MODEL / Series / Product Number EX250-SDN1 EX250-SDN1-X102 Contents Safety Instructions 2 Product Summary 7 Model indication and How to order 8 Summary of

More information

Magnetic Field Resistant 2-color Indication Type Solid State Auto Switch

Magnetic Field Resistant 2-color Indication Type Solid State Auto Switch PRODUCT NAME Magnetic Field Resistant 2-color Indication Type Solid State Auto Switch MODEL / Series / Product Number D-P3DW(A) * Series Contents Safety Instructions 2 Model Indication Method 8 Names and

More information

Digital Flow Switch (Remote type sensor unit)

Digital Flow Switch (Remote type sensor unit) PRODUCT NAME Digital Flow Switch (Remote type sensor unit) MODEL / Series / Product Number PFM5## Table of Contents Safety Instructions 2 Model Indication and How to Order 10 Summary of Product parts 13

More information

Low Differential Pressure Sensor ±1% F.S.

Low Differential Pressure Sensor ±1% F.S. CAT.ES100-49 A Low Differential Pressure Sensor Rated differential pressure range: 0 to 2 kpa Accuracy: ±1% F.S. LED display to confirm energization Series PSE550 Proof pressure: 65kPa Output: 1 to 5VDC

More information

Solid State Auto Switch D-M9#A#

Solid State Auto Switch D-M9#A# PRODUCT NAME Solid State Auto Switch MODEL / Series / Product Number D-M9#A# Contents Safety Instructions 2 Model Indication and How to Order 8 Summary of Product parts 10 Summary of Product parts 10 Definition

More information

SG-B1 SERIES / SG-A1 SERIES

SG-B1 SERIES / SG-A1 SERIES 643 Door with Solenoid Interlock / Door Ultra-slim SG-B1 SERIES / SG-A1 SERIES Related Information General terms and conditions... F-7 General precautions... P.1501 PHOTO PHOTO Conforming to Machine &

More information

Digital Pressure Switch

Digital Pressure Switch PRODUCT NAME Digital Pressure Switch MODEL / Series / Product Number ZSE10(F) ISE10 Table of Contents Safety Instructions 2 Model Indication and How to order 9 Summary of Product parts 11 Definition and

More information

Digital Flow Switch (Remote type monitor unit)

Digital Flow Switch (Remote type monitor unit) PRODUCT NAME Digital Flow Switch (Remote type monitor unit) MODEL / Series / Product Number PF2A3## PF2W3## PF2D3## Table of Contents Safety Instructions 2 Model Indication and How to Order 9 Summary of

More information

Doc. No. IZ -OML0002-B OPERATION MANUAL. Ionizer PRODUCT NAME:

Doc. No. IZ -OML0002-B OPERATION MANUAL. Ionizer PRODUCT NAME: Doc. No. IZ -OML0002-B OPERATION MANUAL PRODUCT NAME: MODEL: Ionizer IZN10 Series Read this operation manual carefully to understand before installation and operation. Pay extra attention on the clause

More information

Digital pressure switch for energy-saving control ejector

Digital pressure switch for energy-saving control ejector PRODUCT NAME Digital pressure switch for energy-saving control ejector MODEL / Series / Product Number ZK2-ZSV####-A Table of Contents Safety Instructions 2 Model indication and How to order 9 Summary

More information

Digital Flow Switch (Integrated display type)

Digital Flow Switch (Integrated display type) PRODUCT NAME Digital Flow Switch (Integrated display type) MODEL / Series / Product Number PF2A7##H Table of Contents Safety Instructions 2 Model Indication and How to Order 10 Summary of Product parts

More information

Digital Flow Switch (Integrated display type)

Digital Flow Switch (Integrated display type) PRODUCT NAME Digital Flow Switch (Integrated display type) MODEL / Series / Product Number PF2A7## Table of Contents Safety Instructions 2 Model Indication and How to Order 10 Summary of Product parts

More information

Digital Flow Switch PFM7##

Digital Flow Switch PFM7## PRODUCT NAME Digital Flow Switch MODEL / Series / Product Number PFM7## Table of Contents Safety Instructions 2 Model Indication and How to Order 10 Summary of Product parts 13 Definition and terminology

More information

Trimmer Auto Switch D-F7K/D-Y7K D-RNK/D-RPK

Trimmer Auto Switch D-F7K/D-Y7K D-RNK/D-RPK PRODUCT NAME Trimmer Auto Switch MODEL / Series / Product Number D-F7K/D-Y7K D-RNK/D-RPK Table of Contents Safety Instructions 2 Model Indication and How to Order 9 Summary of Product parts 10 Definition

More information

2-Color Display Digital Pressure Switch. NPN/PNP open collector 2 outputs added. Cut-to-zero display function added. Rated Pressure Metal Body Type

2-Color Display Digital Pressure Switch. NPN/PNP open collector 2 outputs added. Cut-to-zero display function added. Rated Pressure Metal Body Type Series ISE70/75/75H New NPN/PNP open collector 2 outputs added. Cut-to-zero display function added. For General Fluids For Air 2-Color Display (Green/Red) Selectable from four patterns ON Red Green Red

More information

Features. 2-wire type available. Max. operation distance: 1.5 mm 0.06 in (Stable sensing range 0 to 1.2 mm 0.05 in)

Features. 2-wire type available. Max. operation distance: 1.5 mm 0.06 in (Stable sensing range 0 to 1.2 mm 0.05 in) 817 Cylindrical Inductive Proximity Sensor SERIES Related Information General terms and conditions... F-3 Glossary of terms...p.1576~ guide... P.781~ General precautions... P.1579~ PHOTO PHOTO panasonic.net/id/pidsx/global

More information

Digital Pressure Switch

Digital Pressure Switch PRODUCT NAME Digital Pressure Switch MODEL / Series / Product Number ZSE80(F) ISE80(H) Table of Contents Safety Instructions 2 Model Indication and How to order 9 Summary of Product parts 10 Definition

More information

2-Color Display Digital Pressure Switch. Rated Pressure Metal Body Type (ISE75H) 2-color digital. Functions

2-Color Display Digital Pressure Switch. Rated Pressure Metal Body Type (ISE75H) 2-color digital. Functions Series ISE70/75/75H NPN/PNP open collector 2 outputs added. Cut-to-zero display function added. For General Fluids For Air 2-Color Display (Green/Red) Selectable from four patterns ON Red Green Red Green

More information

Air Catch Sensor ISA2

Air Catch Sensor ISA2 No.PS##-OMF0007-C PRODUCT NAME Air Catch Sensor MODEL / Series / Product Number ISA2 Table of Contents Safety Instructions 2 Model Indication and How to Order 11 Summary of Product parts 13 Definition

More information

Safety Products. Safety Products. HS5E Series. HS5E Series Miniature Solenoid Locking Switch

Safety Products. Safety Products. HS5E Series. HS5E Series Miniature Solenoid Locking Switch HS5E Series HS5E Series Miniature Solenoid Locking Switch HS5E Key features include: World s smallest 4 contact solenoid interlock switch. (35 40 46 mm.) Four contacts. Gold-plated contacts. Spring lock

More information

2-Colour Display Type High-Precision Digital Pressure Switch Series ZSE30/ISE30 How to Order Option 1 Without lead wire Nil Lead wire with connector (Lead wire length: 2m) L For positive pressure For vacuum/low

More information

0.1 mm. Actuator Position Sensor. D-MP Series. Actuator stroke position is output with an analog signal. Repeatability IP67.

0.1 mm. Actuator Position Sensor. D-MP Series. Actuator stroke position is output with an analog signal. Repeatability IP67. Actuator Position Sensor Actuator stroke position is output with an analog signal. IP67 Repeatability 0.1 mm (Varies depending on the operating conditions.) Analog output 4 measurement ment ranges Voltage

More information

Trimmer Auto Switch D-M9K/D-F7K/D-Y7K D-RNK/D-RPK

Trimmer Auto Switch D-M9K/D-F7K/D-Y7K D-RNK/D-RPK PRODUCT NAME Trimmer Auto Switch MODEL / Series / Product Number D-M9K/D-F7K/D-Y7K D-RNK/D-RPK Table of Contents Safety Instructions 2 Model Indication and How to Order 9 Summary of Product parts 10 Definition

More information

Digital Flow Switch (Sensor Part) Operation Manual

Digital Flow Switch (Sensor Part) Operation Manual Digital Flow Switch (Sensor Part) Operation Manual For Air PF2A 50/5 Series PF2A 5/ 52/ 55 Series For Water PF2W /520/50 Series PF2W 5 Series For Water (High Temperature Fluid Type) PF2W T/520T/50T Series

More information

Differential Pressure Transmitter

Differential Pressure Transmitter Specifications/Instructions Differential Pressure Transmitter General Model PY9000D is a differential pressure transmitter that uses a ceramic cantilever sensor. Deflection of the ceramic cantilever caused

More information

High-speed detection even a little liquid leak

High-speed detection even a little liquid leak 737 Leak Sensor Related Information Amplifier Built-in EX-F70 SERIES SERIES Sensor selection guide...p.11~ / P.77~ General terms and conditions...p.1 General precautions...p.986~ PHOTO PHOTO Conforming

More information

10 PSE53 0 M5. Port size. M5 x 0.8 ø6 reducer 1/4-inch reducer. the cable at the time of shipment. 10-PSE to -101 kpa

10 PSE53 0 M5. Port size. M5 x 0.8 ø6 reducer 1/4-inch reducer. the cable at the time of shipment. 10-PSE to -101 kpa Series 0-PSE50 Remote type pressure sensor How to Order Clean series 0 PSE5 0 M5 Pressure sensing range Option 0 2 High pressure [0 to MPa] Vacuum [0 to 0 kpa] Low pressure [0 to 0 kpa] Compound pressure

More information

SX5 Series Smart I/O (General Information)

SX5 Series Smart I/O (General Information) SX Series Smart I/O (General Information) INTERBUS I/O compatible with IDEC ONC remote I/O Removable terminal blocks for easy maintenance Finger-safe spring-up screw terminals Compact body 7 132 48 mm

More information

Trimmer Auto Switch Series D- 7K/D-R K

Trimmer Auto Switch Series D- 7K/D-R K CAT.ES0-180 B Trimmer Auto Switch Series D- K/D-R K Large work piece OUT1 and OUT are adjustable separately. OUT1 Trimmer OUT Trimmer OUT Medium work piece Small work piece Operating range of sensor (LED

More information

(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2

(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2 Solid-state Contactor (New Heat Sink Construction) G3PB Space and working time saved with new heat sink construction. Series now includes 480-VAC models to allow use in a greater range of applications.

More information

Analog Output Terminal

Analog Output Terminal Analog Output Terminal I/O Interface Converts Binary Data into Analog Output Data Two outputs available. High resolution of 1/6000. Conversion is possible within a range of 5% to 105% FS. High conversion

More information

panasonic.net/id/pidsx/global Solve issues related to machine safety and other safety measures with a safety door switch with key!

panasonic.net/id/pidsx/global Solve issues related to machine safety and other safety measures with a safety door switch with key! 655 Door with Key SERIES Related Information General terms and conditions... F-7 General precautions... P.50 PHOTO PHOTO Conforming to Machine & EMC Directives Recognition Certified MEASURE ITY panasonic.net/id/pidsx/global

More information

Gateway Type Serial Transmission System

Gateway Type Serial Transmission System P99-EX-B Gateway Type Serial Transmission System P Maximum 8 point control (64 inputs/64 outputs) P Flexibility of manifold valve installation improved with 4 branch wiring Flexible installation and removal

More information

Digital display Pressure range ON/OFF output Linear output Model

Digital display Pressure range ON/OFF output Linear output Model Slim Digital Pressure Sensor E8CC with Built-in Microcomputer and Digital Display Withstands a pressure of 49 kpa and highly reliable. Incorporates a two-turn pressure adjuster ensuring easy pressure setting.

More information

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4 Braking Resistor Units 3G3IV-PCDBR2 B/4 B Braking Units Thank you for choosing an OMRON Braking Resistor Unit and Braking Unit. Proper use and handling

More information

Model Number Structure

Model Number Structure Conductive Level Controller CSM DS_E_1_1 Ideal for level control for industrial facilities and equipment. Outputs can be set to self-hold at or using self-holding circuits. Sensitivity adjustment of operating

More information

Technical Documentation

Technical Documentation Technical Documentation Product manual Holding brake controller Document: 0198441113316 Edition: V1.00, 03.2006 Important information The drive systems described here are products for general use that

More information

2-Color Display High-Precision Digital Pressure Switch

2-Color Display High-Precision Digital Pressure Switch 2-Color Display High-Precision Digital Pressure Switch Series ZSE3/ISE3 2-color digital display allows you to choose the setting according to your application requirements. 4 different display settings

More information

Low Torque Metal Seal Type Rotary Joint. MQR Series

Low Torque Metal Seal Type Rotary Joint. MQR Series Doc. No MQR****-OML0002-A. PRODUCT NAME Low Torque Metal Seal Type Rotary Joint MODEL / Series / Product Number MQR Series Contents 1. Contents P1 2. Model / Specifications P2~5 3. Safety Instructions

More information

SYSMAC Transistor Remote Module

SYSMAC Transistor Remote Module 9 SYSMAC Transistor Remote Module Block and Transmission Capability in One Module 1 Two-conductor cable communications available using Omron Wired Remote I/O Master Modules (C200H-RM201 and C500-RM201)

More information

B297SB-01-1K40. AnyWireASLINK System Product Guide. ASLINKSENSOR [Photo Interrupter type] -B297SB011K40 1/7- [Function] [Notes on Safety]

B297SB-01-1K40. AnyWireASLINK System Product Guide. ASLINKSENSOR [Photo Interrupter type] -B297SB011K40 1/7- [Function] [Notes on Safety] READER/WRITER LotNo.*** MADE JAPAN AnyWireAS System Product Guide ASSENSOR [Photo Interrupter type] B297SB-01-1K40 [Notes on Safety] Precautions that must be observed in order to use this system safely

More information

Cylindrical Inductive Proximity Sensor GX-M SERIES

Cylindrical Inductive Proximity Sensor GX-M SERIES Cylindrical Inductive Proximity Sensor GX-M SERIES Listing (2 m cable length type only) Features Wide product range Types: DC 3-wire shielded type DC 3-wire non-shielded type DC 2-wire standard type DC

More information

Insulation method Zero-cross function Indicators Applicable output load Model number Phototriac coupler Yes Yes (See page 6) Main Circuit

Insulation method Zero-cross function Indicators Applicable output load Model number Phototriac coupler Yes Yes (See page 6) Main Circuit SSR with Failure Detection Function Detects failures in SSRs used for heater temperature control and simultaneously outputs alarm signals. This product supports the safe design of heater control systems,

More information

Pneumatic Drive Type Drill Bit Breakage Detection Sensor. DFM3 Series. The World's First!! Pneumatic-Drive Type. Catalog / Instruction Manual US.PAT.

Pneumatic Drive Type Drill Bit Breakage Detection Sensor. DFM3 Series. The World's First!! Pneumatic-Drive Type. Catalog / Instruction Manual US.PAT. Pneumatic Drive Type Drill Bit Breakage Detection Sensor DFM3 Series The World's First!! Pneumatic-Drive Type Catalog / Instruction Manual US.PAT. Pneumatic Drive Type Drill Bit Breakage Detection Sensors

More information

ThinkTop DeviceNetTM VDC DeviceNet is a Trademark of the Open DeviceNet Vendor Association, Inc. (ODVA).

ThinkTop DeviceNetTM VDC DeviceNet is a Trademark of the Open DeviceNet Vendor Association, Inc. (ODVA). PD 65493 GB1 20001-01 ThinkTop DeviceNetTM 11-25 VDC DeviceNet is a Trademark of the Open DeviceNet Vendor Association, Inc. (ODVA). Application The ThinkTop is designed to ensure optimum valve control

More information

Solid State Auto Switch

Solid State Auto Switch PRODUCT NAME Solid State Auto Switch MODEL / Series / Product Number D-M9## D-M9#W# Contents Safety Instructions 2 Model Indication and How to Order 9 Summary of Product parts 10 Definition and terminology

More information

HS6B Series Subminiature Interlock Switch

HS6B Series Subminiature Interlock Switch HS6B Series Subminiature Interlock Switch HS6B features: Only 78 x 30 x 15mm Allows highest level of safety by having 3 contacts: dual load contacts + monitoring contact (ISO13849-1, EN954-1) Two actuator

More information

ITVX Series. Stepless control of air pressure proportional to an electrical signal. Supply pressure: 5.0 MPa

ITVX Series. Stepless control of air pressure proportional to an electrical signal. Supply pressure: 5.0 MPa 5.0 MPa Maximum Supply Pressure High Pressure Electro-Pneumatic Regulator X Series This product is only for blowing gas. This product does not have sufficient pressure control for other applications (driving,

More information

Analog Input Terminal

Analog Input Terminal Analog Input Terminal I/O Interface Converts Analog Input Data into Binary Data Four inputs available. High resolution of 1/6000. Conversion is possible within a range of 5% to 105% FS. High conversion

More information

Digital Gap Checker. ISA3 series

Digital Gap Checker. ISA3 series PRODUCT NAME Digital Gap Checker MODEL / Series / Product Number ISA3 series Table of Contents 1 Before Use Safety Instructions 2 2 About this product Features 7 Model Indication and How to Order 8 Summary

More information

Technical information for LFU20-Z07-3A-X2

Technical information for LFU20-Z07-3A-X2 Technical information for LFU20-Z07-3A-X2 Ultrasonic flow sensor and flow controller Applications: closed-loop flow control. Also requires fluid regulator (separate part) Ultrasonic flow sensor IN18796_LFU

More information

KV series. Innovatively detachable Manifold Block. Smart Solenoid Valve (plug-in type, D-SUB multi-connector type)

KV series. Innovatively detachable Manifold Block. Smart Solenoid Valve (plug-in type, D-SUB multi-connector type) CAT.1101E-S www.sym1.com KV series Innovatively detachable Manifold Block (DIN Rail Mounting) Smart Solenoid Valve (Plug-in type, D-SUB multi-connector ) Compact size with large flow capacity Exceedingly

More information

SV1000/2000/3000/4000

SV1000/2000/3000/4000 Decentralized Serial Wiring (GW System, Branches) Series EX00 Valve manifold and input unit manifold can be connected around the GW unit. ompatible with various protocols by replacing the GW unit. ompatible

More information

SAFETY PRECAUTIONS (Always read these precautions prior to use.)

SAFETY PRECAUTIONS (Always read these precautions prior to use.) Terminal Block Converter Module for Programmable Controller Analog Module Model FALTB40DAG, FATB20TD, FALTB40ADGN, FALTB40TDG, FATB20TC, FALTB40ADDG, FALTB40RD3G Terminal Block Converter Module for Programmable

More information

(Actual size) 2 switches 10 switches. Push Adjust to the set-value by the or button.

(Actual size) 2 switches 10 switches. Push Adjust to the set-value by the or button. Digital Pressure Switch RoHS compliant Low profile 9.8 mm (Actual size) 13.5 mm 53.4 mm Vertical mounting space reduced to approx.! 1 2 Reduced in depth! 26.1 mm Can copy to up to 1 switches simultaneously.

More information

HS5E Miniature Interlock Switches with Solenoid

HS5E Miniature Interlock Switches with Solenoid Small interlock switch with four poles and solenoid. Ideal for applications in small spaces. Compact body. 3 40 46 mm. Four-pole internal switches. Gold-plated contacts. Spring lock and solenoid lock types

More information

HS1L Interlock Switches with Solenoid

HS1L Interlock Switches with Solenoid HS1L Interlock Switches with Solenoid 3000N locking strength (largest in class)! * Suitable for large and heavy doors. Same actuator as HS1E (actuator retention force 3000N) Six contacts in a compact housing

More information

RP Instruction Manual

RP Instruction Manual Instruction Manual TDK Lambda BEFORE USING THE PRODUCT Be sure to read this instruction manual thoroughly before using this product. Pay attention to all cautions and warnings before using this product.

More information

Transistor Remote Modules

Transistor Remote Modules Transistor Remote Modules Compact 8-point and 16-point Transistorized Modules Compact (8-point models: 125 x 40 x 50 mm (W x H x D); 16-point models: 150 x 40 x 50 mm (W x H x D)) Two independent supplies

More information

HS1E Series Full Size Interlock Switch with Locking Solenoid

HS1E Series Full Size Interlock Switch with Locking Solenoid HS1E Series HS1E Series Full Size Interlock Switch with Locking Solenoid HS1E Key features include: Basic unit and solenoid unit in one housing Plastic Housing: Light weight Ease of Wiring: All the terminal

More information

HS6B Series Sub-Miniature Interlock Switch. Direct Opening

HS6B Series Sub-Miniature Interlock Switch. Direct Opening HS6 Series HS6 Series Sub-Miniature Interlock Switch HS6 Key features include: Only 30mm x 15mm x 78mm Allows highest level of safety by having 3 contacts: dual load contacts + monitoring contact (ISO13849-1,

More information

New Concept Connector Type Manifold

New Concept Connector Type Manifold New Concept Connector Type Manifold Series /000/3000/000 The use of multi-pin connectors to replace wiring inside manifold blocks provides flexibility when adding stations or changing manifold configuration.

More information

AS Series. 4.0 g. Weight: Approx. 27% lighter. Flow Rate Reproducibility. Larger Knob. Easy Identification of Product Type. 5.5 g.

AS Series. 4.0 g. Weight: Approx. 27% lighter. Flow Rate Reproducibility. Larger Knob. Easy Identification of Product Type. 5.5 g. Speed Controller with One-touch Fittings In-line In-line Type y Easo t use RoHS Brass Stainless steel Reduces flow setting time! Push-lock type Knob O.D.: Almost doubled! Easy to lock ø9.4 Unlock ø5 Lock

More information

Head-separated Digital Pressure Sensor DP5 SERIES DPH SERIES

Head-separated Digital Pressure Sensor DP5 SERIES DPH SERIES 76 ORDER GUIDE DP / configuration diagram Intermediate cable s Type Vacuum pressure Positive pressure Compound pressure Appearance An intermediate cable is required to connect the controller and the sensor

More information

2-Color Display High-Precision Digital Pressure Switch Series ZSE40A(F)/ISE40A

2-Color Display High-Precision Digital Pressure Switch Series ZSE40A(F)/ISE40A 2-Color Display High-Precision Digital Pressure Switch Series ZSEA(F)/ISEA New M8 connector type RoHS IP65 Applicable fluid Air, Non-corrosive gas, Non-flammable gas Can copy to up to 10 switches simultaneously.

More information

Cylindrical Sensors CY-100 SERIES panasonic-electric-works.net/sunx. Cylindrical Inductive Proximity Sensor GX-M SERIES.

Cylindrical Sensors CY-100 SERIES panasonic-electric-works.net/sunx. Cylindrical Inductive Proximity Sensor GX-M SERIES. Cylindrical Sensors Photoelectric Sensor CY-100 SERIES Inductive Proximity Sensor GX-M SERIES Listing (2 m cable length type only) Cylindrical Inductive Proximity Sensor GX-M SERIES Cylindrical Photoelectric

More information

Digital Gap Checker. ISA3 series

Digital Gap Checker. ISA3 series PRODUCT NAME Digital Gap Checker MODEL / Series / Product Number ISA3 series Table of Contents 1 Before Use Safety Instructions 2 2 About this product Features 7 Model Indication and How to Order 8 Summary

More information

EVS RP6020. Instruction Manual

EVS RP6020. Instruction Manual Instruction Manual TDK Lambda BEFORE USING THE PRODUCT Be sure to read this instruction manual thoroughly before using this product. Pay attention to all cautions and warnings before using this product.

More information

Electro-Pneumatic Regulator Electronic Vacuum Regulator

Electro-Pneumatic Regulator Electronic Vacuum Regulator Electro-Pneumatic Regulator Electronic Vacuum Regulator New Stepless control of air pressure proportional to an electrical signal Added Fieldbus compliant specifications to Series ITV//! Reduced wiring

More information

High Vacuum Solenoid Valve PRODUCT NAME. XSA Series MODEL/ Series

High Vacuum Solenoid Valve PRODUCT NAME. XSA Series MODEL/ Series Doc. No. High Vacuum Solenoid Valve PRODUCT NAME XSA Series MODEL/ Series Thank you for purchasing this SMC product. Be sure to read this Operation Manual carefully and understand its contents before operating

More information

Input terminals Isolation method Zero cross function Operation indicator Alarm output Applicable load (See note.) Model

Input terminals Isolation method Zero cross function Operation indicator Alarm output Applicable load (See note.) Model Solid State Relays with Built-in Current Transformer CSM DS_E_7_ A New-concept SSR with Built-in Current Transformer. Heater Burnout and SSR Shortcircuit Failure Detection. Built-in Current Transformer

More information

DRB-1 Series Instruction Manual

DRB-1 Series Instruction Manual Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.

More information

Series 10-ZSE40A(F)/10-ISE40A

Series 10-ZSE40A(F)/10-ISE40A Series 10-ZSEA(F)/10-ISEA RoHS 2-Color Display High Precision Digital Pressure Switch How to Order For positive pressure Clean series For vacuum/ compound pressure 01 N01 W1 10 Rated pressure range ISEA

More information

Vacuum pump system type

Vacuum pump system type type VS*P Vacuum component C O N T E N T S Series variation 166 20 mm width universal type (/M) 168 10.5 mm width universal type (/M) 184 31.5 mm width discrete type (VSQP) 214 11 mm pitch manifold dedicated

More information

2-Color Display High-Precision Digital Pressure Switch

2-Color Display High-Precision Digital Pressure Switch 2-Color Display High-Precision Digital Pressure Switch Settings can be copied to up to 1 slave sensors at once. The settings of the master sensor can be copied to the slave sensors. Reduced setting efforts

More information

Solid State Relays G3RV. Model Number Structure. Ordering Information. Model Number Legend. List of Models. SSR and Socket Combinations

Solid State Relays G3RV. Model Number Structure. Ordering Information. Model Number Legend. List of Models. SSR and Socket Combinations Solid State Relays G3RV Slimmest OMRON plug-in SSR with maximum width 6.2 mm Long electrical life and high speed switching Large plug-in terminals for reliable connection G3RV-D (DC load) models can manage

More information

TORQUE TRANSDUCER TMHFB-*NM (for Torque Transducer) Instruction Manual. MinebeaMitsumi Inc. Sensing Device Business Unit

TORQUE TRANSDUCER TMHFB-*NM (for Torque Transducer) Instruction Manual. MinebeaMitsumi Inc. Sensing Device Business Unit TORQUE TRANSDUCER TMHFB-*NM (for Torque Transducer) Instruction Manual MinebeaMitsumi Inc. Sensing Device Business Unit Please read this manual thoroughly before attempting to use the equipment. Be sure

More information

Series ITV1000/2000/3000

Series ITV1000/2000/3000 Electro-Pneumatic Regulator Series ITV// How to Order [Option] RoHS ITV S Model type type type Pressure range 5 MPa MPa.9 MPa CE compliant Nil Q CE compliant Note) Refer to pages, 5, and 6 for information

More information

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h)

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h) Mechatronic Analog Timer H3AM Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Refer to Warranty and

More information

Miniature Pre-Leaded Vertical Enclosed Switches

Miniature Pre-Leaded Vertical Enclosed Switches Miniature Pre-Leaded Vertical Enclosed Switches 14CE Series Miniature enclosed switches with outstanding harsh environment resistance, ideal for compact machinery and equipment. Easy mounting by tightening

More information

POWER REGULATOR LD -40PSU

POWER REGULATOR LD -40PSU JZ99D4121A AMPIFIRE AMPIFIRE TYPE D-4PSU ZJ-46A ISTRUCTI MAUA Manual number JZ99D4121 Sub number A Date of preparation ov. 2 Thoroughly read this instruction manual, and then use the unit correctly. Especially,

More information

Fieldbus System (Output device for driving 5 port solenoid valves)

Fieldbus System (Output device for driving 5 port solenoid valves) Fieldbus System (Output device for driving port solenoid valves) New Compact 8mm (ctual size) Space-saving Installation IP67 RoHS EtherNet/IP added! For units with D-sub connector, and when connected to

More information

HS1C Interlock Switches with Solenoid

HS1C Interlock Switches with Solenoid HSC es with The guard door remains locked until the machine stops completely. With the actuator mounted on the guard door and the interlock switch on the machine, the door is mechanically locked when closed.

More information

Contents. Introduction Inspection Notes on Safety Precautions. Chapter 1 Overview Product Overview Names of Parts 2

Contents. Introduction Inspection Notes on Safety Precautions. Chapter 1 Overview Product Overview Names of Parts 2 INSTRUCTION MANUAL Contents Introduction Inspection Notes on Safety Precautions i i ii vii Chapter 1 Overview 1 1.1 Product Overview 1 1.2 Names of Parts 2 Chapter 2 Specifications 5 2.1 Product Specifications

More information

HS1E-K Interlock Switches with Solenoid (3-circuit)

HS1E-K Interlock Switches with Solenoid (3-circuit) HS1E-K Interlock Switches with Solenoid (-circuit) Dual main circuit + lock monitor circuit provide more safety to your system Basic unit and solenoid unit in one housing Lightweight plastic housing All

More information

Technical Operation Manual. SI Unit Model No. : EX230-SDN1

Technical Operation Manual. SI Unit Model No. : EX230-SDN1 21.Aug.2000 Technical Operation Manual Serial Interface Unit ISO Plug-in Manifold Valve Rev 1.004 21.Aug.2000 SI Unit Model No. : EX230-SDN1 Contents 1.Summary...3 2.Structure...3 2-1 System structure...3

More information

HS1C Series Full Size Interlock Switch with Locking Solenoid. GS-ET-15 BG standard in Germany. HS1C Series Functionality

HS1C Series Full Size Interlock Switch with Locking Solenoid. GS-ET-15 BG standard in Germany. HS1C Series Functionality Full Size Interlock Switch with Locking Solenoid HSC Key features include: Rugged Aluminum Die-cast Housing With the actuator mounted on a movable door, and the switch on a machine, the door can be mechanically

More information

HS1E Series Full Size Solenoid Locking Switches

HS1E Series Full Size Solenoid Locking Switches HS1E Series Full Size Solenoid Locking Switches AS-Interface Safety at Work Barriers Enabling Switches Door Interlock Switches X Series E-Stops Overview HS1E features: Basic unit and solenoid unit in one

More information

PRM-4. Phase Sequence and Motor Rotation Tester. Users Manual. For detailed specifications and ordering info go to

PRM-4. Phase Sequence and Motor Rotation Tester. Users Manual. For detailed specifications and ordering info go to PRM-4 Phase Sequence and Motor Rotation Tester Users Manual For detailed specifications and ordering info go to www.testequipmentdepot.com PRM-4 Phase Sequence and Motor Rotation Tester English Users Manual

More information

ISE7 /7 G Series CAT.ES B. MPa/1.6 MPa 1.0. MPa/2.0 MPa. MPa/10 MPa

ISE7 /7 G Series CAT.ES B. MPa/1.6 MPa 1.0. MPa/2.0 MPa. MPa/10 MPa 3-Screen Display High-Precision Digital Pressure Switch Air General Fluids 1.0 ISE70 ISE71 MPa/1.6 MPa 1.0 ISE70G ISE75G MPa/2.0 MPa 5.0 ISE76G ISE77G MPa/10 MPa It is possible to change the settings while

More information

DC I/O Conversion Module FA1-TESV32XY FA1-TESV38COM User's Manual

DC I/O Conversion Module FA1-TESV32XY FA1-TESV38COM User's Manual DC I/O Conversion Module FA1-TESV32XY FA1-TESV38COM User's Manual Thank you for purchasing the FA Goods product. Before using the product, please read this User s Manual and the relevant manuals carefully

More information

Series ZSE30/ISE30. High Precision, 2-color Display Digital Pressure Switch. With One-touch fittings are newly introduced. PSE

Series ZSE30/ISE30. High Precision, 2-color Display Digital Pressure Switch. With One-touch fittings are newly introduced. PSE High Precision, 2-color Display Digital Pressure Switch Series SE30/ISE30 SE ISE PSE I SE3 PS I SE 1 2 SP ISA2 IS SM PF2 IF Data With One-touch fittings are newly introduced. Straight type Elbow type 16-2-1

More information