TYPES DS II AND DSL II METAL ENCLOSED LOW VOLTAGE POWER CIRCUIT BREAKERS

Size: px
Start display at page:

Download "TYPES DS II AND DSL II METAL ENCLOSED LOW VOLTAGE POWER CIRCUIT BREAKERS"

Transcription

1 om.c ww w.e lec tri ca lp ar tm an ua ls TYPES DS II AND DSL II METAL ENCLOSED LOW VOLTAGE POWER CIRCUIT BREAKERS

2 Proven Technology with the Enhancements and Additional Ratings Our Customers Asked For For over 25 years, Types DS and DSL Low Voltage AC Power Circuit Breakers have continually set industry standards for quality, reliability, and extended operating life resulting in the largest installed base of low voltage power circuit breakers. But electrical distribution system requirements are changing and our customers asked for enhancements that provide the capabilities of more accessories, more communications, easier wiring, and improved protection. And they emphasized that we add these enhancements without altering the breakers proven construction and performance characteristics. That s just what we did and the enhanced DSII and DSLII Breakers provide exactly what our customers require. We even added new ratings to help meet their expanding distribution system requirements. Where They re Used DSII and DSLII Breakers are designed specifically for use in metal-enclosed low voltage switchgear assemblies applied at nominal system voltages of , 80, or 600V AC. Six continuous current frame sizes, 800 through 5,000 amperes are covered by just three breaker frame sizes. Above 20V AC, DSII and DSLII Breakers have a short time rating that is equal to the instantaneous rating. This provides for better downstream coordination, allowing the breaker closest to the fault to trip. DSII and DSLII Breakers are also fully interchangeable, meaning they can be placed into compartments having the same dimensions and ratings. 100 Percent Rated DSII and DSLII Beakers are 100 percent rated, UL listed, and are built and tested to applicable NEMA, ANSI, IEEE, and UL standards in an ISO 9001 certified facility. Quality and Reliability Cutler-Hammer performs consistent endurance and reliability tests on DSII and DSLII Breakers. Mini-Life Tests. Daily, a breaker is randomly selected from the production line and tested for an average 150 mechanical operations to assure performance as required. Maxi-Life Tests. MTBF testing continuously tests DSII and DSLII Breakers until they fail. This identifies any weak links in the breaker mechanism and also demonstrates how design changes improve the performance and quality of the breakers. 2 Cutler-Hammer Products Low Voltage AC Power Circuit Breakers Types DSII and DSLII... The Best Has Become Better Ratings Type DSII-620 Low Voltage AC Power Circuit Breaker (left) and Type DSLII-308 (right) both shown with optional Digitrip RMS 910 Trip Units. Breaker Type Frame Interrupting Ratings, rms Symmetrical Amperes Size Amperes With Instantaneous Trip Without Instantaneous Trip➀➁ V 80V 600V 208V-20V 80V 600V Type DSII Circuit Breakers DSII ,000 30,000 30,000 30,000 30,000 30,000 DSII ,000 50,000 2,000 50,000 50,000 2,000 DSII ,000 65,000 50,000 65,000 65,000 50,000 DSII ,000 50,000 2,000 50,000 50,000 2,000 DSII ,000 65,000 50,000 65,000 65,000 50,000 DSII ,000 65,000 50,000 65,000 65,000 50,000 DSII ,000 65,000 65,000 65,000 65,000 65,000 DSII ,000 85,000 85,000 85,000 85,000 85,000 DSII ,000 85,000 85,000 85,000 85,000 85,000 Type DSLII Circuit Breakers DSLII DSLII DSLII All Types 200,000 on System Voltages 600 or Below DSLII DSLII ➀ Also short time ratings. ➁ Short circuit ratings of nonautomatic breakers except the DSII-80 and DSII-850 which are 65,000. Breaker Weights/Dimensions ➀ Breaker and drawout fuse truck in separate interlocked compartments. Note: DSLII-308, DSLII-516, and DSLII-620 include current limiters integral with drawout breaker elements. DSLII-632 includes DSII-632 Breaker and DSLII-80 includes DSII-80 Breaker and DSII-FT0 drawout fuse truck, in separate interlocked compartments. Breaker Type Frame Size Dimensions Inches Weight Pounds Amperes Height Width Depth Type DSII Circuit Breakers DSII DSII DSII DSII DSII DSII DSII DSII DSII Type DSLII Circuit Breakers DSLII DSLII DSLII DSLII-632➀ DSLII-80➀

3 Up to 60 Contact Points and Only One Standard Connection Drawing The one standard connection drawing feature provides significant time savings because a switchgear builder can prewire a harness prior to installation, making connections to the secondary and zone selective interlocking (ZSI) contacts when the breaker is being installed in the cell. Zone Selective Interlocking Low Voltage AC Power Circuit Breakers New Secondary Contacts Provide for More Accessories and Easier Wiring New Secondary Contacts DSII and DSLII Breakers are now available with up to 8 points of secondary contact in modules of 12 contacts each. More secondary contacts facilitate wiring while providing for nearly twice the number of breaker accessory connections. Standard Breaker Secondary Wiring Diagram Viewed from Front View of Switchgear Cell UV F1 UV LCS ATR ALARMS OTS 3 Auxiliary Switch 2 or OTS RESET NO NO NO NC NC NC F0 A6 SR COM ATR MOT G OTS 1 & 2 or MOT PWR F1 SR Zone Interlock/Communication 12 Point Plug Detail Zone 1 Zone 2 Zone 3 Fault 1 Zone Interlock 1 Z1 DG 2 Z2 SOUT 3 Z3 SIN Fault 2 Breaker Number 1 Fault 3 5 Breaker Number 2 LOAD Breaker Number 3 Z GOUT Z5 GIN Ground Fault Setting: 1200A Pickup 0.5 Seconds Time Delay Ground Fault Setting: 600A Pickup 0.3 Seconds Time Delay Zone Selective Interlock Wiring Ground Fault Setting: 300A Pickup No Time Delay Zone Interlock/Communication Plug NO NO ST GF NC NC Auxiliary Switch 1 Auxiliary Switch Communications 6 C6 COM1 9 C9 12 C12 COM CLOSE 7 8 C7 COM2 C8 10 C10 SHIELD 11 C11 NPOW Fault 1 There are no interlocking signals. The main breaker trip unit will initiate the trip instantaneously. Fault 2 The feeder breaker trip unit will initiate the trip instantaneously to clear the fault; and Zone 2 will send an interlocking signal to the Zone 1 trip unit. The Zone 1 trip unit will begin to time out, and in the event that the feeder breaker in Zone 2 would not clear the fault, the main breaker in Zone 1 will clear the fault in 0.5 seconds. Fault 3 The branch breaker trip unit will initiate the trip instantaneously to clear the fault; and Zone 3 will send an interlocking signal to the Zone 2 trip unit; and Zone 2 will send an interlocking signal to Zone 1. Zone 1 and Zone 2 trip units will begin to time out, and in the event that the branch breaker in Zone 3 would not clear the fault, the feeder breaker in Zone 2 will clear the fault in 0.3 seconds. Similarly, in the event that the feeder breaker in Zone 2 would not clear the fault, the main breaker in Zone 1 will clear the fault in 0.5 seconds. Typical Cell Can Be Prewired and Ready to Accept DSII Circuit Breaker A typical OEM cell shown prewired and ready to accept the breaker as delivered from the factory, assuring a positive connection of all contacts. Wiring for zone selective interlocking and/or IMPACC / PowerNet communications is connected in a pin which is easily inserted into the socket plug. This design also provides for ease of wiring when a customer s requirements increase, requiring the addition of accessories, zone selective interlocking, or IMPACC / PowerNet communications. New Internal Zone Selective Interlocking Contacts For customers whose distribution systems require the added protection of zone selective interlocking (ZSI), we placed the floating design socket plug with 12 points of contact internal to the breaker, next to the secondary disconnect contacts providing for ease of wiring. Zone Selective Interlocking Provides Positive System Coordination without Time Delays Cutler-Hammer pioneered ZSI, which allows the breaker closest to the fault to trip without any preset time delay. Through a hardwired connection between a downstream breaker s Digitrip Trip Unit and a DSII or DSLII main breaker s Digitrip Trip Unit, a restraining signal is sent upstream. This allows the breaker closest to the fault to trip instantaneously while the remainder of the distribution system remains on line, thus avoiding unnecessary and often costly downtime. IMPACC / PowerNet Communications The floating design socket plug is also used when customers require the highly reliable, comprehensive power monitoring capabilities provided by the IMPACC / PowerNet communications system. 3

4 Built-In Safety Features Provide Optimum Operator Safety and System Security Four position automatic mechanical interlocking system when the breaker is in a breaker compartment. 1. Remove. The breaker is nearest the front of the compartment and open with the closing springs discharged. It cannot be closed electrically or manually. It is padlockable in this position. 2. Disconnect. A storage position with the breaker in the compartment but open and disconnected. It can be padlocked in place. 3. Test. Main disconnects are disengaged, secondary contacts are engaged. All functions of the breaker and trip unit can be tested in this position.. Connected. Both main and secondary contacts are connected and the breaker is ready for normal operation. Deadfront faceplate shield isolates the operator from high voltage when the breaker is energized. When the breaker is in a compartment, the compartment door acts as a double deadfront shield. Padlocking provision enables the breaker to be padlocked in a trip-free condition. The breaker cannot be closed or moved with the levering device. The padlock itself is placed in the padlock plate that extends through the front of the breaker faceplate. This helps prevent unauthorized racking and operation of the breaker. Glass polyester insulation provides sufficient mechanical strength to resist short circuit forces and is highly resistant to heat and arcing. Interference interlocks are provided to prevent insertion of breakers with mismatched disconnects or insufficient interrupting ratings into compartments carrying a higher current. Electrical lockout for manually operated breakers prevents closing of an unenergized circuit. When the circuit is energized, the breaker can be closed by pushing the push-to-close mechanism release button. Closed breaker interlock prevents operation of the spring release when the breaker is already closed. DE-ION Arc Extinguishers Provide Superior Arc Quenching Cutler-Hammer developed the DE-ION arc extinguisher that assists in the interruption of high energy faults by dissipating the large amounts of arc energy. Each arc extinguisher includes a series of steel plates that attract the arc and interrupt it by cooling and stretching the arc. Cutler-Hammer Products Types DSII and DSLII Breakers Provide Safety, Security, and Easier Operation User Friendly Operation Types DSII and DSLII Breakers Controls and indicators are functionally grouped on the front of the breakers Rear and front views of Type DSII-620 Low Voltage AC Power Circuit Breaker. 15 Standard Digitrip RMS Trip Unit Drawout Position Indicator Shutter Covering Access to Levering Shaft (Shown in Closed Position) Open-Close Indicator Metal Faceplate Shield Manual Charge Handle Padlock Plate Push-to-Trip Button Push-to-Close Mechanism Release Button 10 Spring Charge Indicator 11 Interphase Barriers 12 Secondary Disconnects 13 Zone Selective Interlock/ IMPACC / PowerNet Communications Plug 1 Main Disconnects 15 Levering Device Arm 16 DE-ION Arc Chute

5 Type DSLII Circuit Breakers Extend Interrupting Ratings up to 200 ka rms Symmetrical DSLII Breakers are a combination of series connected current limiters and standard DSII Breakers extending the interrupting rating of DSII Breakers up to 200 ka. Consequently, they re used on systems where the overload protection and switching functions of air power breakers are required and available fault currents exceed the interrupting ratings of the circuit breakers alone and/or exceed the withstand and interrupting ratings of downstream circuit components. Current Limiters Mounting 800, 1600, and 2000 Ampere Breakers: Integrally mounted in the drawout breaker and 000 Ampere Breakers: Mounted on separate drawout trucks that fit into compartments of equal size to their compatible breakers and are positioned adjacent to one another. Exclusive Features 1 Fault Interruption. On overloads and faults within the breaker interrupting rating, the breaker protects the limiters. On higher fault currents exceeding the breaker rating, the limiters protect the breaker. 3 Low Voltage AC Power Circuit Breakers Types DSII and DSLII Breakers Are Simple to Inspect and Easy to Maintain Blown Limiter Indicators Isolating Transformers for Blown Fuse Indicators Zone Selective Interlock/IMPACC/PowerNet Communications Plug Current Limiters Secondary Disconnects Main Disconnects With properly selected and coordinated limiters, the breaker itself will clear overloads and faults within its interrupting rating, leaving the limiters intact and undamaged. The limiters will provide fast interruption of fault currents beyond the breaker rating up to a maximum 200 ka rms symmetrical. Single-Phasing Protection. Interlock arrangements trip the breaker whenever any limiter blows, preventing singlephasing. The breaker cannot be reclosed on a live source unless there are three unblown limiters on the breaker. There are three blown limiter indicators on the breaker faceplate, providing a visual indication when a limiter in any phase has interrupted a fault. Safety Features. Current limiters on Types DSLII-308, DSLII-516, and DSLII-620 Breakers are accessible only when a breaker has been completely withdrawn from its compartment. For Types DSLII-632 and DSLII-80 Breakers, current limiters are mounted on a separate fuse truck. It is key interlocked with the breaker to prevent withdrawal or insertion unless the breaker is disconnected. Designed for Easy Access, Inspection, and Minimal Maintenance The stored energy mechanism and control devices are easily accessible (in the remove and disconnect positions) and can be inspected by removing the front panel. Inspection, minor maintenance when required (such as lubricating the mechanism), and accessing the control components is simplified. Additionally, many minor replacement functions involving the mechanism, control, and/or accessory devices can be easily accomplished. True Two-Step Stored Energy Mechanism for Manually and Electrically Operated Breakers Stored energy is energy held in waiting, ready to open or close the breaker within five cycles or less. The unique cam and spring design provides necessary energy for a single close-open sequence as well as the energy for multiple charge-close operations such as this possible sequence: charge-close-recharge-open-close-open. This means the energy required to open the breaker is always prestored following a closing operation. On manually operated breakers, closing springs are charged by hand. For electrically operated breakers, springs are normally charged by an electric motor but can be manually charged in the absence of control power. More Information Further information and pricing can be found in PL.22B.01.P.E. 5

6 Cutler-Hammer introduced the first microprocessor-based trip unit and has advanced this technology into a new family of Digitrip RMS Electronic and Digitrip OPTIM Programmable Trip Units. Digitrip RMS 510 is the standard trip unit of DSII and DSLII Breakers. It enables the user to select as many as nine phase and Digitrip RMS Electronic and OPTIM Programmable Trip Units Selection Guide Digitrip RMS 510 is standard. For Voltage/Rating information, refer to Page 2. TRIP UNIT SENSING Cutler-Hammer Products RMS 510 RMS 610 OPTIM 750 RMS 810 RMS 910 OPTIM 1050 rms Sensing Yes Yes Yes Yes Yes Yes PROTECTION AND COORDINATION Protection Ordering Options LI, LS, LSI, LIG LI, LSI, LIG LSI(A), LSIG LI, LS, LSI, LIG LI, LS, LSI, LIG LSI(A), LISG LSG, LSIG LSG, LSIG LSG, LSIG LSG, LSIG Fixed Rating Plug (I n) Yes Yes Yes Yes Yes Yes Overtemperature Trip Yes Yes Yes Yes Yes Yes Long Adjustable Rating Plug (I n) No No No No No No Delay Long Delay Setting (l n) x (I n) x (I n) x (I n) x (I n) x (I n) Protection Long Delay Time I 2 t 2-2 Seconds 2-2 Seconds 2-2 Seconds 2-2 Seconds 2-2 Seconds 2-2 Seconds Long Delay Thermal Memory Yes Yes Yes Yes Yes Yes High Load Alarm No 0.85 x I r x I r 0.85 x I r 0.85 x I r x I r Short Short Delay Setting % S1 & S2 x (I r) % S1 & S2 x (I r) % x (I r) % S1 & S2 x (I r) % S1 & S2 x (I r) % x (I r) Delay Short Delay Time I 2 t ms ms ms ms ms ms Protection Short Delay Time Flat ms ms ms ms ms ms Short Delay Time ZSI Yes Yes Yes Yes Yes Yes Instantaneous Instantaneous Setting % M1 & M2 x (l n) % M1 & M2 x (l n) % x (l n) % M1 & M2 x (l n) % M1 & M2 x (l n) % x (l n) Discriminator 0Yes➀ 0Yes➀ Yes 0Yes➀ 0Yes➀ Yes Protection Instantaneous Override Yes Yes Yes Yes Yes Yes Ground Ground Fault Setting % x (I n)➁ % x (I n)➁ 20/25-100%➁ % x (I n)➁ % x (I n)➁ 20/25-100%➁ Fault Ground Fault Delay I 2 t ms ms ms ms ms ms Protection Ground Fault Delay Flat ms ms ms ms ms ms Ground Fault ZSI Yes Yes Yes Yes Yes Yes Ground Fault Thermal Memory Yes Yes Yes Yes Yes Yes SYSTEM DIAGNOSTICS Cause of Trip LEDs Yes Yes Yes Yes Yes Yes Magnitude of Trip Information No Yes Yes Yes Yes Yes Remote Signal Contacts No Yes Yes Yes Yes Yes SYSTEM MONITORING Digital Display No Yes 0Yes➂ Yes Yes 0Yes➂ Current No Yes Yes Yes Yes Yes Voltage No No No No Yes Yes Power and Energy No No No Yes Yes Yes Power Quality Harmonics No No No No Yes Yes Power Factor No No No 0Yes Yes Yes SYSTEM COMMUNICATIONS IMPACC / PowerNet No No Yes Yes Yes Yes FIELD TESTING Testing Method➄ Integral Integral OPTIMizer, BIM, Integral Integral OPTIMizer, BIM, IMPACC / PowerNet IMPACC / PowerNet ➀ LS, LSG only. ➁ Not to exceed 1200A. 6 ➂ By OPTIMizer/BIM. Over IMPACC / PowerNet only. A Wider Selection of Trip Units Provide Expanded Protection Capabilities ground current protection settings for maximum flexibility in trip-curve shaping and multi-unit coordination. For more sophisticated distribution systems, other Digitrip Electronic or Programmable Trip Units may be specified to provide IMPACC / PowerNet communications, systems diagnostics information, and systems ➄ Set by adjustable rating plug. monitoring information including power factor, voltage values, harmonic distortion values, and waveform capture. For additional Digitrip information, contact your Cutler-Hammer distributor or sales engineer. I n = Rating plug rating. I r = LDPU setting. I s = Sensor rating. BIM = Breaker Interface Module.

7 IMPACC / PowerNet Communications: A Highly Reliable System that Will Improve the Operating Efficiency of Your Plant or Building As a high frequency-based system, IMPACC / PowerNet is unaffected by the electromagnetic fields that result when current flows through conductors. This helps provide for increased reliability while significantly reducing equipment and installation costs. A master control unit (connected to the DSII or DSLII Breaker with a shielded twisted pair communications wire) is used to monitor, control, and communicate with the breaker s Digitrip RMS Trip Unit. The master control unit may be a personal A Full Range of Factory Installed Breaker Accessories Electrical Operator. A universal type electric motor, internal to the breaker, that charges the springs automatically. Shunt Trip for Manually Operated Breakers. Provides remote controlled tripping. Undervoltage Release Instantaneous. Trips the breaker instantaneously when voltage on its coil falls between 30 to 60 percent of normal. Low Voltage Switchgear Structural Components DSII Power Modules Complete structures including fully equipped breaker compartments. The switchgear manufacturer provides value-added items such as doors, bus, cable area compartment, instruments, relays, and associated wiring. Low Voltage AC Power Circuit Breakers IMPACC / Power Net Communications, Breaker Accessories, and Structural Components On-Site Location Off-Site Location Undervoltage Release Time Delay. Provided with a nonadjustable time delay that prevents the breaker from tripping during momentary fluctuations of system voltage. Auxiliary Switches. Provide the capability to remotely indicate if the breaker is open or closed and may be used on breakers with either manually or electrically operated stored energy mechanisms. Two types of auxiliary switches are available: 2A/2B switches have two The Cutler-Hammer value-added modular approach for assembling low voltage switchgear featuring DSII Breakers and structures provides switchgear manufacturers DSII Substructure The basic assembled breaker supporting structure including breaker mounting pan, contact mounting plate, stationary main contacts, drawout extension rails, and side and back sheets. The switchgear manufacturer provides value-added items such as doors, bus, cable area compartment, instruments, relays, and associated wiring. computer, an existing building management system, a programmable logic controller, or a distributed control system. Through IMPACC / PowerNet, information communicated from a DSII or DSLII Breaker includes breaker status (open/close/trip), cause and magnitude of trip, metering values, trip rating, and time stamping of events. The breaker itself can be remotely opened or closed. For additional IMPACC / PowerNet information, contact your Cutler-Hammer distributor or sales engineer. normally open and two normally closed contacts. 5A/5B switches have five normally open and five normally closed contacts. Operation Counter. A mechanical counter that provides a record of the number of breaker operations. Contact your Cutler-Hammer distributor or sales engineer for a complete list of accessories. with opportunities to add the most value to their low voltage switchgear. For more information refer to PL.B.0.P.E. DSII Breaker Cell Parts Breaker mounting pan, contact mounting plate, and stationary main contacts. In addition to assembling these parts, the switchgear manufacturer provides value-added items such as doors, bus, cable area compartment, side sheets, instruments, relays, and associated wiring. Breaker cell parts are available individually or as an entire kit. 7

8 Cutler-Hammer, a part of Eaton Corporation, is a worldwide leader providing customer-driven solutions. From power distribution and electrical control products to industrial automation, Cutler-Hammer utilizes advanced product development, world-class manufacturing, and offers global engineering services and support. For more information on Cutler-Hammer products, call or , for engineering services call , or visit our website at Pittsburgh, Pennsylvania U.S.A. Publication No. B.22B.01.S.E February 2001 Printed in U.S.A. / CMS 2159 B22B01SE

Magnum IEC Low Voltage Air Circuit Breakers

Magnum IEC Low Voltage Air Circuit Breakers Magnum IEC Low Voltage Air Circuit Breakers Product Focus Up to 690 Vac 42 ka to 100 ka Icu 800 to 6300 Amperes EN 60947-2 A Global Source for Innovative Electrical Power Distribution Solutions Proven

More information

Cutler-Hammer May 2001

Cutler-Hammer May 2001 Low-Voltage Power Circuit Breakers Magnum DS General Description Index Page General Description Magnum DS............. A1-1 General Description DSII/DSLII............... A1-7 Technical Data Magnum DS.

More information

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035 Instruction Bulletin 4402-997-0 February 999 Middletown, OH, USA DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 605 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker

More information

Magnum IEC Low Voltage Air Circuit Breakers

Magnum IEC Low Voltage Air Circuit Breakers Magnum IEC Low Voltage Air Circuit Breakers Product Focus Up to 690 V ac 42 ka to 0 ka I cu 800 to 6300 A IEC 60947-2 Proven Performance Expanded Capabilities High Withstand Ratings A global source for

More information

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII Effective July 2010 Supersedes July 1997 IB694C694-02 Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII Effective July 2010 PURPOSE This

More information

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs. SECTION 16904 MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS PART 2 PRODUCTS 01 MANUFACTURERS A. B. C. Eaton * * The listing of specific manufacturers above does not imply acceptance of their products

More information

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut Page 1 Supersedes Renewal Parts Data 33-790-1G pages 1-20 dated December, 1988 Mailed to: C, D, E/33-700 Westinghouse DS and DSL Low Voltage Power Circuit Breakers and Cell Parts Contents Pages DS Breaker

More information

Switchgear. Low Voltage

Switchgear. Low Voltage January 2001 Vol. 1, Ref. No. [0923] -1 Low Voltage Switchgear Contents Description Page Magnum DS Metal-Enclosed Product Description........................................... -2 Application Description........................................

More information

2.2. Molded Case Circuit Breakers. Contents. NG-Frame ( Amperes) Series G

2.2. Molded Case Circuit Breakers. Contents. NG-Frame ( Amperes) Series G . NG-Frame (00 ) NG-Frame (30 00 s) Product All Eaton NG-Frame circuit breakers are suitable for reverse feed use All NG-Frame circuit breakers are HACR rated Contents Page EG-Frame (5 5 s)..................

More information

Critical Power Switchboards. Selection and Application Guide

Critical Power Switchboards. Selection and Application Guide Selection and Application Guide Siemens RCIII (rear connected) switchboards utilizing Siemens Type SB Encased Breakers are a perfect solution for your critical power distribution needs. Whether your installation

More information

FOR PRICES ON DSII and DSLII BREAKERS, REFER TO PRICE LIST PL.22B.01.P.E

FOR PRICES ON DSII and DSLII BREAKERS, REFER TO PRICE LIST PL.22B.01.P.E Supersedes PL.44B.04.P.E Dated September 1998 600 Volts AC Maximum 200 ka, RMS Sym. Short Circuit Maximum 800-5000 Amps Continuous Effective: October 1999 Page 1 Index Page Table Description/Application...

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS DIVISION 26 ELECTRICAL SECTION 26 28 19 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection

More information

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Specification for 70mm pole pitch Air circuit breaker up to 1600 A Specification for 70mm pole pitch Air circuit breaker up to 1600 A Protective device for low voltage electrical installation Last update :2011-07-08-1 - Table of contents: 1 General...3 2 Compliance with

More information

Power Break II Switchboard

Power Break II Switchboard Power Break II Switchboard Now available with PowerBreak II Circuit Breakers through 4000A GE s Power Break II Switchboard is now available with the new Power Break II Insulated Case Circuit Breaker (800A

More information

POWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers

POWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers POWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers Class 6037 CONTENTS Schneider Electric Brands Description Page Product Description..................................................

More information

.1 Low Voltage Switchgear Magnum DS Switchgear with Molded Case Circuit Breaker Feeder Section Cross-Reference Eaton s Electrical Sector has an organi

.1 Low Voltage Switchgear Magnum DS Switchgear with Molded Case Circuit Breaker Feeder Section Cross-Reference Eaton s Electrical Sector has an organi Low Voltage Switchgear Magnum DS Switchgear.1 Cross-Reference................................................ 102 Product Description............................................. 102 Application Description...........................................

More information

17.1. Low Voltage Switchgear. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents

17.1. Low Voltage Switchgear. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents .1 Low Voltage Switchgear Magnum DS Metal-Enclosed Magnum DS Switchgear with Molded Case Circuit Breaker Feeder Section Cross-Reference Eaton s Electrical Sector has an organization dedicated to the support

More information

3.1. Power Breakers, Contactors and Fuses. Contents. Series NRX Low Voltage Power Circuit Breakers. Power Circuit Breakers

3.1. Power Breakers, Contactors and Fuses. Contents. Series NRX Low Voltage Power Circuit Breakers. Power Circuit Breakers .1 Series NRX Low Voltage Series NRX Low Voltage Product Description Series NRX is a low voltage power circuit breaker suitable for UL 1558, UL 891, and IEC switchgear and switchboards. The compact size

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

SECTION 16426B. RELATED SECTIONS Section 16671A Transient Voltage Surge Suppression Section Microprocessor-Based Metering Equipment

SECTION 16426B. RELATED SECTIONS Section 16671A Transient Voltage Surge Suppression Section Microprocessor-Based Metering Equipment METAL-ENCLOSED DRAWOUT SWITCHGEAR (DSLII) LOW VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install, where indicated on the drawings, a deadfront type, low voltage metal-enclosed

More information

Table Line and Load Terminals. Terminal Body Material. Wire Type. Aluminum Copper Aluminum. English English English.

Table Line and Load Terminals. Terminal Body Material. Wire Type. Aluminum Copper Aluminum. English English English. -174 Series C Molded Case Circuit s July 7 Molded Case Switches Refer to Eaton for UL listed, series tested Molded Case Switch application data. Table -278. Molded Case Switches Cont. Amp Rating at 40

More information

Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide

Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide GE Industrial Solutions Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide TABLE OF CONTENTS Description Page 1.0 General Information...... 1 1.1 Protection..... 1 2.0 UL Listed Devices...

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

Low Voltage Switchgear

Low Voltage Switchgear Low Voltage Switchgear Magnum DS Switchgear.1 Cross-Reference......................................... Product Description....................................... Application Description....................................

More information

Power Breakers, Contactors and Fuses

Power Breakers, Contactors and Fuses Power Breakers, Contactors and Fuses Power Breakers, Contactors and Fuses Family.1 Power Circuit Breakers Low Voltage Power Circuit Breakers.......................... Magnum DS Low Voltage Power Circuit

More information

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers Specification Guide for RMAX Direct Replacement AC Low Voltage Power Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards... 3 3.0 Supplier Qualifications... 3 4.0 Mechanical and

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers Cutler-Hammer Installation Instructions for the Digitrip OPTIM 550 3-Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers Table of Contents Description Page 1.0 General Information......................1

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

Controlled Power HSN High Speed DC Circuit Breakers

Controlled Power HSN High Speed DC Circuit Breakers Controlled Power HSN High Speed DC Circuit Breakers Each CP Type HSN circuit breaker unit can consist of either a wheeled truck and housing or be panel mounted. The circuit breaker can be mounted on the

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

Air Circuit Breakers

Air Circuit Breakers Siemens AG 203 /2 Introduction 3WL air circuit breakers/ non-automatic air circuit breakers up to 6300 A (AC), IEC /8 Introduction /9 3-pole, fixed-mounted versions /6 3-pole, withdrawable versions /23

More information

Air Circuit Breakers

Air Circuit Breakers Siemens AG 204 /2 Introduction 3WL air circuit breakers/ non-automatic air circuit breakers up to 6300 A (AC), IEC /8 Introduction /9 3-pole, fixed-mounted versions /6 3-pole, withdrawable versions /23

More information

Power Breakers, Contactors and Fuses

Power Breakers, Contactors and Fuses Power Breakers, Contactors and Fuses Family.1 Power Circuit reakers Low Voltage Power Circuit Breakers........................... Magnum DS Low Voltage Power Circuit Breakers................ Magnum MDSL

More information

SECTION 16311A INTEGRATED UNIT SUBSTATIONS (IUS) SECONDARY LESS THAN 1000 V

SECTION 16311A INTEGRATED UNIT SUBSTATIONS (IUS) SECONDARY LESS THAN 1000 V INTEGRATED UNIT SUBSTATIONS (IUS) SECONDARY LESS THAN 1000 V PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the integrated unit substation (IUS) complete from the incoming line terminals

More information

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage Switchgear Low Voltage Introduction...13-1 AKD-10 Low-Voltage Switchgear...13-3 AKD-20 Low-Voltage Switchgear...13-3 Low Voltage Switchgear GE low-voltage switchgear is heavy-duty equipment built to ANSI

More information

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI . Technical Data and Specifications Ratings Frames EG, JG and LG EG JG LG Maximum rated current (amperes) 15, 160 1 50 400, 630 Breaker type 3 B B E S S H H C E S H C U X E S H C U X of poles 1, 3, 4,

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter

More information

OTEC Transfer switch open transition

OTEC Transfer switch open transition Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator

More information

.1 Power Circuit Breakers Power Circuit Breaker Low Voltage Power Circuit Breakers Product Overview Magnum Low Voltage Power Circuit Breakers for Glob

.1 Power Circuit Breakers Power Circuit Breaker Low Voltage Power Circuit Breakers Product Overview Magnum Low Voltage Power Circuit Breakers for Glob Power Breakers, Contactors and Fuses Family.1 Power Circuit Breakers Low Voltage Power Circuit Breakers.......................... Magnum DS Low Voltage Power Circuit Breakers................ Magnum MDSL

More information

VCP-T/T-VAC medium voltage vacuum circuit breakers. Control and protect with Eaton s compact medium voltage circuit breakers

VCP-T/T-VAC medium voltage vacuum circuit breakers. Control and protect with Eaton s compact medium voltage circuit breakers VCP-T/T-VAC medium voltage vacuum circuit breakers Control protect with Eaton s compact medium voltage circuit breakers Eaton Corporation has dedicated years of research, design testing to create a comprehensive

More information

Individual breakers in separate enclosures can be applied in low voltage distribution systems through 600 volts Ac, 50/60 Hertz.

Individual breakers in separate enclosures can be applied in low voltage distribution systems through 600 volts Ac, 50/60 Hertz. Page 2 Introduction The Westinghouse Systems Pow-R Breaker, the worlds first encased power breaker, is not just an extension of existing technology. It represents the biggest breakthrough in circuit protection

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 24 14 600 VOLT DRAWOUT SWITCHGEAR PART 1 - GENERAL 1.01 SECTION INCLUDES: A. Individually mounted rear-accessible low voltage switchgear ANSI rated switchgear and low voltage power circuit breakers

More information

Magnum IEC Low Voltage Air Circuit Breakers

Magnum IEC Low Voltage Air Circuit Breakers Magnum IEC Low Voltage Air Circuit Breakers Product Focus May 2003 Introduction 1 Introduction Overview............................................... 3 One Family...............................................

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

VL Circuit Breaker Features & Benefits. powerful ideas RELIABLE SOLUTIONS

VL Circuit Breaker Features & Benefits. powerful ideas RELIABLE SOLUTIONS VL Circuit Breaker Features & Benefits powerful ideas RELIABLE SOLUTIONS A Solutions Oriented Circuit Protection Family The Tangram An ancient Chinese game in which a few simple components provide endless

More information

Mar H: SUPPLEMENTAL PARALLELING GEAR (16315-H)

Mar H: SUPPLEMENTAL PARALLELING GEAR (16315-H) 2101 Commonwealth Blvd, Suite B Ann Arbor, MI 48105-5759 www.med.umich.edu/facilities/plan/ 263010-H: SUPPLEMENTAL PARALLELING GEAR (16315-H) Related Sections Basis Guideline: N/A For an explanation of

More information

Product Line Overview. The Most Logically Designed Contact Assembly

Product Line Overview. The Most Logically Designed Contact Assembly Circuit Breakers & Supplementary Protectors 15 00 Amperes for UL, CSA & IEC Applications Product Line Overview -3 General Information Cutler-Hammer Series G Molded Case Circuit Breakers provide increased

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General 13 SWITCHGEAR Medium Voltage Equipment -1 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General Overview Features Siemens, 7, 1 and 38kV class medium voltage, one- or two-high vacuum circuit breaker switchgear

More information

AutoLink Frequently Asked Questions

AutoLink Frequently Asked Questions Rev. 3 October 2013 Page 1 of 8 AutoLink Frequently Asked Questions October 2013 1 Rev. 3 October 2013 Page 2 of 8 Table of Contents 1 Background... 4 1.1 What is the AutoLink Single Phase Electronic Sectionalizer?...

More information

DS/DSII Low Voltage Switchgear. Renewal Parts. Cutler-Hammer. Renewal Parts. Effective: October Page 1

DS/DSII Low Voltage Switchgear. Renewal Parts. Cutler-Hammer. Renewal Parts. Effective: October Page 1 New Information Supersedes Data 33-790-1H, dated October 1996 DS/DSII Low Voltage Switchgear Page 1 DS Switchgear Assembly DSII Switchgear Assembly Contents Pages DS Switchgear (Front View) 2 DSII Switchgear

More information

PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers

PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers Catalog 0612CT0101 R02/14 2014 Class 0612 CONTENTS Description............................................. Page General Information..........................................

More information

Eaton Digitrip RMS and Digitrip OPTIM Trip Units with Types DSII and DSLII Low Voltage Power Circuit Breakers

Eaton Digitrip RMS and Digitrip OPTIM Trip Units with Types DSII and DSLII Low Voltage Power Circuit Breakers Effective July 2010 Supersedes July 1997 IL8700C39-03 Eaton Digitrip RMS and Digitrip OPTIM Trip Units with Types DSII and DSLII Low Voltage Power Circuit Breakers Contents Description Page 1.0 Supplementary

More information

Zone Selective Interlocking

Zone Selective Interlocking Application Paper AP02602002EN Supersedes 08/2003 Zone Selective Interlocking Contents Description.... Page What is Zone Selective Interlocking?... 3 What is the purpose of Zone Selective Interlocking?....3

More information

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers The National Electrical Code makes the following statement regarding ground fault conformance testing:

More information

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear 13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of

More information

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear ATLV MaxSG Low Voltage Metal Enclosed Switchgear ABB, INC. Product General Description MaxSG Switchgear ABB MaxSG switchgear is a further continuation in the development of innovative products from ABB,

More information

GE Consumer & Industrial Electrical Distribution. Power Break II. Insulated Case Circuit Breakers

GE Consumer & Industrial Electrical Distribution. Power Break II. Insulated Case Circuit Breakers GE Consumer & Industrial Electrical Distribution Power Break II Insulated Case Circuit Breakers Table of Contents Power Break II Circuit Breakers......................... 3 Basic Configuration.......................................

More information

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear Robert J. Gustin Eaton Fellow Application Engineer, P. E. Southfield, Michigan Definitions Metal-enclosed load interrupter switchgear type ME Metal-enclosed switchgear is defined in ANSI C37.20.3-1987,

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

IN2 Enclosed Switches and Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications Student Resource Building University of California Santa Barbara Clement Fung Lighting Electrical Option APPENDIX E Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection

More information

Industrial Generator Set Accessories. Standard Features. Line Circuit Breakers kw

Industrial Generator Set Accessories. Standard Features. Line Circuit Breakers kw Industrial Generator Set Accessories Line Circuit Breakers 15-2500 kw Standard Features Single Circuit Breaker Kit with Neutral Bus Bar 15-300 kw Model Shown The line circuit breaker interrupts the generator

More information

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC c c SIEMENS Series 8100oT Vacuum Controllers Bulletin CC3802-02 Technological Development Vacuum technology has developed rapidly in recent years and is becoming widely accepted for medium voltage motor

More information

DMX 3 -I 2500 switch disconnectors

DMX 3 -I 2500 switch disconnectors 8704 LIMOGES Cedex Telephone : 0 0 87 87 Fax : 0 0 88 88 DMX 3 200 circuit breakers DMX 3 -I 200 switch disconnectors References: 0 28 20 / 21 / 22 / 23 / 24 / 2 / 2 / 30 / 31/ 32/ 33/ 34 / 3 / 3 / 40

More information

Transfer switch OTEC and OTECSE open transition

Transfer switch OTEC and OTECSE open transition Specification sheet OTEC and OTECSE open transition 125-600 Amp Description OTEC transfer es are designed for operation and ing of electrical loads between primary power and standby generator sets. They

More information

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified. SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

W-VACi IEC medium voltage vacuum circuit breakers 12 kv, 17,5 kv and 24 kv

W-VACi IEC medium voltage vacuum circuit breakers 12 kv, 17,5 kv and 24 kv This is a photographic template your photograph should fit precisely within this rectangle. W-VACi IEC medium voltage vacuum circuit breakers 12 kv, 17,5 kv and 24 kv Mostapha Azzahimi Product Manager

More information

Bolted contact switches. Pringle switches

Bolted contact switches. Pringle switches Bolted contact switches Pringle switches Eaton s Pringle bolted contact switches History Eaton s PringleT switches have helped pioneer the development of high-quality electrical products for commercial

More information

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Solid Dielectric, Three Phase Reclosers CATALOG VS11 Solid Dielectric, Three Phase Reclosers Providing electronic, three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance

More information

Molded Case Circuit Breakers

Molded Case Circuit Breakers Series G Circuit Breakers.1 Introduction Product Overview........................................ V4-T- Typical Applications....................................... V4-T- Series G in Eaton Assemblies...............................

More information

Design Standard. Purpose: Design Standard:

Design Standard. Purpose: Design Standard: Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard

More information

Courtesy of CMA/Flodyne/Hydradyne Motion Control Hydraulic Pneumatic Electrical Mechanical (800) RG H ZG E C

Courtesy of CMA/Flodyne/Hydradyne Motion Control Hydraulic Pneumatic Electrical Mechanical (800) RG H ZG E C Courtesy of CMA/Flodyne/Hydradyne Motion Control Hydraulic Pneumatic Electrical Mechanical (800) 46-5480 www.cmafh.com Selection This information is presented only as an aid to understanding catalog numbers.

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7 Construction Standards Page 1 of 7.1 General.1 New buildings are to be provided with an indoor unit substation designed to accept 15kV and 25kV primary voltages, however, the primary voltage connected

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

GTEC Transfer switch Open transition

GTEC Transfer switch Open transition GTE Transfer switch Open transition 40-2000 amp Description GTE transfer switches combine reliability and flexibility in a small, economical package for transferring loads between a utility and a generator

More information

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12 16kA Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A continuous current, 16kA symmetrical interrupting

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

Transfer switch OHPC open or delayed transition

Transfer switch OHPC open or delayed transition Specification sheet Transfer switch OHPC open or delayed transition 125-800 Amp Description The Cummins Series OHPC PowerCommand automatic transfer switch monitors the primary power source, signals the

More information

Selection and Application Guide Supplement. WL UL Pole Circuit Breakers. usa.siemens.com/wlbreaker

Selection and Application Guide Supplement. WL UL Pole Circuit Breakers. usa.siemens.com/wlbreaker Selection and Application Guide Supplement WL UL1066 4-Pole Circuit Breakers usa.siemens.com/wlbreaker WL Power Circuit Breaker Table of Contents Ratings for UL 1066 (ANSI C37) Circuit Breakers Frame size

More information

Transfer switch OTEC open or delayed transition

Transfer switch OTEC open or delayed transition Transfer switch OTEC open or delayed transition 40-1000 Amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and standby generator sets.

More information

SURE TRIP RETRO KITS

SURE TRIP RETRO KITS RMS CURRENT MEASUREMENT with SURE TRIP RETRO KITS Circuit Breaker Solid State Controls with SURE TRIP LOGIC The Sure Trip Solid State Tripping Systems Have Been Designed, Tested And Produced To all Applicable

More information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

Safety, Reliability and Performance verified with the KEMA KEUR mark. Series G Moulded Case Circuit Breakers

Safety, Reliability and Performance verified with the KEMA KEUR mark. Series G Moulded Case Circuit Breakers Series G Moulded Case Circuit Breakers Product Focus Up to 690 Vac 18kA to 100kA Icu 16-2500 Amperes IEC 60947-2 Safety, Reliability and Performance verified with the KEMA KEUR mark Safety, Reliability

More information

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv TripSaver II Cutout-Mounted Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing s new TripSaver II Cutout-Mounted Recloser: A better solution for overhead lateral circuit protection

More information

Typical Specification

Typical Specification Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,

More information

VersaRupter 5-38 kv Load Interrupter Switch. Technical Guide

VersaRupter 5-38 kv Load Interrupter Switch. Technical Guide VersaRupter 5-38 kv Load Interrupter Switch Technical Guide NOTICE Components in this catalog are intended for use by switchgear assemblers engaged in original equipment manufacturing. All sales are subject

More information

US Brochure. Tmax XT Molded case circuit breakers Simply XTraordinary

US Brochure. Tmax XT Molded case circuit breakers Simply XTraordinary US Brochure Tmax XT Molded case circuit breakers Simply XTraordinary XTraordinary benefits ABB, a global leader in circuit breaker technology is making major investments in the United States to bring extraordinary

More information

Magnum DS, SB and IEC low voltage power circuit breakers Technical product guide

Magnum DS, SB and IEC low voltage power circuit breakers Technical product guide Magnum DS, SB and IEC low voltage power circuit breakers Technical product guide Table of content Overview of the Magnum low voltage circuit breaker Magnum DS family.... 4 Magnum SB family.... 6 Magnum

More information

Descriptive bulletin. ReliaGear ND ANSI narrow frame metal-clad switchgear

Descriptive bulletin. ReliaGear ND ANSI narrow frame metal-clad switchgear Descriptive bulletin ReliaGear ND ANSI narrow frame metal-clad switchgear Table of contents Introduction...3 Vmax/A breaker...4 Instrument transformers...5 Potential transformers...6 15 kv potential transformers...6

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

ACS motor protection circuit breakers KT 7 Introduction

ACS motor protection circuit breakers KT 7 Introduction Introduction Automatic Type 2 coordination The right circuit breaker for all applications The KT 7 circuit breaker family consists of two basic frame sizes of mm and 5 mm in three variations with different

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

Solid Dielectric, Single Phase Recloser