Installation, use and maintenance instructions. Light Oil Burners. RL 70/M - 100/M - 130/M Low - High or Modulating Operation

Size: px
Start display at page:

Download "Installation, use and maintenance instructions. Light Oil Burners. RL 70/M - 100/M - 130/M Low - High or Modulating Operation"

Transcription

1 Installation, use and maintenance instructions Light Oil Burners RL 70/M - 100/M - 130/M Low - High or Modulating Operation C (3) - 10/2008

2 CONTENTS WARNING TECHNICAL DATA page 3 Burner models designations Accessories Burner description Packaging - Weight Max. dimensions Standard equipment Firing rates Minimum furnace dimensions INSTALLATION Boiler plate Blast tube length Securing the burner to the boiler Choice of nozzle Nozzle assembly Combustion head setting Fuel supply Hydraulic connections Pump Air pressure switch Servomotor Burner calibration Burner starting Burner operation Oil pressure switch Final checks Maintenance Procedure to refer burner operating condition in high altitude plants Flame signal measurements Siemens LAL control sequence of operations Siemens LAL control troubleshooting guide Factory wiring diagram - burner mounted LAL Field wiring diagram- burner mounted LAL Factory wiring diagram - remote panel Spare parts list Start up reports Do not store flammable or hazardous materials in the vicinity of fuel burning appliances. Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or death. Refer to this manual for instructional or additional information. Consult a certified installer, service representative or the gas supplier for further assistance. Burner shall be installed in accordance with manufacturers requirements as outlined in this manual, local codes and authorities having jurisdiction. N.B. Figures mentioned in the text are identified as follows: 1)(A) =part 1 of figure A, same page as text; 1)(A)p.4 =part 1 of figure A, page number 4. 2

3 TECHNICAL DATA MODEL RL 70/M RL 100/M RL 130/M Output (1) High MBtu/hr (3) GPH Low MBtu/hr (3) GPH Fuel # 2 fuel oil Operation Low - high or modulating Nozzle number 1 (return flow nozzle) Standard applications Boilers: water, steam, thermal oil Ambient temperature F (0-40 C) Combustion air temperature F max 140 (60 C) Main power supply (+/- 10%) V/Ph/Hz / 460 / 575 / 3 / 60 Fan motor rpm W - HP V A / 460 / / 2.8 / / 460 / / 3.9 / / 460 / / 5.1 / 3.7 Ignition transformer V1 - V2 I1 - I2 120 V - 2 x 5 kv 3.7 A - 35 ma Pump (1) Reference conditions: Ambient temperature 68 F (20 C) - Barometric pressure 394 WC - Altitude 329 ft a.s.l. (2) Sound pressure measured in manufacturer s combustion laboratory, with burner operating on test boiler and at maximum rated output. (3) Equivalent Btu values based on 1 USGPH = 140,000 Btu/hr. Burner models designations: delivery (at 290 PSI) pressure range fuel temperature GPH PSI F max (90 C) Electrical power consumption W max Electrical protection NEMA 1 Noise levels (2) dba Model Code VOLTAGE Flame safeguard RL 70/M RL 100/M RL 130/M C ( ) C ( ) C ( ) C ( ) C ( ) C ( ) C ( ) C ( ) C ( ) C ( ) C ( ) C ( ) /460/3/60 575/3/ /460/3/60 575/3/ /460/3/60 575/3/ /460/3/60 575/3/ /460/3/60 575/3/ /460/3/60 575/3/60 Burner mounted Burner mounted In an auxiliary panel (see Accessories) In an auxiliary panel (see Accessories) Burner mounted Burner mounted In an auxiliary panel (see Accessories) In an auxiliary panel (see Accessories) Burner mounted Burner mounted In an auxiliary panel (see Accessories) In an auxiliary panel (see Accessories) ACCESSORIES (optional): Available auxiliary panels Auxiliary panel code Flame safeguard type Fireye Landis Kit for lengthening the combustion head L = Standard length L1 = Length obtainable with the kit COD L = 1023/32 L1 = 155/32 RL 70/M COD L = 1023/32 L1 = 155/32 RL 100/M COD L = 1023/32 L1 = 155/32 RL 130/M Flame inversion boiler kit COD RL 70/M - RL 100/M COD RL 130/M Important: The installer is responsible for the supply and installation of any safety device(s) not indicated in this manual. 3

4 (A) inch A B C lbs RL 70/M 459/32 235/8 313/ RL 100/M 45 9 / / / RL 130/M 459/32 235/8 313/ (B) D2349 D36 BURNER DESCRIPTION (A) 1 Ignition electrodes 2 Combustion head 3 Screw for combustion head adjustment 4 Screw for fixing fan to flange 5 Pressure gauge for pressure on nozzle return 6 Pump 7 Non-drip nozzle holder 8 Air damper 9 Fan pressure test point 10 Boiler mounting flange 11 Flame stability disk 12 Servomotor, provides adjustment of fuel delivery regulator and of air damper. When the burner is not operating the air damper is fully closed in order to reduce to a minimum heat dispersion from the boiler. 13 Slide bars for opening the burner and inspecting the combustion head 14 Photocell (cad cell) 15 High oil pressure switch 16 Extensions for slide bars 14) (with kit) 17 Ignition transformer 18 Motor contactor and thermal overload with reset button 19 Power switch for different operations: automatic - manual - off. Button for: power increase - power reduction. 20 Valve assembly with pressure regulator on nozzle return 21 Terminal strip 22 Knockouts for electrical connections by installer 23 Flame safeguard with lock-out pilot light and lock-out reset button 24 Flame inspection window Two types of burner failure may occur: Flame safeguard Lock-out: if the Flame relay 23)(A) pushbutton lights up, it indicates that the burner is in lock-out. To reset, press the pushbutton. Motor trip: release by pressing the pushbutton on thermal overload 18)(A). PACKAGING - WEIGHT (B) - Approximate measurements The burners is supplied skid mounted. Outer dimensions of packaging are indicated in (B). The weight of the burner complete with packaging is indicated in Table (B). MAX. DIMENSIONS (C) - Approximate measurements The maximum dimensions of the burners are given in (C). Keep in mind that inspection of the combustion head requires the burner to be opened and the rear part withdrawn on the slide bars. The maximum dimension of the burner when open, without casing, is given in measurement I. RL A B C D E F (1) G H I (1) /8 1121/ / / / /32-155/32 71/ /16 377/16-423/ /8 129/ / / / /32-155/32 71/ /16 377/16-423/ /4 135/ / / / /32-155/32 77/ /16 377/16-423/4 (1) Blast tube: short - long (obtainable with the kit) D1217 STANDARD EQUIPMENT 2 - Flexible hoses 2 - Gaskets for flexible hoses 1 - Burner head gasket 4 - Screws to secure the burner flange to the boiler 1/2 W 1 - Adaptor G 1 /8 / 1 /8 NPT 1 - Instruction booklet 1 - Spare parts list (C) 4

5 Comb. chamb. WC Comb. chamb. WC FIRING RATES (A) During operation, burner output varies between: MINIMUM OUTPUT: area A; MAXIMUM OUTPUT: area B (and C for model RL 130/ M). Graphs (A): Horizontal axis : Burner output Vertical axis : Combustion chamber pressure The firing rate may be found by plotting a vertical line from the desired delivery and a horizontal line from the pressure in the combustion chamber. The intersection of these two lines is the firing rate which must lie within area A, for MIN output, and within area B, for MAX output. In order to utilize also area C (RL 130/M) it is necessary to perform the calibration of the combustion head as explained on page 6. Note: The FIRING RATE areas given in figure (A) have been reduced by 10% with respect to the maximum range that can be reached. Important: The FIRING RATE area values have been obtained considering an ambient temperature of 68 F (20 C), and an atmospheric pressure of 394 WC and with the combustion head adjusted as shown on page 7. Consult Procedure on page 15 to refer burner operating condition in high altitude plants. MINIMUM FURNACE DIMENSIONS (B) The firing rates were set in relation to certified test boilers. Figure (B) indicates the diameter and length of the test combustion chamber. Comb. chamb. WC Example Output 2579 MBtu/hr: diameter 24 inch - length 6.6 ft. (A) D2350 Diameter (inches) Furnace dimensions Length (ft) (B) D2919 5

6 inch A B C RL 70/M 79/ / /16 1/2 W RL 100/M 79/ / /16 1/2 W RL 130/M 721/ / /16 1/2 W (A) D455 INSTALLATION BOILER PLATE (A) Drill the combustion chamber mounting plate as shown in (A). The position of the threaded holes can be marked using the head gasket supplied with the burner. BLAST TUBE LENGTH (B) The length of the blast tube must be selected according to the indications provided by the manufacturer of the boiler, and it must be greater than the thickness of the boiler door complete with its insulation. The range of lengths available, L (inch), is as follows: Blast tube 9): RL 70/M RL 100/M RL 130/M short 1023/ / /32 long 155/32 155/32 155/32 For boilers with front flue passes 12) or flame inversion chambers, protective insulaton material 10) must be inserted between the boiler refractory 11) and the blast tube 9). This protective insulation must not compromise the extraction of the blast tube. For boilers having a water-cooled front the insulation 10)-11)(B) is not required unless it is required by the boiler manufacturer. (B) (C) D690 D1219 SECURING THE BURNER TO THE BOILER (B) Disassemble the blast tube 9) from the burner 6) by proceeding as follows: - Loosen the four screws 3) and remove the cover 1). - Remove the screws 2) from the two slide bars 5). - Remove the two screws 4) fixing the burner 6) to the flange 7). - Withdraw the blast tube 9) complete with flange 7) and slide bars 5). COMBUSTION HEAD CALIBRATION At this point check, for model RL 130/M, whether the maximum delivery of the burner is contained in area B or in area C of the firing rate. See page 5. If it is in area B then no operation is required. If, on the other hand, it is in area C: - Unscrew the screws 1)(C) and disassemble the blast tube 5); - Unscrew the screws 3) and remove the shutter 4); - Tighten the screws 3) on the rod 2); - Now refit the blast tube 5) and the screws 1). Once this operation has been carried out (if required), secure flange 7)(B) to the boiler plate inserting the supplied gasket 8)(B). Use the 4 screws provided after having protected the thread with an anti-seize product. The burner-boiler seal must be airtight. 6

7 (A) D1220 CHOICE OF NOZZLE (A) See diagrams (B)page 11. In case an intermediate delivery between the two values indicated in the diagrams (B) page 11 is required, a nozzle with higher delivery must be chosen. Delivery reduction will be obtained by means of the pressure regulator. RECOMMENDED NOZZLES: Type A4 return flow nozzles - 45 angle NOZZLE ASSEMBLY At this stage of installation the burner is still disassembled from the blast tube; it is therefore possible to fit the nozzle with the box wrench 1)(A), inserting the wrench through the central hole in the flame stability disk. Do not use any sealing products such as gaskets, sealing compound, or tape. Be careful to avoid damaging the nozzle sealing seat. Make sure that the electrodes are positioned as shown in Figure (B). Finally remount the burner 3)(C) on the slide bars 2) and slide it up to the flange 5), keeping it slightly raised to prevent the flame stability disk from pressing against the blast tube. Tighten the screws 1) on the slide bars 2) and screws 4) fixing the burner to the flange. D2528 (B) D1221 (C) If it proves necessary to change a nozzle with the burner already fitted to the boiler, proceed as outlined below: - Pull back the burner on its slide bars as shown in fig. (B)p.6. - Remove the nuts 1)(D) and the disk 2). - Use wrench 3)(D) to change the nozzles. COMBUSTION HEAD SETTING The setting of the combustion head depends exclusively on the maximum burner delivery at which it will be operating. Turn screw 4)(E) until the notch shown in diagram (F) is level with the front surface of flange 5)(E). Example: RL 70/M, maximum light oil delivery = 16 GPH Diagram (F) indicates that for a delivery of 16 GPH the RL 70/M Model requires the combustion head to be set to approx. three notches, as shown in Figure (E). (D) D1222 (E) D462 N Notches (F) Max Fuel oil delivery USGPH D2351 7

8 HYDRAULIC SYSTEM / H + H V P 5 7 A 1 B 3 D737 2 FUEL SUPPLY Double-pipe circuit (A) The burner is equipped with a self-priming pump which is capable of feeding itself within the limits listed in the table at the side. The tank higher than the burner A Distance "P" must not exceed 33 ft in order to avoid subjecting the pump's seal to excessive strain; distance "V" must not exceed 13 ft in order to permit pump self-priming even when the tank is almost completely empty. The tank lower than the burner B Pump suction values higher than 13 Hg must not be exceeded because at higher levels gas is released from the fuel, the pump starts making noise and its working life-span decreases. It is good practice to ensure that the return and suction lines enter the burner from the same height; in this way it will be less probable that the suction line fails to prime or stops priming. The loop circuit A loop circuit consists of a loop of piping exiting and returning to the tank with an auxiliary pump that circulates the fuel under pressure. A branch connection from the loop goes to feed the burner. This circuit is extremely useful whenever the burner pump does not succeed in self-priming because the tank distance and/or height difference are higher than the values listed in the Table. Key H = Pump/foot valve height difference L = Piping length Ø = Inside pipe diameter 1 = Burner 2 = Pump 3 = Filter 4 = Manual on/off valve 5 = Suction line 6 = Foot valve 7 = Return line (A) + H - H (ft) L (ft) Ø (inch) 3/8 1/2 5/ D1224 HYDRAULIC CONNECTIONS (B) The pumps are equipped with a by-pass that connects the return line and suction line. The pumps are installed on the burner with the by-pass closed by screw 6)(A)p.13. It is therefore necessary to connect both hoses to the pump. The pump seal will be dammaged immediately if it is run with the return line closed and the by-pass screw inserted. Remove the plugs from the suction and return connections of the pump. Insert the hose connections with the supplied seals into the connections and screw them down. Take care that the hoses are not stretched or twisted during installation. Install the hoses where they cannot be stepped on or come into contact with hot surfaces of the boiler. Now connect the other end of the hoses to the suction and return lines. (B) 8

9 PUMP SUNTEC J7 C PUMP (A) 1 - Suction 1/2" NPT 2 - Return 1/2" NPT 3 - Pressure gauge attachment G 1/8" 4 - Vacuum gauge attachment G 1/8" 5 - Pressure adjustment screw 6 - By-pass screw A - Min. delivery rate at 290 PSI pressure B - Delivery pressure range C - Max. suction pressure D - Viscosity range E - Max light oil temperature F - Max. suction and return pressure G - Pressure calibration in the factory H - Filter mesh width J7 C PUMP PRIMING - Before starting the burner, make sure that the tank return line is not clogged. Obstructions in the line could cause the seal located on the pump shaft to break. The time required for this operation depends upon the diameter and length of the suction tubing. If the pump fails to prime at the first starting of the burner and the burner locks out, wait approx. 15 seconds, reset the burner, and then repeat the starting operation as often as required. After 5 or 6 starting operations allow 2 or 3 minutes for the transformer to cool. Important: the priming operation is possible because the pump is already full of fuel when it leaves the factory. If the pump has been drained, fill it with fuel through the opening on the vacuum meter prior to starting; otherwise, the pump will seize. Whenever the length of the suction piping exceeds ft, the supply line must be filled using a separate pump. (A) AIR PRESSURE SWITCH A B C D E F G H GPH PSI Hg cst F PSI PSI inch , (90 C) ,006 D2352 AIR PRESSURE SWITCH (B) Adjust the air pressure switch after having performed all other burner adjustments with the air pressure switch set to the start of the scale (B). With the burner operating at min. output, increase adjustment pressure by slowly turning the relative dial clockwise until the burner locks out. Then turn the dial anti-clockwise by about 20% of the set point and repeat burner starting to ensure it is correct. If the burner locks out again, turn the dial anti-clockwise a little bit more. (B) 9

10 SERVOMOTOR (A) The servomotor gives simultaneous regulation of the air damper through the adjustable profile cam 2)(F) and the pressure controller (A) pag. 11. It rotates by 130 in approx. 35 s. The factory settings must not be changed for the first firing, just check that they comply with the details below. To open the servomotor, remove the screws and pull the cover outward, fig. (A). CAMS AND TRIM POTENTIOMETERS FUNC- TIONS (A) YES D2277 NO Cam 1: 130 Limits rotation towards maximum. Cam 2: 0 Limits rotation towards minimum, air damper closed on stand by. Cam 3: 20 Limits ignition position. Cams : not used Trim potentiometer MAX Limits maximum modulation. It must be set near the stroke end (cam 1) to exploit as far as possible the variable profile cam. Trim potentiometer MIN Limits minimum modulation. It must be set near the stroke end (cam 2) to exploit as far as possible the variable profile cam. Trim potentiometer POS Limits an intermediate operating position between MAX and MIN, supplying power to the "P" terminal in the servomotor (through an external command). This function cuts out any external signals. Note Using the slide switch to select MAX or MIN, the servomotor goes into the position for the respective settings of the MAX and MIN TRIM POTENTIOMETERS. When the settings are complete, place the slide switch on OPE.(operate) (B) D2585 Figure above shows how the servomotor is released to manually check there is no binding though its motion. Position jumpers Don t release the button indicated in this figure: the syncronization of the cams made in factory would be changed. Trim potentiometers Slide switch (C) (D) (E) 1 Servomotor 2 Adjustable profile cam 3 Adjustment screws for cam starting profile 4 Adjustment fixing screws 5 Adjustment screws for cam and profile D1229 (F) 10

11 PRESSURE CONTROLLER BURNER CALIBRATION The optimum calibration of the burner requires an analysis of the flue gases at the boiler outlet. The following settings that have already been made do not require modification under normal circumstances: Combustion head; Servomotor, cams I - II - III (A) Nozzle flow rate D1227 Type A4 return flow nozzle (45 ) 1 - Gauge for pressure in return line 2 - Oil pressure switch 3 - Ring for piston stop 4 - Nut and lock-nut for piston setting 5 - Eccentric adjusting screw 6 - Variable eccentric 7 - Eccentric locking screws Return pressure Delivery pressure 290 PSI The values indicated in the right side of the diagram, refer to the data printed on the nozzle. ADJUSTING THE NOZZLE FLOW RATE The nozzle flow rate varies according to the fuel pressure on the nozzle return. Diagram (B) indicates this relationship for type A4 return flow nozzles with pump delivery pressure of 290 PSI. Diagrams (B): Horizontal axis : PSI, nozzle return pressure Vertical axis : GPH, nozzle flow rate NOTE: with a pump delivery pressure of 290 PSI, the pressure on the nozzle return must not exceed PSI. The pressure difference between pump delivery and nozzle return must be at least 43.5 PSI. With smaller pressure differences, the pressure on the nozzle return can be unstable. The nozzle return pressure value is indicated by the pressure gauge 1)(A). The output and the pressure of the nozzle are at maximum when the servomotor is positioned on maximum. The fine adjustment of the pressure in the return line may be carried out by changing the setting of the eccentric 6)(A), of the nut and lock-nut 4)(A). The eccentric setting should be carried out by loosening screws 7), and turning the screw 5) to obtain the desired eccentricity. Turn clockwise, screw 5) to increase the eccentricity, increasing the difference between the min. and max. capacity of the nozzle; turn counter-clockwise, screw 5) to decrease the eccentricity and, consequently the difference between the min. and max. capacity of the nozzle. NOTE The proper setting of the eccentric 6) is possible when its operation field follows the servomotor operation field ( ): so, that every variation of the servomotor position corresponds to a pressure variation. Do not let the piston bottom out repeatedly: the stop ring 3)(A) determines the max. stroke. When the setting is carried out, verify manually that no slow-down occurs between 0 and 130 and that the maximum and minimum pressures correspond to those chosen as per diagrams (B). If you wish to check the delivery capacity of the nozzle, open the burner, attach the nozzle, simulate the startup and then proceed with observing of the maximum and minimum pressures of the fuel. If at the maximum capacity of the nozzle (maximum pressure in the return line) pressure fluctuations are detected on the gauge 1), slightly decrease the pressure in the return line until they are completely eliminated. (B) D

12 Position jumpers (A) Trim potentiometers Slide switch BURNER STARTING Close the control circuit, with the switches in fig. (C) and (E) in the AUTO position. On firing turn the switch (C) to MAN. MAXIMUM OUTPUT Using button (B), "increase output" until it stops at app. 130 (cam 1). Place the slide switch on MAX and set the relative MAX trim potentiometer (setting must be very near to 130 ) to exploit as far as possible the variable profile cam 2)(D). The setting of the oil delivery must be made on the variable eccentric 6)(A) page 11 by turning the screw 5)(A) page. 11. The air setting must be made on the variable profile cam 2)(D) after loosening the screws 4) by turning the screws 3). (B) (C) D2593 MINIMUM OUTPUT With the slide switch on the OPE position, use button (B) "decrease output" until it stops at app. 20 (cam 3). Put the slide switch in the MIN position and set the modulation minimum using the relative MIN trim potentiometer. The setting of the oil delivery must be made on the nut and lock-nut 4)(A)page.11 and, if necessary, on the variable eccentric 6)(A) page 11. Important When the eccentricity is modified, it is necessary to bring back to MAX and check the setting again. The setting must be made on the adjustable profile cam 2)(D). INTERMEDIATE OUTPUTS With the switch (C) in the AUTO position, the slide switch in the OPE position and the switch 1)(E) in the MAN position, move the button 2)(E) in various intermediate levels between maximum and minimum and set the variable profile cam 2)(D) to achieve optimum combustion, by turning the screws 3). D Servomotor 2 Adjustable profile cam 3 Adjustment screws for cam starting profile 4 Adjustment fixing screws 5 Adjustment screws for cam and profile If possible, do not change the previously set maximum and minimum levels. Do not change the eccentric, already adjusted for MAX and MIN. Check the various setting levels with a combustion analysis. Important Make a progressive setting of the profile, without sharp changes. When the setting is complete, lock the cam profile using screws 4)(D). (D) 1 2 (E) D791 12

13 (A) D2444 BURNER OPERATION BURNER STARTING (A) - (B) Operating control closes, the motor starts. The pump 3) draws the fuel from the tank through the piping 1) and pumps it under pressure for delivery. The piston 4) rises and the fuel returns to the tank through the piping 5) - 7). The screw 6) closes the by-pass heading towards suction and the de-energized solenoid valves 8) - 9) - 2) close the passage to the nozzle. Servomotor starts: 130 rotation to right, until contact is made on cam 1. The air damper is positioned on MAX. output. Pre-purge stage with air delivery at MAX. output. Servomotor rotates to left until contact is made on cam 3. Air damper and pressure regulator are positioned on MIN output. Ignition electrode strikes a spark. Solenoid valves 8) - 9) - 2) open; the fuel passes through the piping 10) and filter 11), and enters the nozzle. A part of the fuel is then sprayed out through the nozzle, igniting when it comes into contact with the spark: flame at a low output level; the rest of the fuel passes through piping 12 at the pressure adjusted by the regulator 13, then, through piping 7), it goes back into the tank. The spark goes out. The starting cycle ends. STEADY STATE OPERATION At the end of the starting cycle, the servo-motor control then passes to load control for boiler pressure or temperature. If the temperature or pressure is low (and the load control is consequently closed), the burner progressively increases output up to MAX. If subsequently the temperature or pressure increases until the load control opens, the burner progressively decreases output down to MIN. The burner shuts off when demand for heat is less than the heat supplied by the burner in the MIN output. The servomotor returns to the 0 angle limited by contact with cam 2. The air damper closes completely to reduce thermal dispersion to a minimum. Every time output is changed, the servomotor automatically modifies oil delivery (pressure regulator) and air delivery (fan damper). FIRING FAILURE If the burner does not fire, it goes into lock-out within 5 s of the opening of the light oil valve. FIRING FAILURE If the flame should go out for accidental reasons during operation, the burner will lock out in 1 s. OIL PRESSURE SWITCH The oil pressure switch 15)(A) page 4 is factory set to 43.5 PSI (3 bar). If the oil pressure goes above this value in the return piping, the pressure switch stops the burner. Burner starts again automatically if the pressure goes down under 43.5 PSI (3 bar) after burner shut down. If a loop circuit with Px pressure feeds the burner, the pressure switch should be adjusted to Px PSI. 13

14 FINAL CHECKS Obscure the photocell and switch on the control devices: the burner should start and then lock-out about 5 s after starting. Illuminate the photocell and switch on the control devices: burner should go into lock-out. Obscure the photocell while the burner is operating: flame should go out and burner lock out within 1 s. Switch off control devices while the burner is operating: the burner should stop. MAINTENANCE Combustion An analysis of the flue gases at the boiler outlet is required. Significant differences with respect to the previous measurements indicate the points where more care should be exercised during maintenance. Pump The pump delivery pressure must be stable at 290 PSI. The suction must be less than 6.5 PSI. Unusual noise must not be evident during pump operation. If the pressure is found to be unstable or if the pump runs noisily, the flexible hose must be detached from the line filter and the fuel must be sucked from a tank located near the burner. This measure permits the cause of the anomaly to be traced to either the suction line or the pump. If the pump is found to be responsible, check to make sure that the filter is not dirty. The vacuum gauge is installed up-line from the filter and consequently will not indicate whether the filter is clogged or not. If the problem lies in the suction line, check to make sure that the filter is clean and that air is not entering the piping. Servomotor Disengage the cam 4)(A)p.10 from the servomotor and turn it backwards and forwards by hand to make sure it moves freely. Filters (A) Check the following filters: on line 1) in pump 2) at nozzle 3), and clean or replace as required. If rust or other impurities are observed inside the pump, use a separate pump to suck out any water and other impurities that may have deposited on the bottom of the tank. Combustion head Check to make sure that all the parts of the combustion head are in good condition, positioned correctly, free of all impurities, and that no deformation has been caused by operation at high temperatures. Nozzle Do not clean the nozzle orifices. Replace the nozzles every 2-3 years or whenever necessary. Combustion must be checked after the nozzles have been changed. Photocell (cad cell) (B) Clean the glass cover from any dust that may have accumulated. Photocell 1) can be removed by pulling it outward forcefully. Flame inspection window (C) Clean the glass. Flexible hoses Check to make sure that the flexible hoses are still in good condition. Fuel tank Every 5 years, or whenever necessary, suck out any water or other impurities present on the bottom of the tank using a separate pump. Burner Make sure that the screws are fully tightened. TO OPEN THE BURNER (D) - Switch off the electrical power - Loosen screws 1) and withdraw the cover 2) - Unscrew screws 3) - Fit the two extensions 4) supplied with a kit on request onto the slide bars 5) (models with long blast tube) - Pull part A backward keeping it slightly raised to avoid damaging the disk 6) on blast tube 7). FUEL PUMP AND/OR COUPLINGS REPLACEMENT (E) As per fig. (E), dimension X should set as follows: RL70/M - 1/2 RL100/M - 5/16 RL130/M - 7/16 (A) (B) (D) D1232 D1233 D707 D709 (C) (E) X dimension D

15 PROCEDURE TO REFER BURNER OPERATING CONDITION IN HIGH ALTITUDE PLANTS - Find the corrected burner capacity for the plant s altitude in chart 1 and the corrected pressure in chart 2. - Check in the firing rate graph of the burner (page 5), if the working point defined by the values above is within the range limits. If not, higher burner size is needed. Note Charts are based only on altitude variation (reference temperature = 68 F, 20 C) To get the combined correction in case of different air temperature, a compensation of 1000 ft each 20 F (305 m each 11 C) is applicable. Example Rated capacity = 3000 MBtu/hr - Rated air pressure = 1.5 w.c. Real altitude = 5000 ft - Real temperature = 108 F Δ = 108 F - 68 F (reference temp.) = 40 F (equivalent 2000 ft variation) Proceeding as descripted above and considering a virtual altitude of ( ) ft: - the corrected capacity is 3847 MBtu/hr; Burner RL 100/M is OK - the corrected burner air pressure is CORRECTED BURNER CAPACITY ACCORDING TO ALTITUDE Altitude Rated Capacity m. a.s.l ft a.s.l Average barometric Pressure (20 C) mbar ,4 942,8 908,2 875,8 843,5 811,85 779,8 747,8 Average barometric Pressure (68 F) "w.c CORRECTED BURNER AIR PRESSURE ACCORDING TO ALTITUDE Altitude Rated Pressure m. a.s.l ft a.s.l ,50 0,49 0,50 0,51 0,53 0,55 0,57 0,59 0,62 0,64 0,67 1,00 0,99 1,00 1,02 1,06 1,10 1,14 1,19 1,23 1,28 1,34 1,50 1,48 1,50 1,53 1,59 1,65 1,71 1,78 1,85 1,92 2,01 2,00 1,97 2,00 2,05 2,12 2,20 2,28 2,37 2,46 2,56 2,67 2,50 2,47 2,50 2,56 2,65 2,75 2,85 2,96 3,08 3,21 3,34 3,00 2,96 3,00 3,07 3,18 3,30 3,43 3,56 3,70 3,85 4,01 3,50 3,46 3,50 3,58 3,71 3,85 4,00 4,15 4,31 4,49 4,68 4,00 3,95 4,00 4,09 4,24 4,40 4,57 4,74 4,93 5,13 5,35 4,50 4,44 4,50 4,60 4,77 4,95 5,14 5,33 5,54 5,77 6,02 5,00 4,94 5,00 5,12 5,30 5,51 5,71 5,93 6,16 6,41 6,69 5,50 5,43 5,50 5,63 5,83 6,06 6,28 6,52 6,77 7,05 7,35 6,00 5,92 6,00 6,14 6,36 6,61 6,85 7,11 7,39 7,69 8,02 6,50 6,42 6,50 6,65 6,89 7,16 7,42 7,71 8,01 8,34 8,69 7,00 6,91 7,00 7,16 7,42 7,71 7,99 8,30 8,62 8,98 9,36 7,50 7,40 7,50 7,67 7,96 8,26 8,56 8,89 9,24 9,62 10,03 8,00 7,90 8,00 8,18 8,49 8,81 9,13 9,48 9,85 10,26 10,70 8,50 8,39 8,50 8,70 9,02 9,36 9,71 10,08 10,47 10,90 11,37 9,00 8,88 9,00 9,21 9,55 9,91 10,28 10,67 11,09 11,54 12,04 9,50 9,38 9,50 9,72 10,08 10,46 10,85 11,26 11,70 12,18 12,70 10,00 9,87 10,00 10,23 10,61 11,01 11,42 11,86 12,32 12,82 13,37 Average barometric Pressure (20 C) mbar ,4 942,8 908,2 875,8 843,5 811,85 779,8 747,8 Average barometric Pressure (68 F) "w.c Reference conditions (Charts 1-2): Ambient temperature 68 F (20 C) - Barometric pressure 394 WC (1000 mbar) - Altitude 328 ft a.s.l. (100 m a.s.l.) 15

16 LAL2... Sub-base FLAME SIGNAL MEASUREMENT (A) Min value for a good signal: 8 μa. If the value is lower, it can be due to: Worn photocell; Low current; Bad set up of the burner. In order to measure the current, use a microammeter of 100 μa c.c., connected to the scanner, as in the diagram. Min. detector current required at AC 230 V 8 μa Max. detector current required without flame 0.8 μa Max. detector current that can occur 35 μa (A) D3206 Instrument s + pole to term. 22 Length of detector line Full modulation In the same cable as the control lines Separate cable in the cable duct not perm. 20 m Three-wire cable --- Two-wire cable for the detector line (bl, sw); separate single-wire cable for the line (br) --- Shielded cable (e.g. RG62, shielding insulated) 200 m Shielding to term. 23 SEQUENCE OF OPERATION - LAL CONTROL See fig. (B) - (C). Switching times are given in seconds, in the burner startup sequence. LAL 2.25 t1 t2 t3 t t5 t6 t7 t8 optional optional 12 4 (B) High - low D2871 Legend for the times t1 Pre-purge time with air damper open t2 Safety time t3 Pre-ignition time, short ( Z connected to terminal 16 ) t4 Interval between voltage at terminals 18 and 20 t5 Air damper running time to OPEN position t6 Air damper running time to low-flame position (MIN) t7 Permissible after-burn time t8 Interval to the OPEN command for the air damper (C) D

17 BURNER FAULTS SYMBOL (1) FAULT PROBABLE CAUSE SUGGESTED REMEDY The burner does not start 1 - A limit or safety control device is open Adjust or replace 2 - Control box lock-out Reset control box 3 - Oil pressure switch tripped Adjust pressure switch or eliminate pressure 4 - Motor protection tripped Reset thermal cut-out 5 - No electrical power supply Close all switches - Check connections 6 - Flame safeguard fuse blown Replace 7 - Contact II of servomotor does not operate, Adjust cam II or replace servomotor flame safeguard terminals Pump is jammed Replace 9 - Defective motor command control device Replace 10 - Defective Flame safeguard Replace 11 - Defective electrical motor Replace The burner does not start and a function lock-out occurs 12 - Flame simulation Replace control box 13 - Photocell short-circuit Replace photocell 14 - Missing phase Reset thermal cut-out thermal cut-out trips when third phase is re-connected The burner starts but stops at maximum air damper setting 15 - Contact I of servomotor does not operate, Adjust cam I or replace servomotor flame safeguard terminals 9-8 The burner starts and then goes 16 - Fault in flame detection circuit Replace flame safeguard into lock-out The burner remains in pre-purging 17 - Contact III of servomotor does not operate, Adjust cam III or replace servomotor phase flame safeguard terminals I After pre-purge and the safety time, the burner goes to lock-out and the flame does not appear The flame ignites normally but the burner locks out when the safety time has elapsed Firing with pulsations or flame detachment, (lift off) delayed firing The burner does not pass to 2nd stage Uneven fuel supply Internally rusted pump Noisy pump, unstable pressure Pump loses prime after prolonged pause Pump leaks light oil Smoke in flame - dark Bacharach - yellow Bacharach Dirty combustion head During operation, the burner stops in lock out 18 - No fuel in tank; water on tank bottom Top up fuel level or suck up water 19 - Inappropriate head and air damper adjustments Adjust 20 - Light oil solenoid valves fail to open Check connections; replace coil 21 - Nozzle clogged, dirty, or deformed Replace 22 - Dirty or poorly adjusted firing electrodes Adjust or clean 23 - Grounded electrode due to broken insulation Replace 24 - High voltage cable defective or grounded Replace 25 - High voltage cable deformed by high temperature Replace and protect 26 - Ignition transformer defective Replace 27 - Poor electrical connections of valves or transformer..... Check 28 - Defective flame safeguard Replace 29 - Pump unprimed Prime pump and see "Pump unprimes 30 - Pump/motor coupling broken Replace 31 - Pump suction line connected to return line Correct connection 32 - Valves up-line from pump closed Open 33 - Filters dirty: line - pump - nozzle Clean 34 - Incorrect motor rotation direction Change motor electrical connections 35 - Defective photocell or flame safeguard Replace photocell or flame safeguard 36 - Dirty photocell Clean 37 - Poorly adjusted head Adjust 38 - Poorly adjusted or dirty firing electrodes Adjust 39 - Poorly adjusted fan air gate: too much air Adjust 40 - Nozzle unsuited for burner or boiler See Nozzle Table 41 - Defective nozzle Replace 42 - Inappropriate pump pressure Adjust 43 - Control device TR does not close Adjust or replace 44 - Defective control box Replace 45 - Check if cause is in pump or Feed burner from tank fuel supply system located near burner 46 - Water in tank remove water from tank bottom with separate pump 47 - Air has entered the suction line Tighten connectors - Depression value too high (higher than 35 cm Hg): 48 - Tank/burner height difference too great Feed burner with loop circuit 49 - Piping diameter too small Increase 50 - Suction filters clogged Clean 51 - Suction valves closed Open 52 - Paraffin solidified due to low temperature Add additive to light oil 53 - Return pipe not immersed in fuel Bring to same height as suction pipe 54 - Air enters suction piping Tighten connectors 55 - Leakage from sealing organ Replace pump 56 - Not enough air Adjust head and fan damper 57 - Nozzle worn or dirty Replace 58 - Nozzle filter clogged Clean or replace 59 - Erroneous pump pressure Adjust 60 - Flame stability disk dirty, loose, or deformed Clean, tighten in place, or replace 61 - Boiler room air vents insufficient Increase 62 - Too much air Adjust head and fan damper 63 - Nozzle or filter dirty Replace 64 - Unsuitable nozzle delivery or angle See recommended nozzles 65 - Loose nozzle Tighten 66 - Impurities on flame stability disk Clean 67 - Wrong head adjustment or not enough air Adjust, open air damper 68 - Blast tube length unsuited to boiler Contact boiler manufacturer 69 - Dirty or defective photocell Clean or replace (1) When the burner does not fire or stops following a fault, the symbol which appears on control box after lockout indicates type of problem. (2) The fuse is located in the rear part of the control box. A spare fuse is also available located under a break off tang. 17

18 Factory Wiring Diagram RL /M with burner mounted Siemens LAL control D2815 Continuous fan operation Change the wire connection from terminal 7 to terminal 1, move the jumper from terminals to terminals 4-12 and remove the wire from terminal 13 of control box. (A) LAYOUT (A) Burners RL 70/M - RL 100/M - RL 130/M Key to Layout (A) CMV - Motor contactor DA - Control box FR - Photocell MB - Terminal strip MV - Fan motor PA - Air pressure switch PO - High oil pressure switch RT - Thermal overload S1 - Switch for following operations : MAN = manual AUT = automatic D2873 OFF S2 - Button for : - = power reduction + = power increase SM - Servomotor TA - Ignition transformer TB - Burner ground (earth) connection VM - Delivery pump valve VS - Delivery pump valve (safety valve) VR - Valve on nozzle return 18

19 Field Wiring Diagram RL /M with burner mounted LAL flame safeguard D V RL 70/M RL 100/M RL 130/M 460 V 575 V 230 V 460 V 575 V V 460 V 575 V F A T10 T6 T6 T15 T10 T6 T15 T10 T10 S AWG Motor Connection (A) D3686 FIELD WIRING CONNECTIONS set by installer Use flexible cables according to local regulation. LAYOUT (A) RL /M electrical connection three-phase /460 V power supply Key to wiring layouts (A) H1 - Remote lock-out signal H2 - Burner on signal H4 - Power on signal H5 - Limit satisfied IN - Manual burner stop switch MB - Terminal strip PS - Remote lock-out reset OC - Operating control. HL - High limit control. N.B. The setting of the thermal overload must be according to the total burner amperage draw. The RL /M burners leave the factory preset for: V power supply: only in this case, if 460 V power supply is required, change the fan and the pump motor connection from delta to star and change the setting of the thermal overload as well; - or 575 V power supply; depending on the burner model (see page 3). The RL 70/M - RL 100/M - RL 130/M burners have been type-approved for intermittent operation. This means they should be stopped at least once every 24 hours to enable the control box to perform self checks at start-up. Burner halts are normally provided for automatically by the boiler load control system. 19

20 Factory Wiring Diagram RL /M With auxiliary panel 20 (A)

21 Factory Wiring Diagram RL /M With auxiliary panel 21 (B)

22 LAYOUT (A) - (B) page Burners RL /M The flame safeguard is in an auxiliary panel. See the internal electrical systems of the auxiliary panel in order to have the complete wiring diagram. Key to Layouts (A) - (B) B2 - Photocell BB - On the burner F1 - Fan motor thermal overload K1 - Fan motor contactor M1 - Fan motor SM - Servomotor S10 - Air pressure switch S14 - High oil pressure switch TB - Burner ground (earth) connection T1 - Ignition transformer XMB - Burner terminal strip XMQ - Auxiliary panel terminal strip XQ1-3-pin plug-socket XQ2-12-pin plug-socket XQ3-12-pin plug-socket XQ4-12-pin plug-socket Y20 - Safety oil valve Y21 - Oil valve on delivery Y24 - Oil valve on return 22

23 SPARE PARTS LIST

24 N. CODE DESCRIPTION DESCRIZIONE C ( ) C ( ) C ( ) * C ( ) * C ( ) C ( ) C ( ) * C ( ) * C ( ) C ( ) C ( ) * C ( ) * BURNER SERIAL NUMBER MATRICOLA BRUCIATORE AIR INTAKE BOCCA D'ASPIRAZIONE AIR DAMPER ASSEMBLY GRUPPO SERRANDA GRID PROTEZIONE SEAL GUARNIZIONE CONNECTOR RACCORDO CONNECTOR RACCORDO CONNECTOR RACCORDO CONNECTOR RACCORDO AIR PRESSURE SWITCH PRESSOSTATO ARIA DRIVE DISC DISCO ELASTICO TUBE TUBO SEAL GUARNIZIONE FILTER FILTRO CONNECTOR RACCORDO BAR PERNO SEAL GUARNIZIONE PLUG TAPPO OIL PRESSURE SWITCH PRESSOSTATO OLIO ANCHOR PLATE PIASTRA PUMP SEAL ORGANO DI TENUTA BASE PLATE MENSOLA BASE PLATE MENSOLA 22 C CONTROL BOX LAL 2.25 APPARECCHIATURA LAL SUPPORT SUPPORTO SWITCH INTERRUTTORE MEMBRAN MEMBRANA COVER COFANO OVERLOAD+CONTACTOR /460V RELE' TERMICO+CONTATTORE /460V OVERLOAD+CONTACTOR /460V RELE' TERMICO+CONTATTORE /460V OVERLOAD+CONTACTOR /460V RELE' TERMICO+CONTATTORE /460V OVERLOAD+CONTACTOR 575V RELE' TERMICO+CONTATTORE 575V OVERLOAD+CONTACTOR 575V RELE' TERMICO+CONTATTORE 575V OVERLOAD+CONTACTOR 575V RELE' TERMICO+CONTATTORE 575V TRANSFORMER TRASFORMATORE PRESSURE GAUGE MANOMETRO BEARING CUSCINETTO SOUND DAMPING FONOASSORBENTE INSPECTION WINDOW VISORE FAN GIRANTE FAN GIRANTE FAN GIRANTE DRIVE COUPLING GRUPPO GIUNZIONE DRIVE COUPLING GRUPPO GIUNZIONE NEEDLE VALVE VALVOLA DI SCARICO

25 N. CODE DESCRIPTION DESCRIZIONE C ( ) C ( ) C ( ) * C ( ) * C ( ) C ( ) C ( ) * C ( ) * C ( ) C ( ) C ( ) * C ( ) * BURNER SERIAL NUMBER MATRICOLA BRUCIATORE O RING ANELLO OR HALF-SHELL GUSCIO MOTOR /460V MOTORE /460V MOTOR /460V MOTORE /460V MOTOR /460V MOTORE /460V MOTOR 575V MOTORE 575V MOTOR 575V MOTORE 575V MOTOR 575V MOTORE 575V SERVOMOTOR SERVOMOTORE SCREW VITE BAR PERNO 42 C P.E. CELL FOTORESISTENZA PLUG TAPPO PUMP POMPA SUPPORT SUPPORTO TUBE TUBO H.T. LEAD COLLEGAMENTO ELECTRODE ELETTRODO U BOLT CAVALLOTTO SUPPORT SUPPORTO NUT DADO NOZZLE HOLDER ASSEMNLY GRUPPO PORTAUGELLO DIFFUSER DISC ELICA DIFFUSER DISC ELICA SPACER DISTANZIALE CONTROL DEVICE GRUPPO REGOLATORE FRONT PIECE FRONTONE FRONT PIECE FRONTONE SQUARE SQUADRETTA SQUARE SQUADRETTA SQUARE SQUADRETTA SHUTTER OTTURATORE SHUTTER OTTURATORE END CONE IMBUTO FIAMMA END CONE IMBUTO FIAMMA END CONE IMBUTO FIAMMA CONNECTOR RACCORDO 62 C CONTROL BOX BASE ZOCCOLO LEVER LEVA BAR PERNO BAR PERNO PIN JOINT SNODO SFERICO BEARING CUSCINETTO

26 N. CODE DESCRIPTION DESCRIZIONE C ( ) C ( ) C ( ) * C ( ) * C ( ) C ( ) C ( ) * C ( ) * C ( ) C ( ) C ( ) C ( ) BURNER SERIAL NUMBER MATRICOLA BRUCIATORE TUBE TUBO TUBE TUBO CONNECTOR RACCORDO TIE ROD TIRANTE CONNECTOR RACCORDO LEVER LEVA BEARING CUSCINETTO FLAT SPRING MOLLA CAM ASSEMBLY CAMMA COMPLETA SPRING MOLLA SHAFT ALBERO COIL BOBINA O RING ANELLO OR SEAL GUARNIZIONE NUT DADO MODULATOR MODULATORE CONNECTOR RACCORDO CONNECTOR RACCORDO PLUG SPINA

Light Oil Burners RL 190/M Low - High or Modulating Operation

Light Oil Burners RL 190/M Low - High or Modulating Operation Installation, use and maintenance instructions Light Oil Burners RL 190/M Low - High or Modulating Operation C6505049-2916051 (5) - 03/2008 CONTENTS TECHNICAL DATA...............................page 3

More information

Light oil burners. Low - High or modulating operation. Installation, use and maintenance instructions

Light oil burners. Low - High or modulating operation. Installation, use and maintenance instructions Installation, use and maintenance instructions GB Light oil burners Low - High or modulating operation CODE MODEL C9514300 - C9514301 - C9514303 RL 70/M C9515300 - C9515301 - C9515303 RL 100/M C9516300

More information

Light oil burners. Low - high or modulating operation. Installation, use and maintenance instructions

Light oil burners. Low - high or modulating operation. Installation, use and maintenance instructions Installation, use and maintenance instructions GB Light oil burners Low - high or modulating operation CODE MODEL 20011027 RL 190/M 3477870 RL 190/M 3477875 RL 190/M 2916051 (12) - 11/2014 CONTENTS INFORMATION

More information

CODE MODEL TYPE PRESS GW 605 T80

CODE MODEL TYPE PRESS GW 605 T80 Installation, use and maintenance instructions Pressure jet burner CODE MODEL TYPE 3473784 PRESS GW 605 T80 291 (2) - 08/2012 Thermal power 107 / 178-350 kw - 92.000 / 153.000-301.000 kcal/h Output 9/15-30

More information

Kerosene - oil burner

Kerosene - oil burner Installation, use and maintenance instructions Kerosene - oil burner Two stage operation CODE MODEL TYPE 3746686 G0D 76T8 90 (0) TECHNICAL FEATURES Thermal power output 44 / 54 0 kw 3.7 / 4.5 0 kg/h Fuel

More information

Light oil - kerosene burner

Light oil - kerosene burner Installation, use and maintenance instructions Light oil - kerosene burner One stage operation CODE MODEL TYPE 3747455 G0KI 474T5 90403 (4) - 0/008 TECHNICAL DATA Thermal power output 95 3 kw 8 8 kg/h

More information

Oil - kerosene burner

Oil - kerosene burner Installation, use and maintenance instructions Oil - kerosene burner One stage operation CODE MODEL TYPE 374445 G5 444T50 9038 () TECHNICAL FEATURES Thermal power output 8 0 kw.3 5 kg/h Fuel Gas oil 35s,

More information

EC 200 EC 300 GE 360 GE 400 GE 600 L-S BM

EC 200 EC 300 GE 360 GE 400 GE 600 L-S BM DIESEL SPACE HEATER - SERVICE MANUAL INDEX 1. CONTROLS AND COMPONENTS 2. FLAME CONTROL CYCLES 3. MAINTENANCE SCHEDULE 4. REPAIR PROCEDURES 1. FAN MOTOR ASSEMBLY 2. FUEL FILTER ASSEMBLY 3. FUEL PUMP ASSEMBLY

More information

CODE MODEL TYPE G3BF 490T G5BF 492T G5BF 489T53

CODE MODEL TYPE G3BF 490T G5BF 492T G5BF 489T53 Installation, use and maintenance instructions Kerosene burners One stage operation CODE MODEL TYPE 3749053 G3BF 490T53 374957 G5BF 49T57 3748953 G5BF 489T53 9036 (6) TECHNICAL FEATURES TYPE - Boiler

More information

RL/M BLU SERIES. Low NOx Modulating Light Oil Burners FIRING RATES. LOW NOx T. M 190/ kw M 223/ kw

RL/M BLU SERIES. Low NOx Modulating Light Oil Burners FIRING RATES. LOW NOx T. M 190/ kw M 223/ kw LOW NOx T The RL/M BLU burners series covers a firing range from 360 to 1023 kw, and it has been designed for use in hot or superheated water boilers, hot air or steam generators and diathermic oil boilers.

More information

X4 Installation and Operation Manual - POWER FLAME INCORPORATED

X4 Installation and Operation Manual - POWER FLAME INCORPORATED 7.13.2 Set the burner s combustion air inlet damper to the approximate setting as shown in this manual for the desired firing rate. Also, verify that the correct main orifice is installed in the main orifice

More information

VAL6 KBE5S. Service Manual

VAL6 KBE5S. Service Manual VAL6 KBE5S Service Manual 1 2 Specifications Type VAL6 KBE5S Heat Output 111,000BTU/h Fuel Kerosene, Diesel Tank Capacity 9 gallons Fuel Consumption 0.85gallon/h Power Source 120V, 60Hz single phase Power

More information

Installation- and maintenance instruction BENTOFLEX ST 108 PL

Installation- and maintenance instruction BENTOFLEX ST 108 PL Installation- and maintenance instruction BENTOFLEX ST 108 PL 1 171 625 30 03-01 178 001 13 DESCRIPTION COMPONENTS 1. Reset button 2. Control box 3. Ignition transformer 4. Ignition cables 5. Nozzle assembly

More information

Installation- and maintenance instruction BENTOFLEX ST120KAV

Installation- and maintenance instruction BENTOFLEX ST120KAV Installation- and maintenance instruction BENTOFLEX ST120KAV 1 171 625 61 05-01 178 001 16 DESCRIPTION COMPONENTS 1. Reset button 2. Control box 3. Ignition transformer 4. Ignition cables 5. Nozzle assembly

More information

HVF110, 210, 310, 410HD

HVF110, 210, 310, 410HD 342 N. Co. Rd. 400 East Valparaiso, IN 46383 219-464-8818 Fax 219-462-7985 www.heatwagon.com Installation and Maintenance Manual Please retain this manual for future reference. HVF110, 210, 310, 410HD

More information

Installation- and maintenance instruction B80-2/3

Installation- and maintenance instruction B80-2/3 Installation- and maintenance instruction B80-2/3 1 171 625 22 05-01 178 002 64 DESCRIPTION COMPONENTS 1. Flame cone 2. Shrouded disc 3. Nozzle 4. Nozzle assembly 5. Ignition electrodes 6. Ignition cable

More information

Installation- and maintenance instruction ST120 S75/21

Installation- and maintenance instruction ST120 S75/21 Installation- and maintenance instruction ST120 S75/21 1 171 615 30 05-01 178 058 15 DESCRIPTION Components 1. Reset button 2. Control box 3. Ignition transformer 4. Ignition cables 5. Nozzle assembly

More information

Mobile Diesel Heaters TOR / MIR Technical Training Course

Mobile Diesel Heaters TOR / MIR Technical Training Course Mobile Diesel Heaters TOR / MIR Technical Training Course 1 Rev. No. 0 March 3 rd, 2010 MIR Indirect-fired Diesel Heaters MIR 37 WE MIRAGE 37 H MIR 55 WE MIRAGE 55 H (EURO MODELS) MIR 85 WE MIRAGE 85 H

More information

PAGE 1. TES Operation & Testing Guidelines: Tes Trouble shooting

PAGE 1. TES Operation & Testing Guidelines: Tes Trouble shooting PAGE 1 This document outlines questions to ask and components to check during TES troubleshooting. More detailed troubleshooting procedures are available in the TES Troubleshooting Guide. 1. Flow Light

More information

Weishaupt Monarch oil burners Sizes 5 to 11 1/2002 CA

Weishaupt Monarch oil burners Sizes 5 to 11 1/2002 CA Weishaupt Monarch oil burners Sizes 5 to 11 1/2002 CA 1 Description, Types of regulation, Model overview Weishaupt Monarch oil burners are of the fully automatic pressure atomizing type. Their design has

More information

TWO STAGE PROGRESSIVE AND MODULATING GAS BURNERS RIELLO 40 GS/M SERIES GS 10/M 22/ kw GS 20/M 43/ kw

TWO STAGE PROGRESSIVE AND MODULATING GAS BURNERS RIELLO 40 GS/M SERIES GS 10/M 22/ kw GS 20/M 43/ kw TWO STAGE PROGRESSIVE AND MODULATING GAS BURNERS RIELLO GS/M SERIES GS /M / 5 3/8 19 The Riello GS/M series of two stage progressive or modulating gas burners, is a complete range of products developed

More information

Installation- and maintenance instruction BENTOFLEX ST133KA/K

Installation- and maintenance instruction BENTOFLEX ST133KA/K Installation- and maintenance instruction BENTOFLEX ST133KA/K 178 007 17 DESCRIPTION Components 1. Reset button 2. Control box 3. Ignition transformer 4. Ignition cables 5. Nozzle assembly 6. Nozzle 7.

More information

TROUBLESHOOTING. 1. What is the model and serial number? If you don t know, how old is it? Give description.

TROUBLESHOOTING. 1. What is the model and serial number? If you don t know, how old is it? Give description. TROUBLESHOOTING There is excellent literature on our website: heatec.com. Look under TEC-NOTE. You will find our newest heater manual. This is full of information (complete with great pictures) on our

More information

E Series CE Approved Intermittent Pilot Ignition Control

E Series CE Approved Intermittent Pilot Ignition Control Installation Instructions Issue Date January 11, 2013 E Series CE Approved Intermittent Pilot Ignition Control Application The E Series CE Approved Intermittent Pilot Ignition Control is a safety control

More information

ONE STAGE GAS BURNERS RDBS SERIES

ONE STAGE GAS BURNERS RDBS SERIES ONE STAGE GAS BURNERS RDBS SERIES 16 47 kw RDBS.1 16 47 kw The Riello RDBS is a new series of one stage gas burners with integrated gas train, characterised by its small dimensions in spite of its high

More information

Modulating Furnace Information. Warning on Meter Setting - Read First!

Modulating Furnace Information. Warning on Meter Setting - Read First! Modulating Furnace Information Pressure Transducer Pressure DC Volts 0.00" 0.25 0.20" 0.63 0.25" 0.72 0.30" 0.82 0.35" 0.91 0.40" 1.00 0.45" 1.09 0.50" 1.19 0.55" 1.28 0.60" 1.38 0.65" 1.47 0.70" 1.56

More information

2.0 Burner Operating Parameters and Requirements

2.0 Burner Operating Parameters and Requirements ECLIPSE INFORMATION GUIDE Silicon Carbide Radiant Auto-Recupes Info 322 2/99 WARNING Handle silicon carbide tubes carefully. Do not drop them or hammer on them. Although they feature excellent mechanical

More information

RS SERIES. Two Stage Progressive Gas Burners FIRING RATES

RS SERIES. Two Stage Progressive Gas Burners FIRING RATES The RS burners series covers a firing range from 44 to 2290 kw, and it has been designed for use in low or medium temperature hot water boilers, hot air or steam boilers, diathermic oil boilers. Operation

More information

Installation- and maintenance instruction B20KA/K

Installation- and maintenance instruction B20KA/K Installation- and maintenance instruction B20KA/K 1 171 615 27 05-01 178 091 07 DESCRIPTION COMPONENTS 1. Air intake 2. Scale, nozzle assembly 3. Nozzle assembly adjustment 4. Test nipple 5. Ignition cables

More information

TWO STAGE LIGHT OIL BURNERS PRESS G SERIES

TWO STAGE LIGHT OIL BURNERS PRESS G SERIES TWO STAGE LIGHT OIL BURNERS PRESS G SERIES 7/178 356 kw PRESS 1G 13/19 534 kw PRESS 2G 214/356 712 kw PRESS 3G 273/534 1168 kw PRESS 4G 415/83 166 kw The PRESS G series of burners covers a firing range

More information

USE and MAINTENANCE INSTRUCTION MANUAL AZ3 HTE2 AZ3 HTE2 HVLP GRAVITY. SPRAY GUN Series. en it fr es pt de se

USE and MAINTENANCE INSTRUCTION MANUAL AZ3 HTE2 AZ3 HTE2 HVLP GRAVITY. SPRAY GUN Series. en it fr es pt de se USE and MAINTENANCE INSTRUCTION MANUAL AZ3 HTE2 AZ3 HTE2 HVLP GRAVITY SPRAY GUN Series en it fr es pt de se TECHNICAL DATA Technical AZ3 HTE2 AZ3 HTE2 HVLP 1.0 80 180 1.3 10-15HTE 140 200 240 1.5 2.0 160

More information

Installation- and maintenance instruction B20KAV/KV

Installation- and maintenance instruction B20KAV/KV Installation- and maintenance instruction B20KAV/KV 1 171 615 33 05-01 178 035 08 DESCRIPTION COMPONENTS 1. Air intake 2. Scale, nozzle assembly 3. Nozzle assembly adjustment 4. Test nipple 5. Ignition

More information

HVF110, 210, 310, 410HD

HVF110, 210, 310, 410HD 342 N. Co. Rd. 400 East Valparaiso, IN 46383 219-464-8818 Fax 219-462-7985 www.heatwagon.com Installation and Maintenance Manual Please retain this manual for future reference. HVF110, 210, 310, 410HD

More information

PRESS P/N - P/N ECO SERIES

PRESS P/N - P/N ECO SERIES The PRESS P/N series of burners covers a firing range from 800 to 5130 kw. They have been designed in three versions for use in commercial and industrial installation, to burn different oil viscosity from

More information

Heating and Gas Installations - December 2014

Heating and Gas Installations - December 2014 This is an example of good practice maintenance specifications. It is not exhaustive and should only be used to assist with facilities management or specification of a maintenance contract. Emergency Gas

More information

ONE STAGE GAS BURNER GULLIVER RSF SERIES RS5F kw

ONE STAGE GAS BURNER GULLIVER RSF SERIES RS5F kw ONE STAGE GAS BURNER GULLIVER RSF SERIES 160 330 kw The Riello Gulliver, is a new model of the series of one stage gas burners, developed to respond to any request for light industrial processes like bakery

More information

TWO STAGE GAS BURNER GULLIVER RSD SERIES RS5D 160/ kw

TWO STAGE GAS BURNER GULLIVER RSD SERIES RS5D 160/ kw TWO STAGE GAS BURNER GULLIVER RSD SERIES 160/208 345 kw The Riello Gulliver is a new model of the series of two stage gas burners, characterized for its small dimensions in spite of its high combustion

More information

RS/M SERIES. Modulating Gas Burners FIRING RATES

RS/M SERIES. Modulating Gas Burners FIRING RATES The RS/M burners series covers a firing range from 45 to 2650 kw, and it has been designed for use in low or medium temperature hot water boilers, hot air or steam boilers, diathermic oil boilers. Operation

More information

PIERBURG. Carburetor: 2E3

PIERBURG. Carburetor: 2E3 PIERBURG Carburetor: 2E3 1 fast idle adjusting screw 2 throttle lever 3 fuel mixture adjusting screw 4 main body 5 idle cut off valve 6 stop screw 7 accelerator pump cover 8 diaphragm 9 spring 10 valve

More information

Installation- and maintenance instruction B20KA/K

Installation- and maintenance instruction B20KA/K Installation- and maintenance instruction B20KA/K 178 091 07 DISCRIPTION Components 1. Air intake 2. Scale, nozzle assembly 3. Nozzle assembly adjustment 4. Test nipple 5. Ignition cables 6. Schrouded

More information

Installation- and maintenance instruction B20K-2

Installation- and maintenance instruction B20K-2 Installation- and maintenance instruction B20K-2 1 171 615 51 05-01 178 017 09 DESCRIPTION COMPONENTS 1. Damper motor 2. Air damper 3. Photocell 4. Scale, nozzle assembly 5. Test nipple 6. Nozzle assembly

More information

RIELLO 40 F SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL. F kw F kw F kw

RIELLO 40 F SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL. F kw F kw F kw The Riello 40 F series of one stage light oil burners, is a complete range of products developed to respond to any request for light industrial applications. The Riello 40 F series is available in three

More information

Pressure chlorine changeover unit C 7520

Pressure chlorine changeover unit C 7520 BW 2 24 04 / 1 Content 1. Scope of delivery 2. Device description 3. Installation 4. Operation 5. Shutdown 6. Maintenance 7. Troubleshooting 1 Scope of delivery The chlorine gas changeover unit C 7520

More information

Farval. Dualine Installation System Start-Up. Bulletin DL300 BIJUR DELIMON INTERNATIONAL

Farval. Dualine Installation System Start-Up. Bulletin DL300 BIJUR DELIMON INTERNATIONAL Farval Dualine Installation System Start-Up Bulletin DL300 BIJUR DELIMON INTERNATIONAL 2685 Airport Road Kinston, NC 28504 Tel. 800-227-1063 Fax: 252-527-9232 website: www.bijurdelimon.com DC1-1 SECTION

More information

VERTICAL MULTI-STAGE CENTRIFUGAL PUMPS

VERTICAL MULTI-STAGE CENTRIFUGAL PUMPS Installation and Operating Instructions VERTICAL MULTI-STAGE CENTRIFUGAL PUMPS Models 1, 3, 5, 10, 15, 20, 32, 45, 64, 90 1. Model numbering and nameplate format 1.1 Model numbering Example: SBI / SBN

More information

Service Manual. Contents. Names of components. 3. Specifications Wiring Diagam Sequence Time Chart

Service Manual. Contents. Names of components. 3. Specifications Wiring Diagam Sequence Time Chart Service Manual Contents 1. Names of components 2 2. Safety Devices 3 3. Specifications 4 4. Wiring Diagam 4 5. Sequence Time Chart 5 6. 7. 8. Troubleshooting 6 Standard resistance & Voltage 13 Check &

More information

NSGV PT-1000 PORTABLE WELDING STATION I, O & M MANUAL

NSGV PT-1000 PORTABLE WELDING STATION I, O & M MANUAL APPLICATION OF DUST CONTROL EQUIPMENT: CAUTION - Warning Improper operation of dust control system may contribute to conditions in the work area or facility that could result in severe personal injury

More information

FD68 BURNERS SELECTION GUIDE & ENGINEERING SPECS

FD68 BURNERS SELECTION GUIDE & ENGINEERING SPECS SELECTION GUIDE The following data can be used to fill in the information appropriate for the burner size required: FD68 C A 150 L M BD FORCED DRAFT MODEL 68 FUEL A-OIL ONLY G-GAS ONLY C-GAS/OIL TYPE OF

More information

Section 7 - Troubleshooting Guide

Section 7 - Troubleshooting Guide Section 7 - Troubleshooting Guide Section 7 - Troubleshooting Guide IMPORTANT While this troubleshooting guide provides information to aid in troubleshooting problems with the range, it does not contain

More information

16000SIII Automatic Grease System

16000SIII Automatic Grease System Manual # 99905495 16000SIII Automatic Grease System Effective 20120716 IOWA MOLD TOOLING CO., INC. PO Box 189 Garner, IA 50438 Tel: 641-923-3711 FAX: 641-923-2424 Website: http://www.imt.com Copyright

More information

G72x Series Direct Spark Ignition Controls

G72x Series Direct Spark Ignition Controls Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin G72x Issue Date 1299 G72x Series Direct Spark Ignition Controls Figure 1: G72x Direct Spark Ignition

More information

Info 110 4/98. RatioMatic Burners. RM Series version through 600 Sizes. 750 through 2000 Sizes

Info 110 4/98. RatioMatic Burners. RM Series version through 600 Sizes. 750 through 2000 Sizes Info 110 4/98 RatioMatic Burners RM Series version 1.01 50 through 600 Sizes 750 through 2000 Sizes For Ratiomatic Serial Numbers 95-5500 and Above Version 1.01 7/97 Contents 1.0 Operating Parameters &

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL HP COMBINATION GAS/OIL BURNERS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone 316-421-0480, Fax 316-421-0948

More information

MUELLER GAS. Shur StopTM Unit 812 PE Line Stopping. System 8" 12" SDR Reliable Connections. General Information 2

MUELLER GAS. Shur StopTM Unit 812 PE Line Stopping. System 8 12 SDR Reliable Connections. General Information 2 operating Instructions manual MUELLER GAS TAble of contents PAGE TM Unit 812 PE Line Stopping General Information 2 Equipment, Parts and Dimensions 3-5 Operating Instructions 6-12 Troubleshooting and Storage

More information

Starting up hydraulic systems

Starting up hydraulic systems General / Installation A hydraulic system that operates economically, safely, and trouble-free requires careful planning, as well as proper installation and start-up. Conscientious maintenance has a considerable

More information

Series 20 Installation Instructions

Series 20 Installation Instructions Series 20 Installation Instructions Installation Instructions and field service checklist Read these instructions carefully. Failure to follow them could result in a fire or explosion causing property

More information

HOT WASHER MODEL NO: KING 125 OPERATION & MAINTENANCE INSTRUCTIONS PART NO: LS1009

HOT WASHER MODEL NO: KING 125 OPERATION & MAINTENANCE INSTRUCTIONS PART NO: LS1009 HOT WASHER MODEL NO: KING 125 PART NO: 7320170 OPERATION & MAINTENANCE INSTRUCTIONS LS1009 INTRODUCTION Thank you for purchasing this Hot Washer. This machine is a portable, high pressure power washer,

More information

BRAKE SYSTEM Return To Main Table of Contents

BRAKE SYSTEM Return To Main Table of Contents BRAKE SYSTEM Return To Main Table of Contents GENERAL... 2 BRAKE PEDAL... 10 MASTER CYLINDER... 13 BRAKE BOOSTER... 16 BRAKE LINE... 18 PROPORTIONING VALVE... 19 FRONT DISC BRAKE... 20 REAR DRUM BRAKE...

More information

VERTICAL MULTI-STAGES CENTRIFUGAL PUMPS

VERTICAL MULTI-STAGES CENTRIFUGAL PUMPS Installation and Operating Instructions VERTICAL MULTI-STAGES CENTRIFUGAL PUMPS Models 1, 3, 5, 10, 15, 20, 32, 45, 64, 90, 120, 150 1. Model numbering and nameplate format 1.1 Model numbering Example:

More information

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains

More information

HALLMARK INDUSTRIES INC

HALLMARK INDUSTRIES INC Performance Part No. HP. CONVERTIBLE JET PUMP USER S MANUAL GPH of Water @ Total Discharge Pressure of 40 psi Max. Pressure Max suction (shallow well) Max Suction (deep well) Max GPM (@0 head) Max Discharge

More information

Safe & Secure Series Electric Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual

Safe & Secure Series Electric Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual Safe & Secure Series Electric Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual For Use with: SNS4, SNS6, SNS10 & SNS15 Models Additional supplements may be needed for

More information

ORDER ON-LINE /

ORDER ON-LINE   / NM249 NM248 INTERNAL SYSTEMS FOR TRAILERS INSTALLATION MANUAL VERSION 1-2013 ORDER ON-LINE www.vigia.ca / 1-888 438-8444 IMPORTANT Installation requires an experienced mechanic with knowledge of tools

More information

3 Phase Smart Controller

3 Phase Smart Controller 3 Phase Smart Controller Installation and Owner s Manual STP-SCIII 208-230 VAC, 60Hz, 120 Volt Coil Franklin Fueling 3760 Marsh Rd. Madison WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838

More information

R & D SPECIALTIES ROTROL I USER'S MANUAL

R & D SPECIALTIES ROTROL I USER'S MANUAL R & D SPECIALTIES ROTROL I USER'S MANUAL TABLE OF CONTENTS INTRODUCTION...2 SPECIFICATIONS...2 CONTROLS AND INDICATORS...3 TIME DELAYS...4 INSTALLATION...5 SYSTEM OPERATION...9 TROUBLESHOOTING...13 OPTIONAL

More information

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version MD10 Engine Controller Installation and User Manual for the MD10 Engine Controller. Full Version File: MartinMD10rev1.4.doc May 16, 2002 2 READ MANUAL BEFORE INSTALLING UNIT Receipt of shipment and warranty

More information

Routine Burner Service

Routine Burner Service Routine Burner Service WARNING Rural Energy Enterprises, Inc. does not accept liability for the improper use of this information. Installation, service, and maintenance of heating equipment should be performed

More information

LOW NOx TWO STAGE GAS BURNERS GULLIVER BSD SERIES BS1D 16/19 52 kw BS2D 35/40 91 kw BS3D 65/ kw BS4D 110/ kw

LOW NOx TWO STAGE GAS BURNERS GULLIVER BSD SERIES BS1D 16/19 52 kw BS2D 35/40 91 kw BS3D 65/ kw BS4D 110/ kw LOW NOx TWO STAGE GAS BURNERS GULLIVER BSD SERIES 1/19 5 kw 35/4 91 kw 5/75 19 kw 11/14 4 kw The Riello Gulliver BSD series of two stage gas burners, is a complete range of Low NOx emission products, developed

More information

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Contents Section 1. General Observations... 2 2. Operation... 4 3. Control During Operation... 5 4. Trouble Shooting... 6 5. Maintenance... 7 Please

More information

XID ENHANCEMENT SYSTEM IMPROVED EFFICIENCY AND PERFORMANCE

XID ENHANCEMENT SYSTEM IMPROVED EFFICIENCY AND PERFORMANCE IMMERSION FIRED HOT WATER BOILER April 1, 2003 GENERAL DESCRIPTION The Sellers immersion fired hot water boiler is a horizontal, single pass, firetube boiler designed to burn natural gas. The unique burner

More information

SECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION

SECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION SECTION 3.00 ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION Be sure that the clutch, circuit breaker, or other main power transmission device is disconnected. Generators develop voltage as soon as the

More information

#9040 FUEL TANK SWEEPER

#9040 FUEL TANK SWEEPER #9040 FUEL TANK SWEEPER INSTRUCTION MANUAL FILTERS AND REMOVES FINE BIO-CONTAMINANTS, ALGAE, ETC. SWEEPING PROCESS REMOVES LARGE CONTAMINANTS FROM OIL TANKS SUCH AS RUST, WATER, CRUDE AND DIRT CIRCULATES

More information

OIL BURNERS MAIOR P 45 AB. techniques for energy saving MODEL. HYDRAULIC SYSTEM 220/380 V 60 Hz LB

OIL BURNERS MAIOR P 45 AB. techniques for energy saving MODEL. HYDRAULIC SYSTEM 220/380 V 60 Hz LB OIL BURNERS techniques for energy saving MODEL MAIOR P 45 AB HYDRAULIC SYSTEM 220/380 V 60 Hz LB462 09.12.99 TECHNICAL DATA MODEL MAIOR P 45 AB Thermal power max. kcal/h 450.000 kw 522 Thermal power min.

More information

IBT Series Square Drive Torque Wrenches

IBT Series Square Drive Torque Wrenches IBT Series Square Drive Torque Wrenches Operation and Maintenance Manual Model.75, 1, 3, 5, 8, 10, 20, 25, 35, 50 http://www.torsionx.com Use the IBT Series Square Drive Torque Wrenches Model.75, 1, 3,

More information

Operation and Maintenance Manual http://www.torsionx.eu Use the MaxDrv Series Square Drive Torque Wrench Model.75, 1, 3, 5, 8, 10, 20, 25, 35, 50 to install and remove threaded fasteners requiring precise

More information

Surepowr Series 100 Installation Manual

Surepowr Series 100 Installation Manual Surepowr Series 100 Installation Manual Safety First In the maintenance and operation of mechanical equipment, safety is the basic factor which must be considered at all times. Through the use of the proper

More information

PRESS G SERIES. Two Stage Light Oil Burners FIRING RATES

PRESS G SERIES. Two Stage Light Oil Burners FIRING RATES The PRESS G series of burners covers a firing range from 107 to 1660 kw and they have been designed for use in civil installations of average dimensions, like building areas and large apartment groups

More information

DP556 Pump. 55:1, Air-operated, Grease. General. Operation. Technical Data. Installation. Mounting with Reinforced Cover (Recommended)

DP556 Pump. 55:1, Air-operated, Grease. General. Operation. Technical Data. Installation. Mounting with Reinforced Cover (Recommended) DP556 Pump 55:1, Air-operated, Grease General The DP556 Pump is a compressed air-operated reciprocating piston pump. This high capacity demand pump is compatible with mineral and synthetic grease and suitable

More information

M-3025CB-AV Fuel Pump

M-3025CB-AV Fuel Pump SAVE THESE INSTRUCTIONS M-3025CB-AV Fuel Pump Owner s Manual TABLE OF CONTENTS General Information... 2 Safety Instructions... 2 Installation... 3 Operation... 4 Maintenance... 4 Repair... 5 Troubleshooting...

More information

SERVICE MANUAL RRG SERIES HEAVY DUTY GAS GRIDDLE - NOTICE - ML ML ML RRG Shown

SERVICE MANUAL RRG SERIES HEAVY DUTY GAS GRIDDLE - NOTICE - ML ML ML RRG Shown SERVICE MANUAL RRG SERIES HEAVY DUTY GAS GRIDDLE 24RRG 36RRG 48RRG 60RRG ML-135339-00024 ML-135340-00036 ML-135341-00048 ML-135342-00060 24RRG Shown - NOTICE - This Manual is prepared for the use of trained

More information

HexPro Series Low Profile Wrenches

HexPro Series Low Profile Wrenches HexPro Series Low Profile Wrenches Operation and Maintenance Manual Model 2HP 4HP 8HP 14HP 30HP www.torquetoolsinc.com Use the HEXPRO Series Low Profile Wrenches Model 2HP 4HP 8HP 14HP 30HP to install

More information

User s Manual. Automatic Switch-Mode Battery Charger

User s Manual. Automatic Switch-Mode Battery Charger User s Manual Automatic Switch-Mode Battery Charger IMPORTANT Read, understand, and follow these safety rules and operating instructions before using this battery charger. Only authorized and trained service

More information

SERVICE MANUAL (INTERNATIONAL)

SERVICE MANUAL (INTERNATIONAL) SERVICE MANUAL (INTERNATIONAL) IMPINGER CONVEYOR OVENS MODEL 1433-000-E, 1434-000-E, 1456, 1457 WITH PUSH BUTTON CONTROLS Lincoln Foodservice Products, LLC 1111 North Hadley Road Fort Wayne, Indiana 46804

More information

Troubleshooting Manual

Troubleshooting Manual Troubleshooting Manual NOTICE: DO NOT DISCARD THIS MANUAL Models: LEGACY42-IFT PHOENIX42-IFT 1 TABLE OF CONTENTS A. Normal Operation...3 B. Wiring Diagram...4 C. Troubleshooting IntelliFire Touch...5 D.

More information

Installation- and maintenance instruction BENTOFLEX ST133K

Installation- and maintenance instruction BENTOFLEX ST133K Installation- and maintenance instruction BENTOFLEX ST133K 171 625 37 07-01 178 004 17 TECHNICAL DATA Type designation ST133K Dimensions B 200 258 ø89 54 237 158 295 Burner tube Length of burner tube Incl.

More information

Installation- and maintenance instruction B45A2.2

Installation- and maintenance instruction B45A2.2 Installation- and maintenance instruction B45A2.2 160 012 85 DESCRIPTION Components 1. Flame cone 2. Fan housing 3. Fan wheel 4. Damper motor 5. Motor 6. Pump 7. Shrouded disc 8. Nozzle 9. Ignition transformer

More information

USE and MAINTENANCE INSTRUCTION MANUAL W-300 W-300 WB LPH-300 GRAVITY. SPRAY GUN Series. en it fr es pt de se

USE and MAINTENANCE INSTRUCTION MANUAL W-300 W-300 WB LPH-300 GRAVITY. SPRAY GUN Series. en it fr es pt de se USE and MAINTENANCE INSTRUCTION MANUAL W-300 W-300 WB LPH-300 GRAVITY SPRAY GUN Series en it fr es pt de se TECHNICAL DATA High T.E.C. series Nozzle_Needle set Combination W-300 WB W-300 W-300-081G 0.8

More information

RUFNEX Series Low Profile Wrenches Operation and Maintenance Manual

RUFNEX Series Low Profile Wrenches Operation and Maintenance Manual RUFNEX Series Low Profile Wrenches Operation and Maintenance Manual http://www.torsionx.com Use the RUFNEX Series Ultra-Low Profile Wrenches to install and remove large bolts that have minimal wrench clearance.

More information

INSTALLATION MANUAL ACL 5500 COMBUSTION SAFETY CONTROLLER

INSTALLATION MANUAL ACL 5500 COMBUSTION SAFETY CONTROLLER 5500 COMBUSTION SAFETY CONTROL INSTALLATION MANUAL FOR 5500 COMBUSTION SAFETY CONTROLLER WARNING This manual must be read in its entirety before installation of this controller. Installation must be performed

More information

Twin Power. Manual. Pneumatic Multiturn actuator in Standard and ATEX design WARNING! WARNING! Mounting. Assembly example

Twin Power. Manual. Pneumatic Multiturn actuator in Standard and ATEX design WARNING! WARNING! Mounting. Assembly example Top Quality Valve Actuators Made in Sweden Twin Power Manual Pneumatic Multiturn actuator in Standard and ATEX design Mounting The Twin Power actuator works beyond reproach in all positions. Valves with

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin LowNOx Commercial Gas Electronic Spark Ignition Sequence

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin LowNOx Commercial Gas Electronic Spark Ignition Sequence The Universal TM gas LowNOx series water heaters contain an electronic spark ignition system. The heater is connected to a 120VAC power source required by the transformer. The transformer steps down the

More information

RES G MRBLU SERIES. Low NOx One Stage Light Oil Burners FIRING RATES. LOW NOx LIGHT OIL

RES G MRBLU SERIES. Low NOx One Stage Light Oil Burners FIRING RATES. LOW NOx LIGHT OIL Low NOx One Stage Light Oil Burners RES G MRBLU SERIES LOW NOx LIGHT OIL RES (Riello Environment Solution) is the new Low NOx light oil burners series with extremely low emissions to meet the increasingly

More information

User s Manual D-Series Blowers and Exhausters

User s Manual D-Series Blowers and Exhausters User s Manual D-Series Blowers and Exhausters D05-1 ½ HP TEFC 115/230 VOLTS, 1 PH D05-3 ½ HP TEFC 208/230/460 VOLTS, 3 PH D10-1 1 HP TEFC 115/230 VOLTS, 1 PH D10-3 1 HP TEFC 208/230/460 VOLTS, 3 PH D15-1

More information

Low Profile Wrenches Operation and Maintenance Manual

Low Profile Wrenches Operation and Maintenance Manual Low Profile Wrenches Operation and Maintenance Manual http://www.torquetoolsinc.com Use the HEXPRO Series Low Profile Wrenches Model 2HP 4HP 8HP 14HP 30HP to install and remove large bolts that have minimal

More information

RS Series Two Stage Progressive Gas Burners

RS Series Two Stage Progressive Gas Burners Technical Data Leaflet Gas TS0046UK06 RS Series Two Stage Progressive Gas s RS 34 MZ 70/130 390 kw RS 44 MZ 101/203 550 kw RS 50 116/290 580 kw RS 64 MZ 150/400 850 kw RS 70 192/465 814 kw RS 100 232/698

More information

Sofa Slideout Assembly OWNER'S MANUAL. Rev: Page 1 Sofa Slideout Owners Manual

Sofa Slideout Assembly OWNER'S MANUAL. Rev: Page 1 Sofa Slideout Owners Manual Sofa Slideout Assembly OWNER'S MANUAL Rev: 06.14.2016 Page 1 Sofa Slideout Owners Manual TABLE OF CONTENTS Warning, Safety, and System Requirement Information 3 Product Information 3 Prior to Operation

More information

Oil, Gas and Dual Fuel Burners

Oil, Gas and Dual Fuel Burners Oil, Gas and Dual Fuel Burners Burner series 130...150 50, 0 Group 3 Capacity 390-3,500 Table of contents General 1 How to choose a burner Light oil burners Technical data and dimensions 3- PI-diagrams

More information

BOLT-ON AND WELD-ON FLUSH FLOOR SLIDEOUT SYSTEMS OPERATION AND SERVICE MANUAL

BOLT-ON AND WELD-ON FLUSH FLOOR SLIDEOUT SYSTEMS OPERATION AND SERVICE MANUAL BOLT-ON AND WELD-ON FLUSH FLOOR SLIDEOUT SYSTEMS OPERATION AND SERVICE MANUAL TABLE OF CONTENTS SYSTEM...... Warning........ Description...... Prior to Operation OPERATION... Main Components... Mechanical...

More information

Mobile Diesel Heaters GRY-D / GRY-I Service Training Course

Mobile Diesel Heaters GRY-D / GRY-I Service Training Course Mobile Diesel Heaters GRY-D / GRY-I Service Training Course 1 Rev. No. 3 January 24, 2011 GRY-I Indirect-fired Diesel Heaters GRY-I 15 WU GRYP 50 AP GRY-I 25 WU GRYP 90 AP GRY-I 40 WU GRYP 135 AP 2 GRY-D

More information

US - UP3-R 12V US - UP3-R 24V

US - UP3-R 12V US - UP3-R 24V SELF-PRIMING ELECTRIC PUMP FOR TRANSFERRING VARIOUS LIQUIDS INSTRUCTIONS FOR USE 05/0/6 Rev.00 6 008 -US - UP3-R V 6 008 3-US - UP3-R V PRODUCT DESCRIPTION Self-priming electric pump for the transfer of

More information