MC 785-SC. Operating Manual (Wall and panel mounting) Type: MANUAL Number of pages: 32 Version: V2.3

Size: px
Start display at page:

Download "MC 785-SC. Operating Manual (Wall and panel mounting) Type: MANUAL Number of pages: 32 Version: V2.3"

Transcription

1 MC 785SC Operating Manual (Wall and panel mounting) Description : MC 785SC Step Control Doc.nr.: 2291 Type: MANUAL Number of pages: 32 Version: V2.3 File: Do2291 MC785SC v23 EN.wpd Software: MC785SC V2.11 By: BJB Date: VDH Products BV Roden Holland Signed: File: Doc'2

2 MC 785SC Client : General Page : 2 of 32 Table of contents 1. Technical specifications... 3 General... 3 Front... 3 Inputs and outputs Functional specifications Control... 6 General... 6 Switching the controller on and off Password Readout and setting the clock The SUCTION part (compressorside)... 7 Readout selection on the SUCTION display Showing status of the compressors Readout or changing the suction pressure (/temperature) setpoint Setting a compressor in or out of service Resetting operation hours of a particular compressor The DISCHARGE part (condenserside)... 8 Readout selection on the DISCHARGE display Showing status of the condensers Readout or changing the discharge pressure (/temperature) setpoint Setting a condenser in or out of service Resetting operation hours of a particular condenser Programming internal settings... 9 Parameter table... 9 *) Table of assignment of relay outputs...18 $) Table of assignment of analog outputs (1Vdc)...19 #) Table of assignment of digital inputs Alarms Function flow...22 Operation of the Pband on the suction pressure side (Compressorside)...22 Overview of the function flow for 4compressors for the switching up and down of compressors...22 Overview of the function flow for compressor with 5cylinders...23 Working of compressor control with unequal steps Front view Diagrams of connections Dimensions...31 The information contained in this document is assumed to be accurate. However VDH Products BV accepts no liability for eventual mistakes or errors and has the right to change this document without notice.

3 MC 785SC Client : General Page : 3 of Technical specifications General Type : MC 785SC (StepControl) Wallmounting: Housing : Grey plastic Material : Polystyrol 454h KG 2 natur BASF Dimensions : 213 x 18 x 85mm (whd) Front : Polycarbonate (IP44) Panelmounting: Housing : Steel plate panel Material : Steel in silver grey Dimensions : 217 x 155 x 85mm (whd) Panel cutout : min. 28 x 146mm (wh) Front : Polycarbonate (IP44) Supply : 23 Vac; 5/6 Hz (1/+5%). Used power : 9 VA Pressure range : /+5 per.1 (Suction: 4/+5 C per.1 C) (Discharge: 3/+1 C per.1 C) Accuracy : ±.5 % of the range Operation temperature : 2/+5 C Operation rel. humidity : 1/+9 % RH not condensing Front Displays : 4digit display for suction pressure (SUCTION) with 7 day LEDs 4digit display for discharge pressure (DISCHARGE) with 7 day LEDs LED bars : 8 LEDs on/off and 8 LEDs delay, for maximal 8 compressors 8 LEDs on/off and 8 LEDs delay, for maximal 8 condenser fans Keys : ON/OFF = On/off key controller with LED indication = Clock key with LED indication PRG = Program key with LED indication RESET/ALARM = Reset alarm key with LED indication (2x) = Up keys (2x) = Down keys SET (2x) = Setpoint keys with LED indication SELECT (2x) = Display select keys at displays MODE/SELECT (2x) = Mode select keys LEDs at displays : (2x) = LED indications for readout in O C (2x) = LED indications for readout in degrees Celsius Hrs (2x) = LED Indications for readout in operation hours % (2x) = LED indications for readout in percentage (2x) = LED indications control is increasing (2x) = LED indications control is decreasing Service (2x) = LED indications service Fail (2x) = LED indications fail (2x) = LED indications alarm

4 MC 785SC Client : General Page : 4 of 32 Inputs and outputs Pressure gauges : Pressure sensor1 Suction (4/2mA signal, PX77/2: 2wire system) Pressure sensor2 Discharge (4/2mA signal, PX77/2: 2wire system) Temperature sensors : SM811 temperature sensor1 Suction (1KOhm PTC, 2wire) SM811 temperature sensor2 Discharge (1KOhm PTC, 2wire) Analog outputs : Out1 [1] (/1Vdc signal, 2wire (Rb min. 1 Kohm) Out2 [2] (/1Vdc signal, 2wire (Rb min. 1 Kohm) Communications : RS485 Network (2wire shielded; A,B,GND) I 2 Cbus (extensionbus) (2wire shielded; SDA, SCL, V) Relays : Relay1 [1] programmable. (C/NO/NC, 25Vac/1A not inductive) Next relays have one common; Relay2 [2] programmable (NO, 25Vac/1A not inductive) Relay3 [3] programmable (NO, 25Vac/1A not inductive) Relay4 [4] programmable (NO, 25Vac/1A not inductive) Relay5 [5] programmable (NO/NC, 25Vac/1A not inductive) 2. Functional specifications The MC 785SC is an 8stage step controller, which controls maximal 8 compressors and 8 condenser fans stepping up or down, based on the measured suction and discharge pressure and its setpoints. To control stepping up or down the controller can be set to the following choices: Compressor control: On/off control, with or without valve lifting (xstage compressors) or Frequency control Condenser control: On/off control or Frequency control The controller can also step up or down a compressor or condenser, based on the total operation hours or based on the power of the compressors or condensers. It is also possible to disable compressors or condensers for maintenance or when a failure occurs. To safeguard the control it is possible to set: a minimum and maximum pressure alarm, a minimum and maximum pressure failure, a minimum and maximum temperature alarm, a minimum and maximum temp. failure. All inputs and outputs can be assigned thru setting internal parameters, so an efficient use of the inputs and outputs is possible. If not enough inputs or outputs are available on the controller these can be extended by use of extra LMS Modules connected at the I 2 Cbus. At max the following LMS modules can be connected to the controller; 4 extra LMSRelayModules, with 4 relays per module (uses a 1mA per module) 4 extra LMSAnalogoutModules, with 4 analog outputs per module (uses 1mA /mod) 4 extra LMSDigitalinModules, with 6 digital inputs per module (uses 1mA/module) To use these modules sufficient SupplyModule(s) must be used, see connection drawing 1822.

5 MC 785SC Client : General Page : 5 of 32 5 relay outputs and 2 analog outputs are standard on the MC785SC, there are no digital inputs available, all other needed outputs can be obtained thru extra LMSmodules. Output(s) can by assigned to: Compressor on relay Compressor no load on relay Compressor 5% relay for 2stage (valve lifting) compressors. Compressor 66% relay + 33% relay for 3stage (valve lifting) compressors. Compressor 75% relay + 5% relay + 25% relay for 4stage (valve lifting) compressor. Compressor 8% relay + 6% relay + 4% relay + 2% relay for 5stage (valve lifting) compr. Attention: For compressors with more cylinders only the first valve lifting relay will be assigned, the following relays required will be assigned automatically after the previous relay(s). e.g. Compressor1 as 4stage compressor (Parameter P11=4) and the first valve lifting relay assigned to relay 3 of the first LMS Relay Module (Parameter P113 = 1 3") gives: Relay3 of LMSRelayModule 1 = 75% valve lifting contact, Relay4 of LMSRelayModule 1 = 5% valve lifting contact and Relay1 of LMSRelayModule 2 = 25% valve lifting contact. Compressor analog output...1vdc Condenser on contact Condenser 5% / 1% relay for a 2stage condenser. Condenser analog output...1vdc Input(s) can by assigned to: Compressor failure Condenser failure (with NC (normally closed) or NO (normally open) input contact) (with NC (normally closed) or NO (normally open) input contact) A general alarm is also available to be assigned. This relay is normally active CNO is closed and when an alarm occurs, which has not been reset, the relay switches off CNC is closed. All settings and controls can be authorised by a password, to prevent unauthorised using of the controller. There is also a RS485network available on the controller for controlling the MC785SC by a PC. For this job the controller must be attached to a PCinterface and the PC must have an installed software program for this job.

6 MC 785SC Client : General Page : 6 of Control The MC785SC is divided into two parts: on the left side is the compressor part (SUCTION) and on the right side is the condenser part (DISCHARGE). Both these parts are almost identical for control or readout. The current status of the controller is shown on the front. General: Switching the controller on and off. By pressing the ON/OFF key the controller can be switched on or off. Password. Before any change can be made, the controller will ask for a password. In the SUCTION display appears Code and in the DISCHARGE display. By pressing the UP or DOWN keys the last number will be changed, set it to the right number (see parameter 999). By pressing the SELECT key the next number can be set (with the UP or DOWN keys). All four numbers must be set to the correct code (P 999) and, as a last action, press the SELECT key. If the code is correct, the settings of the controller can now be changed. The correct password can be used for 2 minutes, after which time it deactivates so that the controller is locked again. The password can be set at the internal parameter P999 and is set on a default value as shown in the parameter table. Attention: Remember a set password well and keep it in a safe place! Readout and setting the clock. Press the CLOCK key to readout the time on the DISCHARGE display. To set the clock, first readout the clock as above, then press the right SELECT key in order to change the hours and minutes with the right UP and/or DOWN keys. Then press the right SELECT key again to change the day setting with the right UP and/or DOWN keys. Finally, press the right SELECT key yet again to activate the new time setting. If no key is pressed for 1 seconds, the controller will return to its normal function.

7 MC 785SC Client : General Page : 7 of 32 The SUCTION part (compressorside): Readout selection on the SUCTION display. By pressing the left SELECT key next to the SUCTION display once or more, the following values can be shown on the display: S The suction pressure in s, LED next to the display lights up. S The calculated suction temperature (depends on coolant) in degrees Celsius, LED s and O C light up. S The suction temperature, of temperature sensor1, in degrees Celsius, LED O C lights up. S The operation hours of one of the compressors, to select another compressor, press the left UP or DOWN keys. To show which compressor has been selected for readout, the corresponding LED in the compressor bar will light up and the LED Hrs. will light up. S Current control signal in percentage, LED % lights up. Further, there are two more LEDs ( and ) in the SUCTION display panel, these LED s indicate if the control signal is increasing or decreasing the compressor power. Showing status of the compressors. In the COMPRESSOR panel the status of the compressors is shown in different ways which can be selected by the left MODE/SELECT key. These readout modes are; S Or S Normally the LED s Service and Fail will not be lit, then the LED bars indicate: Upper LED bar shows which compressors are active. Lower LED bar shows which compressors are running in time delay. LEDs Service and Fail are lit, then the LED bars indicate: Upper LED bar shows which compressor is in service. (These compressor(s) will not be selected for controlling by the controller). Lower LED bar shows which compressor is in failure. Readout or changing the suction pressure (/temperature) setpoint. By pressing the left SET key, the suction pressure setpoint is shown in the SUCTION display. To indicate this the lights up. By pressing the left SELECT key, the setpoint will be shown in degrees Celsius (also adjustable), LEDs and O C light up. To change the setpoint value now press the left UP or DOWN keys. 1 seconds after the keys have been released the new setpoint will be active and the controller will return to its normal display function again. Notice that the controller calculates the temperature signals to pressure signals and controls on the pressure signals. Setting a compressor in or out of service. To put a particular compressor out of function, it must be set in service. To see which compressors are in service press the PRG key together with the left MODE/SELECT key. The LED Service will light up and the LED bars show: Upper LED bar shows which compressors are in service and Lower LED bar shows the currentlyselected compressor. With the left UP and DOWN keys another compressor can be selected. The compressor to be put in or out service can be put in or out of service by pressing the left MODE/SELECT key. Resetting operation hours of a particular compressor. Read out the operation hours on the SUCTIONdisplay by pressing the left SELECT key once or more, until the LED Hrs lights up. Then select the compressor which has to be set to zero with the left UP and/or DOWN keys. Now press the RESET/ALARM key, hold it down and press simultaneously on the left MODE/SELECT key to set the selected compressor operation hours to zero.

8 MC 785SC Client : General Page : 8 of 32 The DISCHARGE part (condenserside): Readout selection on the DISCHARGE display. By pressing the right SELECT key next to the DISCHARGE display once or more, the following values can be shown on the display: S The discharge pressure in s, LED next to the display lights up. S The calculated discharge temperature (depends on coolant) in degrees Celsius, LED s and O C light up. S The discharge temperature, of temperature sensor2, in degrees Celsius, LED O C lights up. S The operation hours of one of the condensers, to select another condenser, press the right UP or DOWN keys. To show which condenser has been selected for readout, the corresponding LED in the condenser bar will light up and the LED Hrs. will light up. S Current control signal in percentage, LED % lights up. Further, there are two more LEDs ( and ) in the DISCHARGE display panel. These LEDs indicate if the control signal is increasing or decreasing the condenser power. Showing status of the condensers. In the CONDENSER panel the status of the condensers is shown in different ways which can be selected by the right MODE/SELECT key. These readout modes are: S Or S Normally the LEDs Service and Fail will not be lit, then the LED bars indicate: Upper LED bar shows which condensers are active. Lower LED bar shows which condensers are running in time delay. LEDs Service and Fail are lit, then the LED bars indicate: Upper LED bar shows which condenser is in service. (These condenser(s) will not be selected for controlling by the controller). Lower LED bar shows which condenser is in failure. Readout or changing the discharge pressure (/temperature) setpoint. By pressing the right SET key, the discharge pressure setpoint is shown in the DISCHARGE display. To indicate this the lights up. By pressing the right SELECT key the setpoint will be shown in degrees Celsius (also adjustable); LEDs and O C light up. To change the setpoint value now press the right UP or DOWN keys. 1 seconds after the keys have been released the new setpoint will be active and the controller will return to its normal display function again. Notice that the controller calculates the temperature signals to pressure signals and controls on the pressure signals. Setting a condenser in or out of service. To put a particular condenser out of function, it must be set in service. To see which condensers are in service press the PRG key together with the right MODE/SELECT key. The LED Service will light up and the LED bars show: Upper LED bar shows which condensers are in service and Lower LED bar shows the currentlyselected condenser. With the right UP and DOWN keys another condenser can be selected. The condenser to be put in or out of service can be put in or out of service by pressing the right MODE/SELECT key. Resetting operation hours of a particular condenser. Read out the operation hours on the DISCHARGEdisplay by pressing the right SELECT key once or more, until the LED Hrs lights up. Then select the condenser which has to be set to zero with the right UP and/or DOWN keys. Now press the RESET/ALARM key, hold it down and press simultaneously on the right MODE/SELECT key to set the selected condenser operation hours to zero.

9 MC 785SC Client : General Page : 9 of Programming internal settings By pressing the PRG key for more than 5 seconds, the Internal Parameter Menu is entered. In the SUCTION display a P appears with a number behind it. With the left UP and/or DOWN keys the required parameter can be selected. The value of the selected parameter is shown in the DISCHARGE display. By pressing the UP and/or DOWN keys, the value can be adjusted. If during 3 seconds no key is touched or the ON/OFF key is pressed, the display reverts to the normal operation mode. Parameter table. PNr Description Range Unit Default Parameters General P 1 P 11 P 12 P 13 P 14 P 15 P 16 P 17 P 18 P 19 Minimal adjustable pressure setpoint compressor Maximal adjustable pressure setpoint compressor Pband compressor Maximum suction pressure before the first compressor will be switched on without delay Switch on delay for the next step Time delay for next compressor step Time delay for previous compressor step Type of compressor control = Switching up/down based on running hours (with equal capacities) 1 = Switching up/down based on longest on/off (with equal capacities) 2 = Capacity calculation (with unequal capacities) Compressor strategy = None restrictions 1 = Let active compressor by active 2 = Switch compressors only up Minimum capacity gain per step (as P17=2) 1..5,..5,,1..5, ,1..3, Sec. Sec. Sec. kw 1, 5, 8, , P 2 P 21 P 22 Minimum time between switching the same compressor off and on Noload running time on starting compressor (valves are lifted) Minimum ontime of compressor Sec. Sec. Sec P 23 P 24 Pumpingout pressure value Pumpingout pressure active 1,..5, =no 1=yes 1, (no) P 25 P 26 Pressure release for economizer Differential economizer release 1,..5,,1..,5 2,3,3

10 MC 785SC Client : General Page : 1 of 32 PNr Description Range Unit Default P 3 P 31 P 32 P 35 P 36 P 37 Minimum adjustable pressure setpoint Condenser Maximum adjustable pressure setpoint Condenser Pband condenser control Switching up time between the condensers Switching down time between the condensers Type of condenser control = Switching up/down on running hours (equal capacities) 1 = Switching up/down on set sequence (1,2,3,4...4,3,2,1)..5,..5,,1..5, Sec. Sec. 1, 5, 8, 3 3 P 4 P 41 Suction temperature sensor(sensor1) = Absent 1 = Present, readout only 2 = Present, readout and alarms Discharge temperature sensor (sensor2) = Absent 1 = Present, readout only 2 = Present, readout and alarms 3 = Present, outdoor temperature for Delta T control P 42 P 43 P 44 P 45 P 46 P 47 Minimum suction temp. sensor alarm Minimum suction temp. sensor failure (Everything switches off) Maximum discharge temp. sensor alarm Maximum discharge temp. sensor failure (Everything switches off) Offset suction temperature sensor Offset discharge temperature sensor 4..5, 4..5, 4..1, 4..1, 1..1, 1..1, O C O C O C O C O C O C 4, 4, 1, 1,,, P 5 P 51 P 52 P 6 Low pressure alarm input (see table) Fluid level too low warning input (see table) Level input gives fatal error Alarm relay (normally powered) (see table).. 4nc6.. 4nc6 =no, 1=yes P 7 P 71 P 72 P 73 P 8 P 81 P 82 Suction pressure corresponding to 4. ma Suction pressure corresponding to 2. ma Offset pressure sensor suction pressure Read out suction pressure senor in,1 Discharge pressure corresponding to 4. ma Discharge pressure corresponding to 2. ma Offset pressure sensor discharge pressure 1,..5, 1,..5, 1..1, =no, 1=yes 1,..5, 1,..5, 1..1,, 25,,, 25,, P 9 P 91 P 92 P 93 Coolant type: = unknown 1 = R22 2 = R134A 3 = R44A (bubble and dew point) 4 = R47A (bubble and dew point) 5 = R47C (bubble and dew point) 6 = R717 (Ammoniac) 7 = R57 Super heat detection active (=no, 1=yes) Super heat warning Super heat alarm..7..1,..5,,..5, Kelvin Kelvin 8, 7,

11 MC 785SC Client : General Page : 11 of 32 PNr Description Range Unit Default P 95 P 96 P 97 Outdoor temp. control active (=no, 1=yes) Delta T condenser with outdoor temperature Maximum pressure set point condenser..1 1,..5,,..5, Kelvin (no) 1, 5, P1 P11 P12 P15 P16 P17 Minimum pressure alarm suction side Minimum pressure alarm suction side delay Minimum pressure failure suction side (This is not delayed and the compressors are blocked) Maximum pressure alarm discharge side Maximum pressure alarm discharge side delay Maximum pressure failure discharge side (This is not delayed and the compressors and condensers are blocked) 1,..5, ,..5, 1,..5, ,..5, Sec. Sec.,5 1 18, 1 2, Parameters for Compressors 1 to 8 P11 P111 P112 P113 P114 P115 P116 P117 P118 P119 P12 P121 P122 P123 Compressor1 type: = not present 1 = on/off 2 = 2Cylinder (51%) 3 = 3Cylinder (33661%) 4 = 4Cylinder (255751%) 5 = 5Cylinder (24681%) 6 = Screw compressor (5751%) 7 = FRQ 1Stage frequency controlled Power Compressor1 in KW On/off relay Compressor1 Valve lifting relay Compressor1 For noload running, relay is active when starting First valve lifting relay..% Percentage depends on number of cylinders, subsequent cylinders are assigned automatically hereafter. (For operation see page 5) Analog output Compressor1 (1V) Failure input Compressor1 High pressure input Compressor1 Failure oil pressure contactinput Compressor1 Operationswitch input Pause input Economizer relay Minimum percentage output frequency control Maximum percentage output frequency control nc6.. 4nc6.. 4nc6.. 4nc6.. 4nc KW $ S # % %

12 MC 785SC Client : General Page : 12 of 32 PNr Description Range Unit Default P13 P131 P132 P133 P134 P135 P136 P137 P138 P139 P14 P141 Compressor2 type: = Not present 1 = On/off 2 = 2Cylinder (51%) 3 = 3Cylinder (33661%) 4 = 4Cylinder (255751%) 5 = 5Cylinder (24681%) 6 = Screw compressor (5751%) Power Compressor2 in KW On/off relay Compressor2 Valve lifting relay Compressor2 For noload running, relay is active when starting First valve lifting relay..% Percentage depends on number of cylinders, subsequent cylinders are assigned automatically hereafter. (For operation see page 5) Analog output Compressor2 (1V) Failure input Compressor2 High pressure input Compressor2 Failure oil pressure contractinput Compressor2 Operationswitch input Pause input Economizer relay nc6.. 4nc6.. 4nc6.. 4nc6.. 4nc KW $ S #.1 P15 P151 P152 P153 P154 P155 P156 P157 P158 P159 P16 P161 Compressor3 type: = Not present 1 = On/off 2 = 2Cylinder (51%) 3 = 3Cylinder (33661%) 4 = 4Cylinder (255751%) 5 = 5Cylinder (24681%) 6 = Screw compressor (5751%) Power Compressor3 in KW On/off relay Compressor3 Valve lifting relay Compressor3 For noload running, relay is active when starting First valve lifting relay..% Percentage depends on number of cylinders, subsequent cylinders are assigned automatically hereafter. (For operation see page 5) Analog output Compressor3 (1V) Failure input Compressor3 High pressure input Compressor3 Failure oil pressure contactinput Compressor3 Operationswitch input Pause input Economizer relay nc6.. 4nc6.. 4nc6.. 4nc6.. 4nc KW $ S #.1

13 MC 785SC Client : General Page : 13 of 32 PNr Description Range Unit Default P17 P171 P172 P173 P174 P175 P176 P177 P178 P179 P18 P181 Compressor4 type: = Not present 1 = On/off 2 = 2Cylinder (51%) 3 = 3Cylinder (33661%) 4 = 4Cylinder (255751%) 5 = 5Cylinder (24681%) 6 = Screw compressor (5751%) Power Compressor4 in KW On/off relay Compressor4 Valve lifting relay Compressor4 For noload running, relay is active when starting First valve lifting relay..% Percentage depends on number of cylinders, subsequent cylinders are assigned automatically hereafter. (For operation see page 5) Analog output Compressor4 (1V) Failure input Compressor4 High pressure input Compressor4 Failure oil pressure contactinput Compressor4 Operationswitch input Pause input Economizer relay nc6.. 4nc6.. 4nc6.. 4nc6.. 4nc KW $ S #.1 P19 P191 P192 P193 P194 P195 P196 P197 P198 P199 P2 P21 Compressor5 type: = Not present 1 = On/off 2 = 2Cylinder (51%) 3 = 3Cylinder (33661%) 4 = 4Cylinder (255751%) 5 = 5Cylinder (24681%) 6 = Screw compressor (5751%) Power Compressor5 in KW On/off relay Compressor5 Valve lifting relay Compressor5 For noload running, relays is active when starting First valve lifting relay..% Percentage depends on number of cylinders, subsequent cylinders are assigned automatically hereafter. (For operation see page 5) Analog output Compressor5 (1V) Failure input Compressor5 High pressure input Compressor5 Failure oil pressure contactinput Compressor5 Operationswitch input Pause input Economizer relay nc6.. 4nc6.. 4nc6.. 4nc6.. 4nc KW $ S #.1

14 MC 785SC Client : General Page : 14 of 32 PNr Description Range Unit Default P21 P211 P212 P213 P214 P215 P216 P217 P218 P219 P22 P221 Compressor6 type: = Not present 1 = On/off 2 = 2Cylinder (51%) 3 = 3Cylinder (33661%) 4 = 4Cylinder (255751%) 5 = 5Cylinder (24681%) 6 = Screw compressor (5751%) Power Compressor6 in KW On/off relay Compressor6 Valve lifting relay Compressor6 For noload running, relay is active when starting First valve lifting relay..% Percentage depends on number of cylinders, subsequent cylinders are assigned automatically hereafter. (For operation see page 5) Analog output Compressor6 (1V) Failure input Compressor6 High pressure input Compressor6 Failure oil pressure contactinput Compressor6 Operationswitch input Pause input Economizer relay nc6.. 4nc6.. 4nc6.. 4nc6.. 4nc KW $ S #.1 P23 P231 P232 P233 P234 P235 P236 P237 P238 P239 P24 P241 Compressor7 type: = Not present 1 = On/off 2 = 2Cylinder (51%) 3 = 3Cylinder (33661%) 4 = 4Cylinder (255751%) 5 = 5Cylinder (24681%) 6 = Screw compressor (5751%) Power Compressor7 in KW On/off relay Compressor7 Valve lifting relay Compressor7 For noload running, relay is active when starting First valve lifting relay..% Percentage depends on number of cylinders, subsequent cylinders are assigned automatically hereafter. (For operation see page 5) Analog output Compressor7 (1V) Failure input Compressor7 High pressure input Compressor7 Failure oil pressure contactinput Compressor7 Operationswitch input Pause input Economizer relay nc6.. 4nc6.. 4nc6.. 4nc6.. 4nc KW $ S #.1

15 MC 785SC Client : General Page : 15 of 32 PNr Description Range Unit Default P25 P251 P252 P253 P254 P255 P256 P257 P258 P259 P26 P261 Compressor8 type: = Not present 1 = On/off 2 = 2Cylinder (51%) 3 = 3Cylinder (33661%) 4 = 4Cylinder (255751%) 5 = 5Cylinder (24681%) 6 = Screw compressor (5751%) Power Compressor8 in KW On/off relay Compressor8 Valve lifting relay Compressor8 For noload running, relay is active when starting First valve lifting relay..% Percentage depends on number of cylinders, subsequent cylinders are automatically assigned hereafter. (For operation see page 5) Analog output Compressor8 (1V) Failure input Compressor8 High pressure input Compressor8 Failure oil pressure contactinput Compressor8 Operationswitch input Pause input Economizer relay nc6.. 4nc6.. 4nc6.. 4nc6.. 4nc KW $ S #.1 Parameters for Condensers 1 to 8 fans P27 P271 P272 Condenser1 type: = Not present 1 = On/off 2 = 2speed (5%1%) 3 = FRQ frequency controlled On/off relay Condenser1 Relay for 5% 1% Relay is active at 1% drive P273 P274 P275 P276 Analog output Condenser1 (1V) Failure input Condenser1 Minimum percentage output frequency control Maximum percentage output frequency control nc $ % % 5 1 P29 P291 P292 P293 P294 Condenser2 type: = Not present 1 = On/off 2 = 2speed (5%1%) On/off relay Condenser2 Relay for 5% 1% Relay is active at 1% drive Analog output Condenser2 (1V) Failure input Condenser nc6 $

16 MC 785SC Client : General Page : 16 of 32 PNr Description Range Unit Default P31 P311 P312 P313 P314 Condenser3 type: = Not present 1 = On/off 2 = 2Speed (5%1%) Aan/uit relais Condenser3 Relay for 5% 1% Relay is active at 1% drive Analog output Condenser3 (1V) Failure input Condenser nc6 $ P33 P331 P332 Condenser4 type: = Not present 1 = On/off 2 = 2speed (5%1%) On/off relay Condenser4 Relay for 5% 1% Relay is active at 1o% drive P333 P334 Analog output Condenser4 (1V) Failure input Condenser nc6 $ P35 P351 P352 Condenser5 type: = Not present 1 = On/off 2 = 2speed (5%1%) On/off relay Condenser5 Relay for 5% 1% Relay is active at 1% drive P353 P354 Analog output Condenser5 (1V) Failure input Condenser nc6 $ P37 P371 P372 Condenser6 type: = Not present 1 = On/off 2 = 2speed (5%1%) On/off relay Condenser6 Relay for 5% 1% Relay is active at 1% drive P373 P374 Analog output Condenser6 (1V) Failure input Condenser nc6 $ P39 P391 P392 Condenser7 type: = Not present 1 = On/off 2 = 2speed (5%1%) On/off relay Condenser7 Relay for 5% 1% Relay is active at 1% drive P393 P394 Analog output Condenser7 (1V) Failure input Condenser nc6 $

17 MC 785SC Client : General Page : 17 of 32 PNr Description Range Unit Default P41 P411 P412 Condenser8 type: = Not present 1 = On/off 2 = 2speed (5%1%) On/off relay Condenser8 Relay for 5% 1% Relay is active at 1% drive P413 P414 Analog output Condenser8 (1V) Failure input Condenser nc6 $ Parameters for external setpoints P5 External compressors setpoint input1.. 4nc6 P51 External compressors setpoint P51 External compressors setpoint input2.. 4nc6 P511 External compressors setpoint P52 External compressors setpoint input3.. 4nc6 P521 External compressors setpoint Parameters for Network P8 P81 Network number Log interval Minute s 15 Parameters Software/Series number etc. P991 P992 P993 P999 Software version no. Serial number Production date (year/week) Password ( = password not active) Key to symbols: *) = See table of assignment of relay outputs #) = See table of assignment of digital inputs $) = See table of assignment of analog outputs Remarks about P13 to P15: Whit P13 it is possible to enter a limit for switching on the first compressor. As soon as the pressure is higher then P13 the first compressor will switch on without delay. The minimal off time (P2) will still be valid. If the value from P15 is lower then the value of P14 then the value of P14 will be used. If another step has to switch on, the value of P15 will be used. Remarks about P5 to P521: When one or more inputs are closed the input with the lowest setpoint will be active as setpoint for the compressors! During the readout of the setpoint a flashing c will indicate that an input is active. In this mode the set point CANNOT be changed.

18 MC 785SC Client : General Page : 18 of 32 *) Table of assignment of relay outputs Value Relay number On Controller/Module Contact No relay assigned Remarks: Relay1 Relay2 Relay3 Relay4 Relay5 Relay1 Relay2 Relay3 Relay4 Relay5 Relay6 Relay7 Relay1 Relay2 Relay3 Relay4 Relay5 Relay6 Relay7 Relay1 Relay2 Relay3 Relay4 Relay5 Relay6 Relay7 Relay1 Relay2 Relay3 Relay4 Relay5 Relay6 Relay7 MC785SC controller LMSrelaymodule1 (JP1 with jumper and JP2 with jumper) LMSrelaymodule2 (JP1 without jumper and JP2 with jumper) LMSrelaymodule3 (JP1 with jumper and JP2 without jumper) LMSrelaymodule4 (JP1 without jumper and JP2 without jumper) CNONC NO common C NO,, NO,, NO/NC,, CNONC CNO CNO CNO CNONC CNONC CNONC CNONC CNO CNO CNO CNONC CNONC CNONC CNONC CNO CNO CNO CNONC CNONC CNONC CNONC CNO CNO CNO CNONC CNONC CNONC The 4 and 7relay type LMS modules may be mixed together but at maximum 4 relay modules can be assigned. So at minimum there are 5 relays available on MC 785SC and at maximum there are 5+4x7=33 relays available MC785SC(5) + 4x LMS 7RELAY MODULE.

19 MC 785SC Client : General Page : 19 of 32 $) Table of assignment of analog outputs (1Vdc) Value Analog output number On Controller/Module Signal No output assigned Analogoutput1 Analogoutput2 Analogoutput1 Analogoutput2 Analogoutput3 Analogoutput4 Analogoutput1 Analogoutput2 Analogoutput3 Analogoutput4 Analogoutput1 Analogoutput2 Analogoutput3 Analogoutput4 Analogoutput1 Analogoutput2 Analogoutput3 Analogoutput4 MC785SC regelaar LMSanalogmodule1 (JP1 with jumper and JP2 with jumper) LMSanalogmodule2 (JP1 without jumper and JP2 with jumper) LMSanalogmodule3 (JP1 with jumper and JP2 without jumper) LMSanalogmodule4 (JP1 without jumper and JP2 wihtout jumper) 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc 1Vdc #) Table of assignment of digital inputs Value Digital input number On Controller/Module Input contact No input assigned Digital input1 Digital input2 Digital input3 Digital input4 Digital input5 Digital input6 Digital input1 Digital input2 Digital input3 Digital input4 Digital input5 Digital input6 Digital input1 Digital input2 Digital input3 Digital input4 Digital input5 Digital input6 LMSdiginmodule1 (JP1 with jumper and JP2 with jumper) LMSdiginmodule2 (JP1 without jumper and JP2 with jumper) LMSdiginmodule3 (JP1 with jumper and JP2 without jumper) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make)

20 MC 785SC Client : General Page : 2 of 32 Value Digital input number On Controller/Module Input contact nc1 1nc2 1nc3 1nc4 1nc5 1nc6 2nc1 2nc2 2nc3 2nc4 2nc5 2nc6 3nc1 3nc2 3nc3 3nc4 3nc5 3nc6 4nc1 4nc2 4nc3 4nc4 4nc5 4nc6 Digital input1 Digital input2 Digital input3 Digital input4 Digital input5 Digital input6 Digital input1 Digital input2 Digital input3 Digital input4 Digital input5 Digital input6 Digital input1 Digital input2 Digital input3 Digital input4 Digital input5 Digital input6 Digital input1 Digital input2 Digital input3 Digital input4 Digital input5 Digital input6 Digital input1 Digital input2 Digital input3 Digital input4 Digital input5 Digital input6 LMSdiginmodule4 (JP1 without jumper and JP2 without jumper) LMSdiginmodule1 (JP1 with jumper and JP2 with jumper) LMSdiginmodule2 (JP1 without jumper and JP2 with jumper) LMSdiginmodule3 (JP1 with jumper and JP2 without jumper) LMSdiginmodule4 (JP1 without jumper and JP2 without jumper) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NOC (make) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break) NCC (break)

21 MC 785SC Client : General Page : 21 of Alarms The following alarm messages may appear in the SUCTIONdisplay: E1 = Pressure sensor suction defect. Action: Everything off E3 = Temperature sensor suction defect. Action: None (no control function) E1 = Low pressure alarm. Action: None E2 = Low pressure failure. Action: Everything off E3 = External low pressure failure. Action: Everything off E4 = Low temperature alarm Action: None E5 = Low temperature failure. Action: Everything off E6 = Oil pressure failure. Action: Turn off compressor concerned E7 = Fluid level warning. Action: None E8 = Maximum number of control steps has been exceeded. Action: Regulate the pressure up to and including step 5. T9 = Super heat warning E9 = Super heat alarm The following alarm messages may appear in the DISCHARGEdisplay: E2 = Pressure sensor discharge defect. Action: Everything off E4 = Temperature sensor discharge defect. Action: None (no control function) E11 = High pressure alarm Action: None E21 = High pressure failure. Action: Everything off E31 = External high pressure failure. Action: Everything off E41 = High temperature alarm. Action: None E51 = High temperature failure. Action: Everything off When an alarm occurs the relevant alarmcode appears in the appropriate display and the LED on the appropriate side switches on. If an external alarm is registered, the appropriate fail LED will lit. By means of the MODE/SELECT key it is possible to see which compressor and/or which condenser has given the alarm. At the same time the LED above the RESET/ALARM key will flash as a reminder that another alarm must be reset by pressing the RESET/ALARM key. If there are more than one alarm then the first alarm to occur will be visible until it is reset, then the second alarm will be visible until it is reset, and so on. If they have all been reset but not resolved then the alarm codes will flash on the display and can be skimmed through with the RESET/ALARM key. In addition it is possible to assign a relay as a general alarm relay; this is normally on and goes off in case of alarm.

22 MC 785SC Client : General Page : 22 of Function flow Operation of the Pband on the suction pressure side (Compressorside): Overview of the function flow for 4compressors for the switching up and down of compressors:

23 MC 785SC Client : General Page : 23 of 32 Overview of the function flow for compressor with 5cylinders: Working of compressor control with unequal steps; At maximum 7 controlsteps can be made. This is f.i. 6 compressors (= 64 steps). When the number of steps is exceeded, the error message E 8' will appear. The controller will then control with the number of steps calculated up til then. It is also possible to use compressors with valve lifting. The number of steps can be calculated as follows: number of steps compr1 * number of steps compr2... etc. Example1: Compr 1: 3 cylinder (33661% = 4 steps) e.g. 1KW Compr 2: 2 cylinder (51% = 3 steps) e.g. 2KW gives: 4 * 3 = 12 steps. Example2: Compr 1: 2 cylinder (51% = 3 steps) Compr 2,3,4,5: (1% = 2 steps) gives: 3 * 2 * 2 * 2 * 2 = 48 steps

24 MC 785SC Client : General Page : 24 of 32 Step Compressor1, 3cylinder model 1kW Compressor2, 2cyl.model 2kW Total cyl. 1cyl. 2cyl. 3cyl. kw cyl. 1cyl. 2cyl. kw kw % % 33% 66% 1 % % 5% 1 % 1 x x 2 x.33 x x.66 x x 1 x x x x.33 x x.66 x x 1 x x x x.33 x x.66 x x 1 x Example1 overview of the control steps with the cooling capacity in percentages ( x=active) Increasing compressors: When two or more steps result in the same capacity the step leading to the switching down of the fewest compressors is first selected. If the steps are then still equal the step with the shortest increase delay is selected. If the steps are then still equal the step with the fewest running hours is selected. If this still does not lead to an unambiguous step then the first step is increased. Decreasing compressors: When two or more steps result in the same capacity the step leading to the switching down of the fewest compressors is selected. If the steps are then still equal the step with the shortest switching down delay is selected. If the steps are then still equal the step with the most running hours is selected. If this still does not lead to an unambiguous step then the first step is increased. If the minimum on and off times are longer than the switching up and down times this can result in an unstable system. When the switching down time is over there must always be a switching down (provided that the minimum ontime is over). Example3: Three compressors (1kW, 2kW, 4kW) run in the stand 11 (step4=3kw) The suction pressure is still too high so the next step is 1 (step5=4kw) Now the suction pressure will fall to the switching down point. If the compressors1 and 2 are still running in their minimum offtime, then the control will still decrease compressor 3. The result of this is that all compressors are now off. they When compressors have to be switched on during the switching down process will always continue to run for their minimum ontime.

25 MC 785SC Client : General Page : 25 of 32 Step Compressor1 on/off 1KW model Compressor2 on/off 2KW model Compressor3 on/off 4KW model Total x=on KW x=on KW x=on KW KW % 1 2 x x x 1 x x x 1 x x 2 x x 1 x 2 x Example3: overview of the control steps with the cooling capacity in percentages (x=active)

26 MC 785SC Client : General Page : 26 of Front view Front of MC 785SC (wall mounting, drawing 1718) Front of MC 785SC (panel mounting, drawing 21842)

27 MC 785SC Client : General Page : 27 of Diagrams of connections Connection diagram for MC 785SC (wall mounting, drawing 1735) Connection diagram for RS485 network

28 MC 785SC Client : General Page : 28 of 32 Connection diagram for MC 785SC (panel mounting drawing 21841)

29 MC 785SC Client : General Page : 29 of 32 Connection diagram for LMSmodules for MC785SC drawing 1822

30 MC 785SC Client : General Page : 3 of 32 Connections LMS 7x RELAYSC MODULE (91.49)

31 MC 785SC Client : General Page : 31 of Dimensions Dimensions of MC785SC panel mounting model drawing 9424

32 MC 785SC Client : General Page : 32 of 32 Dimensions of MC785SC wall mounting drawing

PCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS

PCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS PCT plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS Ver. DESCRIPTION The PCT plus is a pressure controller for refrigeration plants that require control in their suction and discharge stages. With

More information

SMT-150 Installer Manual

SMT-150 Installer Manual SMT-150 Installer Manual 3 Stage Digital HVAC Controller Version 1.0 Version History January 2019 Version 1 - Original Document Thank you for your purchase of this premier product. Please take the time

More information

ECONOMISER SERIES E2T USER MANUAL

ECONOMISER SERIES E2T USER MANUAL TURBO S.R.L. Electronic Control Systems for Dust Collectors e-mail: info@turbocontrols.it web: www.turbocontrols.it TEL. ++39 (0)362 574024 FAX ++39 (0)362 574092 ECONOMISER SERIES E2T USER MANUAL 24/06/2014

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00 Inlet Controller TC5-ITA USER'S MANUAL M 890-00047 rev. 02 K 895-00458 rev. 00 TABLE OF CONTENTS PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE CONTROLS... 5 Status Leds...5 Internal Switches...6 INSTALLATION

More information

OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets

OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets Art. nr. 40200261 OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets WHISPERPOWER BV Kelvinlaan 82 9207 JB Drachten Netherlands Tel.: +31-512-571550 Fax.: +31-512-571599

More information

Application Engineering

Application Engineering Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the

More information

Fan Coil Thermostat. Specification & Installation instructions TFC54F3X1. Technical Data

Fan Coil Thermostat. Specification & Installation instructions TFC54F3X1. Technical Data Fan Coil Thermostat Feature: Selectable analog & digital output Selectable fan speed contact Selectable Fahrenheit or Celsius scale Manual Night Set Back override (programmable) Multi level lockable access

More information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary

More information

CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS

CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS Date of last update: Apr-15 Ref: D7.8.4/0112-0415/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors...

More information

Vission 20/20 micro-controller. Operation and service manual

Vission 20/20 micro-controller. Operation and service manual Vission 20/20 micro-controller Operation and service manual Section Title Table of Contents Section Number How To Use This Manual...TOC-8 Section 1 Operational Flow Charts Requirements to Start Compressor...1-1

More information

ST48-WHUV.102. Wiring diagram. Product description. PID controller. Order number

ST48-WHUV.102. Wiring diagram. Product description. PID controller. Order number ST48-WHUV.12 PID controller Order number 935.15 Wiring diagram Product description This micro-processed controller serves for temperature control at high measuring accuracy. Beside resistance sensors and

More information

RVS-DN Digital Reduced Voltage Motor Starter

RVS-DN Digital Reduced Voltage Motor Starter RVS-DN Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

MB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR

MB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR MB-3688 120A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR User Manual Warning and Precautions MB-3688 is built with corrosion resistant material and the main electronic assembly is well sealed inside

More information

PCT-3001 plus. Display LCD

PCT-3001 plus. Display LCD PCT3 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS DESCRIPTION Pressure controller for refrigeration systems capable to control suction (compressors) and discharge (fans) pressures. It is possible

More information

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL Temperature Controller TC5+2V4SA Plus USER'S MANUAL NOTICE Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject

More information

RVS-DX Digital Reduced Voltage Motor Starter

RVS-DX Digital Reduced Voltage Motor Starter RVS-DX Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

A419ABG-3C Electronic Temperature Control

A419ABG-3C Electronic Temperature Control Installation Instructions Issue Date June 16, 2003 A419ABG-3C Electronic Temperature Control Application IMPORTANT: Use this A419ABG-3C Electronic Temperature Control only as an operating control. Where

More information

Application Engineering Europe

Application Engineering Europe Date of last update: Feb-12 Ref: D7.8.4/0112-0212/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS 1/17 1 Introduction CoreSense is an ingredient brand name for

More information

USERS MANUAL MCD REMOTE OPERATOR

USERS MANUAL MCD REMOTE OPERATOR USERS MANUAL MCD REMOTE OPERATOR Order Code: 175G9004, 175G3061 Contents Contents Introduction...2 Important User Information...2 General Description...2 Symbols Used in this Manual...2 Installation...3

More information

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING AUGUST, 2004 REV.A CURTIS TOLEDO OPERATOR S MANUAL SUPPLEMENT AF Series Compressors VS models with VFD WARNING Personal injury and/or equipment damage will result by failing to pay attention to the vital

More information

Documentation. RM-BV4 Micro DP. Filter control

Documentation. RM-BV4 Micro DP. Filter control Documentation RM-BV4 Micro DP Filter control Contents 1 Safety instructions... 3 2 Device description... 3 3 Installation... 4 4 Installation... 5 4.1 Connection of the differential pressure measuring

More information

REVISION HISTORY REVISION HISTORY

REVISION HISTORY REVISION HISTORY FILTER CONTROLLER REVISION HISTORY Filter Flush Controller forms part of the Netafim range of filtration controllers all designed to make filteration more reliable and economical.. Contact any of the Netafim

More information

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Installation Instructions Issue Date April 8, 2008 A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Application IMPORTANT: The A419 Series Electronic Temperature

More information

ST Wiring diagram. Product description. Temperature controller. Order number

ST Wiring diagram. Product description. Temperature controller. Order number ST7-31.3 Temperature controller Order number 9154.12 Wiring diagram Product description The switching exits of the thermostatic controller can be programmed as -two-point controller with alarm -three-point

More information

SE8300 Series Installation Guide 24 Vac Low Voltage

SE8300 Series Installation Guide 24 Vac Low Voltage Installation Guide 24 Vac Voltage mercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 2 Configurable BI/UI Universal Inputs Overview 3 Setup Screen Display 3 Terminal Identification

More information

HERZ Electronic room thermostat analog and digital

HERZ Electronic room thermostat analog and digital Dimension in mm 3 F799 11-3 F799 14 HERZ Electronic room thermostat analog and digital Data sheet for F799, Issue 0317 3 F799 15 3 F799 18 Mounting plate Page 1 Technical data 3 F799 11-14 3 F799 15-18

More information

HBLT-C1 Controller. Instruction Manual. For pump control of levels in industrial refrigeration systems

HBLT-C1 Controller. Instruction Manual. For pump control of levels in industrial refrigeration systems Instruction Manual HBLT-C1 Controller For pump control of levels in industrial refrigeration systems Instruction manual HBLT-C1 Controller (006-UK) 1 / 14 Table of Contents Safety Instructions... 3 Introduction...

More information

Temperature Controller OVATION 214 User's Guide

Temperature Controller OVATION 214 User's Guide Temperature Controller User's Guide Read this guide carefully before using the controller. 890-00045 rev.00 TABLE OF CONTENTS Page TABLE OF CONTENTS... 2 PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE

More information

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains

More information

Digital Diesel Control Remote control panel for GENVERTER GV4 and GV7i

Digital Diesel Control Remote control panel for GENVERTER GV4 and GV7i OPERATING MANUAL Digital Diesel Control Remote control panel for GENVERTER GV4 and GV7i Art. nr. 40200801 WHISPER POWER BV ENGLISH: PAGE 1 Kelvinlaan 82 9207 JB Drachten NEDERLANDS: PAGINA 41 Netherlands

More information

STRA-24 for chilled beams

STRA-24 for chilled beams STRA- Installation and commissioning manual STRA- for chilled beams STRA- is the room controller for the pressure independent (Pi) and constant air volume chilled beams. It is possible to set different

More information

Differential Pressure Sensor

Differential Pressure Sensor Differential Pressure Sensor "Cube" Type Differential Pressure Sensor with LED Display Offers High Precision Sensing 31 (1.) x 3 (1.18) x 3 (1.18) mm compact-cube style saves mounting space Easy-to-read

More information

PSK203/PSK223/PSK233. Digital Thermostats for Low Temperature Refrigerating Units 1 GETTING STARTED PSK203 PSK223 PSK233

PSK203/PSK223/PSK233. Digital Thermostats for Low Temperature Refrigerating Units 1 GETTING STARTED PSK203 PSK223 PSK233 September 2012 / Bulletin 100-50-6.2 PSK203/PSK223/PSK233 Digital Thermostats f Low Temperature Refrigerating Units INSTALLATION OPERATING INSTRUCTIONS 1 GETTING STARTED 1.1 Imptant Read these instructions

More information

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75 Cascade CD101 Auto-Start Controller Installation and Operations Manual 00-02-0594 2018-02-15 Sections 40 & 75 In order to consistently bring you the highest quality, full featured products, we reserve

More information

Flight Systems. Replacement for KASSEC DESCRIPTION

Flight Systems.   Replacement for KASSEC DESCRIPTION DESCRIPTION The is a universal generator controller that will start, stop, and provide engine protection for most generators. Universal replacement for both the 90353 and 90354 KASSEC Compatible with most

More information

OPERATING INSTRUCTIONS ECON-M

OPERATING INSTRUCTIONS ECON-M OPERATING INSTRUCTIONS ECON-M INDEX 1.0 Introduction 2.0 Salient features, Protection & Supervision 3.0 Display/ Front Panel 4.0 Switches Description 5.0 LED Annunciations Description 6.0 Lamp Test 7.0

More information

Description. functions including single duct pressure dependent or pressure independent systems.

Description. functions including single duct pressure dependent or pressure independent systems. Description The Meridian Basic control system converts a single zone HVAC unit into a variable air volume/variable air temperature multiple zone system. The microprocessor based Zone Manager calculates

More information

Vission 20/20 micro-controller. Operation and service manual Version 2.6

Vission 20/20 micro-controller. Operation and service manual Version 2.6 Vission 20/20 micro-controller Operation and service manual Version 2.6 Important Message READ CAREFULLY BEFORE OPERATING YOUR COMPRESSOR. The following instructions have been prepared to assist in operation

More information

Inlet Controller SB3500 USER'S MANUAL

Inlet Controller SB3500 USER'S MANUAL Inlet Controller USER'S MANUAL NOTICE Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject to change without notice

More information

Temperature Controller TC5-2V8SA USER'S MANUAL. M rev. 03 K rev. 00

Temperature Controller TC5-2V8SA USER'S MANUAL. M rev. 03 K rev. 00 Temperature Controller USER'S MANUAL M 890-00174 rev. 03 K 895-00327 rev. 00 TABLE OF CONTENTS Page PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE CONTROLS... 6 Controller Status Leds... 7 Internal Switches...

More information

Combined Ventilation Controller RVWS-T-224HA

Combined Ventilation Controller RVWS-T-224HA Combined Ventilation Controller RVWS-T-224HA 8-stage Control for Power/Natural Applications 2 variable speed stages, 2 curtain winch stages, 2 fixed speed ventilation stages, 1 thermo/mister cycle stage

More information

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology HGM1780 Automatic Genset Controller USER MANUAL Smartgen Technology Smartgen Technology Co., Ltd No. 28 Jinsuo Road Zhengzhou Henan Province P. R. China Tel: 0086-371-67988888/67981888 0086-371-67991553/67992951

More information

Installation Instructions & Users Manual

Installation Instructions & Users Manual Installation Instructions & Users Manual UTILITY/ BUILDING INPUT 120 VAC ( OPTION) 15-20A N L CONTROL BOARD G SECURITY LIGHTING POWER SUPPLY (OPTION) CHARGER- POWER SUPPLY ASSBY XFMR (OPTION) CBM MODEL

More information

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech The Axpert-CSS is a range of Combination Soft Starter panels offered by AMTECH DRIVES. We also offer the module unit as an individual product, named as Axpert-Opti torque Soft Starter. This is only the

More information

Te 803 Electronic Controller. Service, Operation & Technical Information Manual

Te 803 Electronic Controller. Service, Operation & Technical Information Manual Te 803 Electronic Controller Service, Operation & Technical Information Manual WARNING! Technical descriptions and data given in this document are accurate, to the best of our knowledge, but can be subject

More information

ELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE A

ELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE A ELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE 012945A0 040906 1 MAIN FEATURES Power supply 230V~ ±10% 50Hz Backlit alphanumeric LCD display Management of 5 output

More information

INSTALLATION AND OPERATION INSTRUCTION

INSTALLATION AND OPERATION INSTRUCTION INSTALLATION AND OPERATION INSTRUCTION ATi Max 2-1/2-6, 65-150mm Install the ATi Max valve either in the supply or return pipework for the unit. It is recommended that a strainer be installed prior to

More information

M u l t i P o w e r. CM MultiPower. Installation and Operating Manual

M u l t i P o w e r. CM MultiPower. Installation and Operating Manual M u l t i P o w e r CM MultiPower Installation and Operating Manual Index 1. Introduction of the 4HS submersible pumps range... 3 2. Safety Instructions... 4 3. CM MP installation... 5 3.1 Electric wiring...

More information

l The Battery Tester is designed for measuring the l AC four-terminal method to measure the internal

l The Battery Tester is designed for measuring the l AC four-terminal method to measure the internal Certificate of Calibration We hereby certify that this product has been calibrated and found to be in accordance with the applicable SPECIFICATIONS and STANDARDS. Accuracies of the standard equipment used

More information

Energy Division

Energy Division Energy Division http://energy.tycoelectronics.com Installation and Operating Manual GEN-TRANS Automatic Generator Transfer Switch Controller with Metering Tyco Electronics UK Limited Crompton Instruments

More information

KCR1. Kiln Controller Handbook. Kilncare Ltd. The Kiln Works 907 Leek New Road Baddeley Green Stoke-on-Trent Staffordshire, ST2 7HQ United Kingdom

KCR1. Kiln Controller Handbook. Kilncare Ltd. The Kiln Works 907 Leek New Road Baddeley Green Stoke-on-Trent Staffordshire, ST2 7HQ United Kingdom KCR1 Kiln Controller Handbook Issue: a b Date: 04Sep2008 05Sep2008 Kilncare Ltd. The Kiln Works 907 Leek New Road Baddeley Green Stoke-on-Trent Staffordshire, ST2 7HQ United Kingdom Tel: 01782 535915 Tel:

More information

JConn Inv. PID Controller Instruction Manual

JConn Inv. PID Controller Instruction Manual JConn Inv. PID Controller Instruction Manual This information is specific to the Mypin TA4 based controller sold by JConn Inv. but it should work for most TA4 types - within limits. Table of Contents 1.

More information

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology HGM501 Gen-set Controller USER MANUAL Smartgen Technology Contents 1. 2. 3. 4. 5. 6. 7. 8. 9. OVERVIEW... 4 PERFORMANCE AND CHARACTERISTICS... 4 TECHNICAL DATA... 5 OPERATION... 6 4.1. BUTTON DESCRIPTION...

More information

OPTI-Solar SC MPPT Series

OPTI-Solar SC MPPT Series www.opt i -sola r. c o m OPTI-Solar SC MPPT Series SOLAR CHARGE CONTROLLER SC-50 / SC-80 / SC-80X / SC-160X MPPT Installation and Operation Manual CONTENTS Introduction... Feature... Specification... Dimension...VII

More information

MATRIX LLC LEVEL CONTROL PANEL

MATRIX LLC LEVEL CONTROL PANEL MATRIX LLC LEVEL CONTROL PANEL Installation Operation Maintenance Manual 1-26-09 REV-0.3 1 INDEX Introduction. 3 Product Configurations..... 4 I/O Descriptions. 8 Operation o Intercooler, Accumulator,

More information

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide Factory Packaged Controls OE377-26-00058 (AAON Part No. V12090) MODGAS-X Controller Table of Contents GENERAL INFORMATION... 3 Overview...3 Features...3 INSTALLATION & WIRING... 4 Supply Air Temperature

More information

ELECTROMAGNETIC LOCKS

ELECTROMAGNETIC LOCKS safety 17 18 SAFETY ELECTROMAGNETIC LOCKS 12500 Electromagnetic lock Micro series Version: for mortice fixing body in stainless steel protected against humidity Dimensions of the body (mm): 170 x 32 x

More information

SNMP dedicated to ORVALDI Solar Infini

SNMP dedicated to ORVALDI Solar Infini SNMP dedicated to ORVALDI Solar Infini User s Manual Management Software for Solar Inverter Table of Contents 1. 2. 3. Overview...1 1.1 Introduction...1 1.2 Features...1 1.3 Overlook...1 1.4 Installation

More information

GRUNDFOS INSTRUCTIONS. Control HVAC. Installation and operating instructions. Other languages. net.grundfos.com/qr/i/

GRUNDFOS INSTRUCTIONS. Control HVAC. Installation and operating instructions. Other languages. net.grundfos.com/qr/i/ GRUNDFOS INSTRUCTIONS Control HVAC Installation and operating instructions Other languages net.grundfos.com/qr/i/98800750 English (GB) English (GB) Installation and operating instructions Original installation

More information

SWA-2441/2451 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL

SWA-2441/2451 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL Instruction Manual SWA-2441/2451 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL Version 1.14 (August, 215) 1. Caution 3. Terminal Assignment Model SWA-2441 Model SWA-2451 This controller is intended to

More information

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com

More information

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0 Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n 107065-01 Revision 0 May 20, 2016 Contents Introduction 2 Installation Pre-installation 3 Installation Procedure 4 Electrical

More information

Automatic Genset Controller, AGC-4 Display readings Push-button functions Alarm handling Log list

Automatic Genset Controller, AGC-4 Display readings Push-button functions Alarm handling Log list OPERATOR'S MANUAL Automatic Genset Controller, AGC-4 Display readings Push-button functions handling Log list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com

More information

SP-32 & SP-32D SP-33, SP-33D SP-34, SP-34D. Description. Specifications. Single Stage Temperature Control

SP-32 & SP-32D SP-33, SP-33D SP-34, SP-34D. Description. Specifications. Single Stage Temperature Control SP-32, SP-32D SP-33, SP-33D SP-34, SP-34D Single Stage Temperature Control Description The SP-3x and SP-3xD series of controls are single stage, general purpose, temperature controls with wide application

More information

Advanced Battery Charger 0 ~ 15A 0 ~ 25A 0 ~ 35A 0 ~ 50A 0 ~ 80A. 3 - stage charging capability (IUOU) 90 ~ 264VAC (refer to de-rating curve)

Advanced Battery Charger 0 ~ 15A 0 ~ 25A 0 ~ 35A 0 ~ 50A 0 ~ 80A. 3 - stage charging capability (IUOU) 90 ~ 264VAC (refer to de-rating curve) Cxx Features: Universal AC input with active PFC Compatible with Lead Acid, Li-ion, Gel and AGM batteries Support optional remote controller (CR-) Voltage / temperature compensation with battery temp.

More information

HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic

HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic CONTENT 1. SUMMARY... 4 2. PERFORMANCE AND CHARACTERISTICS... 4 3. SPECIFICATIONS... 5 4. OPERATION... 6 5. PROTECTION...

More information

Model H30 Operation Manual

Model H30 Operation Manual Model H30 Operation Manual Model H30 Version 1.0 August 1, 2007 2 135 West Davenport Street Rhinelander WI 54501 Phone: 866.441.7997 Fax: 866.278.0036 info@houstonst.com www.houstonst.com 3 Table of Contents

More information

System 350 S350P Proportional Plus Integral Temperature Stage Module

System 350 S350P Proportional Plus Integral Temperature Stage Module FANs 930, 930.5 Add-On Modules Section Product/Technical Bulletin S350P Issue Date 0997 System 350 S350P Proportional Plus Integral Temperature Stage Module The S350P is used in conjunction with the A350

More information

Motor Controllers AC Semiconductor Motor Controller Type RSHP Flexy

Motor Controllers AC Semiconductor Motor Controller Type RSHP Flexy otor Controllers AC Semiconductor otor Controller Type RSHP Flexy Soft starting and stopping of 3-phase squirrel cage motors Low surge and vibration-free starting User-selected ramping profiles Integral

More information

InBin-P Pressure switches 5 Pa Pa

InBin-P Pressure switches 5 Pa Pa InBin-P Pressure switches 5 Pa... 5.000 Pa Electrical binary pressure / differential pressure switches 5 Pa...100 Pa with adjustable switch activation delay 24 VAC/DC supply voltage, potential free switching

More information

ST315B. User Handbook STAFFOR. ST315B Temperature Programmer. See separate handbook for Installation Instructions Issue: 2.00

ST315B. User Handbook STAFFOR. ST315B Temperature Programmer. See separate handbook for Installation Instructions Issue: 2.00 STAFFOR D ST315B User Handbook ST315B Temperature Programmer See separate handbook for Installation Instructions Issue: 2.00 ST315B Copyright User Handbook 2009-2016 Stafford Instruments Ltd. Date: 08

More information

Modbus Integration Integration for Modbus Functionality for VT8600 Series

Modbus Integration Integration for Modbus Functionality for VT8600 Series Modbus Integration Integration for Modbus Functionality for VT8600 Series Building Management System *For data visualization and analysis Modbus Controller VT8000 Series room controllers 2 TABLE OF CONTENTS

More information

PRELIMINARY UNIT OPERATION. Operation & Service Manual. Carrier Transicold Europe 03/09/07 Viento/Xarios/Zephyr - Unit operation Road only /Rev- #1/15

PRELIMINARY UNIT OPERATION. Operation & Service Manual. Carrier Transicold Europe 03/09/07 Viento/Xarios/Zephyr - Unit operation Road only /Rev- #1/15 UNIT OPERATION Carrier Transicold Europe 03/09/07 Viento/Xarios/Zephyr - Unit operation Road only /Rev- #1/15 UNIT OPERATION Table of content Introduction...3 Operation principle...4 Cab command description...5

More information

Troubleshooting. 3516B and 3516B High Displacement Engines for Caterpillar Built Machines. For use with 793D Off-Highway Trucks/Tractors

Troubleshooting. 3516B and 3516B High Displacement Engines for Caterpillar Built Machines. For use with 793D Off-Highway Trucks/Tractors RENR5622 September 2005 Troubleshooting 3516B and 3516B High Displacement Engines for Caterpillar Built Machines FDB1-Up (Machine) 8WM1-Up (Engine) 7TR1-Up (Engine) For use with 793D Off-Highway Trucks/Tractors

More information

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION... CONTENT 1. SUMMARY...4 2. PERFORMANCE AND CHARACTERISTICS...4 3. SPECIFICATION...5 4. OPERATION...6 4.1. DISPLAY PANEL...6 4.2. LCD ICON INSTRUCTION...7 4.3. DISPLAY INSTRUCTIONS...7 4.4. DISPLAY DESCRIPTION...8

More information

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide 32XR 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide RED ALARM LIGHT LEVEL CONTROLLER H-O-A SWITCHES HORN SILENCE INNER DOOR MOTOR STARTERS WITH INTERCHANGEABLE OVERLOAD MODULES

More information

INSTRUMENTATION & CONTROL

INSTRUMENTATION & CONTROL Irrigation Controller.................... 172 Window Controller.................... 174 Water Meter Controller.................. 176 Digital Level Switch.................... 177 Filtration Controller Set..................

More information

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016 PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS v1.1 Revised Table of Contents 1 Common Alarms and Warnings... 1 2 Common Issues... 6 2.1 Communication problems... 6 2.1.1 Controller communication

More information

Pulsar EXtreme 2200C / 3200C

Pulsar EXtreme 2200C / 3200C www.mgeups.com MGE UPS SYSTEMS Pulsar EXtreme 00C / 300C Installation and user manual P O W E R P R O V I D E R L E I B E R R U P T N T N I E U T H 3400753EN/AA - Page Introduction Thank you for selecting

More information

Advanced Battery Charger. 3 - stage charging capability (IUoU) 25A

Advanced Battery Charger. 3 - stage charging capability (IUoU) 25A Cxx Features: Universal AC input with active PFC Compatible with Lead Acid, Li-ion, Gel and AGM batteries Support optional remote controller (CR-) Voltage / temperature compensation with battery temp.

More information

User manual. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS.

User manual. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS. User manual Manual version: 2.4 dated 27/02/08 Program code: FLSTDmMCDE LEGGI

More information

SE7200 Series Installation Guide

SE7200 Series Installation Guide SE7200 Series Installation Guide 24 VAC Low Voltage Zoning Terminal Equipment Controller For Commercial HVAC Applications CONTENTS Installation 2 Preparation 2 Location 2 Installation 2 Configurable BI/UI

More information

Emotron DCM Control Unit

Emotron DCM Control Unit Emotron DCM Control Unit Data sheet English 9 2 3 4 5 6 7 8 The Emotron DCM is a control unit that remotely controls submersible pump equipment. Level sensors are not needed to initiate start and stop.

More information

GS2 Series - Introduction

GS2 Series - Introduction GS2 Series - Introduction GS2 Series Drives Rating Hp.25.5 1 2 3 5 7.5 10 kw 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 Single-Phase 115 Volt Class Single/Three-Phase 230 Volt Class Three-Phase 230 Volt Class Three-Phase

More information

DKG-109 AUTOMATIC MAINS FAILURE UNIT

DKG-109 AUTOMATIC MAINS FAILURE UNIT Tel: +90-216-466 84 60 Fax: +90-216 364 65 65 datakom@datakom.com.tr http://www.datakom.com.tr DKG-109 AUTOMATIC MAINS FAILURE UNIT FEATURES Automatic mains failure Engine control Generator protection

More information

HGM7100N SERIES (HGM7110N/7120N) GENSET CONTROLLER USER MANUAL

HGM7100N SERIES (HGM7110N/7120N) GENSET CONTROLLER USER MANUAL HGM7100N SERIES (HGM7110N/7120N) GENSET CONTROLLER USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD. Chinese trademark English trademark SmartGen make your generator smart SmartGen Technology Co.,

More information

System 350 P352AB Electronic Pressure Control Series

System 350 P352AB Electronic Pressure Control Series System 350 P352AB Electronic Pressure Control Series System 350 Product Guide 930 Basic Controls Section Product/Technical Bulletin P352AB Issue Date 0200 The P352AB controls are On/Off electronic pressure

More information

SED2. Variable Frequency Drives. with Conventional Bypass Options. Variable Frequency Drives. Description. Features F-9.

SED2. Variable Frequency Drives. with Conventional Bypass Options. Variable Frequency Drives. Description. Features F-9. SED2 with Conventional Bypass Options Important Note: VD products are only available through authorized distribution channels. To locate an authorized distributor, please contact a Siemens Building Technologies

More information

Company name: GSI Created by: Xiao Ying Wong Phone: Date: 10/03/2017 Client: Client Number: Contact:

Company name: GSI Created by: Xiao Ying Wong Phone: Date: 10/03/2017 Client: Client Number: Contact: Position Qty. Description 2 NBG 125-8-16/156 A-F2-A-BAQE Product No.: On request Non-self-priming, single-stage, centrifugal volute pump designed according to ISO 5199 with dimensions and rated performance

More information

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, P/N: , Revision 1

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, P/N: , Revision 1 Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, P/N: 107065-01, Revision 1 March 03, 2017 Contents Introduction 2 Installation Pre-installation 3 Installation Procedure 4 Electrical

More information

SmartPak Welding Controller WK-MPS-16 Constant Current

SmartPak Welding Controller WK-MPS-16 Constant Current SmartPak Welding Controller WK-MPS-16 Constant Current Features Latest state of the art ATMEL 8 bit microprocessor technology Synchronous digital welding control allows absolute precision Up to16 programmers

More information

EXPERT 2V4SA. Temperature Controller. User s manual CLEAN MODE COMPENSATION HUMIDITY OUTSIDE TEMPERATURE

EXPERT 2V4SA. Temperature Controller. User s manual CLEAN MODE COMPENSATION HUMIDITY OUTSIDE TEMPERATURE CLEAN MODE Temperature Controller User s manual CURRENT CONDITIONS ROOM TEMPERATURE PROBE TEMPERATURE OUTSIDE TEMPERATURE RELATIVE HUMIDITY STATIC PRESSURE TIME / DATE SETTINGS SET POINT / CURVE MINIMUM

More information

Signet Pressure Transmitter

Signet Pressure Transmitter Signet 8450 Pressure English 8450.090 8450.090 Rev. G /06 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal injury. Contents

More information

OPERATING INSTRUCTIONS MCP-MT1

OPERATING INSTRUCTIONS MCP-MT1 OPERATING INSTRUCTIONS MCP-MT1 MRM PROCOM Pvt Ltd ISO-9001-2008 certified organization Plot No. : 20-21, Industrial Estate, Sector - 59, Phase-II, Faridabad (Haryana) Ph.: 0129-4700400(10 Lines) Email:

More information

BMS24. Thanks for your purchasing the BMS24 for your vehicle.

BMS24. Thanks for your purchasing the BMS24 for your vehicle. BMS24 for 2S-24S LiPo & LiFe Low power consumption High accuracy 2.8 TFT LCD display Programmable Thanks for your purchasing the BMS24 for your vehicle. Read the ENTIRE instruction manual to become familiar

More information

DKG-109J AUTOMATIC MAINS FAILURE UNIT

DKG-109J AUTOMATIC MAINS FAILURE UNIT DKG-109J AUTOMATIC MAINS FAILURE UNIT CANBUS VERSION FEATURES True RMS measurements Automatic mains failure ECU control and monitoring through J1939 CAN J1939 ECU warnings displayed as text Various engine

More information

Installation Guide. ECL Comfort 210 / 310, application A231 / A Table of Contents

Installation Guide. ECL Comfort 210 / 310, application A231 / A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 4 2.1 Before you start.....................................................

More information

Aquatrac Instruments Application Note

Aquatrac Instruments Application Note 1. OBJECTIVE Provides up to two independent feed verification functions per controller. Meters chemical feed in ml, calculates and logs ppm, calculates and logs inventory, displays and logs ml/hour, supports

More information